Ferdinand Schad KG Steigstrae 25-27 D-78600 Kolbingen Telephone +49 (0) 74 63 - 980 - 0 Fax +49 (0) 74 63 - 980 - 200 [email protected] www.schako.de Room Air-Conditioning Module Model CULTRA Studioline

Room Air-Conditioning Module - SCHAKOSC 104 - HT4 S2 SC 203 - HT2 1100 2000 250 approx. 91 1025×125 1048 152 1025×315 1050 352 SC 204 - HT4 S3 SC 303 - HT2 1450 2000 250 approx

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Room Air-Conditioning Module - SCHAKOSC 104 - HT4 S2 SC 203 - HT2 1100 2000 250 approx. 91 1025×125 1048 152 1025×315 1050 352 SC 204 - HT4 S3 SC 303 - HT2 1450 2000 250 approx

Ferdinand Schad KGSteigstraße 25-27

D-78600 KolbingenTelephone +49 (0) 74 63 - 980 - 0

Fax +49 (0) 74 63 - 980 - [email protected]

Room Air-Conditioning ModuleModel CULTRA Studioline

Page 2: Room Air-Conditioning Module - SCHAKOSC 104 - HT4 S2 SC 203 - HT2 1100 2000 250 approx. 91 1025×125 1048 152 1025×315 1050 352 SC 204 - HT4 S3 SC 303 - HT2 1450 2000 250 approx

Contents

Construction subject to change. No return possible!

Room Air-Conditioning Module Cultra Studioline

11/03 - 2 31.08.2012Version:

Description ........................................................................................................................................3Model ......................................................................................................................................................................................... 4Accessories ................................................................................................................................................................................ 4

Models and dimensions .........................................................................................................................5Dimensions ................................................................................................................................................................................ 5Dimensions of accessories ........................................................................................................................................................ 7Circuit diagrams ....................................................................................................................................................................... 13Performance data for 2-pipe system ........................................................................................................................................ 15Performance data for 4-pipe system ........................................................................................................................................ 16

Technical data .................................................................................................................................. 17Maximum end velocity of jet .................................................................................................................................................... 17Critical throw ........................................................................................................................................................................... 19Temperature and induction ratios ............................................................................................................................................ 21

Legend ........................................................................................................................................... 23Order details .................................................................................................................................... 23Specification texts .............................................................................................................................. 24

Page 3: Room Air-Conditioning Module - SCHAKOSC 104 - HT4 S2 SC 203 - HT2 1100 2000 250 approx. 91 1025×125 1048 152 1025×315 1050 352 SC 204 - HT4 S3 SC 303 - HT2 1450 2000 250 approx

Room Air-Conditioning Module Cultra-Studioline

DescriptionThe room air-conditioning module CULTRA-Studioline can be po-sitioned either in front of the wall or integrated into the wall, thuspreventing costly waste of office space. For integration of theroom air-conditioning module CULTRA-Studioline, sliding con-necting pieces are required for connecting the air intake and airoutflow grilles to the room air-conditioning module (at an extracharge). This architectural flexibility allows an absolutely free useof space. The room air-conditioning module CULTRA-Studiolineis a recirculating air cooling device for offices, medical practicesand can even meet the requirements of sound studios, as it sat-isfies the requirements of GK 15 in connection with room-sidesound measures according to DIN 15 996. The dimensions of thewall module permit installation into walls, ceilings or floors. Laterin-front-of-the-wall installation is also possible.The ready-to-insert room air conditioning module allows a cost-efficient and quick installation. In case of changes of room utili-sation or rebuilding, a quick moving of the room air-conditioningmodule is possible. The user can even take the air-conditioningmodule with him when moving, as if it were office furniture. Itssensible cooling power is up to 2300 W. For larger rooms, sev-eral modules can be used. The air volume is up to 485 m³ perhour. As standard, the unit is equipped with 3 different speedsand available in 2-pipe or 4-pipe designs. It is possible to inte-grate room operating devices from a wide range of brands. If sev-eral CULTA-Studioline units are connected in parallel to one roomcontroller, the individual switching stages must be decoupledfrom one another. A relay kit for parallel connection of the fanspeeds of up to 5 CULTRA-Studioline units can be delivered as anoption at an extra charge.

Room air is drawn in through the air intake grille and cleaned bythe built-in filter. The integrated deflection sound absorber reduc-es the flow-generated noise. The air is then taken through thecooling or heating register and is temperature-controlled. A fur-ther deflection sound absorber is connected downstream fornoise reduction. The temperature-controlled air is then blown outinto the room again through the air intake grille. The room air-conditioning module can be used and operated in circulating and/or fresh air.

For maintenance purposes, the complete cover can be taken off.The register and the fan are easy accessible without special tools.The built-in filter is attached directly to the integrated fan coil unitand can simply be exchanged by opening the inspection cover.This means that the inspection cover must be freely accessible.

As a standard feature, the room air-conditioning module CUL-TRA-Studioline is equipped with an air intake grille type PA1 andan air outflow grille type DBB.

Optionally, the room air-conditioning module can be equippedwith smooth wall elements or with office equipment (white board,diary, media wall) or designed as room acoustic module with se-lected design. A wide range of supply and return air grilles allowa great freedom of creativity.

