24
THIS OPERATING PROCEDURE IS FOR TRANSAS TRAINING SIMULATOR USE ONLY Sea Water System System Preparation and Putting in Operation 1. Open the upper sea chest (when in port) – UPPER CHEST. 2. Check that the overboard valve is open. 3. Start the pump (“PUMP 1” or “PUMP 2” button in MANUAL mode). 4. Open the FW COOLER water cooler valve, the LO COOLER oil cooler valve of ME. 5. Open the COMPR. COOLER, CPP Servo and REDUCTION GEAR cooler valves. 6. Check water pressure in the system. 7. Switch the pump control mode to AUTO. 8. Switch the recirculation valve control mode AUTO. 9. Specify SET POINT for the temperature controller. 10. Check that there is no alarm signal in the system. Control Over System Operation 1.When putting to sea, switch over to the lower sea chest – LOWER CHEST. 2. Check water pressure in the system. 3. Check water temperature after/before the coolers. 4. Check for correctness of temperature controller operation – maintaining the proper temperature value. 5. Adjust the rate of flow through the air cooler using the SCAV. AIR COOLER FLOW valve to maintain scavenge air temperature within the working range. 6. Check that there is no alarm signal in the system. Switching Over to In-Port Mode 1. When in port, switch over to the upper chest – UPPER CHEST. 2. Switch the pump control mode to MANUAL. 3. Stop the pump (PUMP 1, PUMP 2 in MANUAL mode). 4. Start the auxiliary (port) pump – AUX. PUMP. 5. Shut the valves of the unused coolers. Fresh Water System System Preparation and Putting in Operation 1. Check if there is water in the both expansion tanks. Add, if necessary (“TANK MAKE UP” button and “MAKE UP” button). 2. Start the pump (“PUMP 1” or “PUMP 2” button in MANUAL mode). 3. Adjust pressure before diesel using the valve ME FLOW, check if there is water flow through the diesel. 4. Switch the pump control mode to AUTO.

RoRo Operating Procedures

Embed Size (px)

DESCRIPTION

RoRo

Citation preview

Page 1: RoRo Operating Procedures

THIS OPERATING PROCEDURE IS FOR TRANSAS TRAINING SIMULATOR USE ONLY

Sea Water System System Preparation and Putting in Operation 1. Open the upper sea chest (when in port) – UPPER CHEST. 2. Check that the overboard valve is open. 3. Start the pump (“PUMP 1” or “PUMP 2” button in MANUAL mode). 4. Open the FW COOLER water cooler valve, the LO COOLER oil cooler valve of ME. 5. Open the COMPR. COOLER, CPP Servo and REDUCTION GEAR cooler valves. 6. Check water pressure in the system. 7. Switch the pump control mode to AUTO. 8. Switch the recirculation valve control mode AUTO. 9. Specify SET POINT for the temperature controller. 10. Check that there is no alarm signal in the system. Control Over System Operation 1.When putting to sea, switch over to the lower sea chest – LOWER CHEST. 2. Check water pressure in the system. 3. Check water temperature after/before the coolers.

4. Check for correctness of temperature controller operation – maintaining the proper temperature value. 5. Adjust the rate of flow through the air cooler using the SCAV. AIR COOLER FLOW valve to maintain scavenge air temperature within the working range. 6. Check that there is no alarm signal in the system. Switching Over to In-Port Mode 1. When in port, switch over to the upper chest – UPPER CHEST. 2. Switch the pump control mode to MANUAL. 3. Stop the pump (PUMP 1, PUMP 2 in MANUAL mode). 4. Start the auxiliary (port) pump – AUX. PUMP. 5. Shut the valves of the unused coolers. Fresh Water System System Preparation and Putting in Operation 1. Check if there is water in the both expansion tanks. Add, if necessary (“TANK MAKE UP” button and “MAKE UP” button). 2. Start the pump (“PUMP 1” or “PUMP 2” button in MANUAL mode). 3. Adjust pressure before diesel using the valve ME FLOW, check if there is water flow through the diesel. 4. Switch the pump control mode to AUTO.

Page 2: RoRo Operating Procedures

THIS OPERATING PROCEDURE IS FOR TRANSAS TRAINING SIMULATOR USE ONLY

5. Switch the thermostatic valve control mode to AUTO. 6. Specify SET POINT for the temperature controller. 7. Open valve of a coolers - COOLER 1 or COOLER 2 and INJECTORS COOLER (FW side and Injectors water side). 8. Start the Injectors cooling system pump (“PUMP 1” or “PUMP 2” button in MANUAL mode). 9. Switch the injectors pump control mode to AUTO. 10. Check that there is no alarm signal in the system. Control Over System Operation 1. Check water pressures before diesel, after injectors cooling system pump, before injectors. 2. Check that there is water flow through the diesel. 3. Check that there is water flow through the each injector. 4. Check water temperatures before and after diesel. 5. Check water temperatures before and after injectors. 6. Check for correctness of temperature controller operation – maintaining the proper temperature value. 7. Check level in the both expansion tanks. 8. Check for alarm signals in the system. Switching Over to In-Port Mode

1. Retain the system running mode for 40 – 60 min. after ME stop. 2. Switch the pumps control mode to MANUAL. 3. Stop the pumps. 4. Use the “PORT MODE” button to switch ME to heating from the running Diesel Generator(s). 5. Open valve of a engine Oil Heater. 6. Check that there is water flow through system. Fuel System System Operation System Preparation and Putting in Operation 1. Check the level in the DO service tank. Drain sludge (the “DO DRAIN” button). Fill up the tank, if necessary (the DO TRANSFER PUMP in the FOT system – the “START/STOP” button). 2. Check the level in the HFO service tank. Drain sludge (the “DRAIN” button). Fill up the tank, if necessary (SEPARATOR in the FOT system – the “START/STOP” button). 3. Check temperature in the heavy fuel service tank – HFO TANK. Turn ON HFO TANK HEATING, if necessary. 4. Set switches of fuel type selection for ME and DG’s to the required position: HFO-OFF-DO and AE1-AE2, respectively. 5. When running on heavy fuel oil – turn ON the heating of the fuel pipelines by the “TRACING” button.

