Product Data Sheet00813-0100-4641, Rev CB
August 2003 Rosemount 3402
www.rosemount.com
• Microprocessor-based electronics
• RS-485 and RS-232 Modbus™ outputs
• Multiple Modbus host support
• Multidrop capability
• Communication LEDs
• Full two-way communication
Content
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 5
Hazardous Locations Certifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 5
Dimensional Drawings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 6
Ordering Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 8
Rosemount 3402 Application
Interface Module (AIM)
Product Data Sheet00813-0100-4641, Rev CB
August 2003Rosemount 3402
2
AIM FEATURES AND BENEFITS
• Microprocessor-based electronicsprovide maximum system flexibility to accommodate various tank architectures.
• Modbus RS-232 and RS-485 communication outputallows easy integration of HTG tank information into control systems or other Modbus masters.
• NEMA 4X enclosuremakes it suitable for use in ordinary locations.
• Internal power supply for tank-mounted equipmentprovides power for up to 14 Rosemount 3201 HIUs and 3202 SAMs.
• Full, two-way communicationsact as a transparent window between the user and individual tank gauge data bases.
• Multidrop capabilityallows up to 31 3402 AIMs to be multidropped on a common RS-485 bus.
INTRODUCTION
The 3402 Application Interface Module (AIM)* serves
as the interface for the Rosemount 3201 Hydrostatic
Interface Unit (HIU) and 3202 Smart Application
Module (SAM). It provides standard RS-232 and
RS-485 Modbus™ outputs to host systems. The
Modbus communication provides process variables,
alarms, and configuration data residing in the HIUs
and SAMs to a wide variety of host systems.
Fisher-Rosemount Control Systems, other
distributed control systems, host computers, and
personal computers are all examples of the HTG
system flexibility. Figure 2 shows a typical system
architecture.
The 3402 AIM powers and communicates with up to
14 3201 HIUs or 3202 SAMs in any configuration on
a 2-wire Modbus Communication and Power (MCAP)
network. The AIM itself requires 115 V ac or 230 V ac
power and can be field or control room mounted.
This power and communication scheme allows easy
connection to existing Modbus communication
highways and makes optimum use of existing wire
runs.
FIGURE 1. The Hydrostatic Tank Gauging System Components
Furthermore, the AIM features MCAP and Modbus
communication LEDs and extensive lightning and
surge protection to ensure maximum system uptime.
MICROPROCESSOR-BASED ELECTRONICS
The 3402 AIM is built around the same stand-alone
modular concept used in all HTG system
components. With its built-in microprocessor, the AIM
converts the MCAP signal to standard RS-232 and
RS-485 Modbus. As shown in Figure 4, multiple
AIMs can be run on a common RS-485 bus to a host
system, providing the flexibility to readily increase
system size, or segregate tank-farm areas for
increased reliability.
The AIM can also be user-configured to act as a
master to other AIMs. In this configuration, the
master AIM will verify the integrity of the data from
the host device and repeat the data to the other AIMs
connected on the RS-485 highway. The master AIM
also sends the data on its own MCAP line to HIUs
and SAMs. Figure 4 illustrates this configuration.
HTG-008AB
Product Data Sheet00813-0100-4641, Rev CB
August 2003
3
Rosemount 3402
COMMUNICATION FLEXIBILITY
The Rosemount 3402 AIM communicates with the
host device using a 2- or 4-wire RS-485
implementation and an RS-232 serial communication
implementation of the Modbus protocol. The AIM
arbitrates between multiple Modbus masters
providing two RS-232 ports and one RS-485 port.
The RS-485 implementation allows up to 31 devices
(AIMs) to be multidropped on a single Modbus
network. The Modbus network also supports a total
of 247 Modbus addresses with each HIU or SAM
counting as one Modbus address.
