1. PROVIDE ALL MATERIALS AND LABOR NECESSARY FOR A COMPLETE PLUMBING SYSTEM. WARRANTY ALL WORK AND MATERIAL FOR A PERIOD OF AT LEAST ONE YEAR AFTER ACCEPTANCE BY OWNER. 2. DO NOT SCALE DRAWINGS. OBTAIN ROUGH IN DIMENSIONS FROM ARCHITECTURAL DRAWINGS OR FROM MANUFACTURERS PRINTED INSTRUCTIONS AND RECOMMENDATIONS ONLY. CONTRACTOR SHALL COORDINATE EXACT LOCATIONS OF ALL EQUIPMENT, CONNECTIONS AND LINES WITH THE OWNER PRIOR TO INSTALLATION OF ANY PIPING. 3. COORDINATE PLUMBING SYSTEMS WITH ALL TRADES TO AVOID INTERFERENCE AND CONFLICTS PRIOR TO INSTALLATION OF PIPING, FIXTURES, AND EQUIPMENT. 4. WHENEVER THE WORD "PROVIDE" IS USED, IT SHALL MEAN FURNISH AND INSTALL COMPLETE AND READY FOR USE. 5. UNLESS OTHERWISE SHOWN OR NOTED, ALL PIPING SHALL BE RUN CONCEALED IN WALLS, CHASES AND/OR ABOVE CEILINGS. 6. ALL SUSPENDED PIPING SHALL BE SUPPORTED FROM FLOOR AND/OR ROOF STRUCTURAL MEMBERS. IN NO CASE SHALL PIPING BE SUSPENDED FROM FLOOR OR ROOF DECK. 7. WHERE PIPES PENETRATE FIRE RATED ASSEMBLIES, SEAL OPENING AROUND PIPES WITH U.L. LISTED FIRE STOPPING MATERIAL TO MAINTAIN THE FIRE RATING OF THE ASSEMBLY. 8. PROVIDE DRAIN VALVES AT ALL LOW POINTS WHERE POSSIBLE IN HOT & COLD PIPING SYSTEMS. 9. PROVIDE DEEP SEAL TRAPS ON ALL FLOOR DRAINS. 10. PROVIDE ALL VENT PENETRATIONS WHERE INDICATED ON FLOOR PLANS. COLLECT ALL VENTS ABOVE CEILING WHERE SHOWN. 11. WALL HYDRANTS SHALL BE MOUNTED 20" ABOVE GRADE, UNO. 12. PROVIDE INSULATION FOR ALL ABOVE CEILING WASTE PIPING COLLECTING CONDENSATE DRAIN. 13. INSTALL ALL SANITARY WASTE AND VENT PIPING IN ACCORDANCE WITH CISPI 301 STANDARD. PROVIDE HANGERS AND SUPPORTS WITHIN 12" OF EACH HORIZONTAL ELBOW. 14. ALL WORK AND MATERIALS SHALL BE IN ACCORDANCE WITH THE IBC INTERNATIONAL PLUMBING CODE 2009. 15. REFER TO PLUMBING SCHEDULES FOR SUPPLY, WASTE AND VENT LINE SIZES TO EACH FIXTURE. 16. PROVIDE COMPLETE COORDINATION DRAWINGS INDICATING ALL OTHER TRADES IN A SCALE NO LESS THAN 1/4 INCH = 1 FOOT. SEE SPECIFICATIONS FOR FURTHER REQUIREMENTS. 17. THE DRAWINGS SHOW THE GENERAL ARRANGEMENTS AND LOCATION OF EQUIPMENT, PIPING AND FIXTURES. THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THE PLUMBING INSTALLATION W/ THE STRUCTURE AND OTHER TRADES AND SHALL PROVIDE ADDITIONAL OFFSETS AND FITTINGS AS REQUIRED. 18. CONTRACTOR SHALL MAKE ALL FINAL CONNECTIONS TO LAB EQUIPMENT AND SECURE THIRD PARTY TESTING AGENCY FOR LABORATORY GAS PIPING. 19. THE CONTRACTOR SHALL LABEL ALL FIXTURES AND DEVICES UTILIZING NON-POTABLE AND PURIFIED WATER WITH A PERMANENTLY AFFIXED, LEGIBLE LABEL. SIZE AND LOCATION TO BE APPROVED BY THE OWNER. 20. LABORATORY GASES SHALL BE INSTALLED AND TESTED AS CATEGORY 3 PER NFPA 99. PLUMBING NOTES: TYP U/G HB (E) BFP B/F A/C AFG FD VTR FCO WCO BV/BFV FD FCO UNDER GROUND TYPICAL HOSE BIBB ABOVE CEILING ABOVE FINISH GRADE BELOW FLOOR BACKFLOW PREVENTER EXISTING ISOLATION AND THROTTLING VALVE FLOOR DRAIN VENT THRU ROOF WALL CLEAN OUT FLOOR CLEANOUT PLUMBING SYMBOLS ABBREVIATION PC PH V W SYMBOL SOIL AND WASTE PIPING VENT PIPING DESCRIPTION POTABLE COLD WATER PIPING POTABLE HOT WATER PIPING TMV THERMOSTATIC MIXING VALVE SD SD 12" STORM DRAIN NFWH NON-FREEZE WALL HYDRANT ST OF OVERFLOW STORM PIPING PRIMARY STORM PIPING AFF ABOVE FINISH FLOOR WHA WATER HAMMER ARRESTOR PHR POTABLE HOT WATER RETURN PIPING PIPE UP PIPE DN PIPE REDUCER PIPE STRAIGHT TEE PIPE TEE DN DN DOWN TP TP TRAP PRIMER EF EXHAUST FAN CU CONDENSING UNIT HD HUB DRAIN MC MECHANICAL CONTRACTOR EC ELECTRICAL CONTRACTOR OFO OVERFLOW OUTLET GCO GRADE CLEANOUT NPC NPH NON-POTABLE COLD WATER PIPING NON-POTABLE HOT WATER PIPING NPHR NON-POTABLE HOT WATER RETURN PIPING AV AW ACID WASTE PIPING ACID VENT PIPING PWS PURIFIED WATER SUPPLY PWR PURIFIED WATER RETURN N NITROGEN GAS VAC VACUUM CA COMPRESSED AIR NG NATURAL GAS BALANCING VALVE UNO UNLESS NOTED OTHERWISE POU POINT-OF-USE AVTR ACID VENT THRU ROOF PP POLYPROPYLENE WC WATER CLOSET LAV LAVATORY UR URINAL MS MOP SINK CRS CLEAN ROOM SINK FS FLOOR SINK PWSB PURIFIED WATER SUPPLY BOX PRV PRESSURE REDUCING VALVE CO CLEANOUT IMB ICEMAKER BOX DWSB DISHWASHER SUPPLY BOX EWC ELECTRIC WATER COOLER OF/RD OVERFLOW/ROOF DRAIN PD PROMENADE DECK DRAIN SK LAB SINK CS CUP SINK BRS BREAK SINK US UTILITY SINK ESH EMERGENCY SHOWER/EYEWASH EW DECK-MOUNDED EYEWASH/DRENCH HOSE UPW ULTRA PURE WATER POLISHING STATION ANT ACID NEUTRALIZATION TANK WH WATER HEATER B BOILER WDBP WATER DISTRIBUTION BOOSTER PUMP SOLENOID VALVE s PLUMBING CODES AND STANDARDS: IPC INTERNATIONAL PLUMBING CODE 2009 NFPA 99 2012 EDITION ANSI UNDERWRITERS LABORATORIES (UL) ALL STATE AND LOCAL CODES AND ORDINANCES COASTAL CAROLINA UNIVERSITY DESIGN GUIDELINES COMPONENT IMPORTANCE FACTOR (Ip) COMPONENT IDENTIFICATION SEISMIC RESTRAINT REQUIREMENT NOTES SEISMIC RESTRAINT REQUIREMENT ROOF MOUNTED RESTRAIN ALL RESTRAIN ALL - FLOOR MOUNTED RESTRAIN ALL RESTRAIN ALL - WALL MOUNTED RESTRAIN ALL RESTRAIN ALL - COMPONENT SUPPORTS RESTRAIN ALL RESTRAIN ALL - RESTRAIN ALL RESTRAIN ALL - SUSPENDED DUCTILE PIPING (STEEL, ALUMINUM, COPPER, ETC.) >3" >1" 3 COMPONENT CERTIFICATION (SEE NOTE 4) NOT REQUIRED REQUIRED - 1.0 1.5 NOTES SEISMIC AND WIND REQUIREMENTS FOR PLUMBING SYSTEMS IBC-2009 /ASCE 7-05 SUSPENDED NON DUCTILE PIPING (CAST IRON, PLASTIC, CERAMIC) SUSPENDED PIPE ON TRAPEZE RESTRAIN ALL RESTRAIN IF ANY PIPE ON TRAPEZE > 3" RESTRAIN IF TOTAL WEIGHT OF PIPES ON TRAPEZE > 10 LBS/FT RESTRAIN ALL 3 3 RESTRAIN IF ANY PIPE ON TRAPEZE > 1" RESTRAIN IF TOTAL WEIGHT OF PIPES ON TRAPEZE > 10 LBS/FT SUSPENDED EQUIPMENT PLUMBING COMPONENT IMPORTANCE FACTOR (Ip) DESIGNATION Ip = 1.0 Ip = 1.5 NOTES: 1. EQUIPMENT 20 LBS. OR LESS IS EXEMPT IF FLEXIBLE CONNECTIONS ARE PROVIDED BETWEEN THE COMPONENT AND ASSOCIATED PIPING AND CONDUIT. RESTRAINTS ARE NOT REQUIRED IF THE COMPONENT WEIGHS 400 LBS. OR LESS, IS MOUNTED AT 4 FT. OR LESS ABOVE A FLOOR, AND HAS FLEXIBLE CONNECTIONS BETWEEN THE COMPONENT AND ASSOCIATED PIPING AND CONDUIT. RESTRAINT IS NOT REQUIRED IF THE PIPING IS SUPPORTED BY HANGERS AND EACH HANGER IN THE PIPING RUN IS 12 IN. OR LESS IN LENGTH FROM THE TOP OF THE PIPE TO THE SUPPORTING STRUCTURE. WHERE PIPES ARE SUPPORTED ON A TRAPEZE, THE TRAPEZE SHALL BE SUPPORTED BY HANGERS HAVING A LENGTH OF 12 IN. OR LESS. WHERE ROD HANGERS ARE USED, THEY SHALL BE EQUIPPED WITH SWIVELS, EYE NUTS OR OTHER DEVICES TO PREVENT BENDING IN THE ROD. COMPONENT CERTIFICATION MUST BE SUPPLIED BY THE EQUIPMENT MANUFACTURER AT TIME OF SUBMITTAL FOR REVIEW BY ENGINEER OF RECORD. 2. 3. 4. A. EQUIPMENT, APPLIANCES AND SUPPORTS (INCLUDING ROOF CURBS & ROOF RAILS) EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND PRESSURES DETERMINED IN ACCORDANCE WITH THE INTERNATIONAL BUILDING CODE. WHERE SEISMIC RESTRAINT IS REQUIRED, THE MORE DEMANDING FORCE OF WIND AND SEISMIC MUST BE USED. SEE SEISMIC INFORMATION CONTAINED IN THE STRUCTURAL DRAWINGS FOR SITE SPECIFIC INFORMATION ON SEISMIC DESIGN CATEGORY. SEE EQUIPMENT SCHEDULES AND DETAILS FOR SPECIFIC COMPONENT IMPORTANCE FACTOR DESIGNATIONS. USE APPLICABLE TABLE BELOW TO DETERMINE SEISMIC RESTRAINT REQUIREMENTS FOR EACH MECHANICAL COMPONENT. FOR ALL COMPONENTS REQUIRING SEISMIC RESTRAINT, THE COMPONENT SUPPORTS AND ATTACHMENTS SHALL BE DESIGNED BY A REGISTERED DESIGN PROFESSIONAL IN THE STATE OF SOUTH CAROLINA. SUBMITTAL MUST INCLUDE STAMPED AND SIGNED DRAWINGS AND CALCULATIONS. WHERE SEISMIC RESTRAINT IS REQUIRED, HOUSEKEEPING PADS NEEDED FOR THE INSTALLATION OF EQUIPMENT UNDER THIS CONTRACT MUST BE DESIGNED BY THE SEISMIC ENGINEER. DO NOT POUR ANY HOUSEKEEPING PADS PRIOR TO THE THE RECEIPT OF THE SEISMIC SUBMITTAL. SEISMIC RESTRAINTS FOR PIPING MUST BE SHOWN ON LAYOUT DRAWINGS SHOWING SPECIFIC RESTRAINT LOCATIONS ALONG WITH ACCOMPANYING DETAILS AND CALCULATIONS. B. C. D. E. · ALL NATURAL GAS APPURTENANCES 1 1, 2 1 1 3 3 3 - 1, 2 · ALL PLUMBING APPURTENANCES, UNO. C E R T I F I C A T E O F A U T H O R I Z A T I O N S O U T H C A R O L I N A CONSULTING ENGINEERS DWG, INC. No.C03649 CHECKED BY: DRAWN BY: DATE: PROJECT: MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS 1 A 2 3 4 5 6 B C D E WWW.LS3P.COM TEL. 843.577.4444 FAX 843.722.4789 205 1/2 KING ST. CHARLESTON SC 29401 STATE PROJECT NO: H17-9588-FW REVISIONS: COPYRIGHT 2014 ALL RIGHTS RESERVED PRINTED OR ELECTRONIC DRAWINGS AND DOCUMENTATION MAY NOT BE REPRODUCED IN ANY FORM WITHOUT WRITTEN PERMISSION FROM LS3P ASSOCIATES LTD. E G No. L T U D S I C A H I S M R E T E K E G . W E S A A 17759 R E G E E R I N E N L R C A H O R P S E F O L N S I O I N O LS3P: 1202-122370 MAY 20, 2014 KMM MGW PLUMBING NOTES & LEGEND P000 BID SET SCIENCE ANNEX II CONSTRUCTION No. Description Date

s SOLENOID VALVE - Coastal Carolina University · PDF filecu condensing unit hd hub drain mc ... kmm mgw plumbing notes & legend p000 bid set science annex ii construction ... bio

  • Upload
    vankhue

  • View
    216

  • Download
    3

Embed Size (px)

Citation preview

Page 1: s SOLENOID VALVE - Coastal Carolina University · PDF filecu condensing unit hd hub drain mc ... kmm mgw plumbing notes & legend p000 bid set science annex ii construction ... bio

1. PROVIDE ALL MATERIALS AND LABOR NECESSARY FOR A COMPLETE PLUMBING SYSTEM.WARRANTY ALL WORK AND MATERIAL FOR A PERIOD OF AT LEAST ONE YEAR AFTER ACCEPTANCEBY OWNER.

2. DO NOT SCALE DRAWINGS. OBTAIN ROUGH IN DIMENSIONS FROM ARCHITECTURAL DRAWINGSOR FROM MANUFACTURERS PRINTED INSTRUCTIONS AND RECOMMENDATIONS ONLY.CONTRACTOR SHALL COORDINATE EXACT LOCATIONS OF ALL EQUIPMENT, CONNECTIONS ANDLINES WITH THE OWNER PRIOR TO INSTALLATION OF ANY PIPING.

3. COORDINATE PLUMBING SYSTEMS WITH ALL TRADES TO AVOID INTERFERENCE AND CONFLICTSPRIOR TO INSTALLATION OF PIPING, FIXTURES, AND EQUIPMENT.

4. WHENEVER THE WORD "PROVIDE" IS USED, IT SHALL MEAN FURNISH AND INSTALL COMPLETEAND READY FOR USE.

5. UNLESS OTHERWISE SHOWN OR NOTED, ALL PIPING SHALL BE RUN CONCEALED IN WALLS,CHASES AND/OR ABOVE CEILINGS.

6. ALL SUSPENDED PIPING SHALL BE SUPPORTED FROM FLOOR AND/OR ROOF STRUCTURALMEMBERS. IN NO CASE SHALL PIPING BE SUSPENDED FROM FLOOR OR ROOF DECK.

7. WHERE PIPES PENETRATE FIRE RATED ASSEMBLIES, SEAL OPENING AROUND PIPES WITH U.L.LISTED FIRE STOPPING MATERIAL TO MAINTAIN THE FIRE RATING OF THE ASSEMBLY.

8. PROVIDE DRAIN VALVES AT ALL LOW POINTS WHERE POSSIBLE IN HOT & COLD PIPING SYSTEMS.

9. PROVIDE DEEP SEAL TRAPS ON ALL FLOOR DRAINS.

10. PROVIDE ALL VENT PENETRATIONS WHERE INDICATED ON FLOOR PLANS. COLLECT ALL VENTSABOVE CEILING WHERE SHOWN.

11. WALL HYDRANTS SHALL BE MOUNTED 20" ABOVE GRADE, UNO.

12. PROVIDE INSULATION FOR ALL ABOVE CEILING WASTE PIPING COLLECTING CONDENSATE DRAIN.

13. INSTALL ALL SANITARY WASTE AND VENT PIPING IN ACCORDANCE WITH CISPI 301 STANDARD.PROVIDE HANGERS AND SUPPORTS WITHIN 12" OF EACH HORIZONTAL ELBOW.

14. ALL WORK AND MATERIALS SHALL BE IN ACCORDANCE WITH THE IBC INTERNATIONAL PLUMBINGCODE 2009.

15. REFER TO PLUMBING SCHEDULES FOR SUPPLY, WASTE AND VENT LINE SIZES TO EACH FIXTURE.

16. PROVIDE COMPLETE COORDINATION DRAWINGS INDICATING ALL OTHER TRADES IN A SCALE NOLESS THAN 1/4 INCH = 1 FOOT. SEE SPECIFICATIONS FOR FURTHER REQUIREMENTS.

17. THE DRAWINGS SHOW THE GENERAL ARRANGEMENTS AND LOCATION OF EQUIPMENT, PIPINGAND FIXTURES. THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THE PLUMBINGINSTALLATION W/ THE STRUCTURE AND OTHER TRADES AND SHALL PROVIDE ADDITIONAL OFFSETSAND FITTINGS AS REQUIRED.

18. CONTRACTOR SHALL MAKE ALL FINAL CONNECTIONS TO LAB EQUIPMENT AND SECURE THIRDPARTY TESTING AGENCY FOR LABORATORY GAS PIPING.

19. THE CONTRACTOR SHALL LABEL ALL FIXTURES AND DEVICES UTILIZING NON-POTABLE ANDPURIFIED WATER WITH A PERMANENTLY AFFIXED, LEGIBLE LABEL. SIZE AND LOCATION TO BEAPPROVED BY THE OWNER.

20. LABORATORY GASES SHALL BE INSTALLED AND TESTED AS CATEGORY 3 PER NFPA 99.

PLUMBING NOTES:

TYP

U/G

HB

(E)

BFP

B/F

A/C

AFG

FD

VTR

FCO

WCO

BV/BFV

FD

FCO

UNDER GROUND

TYPICAL

HOSE BIBB

ABOVE CEILING

ABOVE FINISH GRADE

BELOW FLOOR

BACKFLOW PREVENTER

EXISTING

ISOLATION AND THROTTLING VALVE

FLOOR DRAIN

VENT THRU ROOF

WALL CLEAN OUT

FLOOR CLEANOUT

PLUMBING SYMBOLSABBREVIATION

PC

PH

V

W

SYMBOL

SOIL AND WASTE PIPING

VENT PIPING

DESCRIPTION

POTABLE COLD WATER PIPING

POTABLE HOT WATER PIPING

TMV THERMOSTATIC MIXING VALVE

SD SD 12" STORM DRAIN

NFWH NON-FREEZE WALL HYDRANT

ST

OF OVERFLOW STORM PIPING

PRIMARY STORM PIPING

AFF ABOVE FINISH FLOOR

WHA WATER HAMMER ARRESTOR

PHR POTABLE HOT WATER RETURN PIPING

PIPE UP

PIPE DN

PIPE REDUCER

PIPE STRAIGHT TEE

PIPE TEE DN

DN DOWN

TP TP TRAP PRIMER

EF EXHAUST FAN

CU CONDENSING UNIT

HD HUB DRAIN

MC MECHANICAL CONTRACTOR

EC ELECTRICAL CONTRACTOR

OFO OVERFLOW OUTLET

GCO GRADE CLEANOUT

NPC

NPH

NON-POTABLE COLD WATER PIPING

NON-POTABLE HOT WATER PIPING

NPHR NON-POTABLE HOT WATER RETURN PIPING

AV

AW ACID WASTE PIPING

ACID VENT PIPING

PWS PURIFIED WATER SUPPLY

PWR PURIFIED WATER RETURN

N NITROGEN GAS

VAC VACUUM

CA COMPRESSED AIR

NG NATURAL GAS

BALANCING VALVE

UNO UNLESS NOTED OTHERWISE

POU POINT-OF-USE

AVTR ACID VENT THRU ROOF

PP POLYPROPYLENE

WC WATER CLOSETLAV LAVATORYUR URINAL

MS MOP SINK

CRS CLEAN ROOM SINK

FS FLOOR SINKPWSB PURIFIED WATER SUPPLY BOX

PRV PRESSURE REDUCING VALVECO CLEANOUT

IMB ICEMAKER BOXDWSB DISHWASHER SUPPLY BOXEWC ELECTRIC WATER COOLER

OF/RD OVERFLOW/ROOF DRAIN

PD PROMENADE DECK DRAIN

SK LAB SINK

CS CUP SINKBRS BREAK SINKUS UTILITY SINK

ESH EMERGENCY SHOWER/EYEWASH

EW DECK-MOUNDED EYEWASH/DRENCH HOSE

UPW ULTRA PURE WATER POLISHING STATION

ANT ACID NEUTRALIZATION TANK

WH WATER HEATER

B BOILER

WDBP WATER DISTRIBUTION BOOSTER PUMP

SOLENOID VALVEs

PLUMBING CODES AND STANDARDS:IPC INTERNATIONAL PLUMBING CODE 2009NFPA 99 2012 EDITIONANSIUNDERWRITERS LABORATORIES (UL)ALL STATE AND LOCAL CODES AND ORDINANCESCOASTAL CAROLINA UNIVERSITY DESIGN GUIDELINES

COMPONENT IMPORTANCE FACTOR (Ip)

COMPONENT IDENTIFICATION SEISMIC RESTRAINT REQUIREMENT NOTES SEISMIC RESTRAINT REQUIREMENT

ROOF MOUNTED RESTRAIN ALL RESTRAIN ALL -

FLOOR MOUNTED RESTRAIN ALL RESTRAIN ALL -

WALL MOUNTED RESTRAIN ALL RESTRAIN ALL -

COMPONENT SUPPORTS RESTRAIN ALL RESTRAIN ALL -

RESTRAIN ALL RESTRAIN ALL -

SUSPENDED DUCTILE PIPING(STEEL, ALUMINUM, COPPER,

ETC.)>3" >1" 3

COMPONENTCERTIFICATION(SEE NOTE 4)

NOT REQUIRED REQUIRED -

1.0 1.5

NOTES

SEISMIC AND WIND REQUIREMENTS FOR PLUMBING SYSTEMSIBC-2009 /ASCE 7-05

SUSPENDED NON DUCTILEPIPING

(CAST IRON, PLASTIC, CERAMIC)

SUSPENDED PIPE ON TRAPEZE

RESTRAIN ALL

RESTRAIN IF ANY PIPEON TRAPEZE > 3"

RESTRAIN IF TOTAL WEIGHT OF PIPESON

TRAPEZE > 10 LBS/FT

RESTRAIN ALL 3

3

RESTRAIN IF ANY PIPEON TRAPEZE > 1"

RESTRAIN IF TOTAL WEIGHT OF PIPESON

TRAPEZE > 10 LBS/FT

SUSPENDED EQUIPMENT

PLUMBING COMPONENT IMPORTANCE FACTOR (Ip) DESIGNATION

Ip = 1.0 Ip = 1.5

NOTES:1. EQUIPMENT 20 LBS. OR LESS IS EXEMPT IF FLEXIBLE CONNECTIONS ARE PROVIDED BETWEEN THE COMPONENT AND ASSOCIATED PIPING AND CONDUIT.