Page 3: RoRo Operating Procedures

THIS OPERATING PROCEDURE IS FOR TRANSAS TRAINING SIMULATOR USE ONLY

6. Start the supply pump (the “PUMP 1” or “PUMP 2” button of the “SUPPLY PUMPS” module, in MANUAL mode). Check its operation on the pressure gauge. 7. Switch the pump control mode to AUTO. 8. When running on heavy fuel oil, open the preheater valves (the PREHEATER “ON” button); if operating on diesel oil, open the bypass valve (the “PREHEATER BYPASS” button). 9. Check fuel pressure before diesel (the ENGINE INLET pressure gauge). 10. Check filter pressure drop (the FILTER DROP pressure gauge); change over to the filter stand-by section, if necessary. 11. Switch to the MANUAL mode of thermostatic valve control. 12. Use the HEATING controller to adjust fuel temperature before diesel (PREHEATER OUTLET). 13. Check that there is no alarm signal in the system. Control Over System Operation 1. After starting the diesel, switch to the AUTO mode of thermostatic valve control. 2. Specify SET POINT for the temperature controller. 3. Check fuel temperature before diesel. 4. Check for correctness of temperature controller operation – maintaining the proper temperature value. 5. Check fuel pressure before diesel.

6. Check pressure drop through the filter; change over to the stand-by section of the fuel, if necessary. 7. Check the flow rate for the fuel from the service tanks. 8. Check the level in the DO service tank. Drain sludge (the “DO DRAIN” button). Fill up the tank, if necessary (the DO TRANSFER PUMP in the FOT system –the “START/STOP” button). 9. Check the level in the HFO service tank. Drain the sludge (the “DRAIN” button). Fill up the tank, if necessary (SEPARATOR in the FOT system – the “START/STOP” button). 10. Check temperature in the heavy fuel service tank – HFO TANK. Turn ON HFO TANK HEATING, if necessary. 11. Check that there is no alarm signal in the system. Switching Over to In-Port Mode 1. If your stay in port is of short duration, you can continue to use the running mode of the FOS system for the purpose of being ready for operation on heavy fuel oil. 2. Before a long-duration stay, change the system in due time to DO before manoeuvring. 3. Switch to the MANUAL mode of thermostatic valve control. 4. Set the fuel type selection switch HFO–OFF–DO of the main engine to the DO position. 5. Use the HEATING controller to gradually reduce fuel temperature before diesel (PREHEATER OUTLET). 6. Check fuel pressure before diesel (the ENGINE INLET pressure gauge).

Page 4: RoRo Operating Procedures

THIS OPERATING PROCEDURE IS FOR TRANSAS TRAINING SIMULATOR USE ONLY

7. Open the preheater bypass valve (the “PREHEATER BYPASS” button), close the preheater valves (the PREHEATER “ON” button). 8. Turn ON the fuel pipeline heating using the “TRACING” button. 9. After stopping the diesel, change control of the fuel-supply pumps to the MANUAL mode; stop the pumps.

Fuel Oil Transfer System System Operation DO Service Tank Replenishment 1. Start the DO TRANSFER PUMP to transfer diesel oil from the DO bunker to the DO service tank (the “START/STOP” button). 2. Check pump operation using the pressure gauges on the suction side (SUCTION) and the discharge side (DISCHARGE). 3. Check the fuel level in the DO service tank. 4. Stop the pump in time to prevent overflow. HFO Settling Tank Replenishment 1. Turn ON the heating of the HFO bunker in due time to provide for its normal transfer. 2. Turn ON the heating of the fuel pipelines by the “TRACING” button. 3. Set the HFO TRANSFER PUMP suction switch to the required position i.e From Bunker or From Spill Tank. 4. Start the HFO TRANSFER PUMP (the “START/STOP” button).

5. Check pump operation using the pressure gauges on the suction side (SUCTION) and the discharge side (DISCHARGE). 6. Check the level in the HFO settling tank. 7. Stop the pump in time to prevent overflow. 8. Turn ON the fuel pipeline heating using the “TRACING” button. HFO Service Tank Replenishment 1. Turn ON the heating of the HFO settling tank in due time to provide for it’s normal transfer. 2. Drain sludge. 3. Set the separator suction switch (SUCTION) to the FROM SETTLE position. 4. Set the separator discharge switch (DISCHARGE) to the TO SERVICE position. 5. Turn ON the heating of the fuel to be treated. 6. Start the separator(s) – please see the page OFS. 7. Check the fuel level in the HFO service tank and stop the separator in time to prevent overflow. 8. Turn OFF the heating of the separated fuel.

Page 5: RoRo Operating Procedures

THIS OPERATING PROCEDURE IS FOR TRANSAS TRAINING SIMULATOR USE ONLY

Lube Oil Separators System Operation Separators 1 and 2 in the simulator are intended for the fuel purification or clarification, if necessary. Separator 3 in the simulator is intended for the clarification of the lubricating oil. Separators 1 and 2 can operate:

• In parallel – in this case both separators operate separately;

• In series – in this case, e.g. separator 1 operates in the purification mode, whereas separator 2 operates in clarification mode (for example). Serial or parallel operation of separators is enabled by the pipeline valve which opens the supply of non-purified fuel oil in separator 2 (“TO SEP. 2” button) and three-way valve at the outlet from separator 1 (“PARALLEL – IN SERIES” switch). Before starting the separator(s), it is necessary to supply operating water in the system (“WATER ON”) and open supply of opening and closing water in the separators (“OPEN WATER” and “CLOSING WATER” buttons).

Starting the Separator 1. In the simulator, the separator is started in the manual control mode: “AUTO-MANUAL” switch is in “MANUAL” position. 2. Select the separator operating mode: “Purification” or “Clarification” buttons. 3. Check the separator Brake – “BRAKE” button must be off. 4. Open “WATER ON” valve.

5. Lock the bowl. Feed the closing water – “CLOSE” button. Check the status of the “OPEN” button (must be off). 6. Start the separator drive electric motor (“START” button). Check that the separator bowl develops its rated revolutions (about 10000 rpm). As this is done, the bowl is opened, and the remains of water, product and sludge are removed from it. 7. Open “FUEL INLET” valve. 8. Turn on the pump for supplying the product to the separator (“FEED PUMP” button is on). As this is done, “FLOW” valve feeding fuel to the separator is closed. 9. Turn on the heating (“HEATING” button) and set the required product temperature (“SET POINT, oC” controller). 10. Supply the operating water for water lock – “OPER. WATER” button and the bowl is filled with water until the water appears in the indicator (peep-hole) in the water drain line. 11. The separator bowl is filled with fuel - “FLOW” valve opens slowly to supply the product to the separator (check the required fuel temperature before). The product pressure at the separator outlet (“BACK RESSURE”) is controlled with the aid of “SET POINT, bar” controller. If the waterlock is broken because of the high back pressure, it is necessary to reduce the back pressure by 0,5-1 bars and/or to decrease the fuel feed. Safety solenoid valve is opened if back pressure more than 1 bar and closed if back pressure less then 0,8 bar or in emergency, if sludge or water will appeared in separator outlet (product discharge line). Back pressure regulator especially significant in manual mode. In automatic mode, “WATER DRAIN” valve is closed, if water level in bowl is reduced. Use “AUTO-MANUAL” switch to switch the separator to “AUTO” mode. 12. Set the time of removing the sludge from the separator bowl – the time is set by using “TIME, min” controller (in “AUTO” mode).