Modbus protocol users can easily increase the level
of automation in their tank farms by passing
information from the Rosemount HIU or SAM to other
Modbus-compatible devices. This allows integration
of functions, such as pump and valve control with the
high-accuracy measurements from the HTG system.
The Modbus Communication and Power (MCAP)
network allows the HIUs and SAMs to be
multidropped on a single 2-wire network, thereby
minimizing wiring costs and increasing
communication flexibility.
APPLICATION FLEXIBILITY
The 3402 AIM installation options allow users to
integrate the Rosemount Hydrostatic Tank Gauging
(HTG) System easily with any existing tank farm
architectures. This provides maximum flexibility to
meet today’s tank farm requirements while providing
an automation path for future
HTG systems.
The 3402 AIM requires very little configuration. A
switch bank exists for proper MCAP and Modbus
settings. One switch determines if the AIM acts as a
master to other AIMs.
DIAGNOSTIC CAPABILITY
The 3402 AIM passes all of the HIU and SAM
diagnostic data to the host system. In addition,
multiple LEDs provide a visual indication of all
communication port activity. These diagnostic
features allow for easy system troubleshooting.
FIGURE 2. Hydrostatic Tank Gauging System Architecture
Rosemount 3402
Application
Interface
Module (AIM)
RS-485 Modbus Communications Network
HART Protocol
Rosemount 3201 HIU
or
Rosemount 3202 SAM
(PT)Top Pressure
Transmitter
(PM)Middle
Pressure
Transmitter
RTDTemperature
Sensor
(PB)Bottom Pressure
Transmitter
Host System
HT
G-0
104A
01DMCAP
Network
Product Data Sheet00813-0100-4641, Rev CB
August 2003Rosemount 3402
4
FIGURE 3. RS-485 Host Device Configuration
FIGURE 4. Master AIM Configuration
Rosemount
3201 HIU
Rosemount
3202 SAM
Rosemount
3201 HIU
Rosemount
3202 SAM
Rosemount
3402 AIM
RS-485 Modbus
To Host Device
(Two RS-232
Ports)
Rosemount
3402 AIM
3402
-000
0A03
C
Modbus Communications
and Power (MCAP)
Up to 14 Rosemount 3201
HIUs
or 3202 SAMs
(Any Combination)
Modbus Communications
and Power (MCAP)
Up to 14 Rosemount 3201
HIUs
or 3202 SAMs
(Any Combination)
Up to 31
Devices
Total
(Any
Combination)
Host System
To Host Device
(Two RS-232
Ports)
The 3402 AIM has one RS-485
port and two RS-232 ports.
When AIMs are multidropped on
a RS-485 network and
connected to a host device, the
RS-232 ports can be used by
other host systems to
communicate with the HIUs and
SAMs connected to that AIM. In
this configuration the RS-232
port of one AIM cannot
communicate with HIUs or SAMs
connected to another AIM.
Figure 3 shows the lines of
communication for a network
using a straight RS-485 host
device configuration.
The 3402 AIM has one RS-485
port and two RS-232 ports.
When AIMs are multidropped on
the RS-485 network and one
AIM is used as the master AIM,
one RS-232 port communicates
with the host device. The
second RS-232 port on the
master AIM may be used with a
host to communicate to any HIU
or SAM connected to any of the
AIMs on the RS-485 network.
Figure 4 shows the lines of
communication for a network
using a master AIM
configuration.