The room air-conditioning module CULTRA-Studioline must beinstalled in such a way that it is readily accessible for inspectionpurposes.

Characteristics of each supply and return air outlet:DBB:The support profile blades produce a stable air jet. The moduleis distinguished in particular by its high flexibility. The integratedblades allow many air distribution patterns even later on. Due tothe central housing of the support profile blades, the free cross-section is always the same size. Accordingly, when the bladesare adjusted, the pressure loss and sound power level remainconstant. An adjustment of the air outflow direction at a laterstage is possible at any time, even when the diffuser has alreadybeen fitted.

PA1:The ventilation grille type PA has front side fitted horizontal,fixed profile blades to direct the air. According to the desired airthrow pattern, the blade profiles can be selected from three dif-ferent profiles (PA, PAS or PAZ).

11/03 - 3

Construction subject to change. No return possible!

31.08.2012Version:

Page 4: Room Air-Conditioning Module - SCHAKOSC 104 - HT4 S2 SC 203 - HT2 1100 2000 250 approx. 91 1025×125 1048 152 1025×315 1050 352 SC 204 - HT4 S3 SC 303 - HT2 1450 2000 250 approx

Room Air-Conditioning Module Cultra-Studioline

Construction

Model

AccessoriesAir intake grille PA 1

- Front frame and blades made of aluminium extrusion pro-files natural colour anodised (E6/EV1) with front side hor-izontal stationary profile blades.

Air outflow grille DBB- Faceplate made of sheet steel painted to RAL 9010 (white)

with plastic blades painted to a colour similar to RAL 9005(black) or RAL 9010 (white).

Filter- Filter class G2- Steel frame

Faceplate- Galvanised sheet steel

Housing- Galvanised sheet steel

Deflection sound absorber- Galvanised sheet steel housing- Insulation material, building material class B1 (standard)

to DIN 4102- Insulation material, building material class A2 (non flam-

mable) to DIN 4102 (at an extra charge)Fan

- Galvanised sheet steel housing- Aluminium impeller- Blade mount made of plastic (PA 6)

Heat exchanger- 2-pipe circuit- 4-pipe circuit- Galvanised sheet steel frame- Aluminium blades- Copper pipes

Adapter piece- made of galvanised sheet steel with integrated outflow

grille

CULTRA-Studioline - Room air-conditioning module with airintake and outflow grilles, deflectionsound absorber, fan, filter and coolingand/or heating register.

Room acoustic module (Audimin)- Brochure on request

Valves- for water-side control of air after-treatment devices in

closed circuits- Three-way valve with T-bypass having a nominal pressure

of 16 bar. Red brass housing.Room operating unit

- Two-point controller for heating and/or cooling systemsSliding connection pipe

- for connecting the outlets to the CULTRA-Stuidoline whenthe latter is integrated into a wallLength X = 50-200 mm (specify when ordering).

Condensate pump- for draining the water of condensation formed at the cool-

ing registerInsulating material

- made of A2 non-flammable to DIN 4102Relay kit

- for parallel connection of the fan speeds of up to 5 CUL-TRA-Studioline units to a room controller.

11/03 - 4

Construction subject to change. No return possible!

31.08.2012Version:

Page 5: Room Air-Conditioning Module - SCHAKOSC 104 - HT4 S2 SC 203 - HT2 1100 2000 250 approx. 91 1025×125 1048 152 1025×315 1050 352 SC 204 - HT4 S3 SC 303 - HT2 1450 2000 250 approx

Room Air-Conditioning Module Cultra-Studioline

Models and dimensionsDimensionsCULTRA-Studioline with adapter piece

Available sizes

Attention!When ordering, pleasespecify height H3. It canrange between 500 and1000 mm.

RO = Inspection opening

for the on-site fastening,stud bolts or locking nutshave been mounted exworks.

Aquaris Silent

CULTRA Studioline

Fan coil unitAquaris Silent

B(mm)

H(mm)

T(mm)

Weight Air intake grille Air outflow grille(kg) PA 1 (L×H) L2 H2 DBB-A-Z (L×H) L1 H1

S0SC 003 - HT2

750 2000 250 approx. 62 625×125 648 152 625×215 650 252SC 004 - HT4

S1SC 103 - HT2

900 2000 250 approx. 74 625×225 648 252 625×315 650 352SC 104 - HT4

S2SC 203 - HT2

1100 2000 250 approx. 91 1025×125 1048 152 1025×315 1050 352SC 204 - HT4

S3SC 303 - HT2

1450 2000 250 approx. 110 1225×125 1248 152 1225×315 1250 352

SC 304 - HT4

11/03 - 5

Construction subject to change. No return possible!

31.08.2012Version:

Page 6: Room Air-Conditioning Module - SCHAKOSC 104 - HT4 S2 SC 203 - HT2 1100 2000 250 approx. 91 1025×125 1048 152 1025×315 1050 352 SC 204 - HT4 S3 SC 303 - HT2 1450 2000 250 approx

Room Air-Conditioning Module Cultra-Studioline

Water connection / Condensate connection / Electric connection

top left (-OL) top right (-OR)

center left side (-MSL) center right side (-MSR)

bottom left side (-USL) bottom right side (-USR)

bottom left (-UL) bottom right (-UR)

The water-side connections have been designed with 1/2" spigot nuts,about 50 mm in length.