RESTRAINTS ARE NOT REQUIRED IF THE COMPONENT WEIGHS 400 LBS. OR LESS, IS MOUNTED AT 4 FT. OR LESS ABOVE A FLOOR, AND HAS FLEXIBLECONNECTIONS BETWEEN THE COMPONENT AND ASSOCIATED PIPING AND CONDUIT.RESTRAINT IS NOT REQUIRED IF THE PIPING IS SUPPORTED BY HANGERS AND EACH HANGER IN THE PIPING RUN IS 12 IN. OR LESS IN LENGTH FROM THE TOPOF THE PIPE TO THE SUPPORTING STRUCTURE. WHERE PIPES ARE SUPPORTED ON A TRAPEZE, THE TRAPEZE SHALL BE SUPPORTED BY HANGERS HAVING ALENGTH OF 12 IN. OR LESS. WHERE ROD HANGERS ARE USED, THEY SHALL BE EQUIPPED WITH SWIVELS, EYE NUTS OR OTHER DEVICES TO PREVENTBENDING IN THE ROD.COMPONENT CERTIFICATION MUST BE SUPPLIED BY THE EQUIPMENT MANUFACTURER AT TIME OF SUBMITTAL FOR REVIEW BY ENGINEER OF RECORD.

2.

3.

4.

A. EQUIPMENT, APPLIANCES AND SUPPORTS (INCLUDING ROOF CURBS & ROOF RAILS) EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TORESIST THE WIND PRESSURES DETERMINED IN ACCORDANCE WITH THE INTERNATIONAL BUILDING CODE. WHERE SEISMIC RESTRAINT ISREQUIRED, THE MORE DEMANDING FORCE OF WIND AND SEISMIC MUST BE USED. SEE SEISMIC INFORMATION CONTAINED IN THE STRUCTURALDRAWINGS FOR SITE SPECIFIC INFORMATION ON SEISMIC DESIGN CATEGORY. SEE EQUIPMENT SCHEDULES AND DETAILS FOR SPECIFICCOMPONENT IMPORTANCE FACTOR DESIGNATIONS.USE APPLICABLE TABLE BELOW TO DETERMINE SEISMIC RESTRAINT REQUIREMENTS FOR EACH MECHANICAL COMPONENT.FOR ALL COMPONENTS REQUIRING SEISMIC RESTRAINT, THE COMPONENT SUPPORTS AND ATTACHMENTS SHALL BE DESIGNED BY A REGISTEREDDESIGN PROFESSIONAL IN THE STATE OF SOUTH CAROLINA.SUBMITTAL MUST INCLUDE STAMPED AND SIGNED DRAWINGS AND CALCULATIONS.WHERE SEISMIC RESTRAINT IS REQUIRED, HOUSEKEEPING PADS NEEDED FOR THE INSTALLATION OF EQUIPMENT UNDER THIS CONTRACT MUST BEDESIGNED BY THE SEISMIC ENGINEER. DO NOT POUR ANY HOUSEKEEPING PADS PRIOR TO THE THE RECEIPT OF THE SEISMIC SUBMITTAL.SEISMIC RESTRAINTS FOR PIPING MUST BE SHOWN ON LAYOUT DRAWINGS SHOWING SPECIFIC RESTRAINT LOCATIONS ALONG WITHACCOMPANYING DETAILS AND CALCULATIONS.

B.C.

D.

E.

· ALL NATURAL GAS APPURTENANCES

1

1, 2

1

1

3

3

3

-

1, 2

· ALL PLUMBING APPURTENANCES, UNO.

CERTI F IC

AT E O F A U THO

RIZAT

ION

SOUTH CAROLINA

CONSULTINGENGINEERS

DWG, INC.

No.C03649

CHECKED BY:

DRAWN BY:

DATE:

PROJECT:

MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS

1

A

2 3 4 5 6

B

C

D

E

WWW.LS3P.COMTEL. 843.577.4444 FAX 843.722.4789205 1/2 KING ST. CHARLESTON SC 29401

STATE PROJECT NO:H17-9588-FW

REVISIONS:

COPYRIGHT 2014 ALL RIGHTS RESERVEDPRINTED OR ELECTRONIC DRAWINGS ANDDOCUMENTATION MAY NOT BE REPRODUCEDIN ANY FORM WITHOUT WRITTEN PERMISSIONFROM LS3P ASSOCIATES LTD.

E

G

No.

L

TU

DS

IC

AH

ISM

RE

TE

K

EG. W

ES

AA

17759

RE

GE

ER

INEN

L

RCAHORP

SEFOLN

S IOINO

LS3P: 1202-122370

MAY 20, 2014

KMM

MGW

PLUMBING NOTES& LEGEND

P000

BID SET

SCIENCE ANNEX IICONSTRUCTION

No. Description Date

Page 2: s SOLENOID VALVE - Coastal Carolina University · PDF filecu condensing unit hd hub drain mc ... kmm mgw plumbing notes & legend p000 bid set science annex ii construction ... bio

111098765432

1

A

B

C

D

F

G

H

X5X3X2

VERT. BIO.104

MSCI ECOLRESEARCH LAB

105

MSCI ECOL LAB106

MSCI ECO RES LAB107

M. TLT.109

JAN.100

OFF-10102H

OFF-11102F

RECEPTION102K

SHARED STOR103

OFF-8 / ADMIN102J

OFF-7 / ADV102I

OFF-6 / ADV102G

OFF-5 / ASST DEAN102E

OFF-4 / DEAN102D

OFF-3 / ADMIN102C

RECEPT102A

OFF-2102B

F. TLT.110

FILE / WORK102

MOLEC & MICROBIO115

LOW SVC ECOLLAB119

DATA111

FRESHWATER101

ELEC.112

ELEV. EQ.116

CHEM WASTE118A

FREEZER114

MECH.M1

BIOHAZARD118B

AQUAR.118C

MUDROOM / DOCK118

NMR118D

ANIMAL120A

ADV WET TEACHLAB127

LOW SVC. TEACHLAB - MSCI

125

MICROSCOPE128

GEO/SED TEACH.LAB124

PREP121

HOUSING120B

WASH120C

ELEVE1

CORRIDORC1-5

CORRIDORC1-7

CORRIDORC1-6

MS

SHOWER108

SH-2LAV-2

FS

WSB

MS

PREP123

STAIR 2-1S1N

STAIR 1-1S1WOUTDOOR

SUPPORTOS

FOYERC1-4

FOYERC1-1

CORRIDORC1-3

LOBBYC1-2

ESH

ESH

ESH

ESH

ESH

ESH

ESH

CS

SK3

SK3

SK3

EWC

SK1

SK1A

2" NPC2" NPH

2" NPC2" NPH

2" N

PC2"

NPH

3/4" NPH3/4" NPC1" NPH

2" NPC2" NPH

2" NPC2" NPH

2" NPC2" NPH

1P301

GEO SEDRESEARCH LAB

126

SK1

SK1

SK1

SK1

SK1

SK1

SK1

3/4" NPHR

MS

SK1

SK1 1

SK1

SK1

SK1A

SK1A

SK1

SK1

SK1A

SK1A

SK1

SK1

SK1CSSK1

MS

MS

SK1

2 1/2" PC

3/4" NPHR

CS CS

CS

SK1

3/4"

NPH

R

FD-3

NFWH

SK1

NFWH

NFWH

SH-1

SH-1

NFWH

NFWH

NFWH

HB

2" PWS

2" PWS

2" PWS

2" PWS

1" NPC1" NPH

3/4" NPC

3/4" NPC

2" P

WS

3/4" NPH3/4" NPC

1" NPH

1" NPC

2" PWS

1" NPC

1" NPC1" NPH

1" NPH

1" NPC

1" NPH1" NPC

3/4" NPH3/4" NPC

1" P

C1"

PH

2" P

WS

2" PWS

1/2"

PH

R

2

P4021

Y1

Y23

CS

SK1

CS CS

2

2

2

2

2

2

2

2

2

CS

2

2

CS

CS

2

22" PWS

3/4" NPC

3/4" NPC3/4" NPH

1/2"

NPC

LS

SK1

4

1" NPC1" NPH

2" PWS

2" PWS2" PWS

3/4" NPC3/4" NPH

1" NPC

1" NPH

1" N

PH1"

NPC

3/4" NPC 3/4" NPH1" NPH 1" NPC

1" NPC

1" NPH

1" NPC1" NPH

1" N

PH1"

NPC

3/4"

NPH

3/4"

NPC

1" NPC

1" N

PC

3/4"

NPH

3/4"

NPC

3/4" NPC3/4" NPH

3/4" NPH 3/4" NPC

3/4"

NPH

3/4"

NPC

SK3

3/4" NPH

8.5

BALANCINGVALVE

2" P

WS

2

2" PWS

2" P

WS

2

2

2

2" PWS

2" P

WS

2" P

WS

2" P

WS

1 1/4" PH1/2" PHR

2" PWS

2

2 2

2" PWS

1" NPH1" NPC

BALANCINGVALVE

4

4

E

3/4" NPC

3/4" NPC

3/4" NPH

1/2"

NPH

3/4" NPC3/4" NPH

3/4" NPC3/4" NPH

3/4"

NPH

3/4"

NPC

3/4" NPH3/4" NPC

3/4" NPH3/4" NPC

2" NPC2" NPH3/4" NPHR

2" PC

3/4" PH

1" NPH1" NPC

3/4" NPH

3/4" NPC

2" P

WS

2" P

WS

BALA

NC

ING

VAL

VE

FIRE PUMPM2

3/4" NPC

3/4" NPC

P4023

2" NPC2" NPH3/4" NPHR

TP

TP

TP

TP

TP

TP

TP

TP

TP

TP

TP

TP

TP

CERTI F IC

AT E O F A U THO

RIZAT

ION

SOUTH CAROLINA

CONSULTINGENGINEERS

DWG, INC.

No.C03649

CHECKED BY:

DRAWN BY:

DATE:

PROJECT:

MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS

1

A

2 3 4 5 6

B

C

D

E

WWW.LS3P.COMTEL. 843.577.4444 FAX 843.722.4789205 1/2 KING ST. CHARLESTON SC 29401

STATE PROJECT NO:H17-9588-FW

REVISIONS:

COPYRIGHT 2014 ALL RIGHTS RESERVEDPRINTED OR ELECTRONIC DRAWINGS ANDDOCUMENTATION MAY NOT BE REPRODUCEDIN ANY FORM WITHOUT WRITTEN PERMISSIONFROM LS3P ASSOCIATES LTD.

E

G

No.

L

TU

DS

IC

AH

ISM

RE

TE

K

EG. W

ES

AA

17759

RE

GE

ER

INEN

L

RCAHORP

SEFOLN

S IOINO

5/19

/201

4 2:

48:1

2 PM

C:\U

sers

\km

inog

ue\D

ocum

ents

\120

96_C

CU

Sci

ence

Ann

ex II

Pha

se O

ne_2

013_

kmin

ogue

.rvt

LS3P: 1202-122370

MAY 20, 2014

KMM

MGW

PLUMBING FIRSTFLOOR WATERDISTRIBUTIONPLAN

P101

BID SET

SCIENCE ANNEX IICONSTRUCTION

SCALE: 1/8" = 1'-0"P1011 FIRST FLOOR WATER DISTRIBUTION PLAN

PROVIDE WALL-MOUNTED UPW-1 WATER POLISHER AT THIS LOCATION.

PROVIDE VALVE AT PWS DROP AND MAKE FINAL CONNECTION TO PURIFIED WATEROUTLET. SEE DETAIL.

4" WATER SERVICE SUPPLY. SEE CIVIL FOR CONTINUATION.

PIPING SHALL BE RUN UNDER SLAB.

1

2

GENERAL NOTES:1. ALL LAB FIXTURES AND JANITOR CLOSET MOP SINKS SHALL BE PROVIDED WITHNON-POTABLE WATER.

2. BREAK ROOM SINKS, EWC, RESTROOM/BATHROOM FIXTURES, AND WALLHYDRANTS SHALL BE PROVIDED WITH POTABLE WATER. DO NOT INTERCONNECT NON-POTABLE AND POTABLE DOMESTIC WATER PIPING SYSTEMS UNO.

3. IRRIGATION SYSTEM WATER SUPPLY WILL BE VIA SWAIN SCIENCE BUILDING.

3

4

KEY NOTES:

No. Description Date

Page 3: s SOLENOID VALVE - Coastal Carolina University · PDF filecu condensing unit hd hub drain mc ... kmm mgw plumbing notes & legend p000 bid set science annex ii construction ... bio

UP

11109876543

2

1

A

B

C

D

F

G

H

X5X2

OFF-1241

OFF-13228

OFF-12229

OFF-9232

OFF-7233

OFF-6235

OFF-5236

OFF-4237

OFF-3238

ELEVE2

OFF-8234

OFF-20242

ELEC.240

OFF-10231

OFF-11230

OFF-15227

DATA239

OFF-17224

OFF-14226

OFF-16225

GRAD BULLPEN246

GIS247COMP MODEL

248

COMPUTERSERVER

250

PHYS OCEAN255

OFFICE254

OFFICE253

LOW SVC TEACHLAB252

PREP251

LOW SVC TEACHLAB249

LOW SVC TEACHLAB245

PREP244

LOW SVC TEACHLAB243

ADMIN-1222

OFF-18219

FILE / WORK / BRK217

F. TLT.201

OFF-19218

OFF-1216

OFF-2215

OFF-3214

OFF-5212

OFF-4213

OFF-6211

OFF-7210

OFF-8209

OFF-9208

LECTURECLASSROOM

207

GRAD STD206

LECTURECLASSROOM

205

LECTURECLASSROOM

204

SEMINAR203

M. TLT202

JAN223

STAIR 3S3-2

LG CONF RM220

CORRIDORC2-3

CORRIDORC2-5

STAIR 1-2S2W

STAIR 2-2S2N

CORRIDORC2-4

PLOT256

DWSBIMB

IMB

DWSB

CORRIDORC2-1

CORRIDORC2-2

2" PWS, 2" PWR, 4" PC, 1-1/2"PH, 3/4" PHR, 4" NPC, 2-1/2" NPH,3/4" NPHR, 2" PWS, AND 2" PWRRISERS AND 1-1/2"HVACMAKEUP WATER

ESH ESH

EWC

EWC

ROUTE PIPING FORSINK BELOW FLOOR.COORDINATE STUBUP LOCATION WITHNYCOM.

MS

CS

CS SK1 SK1

SK1SK1

CS

SK1

SK1A SK1A

CS

CS

SK1

SK1

SK1

LSLS

SK1A

SK1

SK1

LS

LSLS

LS

BRS

SK1

SK1A

2" PWS2" PWR

3/4" PC1/2" PH

3/4" NPHR

2" NPC2" NPH

3/4" NPHR1/2" PC1/2" PH

1/2" PHR

1/2" PHR

1" N

PH1"

NPC

1" N

PH1"

NPC

3/4"

NPH 3/

4" N

PC3/

4" N

PH3/

4" N

PC

3/4" NPH3/4" NPC

3/4" NPH3/4" NPC

3/4"

NPH

3/4"

NPC

3/4"

NPH

3/4"

NPC

1" N

PC1"

NPH

3/4"

NPH

3/4"

NPC

3/4" NPH

3/4" NPC

3/4"

NPC

3/4"

NPH

1" N

PC

1" N

PH

1" NPC1" NPH

1" NPC

1" NPH

1

1

11

1

1

1" NPH1" NPC

Y1

Y2

ESH

2 1/2" PC

2" PH

3/4" PHR

3/4" NPHR 2" NPH2" NPC

8.5

2" NPH2" NPC

2" P

WS

2" P

WS

2" PWR

E

P4022

2" P

WR

2" PWS3/

4" N

PC3/

4" N

PH

2" PWS

3/4"

NPH

3/4"

NPC

2" PWS

2" PWS

2" PWS

2" PWS

2" P

WS

2" PWS 2" PWS

2" P

WS

2" P

WS

3/4" NPHR2" NPH2" NPC

2" N

PC

3/4"

NPH

R2"

NPH

EW

EW

PWSB

PWSB

22

2

2

2

2

2

2

2

2

2

3/4" NPC UP

TP

TP

TP

CERTI F IC

AT E O F A U THO

RIZAT

ION

SOUTH CAROLINA

CONSULTINGENGINEERS

DWG, INC.

No.C03649

CHECKED BY:

DRAWN BY:

DATE:

PROJECT:

MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS

1

A

2 3 4 5 6

B

C

D

E

WWW.LS3P.COMTEL. 843.577.4444 FAX 843.722.4789205 1/2 KING ST. CHARLESTON SC 29401

STATE PROJECT NO:H17-9588-FW

REVISIONS:

COPYRIGHT 2014 ALL RIGHTS RESERVEDPRINTED OR ELECTRONIC DRAWINGS ANDDOCUMENTATION MAY NOT BE REPRODUCEDIN ANY FORM WITHOUT WRITTEN PERMISSIONFROM LS3P ASSOCIATES LTD.

E

G

No.

L

TU

DS

IC

AH

ISM

RE

TE

K

EG. W

ES

AA

17759

RE

GE

ER

INEN

L

RCAHORP

SEFOLN

S IOINO

5/19

/201

4 2:

48:3

1 PM

C:\U

sers

\km

inog

ue\D

ocum

ents

\120

96_C

CU

Sci

ence

Ann

ex II

Pha

se O

ne_2

013_

kmin

ogue

.rvt

LS3P: 1202-122370

MAY 20, 2014

KMM

MGW

PLUMBINGSECOND FLOORWATERDISTRIBUTIONPLAN

P102

BID SET

SCIENCE ANNEX IICONSTRUCTION

SCALE: 1/8" = 1'-0"P1021 SECOND FLOOR WATER DISTRIBUTION PLAN

ROUTE PIPING FOR SINK BELOW FLOOR. COORDINATE STUB UP LOCATION WITHNYCOM.

PROVIDE PURIFIED WATER OUTLET WITH VALVE FOR SINK. COORDINATE ROUGH-INLOCATION WITH LAB EQUIPMENT PROVIDER.

1

GENERAL NOTES:1. ALL LAB FIXTURES AND JANITOR CLOSET MOP SINKS SHALL BE PROVIDED WITHNON-POTABLE WATER.

2. BREAK ROOM SINKS, EWC, RESTROOM/BATHROOM FIXTURES, AND WALLHYDRANTS SHALL BE PROVIDED WITH POTABLE WATER. DO NOT INTERCONNECT NON-POTABLE AND POTABLE DOMESTIC WATER PIPING SYSTEMS UNO.

KEY NOTES:

2

No. Description Date

Page 4: s SOLENOID VALVE - Coastal Carolina University · PDF filecu condensing unit hd hub drain mc ... kmm mgw plumbing notes & legend p000 bid set science annex ii construction ... bio

DN

11109

8765432

1A

B

C

D

F

G

H

X5X3X2

ORG CHEM306

A & P TEACHING305

PREP307

ORG CHEM308

PREP304

A&P TEACHING303

M. TLT.310

OFF-19314

OFF-18313

OFF-17312

OFF-16311

F. TLT.302

SECURE FILE301A

OFF-12301B

OFF-11301C

OFF-10301D

OFF-14301Q

DATA316

ELEC317

OFFICE301L

OFF-15301P

CHEM STOR318

OFF-6301H

OFF-5301I

OFF-4301J

OFF-3301K

OFF-2301M

MS M. CHEM.RESEARCH 1

326

MARINE CHEMTEACH LAB

320

MS CHEM INSTR.321

CHEM WET328

PREP329

CHEM. BAL.328B

ADV. CHEM TEACH.330

ROOF TERRACE332

GEN CHEM327

ASTRON. STOR.331

GEN CHEM322

PREP323

MS M CHEMRESEARCH

319A

BALCONY315

OFF-9301E

CORRIDORC3-1

CORRIDORC3-3

CORRIDORC3-2

CORRIDORC3-5

STAIR 2-3S3N

STAIR 1-3S3W

STAIR 3S3-3

ALT TREAD STAIR309

ELEVE3

ROOF ACCESS324

CORRIDORC3-4

CLEAN ROOM319B

OFF-8301F

OFF-7301G

JAN325

MSCI PREP320A

IMB

PWSB

IMB

DWSB

DWSB

PWSB

DW

SB

CS

CS

CRS

PROVIDEUPW-1WATERPOLISHINGSTATION ATEACH LABSINK, THISROOM ONLY.

2" PWS, 2" PWR, 4" PC, 1-1/2"PH, 3/4" PHR, 4"NPC, 2-1/2"NPH, AND 3/4" NPHR RISERSAND 1-1/2" HVAC MAKEUPWATER

SK1

MS

CS SK1

LS

LS

LS

LS

LS

LS

CS CSSK1

SK1

SK1A

SK1

CS

CS

CS CS CS CS

CSCS

CS

CS

CS

2" PWS

2" PWS

2" PWS2" PWS

1" NPH

CSCS

SK1A

SK1

CSCS

CSCS

CSCS

CSCS

SK1

CS

CS

CSCS

CSCS

SK1

SK1

CSCS

CS

CS

CS

CS

CSCS

CSCS

CSCS

CSCS

CSCS

CSCS

SK1

SK1

SK1A

LS SK1A

SK2

CS

SK1A

SK1

SK1A

SK1

2" NPC2" NPH

3/4" NPHR

1" NPC1" NPH

1" NPC1" NPH

2" PWS

1" N

PC

1" N

PH

1" N

PC

1" N

PH1"

NPH

1" N

PC1"

NPC

1" N

PC 1" N

PC

1" N

PH

1" N

PC1"

NPC

1" N

PH

1" N

PC1/

2" N

PH

1" N

PC1"

NPH

1" N

PC1"

NPH

1" N

PC1"

NPH

1" N

PC1"

NPH

1" N

PH1"

NPC

1" N

PH1"

NPC

1" N

PC

1" N

PH

1" N

PH1" N

PC

1" NPC1" NPH

1" N

PC 1" N

PH1"

NPC

1" N

PH1"

NPC

1" N

PC1"

NPH

1" N

PC

1" N

PC

1" NPH1" NPC

1" N

PH1"

NPC

1" N

PH1"

NPC

1" N

PC

1" N

PC1"

NPC

1" NPC1" NPH

1" N

PC1"

NPH1" NPH

1" NPC 1" NPC1" NPH

1" NPH1" NPC

1" NPC1" NPH

1" NPC

1" NPH1" NPC

1" NPH

1" NPC1" NPH

1" N

PH1"

NPC

1" NPH

1" NPC

2" N

PC2"

NPH

3/4"

NPH

R

1" NPH1" NPC

1" NPH

1" NPC

1" NPH

1" NPC

1" NPH

1" NPC

1" NPH 1" NPC

1" N

PC1"

NPH

1" NPC

2" PWS

2" P

WS

2" P

WS

1" NPC 1" NPC 1" NPC1" NPH

1" NPH 1" NPC

1" N

PH

1" N

PC

1" NPC1" NPH

1

1

1

1

1

1

1

1

Y1

Y2

SK1

SK1

CS

CS

SK1

CSSK1SK1

CS

CS

CS

SK1

SK1

3/4" PHR1 1/2" PH2 1/2" PC

2" PWR

2

2" PWS

SK1

SK1

CSCSSK1

CS

SK1

CS

3

3

3

3

3

8.5

E

2" P

WS

2" NPC2" NPH3/4" NPHR

2" PWS

3/4" NPHR2" NPH2" NPC

2" N

PC2"

NPH

2" PWS

1" NPC

1/2" NPH1" NPC

1" NPC

1" NPC

1/2" NPC1/2" NPH

1" N

PC

1" N

PC

1" N

PC

P4024

SK1

SK1

EW

EW

EW

EW

PWSB

PWSB

IMB

DW

SB

2

2

2

2

3

2

3

SK1

3

3

33

3

CS

CS

3 SK1

3

3

3

33

3

3

3

3

3

3

3

22

BALA

NC

ING

VALV

E

BALANCINGVALVE

3/4" NPHR 2" NPH2" NPC

2" NPC2" NPH

3/4" NPHR2" NPH

3/4" NPHR

2" NPC2" NPC2" NPH

3/4" NPHR

2" NPC

3/4" NPHR2" NPH

SK1A

SK2

3

3

3

3

2" PWS

2" PWS

2" PWS

2" PWS

2" PWS

2" P

WS

2" P

WS

2" P

WS

2" P

WS

2" PWS 2" P

WS

2" PWS

2" PWS 2" P

WS

2" PWS2" PWS

2" PWS

2" P

WS

2" PWS2" PWS

2" P

WS

NFWH

NFWH

3/4" NPC DN

TP

TP

TP

TP

TP

TP

TP

TP

TP

SCALE: 1/8" = 1'-0"P1031 THIRD FLOOR WATER DISTRIBUTION PLAN

ROUTE PIPING FOR SINK BELOW FLOOR. COORDINATE STUB UP LOCATION WITH LABCASEWORK PROVIDER AND MAKE FINAL CONNECTIONS.