Rosemount
3201 HIU
Rosemount
3202 SAM
Rosemount
3201 HIU
Rosemount
3202 SAM
Rosemount
3402 Master
AIM
RS-485 Modbus
Rosemount
3402 AIM
RS-232
3402
-000
0A03
D
Host System
Modbus
Communications and Power
(MCAP)
Up to 14 Rosemount 3201 HIUs
or 3202 SAMs
(Any Combination)
Modbus
Communications and Power
(MCAP)
Up to 14 Rosemount 3201 HIUs
or 3202 SAMs
(Any Combination)
Up to 31
Devices
Total
(Any
Combination)
Product Data Sheet00813-0100-4641, Rev CB
August 2003
5
Rosemount 3402
Specifications
Functional Specifications
Power Input Options
115 V ac, 58/62 Hz 230 V ac, 48/62 Hz
Power Quality Requirements
115 V ac: 103.5 to 126.5 V ac
230 V ac: 207 to 250 V ac
MCAP Power Options
Standard: 48 V dc nominal
(47 V dc min., 49 V dc max.), up to 500 mA
Low Voltage: 31 V dc nominal
(30 V dc min., 32 V dc max.), up to 500 mA
MCAP Power Limitations
Up to 14 Rosemount 3201 HIUs or 3202 SAMs (in any
combination) each drawing 31.5 mA with two HART® devices.
Environmental
Operating Temperature Range: –40 to 70 °C (–40 to 158 °F)
Operating Humidity Range: 0–95% relative humidity
(non-condensing)
NEMA 4X protection standard
Lightning and Surge Protection
Surge protection is provided on the 3402 MCAP lines and on the
Modbus RS-485 communication lines. This surge protection meets
the requirements of ANSI/IEEE C62.41-1980
categories A and B.
RFI/EMI
Per SAMA PMC 33.1-1978 Class 2
Performance Specifications
Device Signal (MCAP)
2-wire Modbus Communication and Power (MCAP) data highway
supporting up to 14 devices.
Host Signal
2- or 4-wire Modbus RS-485 multidrop
Two Modbus RS-232 ports. One port user selectable to operate as
a DTE or DCE.
Baud Rate
MCAP Network: user selectable 38400 or 9600
Modbus Host Network: user selectable 19200, 9600, 2400, or
1200
Data Type
Modbus RTU or ASCII
Physical Specifications
Weight
10.7 lb (4.85 kg)
Wiring
MCAP Signal Wiring: one twisted shielded pair, 18 AWG. Wiring
distance is approximately 5,000 feet (1,524 meters) with 14 HIUs
or SAMs, in any combination with 2 HART devices connected. For
more information, see the HIU product data sheet–PDS 4640.
Modbus Host Signal Wiring: RS-485 one or two twisted shielded
pair, 18 AWG. Wiring distance is approximately 5,000 feet (1,524
meters). RS-232 standard serial communication with a RJ45 type
connector which can be used with a 25-pin male or female
connector or a 9-pin male or female connector. Wiring distance is
approximately 50 feet (15.24 meters).
NOTE
One 25- or 50-foot (7.62 or 15.24 meters) cable with 9- or 25-pin
connector can be provided with each AIM. See the ordering table
for more information.
Hazardous Locations Certifications
Factory Mutual (FM) Approval
N5 Approved for Class I, Division 2, Groups A, B, C, and D;
Dust-Ignition Proof, Class II and III, Division 1, Groups E, F,
and G, hazardous locations. Indoor and outdoor (NEMA 4X).
Temperature code T4.
Canadian Standards Association (CSA) Approval
N6 Approved for Class I, Division 2, Groups A, B, C, and D;
Dust-Ignition Proof, Class II and III, Division 1, Groups E, F,
and G, hazardous locations. Indoor and outdoor (CSA
enclosure 4). Temperature code T4A.
Location
Category
Wave
form
Medium
Exposure
Amplitude Type of Load
A .5�s–
100KHz
6KV
200A
High Impedance
Low Impedance
B 1.2 � 50�s
8 � 20 �s
6KV
3KA
High Impedance
Low Impedance
.5�s–
100KHZ
6KV
500A
High Impedance
Low Impedance
Product Data Sheet00813-0100-4641, Rev CB
August 2003Rosemount 3402
6
Dimensional Drawings
FIGURE 5. Rosemount 3402 Application Interface Module Dimensional Drawing.