The condensate connection can be UR, UL (standard), USR, USL. The con-densate discharge top is only possible in connection with a condensatepump (at an extra charge).

Position of the electric connection (standard):

OL = top leftOR = top rightMSL = center left sideMSR = center right sideUSL = bottom left sideUSR = bottom right sideUL = bottom left (standard)UR = bottom right

A = Cold water outlet 1/2"B = Cold water intake 1/2"C = Hot water intake 1/2"D = Hot water outlet 1/2"K = Condensate connectionE = Electric connection

if water connection on the right - electric connection on the leftIf water connection on the left - electric connection on the right

11/03 - 6

Construction subject to change. No return possible!

31.08.2012Version:

Page 7: Room Air-Conditioning Module - SCHAKOSC 104 - HT4 S2 SC 203 - HT2 1100 2000 250 approx. 91 1025×125 1048 152 1025×315 1050 352 SC 204 - HT4 S3 SC 303 - HT2 1450 2000 250 approx

Room Air-Conditioning Module Cultra-Studioline

Dimensions of accessoriesSliding connecting pipe (at an extra charge)for DBB-A-Z and PA1

When designed with sliding connec-tion piece, the dimension X must be specified when ordering.

Valves VMP46Three-way valve having a nominal pres-sure of 16 bar.Brass housing.External thread connections G...B.Provided with manual adjuster.

Valve types

Actuator STA219/STA719Electrothermal actuator for valve of2.5 mm nominal stroke.Including motion and position dis-play.Operating mode 24 V DC.OPEN/CLOSE function or propor-tional PWM

Actuator STA219

Actuator STA719

Cooling(for 2-pipe)

Heating(additionally for 4-pipe)

Size

SC003/004 VMP46.10-0.63 VMP46.10-0.63SC103/104 VMP46.10-0.63 VMP46.10-0.63SC203/204 VMP46.10-1.0 VMP46.10-0.63SC303/304 VMP46.10-1.0 VMP46.10-1.0

- Actuator 230 V AC- OPEN/CLOSE function or proportional PWM

- Actuator 24 V AC- OPEN/CLOSE function or proportional PWM

11/03 - 7

Construction subject to change. No return possible!

31.08.2012Version:

Page 8: Room Air-Conditioning Module - SCHAKOSC 104 - HT4 S2 SC 203 - HT2 1100 2000 250 approx. 91 1025×125 1048 152 1025×315 1050 352 SC 204 - HT4 S3 SC 303 - HT2 1450 2000 250 approx

Room Air-Conditioning Module Cultra-Studioline

Room temperature controller for 2-pipe systemModel RCC10

For systems without automatic switchover, an external switchcan be used for manual switchover instead of the sensor.For systems with permanent heating mode, the controller inputis used without the sensor.For systems with permanent cooling mode, the controller inputmust be electrically short-circuited (B2 with M).

- Output for On/Off valve actuator- Outputs for three-speed fan- Control either by room temperature or return air temperature,

as desired- Automatic heating/cooling mode switchover- Standard, Economy, Antifreeze operating modes or OFF- Switchover contact input for remote circuit- Control parameters selectable- Operating voltage AC 230 V

B1 = Return air sensor (temperature sensor QAH11.1)B2 = Changeover sensor (temperature sensor QAH11.1 +

changeover assembly kit ARG86.3)M1 = 3-speed fanN1 = Room temperature controller RCC10 / RCC10.1S1 = External operating modes selector switchY1 = Zone valves MVE..., MXE...

L, N = Operating voltage AC 230 VB1 = Signal input "return air temperature sensor"M = "Return Air Temperature Sensor" and "Changeover

Sensor" measurement zero B2 = Signal input "Changeover Sensor"D1, GND = Signal input for potential-free operating mode

switch (direction of action adjustable)Q1 = Control output "Fan speed I" AC 230 VQ2 = Control output "Fan speed II" AC 230 VQ3 = Control output "Fan speed III" AC 230 VY11 = "Valve" AC 230 V control output (work contact, for

currentless closed valves)Y12 = "Valve" AC 230 V control output (closed contact, for

currentless open valves)

11/03 - 8

Construction subject to change. No return possible!

31.08.2012Version:

Page 9: Room Air-Conditioning Module - SCHAKOSC 104 - HT4 S2 SC 203 - HT2 1100 2000 250 approx. 91 1025×125 1048 152 1025×315 1050 352 SC 204 - HT4 S3 SC 303 - HT2 1450 2000 250 approx

Room Air-Conditioning Module Cultra-Studioline

Room temperature controller for 4-pipe systemModel RCC30 Model RDF30

- Outputs for On/Off valve actuators- Outputs for three-speed fan- Control either by room temperature or return air temperature,

as desired- Standard, Economy, Antifreeze operating modes or OFF- Operating mode switchover contact input for remote circuit- Control parameters selectable- Operating voltage AC 230 V

B1 = Return air sensor (temperature sensor QAH11.1)M1 = 3-speed fanN1 = Room temperaturre controller RCC30 or RDF30S1 = External operating modes selector switchY1 = Heating valveY2 = Cooling valve

- Outputs for 2-point valve drives- Outputs for three-speed fan- Control either by room temperature or return air temperature,

as desired- Standard, Economy and Standby operating modes- Operating mode switchover contact input for remote circuit- Control parameters adaptable over a wide range- Operating voltage AC 230 V- Display of the room temperature, actual value or setpoint val-

ue can be selected.