PROVIDE PURIFIED WATER OUTLET FOR FUME HOOD. COORDINATE ROUGH-INLOCATION WITH LAB EQUIPMENT PROVIDER AND MAKE FINAL CONNECTION.

PROVIDE PURIFIED WATER OUTLET FOR SINK. COORDINATE ROUGH-IN LOCATIONWITH LAB EQUIPMENT PROVIDER AND MAKE FINAL CONNECTION.

1

CERTI F IC

AT E O F A U THO

RIZAT

ION

SOUTH CAROLINA

CONSULTINGENGINEERS

DWG, INC.

No.C03649

CHECKED BY:

DRAWN BY:

DATE:

PROJECT:

MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS

1

A

2 3 4 5 6

B

C

D

E

WWW.LS3P.COMTEL. 843.577.4444 FAX 843.722.4789205 1/2 KING ST. CHARLESTON SC 29401

STATE PROJECT NO:H17-9588-FW

REVISIONS:

COPYRIGHT 2014 ALL RIGHTS RESERVEDPRINTED OR ELECTRONIC DRAWINGS ANDDOCUMENTATION MAY NOT BE REPRODUCEDIN ANY FORM WITHOUT WRITTEN PERMISSIONFROM LS3P ASSOCIATES LTD.

E

G

No.

L

TU

DS

IC

AH

ISM

RE

TE

K

EG. W

ES

AA

17759

RE

GE

ER

INEN

L

RCAHORP

SEFOLN

S IOINO

5/19

/201

4 2:

48:5

6 PM

C:\U

sers

\km

inog

ue\D

ocum

ents

\120

96_C

CU

Sci

ence

Ann

ex II

Pha

se O

ne_2

013_

kmin

ogue

.rvt

LS3P: 1202-122370

MAY 20, 2014

KMM

MGW

PLUMBING THIRDFLOOR WATERDISTRIBUTIONPLAN

P103

BID SET

SCIENCE ANNEX IICONSTRUCTION

GENERAL NOTES:1. ALL LAB FIXTURES AND JANITOR CLOSET MOP SINKS SHALL BE PROVIDED WITH NON-POTABLE WATER.

2. BREAK ROOM SINKS, EWC, RESTROOM/BATHROOM FIXTURES, AND WALL HYDRANTSSHALL BE PROVIDED WITH POTABLE WATER. DO NOT INTERCONNECT NON-POTABLEAND POTABLE DOMESTIC WATER PIPING SYSTEMS UNO.

3. COORDINATE ALL UTILITY REQUIREMENTS WITH LAB EQUIPMENT SUPPLIER.

2

3

KEY NOTES:

No. Description Date

Page 5: s SOLENOID VALVE - Coastal Carolina University · PDF filecu condensing unit hd hub drain mc ... kmm mgw plumbing notes & legend p000 bid set science annex ii construction ... bio

11109

8765432

B

C

D

F

G

H

X5X3X2

MECHANICALSPACE

401FD-2

FD-2

Y1

Y2

3" AV3"AVTR

3"AV DN

3"AVTR

3"AVTR3"AVTR

3"AVTR3"AVTR

8.5

E

3"AVTR

4"VTR

3"AVTR

3"AVTR

3"AVTR

2"VTR

3"AVTR

P4025

TP

TP

TP

TP

TP

2"VTR

2" V4"W DN

3"VTR

4"WDN

2" V

3" V

2"VCONNECTION

CERTI F IC

AT E O F A U THO

RIZAT

ION

SOUTH CAROLINA

CONSULTINGENGINEERS

DWG, INC.

No.C03649

CHECKED BY:

DRAWN BY:

DATE:

PROJECT:

MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS

1

A

2 3 4 5 6

B

C

D

E

WWW.LS3P.COMTEL. 843.577.4444 FAX 843.722.4789205 1/2 KING ST. CHARLESTON SC 29401

STATE PROJECT NO:H17-9588-FW

REVISIONS:

COPYRIGHT 2014 ALL RIGHTS RESERVEDPRINTED OR ELECTRONIC DRAWINGS ANDDOCUMENTATION MAY NOT BE REPRODUCEDIN ANY FORM WITHOUT WRITTEN PERMISSIONFROM LS3P ASSOCIATES LTD.

E

G

No.

L

TU

DS

IC

AH

ISM

RE

TE

K

EG. W

ES

AA

17759

RE

GE

ER

INEN

L

RCAHORP

SEFOLN

S IOINO

5/19

/201

4 2:

49:0

7 PM

C:\U

sers

\km

inog

ue\D

ocum

ents

\120

96_C

CU

Sci

ence

Ann

ex II

Pha

se O

ne_2

013_

kmin

ogue

.rvt

LS3P: 1202-122370

MAY 20, 2014

KMM

MGW

MECHANICALSPACE PLUMBINGPIPING &EQUIPMENT PLAN

P104

BID SET

SCIENCE ANNEX IICONSTRUCTION

SCALE: 1/8" = 1'-0"P1041 MECHANICAL SPACE PLUMBING PIPING & EQUIPMENT PLAN

GENERAL NOTES:1. SLOPE FLOOR TO FLOOR DRAINS. SEE ARCHITECTURAL DOCUMENTS FOR

MORE INFORMATION.2. PROVIDE 1/8" PER FOOT MINIMUM SLOPE FOR ALL VACUUM PIPING.

PROVIDE DRIP LEG WITH REMOVABLE CAP AT ALL LOW POINTS IN PIPING.

No. Description Date

Page 6: s SOLENOID VALVE - Coastal Carolina University · PDF filecu condensing unit hd hub drain mc ... kmm mgw plumbing notes & legend p000 bid set science annex ii construction ... bio

11109

8765432

1

A

B

C

D

F

G

H

X5X3X2

VERT. BIO.104

MSCI ECOLRESEARCH LAB

105

MSCI ECOL LAB106

MSCI ECO RES LAB107

M. TLT.109

JAN.100

OFF-10102H

OFF-11102F

RECEPTION102K

SHARED STOR103

OFF-8 / ADMIN102J

OFF-7 / ADV102I

OFF-6 / ADV102G

OFF-5 / ASST DEAN102E

OFF-4 / DEAN102D

OFF-3 / ADMIN102C

RECEPT102A

OFF-2102B

F. TLT.110

FILE / WORK102

MOLEC & MICROBIO115

LOW SVC ECOLLAB119

DATA111

FRESHWATER101

ELEC.112

ELEV. EQ.116

CHEM WASTE118A

FREEZER114

MECH.M1

BIOHAZARD118B

AQUAR.118C

MUDROOM / DOCK118

NMR118D

ANIMAL120A

ADV WET TEACHLAB127

LOW SVC. TEACHLAB - MSCI

125

CORRIDORC1-6

CORRIDORC1-7

ELEVE1

CORRIDORC1-5

GEO/SED TEACH.LAB124

MICROSCOPE128

PREP121

HOUSING120B

WASH120C

STAIR 1-1S1W

PREP123

SHOWER108

6" AW

ACID WASTE UNDER SLABSANITARY WASTEUNDER SLAB

4" W

TO ACID NEUTRALIZATIONTANK ANT-1. SEE CIVIL FOR

CONTINUATION OF ACIDWASTE PIPING AND

LOCATION OF ANT-1.

SEE CIVIL FORCONTINUATION OFSANITARY WASTE

PIPING.

4" W

4" A

W

4" W

4" W

4" W

STAIR 2-1S1N

OUTDOORSUPPORT

OS

FOYERC1-4

FOYERC1-1

CORRIDORC1-3

LOBBYC1-2

2" W

4" AW UP

4" AWUP

4" AW UP

4" AW UP

4" AW UP

4" WUP

4" W UP

2"W UP

FCO

2"W A/C

FD-3 FD-3 FD-3

FCO

FCO

FCO

FCO

FCO

FCO

FCO

FCO

FCO

FD-1

LAV-1(TYP.)

MS

URUR-A

LAV-1(TYP.)

FD-1

EWC

EWC

4"AW UP

6" ST

FD-1

FD-2

FD-1

FD-1

FD-1

FD-3

FD-1

FD-1

FD-1

FD-3

4" ST

CS

CS CS

SK1

SK1

SK1

SK1

MS SK1

SK1

SK1A

FD-1

WC-A

WC

WC

WC

WC

WC-A

BRS

SK1

CS

SK1

SK1SK1

MS

CSSK1

CS

SK1ASK1

SK1

SK3 CS

SK1

SK1A

SK1

CS

CS

SK1 SK1

SK1A

CS

SK1A

SK1

SK1

SK1

SK1

SK1

SK1

FD-4FD-4

FD-4

FD-4

FD-4

FD-4

FD-4

FD-4

FD-4

SP-1

3"W UP

WCO

LAV-2

SK1

FD-3

OFO

SEE CIVIL FORCONTINUATION.

6" AW6" AW6" AW6" AW6" AW

2" AW

2" AW

4" AW

4" AW

2" A

W

2" AW 3" AW2" AW

1 1/2" AW

2" AW

2" W4" W

4" W

3" AW

3" A

W

3" AW

4" AW

4" AW

3" AW3" AW

3" AW

2" AW

2" AW

2" AW

1 1/2" AW

6" AW6" AW

4"AW UP

FCO

WCO

CO

OFFSET A/C

2" AW

4" AW

WCO WCO

WCO

WCO

WCO

WCO

WCO

WCO

3" AW

3" AW

4" AW4" AW

4" W

3" W

4" AW

4" W

3" W

3" AW

3" AW

4" AW

4" A

W

4" AW

4" AW

2" AW

4"AW UP

2" A

W

4"AW UP

WCO

SEE CIVIL FORCONTINUATION.

3" AW

4" A

W4"

AW

3" AW 4" AW

2" AW

Y1

Y2

3" AW

3" AW

4" ST

4" ST DN

4" OF

FD-4

ESH

ESH

4" A

W

3" AW

3" AW

3" AW

2" AW

3" AWESH

2" AV

3" AW

ESH

ESH

4" AW

2" AW

ESH2" AW

FD-1

FD-4

ESH

2" AW

SD-1

2" W

3" AW

ESH2" AWWCO

ESH2" AW

4"AW DNIN WALL

3" AW

2" AW

3" AW

ESH

3" AW

3" AW

2" AW2" AW

GEO SEDRESEARCH LAB

126

3" AW

3" AW

2" AV

2" A

W

2" AW

2" A

W2"

AW

3" AW

2" AW

3" AW

SK3

SK3

FD-1

CS

8.5

E

FIRE PUMPM2

FD-1AREA RESERVED

FOR FIRE PUMP

SK1MS

US

4" AW

4" W

4" AW

4" AW

4" AW

4" AW

4" AW

4" AW

4" AW

4" W

4" AW

3" AW

3" A

W

FD-3

FD-3

4" AW

2" AW 2" AW

4" ST UP

4" STOFFSET A/C

3" A

W3"

AW

4" AW

2" AW

4" AW

2" A

V2"

AV

1-1/2"W UP3"AW UP

4"AWUP

4"AW UP 4"AW UP

LS

3"AV UP

3" A

V

3"AV UP

3"AVUP

3"AV UP

3"AV UP3"AV UP 3"AV

UP 3"AVUP

3"AVUP

3"AVUP

2"VUP

3"AV UP

3"AVUP

3"AVUP

LOCATION OF pH MONITORINGSTATION FOR ANT-1. SEE

ELECTRICAL SITE PLAN FORMORE INFORMATION.

3" AW

2"V UP2" V

4"W UP

4" W

4" W

4"WUP

4"W UP.WCO ATBASE

4" W

2" AV 2" AV

2" V

2"VUP

4" W

4"W UP

FD-1

2" AV

2" AV

2" AV

FD-3

2" AV

2" AV

4" AW

4" A

W

4" AW

4" A

W

CERTI F IC

AT E O F A U THO

RIZAT

ION

SOUTH CAROLINA

CONSULTINGENGINEERS

DWG, INC.

No.C03649

CHECKED BY:

DRAWN BY:

DATE:

PROJECT:

MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS

1

A

2 3 4 5 6

B

C

D

E

WWW.LS3P.COMTEL. 843.577.4444 FAX 843.722.4789205 1/2 KING ST. CHARLESTON SC 29401

STATE PROJECT NO:H17-9588-FW

REVISIONS:

COPYRIGHT 2014 ALL RIGHTS RESERVEDPRINTED OR ELECTRONIC DRAWINGS ANDDOCUMENTATION MAY NOT BE REPRODUCEDIN ANY FORM WITHOUT WRITTEN PERMISSIONFROM LS3P ASSOCIATES LTD.

E

G

No.

L

TU

DS

IC

AH

ISM

RE

TE

K

EG. W

ES

AA

17759

RE

GE

ER

INEN

L

RCAHORP

SEFOLN

S IOINO

5/19

/201

4 2:

49:4

9 PM

C:\U

sers

\km

inog

ue\D

ocum

ents

\120

96_C

CU

Sci

ence

Ann

ex II

Pha

se O

ne_2

013_

kmin

ogue

.rvt

LS3P: 1202-122370

MAY 20, 2014

KMM

MGW

PLUMBING FIRSTFLOOR WASTE &VENT PLAN

P111

BID SET

SCIENCE ANNEX IICONSTRUCTION

SCALE: 1/8" = 1'-0"P1111 FIRST FLOOR WASTE & VENT PLAN

GENERAL NOTES:1. ALL LAB FIXTURES AND JANITOR CLOSET MOP SINKS SHALL BE PROVIDED WITHACID WASTE/VENT PIPING.

2. BREAK ROOM SINKS, EWC, RESTROOM/BATHROOM FIXTURES SHALL BEPROVIDED WITH SANITARY WASTE/VENT PIPING.

3. DO NOT INTERCONNECT ACID AND SANITARY PIPING SYSTEMS UNO.

No. Description Date

Page 7: s SOLENOID VALVE - Coastal Carolina University · PDF filecu condensing unit hd hub drain mc ... kmm mgw plumbing notes & legend p000 bid set science annex ii construction ... bio

UP

11109

8765432

1A

B

C

D

F

G

H

X5X3X2

OFF-1241

OFF-13228

OFF-12229

OFF-9232

OFF-7233

OFF-6235

OFF-5236

OFF-4237

OFF-3238

ELEVE2

OFF-8234

OFF-20242

ELEC.240

OFF-10231 OFF-11

230

OFF-15227

DATA239

OFF-17224

OFF-14226

OFF-16225

GRAD BULLPEN246

GIS247

COMP MODEL248

COMPUTERSERVER

250

PHYS OCEAN255

OFFICE254

OFFICE253

LOW SVC TEACHLAB252

PREP251

LOW SVC TEACHLAB249

LOW SVC TEACHLAB245

PREP244

LOW SVC TEACHLAB243

ADMIN-1222

OFF-18219

FILE / WORK / BRK217

F. TLT.201

OFF-19218

OFF-1216

OFF-2215

OFF-3214

OFF-5212

OFF-4213

OFF-6211

OFF-7210

OFF-8209

OFF-9208

LECTURECLASSROOM

207

GRAD STD206

LECTURECLASSROOM

205

LECTURECLASSROOM

204

SEMINAR203

M. TLT202

PLOT256

CORRIDORC2-5

LG CONF RM220

CORRIDORC2-4

CORRIDORC2-3

STAIR 2-2S2N

STAIR 1-2S2W

JAN223

4" AWRISER

2" AW DNAND 2" AV

UP

4"AWRISER

4"WRISER

4"WRISER

EWC

CONNECTTO 4"WRISER

2"W DN

EWC

6"ST RISER

WC-A

WC

UR-A

UR

LAV-1(TYP.)

WC-A

WC

WC

WC

FD-1

FD-1

FD-1

3"AW DN

CO

SK1

CS

SK1

SK1

3" AW

FD-4

SK1

SK1A

LS

LS

BRS

LAV-1(TYP.)

SK1A

LS

CS

SK1

LS

SK1ACS

SK1 SK1

SK1

CS

LS

SK1

SK1A

CS

LS

BRS

SK1

SK1

FD-4

FD-1

FD-4

CO

CO

CO

CO

CO

3"W RISER

4"AW UP& DN

4"AW DN,3"AW UP

4"AW DN4"AW DN3"AW UP

4"AW

4" AWRISER

CO

4" AW

4" AW4" AW

3" A

W

1 1/2" AW

1 1/2" AW

2" A

W3"

AW

2" A

W

1 1/

2" A

W

1 1/2" AW

3" AW2" AW

3" AW

1 1/2" AW

4" AW

1 1/2" AW

4" AW

1 1/2" AW

3" AW4" AW

2" AW

2" AW

2" AW

2" AW

2" AV

2" AV3" AW

2" AW 2" AV

2" A

V

1 1/2" AV

1 1/2" AV

2" AV

2" A

W

3" AW4" AW

1 1/2" AV

CO

2" AW

CO

4"AW UP

4"AW DN

4"AW DN

4"AW UP

2" AW

CO

4" AW

Y1

Y2

4" ST DN

4"ST RISER

4"ST RISER

3" AW

3" AW

ESH ESH

2" AW 2" AW

ESHESH

FD-4

2" AW

3" AW3" AW

2" AW

8.5

E

3" AV UP

3"AV UP

2" A

V

3" A

W2"

AW

4" S

T4"

ST

4"ST UPTO PD

4"ST UPTO PD

4"AW

2" A

V2" AV

3"AVDN

3" AV

3"AV DN

3"AVDN

3"AV DN

3"AV DN

3"AV DN

3"AVDN

3"AVDN

3"AVDN

MS

3"AVDN

2"V DN

3"AV DN3"AVDN

3"AVDN

3" AV

2" AV

3"AV UP

2"V UP

4"AWDN

3"AVUP

3"AVUP

3"AV UP

3"AV UP

3"AV UP

3"AVUP

2" V

2"V UP

2"V RISER

4"W UP

4"WDN

4"W UP

4"W UP

4"W DN

2"V STACK

4"W RISER

CERTI F IC

AT E O F A U THO

RIZAT

ION

SOUTH CAROLINA

CONSULTINGENGINEERS

DWG, INC.

No.C03649

CHECKED BY:

DRAWN BY:

DATE:

PROJECT:

MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS

1

A

2 3 4 5 6

B

C

D

E

WWW.LS3P.COMTEL. 843.577.4444 FAX 843.722.4789205 1/2 KING ST. CHARLESTON SC 29401

STATE PROJECT NO:H17-9588-FW

REVISIONS:

COPYRIGHT 2014 ALL RIGHTS RESERVEDPRINTED OR ELECTRONIC DRAWINGS ANDDOCUMENTATION MAY NOT BE REPRODUCEDIN ANY FORM WITHOUT WRITTEN PERMISSIONFROM LS3P ASSOCIATES LTD.

E

G

No.

L

TU

DS

IC

AH

ISM

RE

TE

K

EG. W

ES

AA

17759

RE

GE

ER

INEN

L

RCAHORP

SEFOLN

S IOINO

5/19

/201

4 2:

50:1

1 PM

C:\U

sers

\km

inog

ue\D

ocum

ents

\120

96_C

CU

Sci

ence

Ann

ex II

Pha

se O

ne_2

013_

kmin

ogue

.rvt

LS3P: 1202-122370

MAY 20, 2014

KMM

MGW

PLUMBINGSECOND FLOORWASTE & VENTPLAN

P112

BID SET

SCIENCE ANNEX IICONSTRUCTION

SCALE: 1/8" = 1'-0"P1121 SECOND FLOOR WASTE & VENT PLAN

GENERAL NOTES:1. ALL LAB FIXTURES AND JANITOR CLOSET MOP SINKS SHALL BE PROVIDED WITHACID WASTE/VENT PIPING.

2. BREAK ROOM SINKS, EWC, RESTROOM/BATHROOM FIXTURES SHALL BE PROVIDEDWITH SANITARY WASTE/VENT PIPING. DO NOT INTERCONNECT ACID AND SANITARYPIPING SYSTEMS UNO.