3.51
(89) 2.81
(71)
3.11
(79)
9.01 (229)
0.44 (11)
11.15
(283)
12.01
(305)
11.37
(289)
17.78 (452)
Approval Label
Nameplate
Cast
Aluminum
Cover
Junction
Box Cover
2.96
(75)
Warning
Labels
¾–14 NPT
Conduit
Connection
(Three places)
Ground LugNOTE
Dimensions are in inches (millimeters).
Product Data Sheet00813-0100-4641, Rev CB
August 2003
7
Rosemount 3402
FIGURE 6. Rosemount 3402 Application Interface Module Detailed View
Cast Aluminum Housing
Terminal Block and Replaceable Fuse
Warning
Labels
Power Supply Board
Microprocessor Board
MCAP
Terminator
Cable
25-Pin (or 9-Pin)
Connector
Cast
Aluminum
Cover
Warning Label
Warning Label
RS-232
Ports
Junction
Box
Cover
3402-0
001C
04A
0001B
04A
01
00A
01A
, 3402-0
000A
01A
Product Data Sheet00813-0100-4641, Rev CB
August 2003 Rosemount 3402
Emerson Process Management
© 2004 Rosemount Inc. All rights reserved.
Rosemount and the Rosemount logotype are registered trademarks of Rosemount Inc.PlantWeb is a mark of one of the Emerson Process Management companies.All other marks are the property of their respective owners.Cover Drawing: 3402_0000b02c
¢00813-0100-4641Z¤
Rosemount Inc.8200 Market BoulevardChanhassen, MN 55317 USAT (U.S.) 1-800-999-9307T (International) (952) 906-8888F (952) 949-7001
www.rosemount.com
Emerson Process ManagementHeath PlaceBognor RegisWest Sussex PO22 9SHEnglandTel 44 (1243) 863 121Fax 44 (1243) 867 5541
Emerson Process Management Asia Pacific Private Limited1 Pandan CrescentSingapore 128461T (65) 6777 8211F (65) 6777 0947/65 6777 0743
Ordering Information
Rosemount Smart Family® Instruments
Rosemount SMART FAMILY instruments include pressure,
temperature, level, and flow measurement.
All SMART FAMILY instruments are designed to communicate
using HART (Highway Addressable Remote Transducer) protocol
with the hand-held HART Communicator and Fisher-Rosemount
Control Systems.
Model Product Description
3402 Application Interface Module (AIM)
Code Power Input Option
A 115 V ac Power Input
B 230 V ac Power Input
Code MCAP Output Option
1 Standard Output (48 V dc nominal)
2 Low Voltage Output (31 V dc nominal)
Code RS-232 Cable Length Option
A None
B 25 ft (7.62 meters)
C 50 ft (15.24 meters)
Code RS-232 Connector Option
A None
B RJ45 to DB25 Male
C RJ45 to DB25 Female
D RJ45 to DB9 Male
E RJ45 to DB9 Female
Code Number of MCAP Line Terminators
1 One Line Terminator
2 Two Line Terminators
3 Three Line Terminators
Code Options
N5 Factory Mutual (FM) Division 2 Approval (Non-incendive)
N6 Canadian Standards Association (CSA) Approval
Q8 Material Traceability Certification per EN102043.IB
Typical Model Number: 3402 A 1 B C 1 N6
SMART FAMILY Companion Products
00813-0100-4275 HART Communicator
Hydrostatic Tank Gauging
00813-0100-4635 Rosemount 3001C Hydrostatic Pressure Transmitter
00813-0100-4638 Rosemount 3001CL Flush-mount Hydrostatic
Pressure Transmitter
00813-0100-4640 Rosemount 3201 Hydrostatic Interface Unit
00813-0100-4641 Rosemount 3402 Application Interface Module
00813-0100-4646 Rosemount 3202 Smart Application Module
00813-0100-4702 Rosemount 3001CH Hydrostatic Pressure
Transmitter for High Process Temperatures