L, N = Operating voltage AC 230 VB1 = Signal input "return air temperature sensor"M = Measurement zero "return air temperature sensor" B2 = Signal input "Changeover Sensor"D1, GND = Signal input for potential-free operating mode

switch (direction of action adjustable)Q1 = Control output "Fan speed I" AC 230 VQ2 = Control output "Fan speed II" AC 230 VQ3 = Control output "Fan speed III" AC 230 VY11 = "Heating Valve" AC 230 V control outputY12 = "Cooling Valve" AC 230 V control output

11/03 - 9

Construction subject to change. No return possible!

31.08.2012Version:

Page 10: Room Air-Conditioning Module - SCHAKOSC 104 - HT4 S2 SC 203 - HT2 1100 2000 250 approx. 91 1025×125 1048 152 1025×315 1050 352 SC 204 - HT4 S3 SC 303 - HT2 1450 2000 250 approx

Room Air-Conditioning Module Cultra-Studioline

Model ACR12.441

Digital compact roomcontroller for 2-pipe with/without heating elementor 4-pipe fan coil units

Connection diagram2-pipe fan coil unit with / without heating element

4-pipe fan coil unit

Other contol units available on request!

- Proportional PWM outputs for electrothermal valve actuators230 V AC

- Automatic or manual 3-speed fans- Manual or automatic winter/summer (heating/cooling) selec-

tor switch (including QAH11.1 sensor)- Three operating modes: Standard, Economy or Standby

mode- Digital input: Operating modes selector switch (for motion

detector or open window)- Optional input for return air temperature sensor (QAH11.1) in

the 4-pipe Aquaris Silent

B2 = Changeover sensor (2-pipe system) or return air sensor(4-pipe system)

E1 = Ext. relay E heaterM1 = 3-speed fanN1 = Controller parameterised for 4-pipe systemN2 = Controller parameterised for 2-pipe systemS1 = Window contact or presence detectorY1 = in N1 application, heating valve

in N2 application, heating or cooling valve (changeo-ver)Y10 = in N1 application, cooling valve

in N2 application, relay for E heater

DU1 = Window contact or presence detector, SELVGND = Measurement zeroM = Measurement zero for sensor inputB2 = Changeover input or return air cooler QAH11.1N, L = Power supply AC 230 VY1 = 4-pipe system / valve output heating / AC 230 V

2-pipe system / valve output heating or cooling / AC230 V

Q1 = Fan Speed 1 output / AC 230 VQ2 = Fan Speed 2 output / AC 230 VQ3 = Fan Speed 3 output / AC 230 VY10 = 4-pipe system / valve output cooling / AC 230 V

2-pipe system / output for ext.relay E heater/ AC 230 V

11/03 - 10

Construction subject to change. No return possible!

31.08.2012Version:

Page 11: Room Air-Conditioning Module - SCHAKOSC 104 - HT4 S2 SC 203 - HT2 1100 2000 250 approx. 91 1025×125 1048 152 1025×315 1050 352 SC 204 - HT4 S3 SC 303 - HT2 1450 2000 250 approx

Room Air-Conditioning Module Cultra-Studioline

Condensate pumpDescriptionThe condensate pump is used to remove the water of conden-sation from the cooling register, in case there is not enough gra-dient towards the on-site drain system. With alarm message(when water height rises above 27 mm).

(1) Condensate drain Ø 8 mm outside (Ø 6 mm inside)(2) Pump(3) Condensation inlet Ø 17 mm outside

(Rubber intake Ø 15 mm inside)(4) Filter (for particles > 1 mm)(5) Float(6) Magnet(7) Electronic control(8) Connection(9) Thermal protection

Technical dataPower supply 230 V-50/60 HzOutput (230 V-50 Hz) 6 WRated current 30 mAMaximum power 10 WThermal protection 90 °CAlarm contact NC contactSafety measure Connection to earthMedium WaterTemperature of the medium between 0° C and 33° CAmbient temperature max. 50°CMax. flow 8 l/hMax. pressure difference 8 mMax. delivery height 8 mPump type Piston pumpSound level <28 dB(A)Dimensions 91 × 68 × 45 mmFloat switch ON (24 mm); OFF (19 mm);

ALARM (27 mm)

11/03 - 11

Construction subject to change. No return possible!