No. Description Date

Page 8: s SOLENOID VALVE - Coastal Carolina University · PDF filecu condensing unit hd hub drain mc ... kmm mgw plumbing notes & legend p000 bid set science annex ii construction ... bio

DN

11109

8765432

1A

B

C

D

F

G

H

X5X3X2

ORG CHEM306

A & P TEACHING305

PREP307

ORG CHEM308

PREP304

A&P TEACHING303

M. TLT.310

OFF-19314

OFF-18313

OFF-17312

OFF-16311

F. TLT.302

SECURE FILE301A

OFF-12301B

OFF-11301C

OFF-10301D

OFF-14301Q

DATA316

ELEC317

OFFICE301L

OFF-15301P

CHEM STOR318

OFF-6301H

OFF-5301I

OFF-4301J

OFF-3301K

OFF-2301M

MS M. CHEM.RESEARCH 1

326

MARINE CHEMTEACH LAB

320

MS CHEM INSTR.321

CHEM WET328

PREP329

CHEM. BAL.328B

ADV. CHEM TEACH.330

ROOF TERRACE332 GEN CHEM

327

ASTRON. STOR.331

GEN CHEM322

PREP323

MS M CHEMRESEARCH

319A

BALCONY315

OFF-9301E

CORRIDORC3-1

CORRIDORC3-3

CORRIDORC3-2

CORRIDORC3-5

STAIR 2-3S3N

STAIR 1-3S3W

STAIR 3S3-3

ALT TREAD STAIR309

ELEVE3

ROOF ACCESS324

CORRIDORC3-4

CLEAN ROOM319B

OFF-8301F

OFF-7301G

JAN325

MSCI PREP320A

4" AW DN

4" AW DN

4" W DN

4"AW DN

4" WDN

2" W DN

EWC

4"AWDN

SK1

SK1

SK1A

SK1

SK1A

SK1 SK1SK1

SK1

SK1

SK1

SK1

SK1SK1A

SK1

SK1

SK1

SK1

SK1

SK1

SK2

SK1A

SK1

SK1A

SK2

SK1A

SK1

SK1

SK1

SK1

SK1A

SK1

3"AW DN

SK1

SK1

ADMIN301

MS

CS

CS

CS

CS

CSCS

CS

CS

CS

CS

CS

BRS

LAV-1

LAV-1

CS

CS

CS

CS

CS

CS

CS CS CS

CSCS

SK1

1

1

CO

UR-A

UR

WCWC-A

WC-A

WC

WC

WC FD-1

FD-1

FD-3

FD-3

FD-1

CS CS

CS CS CS CS

CS

CS

CSCS

CS

CS

CS

CS

CS

CS

CS CS CS CS

CS

CS

CS

CS

CS

CS

CS CS CS CS CS CS CS CS CS

CS

CS

CS

COFD-4

FD-4

FD-4

FD-4

FD-4

FD-4

FD-4

FD-4

FD-4

CO

LS

COCO

CO

CS CS

COCO

LS

CO

CO

LS

COCO

CO

CO CO

CO

LS

CO

CO

CO

LS

CO

(TYP)

(TYP)

CO

3"AW DN 3"AW DN

FD-4

CS

CRS

3"W DN

CO 4" OF

CO

3" A

W

4" AW

3" AW

3" A

W

2" A

W

CO

3" AW

2" AW

2" AW

3" AW

4" AW

2" AW

3" A

W

2" AWESH

2" AW

CO

3" AW

3" AW

CO

CO3" AW

2" AW3" AW 3" AW

2" AW

CO

3" AW

3" AW

1 1/2" AV

3" AW 3" AW

4" AW4" AW 4" AW

4" AW

2" AW 2" AW

4"AW DN

3" AW

3" AW2" AW

3" AW

1 1/2" AV

3" AW

3" A

W

2" AW

2" AW

2" AW1 1/2" AW

2" AW

3"AW DN

4"AW DN

3" AW

3" AW

6" ST UP TO ROOF

6" ST ON2" AW

4"ST DN

4"OF DN

3" AV

2" AW 1 1/2" AW

3" AW

1 1/2" AW

2" AW 2" AW

3" AW3" AW

3" A

W

1 1/2" AW

4" ST

3" AW1 1/2" AW

4" AW

4" AW

3" AW

3" AW

1 1/2" AW

1 1/2" AW

3" AW

1 1/2" AW

4" AW

3" AW

3" A

W

4" AW 4" AW 4" AW

4" A

W

1 1/

2" A

W

4" AW

2" A

W

3" A

W

4" AW

4" AW2" AW

3" AW

4" AW

3" AW

2" AW

3" AW

4"AW DN

3" AV

3" AV

CO

2" AV3" AV3" AV

Y1

Y2

4" AW

3"AVTR

3"AVTR

3"AVTR2"

AV

2" A

V

2" A

V

2" A

V3"AVTR

3" AV

3" A

V

3"AVTR

4" AW

3" AW

3" AV

3"AVTR

3" AW

2" A

V

3" AW3" AW

3" A

W

3" A

V

2" AV2" AV

4" S

T4"

ST

3" VERTICALST DN

PD

PD

PD

PD

ESH

3" AWESH

FD-4

ESH

ESH

ESH

ESH

ESH

FD-4

ESH

ESH

ESH

ESH

3" AW

3" AW

3" AW

2" AW

3" AW

2" AW 3" AW

3" AW

3" AW

3" AW

3" A

W

2" AV

2" AV3" AV

3" A

W3"

AW

3" A

W

3" A

W3"

AW

1 1/2" AV

2" AW

3" A

V

SK1

2" AW

3" AW

3" AW

3" AW

3" AW

SK1

CS

8.5

E

4" A

W

LS

2" AV2" AV

LS

3" AV

2" AV

3" AV

1 1/

2" A

V

2" AV

4" V

2" A

V

2" AV

2" A

V

4" W

3"WRISER

3" V

4" V

4" V

3" A

V

3" AW3" AV3" AV

3"AV DN

2"AV DN

2" A

V

3"AV DN3"AVTR

3"AV

TR

3"AV

TR

4"VTR

3"AVTR

3"AV DN

2" V 2"AV DN

3"AVDN

3"AVTR3"AVDN

3" A

V

3" A

V

1-1/2"V DN

2"VTR

3"AV DN

3" AV

3"AVTR

3"AV DN

3"AVDN

3"AVDN

3" AW

4" AW

2"V DN &UP TO VTR

4"W RISER

2" V

2"V DN

4" V

4"W UP4"W DN

4" W

4"W DN

4" W4"WUP

2" AV

2" A

V

2" A

V

1 1/2" AV

4"W UP

4" W4"WDN

CERTI F IC

AT E O F A U THO

RIZAT

ION

SOUTH CAROLINA

CONSULTINGENGINEERS

DWG, INC.

No.C03649

CHECKED BY:

DRAWN BY:

DATE:

PROJECT:

MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS

1

A

2 3 4 5 6

B

C

D

E

WWW.LS3P.COMTEL. 843.577.4444 FAX 843.722.4789205 1/2 KING ST. CHARLESTON SC 29401

STATE PROJECT NO:H17-9588-FW

REVISIONS:

COPYRIGHT 2014 ALL RIGHTS RESERVEDPRINTED OR ELECTRONIC DRAWINGS ANDDOCUMENTATION MAY NOT BE REPRODUCEDIN ANY FORM WITHOUT WRITTEN PERMISSIONFROM LS3P ASSOCIATES LTD.

E

G

No.

L

TU

DS

IC

AH

ISM

RE

TE

K

EG. W

ES

AA

17759

RE

GE

ER

INEN

L

RCAHORP

SEFOLN

S IOINO

5/19

/201

4 2:

50:4

5 PM

C:\U

sers

\km

inog

ue\D

ocum

ents

\120

96_C

CU

Sci

ence

Ann

ex II

Pha

se O

ne_2

013_

kmin

ogue

.rvt

LS3P: 1202-122370

MAY 20, 2014

KMM

MGW

PLUMBING THIRDFLOOR WASTE &VENT PLAN

P113

BID SET

SCIENCE ANNEX IICONSTRUCTION

SCALE: 1/8" = 1'-0"P1131 THIRD FLOOR WASTE & VENT PLAN

KEY NOTES:PROVIDE ACID DILUTION TANK FOR ACID WASTE HOOD. INSTALL TANK UNDER HOODPROVIDED BY LAB EQUIPMENT SUPPLIER AND MAKE FINAL CONNECTIONS TO WASTEOUTLET. BASIS OF DESIGN: ORION P-8 OR EQUAL.

1

GENERAL NOTES:1. ALL LAB FIXTURES AND JANITOR CLOSET MOP SINKS SHALL BE PROVIDED WITH ACIDWASTE/VENT PIPING.

2. BREAK ROOM SINKS, EWC, RESTROOM/BATHROOM FIXTURES SHALL BE PROVIDEDWITH SANITARY WASTE/VENT PIPING. DO NOT INTERCONNECT ACID AND SANITARYPIPING SYSTEMS UNO.

KEY NOTES:

No. Description Date

Page 9: s SOLENOID VALVE - Coastal Carolina University · PDF filecu condensing unit hd hub drain mc ... kmm mgw plumbing notes & legend p000 bid set science annex ii construction ... bio

11109

8765432

1

A

B

C

D

F

G

H

X5X3X2

1P301

VERT. BIO.104

MSCI ECOLRESEARCH LAB

105

MSCI ECOL LAB106

MSCI ECO RES LAB107

M. TLT.109

JAN.100

OFF-10102H

OFF-11102F

RECEPTION102K

SHARED STOR103

OFF-8 / ADMIN102J

OFF-7 / ADV102I

OFF-6 / ADV102G

OFF-5 / ASST DEAN102E

OFF-4 / DEAN102D

OFF-3 / ADMIN102C

RECEPT102A

OFF-2102B

F. TLT.110

FILE / WORK102

MOLEC & MICROBIO115

LOW SVC ECOLLAB119

DATA111

FRESHWATER101

ELEC.112

ELEV. EQ.116

CHEM WASTE118A

FREEZER114

MECH.M1

BIOHAZARD118B

AQUAR.118C

MUDROOM / DOCK118

NMR118D

ANIMAL120A

ADV WET TEACHLAB127

LOW SVC. TEACHLAB - MSCI

125

MICROSCOPE128

GEO/SED TEACH.LAB124

PREP121

HOUSING120B

WASH120C

ELEVE1

CORRIDORC1-5

CORRIDORC1-7

CORRIDORC1-6

SHOWER108

PREP123

STAIR 2-1S1N

STAIR 1-1S1W

OUTDOORSUPPORT

OS

FOYERC1-4

FOYERC1-1

CORRIDORC1-3

LOBBYC1-2

5" N

G

5" NGRISER

GEO SEDRESEARCH LAB

126

12

3

11

1

1

1

2" NG2" CA

2" N

G

4

2" NG

3/4" NG

1" N

G

1 1/

2" N

G

1 1/2" NG

2" C

A

5

5

1" VAC

2" V

AC

6

Y1

Y2

1

1/2" NG1" VAC

7

7

7

8.5

E

3/4"

VAC

2" N UP

3/4"

NG

3/4"

VAC

2" VAC2" NG

2" VAC 2" VAC

3/4" VAC3/4" NG

5 5

2" V

AC2"

NG

2" N

G2"

VAC

3/4" VAC1" VAC

2" NG2" VAC

2" NG

2" CARISER

NATURAL GAS SERVICEENTRANCE. SEE DETAIL.

COORDINATE EXACT LOCATIONWITH OWNER'S CONTRACTOR.

U/G NATURAL GAS PIPING BY OTHERS.

2"VACRISER

FIRE PUMPM2

TERMINATE VENTING FORUNDERGROUND GAS PIPING

CASING AT EXTERIORLOCATION INDICATED.

COORDINATE LOCATIONWITH HVAC PIPING

8

CERTI F IC

AT E O F A U THO

RIZAT

ION

SOUTH CAROLINA

CONSULTINGENGINEERS

DWG, INC.

No.C03649

CHECKED BY:

DRAWN BY:

DATE:

PROJECT:

MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS

1

A

2 3 4 5 6

B

C

D

E

WWW.LS3P.COMTEL. 843.577.4444 FAX 843.722.4789205 1/2 KING ST. CHARLESTON SC 29401

STATE PROJECT NO:H17-9588-FW

REVISIONS:

COPYRIGHT 2014 ALL RIGHTS RESERVEDPRINTED OR ELECTRONIC DRAWINGS ANDDOCUMENTATION MAY NOT BE REPRODUCEDIN ANY FORM WITHOUT WRITTEN PERMISSIONFROM LS3P ASSOCIATES LTD.

E

G

No.

L

TU

DS

IC

AH

ISM

RE

TE

K

EG. W

ES

AA

17759

RE

GE

ER

INEN

L

RCAHORP

SEFOLN

S IOINO

5/19

/201

4 2:

51:1

1 PM

C:\U

sers

\km

inog

ue\D

ocum

ents

\120

96_C

CU

Sci

ence

Ann

ex II

Pha

se O

ne_2

013_

kmin

ogue

.rvt

LS3P: 1202-122370

MAY 20, 2014

KMM

MGW

PLUMBING FIRSTFLOOR GAS PLAN

P121

BID SET

SCIENCE ANNEX IICONSTRUCTION

SCALE: 1/8" = 1'-0"P1211 FIRST FLOOR GAS PLAN

EMERGENCY SHUTOFF BUTTON SHALL CLOSE GAS SOLENOID VALVE UPONACTIVIATION. COORDINATE WITH SHUNT TRIP REQUIREMENTS AND ELECTRICALDOCUMENTS. INSTALL GAS SOLENOID VALVE AND MANUAL SHUTOFF VALVE ABOVEACCESSIBLE CEILING ON CORRIDOR SIDE OF DOOR.

PROVIDE SHUTOFF VALVE IN ACCESSIBLE LOCATION ABOVE CEILING.

PROVIDE CASING FOR UNDERGROUND GAS PIPING. SEE DETAIL.

COORDINATE CONNECTION TO EQUIPMENT WITH OWNER.

PROVIDE 1" PIPING TO GAS TURRET AT TABLE. SEE ISOMETRIC VIEW FORUNDERGROUND NATURAL GAS PIPING FOR THIS ROOM.

PROVIDE NITROGEN GAS MANIFOLD AND HEADER BAR WITH REGULATOR.BASIS OF DESIGN (OR EQUAL):AMICO M3A-DL-HH-U-NITAMICO M2-HBXS-08L-NIT

3/4" VACUUM PIPING TO PANEL MOUNT OUTLET. THIS CONTRACTOR SHALL MAKEFINAL CONNECTION. COORDINATE EXACT LOCATION WITH LAB EQUIPMENTSUPPLIER.

PROVIDE DRAIN AT BASE OF VACUUM RISER. DRAIN SHALL BE 2" DIAMETER FOR 3'LENGTH BELOW HORIZONTAL CONNECTION TO RISER BEFORE INSTALLATION OFBALL VALVE. PIPING DOWNSTREAM OF BALL VALVE SHALL BE 3/4" DIAMETER. PIPE TONEAREST FLOOR DRAIN.

1

2

3

4

5

6

GENERAL NOTES:1. ALL PIPING SHALL BE CONCEALED ABOVE FIRST FLOOR CEILING, UNO.2. MAKE FINAL CONNECTIONS TO LAB GAS PIPING FROM FUME HOODS ABOVE

CEILING. PIPING CONNECTION SIZE SHALL BE AS FOLLOWS:NATURAL GAS: 1/2"VACUUM: 3/4"COMPRESSED AIR: 1/2"NITROGEN: 1/2"

3. PROVIDE 1/8" PER FOOT MINIMUM SLOPE FOR ALL VACUUM PIPING.PROVIDE DRIP LEG WITH REMOVABLE CAP AT ALL LOW POINTS IN PIPING.

7

KEY NOTES:

8

No. Description Date

Page 10: s SOLENOID VALVE - Coastal Carolina University · PDF filecu condensing unit hd hub drain mc ... kmm mgw plumbing notes & legend p000 bid set science annex ii construction ... bio

UP

11109

8765432

1A

B

C

D

F

G

H

X5X3X2

OFF-1241

OFF-13228

OFF-12229

OFF-9232

OFF-7233

OFF-6235

OFF-5236

OFF-4237

OFF-3238

ELEVE2

OFF-8234

OFF-20242

ELEC.240

OFF-10231

OFF-11230

OFF-15227

DATA239

OFF-17224

OFF-14226

OFF-16225

GRAD BULLPEN246

GIS247COMP MODEL

248

COMPUTERSERVER

250

PHYS OCEAN255

OFFICE254

OFFICE253

LOW SVC TEACHLAB252

PREP251

LOW SVC TEACHLAB249

LOW SVC TEACHLAB245

PREP244

LOW SVC TEACHLAB243

ADMIN-1222 OFF-18

219

FILE / WORK / BRK217

F. TLT.201

OFF-19218

OFF-1216

OFF-2215

OFF-3214

OFF-5212

OFF-4213

OFF-6211

OFF-7210

OFF-8209

OFF-9208

LECTURECLASSROOM

207

GRAD STD206

LECTURECLASSROOM

205

LECTURECLASSROOM

204

SEMINAR203

M. TLT202

JAN223

STAIR 3S3-2

LG CONF RM220

CORRIDORC2-3

CORRIDORC2-5

STAIR 1-2S2W

STAIR 2-2S2N

CORRIDORC2-4

PLOT256

CORRIDORC2-1

CORRIDORC2-2

2" CARISER

1 11 1

1

1

2

2

2

222

3/4" NG

3/4"

NG

3/4" NG2" NG2" NG2" NG2" NG

3/4" VAC1/2" NG

3/4"

VAC

3/4"

NG

3/4"

NG

1/2"

NG

3/4"

VAC

3/4"

VAC

1/2"

NG

2" VAC2" VAC 2" VAC 2" VAC

3/4" VAC

3/4"

VAC

Y1

Y2

1/2" NG3/4" VAC

1/2"

NG

3/4"

VAC

3/4"

VAC

1/2"

NG

8.5

E

2" N FROM 1STFLR TO 3RD FLR

2" VAC2" NG

1" VAC

CONNECT TO2" VAC RISER

CONNECTTO 5" NG

RISER

3/4" VAC

CERTI F IC

AT E O F A U THO

RIZAT

ION

SOUTH CAROLINA

CONSULTINGENGINEERS

DWG, INC.

No.C03649

CHECKED BY:

DRAWN BY:

DATE:

PROJECT:

MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS

1

A

2 3 4 5 6

B

C

D

E

WWW.LS3P.COMTEL. 843.577.4444 FAX 843.722.4789205 1/2 KING ST. CHARLESTON SC 29401

STATE PROJECT NO:H17-9588-FW

REVISIONS:

COPYRIGHT 2014 ALL RIGHTS RESERVEDPRINTED OR ELECTRONIC DRAWINGS ANDDOCUMENTATION MAY NOT BE REPRODUCEDIN ANY FORM WITHOUT WRITTEN PERMISSIONFROM LS3P ASSOCIATES LTD.

E

G

No.

L

TU

DS

IC

AH

ISM

RE

TE

K

EG. W

ES

AA

17759

RE

GE

ER

INEN

L

RCAHORP

SEFOLN

S IOINO

5/19

/201

4 2:

51:2

4 PM

C:\U

sers

\km

inog

ue\D

ocum

ents

\120

96_C

CU

Sci

ence

Ann

ex II

Pha

se O

ne_2

013_

kmin

ogue

.rvt

LS3P: 1202-122370

MAY 20, 2014

KMM

MGW

PLUMBINGSECOND FLOORGAS PLAN

P122

BID SET

SCIENCE ANNEX IICONSTRUCTION

SCALE: 1/8" = 1'-0"P1221 SECOND FLOOR GAS PLAN

EMERGENCY SHUTOFF BUTTON SHALL CLOSE GAS SOLENOID VALVE UPONACTIVIATION. COORDINATE WITH SHUNT TRIP REQUIREMENTS AND ELECTRICALDOCUMENTS. INSTALL GAS SOLENOID VALVE AND MANUAL SHUTOFF VALVE ABOVEACCESSIBLE CEILING ON CORRIDOR SIDE OF DOOR.

ROUTE PIPING FOR GAS OUTLET AT INSTRUCTOR'S TABLE BELOW FLOOR.COORDINATE STUB UP LOCATION WITH LAB EQUIPMENT SUPPLIER. MAKE FINALCONNECTION TO GAS OUTLET.

1

2

GENERAL NOTES:KEY NOTES:1. ALL PIPING SHALL BE CONCEALED ABOVE FIRST FLOOR CEILING, UNO.2. MAKE FINAL CONNECTIONS TO LAB GAS PIPING FROM FUME HOODS

ABOVE CEILING. PIPING CONNECTION SIZE SHALL BE AS FOLLOWS:NATURAL GAS: 1/2"VACUUM: 3/4"COMPRESSED AIR: 1/2"NITROGEN: 1/2"

3. PROVIDE 1/8" PER FOOT MINIMUM SLOPE FOR ALL VACUUM PIPING.PROVIDE DRIP LEG WITH REMOVABLE CAP AT ALL LOW POINTS IN PIPING.

No. Description Date

Page 11: s SOLENOID VALVE - Coastal Carolina University · PDF filecu condensing unit hd hub drain mc ... kmm mgw plumbing notes & legend p000 bid set science annex ii construction ... bio

DN

11109

87654321A

B

C

D

F

G

H

X5X3X2

ORG CHEM306

A & P TEACHING305

PREP307

ORG CHEM308

PREP304

A&P TEACHING303

M. TLT.310

OFF-19314

OFF-18313

OFF-17312

OFF-16311

F. TLT.302

SECURE FILE301A

OFF-12301B

OFF-11301C

OFF-10301D

OFF-14301Q

DATA316

ELEC317

OFFICE301L

OFF-15301P

CHEM STOR318

OFF-6301H

OFF-5301I

OFF-4301J

OFF-3301K

OFF-2301M

MS M. CHEM.RESEARCH 1

326

MARINE CHEMTEACH LAB

320

MS CHEM INSTR.321

CHEM WET328

PREP329

CHEM. BAL.328B

ADV. CHEM TEACH.330

ROOF TERRACE332

GEN CHEM327

ASTRON. STOR.331

GEN CHEM322

PREP323

MS M CHEMRESEARCH

319A

BALCONY315

OFF-9301E

CORRIDORC3-1

CORRIDORC3-3

CORRIDORC3-2

CORRIDORC3-5

STAIR 2-3S3N

STAIR 1-3S3W

STAIR 3S3-3

ALT TREAD STAIR309

ELEVE3

ROOF ACCESS324

CORRIDORC3-4

CLEAN ROOM319B

OFF-8301F

OFF-7301G

JAN325

MSCI PREP320A

CONNECTTO 5" NG

RISER

2

2

2

1/2" NG

1/2" NG

1/2" NG

1

1

1

1

1

1

3/4" NG

3/4" CA

3/4" NG1" VAC3/4" CA

2" VAC 1" NG

1" NG

2" VAC

1" N1" NG

1

3/4" VAC

1" NG

1" NG

1" VAC

1-1/2"CAMANIFOLD

2" CA2" N

2" NG 2" NG2" CA

2" N

2" NG2" CA

2" NG2" CA2" N

2" NG2" CA

2" N

2" NG2" CA

2" N

1/2" NG3/4" VAC

3/4" VAC1/2" NG

3/4" VAC1/2" NG1/2" NG

1" NG

3/4" NG

1" VAC

3/4"

NG

3/4" VAC1/2" NG

1/2"

NG

3/4"

VAC

2" NG

2" N

G2"

CA

2" N

G2"

NG

4

4

2" C

A

4

4

4

41" NG

1" VAC

1" VAC1" NG

2" NG

1/2" NG

3/4" VAC

1" NG1" VAC

P4013

Y1

Y2

3/4" VAC

3/4" VAC

2" NG

3/4"

NG

1" V

AC1/

2" C

A1/

2" N

3

1" VAC1" CA

2" C

A

8.5

1

1

5

1" NG1" N

1" VAC1" CA

3/4" CA3/4" VAC1/2" N1/2" NG

E

1/2" NG1/2" N3/4" VAC1/2" CA

1/2" CA3/4" VAC

1/2" N1/2" NG

1/2" CA3/4" VAC

1/2" NG1/2" N

1/2" NG1/2" N3/4" VAC3/4" CA

1/2" CA3/4" VAC1/2" N1/2" NG

1/2" CA3/4" VAC1/2" N1/2" NG

DN INWALL

2" N

3/4" VAC

P4012

2" N DNIN WALL

1" N

2" CACONNECTTO 2" CARISER

2" VAC

2" VAC

2" V

AC2"

VAC

2" V

AC

2" VAC

2" CA

2" VAC

1" N

G1"

VAC

2" VAC 2" VAC

1" V

AC

1" N

G1"

VAC

CONNECTTO 2" VACRISER

2" VAC

ADMIN301

2" VAC

2" NG

1" VAC

2" VAC

1 1/2" CA

2" N

G

2" N

G

CERTI F IC

AT E O F A U THO

RIZAT

ION

SOUTH CAROLINA

CONSULTINGENGINEERS

DWG, INC.

No.C03649

CHECKED BY:

DRAWN BY:

DATE:

PROJECT:

MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS

1

A

2 3 4 5 6

B

C

D

E

WWW.LS3P.COMTEL. 843.577.4444 FAX 843.722.4789205 1/2 KING ST. CHARLESTON SC 29401

STATE PROJECT NO:H17-9588-FW

REVISIONS:

COPYRIGHT 2014 ALL RIGHTS RESERVEDPRINTED OR ELECTRONIC DRAWINGS ANDDOCUMENTATION MAY NOT BE REPRODUCEDIN ANY FORM WITHOUT WRITTEN PERMISSIONFROM LS3P ASSOCIATES LTD.

E

G

No.

L

TU

DS

IC

AH

ISM

RE

TE

K

EG. W

ES

AA

17759

RE

GE

ER

INEN

L

RCAHORP

SEFOLN

S IOINO

5/19

/201

4 2:

51:4

7 PM

C:\U

sers

\km

inog

ue\D

ocum

ents

\120

96_C

CU

Sci

ence

Ann

ex II

Pha

se O

ne_2

013_

kmin

ogue

.rvt

LS3P: 1202-122370

MAY 20, 2014

KMM

MGW

PLUMBING THIRDFLOOR GAS PLAN

P123

BID SET

SCIENCE ANNEX IICONSTRUCTION

SCALE: 1/8" = 1'-0"P1231 THIRD FLOOR GAS PLAN

EMERGENCY SHUTOFF BUTTON SHALL CLOSE GAS SOLENOID VALVE UPONACTIVATION. COORDINATE WITH SHUNT TRIP REQUIREMENTS AND ELECTRICALDOCUMENTS. INSTALL GAS SOLENOID VALVE AND MANUAL SHUTOFF VALVEABOVE ACCESSIBLE CEILING ON CORRIDOR SIDE OF DOOR.