Page 6: RoRo Operating Procedures

THIS OPERATING PROCEDURE IS FOR TRANSAS TRAINING SIMULATOR USE ONLY

13. Check the separation quality – water content in the product before/after the separator or the content of solid particles. It’s simulated by “WATER CONTENTS, % – INLET/OUTLET” and “IMPURITY, ppm – INLET/OUTLET” displays. 14. Check the separator operating parameters by using the indicators on the control panels. Separator Washing 1. The separator operates in “AUTO” mode. 2. Empty the bowl (“DISCHARGE” button). 3. Switch the separator to “MANUAL” mode. 4. Supply closing water – “CLOSE” button. 5. Supply operating water – “OPER. WATER” button. The bowl is filled with water and is washed. 6. Empty the bowl. Operations can be repeated several times depending on how dirty the separator is. Stopping the Separator 1. The separator operates in “AUTO” mode. 2. Empty the bowl (“DISCHARGE” button). 3. Switch the separator to “MANUAL” mode. 4. Cut the water supply to the separator. 5. Stop the separator drive electric motor (“STOP” button).

6. Brake the separator (“BRAKE” button). 7. In emergencies, use “EMERGENCY STOP” button. Specific Features of Separator Operation in Clarification Mode In the case of product clarification, the sludge and remains of water are removed at regular intervals rather than constantly. The sludge is removed either when some amount of it is accumulated in the bowl (by level) or over a certain time interval (by timer). In the separation of lubricating oil, hot operating water used for clarifying the lub. Oil – it is deoxidation in MANUAL control mode.

Lubricating Oil Systems System Operation System Preparation and Putting in Operation 1. Check the level of lube oil in the both oil tanks. If replenishment is required, use the MAKE UP valves. 2. Open the valve of an oil heater (“HEATER” button). 3. Start Pump 3 for engine pre-lubricating and preheating (“PUMP 3” button). Make sure there is pressure in the system. Stop Pump 3 after engine pre-lubricating and preheating. 4. Set the PRESSURE LIMIT valve of pressure adjustment to the position that ensures the minimum pressure in the system. 5. Switch the thermostatic valve control mode to AUTO.

Page 7: RoRo Operating Procedures

THIS OPERATING PROCEDURE IS FOR TRANSAS TRAINING SIMULATOR USE ONLY

6. Specify SET POINT for the temperature controller. 7. Open the valve of a cooler: COOLER 1 or COOLER 2. 8. Select the MANUAL mode for the main circulation oil pumps and start of them (the “PUMP 1” or” PUMP 2” button). Make sure there is pressure in the system. 9. Adjust pressure before diesel using the PRESSURE LIMIT valve. 10. Set the circulation oil pump control to the AUTO mode. 11. Select the MANUAL mode for the valve rockers oil pumps and start of them (the “PUMP 1” or” PUMP 2” button). Make sure there is pressure in the system. 12. Set the valve rockers oil pump control to the AUTO mode. 13. Make sure there is no alarm signals in the LO system. Control Over System Operation 1. Check the pressure of oil before diesel (engine inlet). 2. Check the level of oil in the both collecting tanks. If replenishment is required, use the MAKE UP valves. 3. Check pressure drop through the filters (of both systems); change over to the stand-by section of the fuel, if necessary. 4. Check the temperature oil before diesel (engine inlet). 5. Check flow and temperature of oil at its exit after piston cooling, for each cylinder.

6. Check for correctness of temperature controller operation – maintaining the proper temperature value. 7. Check for alarm signals in the LO system. Setting the System to the In-Port Mode 1. Maintain the system running mode for 60 to 80 min. after stopping ME. 2. Switch over to the MANUAL mode of oil pump control (both sub-systems). 3. Set the PRESSURE LIMIT valve of pressure adjustment for minimum pressure. 4. Stop the running oil pumps.

Compressed Air System System Operation System Preparation and Putting in Operation 1.Blow down the RECEIVER 1, RECEIVER 2 bottles (the “BLOW DOWN” module). 2. Open the bottle 1 valves (the “RECEIVER 1” module) – FROM COMPRESSOR. 3. Open the bottle 2 valves (the “RECEIVER 2” module) – FROM COMPRESSOR. 4. Make sure the cooling of components is ON in the SW system.

Page 8: RoRo Operating Procedures

THIS OPERATING PROCEDURE IS FOR TRANSAS TRAINING SIMULATOR USE ONLY

5. Start the compressor (the “STOP”/“START” buttons for COMPRESSOR 1 and COMPRESSOR 2 in MANUAL mode), fill up both bottles up to 30 bar. 6. Set compressor control to the AUTO mode. 7. Open the bottle 1 valves (the “RECEIVER 1” module) – START AIR, CNTRL. AIR. 8. Check that there is no alarm signal in the system. Control Over System Operation 1. Check and maintain proper pressure in bottle 1. 2. In emergency, if short of compressed air supply, open the valves of bottle 2 (the “RECEIVER 2” module) – START AIR, CNTRL. AIR. 3. Regularly blow down the RECEIV. 1, RECEIV. 2 bottles (the “BLOW DOWN” module). 4. When starting the compressor, check operation of the SEPARATOR valve designed for automatic blow-down of the water separator (the “BLOW DOWN” module). 5. Control over the reducing station on the CONTROL AIR pressure gauge. 6. Check that there is no alarm signal in the system.

Controllable Pitch Propeller System Preparation and Putting in Operation CPP pitch setter: 1. Check oil level in the CPP hydraulic drive oil tank. Replenish the tank using the “MAKE UP” valve, if necessary. 2. Start the pump; make sure it creates the working pressure (about 40 bar for maintaining a specified pitch, and about 70 bar for changing it). 3. Set the pump control mode switch to AUTO – the stand-by pump will start automatically in case of pressure drop in the system. 4. Check filter pressure drop, if the filter is fouled, switch over to the second one. 5. In the SW system, open the valve that supplies water to the CPP oil cooler; oil temperature is maintained automatically by the three-way thermostatic valve. Clutch, reduction gear: Clutch, reduction gear: 1. Before starting the diesel, check oil level in the reduction gear splash pan; replenish it, if necessary. 2. Start the stand-by electric pump to circulate oil through the reduction gear bearings (the “PRIMING” button). 3. Check pressure on the LUB. PRESSURE gauge of the “REDUCTION GEAR” module on the CPP page. 4. Check filter pressure drop on the PRESSURE DROP pressure gauge, if the filter is fouled, switch over to the second one.