31.08.2012Version:

Page 12: Room Air-Conditioning Module - SCHAKOSC 104 - HT4 S2 SC 203 - HT2 1100 2000 250 approx. 91 1025×125 1048 152 1025×315 1050 352 SC 204 - HT4 S3 SC 303 - HT2 1450 2000 250 approx

Room Air-Conditioning Module Cultra-Studioline

Connection scheme / terminal diagramCondensation water pump type 8 FC

Important:The pump is equipped with a C & NC / C & NO (reversible) over-flow alarm contact (8 A/250 V). The connecting cable must beselected accordingly. The contact can be used, for example, toswitch off a cooling system in which there is a risk of conden-sate overflow (after a detailed check of the customer specifica-tion and the resulting electric connection diagram by theinstaller). The installation is done on site. The condensation wa-ter pumps are delivered unassembled.Optionally, the assembly and wiring can be done ex works (at anextra charge).

The diagram shows the capacity of the condensation waterpump as a function of the vertical distance V and the horizontaldistance H (relative to the latent capacity).

on-site:

(1) Plenum box(2) cable(3) 630 mA fuse(4) Solenoid valve(5) Compressor(6) or

P = redN = blueConnection to earth = yellow / greenC = blackNC = black

QL (kW) = Latent capacity

QL = Qges - Qsen

11/03 - 12

Construction subject to change. No return possible!

31.08.2012Version:

Page 13: Room Air-Conditioning Module - SCHAKOSC 104 - HT4 S2 SC 203 - HT2 1100 2000 250 approx. 91 1025×125 1048 152 1025×315 1050 352 SC 204 - HT4 S3 SC 303 - HT2 1450 2000 250 approx

Room Air-Conditioning Module Cultra-Studioline

Circuit diagramsSCO.../SC1.../SC2.../SC3...Version 1

x = Oil-resistant flexible cable 7x1.5mm² mounted to the Cultra-StudiolineT = Thermal contacts designed as thermal circuit1 = Room thermostat / room controller

white*white*

bluebrownblackgreyvioletorangered min.

yellow / green

4

medium

yellow

green

5

3

21

on-site

max

6

mingr/ye

x

1

white*white*

bluebrownblackgreyvioletorangered min.

yellow / green

mediummin

yellow

green

on-site

max

x

1

11/03 - 13

Construction subject to change. No return possible!

31.08.2012Version:

Page 14: Room Air-Conditioning Module - SCHAKOSC 104 - HT4 S2 SC 203 - HT2 1100 2000 250 approx. 91 1025×125 1048 152 1025×315 1050 352 SC 204 - HT4 S3 SC 303 - HT2 1450 2000 250 approx

Room Air-Conditioning Module Cultra-Studioline

SCO.../SC1.../SC2.../SC3...Version 2

Electric valves Condensate pump

Applies to motorised valve actuatorsFor thermal actuators, terminals 3 and 6 are not used.

x = Oil-resistant flexible cable 7x1.5mm² mounted to the Cultra-StudiolineT = Thermal contacts designed as potential-free switching contact1 = Room thermostat / room controller

white*white*

bluebrownblackgreyvioletorangered min.

yellow / green

4

mediummin

yellow

green

5

3

21

gr/ye

on-site

max

thermal c.

6thermal c.

x

1

white*white*

bluebrownblackgreyvioletorangered min.

yellow / green

mediummin

yellow

green

on-site

max

x

1

V1V1V1V2V2V2

Valve 1

Valve 2

M~

N230V/AC 50HzTTN8A/250V

Input

Output

11/03 - 14

Construction subject to change. No return possible!

31.08.2012Version:

Page 15: Room Air-Conditioning Module - SCHAKOSC 104 - HT4 S2 SC 203 - HT2 1100 2000 250 approx. 91 1025×125 1048 152 1025×315 1050 352 SC 204 - HT4 S3 SC 303 - HT2 1450 2000 250 approx

Room Air-Conditioning Module Cultra-Studioline

Performance data for 2-pipe system

*valid for a minimum height of 2000 mm.Lower heights reduce the noise level

SC003-HT2RR SC103-HT2RRQ (KW) QS (KW) Q (KW) QS (KW)

Speed setting Speed setting Speed setting Speed setting1 2 3 1 2 3 1 2 3 1 2 3

V (m³/h) 125 140 195 125 140 195 120 180 260 120 180 260

CoolingAir 27° / 47% r.h.

6°C / 12°C 0,81 0,88 1,14 0,60 0,66 0,87 0,85 1,19 1,60 0,62 0,88 1,207°C / 12°C 0,79 0,87 1,12 0,59 0,65 0,86 0,83 1,17 1,57 0,61 0,87 1,188°C / 14°C 0,63 0,69 0,88 0,53 0,58 0,76 0,67 0,94 1,25 0,54 0,77 1,0510°C / 16°C 0,47 0,52 0,69 0,47 0,52 0,69 0,46 0,69 0,95 0,46 0,69 0,95

SC203-HT2RR SC303-HT2RRQ (KW) QS (KW) Q (KW) QS (KW)

Speed setting Speed setting Speed setting Speed setting1 2 3 1 2 3 1 2 3 1 2 3

V (m³/h) 300 340 415 300 340 415 220 330 485 220 330 485

CoolingAir 27° / 47% r.h.