PROVIDE SHUTOFF VALVE IN READILY ACCESSIBLE LOCATION.

ROUTE PIPING BELOW SLAB. COORDINATE NUMBER AND LOCATION OF GASOUTLETS WITH LAB EQUIPMENT SUPPLIER.

ROUTE PIPING FOR NG AND VAC OUTLETS AT INSTRUCTOR'S TABLE BELOWFLOOR. COORDINATE STUB UP LOCATIONS WITH LAB EQUIPMENT SUPPLIER. MAKEFINAL CONNECTION TO GAS OUTLETS.

MAKE FINAL CONNECTION TO OUTLET PROVIDED BY LAB EQUIPMENT SUPPLIER.

1

2

3

4

GENERAL NOTES:

5

KEY NOTES:1. ALL PIPING SHALL BE CONCEALED ABOVE CEILING, UNO.2. MAKE FINAL CONNECTIONS TO LAB GAS PIPING FROM FUME HOODS ABOVE

CEILING. PIPING CONNECTION SIZE SHALL BE AS FOLLOWS:NATURAL GAS: 1/2"VACUUM: 3/4"COMPRESSED AIR: 1/2"NITROGEN: 1/2"

3. PROVIDE 1/8" PER FOOT MINIMUM SLOPE FOR ALL VACUUM PIPING.PROVIDE DRIP LEG WITH REMOVABLE CAP AT ALL LOW POINTS IN PIPING.

No. Description Date

Page 12: s SOLENOID VALVE - Coastal Carolina University · PDF filecu condensing unit hd hub drain mc ... kmm mgw plumbing notes & legend p000 bid set science annex ii construction ... bio

F

PLUMBING AND MECHANICAL PIPINGSHALL SUPPORTED ON SINGLETRAPEZE HANGER SIZED FOR ALLPIPING IN THIS AREA. LOCATIONSTYPICAL OF ALL CORRIDORS.

STRUCTURAL BEAM AT THIS LOCATION.

SHUTOFF VALVES SHALLBE LOCATED AT ANACCESSIBLE LOCATIONAS LOW AS POSSIBLEABOVE CEILING.

DUCTWORK SHOWNFOR REFERENCE.LOCATIONS TYPICAL OFALL CORRIDORS.

CABLE TRAY SHOWNFOR REFERENCE.LOCATION TYPICALOF ALL CORRIDORS.

CERTI F IC

AT E O F A U THO

RIZAT

ION

SOUTH CAROLINA

CONSULTINGENGINEERS

DWG, INC.

No.C03649

CHECKED BY:

DRAWN BY:

DATE:

PROJECT:

MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS

1

A

2 3 4 5 6

B

C

D

E

WWW.LS3P.COMTEL. 843.577.4444 FAX 843.722.4789205 1/2 KING ST. CHARLESTON SC 29401

STATE PROJECT NO:H17-9588-FW

REVISIONS:

COPYRIGHT 2014 ALL RIGHTS RESERVEDPRINTED OR ELECTRONIC DRAWINGS ANDDOCUMENTATION MAY NOT BE REPRODUCEDIN ANY FORM WITHOUT WRITTEN PERMISSIONFROM LS3P ASSOCIATES LTD.

E

G

No.

L

TU

DS

IC

AH

ISM

RE

TE

K

EG. W

ES

AA

17759

RE

GE

ER

INEN

L

RCAHORP

SEFOLN

S IOINO

5/19

/201

4 2:

52:2

0 PM

C:\U

sers

\km

inog

ue\D

ocum

ents

\120

96_C

CU

Sci

ence

Ann

ex II

Pha

se O

ne_2

013_

kmin

ogue

.rvt

LS3P: 1202-122370

MAY 20, 2014

KMM

MGW

PLUMBINGSECTIONS &ISOMETRICS

P301

BID SET

SCIENCE ANNEX IICONSTRUCTION

SCALE: NOT TO SCALEP3011 PIPING AT CORRIDOR SECTION

SCALE:P3012 ACID WASTE & VENT ISOMETRIC VIEW

SCALE:P3013 SANITARY WASTE & VENT ISO VIEW

NOT TO SCALE

NOT TO SCALE

No. Description Date

Page 13: s SOLENOID VALVE - Coastal Carolina University · PDF filecu condensing unit hd hub drain mc ... kmm mgw plumbing notes & legend p000 bid set science annex ii construction ... bio

98

B

C

D

X2

Y1

1

1

2" NG2" VAC

2" NG2" VAC

2" CA2" NG2" VAC

2" CA2" NG2" VAC

2" CA2" NG2" VAC

2" CA2" NG2" VAC

2" NG2" VAC

1/2" NG

3/4" VAC

2" VAC2" NG2" CA

2" V

AC2"

NG

2" C

A

2" N

G2"

CA

2" V

AC

2" V

AC2"

NG

2" C

A

2" V

AC2"

NG

2" C

A

2" V

AC2"

NG

2" C

A

2" CA

3/4" NG

1" VAC

2" V

AC2"

NG

2" C

A

2" V

AC2"

NG

2" C

A

2" V

AC2"

NG

2" C

A

2" V

AC

2" N

G2"

CA

2" CA

2" NG

2" VAC

2" VAC2" NG2" CA

2" VAC2" NG

2" CA

1" CA

2" V

AC2"

NG

2" C

A

2" C

A

2" N

G2"

VAC

2" C

A2"

NG

2" V

AC

2" C

A2"

NG

2" V

AC

2" C

A2"

NG

2" V

AC

2" CA2" NG

2" C

A 2" N

G

2" V

AC

2" C

A2"

NG

2" V

AC

2" C

A2"

NG

2" V

AC

2" C

A2"

NG

2" V

AC

2" CA2" NG2" VAC

2" CA2" NG

2" VAC

2" NG2" VAC

2" VAC2" NG2" CA 2"

VAC

2" N

G2"

CA

2" VAC

2" NG

2" CA

2" V

AC

2" V

AC

2" V

AC

2" CA

2" V

AC

2" V

AC

2" V

AC

2" NG2" VAC

1/2" CA

1/2" N

2

2

3

3

EXTEND CASING TOEXTERIOR ANDPROVIDE VENT

SEE PLAN FORCONTINUATION

DN IN WALL

SEE PLAN FORCONTINUATION

CONNECT TO GASTURRET PROVIDED BYLAB EQUIPMENTSUPPLIER (TYP.)

SHUTOFF VALVES A/C

4

G

1" VAC3/4" NG3/4" CA3/4" N

3/4" VAC 3/4" VAC

1/2"

NG

1/2"

CA

1/2"

N1/

2" N

1/2"

CA

1/2"

NG

3/4"

VAC

3/4"

VAC

1/2"

NG

1/2"

CA

1/2"

N1/

2" N

1/2"

CA

1/2"

NG

3/4" N3/4" CA3/4" NG1" VAC3/

4" N

3/4"

CA

3/4"

NG

SEE THIRD FLOORGAS PLAN FORCONTINUATION

1" V

AC

2

CERTI F IC

AT E O F A U THO

RIZAT

ION

SOUTH CAROLINA

CONSULTINGENGINEERS

DWG, INC.

No.C03649

CHECKED BY:

DRAWN BY:

DATE:

PROJECT:

MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS

1

A

2 3 4 5 6

B

C

D

E

WWW.LS3P.COMTEL. 843.577.4444 FAX 843.722.4789205 1/2 KING ST. CHARLESTON SC 29401

STATE PROJECT NO:H17-9588-FW

REVISIONS:

COPYRIGHT 2014 ALL RIGHTS RESERVEDPRINTED OR ELECTRONIC DRAWINGS ANDDOCUMENTATION MAY NOT BE REPRODUCEDIN ANY FORM WITHOUT WRITTEN PERMISSIONFROM LS3P ASSOCIATES LTD.

E

G

No.

L

TU

DS

IC

AH

ISM

RE

TE

K

EG. W

ES

AA

17759

RE

GE

ER

INEN

L

RCAHORP

SEFOLN

S IOINO

5/19

/201

4 2:

52:3

3 PM

C:\U

sers

\km

inog

ue\D

ocum

ents

\120

96_C

CU

Sci

ence

Ann

ex II

Pha

se O

ne_2

013_

kmin

ogue

.rvt

LS3P: 1202-122370

MAY 20, 2014

KMM

MGW

PLUMBINGENLARGED PLANS

P401

BID SET

SCIENCE ANNEX IICONSTRUCTION

SCALE: 1/4" = 1'-0"P4013 ORG CHEM 306 & 308 ENLARGED GAS PLAN

ROUTE PIPING FOR NG & VAC OUTLETS AT INSTRUCTOR'S TABLE BELOW FLOOR.COORDINATE STUB UP LOCATIONS WITH LAB EQUIPMENT SUPPLIER. MAKE FINALCONNECTIONS TO GAS OUTLETS.

LAB GAS MANUAL SHUTOFF VALVE A/C IN ACCESSIBLE LOCATION.

EMERGENCY SHUTOFF BUTTON SHALL CLOSE GAS SOLENOID VALVE UPONACTIVATION. COORDINATE WITH SHUNT TRIP REQUIREMENTS AND ELECTRICALDOCUMENTS. INSTALL GAS SOLENOID VALVE AND MANUAL SHUTOFF VALVE ABOVEACCESSIBLE CEILING ON CORRIDOR SIDE OF DOOR.

1

GENERAL NOTES:KEY NOTES:

SCALE:P4011 LOW SVC. TEACH LAB - MSCI 125 NATURAL GAS ISOMETRIC

NOT TO SCALE

SCALE: 1/4" = 1'-0"P4012 PREP 329 ENLARGED GAS PLAN

1. ALL PIPING SHALL BE CONCEALED, UNO.2. MAKE FINAL CONNECTIONS TO LAB GAS PIPING FROM FUME HOODS ABOVE

CEILING. PIPING CONNECTION SIZE SHALL BE AS FOLLOWS:NATURAL GAS: 1/2"VACUUM: 3/4"COMPRESSED AIR: 1/2"NITROGEN: 1/2"

SEE THIRD FLOORGAS PLAN FORCONTINUATION

SEE THIRD FLOORGAS PLAN FORCONTINUATION

SEE THIRD FLOORGAS PLAN FORCONTINUATION

1

2

3

No. Description Date

Page 14: s SOLENOID VALVE - Coastal Carolina University · PDF filecu condensing unit hd hub drain mc ... kmm mgw plumbing notes & legend p000 bid set science annex ii construction ... bio

10

X3 LAV-1(TYP)

WC-AWC UR UR-A

2" PC3/4" PH

2" PC 3/4" PC

2" PC1/2" PH3/4" PC

3/4" PC

BRS

LAV-1(TYP)

2" P

C 3/4"

PH

2 1/2" PC

2 1/2" PC 1" PH

3/4" PH3/4" PH

HB

WC-AWCWCWC

EWC

3/4" PC2 1/2" PC

2 1/2" PC

2" PC 2" PC

2" P

C

F. TLT.110

M. TLT.109

Y1

E

HB

10

9

X3

Y1

E

2" P

C

3/4"

PH

R3/

4" P

H

2" PC

3/4" PH

3/4" PHR

3/4" PC3/4" PH

1 1/

2" P

C

1/2"

PC

2" P

C

3/4" PHR

2" PH

2 1/2" PC

1" P

H

HB

WC-A WC

UR UR-A

LAV-1(TYP.)

M. TLT202

F. TLT.201

3/4" PC

1 1/2" PC

HB

BRS

LAV-1(TYP.)

WC-A

WCWCWC

3/4" PH

3/4"

PC

2" PC

2" PC

2" P

C

10

9

X3

Y1

E2" P

C

2" P

C3/

4" P

H3/

4" P

HR

3/4" PH

2" PC

3/4" PC

2" PC

2 1/2" PC

1 1/2" PH

3/4" PHR 1" PH

2" P

C

2" P

C

2" PC

3/4" PC1/

2" P

C

1/2"

PC

1/2" PH

LAV-1(TYP.)

WC-AWC

URUR-A

2" PC

TP

TP

HB

LAV-1(TYP.)

WC-AWC

WCWC

HB

1 1/2" PC

3/4" PC

8

H

X5 8.5

MECH.M1

FIRE PUMPM2

1/2" PHR

1 1/4" PH

2 1/2" PC

1M: 7,9,11

2" PWS

3/4" NPC

2" PWS

1/2" PC

3/4" NPHR

2" NPH

2" NPC

2

PROVIDE BACKFLOW PREVENTERS FOR1-1/2" HVAC MAKE-UP WATER, 4" NON-POTABLE LAB WATER, AND 4" POTABLEDOMESTIC WATER IN HEADERCONFIGURATION AT THIS LOCATION.SEE DETAIL.

2" PWS, 2" PWR, 4" PC, 1-1/2" PH, 3/4"PHR, 4"NPC, 2-

1/2"NPH, & 3/4"NPHRRISERS AND 1-1/2"HVAC

MAKEUP WATER.

CONNECT TORISER

CONNECTTO RISER

PROVIDE VALVE AT PWS DROP ANDMAKE FINAL CONNECTION TO PURIFIEDWATER OUTLET. SEE DETAIL.

SK1

WDBP-1,2

SEE WATER DISTRIBUTIONBOOSTER PUMP DETAIL

FOR CONTINUATION.

8

F

G

X3

Y2

1 1/2" NPC2" VAC2" CA

5" NG2" PWS3/4" NPC3/4" NPH

2" PWR

WH-3NPWH-2NPWH-1P

FD-1FD-2

FD-2

FD-1

FD-2

FD-2

3"AVTR

CONNECT TO AIRCOMPRESSOR. SEE DETAIL

FOR PIPING CONTINUATION.

1-1/2" NPC FORHVAC, WITHVALVE ANDCAPPED. SEEMECH. FOR MOREINFORMATION.

CONNECT TO VACUUMPUMP. SEE DETAIL FORPIPING CONTINUATION.

SEE PURIFIEDWATER SYSTEMPIPING SCHEMATICFOR CONTINUATION

3"AVTR

TP

RECEIVER TANK FORCOMPRESSED AIR

SYSTEM. SEE DETAIL.

3/4" NPHR

1 1/2" NPC

2 1/2" NPH

3/4" PHR

1 1/2" PC

1 1/2" PH

FD-1

FD-1

5" NG5" NG5" NG 5" NG5" NG

EXPANSION TANK FORNON-POTABLE WATERSYSTEM

EXPANSION TANK FORPOTABLE WATER

SYSTEM

SEE DETAILS FORPIPING CONTINUATION

2"PWS, 2" PWR, 5" NG, 4" PC, 1-1/2" PH, 3/4"PHR, 4"NPC, 2-

1/2"NPH, & 3/4"NPHR RISERS AND1-1/2"HVAC MAKEUP WATER

V-1

AC-1

TP

TP

FD-2

4" W

4" W

4" W

3" V

4"W DN4" W

3"VTR

4" W

4" W

4"W DN

4" W

4" W

3"VCONNECTION

4" VENT AND AIRINTAKE FOR WATERHEATER. TERMINATEWITH CONCENTRICVENT KIT.

3" VAC VENT

3"VAC VENTTHROUGH ROOF

3"V PIPING AT12'-6" AFF MIN.

CERTI F IC

AT E O F A U THO

RIZAT

ION

SOUTH CAROLINA

CONSULTINGENGINEERS

DWG, INC.

No.C03649

CHECKED BY:

DRAWN BY:

DATE:

PROJECT:

MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS

1

A

2 3 4 5 6

B

C

D

E

WWW.LS3P.COMTEL. 843.577.4444 FAX 843.722.4789205 1/2 KING ST. CHARLESTON SC 29401

STATE PROJECT NO:H17-9588-FW

REVISIONS:

COPYRIGHT 2014 ALL RIGHTS RESERVEDPRINTED OR ELECTRONIC DRAWINGS ANDDOCUMENTATION MAY NOT BE REPRODUCEDIN ANY FORM WITHOUT WRITTEN PERMISSIONFROM LS3P ASSOCIATES LTD.

E

G

No.

L

TU

DS

IC

AH

ISM

RE

TE

K

EG. W

ES

AA

17759

RE

GE

ER

INEN

L

RCAHORP

SEFOLN

S IOINO

5/19

/201

4 2:

52:5

5 PM

C:\U

sers

\km

inog

ue\D

ocum

ents

\120

96_C

CU

Sci

ence

Ann

ex II

Pha

se O

ne_2

013_

kmin

ogue

.rvt

LS3P: 1202-122370

MAY 20, 2014

KMM

MGW

PLUMBINGENLARGED PLANS

P402

BID SET

SCIENCE ANNEX IICONSTRUCTION

SCALE: 1/4" = 1'-0"P4021 FIRST FLOOR RESTROOM ENLARGED DOMESTIC WATER PLAN

SCALE: 1/4" = 1'-0"P4022 SECOND FLOOR RESTROOM ENLARGED DOMESTIC WATER PLAN

SCALE: 1/4" = 1'-0"P4024 THIRD FLOOR RESTROOM ENLARGED DOMESTIC WATER PLAN

SCALE: 1/4" = 1'-0"P4023 MECH M1 & FIRE PUMP M2 ENLARGED WATER PIPING PLAN

SCALE: 1/4" = 1'-0"P4025 ENGLARGED MECHANICAL SPACE PIPING & EQUIPMENT PLAN

No. Description Date

Page 15: s SOLENOID VALVE - Coastal Carolina University · PDF filecu condensing unit hd hub drain mc ... kmm mgw plumbing notes & legend p000 bid set science annex ii construction ... bio

3RDFLOOR

2RDFLOOR

1RDFLOOR

CONTROL VALVE

CONTROL VALVE

CONTROL VALVE

POUDROP

POUDROP

POUDROP

FLOWMETER

PWR

RIS

ER

PWS

RIS

ER

1. AT EACH DROP, REDUCE TO 1/2" PP VALVE INCLUDE A1/2" FPT ADAPTER ON OUTLET OF VALVE FOR CONNECTIONTO FAUCET.2. FOR SERVICE OF ONE FLOOR, CLOSE BOTH CONTROLVALVES.

NOTES

PWS

PWS

PWR

PWR

PWS

PWS

PWS

PWR

PWR

PWR

FLOWMETER

FLOWMETER

CONTROL VALVE

CONTROL VALVE

CONTROL VALVE

NOTE: PIPING SHALL BE CONCEALED IN WALL CAVITY.

CEILING

WALL FACE

FRONTVIEW

COUNTER TOP

ORIENT SUCH THAT VALVE ISINSTALLED HORIZONTALLY,EXPOSED IN LOWER CABINET. MAKEFINAL CONNECTION TO FIXTUREREQUIRING PURIFIED WATER.

LEGEND GM

PIPE PRESSURE SWITCHP

LAB

GAS

SU

PPLY

MANIFOLD, MONITORING OFINTERNAL PRESSURETRANSDUCERS AND RESERVETANK SWITCHOVER (TYPICALFOR EACH MANIFOLD)

ISOLATION VALVE (TYPICAL)

1 X 1 GAS MANIFOLD, SEE SCHEDULE FOR GAS TYPEGM

MANIFOLD VENT LINE ROUTED TOROOF, INSTALL PER MANUFACTURER'SRECOMMENDATIONS. TURNED DOWNAND SCREENED

CHECK VALVE (TYPICAL)

GAS STORAGE BOTTLESPROVIDED BY OWNERCONTRACTOR INSTALLED

SECURE CYLINDERS INACCORDANCE WITH NFPA(TYP.)

PROVIDE UNISTRUT SUPPORTSWITH PIPE CLAMPS FORMANIFOLD (TYP.)

TRAPEZE HANGER ASSEMBLYNOTES :

PIPE CLAMP, TYP.

HANGER ROD, TYP.

PIPES

1. TYPICAL MOUNTING DETAIL OF PIPING ON TRAPEZEHANGER.

2. REFER TO THE PLANS FOR NUMBER AND SIZE OF PIPES.

3. PROVIDE DIELECTRIC SHIELDS FOR COPPER PIPINGSUPPORTED IN TRAPEZE.

4 SEE SEISMIC NOTES FOR ADDITIONAL BRACINGREQUIREMENTS.

SUPPLY TO FIXTURE

SUPPLY RISER

TYPE "A" WATER HAMMER ARRESTOR(UNO), WATHER HAMMER ARRESTORSCHEDULE. INSTALL AT EACH FIXTURE,HOSE BIB & WATER HEATER ON HOT ANDCOLD WATER PIPING.

CONCRETE SUPPORT

FLOW

18" SQ.x 6" DEEP CONC.PAD. SLOPE TO GRADE

CAST IRON FERRULEW/COUNTER SUNKBRONZE PLUG.

18" MIN.

1"

FIN. GRADE

EXTENSION LENGTHAS REQ'D

FOR CLEANOUT AT END OFLINE, PLUG WYE AT THIS PONT.

NOTES:

AREAS. SIZE AS REQUIRED.

1. PROVIDE DATA SHEETS FOR CAULKING MATERIALS FOR REVIEW. FAILURE TO COMPLY PRIOR TOINSTALLATION OF ANY CAULKING MATERIALS SHALL REQUIRE THE REMOVAL OF ALL PIPE CAULK MATERIALS.2. UL LISTED FIRESTOP PENETRATION ASSEMBLIES:

MASONRY- STEEL: WJ1000 SERIES- UNINSULATED COPPER: WJ1000 SERIES- FIBERGLASS INSULATED COPPER: WJ5000 SERIES- CLOSED CELL FOAM INSULATED COPPER: WJ5000 SERIES

GYPSUM- STEEL: WL1000 SERIES- UNINSULATED COPPER: WL1000 SERIES- FIBERGLASS INSULATED COPPER: WL5000 SERIES- CLOSED CELL FOAM INSULATED COPPER: WL5000 SERIES

PER U.L. 1479 AND ASTMTHICKNESS AND MATERIAL

FIRE SAFING

E814. (TYPICAL)

PROVIDE CAULKING-

MATERIAL

PIPE

BRASS ESCUTCHEON FOR FINISHEDPROVIDE CHROME PLATED CAST

LOCATIONS)DRGS FOR RATINGS ANDRATED WALL (SEE ARCH

INSULATION (AS APPLICABLE). MAINTAINTHROUGH PENETRATION IF INSULATED

SIZE SLEEVE AS REQUIRED TO MAINTAIN THEU.L. LISTING AND IN ACCORDANCE WITHSEALANT MFR REQT'S

TRAP PRIMER

INSTALLATION NOTE:PROVIDE POSITIVE SLOPE TO TRAP CONNECTION.

3/4" STRAINER

COLD WATER LINE

BALL VALVE

FLOOR DRAIN ORHUB DRAIN, SEE PLAN FORFLOOR HUB DRAINQUANTITY

ROUTE TO TRAP PRIMERCONNECTION ON FLOORDRAINS/SINKS

CHECK VALVE

1. FACE OF PRESSURE GAUGES TO BE TURNED SO AS TO BE ABLE TO BE READ STANDING AT FLOOR LEVEL.2. COORDINATE TIMER SETTINGS WITH ON-SITE MAINTENANCE STAFF.3. SET AQUASTAT CONTROL FOR 20°F DROP IN RETURN LINE.

NOTE:

1/2" SHUT-OFF COCK

PRESSURE GAGE

STRAINER

UNION

UNION

PLAN VIEW

TIMER AND AQUASTAT

MOTOR

CP-1,2

REDUCING TEE

1/4" SHUT-OFF COCK

PRESSURE GAGE

SET TO 3.0 GPM.BALANCING VALVE,FLOW METER ANDMANUAL IN-LINE

BALL VALVE

REDUCING TEE

BALL VALVE

COMP.#1

COMP.#2

COMP.#3

COMP.#4

INLET FILTER(INTERNAL)

AIRCOOLEDAFTER

COOLERAIR

COOLEDAFTER

COOLERAIR

COOLEDAFTER

COOLERAIR

COOLEDAFTER

COOLER

CHECK VALVE(TYP.)