Page 9: RoRo Operating Procedures

THIS OPERATING PROCEDURE IS FOR TRANSAS TRAINING SIMULATOR USE ONLY

5. In the SW system, open the valve that supplies water to the reduction gear oil cooler; the oil temperature being maintained automatically by the three-way thermostatic valve. 6. After starting the diesel, turn the electric pump off and check oil pressure on the CLUTCH PRESSURE and LUB. PRESSURE gauges in the “REDUCTION GEAR” module on CPP page. 7. To engage the clutch, press the “ON” button in the “CLUTCH” module on the ME page, when the “READY” indicator is highlighted. When the clutch engages, the “ENGAGED” indicator will be highlighted. The “PROPELLER RPM” indicator on the ME page shows the current propeller shaft revolution speed. 8. To avoid clutch overheating, do the engagement at a maximum diesel revolution of 380 RPM. 9. To avoid diesel overloading, do the clutch engagement at the zero propeller pitch. Stern tube – check oil level in the header tanks, make use of the “MAKE UP” button, if needed. Control Over System Operation CPP pitch setter: 1. All system faults are reported by the alarm indicators on the CPP page. 2. Pressure, oil temperature, and oil filter pressure drop are monitored by the corresponding instruments (PRESSURE, OIL TEMP, and FILTER DROP respectively). The oil level in the tank should be also checked. 3. The current position of propeller blades can be checked on the PROPELLER PITCH instrument. Clutch, reduction gear:

1. All system faults are reported by the alarm indicators on the CPP page. 2. Pressure, oil temperature in the system, thrust bearing temperature, and oil filter pressure drop are maintained by the corresponding instruments. The oil level in the reduction gear splash pan should be also checked. 3. Clutch slipping can be identified by reduction of propeller shaft revolutions as compared with a constant diesel revolution speed. Stern tube: 1. Check oil level in the header tanks. 2. Condition of stern tube bearings should be checked on the temperature of oil in the stern tube. Setting the System to the In-Port Mode CPP pitch setter: 1. Set the pump control mode switch to MANUAL. 2. Stop the operating pump. 3. Turn off the valve that supplies water to the CPP oil cooler on the “SOFTWARE” page. Clutch, reduction gear: 1. To avoid a dramatic increase of diesel revolutions, the clutch should be disengaged at the zero propeller pitch. 2. To disengage the clutch, press the “OFF” button in the “CLUTCH” module on the ME page. When the clutch disengages, the ‘DISENG.” indicator will be highlighted. 3. After stopping the diesel, start the electric oil pump to circulate oil through the reduction gear bearings to cool them gradually down.

Page 10: RoRo Operating Procedures

THIS OPERATING PROCEDURE IS FOR TRANSAS TRAINING SIMULATOR USE ONLY

Main Engine Start System Preparation and Putting in Operation Turn ON the ARC system by the “CNTRL ON” button. In case of joint work with the NTPro navigation simulator, select in cooperation with the bridge a control station (BRIDGE or ECR). In case of the simulator’s stand-alone mode, select ECR as the control station. Check for readiness of the other systems. Open the main start valve, check start air pressure using the START AIR PRESSURE indicator. If necessary, set the maximum limit for CPP pitch using the “Pitch Limit” controller. Select a control mode: “Fixed R.P.M. – Combined Mode”. If the “Fixed R.P.M.” is selected, engage the reduction gear clutch using the “On” button. The ET lever should be in the “STOP” position, which corresponds to the zero CPP pitch. Start ME using the “Start” button. The engine will run up the rated revolution. In case of the “Combined Mode” mode selected, start ME using the “START” button. The ET lever should be in the “STOP” position, which corresponds to the zero CPP pitch and ME idle revolutions. Then engage the clutch by the “On” button. Diesel Control Diesel operation mode setting comes to the ARC system:

• In the BRIDGE CONTROL model – from the engine telegraph located on the bridge; • In the ECR CONTROL mode – from the engine telegraph located in ECR, being monitored by SPEED SETPOINT digital indicator.

The current mode of diesel operation is monitored using:

– LOAD DIAGRAM; – ME RPM meter, CPP revolution indicator CPP pitch indicator; – Digital POWER indicator; – FUEL INDEX analog/digital indicator of FUEL INDEX fuel lever position.

2. The SPEED digital indicator monitors ship’s speed. 3. The Slow Down and Shut Down indicators register actuation of the safety diesel protection system. The safety system can be unlocked using the “SAFETY RESET” button. To turn OFF the safety system, press the “EMERGENCY RUN” button. 4. To stop diesel in emergency, use the “EMERGENCY STOP” button. 5. Emergency CPP control is performed using the “Astern”/“Ahead” buttons with a depressed “ON” button.

Page 11: RoRo Operating Procedures

THIS OPERATING PROCEDURE IS FOR TRANSAS TRAINING SIMULATOR USE ONLY

ELECTRICAL SYSTEM Electrical System Operating Instructions This section provides recommendations for SEPS preparation for operation, setting to work and operation. SEPS Control SEPS Manual Control Mode • Turn the CONTROL MODE switch to the MANUAL position; • Control of generators and consumers on the switchboards 24VDC, 220VAC and 380VAC should be performed in the manual mode. SEPS Control in the Automatic Mode • Turn the CONTROL MODE switch to the AUTOMATION position; • Apply power to the diesel generator GBC’s (turn the CIRCUIT BREAKER SUPPLY switch to position “1”); • Select an automatic control mode for SEPS (EQUAL, CYCLIC, OPTIMAL or CONST FREQ.); • Control of consumers on the switchboards 24VDC, 220VAC and 380VAC should be performed in the manual mode.

Page 12: RoRo Operating Procedures

THIS OPERATING PROCEDURE IS FOR TRANSAS TRAINING SIMULATOR USE ONLY

Auxiliary Diesel Engine Control Startup Preparation

• Turn on the oil priming pump (set the PRE-LUBRICATION switch to RUN);

• TURN ON ENGINE preheating (open the cut-off valve in the freshwater system)m (depress the “PREHEATING ON” button).

Standard Start Depress the “START” button. At this moment, if pressure in the lubrication system is below 2.0 bar, the electric oil-priming pump will be switched on prior to air supply. When the pressure reaches the specified value, the diesel engine will be started. The engine is brought down to 80% of its rated RPM and is maintained at this RPM for 35 seconds for heating the cooling water and lubrication oil. Then the RPM is brought to the rated value, and the engine is ready to accept 50% of load. After another 2 minutes the engine is ready for 100% load. Emergency Start Press the “EMCY START” button. In this case, the engine will be started without checking the initial oil pressure, and come to its rated RPM in minimum time. Standard Shut Down

• Remove the generator from MSB buses using the “DISCONNECT” button of the GCB;

• Depress the “STOP” button, In case of a standard stop, the engine is brought down to 80% of its rated RPM and is maintained at this RPM for 1 minute. The engine is then stopped by cutting off the fuel supply. SEPS Operation Instructions

Emergency Stop Press the “EMCY STOP” button, which will result in automatic disconnection of the generator circuit breaker and fuel supply cutting off. The “EMCY START”, “EMCY STOP” buttons are of higher priority. If the engine is started by using first the “START” button and then the “EMCY START”, it will be started according to the emergency start procedure from the moment of pressing the “EMCY START” button. In this case no return to the standard start program is possible. The “STOP” and “EMCY STOP” button have a similar way of operation. Coupling the Auxiliary Diesel Generator Closing to Dead MSB Buses

• Start the engine;

• Check that generator frequency has reached 50 Hz (engine preheated and reached 100% of its rate RPM), and generator voltage has reached 400V;

• Supply power to GCB (CIRCUIT BREAKER SUPPLY in position

“1”);

• Arm GCB, if applicable (move the HAND DRIVE handle to the upper position);

• Press the “CONNECT” button.

Page 13: RoRo Operating Procedures

THIS OPERATING PROCEDURE IS FOR TRANSAS TRAINING SIMULATOR USE ONLY

Switching to the Parallel Operation (MSB Energized)

• Start the diesel engine;

• Check that generator frequency has reached 50 Hz (engine preheated and reached 100% of its rate RPM), and generator voltage has reached 400V;

• Supply power to GCB (CIRCUIT BREAKER SUPPLY in position “1”);

• Arm GCB, if applicable (move the HAND DRIVE handle to the upper position);

• Synchronize the generator to be connected to MSB buses manually or automatically.

Manual synchronization: – use the “More/Less” buttons of the DG frequency regulation system (GOVERNOR CONTROL 2) to adjust the frequency of the generator to be closed to the MSB frequency. The frequency of the generator to be closed should slightly exceed the MSB frequency. Monitoring is performed using the frequency meters on the synchronization section; – use the “More/Less” buttons of the DG frequency regulation system (GOVERNOR CONTROL) to reduce the phase difference (phase displacement) between the generator voltage and the MSB voltage. Monitoring is performed using the synchronoscope;

– at the moment of the zero phase difference (the (“12 o’clock” indicator illuminates at the synchronoscope) or a minimum phase

difference, press the “CONNECT GCB” button for the generator to be synchronized.

Automatic synchronization:

– press the selection button for the generator to be synchronized at the synchronization section (DG1, DG2); – move the synchronization mode switch to the AUTO position. The moment of moving the synchronization mode switch to the AUTO position is the synchronization process starting moment. On completion of the synchronization process, the synchronized generator will be closed to the MSB buses. Then the synchronization mode selection switch will automatically return from the AUTO position to the MANUAL position.

Active Power Distribution in Parallel Operation Use the “More/Less” buttons of the DG frequency regulation system (GOVERNOR CONTROL) to change the generator active power. The active load increases with frequency. Monitoring of the active load is performed using the wattmeter on the MSB generator section. Reactive Power Distribution in Parallel Operation Adjust generator voltage using the handle of the automatic voltage regulator controller (VOLTAGE). The reactive load increases with voltage. Monitoring of the reactive load is performed using the reactive-power meter on the MSB generator section. Taking Generator out of Parallel Operation

• Use the “More/Less” buttons of the DG frequency regulation system (GOVERNOR CONTROL) do decrease generator load down to 50kW to 100 kW. The active load decreases with

Page 14: RoRo Operating Procedures

THIS OPERATING PROCEDURE IS FOR TRANSAS TRAINING SIMULATOR USE ONLY

frequency. Monitoring of the active load is performed using the wattmeter on the MSB generator section; • Press the “GCB DISCONNECT” button.

Shaft Generator Drive Control Standard Coupling Engagement

• The clutch can be switched on, if the READY TO CLUTCH TURN indicator illuminates (when oil pressure in the gearbox is above 2 bar; the temperature being above 30°C);

• Press the “CLUTCH ON” button before the gearbox speed

doesn’t exceed 400 RPM. Emergency Coupling Engagement Press the “CLUTCH ON” button. Coupling Disengagement Press the “CLUTCH OFF” button. Coupling the Shaft Generator Closing to Dead MSB Buses • Switch on the ShG drive clutch; • When ShG speed frequency reaches 47.5 Hz to 50 Hz, press the “GENERATOR

EXCITATION ON” button, i.e. supply power to the generator excitation winding;

• Check that generator voltage has reached 400V;

• Energize GCB (CIRCUIT BREAKER SUPPLY);

• Wind the GCB springs (HAND DRIVE), if necessary;

• Press the “CONNECT” button. Setting to the Parallel Operation (MSB Energized)

• Switch on the ShG drive clutch;

• When ShG speed frequency reaches 47.5 Hz to 50 Hz, supply power to the generator excitation winding (press the “GENERATOR EXCITATION ON” button);

• Check that generator voltage has reached 400V;

• Energize GCB (CIRCUIT BREAKER SUPPLY);

• Wind GCB, if necessary (HAND DRIVE);

• Synchronize the shaft generator with the MSB buses (manually or automatically).

Manual synchronization:

– use the “More/Less” buttons of the frequency regulation system of one or both diesel generators (GOVERNOR CONTROL) to adjust MSB bus voltage frequency to the shaft generator voltage. Voltage frequency of the ShG to be closed should slightly exceed

Page 15: RoRo Operating Procedures

THIS OPERATING PROCEDURE IS FOR TRANSAS TRAINING SIMULATOR USE ONLY

the MSB voltage frequency. Monitoring is performed using the frequency meters on the synchronization section;

– use the “More/Less” buttons of the DG/DG’s frequency regulation system

(GOVERNOR CONTROL) to reduce the phase difference (phase displacement) between the shaft generator voltage and the MSB voltage; – at the moment of the zero phase difference (the “12 o’clock” indicator illuminates at the synchronoscope) or a minimum phase difference, press the “CONNECT GCB” button for the shaft generator. Automatic synchronization:

– press the selection button for the generator\shaft generator to be synchronized at the synchronization section; – move the synchronization mode switch to the AUTO position. The moment of moving the synchronization mode switch to the AUTO position is the synchronization process starting moment. On completion of the synchronization process, the synchronized generator will be closed to the MSB buses. Then the synchronization mode selection switch will automatically return from the AUTO position to the MANUAL position:

• Use the buttons for changing specified frequency values to reduce the DG/DG’s load down to 50kw to 100 kW;

• Switch off the diesel generator GCB(s).

Taking out of Operation

• Set the diesel generator(s) to the parallel operation with ShG;

• Use the buttons for changing diesel generator(s) frequency to increase its/their load for the purpose of reducing the shaft generator load down to 50kw to 100 kW;

• Press the “DISCONNECT” button of the shaft generator circuit breaker.

Page 16: RoRo Operating Procedures

THIS OPERATING PROCEDURE IS FOR TRANSAS TRAINING SIMULATOR USE ONLY

Auxiliary Systems Boiler fuel System System Operation Pre requisites: Check the boiler water level is half a glass. Drain down or make up level as required. 1. Check if there are alarm signals in the system. Acknowledge active alarms and sort out the situation: determine what caused the alarm to trigger off. Check if the boiler system safety system is activated (“RESET” button) (see Steam Plant system). 2. Check if there is fuel in heavy and diesel fuel oil tanks. Replenish the fuel store as required by opening “HFO MAKE UP” or “DO MAKE UP” valve and checking the tank refilling by the level indicators. Tank overflow is not permitted. 3. Check the heavy fuel oil temperature in the tank (“HFO TANK” pressure gauge). If the temperature is low, turn on the heating of fuel in the tank (“HFO HEATING” button). Do not allow the “Fuel Low/High Temperature” alarm to be generated. 4. Select the type of fuel to be used by using “HFO-OFF-DO” switch. 5. With the use of the heavy fuel oil, turn on the heating or pipelines: “TRACING” button. 6. With the use of heavy fuel oil, supply steam to the fuel oil heater by pressing “PREHEATER ON” button. Select the steam heater operating mode: “MANUAL” or “AUTO”. In “MANUAL” mode, control the steam

supply to the fuel oil heater by using “HEATING” controller. In “AUTO” mode, set the required fuel oil temperature by using “SET POINT, оС” rotating knob. 7. If diesel oil is used, turn on the fuel oil heater bypassing by using “PREHEATER BYPASS” button. 8. Select the “hot” filter section by using “FILTER 1-2” switch. 9. Select MANUAL fuel pump operation mode by using “MANUAL-AUTO” switch. Start the required pump by using “PUMP 1” or “PUMP 2” button. The fuel will start circulating in the system. 10. Control the pressure at the burner unit inlet by using “PRESSURE SET POINT, Bar” controller. Check the parameters by using the available pressure and temperature gauges. 11. To enable of operation of burners in Steam Plant system and operation of the boiler, open the supply of fuel oil to the boiler burners by using “BURNER 1 ON” or “BURNER 2 ON” button. 12. Put the extraction and feed system into operation Warning In the event of a “flameout” ensure that the boiler is purged before attempting to restart a burner.

Page 17: RoRo Operating Procedures

THIS OPERATING PROCEDURE IS FOR TRANSAS TRAINING SIMULATOR USE ONLY

Boiler System Operation 1. Check if there are alarm signals in the system. Acknowledge active alarms and sort out the situation: determine what caused the alarm to trigger off. Check if the boiler system safety system is activated (“RESET” button) (see Steam Plant system). 2. Check if there is fuel in heavy and diesel fuel oil tanks. Replenish the fuel store as required by opening “HFO MAKE UP” or “DO MAKE UP” valve and checking the tank refilling by the level indicators. Tank overflow is not permitted. 3. Check the heavy fuel oil temperature in the tank (“HFO TANK” pressure gauge). If the temperature is low, turn on the heating of fuel in the tank (“HFO HEATING” button). Do not allow the “Fuel Low/High Temperature” alarm to be generated. 4. Select the type of fuel to be used by using “HFO-OFF-DO” switch. 5. With the use of the heavy fuel oil, turn on the heating or pipelines: “TRACING” button. 6. With the use of heavy fuel oil, supply steam to the fuel oil heater by pressing “PREHEATER ON” button. Select the steam heater operating mode: “MANUAL” or “AUTO”. In “MANUAL” mode, control the steam supply to the fuel oil heater by using “HEATING” controller. In “AUTO” mode, set the required fuel oil temperature by using “SET POINT, о

С” rotating knob. 7. If diesel oil is used, turn on the fuel oil heater bypassing by using “PREHEATER BYPASS” button. 8. Select the “hot” filter section by using “FILTER 1-2” switch.

9. Select MANUAL fuel pump operation mode by using “MANUAL-AUTO” switch. Start the required pump by using “PUMP 1” or “PUMP 2” button. The fuel will start circulating in the system. 10. Control the pressure at the burner unit inlet by using “PRESSURE SET POINT, Bar” controller. Check the parameters by using the available pressure and temperature gauges. 11. To enable of operation of burners in Steam Plant system and operation of the boiler, open the supply of fuel oil to the boiler burners by using “BURNER 1 ON” or “BURNER 2 ON” button.

Water Making Plant Procedure to Put the Plant into Operation 1. Switch on SEA WATER pump. 2. Open the ejector’s cut-off valve. 3. Open the condenser cooling water supply valve, which controls the cooling water flow. 4. Open the feed water supply valve as appropriate for the required plant capacity. 5. Open the evaporator heating water valve as appropriate for the heating water temperature and desired plant capacity. 6. Set the solenoid valve control switch in Salinity Control group to AUTO mode. 7. Set SET POINT distillate salinity control to the required position (at 2.5 PPM for obtaining the boiler feed water, at 200 PPM for the drinking and domestic water).

Page 18: RoRo Operating Procedures

THIS OPERATING PROCEDURE IS FOR TRANSAS TRAINING SIMULATOR USE ONLY

8. Set the distillate pump control switch to the AUTO mode. 9. Check the plant operation parameters maintaining their values within the rated value range.

Provisions Cooling Procedure for Starting the Plant in Manual Mode 1. Turn on the sea water pump. Monitor its operation by the pressure gauge. 2. Set the compressor operating mode switch to MANUAL position. 3. Open the shut-off valves on the liquid refrigerant circulation lines. 4. If the refrigeration plant is expected to operate for its own group of storerooms only, shut-off valves on the connecting steam and liquid pipelines are closed. If one of the refrigeration plants operates for both groups of consumers (the second plant is not turned on), the shut-off valves should be closed. 5. Adjust the low pressure switch. On “OFF” scale, set the pressure value whereby the compressor is turned off. By the moment of the compressor stop, the temperature in all the cooled storerooms should achieve the set value. On “ON” scale, set the pressure value whereby the compressor is turned on. By this moment, temperature in at least one room has grown to more than the set value. 6. Adjust thermoswitches for each storeroom. 7. For “Butter” and “Dry. Prov.” storerooms. Adjust the evaporation pressure control.

8. Open the master solenoid valve. 9. Start the compressor. 10. Set the operating mode switch of the equipment defrosting system to AUTO position. 11. Set the time interval (in hours) at which the defrosting of refrigeration equipment will be performed in each cooling space. 12. Set the defrosting system control switch to AUTO position. 13. Monitor the plant operation parameters maintaining their values within the standard range. You will be advised about all the faults by the alarm system. As a monitored parameter reaches the maximum permissible value, the safety system is actuated: an appropriate alarm is turned on in the bottom part of the screen. 14. Load (unload) as necessary the set mass of goods (products) into/from the storerooms. Defrosting of Refrigeration Equipment in Manual Mode This is used in case of excessive growth of hoar frost on the surface of refrigerating units: 1. If the thickness of the hoar frost layer is 5 mm or more, and the equipment defrosting process has not been started automatically, then it is necessary to: Set the defrosting system control switch to MANUAL position. 2. Press “ON” button under the switch.

Page 19: RoRo Operating Procedures

THIS OPERATING PROCEDURE IS FOR TRANSAS TRAINING SIMULATOR USE ONLY

Replenishment of Liquid Refrigerant This is performed if the refrigerating plant operating mode indicates the insufficiency of liquid refrigerant in the system (low level of liquid refrigerant in the condenser receiver part, gas bubbles in the sight glass, low suction pressure, extensive overheating on the suction line and high charging temperature): 1. Set the compressor operating mode switch to MANUAL position. 2. Close the shut-off valve on the liquid line after the condenser. 3. Open the make-up valve. 4. Monitor the liquid refrigerant level by using the sight glass on the receiver part of the condenser. 5. After the end of the process, close the make-up valve (the liquid refrigerant level on the condenser sight glass is 0.4⎟0.5 Н). 6. Open the shut-off valve after the condenser. 7. Turn the compressor on. 8. Set the operating mode switch to AUTO. 9. Monitor the refrigerating plant operation parameters. In case of the system overfilling with liquid refrigerant, there may be “damp” compressor operation. Compressor Replenishment with Oil This is performed if the oil level in the sight glass on the compressor sump has dropped to below ½ Н mark. The oil should best be added with the compressor not running (the oil level is clearly visible in the sight glass):

1. Set the compressor operating mode switch to MANUAL position. 2. Close the compressor suction valve. 3. After the suction pressure (in the sump) has dropped to a value below the atmospheric pressure (Ε -0.5 bars), stop the compressor. 4. Open the oil make-up valve. 5. After the end of the process (oil level is not higher than 2/3 of the sight glass), close the valve. 6. Turn the compressor on. 7. Set the operating mode switch to AUTO position. 8. Monitor the refrigerating plant operating parameters. Where the compressor cannot be stopped (e.g. loading of a considerable amount of goods with rather high temperature) at the moment of oil replenishment, it is necessary: 9. To re-adjust the low pressure switch – on “OFF” scale make Η -0.5 – -0.3 setting. 10. After the pressure has dropped below the atmospheric pressure, open the oil make-up valve. 11. After the end of the process, close the valve. 12. Re-adjust the low pressure switch to the operating mode. 13. Monitor the refrigerating plant operating parameters. If oil is added to the operating compressor, the replenishment will be either excessive or incomplete.

Page 20: RoRo Operating Procedures

THIS OPERATING PROCEDURE IS FOR TRANSAS TRAINING SIMULATOR USE ONLY

Air Discharge This is performed if the pressure gauge needle on the charging line makes jerking oscillatory motions, and the charging pressure exceeds the optimum value by 0.2 MPa and more: 1. Set the compressor operating mode switch to MANUAL position. 2. Turn the compressor off. 3. Turn the compressor off (on the right in Fig). 4. After the water temperature drops at the condenser outlet (OUTLET temperature gauge) down to the sea water temperature (INLET temperature gauge), open the valve for the discharge of air from the system. 5. As the charging pressure drops to the value corresponding to the optimum condensation temperature, i.e. as the temperature readings in DISCHARGE pressure gauge and DISCHARGE temperature gauge are equalised, close the air discharge valve. 6. Monitor the level of liquid refrigerant by using the sight glass on the condenser (there should be no lowering of the level). 7. Adjust the condensation pressure control for the maintaining of the set pressure value (0.6 – 0.7 MPa). 8. Turn the compressor on. 9. Set the operating mode switch to AUTO position. Replacement of Filter Drain This is done when the colour of the sight glass indicator changes. The indicator

colour changes from green to yellow as the moisture penetrates in the liquid refrigerant system: 1. Close the shut-off valves of the filter drain. 2. Open the bypass valve of the filter drain. As this is done, the indicator colour will change from the yellow colour to green, i.e. there will be an imitation of the filter drain replacement. 3. Open the shut-off valves of the filter drain. 4. Close the bypass valves of the filter drain. Compressor Breakdown In case of failure of one of the compressors, the other compressor will maintain the required temperature in all the six provision storerooms: 1. Re-adjust the low pressure switch of the operating compressor (N2) as required (in case of breakdown of compressor N1). 2. Set the operating mode switch of the stopped (broken) compressor to MANUAL position. 3. Close the master solenoid valve on the refrigerating plant which is not operating. 4. Open the shut-off valves on the steam and liquid connecting lines.

Page 21: RoRo Operating Procedures

THIS OPERATING PROCEDURE IS FOR TRANSAS TRAINING SIMULATOR USE ONLY

Air Conditioning Plant Operation and Maintenance Procedure to Bring the Air Conditioning System into Operation in Summer Mode The air conditioning system is switched to the summer more as the ambient temperature grows to +25°С: 1. Set the conditioner operating mode switch to SUMMER position. 2. Open the valve for feeding water to the compressors cooling. 3. Turn on the sea water pump. 4. Open the shut-off valves on the liquid refrigerant circulation lines. 5. Adjust temperature switches. 6. Set the compressors operating mode switch to MANUAL position. Simulator Module Systems 7. Adjust the low pressure switch. On “OFF” scale, set the suction pressure value whereupon, with some delay, the compressor cylinders will start to turn off. On “ON” scale, set the pressure value whereupon the compressor cylinders will start to turn on, by the timer, too. 8. Open the master solenoid valve. 9. Check if the compressor suction valve is closed. 10. Run the compressor.

As this is done, the electromagnetic actuators which raise the suction valve plates are ON, taking the cylinders out of operation and thus creating the compressor’s idle running. After the compressor has been run, the pushing devices are turned off in several seconds, and its cylinders start operating: 1. Partly open (to 5-10%) the compressor suction valve. 2. Check pressure in the compressor lubricating system. 3. With normal oil pressure value, continue opening the suction valve observing safety precautions. 4. Set the compressor operating mode switch to AUTO position. Simulator Module Systems 5. Use manual switches to set the desired air temperature in the cabins. 6. Use manual switches to set the desired air temperature in the cabins. Values of temperature and humidity in the cabin are shown on indicators. 7. Monitor the plant operating parameters maintaining their values within a standard range. The alarm system will signal about all the possible faults. As a monitored parameters reaches its limit value, and appropriate alarm lights up in the bottom part of the screen. Where no steps are made to normalise the compressor operation, SHUT DOWN protection is actuated, and the compressor is stopped, where after it can be brought back into operation in MANUAL mode only. Procedure to Bring the Air Conditioning System into Operation in Transient Mode The air conditioning system is switched to the transient mode at the ambient temperature of +15°С to +25°С.

Page 22: RoRo Operating Procedures

THIS OPERATING PROCEDURE IS FOR TRANSAS TRAINING SIMULATOR USE ONLY

Set the conditioner operating mode switch to WINTER position, turn off the heaters and humidifier: the fan only will remain operating. Procedure to Bring the Air Conditioning System into Operation in Winter Mode The air conditioning system is switched to the winter operating mode when the ambient temperature drops to +15°С: 1. Set the conditioner operating mode switch to WINTER position. 2. Depending on the ambient temperature (tн), tune on the first and second stage heaters. Ambient temperature after the first and second stage heaters, as well as relative humidity of the treated air is maintained automatically by using the direct-acting temperature controls (steam control valves). In this case, the first stage control maintains constant temperature at the first duct outlet, whereas the second stage control maintains temperature at the second duct outlet in accordance with its setting changed automatically with the ambient temperature. Simulator Module Systems 3. To control the air humidity, it is first necessary to turn on “H2O” valve manually monitoring the air humidity values in the first and second ducts. After it has been set, humidity is controlled automatically in accordance with the ambient temperature by the first duct temperature control. 4. Use manual switches in the cabin to set the desired temperature in the cabin. 5. Monitor the air conditioned operation parameters maintaining their values within the standard range.

Refrigerant Replenishment The operation is performed if the refrigeration plant operating mode indicates insufficient refrigerant in the system (low refrigerant level in the receiver, gas bubbles in the sight glass, low suction pressure, excessive heating in the suction line and high temperature on the charging line): 1. Set the compressor operating mode switch to MANUAL position. 2. Close the shut-off valve on the liquid line after the receiver. 3. Open the make-up valve. 4. Monitor the refrigerant level by the sight glass on the receiver. 5. After the end of the process, close the make-up valve (the refrigerant level on the receiver sight glass is 50%). 6. Open the shut-off valve after the receiver. 7. Set the operating mode switch to AUTO position. 8. Monitor the refrigerating plant operation parameters. 9. In case of the system overfilling with liquid refrigerant, there may be “damp” compressor operation. Compressor Replenishment with Oil This is performed if the oil level in the sight glass on the compressor sump has dropped to below ½ height mark. The oil should best be added with the compressor not running (oil level is clearly visible in the sight glass): 1. Set the compressor operating mode switch to MANUAL position. 2. Close the compressor suction valve.

Page 23: RoRo Operating Procedures

THIS OPERATING PROCEDURE IS FOR TRANSAS TRAINING SIMULATOR USE ONLY

3. After the suction pressure (in the sump) has dropped to a value below the atmospheric pressure (Ε-0.5 bars), stop the compressor. 4. Open the oil make-up valve. 5. After the end of the process (oil level is not higher than 2/3 of the sight glass), close the valve. 6. Turn the compressor on. 7. Open the compressor suction valve. 8. Set the operating mode switch to AUTO position. 9. Monitor the refrigerating plant operating parameters. Air Discharge from the Refrigerant System This is performed if the pressure gauge needle on the charging line makes jerking oscillatory motions, and the charging pressure exceeds the optimum value by 2 bars or more: 1. Set the compressor operating mode switch to MANUAL position. 2. Close the compressor suction valve. 3. Turn the compressor off. 4. Adjust the condensation pressure control to 100% opening (which corresponds to the setter’s position “5”). 5. After the water temperature drops at the condenser outlet (OUTLET temperature gauge) down to the sea water temperature (INLET temperature gauge), open the valve for the discharge of air from the system.

6. As the charging pressure drops to the value corresponding to the optimum condensation temperature, i.e. as the temperature readings in DISCHARGE pressure gauge and DISCHARGE temperature gauge are equalised, close the air discharge valve. 7. Monitor the level of refrigerant by using the sight glass on the condenser (there should be no lowering of the level). 8. Adjust the condensation pressure control for the maintaining of the set pressure value (9-10 bars). 9. Turn the compressor on. 10. Open the compressor suction valve. 11. Set the operating mode switch to AUTO position. Simulator Module Systems Replacement if Moisture Eliminator This is done when the colour of the sight glass indicator changes. The indicator colour changes from green to yellow as the moisture penetrates in the refrigerant system: 1. Close the moisture eliminator shut-off valves. 2. Open the moisture eliminator bypass valve. 3. Open the valve for drawing off refrigerant from the moisture eliminator for several minutes (1-2 minutes). 4. Close the valve for drawing off refrigerant from the moisture eliminator. 5. Open the moisture eliminator shut-off valves. 6. Close the moisture eliminator bypass valve. As this is done, the indicator colour will change from the yellow colour to green, i.e. there will be an imitation of the moisture eliminator replacement.

Page 24: RoRo Operating Procedures

THIS OPERATING PROCEDURE IS FOR TRANSAS TRAINING SIMULATOR USE ONLY

Elimination of Compressor Damp Operation This is performed if there is a sharp drop of temperature on the charging line (down to +10-0°С), overheating decreases, the compressor noise changes to dull, the cylinder walls and sump are covered with ice (if there is considerable flooding with liquid refrigerant), rattling noise appears, and the amperemeter needle goes beyond the red line: 1. Close the compressor suction valve leaving it 5-10% open. 2. After the indications of damp operation disappear, open the compressor suction valve slowly. 3. Check oil level in the sump replenish the compressor with oil as required. Breakage of Conditioner Fan If a fan is broken, air is supplied to this conditioner by the fan of the conditioner on the other board through the air flap. To do this, press the air flap control button. You can act in much the same way in case of the fan air filter fouling until it is “replaced” (the fault is eliminated from the instructor workplace). Breakage of Automatic Steam Control Valve If the automatic steam control valve is broken: 1. Close the shut-off valves “Bypass 1” and “Bypass 2” of the steam control (for the time of the repairs). 2. Open the manual control valve on the bypass line, adjusting its flow by the

readings of temperature gauges at the outlets of the first and second ducts.