6°C / 12°C 1,91 2,11 2,46 1,42 1,58 1,86 1,61 2,28 3,13 1,16 1,66 2,307°C / 12°C 1,87 2,07 2,41 1,40 1,56 1,84 1,57 2,22 3,05 1,14 1,63 2,278°C / 14°C 1,50 1,65 1,92 1,25 1,39 1,64 1,28 1,81 2,46 1,02 1,46 2,0310°C / 16°C 1,12 1,25 1,47 1,12 1,25 1,47 0,89 1,25 1,82 0,87 1,24 1,82

SC 003 SC 103 SC 203 SC 303Speed setting Speed setting Speed setting Speed setting

1 2 3 1 2 3 1 2 3 1 2 3LW [dB(A)] * 29,4 31,1 35,7 21,8 28,2 33,2 23,0 28,1 38,4 26,1 30,3 39,2

V (m³/h) = Volumetric flowQ (kW) = Total capacityQS (kW) = Sensible cooling powerLW [dB(A)] = Sound power level

11/03 - 15

Construction subject to change. No return possible!

31.08.2012Version:

Page 16: Room Air-Conditioning Module - SCHAKOSC 104 - HT4 S2 SC 203 - HT2 1100 2000 250 approx. 91 1025×125 1048 152 1025×315 1050 352 SC 204 - HT4 S3 SC 303 - HT2 1450 2000 250 approx

Room Air-Conditioning Module Cultra-Studioline

Performance data for 4-pipe system

*valid for a minimum height of 2000 mm.Lower heights reduce the noise level

SC004-HT4RR SC104-HT4RRQ (KW) QS (KW) Q (KW) QS (KW)

Speed setting Speed setting Speed setting Speed setting1 2 3 1 2 3 1 2 3 1 2 3

V (m³/h) 105 120 180 105 120 180 115 175 250 115 175 250

CoolingAir 27° / 47% r.h.

6°C / 12°C 0,70 0,78 1,07 0,52 0,58 0,82 0,82 1,17 1,55 0,59 0,86 1,167°C / 12°C 0,68 0,76 1,06 0,51 0,57 0,81 0,80 1,14 1,52 0,59 0,85 1,148°C / 14°C 0,54 0,61 0,83 0,45 0,51 0,72 0,65 0,92 1,22 0,52 0,75 1,0210°C / 16°C 0,41 0,46 0,64 0,41 0,46 0,64 0,44 0,67 0,92 0,44 0,67 0,92

HeatingAir 20° / 50% r.h.

70°C / 60°C 0,78 0,86 1,13 0,78 0,86 1,13 0,93 1,26 1,60 0,93 1,26 1,6050°C / 40°C 0,40 0,44 0,57 0,40 0,44 0,57 0,49 0,65 0,83 0,49 0,65 0,83

SC204-HT4RR SC304-HT4RRQ (KW) QS (KW) Q (KW) QS (KW)

Speed setting Speed setting Speed setting Speed setting1 2 3 1 2 3 1 2 3 1 2 3

V (m³/h) 290 330 400 290 330 400 210 320 470 210 320 470

CoolingAir 27° / 47% r.h.

6°C / 12°C 1,86 2,06 2,39 1,38 1,54 1,80 1,55 2,22 3,05 1,11 1,61 2,247°C / 12°C 1,82 2,02 2,34 1,36 1,52 1,78 1,50 2,16 2,97 1,09 1,59 2,218°C / 14°C 1,46 1,61 1,87 1,22 1,35 1,59 1,23 1,76 2,40 0,98 1,42 1,9710°C / 16°C 1,09 1,22 1,43 1,09 1,22 1,43 0,86 1,22 1,77 0,92 1,21 1,77

HeatingAir 20° / 50% r.h.

70°C / 60°C 2,00 2,19 2,49 2,00 2,19 2,49 1,76 2,37 3,09 1,76 2,37 3,0950°C / 40°C 1,05 1,15 1,30 1,05 1,15 1,30 0,92 1,23 1,60 0,92 1,23 1,60

SC 004 SC 104 SC 204 SC 304Speed setting Speed setting Speed setting Speed setting

1 2 3 1 2 3 1 2 3 1 2 3LW [dB(A)] * 29,4 31,1 35,7 21,8 28,2 33,2 23,0 28,1 38,4 26,1 30,3 39,2

V (m³/h) = Volumetric flowQ (kW) = Total capacityQS (kW) = Sensible cooling powerLW [dB(A)] = Sound power level

11/03 - 16

Construction subject to change. No return possible!

31.08.2012Version:

Page 17: Room Air-Conditioning Module - SCHAKOSC 104 - HT4 S2 SC 203 - HT2 1100 2000 250 approx. 91 1025×125 1048 152 1025×315 1050 352 SC 204 - HT4 S3 SC 303 - HT2 1450 2000 250 approx

Room Air-Conditioning Module Cultra-Studioline

Technical data

Maximum end velocity of jetCultra-Studioline SC003 Cultra-Studioline SC004

Ceiling jet adjustment

To achieve a coanda effect, the upper edge of theCultra-Studioline should be no more than 0.5 mfrom the ceiling.

Free jet adjustment

If the distance from the ceiling is more than 0.6 m, the free jet setting is recommended.