SAFETY VALVE(INTERNAL)

PRESSURETRANSDUCER(INTERNAL)

1"

BALL VALVE(TYP.)

SEPERATOR

FLEX HOSE

DESICCANTDRYER

240GALLON

ASMETANK

1" OUTLET. PROVIDEINCREASER TO 2"

DISTRIBUTION PIPING.

1"

P

PRESSUREGAUGE

1/2" DRAIN

115 VOLT ELECTRICAUTO DRAIN

1/2" DRUM

COMPRESSOR ENCLOSURE

NOTES:1. DETAIL INDICATES EQUIPMENT TO BE PROVIDED BY EQUIPMENT MANUFACTURER.

CONTRACTOR SHALL PIPE ALL DRAINS SHOWN TO NEAREST FLOOR DRAIN.2. SEE ELECTRICAL DRAWINGS FOR ELECTRICAL REQUIREMENTS.

1"

CERTI F IC

AT E O F A U THO

RIZAT

ION

SOUTH CAROLINA

CONSULTINGENGINEERS

DWG, INC.

No.C03649

CHECKED BY:

DRAWN BY:

DATE:

PROJECT:

MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS

1

A

2 3 4 5 6

B

C

D

E

WWW.LS3P.COMTEL. 843.577.4444 FAX 843.722.4789205 1/2 KING ST. CHARLESTON SC 29401

STATE PROJECT NO:H17-9588-FW

REVISIONS:

COPYRIGHT 2014 ALL RIGHTS RESERVEDPRINTED OR ELECTRONIC DRAWINGS ANDDOCUMENTATION MAY NOT BE REPRODUCEDIN ANY FORM WITHOUT WRITTEN PERMISSIONFROM LS3P ASSOCIATES LTD.

E

G

No.

L

TU

DS

IC

AH

ISM

RE

TE

K

EG. W

ES

AA

17759

RE

GE

ER

INEN

L

RCAHORP

SEFOLN

S IOINO

5/20

/201

4 4:

00:4

3 PM

C:\U

sers

\km

inog

ue\D

ocum

ents

\120

96_C

CU

Sci

ence

Ann

ex II

Pha

se O

ne_2

013_

kmin

ogue

.rvt

LS3P: 1202-122370

MAY 20, 2014

KMM

MGW

PLUMBINGDETAILS

P501

BID SET

SCIENCE ANNEX IICONSTRUCTION

SCALE: NOT TO SCALEP5012 PWS & PWR RISER SCHEMATIC DIAGRAM

SCALE: NOT TO SCALEP5011 RO/DI WATER PIPING DROPS DETAIL

SCALE: NOT TO SCALEP5013 LAB GAS MANIFOLD DETAIL

SCALE: NOT TO SCALEP5015 PIPE HANGER DETAIL

SCALE: NOT TO SCALEP5016 WATER HAMMER ARRESTOR INSTALLATION DETAIL

SCALE: NOT TO SCALEP5017 GRADE CLEANOUT DETAIL

SCALE: NOT TO SCALEP5018 PIPE THRU RATED ASSEMBLY

SCALE: NOT TO SCALEP5019 TRAP PRIMER DETAIL

SCALE: NOT TO SCALEP50110 IN-LINE CIRCULATING PUMP

SCALE: NOT TO SCALEP5014 AIR COMPRESSOR PIPING SCHEMATIC No. Description Date

Page 16: s SOLENOID VALVE - Coastal Carolina University · PDF filecu condensing unit hd hub drain mc ... kmm mgw plumbing notes & legend p000 bid set science annex ii construction ... bio

TRAP PRIMERCONNECTION PROVIDEPOSITIVE SLOPE

DEEP SEAL P-TRAP

STRAINER SET FLUSHWITH FLOOR. PROVIDESQUARE TOP FOR TILEFLOORS

SLOPED FLOOR SLAB

GAS SUPPLYINTO BUILDING

FROM CAMPUS UNDERGROUNDDISTRIBUTION SYSTEM AT APPROXIMATELY18 PSI. COORDINATE EXACT LOCATION WITHOWNER'S NG CONTRACTOR.

PLUGGED TEE

GAS COCK (TYP.)

INSULATING UNION

GAS PRESSURE REGULATOR SETAT 2 PSI. COORDINATE SIZE OF

PIPING UPSTREAM OF REGULATORWITH OWNER'S NG CONTRACTOR.

FIN. GRADE

EARTHQUAKE VALVE

PROVIDE DRIP LEG WHEREVERPIPING TURNS UP (TYP)

CAP (TYP.)

MANUAL SHUTOFFVALVE

STRAINER CONTRACTORPORTION

OWNERPORTION

GAS METER PROVIDED ANDINSTALLED BY OWNERSCONTROLS CONTRACTOR.

SP-1

(SQUARE)2'-0"

ELEVATORSHAFT FLOOR

2-1/2" WASTE COPPER DISCHARGE

STRUCTURAL DRAWINGSSUMP GRATE - REFER TO

SUMP PIT - REFER TOARCHITECTURAL FORLOCATION

NON-SLAM BRONZE

BALL VALVE

CHECK VALVE

FLOAT SWITCH

ELEVATOR SHAFT WALL2'

-0"

FINISHED FLOOR FINISHED FLOOR

ELEVATOR SHAFT WALL

ROUTE A/C TO MOP SINKLOCATED IN JANITOR'SCLOSET.

ELECTRICAL JUNCTION BOXRE: ELECTRICAL DRAWINGS

ELECTRICAL POWER CORD

MECHANICAL CONTROLS CONTRACTOR TOWIRE ALARM TO CONTROL PANEL FOR DDCMONITORING. REFER TO ELECTRICAL FORALARM/CONTROL PANEL LOCATION. PANEL TOBE LOCATED WITHIN MUDROOM/DOCK 118.

NOTES:1. INSTALL AND PROVIDE ALL PLUMBING AND ELECTRICAL PERPUMP MANUFACTURER'S REQUIRMENTS,

NOTES:

1. DETAIL APPLIES TO BASIS OF DESIGN THERMOSTATIC MIXING VALVE.SUBMIT MANUFACTURER'S INSTALLATION INSTRUCTIONS AND PIPINGMETHOD TO A/E FOR REVIEW.

2. UNIT PIPING SHALL BE INSTALLED IN ACCORDANCE WITHMANUFACTURER'S INSTALLATION INSTRUCTIONS AND PIPING METHODTO ENSURE PROPER HEAT TRAPPING OCCURS.

3. SEE FLOOR PLANS FOR PIPING DIMENSIONS NOT SHOWN.

CP

TMV-1,2TO WATER HEATER

FROM WATER HEATER

CHECK VALVE(TYP.)

HEAT TRAP

THERMOMETER SET MIXINGVALVE DISCHARGE TO 110°F

BALL VALVE(TYP.)

TEMPERED DOMESTIC HOTWATER TO PLUMBING FIXTURES

DOMESTIC COLDWATER SUPPLY

3/4" BYPASS

3/4" DOMESTIC COLDWATER PIPING

CIRCUIT SETTER

IN-LINE CIRCULATINGPUMP. SEE DETAIL.

EXHAUST

COMBUSTION AIR

ROOF

PER MFRSINSTALLMANUAL

COMBUSTION AIREXHAUST

1. SEE ARCHITECTURAL DOCUMENTS FOR ROOF PENETRATION DETAIL.

NOTE:

FLOOR CLEANOUTSINGLE TWO-WAY CLEANOUTWALL CLEAN OUT

OMIT EXTENSIONAT END OF LINE

CLEAN OUT

FINISHED FLOORFINISHED WALL

ACCESS PLATE

CLEAN OUT

CLEAN OUT

FINISHED FLOOR /FINISHED GRADE

FIN. FLR.

HOSE BIBB

SEISMIC CONCRETE PAD.CONTRACTOR SHALL SUBMITSHOP DRAWINGS TO A/E FOR

REVIEW.

BACKFLOW PREVENTER (TYP.).SEE PLAN FOR LOCATION

WATERSERVICE

1" DRAINVALVE

PRESSURE GAUGE(TYP.)

STRAINER

UNION(TYP.)

4" PCFULL PORT BALL VALVENORMALLY CLOSED.WATTS FBV OR EQUAL(TYP.)

BFPCHECK VALVE

(WDBP) PACKAGED BOOSTER PUMPSEE SCHEDULE

ACCUMULATOR TANK

BFP

BFP

4" NPC

1-1/2" NPCTO HVAC

4" DISCHARGE

4" HEADER

SUBMETER PROVIDED ANDINSTALLED BY OWNERS

CONTROLS CONTRACTOR.

36"CEILING

PIPE SUPPORT

3-1/2"

1" IPS X 21"STAINLESS STEEL

NIPPLE

1" IPS BRASS STAY-OPENBALL VALVE WITH 1" NPT

FEMALE UNIONS ON INLETAND OUTLET (FURNISHED BY LAB

EQUIPMENT PROVIDER,INSTALLED BY CONTRACTOR)

31"

STAINLESS STEELDRAIN PAN

STAINLESS STEELCABINET

90°

PROVIDESTAINLESS STEEL

PIPING EXTENSION ASREQUIRED

STAINLESS STEELESCUTCHEON

STAINLESS STEELSHOWER HEAD

20-1/2" TOFINISH FLOOR

NOTES:

15-1/2"18-1/4"

1. EACH SPRAY HEAD HAS AN INTERNAL FLOW CONTROL AND FILTER TOREMOVE IMPURITIES FROM THE WATER FLOW.

2. PROVIDE IN-LINE STRAINER.

3. FIXTURE IN DASHED LINES IS FURNISHED BY LAB EQUIPMENT SUPPLIERAND INSTALLED BY CONTRACTOR. CONTRACTOR SHALL PROVIDE ALLPIPING, TRIM, AND ANY RELATED APPURTENANCES REQUIRED FOR ACOMPLETE INSTALLATION.

EYEWASH DRAIN

GAS LINE

PROVIDE INSECTSCREEN AT END

OF VENT

18" A.F.G.

3" GAS CASINGINSTALLEDBELOW SLAB

SEAL END OF CASING WATER TIGHTWITH BACKING MATERIAL AND SEALANT

1" GOOSE NECK VENT

3"x 1" REDUCER

CERTI F IC

AT E O F A U THO

RIZAT

ION

SOUTH CAROLINA

CONSULTINGENGINEERS

DWG, INC.

No.C03649

CHECKED BY:

DRAWN BY:

DATE:

PROJECT:

MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS

1

A

2 3 4 5 6

B

C

D

E

WWW.LS3P.COMTEL. 843.577.4444 FAX 843.722.4789205 1/2 KING ST. CHARLESTON SC 29401

STATE PROJECT NO:H17-9588-FW

REVISIONS:

COPYRIGHT 2014 ALL RIGHTS RESERVEDPRINTED OR ELECTRONIC DRAWINGS ANDDOCUMENTATION MAY NOT BE REPRODUCEDIN ANY FORM WITHOUT WRITTEN PERMISSIONFROM LS3P ASSOCIATES LTD.

E

G

No.

L

TU

DS

IC

AH

ISM

RE

TE

K

EG. W

ES

AA

17759

RE

GE

ER

INEN

L

RCAHORP

SEFOLN

S IOINO

5/19

/201

4 2:

53:0

4 PM

C:\U

sers

\km

inog

ue\D

ocum

ents

\120

96_C

CU

Sci

ence

Ann

ex II

Pha

se O

ne_2

013_

kmin

ogue

.rvt

LS3P: 1202-122370

MAY 20, 2014

KMM

MGW

PLUMBINGDETAILS

P502

BID SET

SCIENCE ANNEX IICONSTRUCTION

SCALE: NOT TO SCALEP5023 FLOOR DRAIN (FD)SCALE: NOT TO SCALEP502

1 GAS METER DETAIL

SCALE: NOT TO SCALEP5024 ELEVATOR SUMP PUMP DETAIL

SCALE: NOT TO SCALEP5025 THERMOSTATIC MIXING VALVE DETAIL

SCALE: NOT TO SCALEP5026 WATER HEATER VENTING DETAIL

SCALE: NOT TO SCALEP5027 CLEAN OUT INSTALLATION DETAIL

SCALE: NOT TO SCALEP5028 WATER DISTRIBUTION BOOSTER PUMP DETAIL

SCALE: NOT TO SCALEP5029 EMERGENCY EYEWASH/SHOWER INSTALLATION DETAIL

SCALE: NOT TO SCALEP5022 UNDERGROUND GAS LINE CASING

No. Description Date

Page 17: s SOLENOID VALVE - Coastal Carolina University · PDF filecu condensing unit hd hub drain mc ... kmm mgw plumbing notes & legend p000 bid set science annex ii construction ... bio

3/4" NPC BYCONTRACTOR

1"

T P P

TURBIDITY FILTER WATER SOFTENER

P

1"

CARBON FILTERS

P

1"

P

PRE-FILTER5 MICRON

P

P

1/2"

REVERSE OSMOSIS UNIT

P

2" PWR BYCONTRACTOR

STORAGE TANK500 GALLONS

2"

P

P

2"

DISTRIBUTION PUMP30 GPM @ 75 PSI

DISTRIBUTION PUMP30 GPM @ 70 PSI

P

2"

P

2"

POST FILTER0.2 MICRON

MIXED BED DEIONIZERS3.6 CUBIC FEET EACH

P

2" PWS BYCONTRACTOR

THERMOMETER

MIXING VALVE

SAMPLE PORT (TYP.)PRESSURE GAUGE (TYP.)

FLOWMETER

ISOLATION VALVE (TYP.)SERVICE LIGHT (TYP.)

S

SOLENOIDVALVE (TYP.)

CHECK VALVE (TYP.)

ULTRAVIOLETSTERILIZER

3/4" NPH BYCONTRACTOR

CONTRACTOR SHALL PIPE DRAINTO FLOOR DRAIN (TYP.)

BRINE TANK

NOTES:1. DETAIL INDICATES EQUIPMENT TO BE PROVIDED BY EQUIPMENT MANUFACTURER.

CONTRACTOR SHALL PIPE ALL DRAINS SHOWN TO NEAREST FLOOR DRAIN.2. SEE ELECTRICAL DRAWINGS FOR ELECTRICAL REQUIREMENTS.

D

D D

DRAINGALV SHEET METAL

HEATER. PIPE TO DRAIN.DRAIN PAN BELOW VALVE

BASE MOUNTED OR SUSPENDEDEXPANSION TANK, SEE WATERHEATER SCHEDULE FOR MORE

INFORMATION.

UNION (TYP)

STORED

DIELECTRIC

140°

1-1/2"

FLOW

STORED140°

2-1/2"

ROUTE DRAIN LINETO FLOOR DRAIN

ASME T&P VALVE-SET AT 150PSI. PIPE FULL SIZE TO FLOORDRAIN. (TYPE L COPPER) (TYP)

SEE THERMOSTATICMIXING VALVE DETAIL FORCONTINUATION

SEE THERMOSTATICMIXING VALVE DETAIL FORCONTINUATION

2" x 4"PVC BLOCK

4" PVC AIR INTAKE AND COMBUSTIONAIR THROUGH ROOF. TERMINATE

WITH MANUFACTURER'SCONCENTRIC VENT KIT.

WH-2NP WH-3NP

BASE MOUNTED ORSUSPENDED

FLOW

FLOW

DIELECTRICUNION (TYP)

ASME T&P VALVE-SET AT 150PSI. PIPE FULL SIZE TOHUB DRAIN. (TYPE L COPPER)

3/4"

D

DRAINVALVE

D

STORED140°F

10

10

EXPANSION TANK.

SEE FLOORDRAIN DETAIL

ROUTE DRAIN LINETO FLOOR DRAIN

GALV SHEET METAL

HTR. PIPE TO DRAIN.DRAIN PAN BELOW

2" x 4"PVC BLOCK

SEE THERMOSTATICMIXING VALVE DETAIL FORCONTINUATION.

SEE THERMOSTATICMIXING VALVE DETAIL FORCONTINUATION.

4" PVC AIR INTAKE AND COMBUSTIONAIR THROUGH ROOF. TERMINATE

WITH MANUFACTURER'SCONCENTRIC VENT KIT.

WH-1P

120 GALLONRECEIVER

TANK3"

FLEXJOINT

3"

SOURCE VALVE

SIGHTGAUGE

1/4" DRAINVALVE

3" VAC.PUMP

#1

2"

FLEXJOINT AIR

FILTER

2"

DRIP LEG

1-1/2"

FLEXJOINT

CHECK VALVE (TYP.)2"

VAC.PUMP

#2

TSH2

2"

FLEXJOINT AIR

FILTER

2"

DRIP LEG

1-1/2"

FLEXJOINT

1/4"

VACUUMGAUGE0-30" HG

LEADVACUUMSWITCH

LAGVACUUMSWITCH

LOWVACUUMSWITCH

NOTES:1. DETAIL INDICATES EQUIPMENT TO BE PROVIDED BY EQUIPMENT MANUFACTURER.

CONTRACTOR SHALL PIPE ALL DRAINS SHOWN TO NEAREST FLOOR DRAIN.2. SEE ELECTRICAL DRAWINGS FOR ELECTRICAL REQUIREMENTS.

3" VENT. SEE PLAN FORCONTINUATION.

CERTI F IC

AT E O F A U THO

RIZAT

ION

SOUTH CAROLINA

CONSULTINGENGINEERS

DWG, INC.

No.C03649

CHECKED BY:

DRAWN BY:

DATE:

PROJECT:

MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS

1

A

2 3 4 5 6

B

C

D

E

WWW.LS3P.COMTEL. 843.577.4444 FAX 843.722.4789205 1/2 KING ST. CHARLESTON SC 29401

STATE PROJECT NO:H17-9588-FW

REVISIONS:

COPYRIGHT 2014 ALL RIGHTS RESERVEDPRINTED OR ELECTRONIC DRAWINGS ANDDOCUMENTATION MAY NOT BE REPRODUCEDIN ANY FORM WITHOUT WRITTEN PERMISSIONFROM LS3P ASSOCIATES LTD.

E

G

No.

L

TU

DS

IC

AH

ISM

RE

TE

K

EG. W

ES

AA

17759

RE

GE

ER

INEN

L

RCAHORP

SEFOLN

S IOINO

5/20

/201

4 4:

01:1

2 PM

C:\U

sers

\km

inog

ue\D

ocum

ents

\120

96_C

CU

Sci

ence

Ann

ex II

Pha

se O

ne_2

013_

kmin

ogue

.rvt

LS3P: 1202-122370

MAY 20, 2014

KMM

MGW

PLUMBINGDETAILS

P503

BID SET

SCIENCE ANNEX IICONSTRUCTION

SCALE: NOT TO SCALEP5031 PURIFIED WATER SYSTEM PIPING SCHEMATIC

SCALE: NOT TO SCALEP5033 NON-POTABLE WATER HEATER PIPING SCHEMATIC

SCALE: NOT TO SCALEP5034 POTABLE WATER HEATER PIPING SCHEMATIC

SCALE: NOT TO SCALEP5032 VACUUM PUMP DETAIL

No. Description Date

Page 18: s SOLENOID VALVE - Coastal Carolina University · PDF filecu condensing unit hd hub drain mc ... kmm mgw plumbing notes & legend p000 bid set science annex ii construction ... bio

ITEM

WC-A

LAV-1

MOUNTING HEIGHT / REMARKS

18" SEAT HT. / FLOOR MTD., FLUSH VALVE

PLUMBING FIXTURE SCHEDULE

---

1/2"

HOTWATER

1/2" 1-1/4"

3"

COLDWATER WASTE

1-1/2"

2"

VENT (AFF)1-1/2"WATER CLOSET - HDC'P

LAVATORY

FIXTURE TYPE FIXTURE DESCRIPTION

FLOOR MOUNT, FLOOR OUTLET, VITREOUS CHINA, SIPHON JET FLUSHING ACTIONWITH ELONGATED BOWL, 1-1/2" I.P.S. TOP SPUD INLET (DESIGNED FOR A 1.28 GPMFLUSH CYCLE) FLUSH VALVE. THE WATER CLOSET SHALL BE FITTED WITH OPENFRONT SEAT WITHOUT COVER BY CHURCH. OTHER MANUFACTURERS BENKE ORBEMIS.

FIXTURE: SLOAN MODEL NO. WETS. 2020.1201-1.28 SOLIS. OTHER MANUFACTURERSKOHLER OR AMERICAN STANDARD. WATER CLOSET SHALL BE IN COMPLIANCE TOTHE APPLICABLE SECTIONS OF ASME A112.19.2/CSA B45.1. ADA COMPLIANT OPTIMAPLUS BATTERY POWERED INFRARED SENSOR FOR AUTOMATIC NO HANDSOPERATION. FOUR (4) SIZE AA BATTERIES FACTORY INSTALLED, LOW BATTERYFLASHING LED. 1" I.P.S. SCREWDRIVER BAK-CHEK ANGLE STOP. SPUD COUPLINGAND FLANGE FOR 1-1/2" TOP SPUD.

OVAL DROP-IN LAVATORY

BASIS OF DESIGN SHALL BE BY J.R. SMITH 2000 SERIES.DESCRIPTION: CAST IRON, DRAIN WITH 7" ADJUSTABLE NICKEL BRONZE STRAINERHEAD. PROVIDE COLOR AND ROUND/SQUARE SHAPE TO MATCH FINISHES.COORDINATE FINISHES WITH ARCHITECT. PROVIDE TRAP PRIMER CONNECTIONS.

FLOOR DRAINFD-1 -- 1/2" 4" 2"

SLOAN MODEL NO. SS-3002 OVAL DROP-IN, WHITE VITREOUS CHINA, HANGINGHARDWARE, BACKSPLASH. SINGLE CENTER HOLE PUNCH AND OVERFLOW. OTHERMANUFACTURERS KOHLER OR AMERICAN STANDARD.

FIXTURE: SLOAN OPTIMA SYSTEMS EAF-275-ISM, 0.5 GPM FLOW RATE. OTHERMANUFACTURERS KOHLER OR AMERICAN STANDARD. SENSOR ACTIVATED,ELECTRONIC, CHROME PLATED DIE-CAST METAL, HAND WASHING FAUCET WITH THEFOLLOWING FEATURES:* MODULAR ONE-PIECE CONSTRUCTION WITH ALL CONCEALED COMPONENTS ABOVEDECK* DOUBLE INFRARED SENSORS WITH AUTOMATIC SETUP AND INDICATOR LIGHT* AUTOMATIC SELF-ADAPTING SENSOR TECHNOLOGY* SOLAR POWERED* MAGNETIC SOLENOID VALVE* WATER SUPPLY CONNECTION WITH FLEXIBLE HIGH-PRESSURE HOSE AND STRAINER* 6 VOLT LITHIUM BATTERY BACK-UP POWER SOURCE

GRID DRAIN: EBC OTHER MANUFACTURERS MCGUIRE, DEARBORNP-TRAP: EBC OTHER MANUFACTURERS MCGUIRE, DEARBORNSUPPLIES: EBC OTHER MANUFACTURERS MCGUIRE, BRASS CRAFTTRAP COVERS: TRUEBRO OTHER MANUFACTURERS PROFLO.

FINISH SHALL BE SILVER FOR ALLTOILET ROOMS

WC 16" SEAT HT. / FLOOR MTD., FLUSH VALVE--- 3" 2"1-1/2"WATER CLOSET FLOOR MOUNTED, VITREOUS CHINA, SIPHON JET FLUSHING ACTION WITH ELONGATEDBOWL, 1-1/2" I.P.S. TOP SPUD INLET (DESIGNED FOR A 1.28 GPM FLUSH CYCLE) FLUSHVALVE. THE WATER CLOSET SHALL BE FITTED WITH OPEN FRONT SEAT WITHOUTCOVER.

FIXTURE: SLOAN MODEL NO. WETS. 2000.1201-1.28 SOLIS G2. OTHER MANUFACTURERSAMERICAN STANDARD OR KOHLER. WATER CLOSET SHALL BE IN COMPLIANCE TO THEAPPLICABLE SECTIONS OF ASME A112.19.2/CSA B45.1. ADA COMPLIANT OPTIMA PLUSBATTERY POWERED INFRARED SENSOR FOR AUTOMATIC NO HANDS OPERATION.FOUR (4) SIZE AA BATTERIES FACTORY INSTALLED, LOW BATTERY FLASHING LED. 1"I.P.S. SCREWDRIVER BAK-CHEK ANGLE STOP. SPUD COUPLING AND FLANGE FOR 1-1/2" TOP SPUD. PROVIDE WHITE, PLASTIC OPEN-FRONT EXTRA HEAVY DUTY SEAT BYCHURCH. OTHER MANUFACTURERS BENEKE OR BEMIS.

UR - 3/4" 2" 2"URINAL WALL HUNG ADA (UR-A) 17"AFF RIM HEIGHT

WALL HUNG 24" AFF RIMHEIGHT

WALL HUNG WHITE VITREOUS CHINA, W/ SOLAR-POWERED SENSORACTIVATED FLUSHOMETER.

FIXTURE: SLOAN MODEL NO. WEUS-1000.1201-0.13 SOLIS. OTHERMANUFACTURERS AMERICAN STANDARD OR KOHLER. URINAL SHALL BE INCOMPLIANCE TO THE APPLICABLE SECTION OF ASME 112.19/CSA B45.1. ADACOMPLIANT SOLIS SOLAR-POWERED SENSOR FOR AUTOMATIC NO HANDSOPERATION. COURTESY FLUSH OVERRIDE BUTTON. FOUR (4) SIZE AA BATTERYBACK-UP POWER SOURCE. 3/4" I.P.S. SCREWDRIVER BAK-CHEK ANGLE STOP.FREE SPINNING, VANDAL RESISTANT VACUUM BREAKER FLUSH. SPUDCOUPLING AND FLANGE FOR 3/4" TOP SPUD. 3/4" I.P.S. TOP SPUD INLET. 2" NPTOUTLET FLANGE. INCLUDE ALL MOUNTING HARDWARE. 0.13 GPM WASHDOWNFLUSHING ACTION.

CARRIER: J.R. SMITH OTHER MANUFACTURERS WATTS, ZURN.

MOP SINK SHALL BE FIAT MODEL NO. MSB-2424 WITH 1239BB BUMPERGUARDS, 1453BB STAINLESS STEEL GRID STRAINER. OTHER MANUFACTURERS ACORN ORSWANSTONE.DESCRIPTION: 24"x24" MOLDED STONE MOP BASIN WITH 10" HIGH SIDE AND ANINTEGRAL 3" CHROME PLATED DRAIN WITH A SEAL CONNECTION TO THE WASTEPIPING. MOP BASIN SHALL BE WHITE DRIFT IN COLOR.FAUCET: CHICAGO FAUCET MODEL 897-CP. OTHER MANUFACTURERS TS & BRASSOR ZURN.HOSE AND BRACKET: FIAT 832-AA. OTHER MANUFACTURERS ACORN ORSWANSTONE.PROVIDE BUCKET HOOK, SHUTOFF VALVES FOR CW AND HW AND A CHECK VALVE.

MOP SINKMS 1/2" 1/2" 3" 2" FAUCET SHALL BE MOUNTED 36" AFF

ITEM MOUNTING HEIGHT / REMARKS

PLUMBING FIXTURE SCHEDULE

HOTWATER

COLDWATER WASTE VENT (AFF)FIXTURE TYPE FIXTURE DESCRIPTION

WATER PRESSURE REDUCING VALVES SHALL BE INSTALLED ON THE WATERSERVICE PIPE NEAR ITS ENTRANCE TO THE BUILDING WHERE SUPPLY MAINPRESSURE EXCEEDS 60 PSIG TO REDUCE IT TO 50 PSIG OR LOWER. PROVISIONSHALL BE MADE TO PERMIT THE BYPASS FLOW OF WATER BACK THROUGH THEVALVE INTO THE MAIN WHEN PRESSURES, DUE TO THERMAL EXPANSION ON THEOUTLET SIDE OF THE VALVE, EXCEED THE PRESSURE IN THE MAIN SUPPLY.PRESSURE REDUCING VALVES WITH BUILT-IN BYPASS CHECK VALVES ANDSTRAINER WILL BE ACCEPTABLE. APPROVED VALVES SHALL COMPLY WITH ASSE1003. VALVE SHALL BE A WATTS SERIES 223-S (WITH STRAINER) OTHERMANUFACTURERS APOLLO OR ZURN. BODY MATERIALS SHALL BE BRONZE OR IRON,WITH A REPLACEABLE STAINLESS STEEL SEAT, STAINLESS STEEL STRAINERSCREEN, REINFORCE BUNA-N DIAPHRAGM, AND EPDM VALVE DISC.

PRESSURE REDUCING VALVEPRV SET PRV AT 50 PSIG.

J.R. SMITH 4100 SERIES OTHER MANUFACTURERS JOSAM OR ZURN.DESCRIPTION: CAST IRON BODY WITH ROUND, ADJUSTABLE SCORIATED SECUREDPOLISHED NICKEL BRONZE TOP WITHOUT HUB OUTLET.

FLOOR CLEANOUTFCO-- -- SEE PLANS --

PPP, MODEL P-1 WITH DU-4 DISTRIBUTION UNIT OTHER MANUFACTURERS JOSAM ORZURN.ALL TRAP PRIMERS SHALL HAVE BRAIDED STAINLESS STEEL FLEXIBLE HOSE TOFLOOR DRAINS. SEE PLANS FOR TRAP PRIMER LOCATIONS. SEE DETAIL FOR FURTHERINFORMATION.

TRAP PRIMERTP

-- -- -- --

--

BASIS OF DESIGN: JR SMITH 5618. OTHER MANUFACTURERS JOSAM OR ZURN OREQUIVALENT.DESCRIPTION: ALL BRONZE WITH CHROME PLATED FACE, HOSE CONNECTION ANDINTEGRAL ASSE 1011 VACUUM BREAKER, 360° SWIVEL INLET CONNECTION AND "T"HANDLE KEY.

HOSE BIBB (INTERIOR)HB-- 3/4" -- --

FOR HOSE BIBBS LOCATED IN GANGTOILETS, LOCATE IN AN ACCESSIBLELOCATION SO THAT VANITY PANELWILL NOT NEED TO BE REMOVED.

COORDINATE WITH ARCHITECTURALDOCUMENTS.

-- -- -- --

1/2"

CLEANOUT SHALL BE BY JR SMITH OTHER MANUFACTURERS JOSAM OR ZURN.THREADED PIPE FITTING OR CAST IRON FERRULE WITH GAS TIGHT CLEANOUT PLUG.

CLEANOUTCO -- - SEE PLANS -- --

J.R. SMITH 4100 SERIES OTHER MANUFACTURERS JOSAM OR ZURN.DESCRIPTION: CAST IRON BODY WITH ROUND, ADJUSTABLE SCORIATED SECUREDPOLISHED NICKEL BRONZE TOP WITHOUT HUB OUTLET.

WALL CLEANOUTWCO-- -- SEE PLANS -- --

OATEY MODEL 38811 ICEMAKER BOX COMPLETE WITH VALVE OR EQUIVALENT.OTHER MANUFACTURERS GUY GRAY, HALSEY-TAYLOR.

ICEMAKER BOXIMB -- 1/2" -- -- COORDINATE HEIGHT WITHLAB EQUIPMENT.

NOTES:1. PROVIDE ANGLE STOP VALVES, SUPPLY TUBING, P-TRAPS, ESCUTCHEON PLATES, STRAINERS, ETC., FOR COMPLETE INSTALLATION. BASIS OF DESIGN SHALL BE HEAVY GAUGE, CHROME-PLATED CONSTRUCTION BY EBC ORAPPROVED EQUAL BY MCGUIRE OR DEARBORN.2. PROVIDE CARRIERS FOR COMPLETE INSTALLATION. BASIS OF DESIGN SHALL BE ZURN OR APPROVED EQUAL BY JR SMITH OR JOSAM.2. ALL SUPPLY AND WASTE LINES SHALL BE CONCEALED IN ADJACENT WALL, FLOOR AND CEILING, UNLESS NOTED OTHERWISE.3. SEE DIVISION 22 SPECIFICATION SECTIONS FOR ADDITIONAL INFORMATION.4. MOUNT ALL FIXTURES SO EASILY ACCESSIBLE FOR MAINTENANCE.5. PLUMBING CONTRACTOR SHALL SUBMIT ALL PLUMBING FIXTURE AND COLOR SELECTIONS TO ARCHITECT TO OBTAIN FINAL APPROVAL.6. ACCEPTABLE MANUFACTURERS ARE INDICATED FOR EACH FIXTURE THROUGHOUT THE FIXTURE SCHEDULE. EQUAL PRODUCTS BY OTHER MANUFACTURERS ARE ACCEPTABLE PROVIDING SUBSTITUTIONS ARE SUBMITTED INACCORDANCE WITH REQUIREMENTS LISTED ELSEWHERE IN THE BID DOCUMENTS AND APPROVED BY THE A/E.

PROVIDE, ON EACH ROOF PENETRATION, A FLASHING COUNTER-FLASHING ASSEMBLY.FLASHING SHALL BE 4 LB SEAMLESS LEAD WITH 6" SKIRT AND STEEL REINFORCEDBOOT AND SHALL PERMIT INSTALLATION ON ROOFS WITH UP TO A 20 DEGREE PITCH.COUNTERFLASHING SHALL BE CAST IRON SET SCREW TYPE AND BE ATTACHEDDIRECTLY TO THE ROOF PENETRATION. ALL FLASHING SHALL BE INSTALLED INACCORDANCE WITH MANUFACTURERS RECOMMENDATIONS AND FLASHED INACCORDANCE WITH THE RECOMMENDATIONS OF THE ROOFING MATERIALMANUFACTURER.

BASIS OF DESIGN SHALL BE ELDMOR STONEMAN 1100 SERIES WITH VANDALRESISTANT HOOD.

VENT THRU ROOFVTR-- -- -- -- FLASHING TO BE PROVIDED BY

ROOFING CONTRACTOR. COORDINATEWITH ALL DISCIPLINES.

LAV-2 1/2" 1/2" 1-1/4" 1-1/2"LAVATORY 34" RIM HT. / WALL HUNGSLOAN MODEL NO. SS-3003 WALL HUNG, WHITE VITREOUS CHINA, HANGINGHARDWARE, BACKSPLASH. SINGLE CENTER HOLE PUNCH AND OVERFLOW. OTHERMANUFACTURERS KOHLER OR AMERICAN STANDARD.

FIXTURE: SLOAN OPTIMA SYSTEMS EAF-275-ISM, 0.5 GPM FLOW RATE. OTHERMANUFACTURERS KOHLER OR AMERICAN STANDARD. SENSOR ACTIVATED,ELECTRONIC, CHROME PLATED DIE-CAST METAL, HAND WASHING FAUCET WITH THEFOLLOWING FEATURES:* MODULAR ONE-PIECE CONSTRUCTION WITH ALL CONCEALED COMPONENTS ABOVEDECK* DOUBLE INFRARED SENSORS WITH AUTOMATIC SETUP AND INDICATOR LIGHT* AUTOMATIC SELF-ADAPTING SENSOR TECHNOLOGY* SOLAR POWERED* MAGNETIC SOLENOID VALVE* WATER SUPPLY CONNECTION WITH FLEXIBLE HIGH-PRESSURE HOSE AND STRAINER* 6 VOLT LITHIUM BATTERY BACK-UP POWER SOURCE

GRID DRAIN: EBC OTHER MANUFACTURERS MCGUIRE, DEARBORNP-TRAP: EBC OTHER MANUFACTURERS MCGUIRE, DEARBORNSUPPLIES: EBC OTHER MANUFACTURERS MCGUIRE, BRASS CRAFTCARRIER: J.R. SMITH OTHER MANUFACTURERS WATTS, ZURNTRAP COVERS: TRUEBRO OTHER MANUFACTURERS PROFLO.

BASIS OF DESIGN: J.R. SMITH MODEL NO. 5509 QT. OTHER MANUFACTURERSJOSAM OR ZURN OR EQUIVALENT.DESCRIPTION: BRONZE QUARTER TURN NON-FREEZE AUTOMATIC DRAININGHYDRANT WITH STAINLESS STEEL FACE, HOSE CONNECTION, INTEGRALVACUUM BREAKER AND DUAL CHECK VALVE, "T" HANDLE KEY, WHEEL HANDLEAND STAINLESS STEEL BOX WITH FULL 180° COVER OPENING. PROVIDE WITHPOLISHED BRONZE FINISH.

NON-FREEZE WALL HYDRANTNFWH -- 3/4" -- -- 18" AFG

NOTES:1. PROVIDE ANGLE STOP VALVES, SUPPLY TUBING, P-TRAPS, ESCUTCHEON PLATES, STRAINERS, ETC., FOR COMPLETE INSTALLATION. BASIS OF DESIGN SHALL BE HEAVY GAUGE, CHROME-PLATED CONSTRUCTION BY EBC OR APPROVEDEQUAL BY MCQUIRE OR DEARBORN.2. PROVIDE CARRIERS FOR COMPLETE INSTALLATION. BASIS OF DESIGN SHALL BE ZURN OR APPROVED EQUAL BY JR SMITH OR JOSAM.2. ALL SUPPLY AND WASTE LINES SHALL BE CONCEALED IN ADJACENT WALL, FLOOR AND CEILING, UNLESS NOTED OTHERWISE.3. SEE DIVISION 22 SPECIFICATION SECTIONS FOR ADDITIONAL INFORMATION.4. MOUNT ALL FIXTURES SO EASILY ACCESSIBLE FOR MAINTENANCE.5. PLUMBING CONTRACTOR SHALL SUBMIT ALL PLUMBING FIXTURE AND COLOR SELECTIONS TO ARCHITECT TO OBTAIN FINAL APPROVAL.6. ACCEPTABLE MANUFACTURERS ARE INDICATED FOR EACH FIXTURE THROUGHOUT THE FIXTURE SCHEDULE. EQUAL PRODUCTS BY OTHER MANUFACTURERS ARE ACCEPTABLE PROVIDING SUBSTITUTIONS ARE SUBMITTED INACCORDANCE WITH REQUIREMENTS LISTED ELSEWHERE IN THE BID DOCUMENTS AND APPROVED BY THE A/E.

REDUCED PRESSURE ZONE THE ASSEMBLY SHALL CONSIST OF A PRESSUREDIFFERENTIAL RELIEF VALVE LOCATED IN A ZONE BETWEEN TWO POSITIVE SEATINGCHECK VALVES. THE ASSEMBLY SHALL INCLUDE TWO BALL TYPE SHUTOFF VALVESBEFORE AND AFTER THE ASSEMBLY, TEST COCKS AND A PROTECTIVE STRAINERUPSTREAM OF THE FIRST SHUTOFF VALVE. MATERIALS OF CONSTRUCTION SHALL BEBRONZE OR CAST IRON BODIES, WITH STAINLESS STEEL INTERNALS. THE ASSEMBLYSHALL MEET THE REQUIREMENTS OF ASSE 1013; AWWA STD. C-511-92 AND BE LISTEDIAPMO (UPC) AND SBCCI (STANDARD PLUMBING CODE). PROVIDE WITH AIR GAP FITTING.BASIS OF DESIGN SHALL BE WATTS MODEL LF909QTS, 957OSY.

BACKFLOW PREVENTERBFP-- -- -- -- SEE PLUMBING PLAN FOR LOCATION

AND SIZE

BASIS OF DESIGN SHALL BE BY J.R. SMITH 2000 SERIES WITH FIGURE 3580 FUNNEL.DESCRIPTION: CAST IRON, DRAIN WITH 7" ADJUSTABLE NICKEL BRONZE STRAINERHEAD. PROVIDE COLOR AND ROUND/SQUARE SHAPE TO MATCH FINISHES.COORDINATE FINISHES WITH ARCHITECT. PROVIDE TRAP PRIMER CONNECTIONS.

FLOOR DRAIN WITH FUNNELFD-2 -- 1/2" 4" 2" --

STAINLESS STEEL 12 INCH SQUARE TOP WITH STAINLESS STEEL LOOSE SETHALF GRATE AND SEDIMENT BUCKET. PROVIDE 8" DEEP (MIN.) RECEPTOR BODY,WITH 4" PIPE SIZE OUTLET. PROVIDE TRAP PRIMER CONNECTION, ANDANCHORING/FLASHING FLANGES.BASIS OF DESIGN SHALL BE JR SMITH 3008 PO50. OTHER MANUFACTURERSZURN OR JOSAM.

FLOOR SINKFS1/2" -- 4" 2" --

BASIS OF DESIGN SHALL BE ZURN Z9A-FD2-P.DESCRIPTION: FLAME RETARDANT POLYPROPYLENE BODY WITH 7" ADJUSTABLESTAINLESS STEEL HEAD AND GRATE WITH SEDIMENT BUCKET. PROVIDE TRAP PRIMERCONNECTIONS. PROVIDE ROUND/SQUARE SHAPE TO MATCH FINISHES. COORDINATEFINISHES WITH ARCHITECT.

FLOOR DRAIN WITHSEDIMENT TRAP

FD-3 -- 1/2" 4" 2" --

ELKAY EZH2O DUAL HEIGHT SYSTEM MODEL LZSTL8WSLK. OTHER MANUFACTURERSHAWS OR OASIS. PROVIDE ALL HANGING HARDWARE.

DUAL HEIGHT UNIT SHALL PROVIDE 8 GPH OF 50°F WATER AT 90°F AMBIENT AND 80°FINLET WATER. BOTTLE FILLING UNIT SHALL INCLUDE AN ELECTRONIC SENSOR FORNO-TOUCH ACTIVATION WITH AN AUTOMATIC 30-SECOND SHUT-OFF TIMER. SHALLPROVIDE 1.1-1.5 GPM FLOW RATE WITH LAMINAR FLOW TO MINIMIZE SPLASHING.SHALL INCLUDE ANTIMICROBIAL PROTECTED PLASTIC COMPONENTS TO PREVENTMOLD AND MILDEW. COOLER UNIT SHALL HAVE PUSHBAR ACTIVATION AND WATEREFFICENT BUBBLER. SHALL INCLUDE FILTER, CERTIFIED TO NSF/ANSI 42 AND 53 WITHVISUAL MONITOR TO INDICATE WHEN REPLACEMENT IS NECESSARY. BOTTLE FILLINGUNIT AND COOLER SHALL BE ADA COMPLIANT. UNIT SHALL BE LEAD FREE DESIGNCERTIFIED TO NSF/ANSI 61.

ELECTRIC WATER COOLEREWC -- 1/2" 1 1/4" 1 1/2" WALL MOUNT DUAL HEIGHT 34"AND 26" ORIFICE AFF

CAST IRON BODY WITH FLASHING CLAMP, SUMP RECEIVER, UNDERDECK CLAMPAND METAL DOME. PROVIDE EXTENSION AS REQUIRED FOR ROOF INSULATION.BASIS OF DESIGN SHALL BE JR SMITH 1015 SERIES OTHER MANUFACTURERSJOSAM OR ZURN.

OVERFLOW/ROOF DRAINOF/RD -- -- 4" --DECK-MOUNT

SINK AND FAUCET PROVIDED BY LAB EQUIPMENT SUPPLIER. SUPPLY NON-POTABLE HOT AND COLD WATER AND ACID WASTE AND VENT FOR FIXTURE.PLUMBING CONTRACTOR SHALL MAKE ALL FINAL CONNECTIONS. PROVIDE ANYACCESSORIES NEEDED FOR A COMPLETE INSTALLATION INCLUDING BUT NOTLIMITED TO P-TRAP. COORDINATE WITH LAB EQUIPMENT SUPPLIER.

LAB SINKSK1 1/2" 1/2" 1 1/2" 1 1/2"--

SINK PROVIDED BY LAB EQUIPMENT SUPPLIER AS PART OF FUME HOOD.PROVIDE ACID WASTE AND VENT FOR FIXTURE. PLUMBING CONTRACTORSHALL MAKE ALL FINAL CONNECTIONS. PROVIDE ANY ACCESSORIES NEEDEDFOR A COMPLETE INSTALLATION INCLUDING BUT NOT LIMITED TO P-TRAP.COORDINATE WITH LAB EQUIPMENT SUPPLIER.

CUP SINKCS -- -- -- -- --

SINK: ELKAY LUSTERTONE LRAD1722FAUCET: CHICAGO 895-317E2805-5VPHCP

BREAK SINKBRS 1/2" 1/2" 2" 1-1/2" COUNTERTOP

ADA COMPLIANT RECESSED SAFETY STATION WITH DRAIN PAN & EXPOSEDSHOWER HEAD WITH STAINLESS STEEL COVER, EXPOSED PIPING, ANDESCUTCHEON; BRASS STAY OPEN BALL VALVE; IN-LINE STRAINER. COORDINATECEILING HEIGHTS AND PROVIDE STAINLESS STEEL PIPING EXTENSIONS ASREQUIRED FOR ADA COMPLIANT HEIGHT OF SHOWER HEAD. PROVIDE POINT-OF-USE THERMOSTATIC MIXING VALVE COMPLYING WITH ASSE 1071 OR CSA B125.3LOCATED ABOVE CEILING AT SAFETY STATION TO SUPPLY 75°F TEPID WATER.

SAFETY STATION: BASIS OF DESIGN WATERSAVER SSBF2150. OTHERMANUFACTURERS ACORN, BRADLEY, OR GUARDIAN.EMERGENCY THERMOSTATIC MIXING VALVES: TMV-3 LOCATED ABOVE CEILING.

EMERGENCY SHOWER/EYEWASHESH 3/4" 3/4" 2" 1-1/2" --

12-5/8" SQUARE TOP PROM-DECK DRAIN, DURA-COATED CAST IRON BODY WITHROTATABLE SQUARE PROMENADE FRAME WITH SEEPAGE OPENINGS, FRAMECLAMPS AND DECORATIVE LIGHT DUTY HEEL-PROOF GRATE WITH 3/16" WIDESLOTS AND NICKEL BRONZE VENEER FRAME AND GRATE. PROVIDE EXTENSION ASREQUIRED FOR FINISH.BASIS OF DESIGN SHALL BE ZURN Z154-DT. OTHER MANUFACTURERS JOSAM OR JRSMITH.

PROMENADE DECK DRAINPD -- -- 6" --DECK-MOUNT

SINK AND FAUCET PROVIDED BY LAB EQUIPMENT SUPPLIER. SUPPLY NON-POTABLE HOT AND COLD WATER AND ACID WASTE AND VENT FOR FIXTURE.PLUMBING CONTRACTOR SHALL MAKE ALL FINAL CONNECTIONS. PROVIDE ANYACCESSORIES NEEDED FOR A COMPLETE INSTALLATION INCLUDING BUT NOTLIMITED TO P-TRAP. COORDINATE WITH LAB EQUIPMENT SUPPLIER.

LAB SINKSK1A--

1/2" 1/2" 1 1/2" 1 1/2"

SINK AND FAUCET PROVIDED BY LAB EQUIPMENT SUPPLIER. SUPPLY NON-POTABLE HOT AND COLD WATER AND ACID WASTE AND VENT FOR FIXTURE.PLUMBING CONTRACTOR SHALL MAKE ALL FINAL CONNECTIONS. PROVIDE ANYACCESSORIES NEEDED FOR A COMPLETE INSTALLATION INCLUDING BUT NOTLIMITED TO P-TRAP. COORDINATE WITH LAB EQUIPMENT SUPPLIER.

LAB SINKSK2--

1/2" 1/2" 1 1/2" 1 1/2"

SINK AND FAUCET PROVIDED BY LAB EQUIPMENT SUPPLIER. SUPPLY NON-POTABLE HOT AND COLD WATER AND ACID WASTE AND VENT FOR FIXTURE.PLUMBING CONTRACTOR SHALL MAKE ALL FINAL CONNECTIONS. PROVIDE ANYACCESSORIES NEEDED FOR A COMPLETE INSTALLATION INCLUDING BUT NOTLIMITED TO P-TRAP. COORDINATE WITH LAB EQUIPMENT SUPPLIER.

LAB SINKSK3--

2 X 1/2" 2 X 1/2" 1 1/2" 1 1/2"BASIS OF DESIGN SHALL BE ZURN Z9A-FD2-P.DESCRIPTION: FLAME RETARDANT POLYPROPYLENE BODY WITH 7" ADJUSTABLESTAINLESS STEEL HEAD AND GRATE. PROVIDE TRAP PRIMER CONNECTIONS. PROVIDEROUND/SQUARE SHAPE TO MATCH FINISHES. COORDINATE FINISHES WITH ARCHITECT.

EMERGENCY STATIONFLOOR DRAIN

FD-4 -- 1/2" 3" 2" --

SINK SHALL BE FLORESTONE MODEL FM. OTHER MANUFACTURERS FIAT ORMUSTEE.DESCRIPTION: 23-1/8"x22-3/8" NON-FERROUS UTILITY SINK WITH 35" DEPTH,RESISTANT TO FADING AND ABRASION. COLOR SHALL BE WHITE.FAUCET: CHICAGO FAUCET MODEL 897-CP. OTHER MANUFACTURERS TS & BRASSOR ZURN.

CLEAN ROOM SINKCRS 1/2" 1/2" 1-1/2" 1-1/2" FLOOR-MOUNTED

SERVICE SINK WITH PLAIN BACK AND RIM GUARD, NOMINAL DIMENSIONS 24"X20-1/2"X10-1/2" DEEP. MEETING OR EXCEEDING ASME A112.19.1 FOR CAST IRONPLUMBING FIXTURES. EXPOSED YOKE WALL-MOUNT UTILITY FAUCET WITH VACUUMBREAKER AND STOPS IN SHANK. CAST IRON P-TRAP AND STRAINER.

FIXTURE: AMERICAN STANDARD "AKRON” SERVICE SINK MODEL 7695.000, 8379.026 RIMGUARD.FAUCET: AMERICAN STANDARD 8341.076TRAP: AMERICAN STANDARD 7798.030

OTHER MANUFACTURERS KOHLER, ELJER.

UTILITY SINKUS 1/2" 1/2" 3" 2" FLOOR/WALL MOUNTED

GUY GRAY WHITE POWDER COATED METAL DISH WASHER OUTLET BOXCOMPLETE WITH VALVE OR EQUIVALENT. OTHER MANUFACTURERS OATEY,HALSEY-TAYLOR.

DISHWASHER SUPPLY BOXDWSB 1/2" -- -- -- COORDINATE HEIGHT WITHLAB EQUIPMENT.

EW DECK-MOUNDEDEYEWASH/DRENCH HOSE

FIXTURE PROVIDED BY LAB EQUIPMENT SUPPLIER. SUPPLY NON-POTABLE HOT ANDCOLD WATER. PLUMBING CONTRACTOR SHALL MAKE ALL FINAL CONNECTIONS.PROVIDE TMV-4 LOCATED IN LOWER CABINET SET AT 75°F.

1/2" 1/2" - - DECK MOUNTED.SUPPLY STOPS AT WALL.

PURIFIED WATER SUPPLY BOXPWSB -- -- -- -- COORDINATE HEIGHT WITHLAB EQUIPMENT.

OATEY WHITE POWDER COATED METAL ICE MAKER BOX WITHOUT VALVE, NO. 38687OR EQUIVALENT FOR PURIFIED WATER OUTLET TO DISHWASHER. OTHERMANUFACTURERS OATEY, HALSEY-TAYLOR.

SHOWER HEADAND VALVE

SH-1 1/2" 1/2" -- -- --PRESSURE ACTUATED MIXER WITH STAINLESS STEEL BALANCING PISTON TOEQUALIZE HOT AND COLD SUPPLY PRESSURES. BUILT-IN SHUTOFF FOR SINGLEHANDLE OPERATION. REMOVABLE ONE PIECE UPPER AND LOWER VALVE SEAT,INTERNAL PARTS OF BRONZE AND STAINLESS STEEL, CAST WALL FLANGE ANDLEVER HANDLE, POLISHED CHROME PLATED, MAXIMUM OPERATING PRESSURE: 125PSIG, ADJUSTABLE HIGH TEMPERATURE LIMIT STOP SET FOR 110°F, COLOR CODEDDIAL, OFF THROUGH HOT, WITH DIRECTIONAL INDICATORS, MAXIMUM FLOW 1.5 GPM,ASSE 1016 CERTIFIED, ANGLE CHECKSTOPS, COPPER TUBE CONNECTION, VANDALRESISTANT SCREWS, ARM AND FLANGE.BASIS OF DESIGN SHALL BE LEONARD PAM-II-ST–F VALVE, LEONARD 515P BRASSSHOWER HEAD WITH 1.5 GPM FLOW RATE. OTHER MANUFACTURERS CHICAGOFAUCET AND SYMMONS.

SHOWER DRAINSD-1 -- -- 2" 2" --304 STAINLESS STEEL LINEAR SHOWER DRAIN WITH ADJUSTABLE ANCHORING SUPPORTLEGS, ANTI-PONDING V-SHAPED CHANNEL, ADJUSTABLE SECURED LEVELING FRAMEWITH BUILT-IN TILE EDGE, AND SECURED, LIGHT-DUTY, SLOTTED HEEL-PROOF GRATE.BASIS OF DESIGN: ZURN ZS880-WG. OTHER MANUFACTURERS JOSAM OR JR SMITH.

CERTI F IC

AT E O F A U THO

RIZAT

ION

SOUTH CAROLINA

CONSULTINGENGINEERS

DWG, INC.

No.C03649

CHECKED BY:

DRAWN BY:

DATE:

PROJECT:

MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS

1

A

2 3 4 5 6

B

C

D

E

WWW.LS3P.COMTEL. 843.577.4444 FAX 843.722.4789205 1/2 KING ST. CHARLESTON SC 29401

STATE PROJECT NO:H17-9588-FW

REVISIONS:

COPYRIGHT 2014 ALL RIGHTS RESERVEDPRINTED OR ELECTRONIC DRAWINGS ANDDOCUMENTATION MAY NOT BE REPRODUCEDIN ANY FORM WITHOUT WRITTEN PERMISSIONFROM LS3P ASSOCIATES LTD.

E

G

No.

L

TU

DS

IC

AH

ISM

RE

TE

K

EG. W

ES

AA

17759

RE

GE

ER

INEN

L

RCAHORP

SEFOLN

S IOINO

5/19

/201

4 2:

53:1

1 PM

C:\U

sers

\km

inog

ue\D

ocum

ents

\120

96_C

CU

Sci

ence

Ann

ex II

Pha

se O

ne_2

013_

kmin

ogue

.rvt

LS3P: 1202-122370

MAY 20, 2014

KMM

MGW

PLUMBINGSCHEDULES

P601

BID SET

SCIENCE ANNEX IICONSTRUCTION

No. Description Date

Page 19: s SOLENOID VALVE - Coastal Carolina University · PDF filecu condensing unit hd hub drain mc ... kmm mgw plumbing notes & legend p000 bid set science annex ii construction ... bio

POINT-OF-USE WATER TREATMENTMARK

UPW-1

DESCRIPTION BASIS OF DESIGN

ULTRAPURE WATER POLISHING STATIONWITH ACTIVATED CARBON ABSORBER,PRIMARY AND POLISHING MIXED-BEDDEIONIZERS, PUMPING STATION WITH 185nm UV LIGHT, POSIDYNE MEMBRANEFILTER, AND FAUCET WITH 254 nm UV LIGHTAND RESISTIVITY MONITOR.

EMD MILLIPORE - MILLI Q ADVANTAGE

NOTES:1. WATER SUPPLY SHALL BE RO/DI WATER.2. EQUAL PRODUCTS BY OTHER MANUFACTURERS ARE ACCEPTABLE PROVIDING SUBSTITUTIONS ARE SUBMITTED INACCORDANCE WITH REQUIREMENTS LISTED ELSEWHERE IN BID DOCUMENTS AND APPROVED BY THE A/E.

VACUUM PUMPMARK

V-1

TYPE RATED CFM AT 19.0" Hg ELECTRIC MOTOR DRIVE REC. TANK REMARKS

FACTORY PACKAGED, TANK MOUNTED,DUPLEX OIL-LUBRICATED ROTARY VANEVACUUM PUMP.

41 5 HP EACH10 HP TOTAL

SEE ELECTRICAL DRAWINGS FORMORE INFORMATION

120 GALLONS, VERTICAL BASIS OF DESIGN: POWEREX VVTD0504. 2" OUTLET.

NOTE: EQUAL PRODUCTS BY OTHER MANUFACTURERS ARE ACCEPTABLE PROVIDING SUBSTITUTIONS ARE SUBMITTED IN ACCORDANCE WITH REQUIREMENTS LISTED ELSEWHERE IN BID DOCUMENTS AND APPROVED BY THE A/E.

AIR COMPRESSORMARK

AC-1

TYPE RATED CFMAT 100 PSI

ELECTRICMOTOR DRIVE

REC. TANK REMARKS

FACTORY PACKAGED, SKID MOUNTEDENCLOSED DUPLEX OIL-LESS SCROLLAIR COMPRESSOR SYSTEM. WITH DUALTOWER DESICCANT DRYER.

60.8 20 HPSEE ELECTRICAL FORMORE INFORMATION

240 GALLONS, VERTICAL BASIS OF DESIGN: POWEREX SEQ2007 WITH DESICCANT DRYER OPTION.PROVIDE REGULATOR AT COMPRESSOR OUTLET. COORDINATE AIRPRESSURE REQUIREMENTS WITH OWNER. 1-1/2" OUTLET.

NOTE: EQUAL PRODUCTS BY OTHER MANUFACTURERS ARE ACCEPTABLE PROVIDING SUBSTITUTIONS ARE SUBMITTED IN ACCORDANCE WITH REQUIREMENTS LISTED ELSEWHERE IN BID DOCUMENTS AND APPROVED BY THE A/E.

CONDENSING DOMESTIC WATER HEATER SCHEDULE

WH-1P

THERMALEFF.

BASIS OF DESIGNFUELRECOVERY@ 100 F

CAPACITYITEM

119 GALLON STORAGE 466 GPH NATURALGAS CYCLONE XI BTH 400

NOTES:1. ACCEPTABLE MANUFACTURERS, CONTINGENT UPON COMPLIANCE WITH THE CONTRACT DOCUMENTS, ARE AS FOLLOWS: STATE WATER HEATER, BRADFORD WHITE,

LOCHINVAR AND BOCK. EQUAL PRODUCTS BY OTHER MANUFACTURERS ARE ACCEPTABLE PROVIDING SUBSTITUTIONS ARE SUBMITTED IN ACCORDANCE WITHREQUIREMENTS LISTED ELSEWHERE IN THE BID DOCUMENTS AND APPROVED BY THE A/E.

2. WATER HEATER SHALL INCLUDE AN ASME RATED T&P RELIEF VALVE AND DRAIN VALVE.3. PROVIDE MANUFACTURER'S CONCENTRIC VENT KIT. BASIS OF DESIGN: BTH-400 - 500 VENT KIT. KIT SHALL INCLUDE VENT SUB-ASSEMBLY, TERMINATION ASSEMBLY

AND RAIN CAP ASSEMBLY.4. ALL ADDITIONAL APPURTENANCES INCLUDING PIPE, HANGERS, ADHESIVES ETC. SHALL BE INSTALLED TO PROVIDE A SAFE, SECURE AND OPERATING SYSTEM.5. SEE ELECTRICAL DOCUMENTS FOR VOLTAGE AND AMPERAGE REQUIREMENTS.6. PROVIDE MANUFACTURER'S CONDENSATE NEUTRALIZER KIT.7. PROVIDE EXPANSION TANK FOR DOMESTIC WATER SYSTEM AND NON-POTABLE WATER SYSTEM. SIZE IN ACCORDANCE WITH WATER HEATER MANUFACTURER'S

SIZING GUIDE. BASIS OF DESIGN SHALL BE BELL & GOSSETT PT SERIES. ACCEPTABLE MANUFACTURERS, CONTINGENT UPON COMPLIANCE WITH THE CONTRACTDOCUMENTS, ARE AS FOLLOWS: TACO, AMTROL. EQUAL PRODUCTS BY OTHER MANUFACTURERS ARE ACCEPTABLE PROVIDING SUBSTITUTIONS ARE SUBMITTED INACCORDANCE WITH REQUIREMENTS LISTED ELSEWHERE IN BID DOCUMENTS AND APPROVED BY THE A/E.

8. SUFFIX IN ITEM MARK INDICATES USE FOR POTABLE (P) OR NON-POTABLE (NP) HOT WATER SYSTEM.

INPUTBTUH

399,900 95% A.O. SMITH

MODEL

WH-2NP 119 GALLON STORAGE 576 GPH CYCLONE XI BTH 500499,900 95% A.O. SMITH

WH-3NP 119 GALLON STORAGE 576 GPH CYCLONE XI BTH 500499,900 95% A.O. SMITH

NATURALGAS

NATURALGAS

WATERINLET/

OUTLETSIZE

GASSUPPLY

SIZE

1-1/4"

1-1/4"

1-1/2"

1-1/2"

1-1/2"

1-1/2"

REVERSE-OSMOSIS/DEIONIZED WATER TREATMENT

MARK

PW-1

TYPE DISTRIBUTIONPUMPS STORAGE TANK GENERATION CAPACITY REMARKS

ASTM TYPE 3 HIGH PURITY WATERSYSTEM INCLUDES TURBIDITY FILTER,WATER SOFTENER, CARBON FILTER, 5MICRON PREFILTER, REVERSE OSMOSISUNIT, STORAGE TANK, DUPLEXDISTRIBUTION PUMPS , SIX MIXED BEDDEIONIZERS, 0.2 MICRON POSTFILTER,AND UV STERILIZATION WITH PLCCONTROL PANEL. BETA POLYPROPYLENEINTERCONNECTING PIPING.

DUPLEX PUMPS FORCOMBINED 30 GPMAT 70 PSI.

500 GALLONS 1,000 GALLONS PER DAY. BASIS OF DESIGN: PACKAGE SYSTEM BY HYDRO SERVICE AND SUPPLIESINCLUDING THE FOLLOWING:

TURBIDITY FILTER: ECODYNE INDUSTRIAL M-121A-TCWATER SOFTENER: ECODYNE INDUSTRIAL S-31A-ALT1CARBON FILTER: ECODYNE INDUSTRIAL C-141A-TC-D5 MICRON PREFILTER: ONE 20" LONG X 4-1/2" DIAMETER HIGH CAPACITYFILTERREVERSE OSMOSIS UNIT: HYDRO SERVICE AND SUPPLIESDISTRIBUTION PUMPS: GRUNDFOS CRN LINEMIXED BED DEIONIZERS: HYDRO SERVICE AND SUPPLIES0/2 MICRON POSTFILTER: FIVE 20" LONG BY 2.7" DIAMETERCONTROLLERPLC CONTROL PANEL: ALLEN BRADLEY MICROLOGIX WITH PV600TOUCHSCREEN

SYSTEM SHALL INCLUDE BALL BALVES, SOLENOID VALVES, SAMPLING PORTS,SERVICE LIGHTS, PRESSURE INDICATORS, FLOW METERS, ANALOG INPUTS,TIMERS, PRESSURE SWITCHES, AND ALL ITEMS REQUIRED FOR A COMPLETESYSTEM. PIPING NETWORK SHALL INCLUDE HIGH PURITY WATER RETURNPIPING.

NOTE: EQUAL PRODUCTS BY OTHER MANUFACTURERS ARE ACCEPTABLE PROVIDING SUBSTITUTIONS ARE SUBMITTED IN ACCORDANCE WITH REQUIREMENTS LISTED ELSEWHERE IN BID DOCUMENTS AND APPROVED BY THE A/E.

ACID NEUTRALIZATION TANKMARK

ANT-1

DESCRIPTION BASIS OF DESIGN

BELOW GRADE SEAMLESSPOLYTHYLENE CHEMICAL WASTE TANK,REINFORCED FOR DIRECT BURY. 1,295GALLON LIQUID HOLDING CAPACITY,1,5000 GALLON TOTAL TANK CAPACITY.PROVIDE RISERS TO EXTEND COVERSTO GRADE. PROVIDE pH MONITORINGPACKAGE WITH CENTRAL MONITORINGSTATION.

TANK: SCHIER PRODUCTS NT-1500-BpH MONITORING STATION: SCHIER PRODUCTS COMMANDCENTER

NOTE: EQUAL PRODUCTS BY OTHER MANUFACTURERS ARE ACCEPTABLE PROVIDING SUBSTITUTIONS ARE SUBMITTEDIN ACCORDANCE WITH REQUIREMENTS LISTED ELSEWHERE IN BID DOCUMENTS AND APPROVED BY THE A/E.

NOTES:

1. SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION.2. ELEVATOR SUMP PUMP WITH OIL SENSING TECHNOLOGY. SEE ELECTRICAL DRAWINGS FOR CONTROLLERLOCATION. PUMP CONTROLLER SHALL BE CAPABLE OF PUMP SHUTDOWN UPON DETECTION OFOIL/HYDRAULIC FLUID.3. SEE ELECTRICAL DRAWINGS FOR VOLTAGE REQUIREMENTS.4. PROVIDE WITH LOCAL AND REMOTE AUDIO AND VISUAL WARNING ALARMS.5. INSTALL PER MANUFACTURER'S RECOMMENDATIONS.6. ACCEPTABLE MANUFACTURERS, CONTINGENT UPON COMPLIANCE WITH THE CONTRACT DOCUMENTS, AREAS FOLLOWS: LIBERTY, BELL & GOSSETT. EQUAL PRODUCTS BY OTHER MANUFACTURERS ARE ACCEPTABLEPROVIDING SUBSTITUTIONS ARE SUBMITTED IN ACCORDANCE WITH REQUIREMENTS LISTED ELSEWHERE INTHE BID DOCUMENTS AND APPROVED BY THE A/E.

SUMP PUMP SCHEDULE

SP-1

ITEM MAXGPM

74 37

HEADFT. W.G.

1/2

MAX.MOTOR

HPBASIS OFDESIGN MODEL

STANCOROIL-MINDER

SE-50

RPM

3600

GAS DEMAND SCHEDULE

ITEM # NAME DEMAND(MBTU)

NUMBER OFFIXTURES

TOTALDEMAND

WH-1 1

BASED ON TOTAL DEVELOPED LENGTH: 150'-0"NATURAL GAS @ 4.8" - 10.5" WCPIPE SIZED PER 2009 IFGC

WATER HEATER 399.9 399.9

TOTAL (MBTU) 17,492.4

WH-2

WH-3

B-1

B-2

WATER HEATER

WATER HEATER

BOILER

BOILER

1

1

1

1

499.9

499.9

499.9

499.9

3,0003,000

3,0003,000

LAB OUTLETS 325325130

GENERATOR 8,2688,2681

WATER DISTRIBUTION BOOSTER PUMPMARK

WDBP

SERVICE GPM(EACH)

HEADFT. W.G.

MOTORHP

MODEL

WATER DISTRIBUTION - POTABLEAND NON-POTABLE

250 69 7.5

NOTES:

RPM

3450

VFD

YES

BASIS OF DESIGN

PACKAGED DUPLEX VARIABLESPEED PUMP BY SYNCROFLO

IRONHEART-A SERIES

55DD07XXX-6H-2A-SWFFF-X-SS

1. REFER TO THE ELECTRICAL DRAWINGS FOR VOLTAGE REQUIREMENTS.2. PROVIDE WITH 130 GALLON ACCUMULATOR TANK.3. PUMP SHALL BE ALL STAINLESS STEEL CONSTRUCTION.4. MOUNT VFDS IN NEMA 1 ENCLOSURE.5. HEADERS SHALL BE 6" STAINLESS STEEL.

NOTES:

1. REFER TO THE ELECTRICAL DRAWINGS FOR VOLTAGE REQUIREMENTS.2. PROVIDE PUMP WITH MANUFACTURER'S TIMERS AND IMMERSION TYPE AQUASTATS.3. ACCEPTABLE MANUFACTURERS, CONTIGENT UPON COMPLIANCE WITH THE CONTRACT DOCUMENTS, ARE AS FOLLOWS: ARMSTRONG, GRUNDFOS.EQUAL PRODUCTS BY OTHER MANUFACTURERS ARE ACCEPTABLE PROVIDING SUBSTITUTIONS ARE SUBMITTED IN ACCORDANCE WITH REQUIREMENTSLISTED ELSEWHERE IN THE BID DOCUMENTS AND APPROVED BY THE A/E.

HOT WATER RECIRCULATING PUMP SCHEDULE

CP-1

ITEM GPM

4 25

HEADFT. W.G.

-

MIN.EFF.

1/2

MAX.MOTOR

HPTYPE BASIS OF

DESIGN

INLINE

VFD

NO TACO

RPM

-2/5

MAX.BHP

CP-2 4 25 -1/2 INLINE NO TACO-2/5

THERMOSTATIC MIXING VALVE SCHEDULE

TMV-1

MANUFACTURERCONNECTEDFIXTURES

SYSTEM USEMARK

POTABLE HOT WATER WH-1P, CP-1 805

NOTES:1. ACCEPTABLE MANUFACTURERS, CONTINGENT UPON COMPLIANCE WITH THE CONTRACT DOCUMENTS, ARE AS FOLLOWS: LAWLER, BRADLEY,

SYMMONS, LEONARD. EQUAL PRODUCTS BY OTHER MANUFACTURERS ARE ACCEPTABLE PROVIDING SUBSTITUTIONS ARE SUBMITTED INACCORDANCE WITH REQUIREMENTS LISTED ELSEWHERE IN THE BID DOCUMENTS AND APPROVED BY THE A/E.

2. INSTALL ABOVE CEILING AT FIXTURE.3. INSTALL IN LOWER CABINET. MAKE FINAL CONNECTIONS TO FIXTURE BY OTHERS.

LAWLER

MODEL

TMV-2 NON-POTABLE HOT WATER WH-2NP, WH-3NP, CP-2 805LAWLER

TMV-4 EMERGENCY EYEWASH EEW S19-2000BRADLEY

TMV-3 EMERGENCY SHOWERSTATION ESH S19-2100BRADLEY

APPLICABLESTANDARDS

ASSE 1070 ORCSA B125.3

ASSE 1071

ASSE 1070 ORCSA B125.3

ASSE 1071

1

NOTES

1

1, 3

1, 2

CERTI F IC

AT E O F A U THO

RIZAT

ION

SOUTH CAROLINA

CONSULTINGENGINEERS

DWG, INC.

No.C03649

CHECKED BY:

DRAWN BY:

DATE:

PROJECT:

MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS

1

A

2 3 4 5 6

B

C

D

E

WWW.LS3P.COMTEL. 843.577.4444 FAX 843.722.4789205 1/2 KING ST. CHARLESTON SC 29401

STATE PROJECT NO:H17-9588-FW

REVISIONS:

COPYRIGHT 2014 ALL RIGHTS RESERVEDPRINTED OR ELECTRONIC DRAWINGS ANDDOCUMENTATION MAY NOT BE REPRODUCEDIN ANY FORM WITHOUT WRITTEN PERMISSIONFROM LS3P ASSOCIATES LTD.

E

G

No.

L

TU

DS

IC

AH

ISM

RE

TE

K

EG. W

ES

AA

17759

RE

GE

ER

INEN

L

RCAHORP

SEFOLN

S IOINO

5/19

/201

4 2:

53:1

5 PM

C:\U

sers

\km

inog

ue\D

ocum

ents

\120

96_C

CU

Sci

ence

Ann

ex II

Pha

se O

ne_2

013_

kmin

ogue

.rvt

LS3P: 1202-122370

MAY 20, 2014

KMM

MGW

PLUMBINGSCHEDULES

P602

BID SET

SCIENCE ANNEX IICONSTRUCTION

No. Description Date