Free jet = diagram value x 0.7

Cultra-Studioline SC103 Cultra-Studioline SC104

Speed

SpeedSpeed

Speed

SpeedSpeed

SpeedSpeed

Speed

SpeedSpeed

Speed

11/03 - 17

Construction subject to change. No return possible!

31.08.2012Version:

Page 18: Room Air-Conditioning Module - SCHAKOSC 104 - HT4 S2 SC 203 - HT2 1100 2000 250 approx. 91 1025×125 1048 152 1025×315 1050 352 SC 204 - HT4 S3 SC 303 - HT2 1450 2000 250 approx

Room Air-Conditioning Module Cultra-Studioline

Cultra-Studioline SC203 Cultra-Studioline SC204

Cultra-Studioline SC303 Cultra-Studioline SC304

Ceiling jet adjustment

To achieve a coanda effect, the upper edge of theCultra-Studioline should be no more than 0.5 mfrom the ceiling.

Free jet adjustment

If the distance from the ceiling is more than 0.6 m, the free jet setting is recommended.

Free jet = diagram value x 0.7

SpeedSpeedSpeed

Speed

Speed

Speed

Speed

Speed

Speed

Speed

Speed

Speed

11/03 - 18

Construction subject to change. No return possible!

31.08.2012Version:

Page 19: Room Air-Conditioning Module - SCHAKOSC 104 - HT4 S2 SC 203 - HT2 1100 2000 250 approx. 91 1025×125 1048 152 1025×315 1050 352 SC 204 - HT4 S3 SC 303 - HT2 1450 2000 250 approx

Room Air-Conditioning Module Cultra-Studioline

Critical throwCultra-Studioline SC003

Speed 1 = 125m³/hSpeed 2 = 140m³/h

Speed 3 = 195m³/h

V (m³/h)

Cultra-Studioline SC004

Speed 1 = 105m³/h

Speed 3 = 180m³/hSpeed 2 = 120m³/h

V (m³/h)

Ceiling jet adjustment

To achieve a coanda effect,the upper edge of the Cultra-Studioline should be nomore than 0.5 m from theceiling.

Throw distance xkr (m) x 1.33

Cultra-Studioline SC103

Speed 1 = 120m³/hSpeed 2 = 180m³/h

Speed 3 = 260m³/h

V (m³/h)

Cultra-Studioline SC104

Speed 1 = 115m³/h

Speed 3 = 250m³/hSpeed 2 = 175m³/h

V (m³/h)

Ceiling jet adjustment

To achieve a coanda effect,the upper edge of the Cultra-Studioline should be nomore than 0.5 m from theceiling.

Throw distance xkr (m) x 1.33

11/03 - 19

Construction subject to change. No return possible!

31.08.2012Version:

Page 20: Room Air-Conditioning Module - SCHAKOSC 104 - HT4 S2 SC 203 - HT2 1100 2000 250 approx. 91 1025×125 1048 152 1025×315 1050 352 SC 204 - HT4 S3 SC 303 - HT2 1450 2000 250 approx

Room Air-Conditioning Module Cultra-Studioline

Cultra-Studioline SC203 Cultra-Studioline SC204

Cultra-Studioline SC303 Cultra-Studioline SC304

Ceiling jet adjustment

To achieve a coanda effect, the upper edge of theCultra-Studioline should be no more than 0.5 mfrom the ceiling.

Throw distance xkr (m) x 1.33

Speed 1 = 300m³/hSpeed 2 = 340m³/h

Speed 3 = 415m³/h V (m³/h)

Speed 1 = 290m³/h

Speed 3 = 400m³/hSpeed 2 = 330m³/h V (m³/h)

Speed 1 = 220m³/hSpeed 2 = 330m³/h

Speed 3 = 485m³/h

V (m³/h) Speed 1 = 210m³/h

Speed 3 = 470m³/hSpeed 2 = 320m³/h

V (m³/h)

11/03 - 20

Construction subject to change. No return possible!

31.08.2012Version:

Page 21: Room Air-Conditioning Module - SCHAKOSC 104 - HT4 S2 SC 203 - HT2 1100 2000 250 approx. 91 1025×125 1048 152 1025×315 1050 352 SC 204 - HT4 S3 SC 303 - HT2 1450 2000 250 approx

Room Air-Conditioning Module Cultra-Studioline

Temperature and induction ratiosSC0 Ceiling jet adjustment Free jet adjustment

Correction factors for free jet adjustmentReduction in temperature x 0.67Induction ratio x 1.50

SC1 Ceiling jet adjustment Free jet adjustment

Correction factors for free jet adjustmentReduction in temperature x 0.93Induction ratio x 1.07

11/03 - 21

Construction subject to change. No return possible!

31.08.2012Version:

Page 22: Room Air-Conditioning Module - SCHAKOSC 104 - HT4 S2 SC 203 - HT2 1100 2000 250 approx. 91 1025×125 1048 152 1025×315 1050 352 SC 204 - HT4 S3 SC 303 - HT2 1450 2000 250 approx

Room Air-Conditioning Module Cultra-Studioline

SC2 Ceiling jet adjustment Free jet adjustment

Correction factors for free jet adjustmentReduction in temperature x 0.81Induction ratio x 1.22

SC3 Ceiling jet adjustment Free jet adjustment

Correction factors for free jet adjustmentReduction in temperature x 0.84Induction ratio x 1.19

11/03 - 22

Construction subject to change. No return possible!

31.08.2012Version:

Page 23: Room Air-Conditioning Module - SCHAKOSC 104 - HT4 S2 SC 203 - HT2 1100 2000 250 approx. 91 1025×125 1048 152 1025×315 1050 352 SC 204 - HT4 S3 SC 303 - HT2 1450 2000 250 approx

Room Air-Conditioning Module Cultra-Studioline

Legend

Order details

V (m3/h) = Volumetric flowLW [dB(A)] = Sound power levelvmax (m/s) = Maximum end velocity of jetx+y (m) = Horizontal + vertical throwxkr (m) = Critical throw∆TO (K) = Temperature difference between supply air

temperature and room temperature (∆TO = tZU- tR )

TV (-) = Temperature ratio (TV = ∆TX / ∆TO)i (-) = Induction ratio (i = VX / VZU )

Q (kW) = Total capacityQS (kW) = Sensible capacity∆TX (K) = Temperature difference at point xtZU (°C) = Supply air temperaturetR (°C) = Room temperatureVX (m3/h) = Total air jet volume at point x

Room air conditioning moduletype CULTRA-Studioline

S0 S1 S2 S3

Heat exchanger2-conductor system

-HT2

Heat exchanger4-pipe system

-HT4

-OR -OL -MSL -MSR -USR -USL -UL -UR

Adapter pieceH3=500-1000

Accessories:

Sliding connection pipefor air intake/outflow grille

Order example:CULTRA-Studioline-S0-HT2-USL-KUR-H3=750

Unless stated otherwise, the thick-frame model will be delivered!

-OR -OL -MSL -MSR -USR -USL -UL -UR

Room acoustic moduleAudimin

Room operating unit

Valves

Condensate pump

Insulating materialmade of A2 (non-flamma-

ble)

Water connection-

Condensate connection-K

Relay kit

11/03 - 23

Construction subject to change. No return possible!

31.08.2012Version:

Page 24: Room Air-Conditioning Module - SCHAKOSC 104 - HT4 S2 SC 203 - HT2 1100 2000 250 approx. 91 1025×125 1048 152 1025×315 1050 352 SC 204 - HT4 S3 SC 303 - HT2 1450 2000 250 approx

Room Air-Conditioning Module Cultra-Studioline

Specification texts

Ready-to-insert room air-conditioning module for offices, med-ical practices and even sound studios for cooling and heating.For installation in walls, ceilings or floors or for in-front-of-the-wall installation. Easy to install and uninstall in case of anychanges of room utilisation. Structure-borne noise transmis-sion is prevented by means of a sound-decoupled suspension.Simple filter change due to easily disassembled inspectionopening. For maintenance purposes, quick and easy to open bymeans of a removable lock without requiring special tools.Optional control via 3-speed circuit or as a function of roomtemperature via room temperature sensor (see Accessories).With adapter piece made of galvanised sheet steel. Height H3ranging between 500 and 1000 mm.H3 = _________ mmProduct: SCHAKO type CULTRA-Studioline...

Outlet type: .......... from SCHAKO

Accessories:

- Model:- S0- S1- S2- S3

- Heat exchanger:- 2-pipe system (-HT2)- 4-pipe system (-HT4)

- Water connection (-) / Condensate connection (-K):- top left (-OL)- top right (-OR)- bottom left (-UL, standard)- bottom right (-UR)- center left side (-MSL)- center right side (-MSR)- bottom left side (-USL)- bottom right side (-USR)

- Electric connection:- left (with water connection on the right)- right (with water connection on the right)

- Air intake grille type PA 1:- Front frame made of extruded aluminium profile natural

colour anodised (E6/EV1) with front side horizontal sta-tionary profile blades made of extruded aluminium profilesnatural colour anodised (E6/EV1). Blade profile: PA, PAS,PAZ. With concealed mounting (VM 12).

- Air outflow grille type DBB-A-Z:- Sheet steel front plate painted to RAL 9010 (white). Model A

for supply air, one-way throw. With concealed mounting(VM). With pivoting air deflection blades individually adjust-able and made of plastic in the colours:- RAL 9005 (black),- RAL 9010 (white) or- Aluminium painted to the same RAL colour as the frame

profile Subsequent adjustment of blades not possible.

- Room acoustic module (Audimin)- Valves for water-side control of air after-treatment devices in

closed circuits- Three-way valve with T-bypass having a nominal pressure

of 16 bar. Red brass housing.External thread connections G...B. Type VMP 46...

- Room operating unit: Two-point controller for heating and/orcooling systems.

- Sliding connection pipe for connecting the outlets to the CUL-TRA Stuidoline when the latter is integrated in a wall. LengthX = 50-200 mm (specify when ordering).

- Condensate pump- for draining the water of condensation formed at the cool-

ing register- Insulation material made of A2 (non-flammable) to DIN 4102- Relay kit for the parallel connection of the fan stages of up to

5 CULTRA-Studioline to a room controller.

11/03 - 24

Construction subject to change. No return possible!

31.08.2012Version: