Air Change Australia Pty Ltd accept no responsibility for possible errors in catalogues, brochures and other printed material. Air Change Australia Pty Ltd reserves the right to alter its products without notice. ROOFTOP PACKAGED UNITS ACS11RCRTP TECHNICAL SPECIFICATIONS UNIT VALUE Supply Air L/s 500 Return Air L/s 500 Outdoor Air L/s 500 Condenser Air L/s 300 Exhaust Air – (RA + CA) L/s 800 Compressor Qty 1 Refrigerant Charge (R407C) kg/Comp 2.8 Total Compressor Capacity kWr 11 OUTDOOR AIR TO SUPPLY AIR Pressure Drop Heat Exchanger Pa 101 Pressure Drop Evaporator Coil Pa 80 External Static Pressure Up to Pa 150 Total Pressure on Supply Fan Pa 331 SUPPLY FAN Fan Speed (max) rpm 1350 Motor Power kW 0.75 Motor Poles 4 Motor Torque Nm N/A RETURN AIR TO EXHAUST AIR Pressure Drop Heat Exchanger Pa 101 Pressure Drop Condenser Coil Pa 40 External Static Pressure Up to Pa 150 Total Pressure on Exhaust Fan Pa 291 EXHAUST FAN Fan Speed (max) rpm 1330 Motor Power kW 0.75 Motor Poles 4 Motor Torques Nm N/A CONDENSER AIR Fan Qty 0 Air Flow L/s 300 Fan Speed N/A COIL SIZE Condenser Coil mm 1060 X 508 Evaporator Coil mm 1060 X 356 Face Velocity Coil Evap m/s 1.32 ELECTRICAL POWERING 415/3/50 Compressor (RLA / FLA) A 7.1/17.0 Supply Fan (FLA) A 4.0 Exhaust Fan (FLA) A 4.0 Condenser Fan (FLA) A N/A Nominal Running Current A 7.1/11.1/11.1 Total Full Load Amps A 17.0/21.0/21.0 SOUND LEVEL Sound Pressure Level Intake @ 4m dB (A) 67 Sound Pressure Level Exhaust @ 1m dB (A) 75 ROOFTOP SCHEMATICS & DIMENSIONS Standard With Economy Cycle UNIT DIMENSION (mm) and Weight (kg) Body Width (E) / Overall Width (F) 1560/1760 1750/1950 Body Depth (G) / Overall Depth (H) 1250/1330 1550/1740 Body Height (I) / Overall Height (J) 1050/1150 1100/1200 Weight (kg) 360 440 SPIGOT SIZES (mm) Supply Air (C x D1) 1010 x 325 1010 x 325 Return Air (A x B2) 1460 x 380 1300 x 430 Exhaust Air (C x D2) 1010 x 470 1010 x 470 Outdoor Air (A x B1) 1460 x 520 1300 x 330 CLEARANCE REQUIREMENT (mm) Minimum LHS Requirement 1200 1200 Minimum RHS Requirement 1000 1000 Base Frame (Standard Unit) Base Frame (with Economy Cycle)

ROOFTOP PACKAGED UNITS - Air Change · Exhaust Air – (RA + CA) L/s 800 Compressor Qty 1 Refrigerant Charge (R407C) kg ... Outdoor Air (A x B1) 1650 x 520 1425 x 330 CLEARANCE REQUIREMENT

Embed Size (px)

Citation preview

Page 1: ROOFTOP PACKAGED UNITS - Air Change · Exhaust Air – (RA + CA) L/s 800 Compressor Qty 1 Refrigerant Charge (R407C) kg ... Outdoor Air (A x B1) 1650 x 520 1425 x 330 CLEARANCE REQUIREMENT

Air Change Australia Pty Ltd accept no responsibility for possible errors in catalogues, brochures and other printed material. Air Change Australia Pty Ltd reserves the right to alter its products without notice.

ROOFTOP PACKAGED UNITS

ACS11RCRTP TECHNICAL SPECIFICATIONS UNIT VALUE

Supply Air L/s 500

Return Air L/s 500

Outdoor Air L/s 500

Condenser Air L/s 300

Exhaust Air – (RA + CA) L/s 800

Compressor Qty 1

Refrigerant Charge (R407C) kg/Comp 2.8

Total Compressor Capacity kWr 11

OUTDOOR AIR TO SUPPLY AIR

Pressure Drop Heat Exchanger Pa 101

Pressure Drop Evaporator Coil Pa 80

External Static Pressure Up to Pa 150

Total Pressure on Supply Fan Pa 331

SUPPLY FAN

Fan Speed (max) rpm 1350

Motor Power kW 0.75

Motor Poles 4

Motor Torque Nm N/A

RETURN AIR TO EXHAUST AIR

Pressure Drop Heat Exchanger Pa 101

Pressure Drop Condenser Coil Pa 40

External Static Pressure Up to Pa 150

Total Pressure on Exhaust Fan Pa 291

EXHAUST FAN

Fan Speed (max) rpm 1330

Motor Power kW 0.75

Motor Poles 4

Motor Torques Nm N/A

CONDENSER AIR

Fan Qty 0

Air Flow L/s 300

Fan Speed N/A

COIL SIZE

Condenser Coil mm 1060 X 508

Evaporator Coil mm 1060 X 356

Face Velocity Coil Evap m/s 1.32

ELECTRICAL POWERING 415/3/50

Compressor (RLA / FLA) A 7.1/17.0

Supply Fan (FLA) A 4.0

Exhaust Fan (FLA) A 4.0

Condenser Fan (FLA) A N/A

Nominal Running Current A 7.1/11.1/11.1

Total Full Load Amps A 17.0/21.0/21.0

SOUND LEVEL

Sound Pressure Level Intake @ 4m dB (A) 67

Sound Pressure Level Exhaust @ 1m dB (A) 75

ROOFTOP SCHEMATICS & DIMENSIONS

Standard With Economy Cycle

UNIT DIMENSION (mm) and Weight (kg)

Body Width (E) / Overall Width (F) 1560/1760 1750/1950

Body Depth (G) / Overall Depth (H) 1250/1330 1550/1740

Body Height (I) / Overall Height (J) 1050/1150 1100/1200

Weight (kg) 360 440

SPIGOT SIZES (mm)

Supply Air (C x D1) 1010 x 325 1010 x 325

Return Air (A x B2) 1460 x 380 1300 x 430

Exhaust Air (C x D2) 1010 x 470 1010 x 470

Outdoor Air (A x B1) 1460 x 520 1300 x 330

CLEARANCE REQUIREMENT (mm)

Minimum LHS Requirement 1200 1200

Minimum RHS Requirement 1000 1000

Base Frame (Standard Unit) Base Frame (with Economy Cycle)

Page 2: ROOFTOP PACKAGED UNITS - Air Change · Exhaust Air – (RA + CA) L/s 800 Compressor Qty 1 Refrigerant Charge (R407C) kg ... Outdoor Air (A x B1) 1650 x 520 1425 x 330 CLEARANCE REQUIREMENT

Air Change Australia Pty Ltd accept no responsibility for possible errors in catalogues, brochures and other printed material. Air Change Australia Pty Ltd reserves the right to alter its products without notice.

ROOFTOP PACKAGED UNITS

ACS16RCRTP TECHNICAL SPECIFICATIONS UNIT VALUE

Supply Air L/s 750

Return Air L/s 750

Outdoor Air L/s 750

Condenser Air L/s 450

Exhaust Air – (RA + CA) L/s 1200

Compressor Qty 1

Refrigerant Charge (R407C) kg/Comp 2.7

Total Compressor Capacity kWr 16

OUTDOOR AIR TO SUPPLY AIR

Pressure Drop Heat Exchanger Pa 122

Pressure Drop Evaporator Coil Pa 80

External Static Pressure Up to Pa 150

Total Pressure on Supply Fan Pa 352

SUPPLY FAN

Fan Speed (max) rpm 1350

Motor Power kW 0.75

Motor Poles 4

Motor Torques Nm N/A

RETURN AIR TO EXHAUST AIR

Pressure Drop Heat Exchanger Pa 122

Pressure Drop Condenser Coil Pa 45

External Static Pressure Up to Pa 150

Total Pressure on Exhaust Fan Pa 317

EXHAUST FAN

Fan Speed (max) rpm 1350

Motor Power kW 0.75

Motor Poles 4

Motor Torques Nm N/A

CONDENSER AIR

Fan Qty 0

Air Flow L/s 450

Fan Speed N/A

COIL SIZE

Condenser Coil mm 1060 X 508

Evaporator Coil mm 1060 X 356

Face Velocity Coil Evap m/s 1.99

ELECTRICAL POWERING 415/3/50

Compressor (RLA / FLA) A 8.9/17.0

Supply Fan (FLA) A 4.0

Exhaust Fan (FLA) A 4.0

Condenser Fan (FLA) A N/A

Nominal Running Current A 8.9/12.9/12.9

Total Full Load Amps A 17.0/21.0/21.0

SOUND LEVEL

Sound Pressure Level Intake @ 4m dB (A) 67

Sound Pressure Level Exhaust @ 1m dB (A) 75

ROOFTOP SCHEMATICS & DIMENSIONS

Standard With Economy Cycle

UNIT DIMENSION (mm) and Weight (kg)

Body Width (E) / Overall Width (F) 1560/1760 1750/1950

Body Depth (G) / Overall Depth (H) 1250/1330 1550/1740

Body Height (I) / Overall Height (J) 1050/1150 1100/1200

Weight (kg) 420 500

SPIGOT SIZES (mm)

Supply Air (C x D1) 1010 x 325 1010 x 325

Return Air (A x B2) 1460 x 380 1300 x 430

Exhaust Air (C x D2) 1010 x 470 1010 x 470

Outdoor Air (A x B1) 1460 x 520 1300 x 330

CLEARANCE REQUIREMENT (mm)

Minimum LHS Requirement 1200 1200

Minimum RHS Requirement 1000 1000

Base Frame (Standard Unit) Base Frame (with Economy Cycle)

Page 3: ROOFTOP PACKAGED UNITS - Air Change · Exhaust Air – (RA + CA) L/s 800 Compressor Qty 1 Refrigerant Charge (R407C) kg ... Outdoor Air (A x B1) 1650 x 520 1425 x 330 CLEARANCE REQUIREMENT

Air Change Australia Pty Ltd accept no responsibility for possible errors in catalogues, brochures and other printed material. Air Change Australia Pty Ltd reserves the right to alter its products without notice.

ROOFTOP PACKAGED UNITS

ACS20RCRTP TECHNICAL SPECIFICATIONS UNIT VALUE

Supply Air L/s 1000

Return Air L/s 1000

Outdoor Air L/s 1000

Condenser Air L/s 600

Exhaust Air – (RA + CA) L/s 1600

Compressor Qty 1

Refrigerant Charge (R407C) kg/Comp 4.4

Total Compressor Capacity kWr 20

OUTDOOR AIR TO SUPPLY AIR

Pressure Drop Heat Exchanger Pa 133

Pressure Drop Evaporator Coil Pa 100

External Static Pressure Up to Pa 200

Total Pressure on Supply Fan Pa 433

SUPPLY FAN

Fan Speed (max) rpm 2400

Motor Power kW 1.5

Motor Poles 4

Motor Torques Nm 10.2

RETURN AIR TO EXHAUST AIR

Pressure Drop Heat Exchanger Pa 133

Pressure Drop Condenser Coil Pa 95

External Static Pressure Up to Pa 150

Total Pressure on Exhaust Fan Pa 378

EXHAUST FAN

Fan Speed (max) rpm 2400

Motor Power kW 1.5

Motor Poles 4

Motor Torques Nm 10.2

CONDENSER AIR

Fan Qty 0

Air Flow L/s 600

Fan Speed N/A

COIL SIZE

Condenser Coil mm 1250 X 508

Evaporator Coil mm 1250 X 356

Face Velocity Coil Evap m/s 2.25

ELECTRICAL POWERING 415/3/50

Compressor (RLA / FLA) A 10.2/17.0

Supply Fan (RLA / FLA) A 3.4

Exhaust Fan (RLA / FLA) A 3.4

Condenser Fan (RLA / FLA) A N/A

Nominal Running Current A 18/17/17

Total Full Load Amps A 24.8/23.8/23.8

SOUND LEVEL

Sound Pressure Level Intake @ 4m dB (A) 67

Sound Pressure Level Exhaust @ 1m dB (A) 75

ROOFTOP SCHEMATICS & DIMENSIONS

Standard With Economy Cycle

UNIT DIMENSION (mm) and Weight (kg)

Body Width (E) / Overall Width (F) 1750/1950 2000/2200

Body Depth (G) / Overall Depth (H) 1550/1630 1550/1740

Body Height (I) / Overall Height (J) 1100/1200 1200/1300

Weight (kg) 500 570

SPIGOT SIZES (mm)

Supply Air (C x D1) 1200 x 325 1200 x 325

Return Air (A x B2) 1650 x 430 1425 x 440

Exhaust Air (C x D2) 1200 x 470 1200 x 470

Outdoor Air (A x B1) 1650 x 520 1425 x 330

CLEARANCE REQUIREMENT (mm)

Minimum LHS Requirement 1200 1200

Minimum RHS Requirement 1000 1000

Base Frame (Standard Unit) Base Frame (with Economy Cycle)

Page 4: ROOFTOP PACKAGED UNITS - Air Change · Exhaust Air – (RA + CA) L/s 800 Compressor Qty 1 Refrigerant Charge (R407C) kg ... Outdoor Air (A x B1) 1650 x 520 1425 x 330 CLEARANCE REQUIREMENT

Air Change Australia Pty Ltd accept no responsibility for possible errors in catalogues, brochures and other printed material. Air Change Australia Pty Ltd reserves the right to alter its products without notice.

ROOFTOP PACKAGED UNITS

ACS23RCRTP TECHNICAL SPECIFICATIONS UNIT VALUE

Supply Air L/s 1100

Return Air L/s 1100

Outdoor Air L/s 1000

Condenser Air L/s 660

Exhaust Air – (RA + CA) L/s 1760

Compressor Qty 1

Refrigerant Charge (R407C) kg/Comp 3.4

Total Compressor Capacity kWr 23

OUTDOOR AIR TO SUPPLY AIR

Pressure Drop Heat Exchanger Pa 140

Pressure Drop Evaporator Coil Pa 120

External Static Pressure Up to Pa 200

Total Pressure on Supply Fan Pa 460

SUPPLY FAN

Fan Speed (max) rpm 2400

Motor Power kW 1.5

Motor Poles 4

Motor Torques Nm 10.2

RETURN AIR TO EXHAUST AIR

Pressure Drop Heat Exchanger Pa 140

Pressure Drop Condenser Coil Pa 105

External Static Pressure Up to Pa 150

Total Pressure on Exhaust Fan Pa 395

EXHAUST FAN

Fan Speed (max) rpm 2000

Motor Power kW 2.2

Motor Poles 4

Motor Torques Nm 14.7

CONDENSER AIR

Fan Qty 0

Air Flow L/s 660

Fan Speed N/A

COIL SIZE

Condenser Coil mm 1250 X 508

Evaporator Coil mm 1250 X 356

Face Velocity Coil Evap m/s 2.47

ELECTRICAL POWERING 415/3/50

Compressor (RLA / FLA) A 11.5/17.0

Supply Fan (FLA) A 3.4

Exhaust Fan (FLA) A 4.7

Condenser Fan (FLA) A N/A

Nominal Running Current A 20.6/19.6/19.6

Total Full Load Amps A 26.1/25.1/25.1

SOUND LEVEL

Sound Pressure Level Intake @ 4m dB (A) 67

Sound Pressure Level Exhaust @ 1m dB (A) 75

ROOFTOP SCHEMATICS & DIMENSIONS

Standard With Economy Cycle

UNIT DIMENSION (mm) and Weight (kg)

Body Width (E) / Overall Width (F) 1750/1950 2000/2200

Body Depth (G) / Overall Depth (H) 1550/1630 1550/1740

Body Height (I) / Overall Height (J) 1100/1200 1200/1300

Weight (kg) 580 600

SPIGOT SIZES (mm)

Supply Air (C x D1) 1200 x 325 1200 x 325

Return Air (A x B2) 1650 x 430 1425 x 440

Exhaust Air (C x D2) 1200 x 470 1200 x 470

Outdoor Air (A x B1) 1650 x 520 1425 x 330

CLEARANCE REQUIREMENT (mm)

Minimum LHS Requirement 1200 1200

Minimum RHS Requirement 1000 1000

Base Frame (Standard Unit) Base Frame (with Economy Cycle) Base Frame (Standard Unit) Base Frame (with Economy) Cycle)

Page 5: ROOFTOP PACKAGED UNITS - Air Change · Exhaust Air – (RA + CA) L/s 800 Compressor Qty 1 Refrigerant Charge (R407C) kg ... Outdoor Air (A x B1) 1650 x 520 1425 x 330 CLEARANCE REQUIREMENT

Air Change Australia Pty Ltd accept no responsibility for possible errors in catalogues, brochures and other printed material. Air Change Australia Pty Ltd reserves the right to alter its products without notice.

ROOFTOP PACKAGED UNITS

ACS27RCRTP TECHNICAL SPECIFICATIONS UNIT VALUE

Supply Air L/s 1200

Return Air L/s 1200

Outdoor Air L/s 1200

Condenser Air L/s 720

Exhaust Air – (RA + CA) L/s 1920

Compressor Qty 1

Refrigerant Charge (R407C) kg/Comp 5.7

Total Compressor Capacity kWr 27

OUTDOOR AIR TO SUPPLY AIR

Pressure Drop Heat Exchanger Pa 136

Pressure Drop Evaporator Coil Pa 140

External Static Pressure Up to Pa 200

Total Pressure on Supply Fan Pa 476

SUPPLY FAN

Fan Speed (max) rpm 2400

Motor Power kW 1.5

Motor Poles 4

Motor Torques Nm 10.2

RETURN AIR TO EXHAUST AIR

Pressure Drop Heat Exchanger Pa 136

Pressure Drop Condenser Coil Pa 85

External Static Pressure Up to Pa 200

Total Pressure on Exhaust Fan Pa 421

EXHAUST FAN

Fan Speed (max) rpm 2000

Motor Power kW 2.2

Motor Poles 4

Motor Torques Nm 14.7

CONDENSER AIR

Fan Qty 0

Air Flow L/s 720

Fan Speed N/A

COIL SIZE

Condenser Coil mm 1500 X 584

Evaporator Coil mm 1500 X 432

Face Velocity Coil Evap m/s 1.85

ELECTRICAL POWERING 415/3/50

Compressor (RLA / FLA) A 13.5/20.0

Supply Fan (FLA) A 3.4

Exhaust Fan (FLA) A 4.7

Condenser Fan (FLA) A N/A

Nominal Running Current A 22.6/21.6/21.6

Total Full Load Amps A 29.1/28.1/28.1

SOUND LEVEL

Sound Pressure Level Intake @ 4m dB (A) 67

Sound Pressure Level Exhaust @ 1m dB (A) 75

ROOFTOP SCHEMATICS & DIMENSIONS

Standard With Economy Cycle

UNIT DIMENSION (mm) and Weight (kg)

Body Width (E) / Overall Width (F) 2000/2200 2050/2250

Body Depth (G) / Overall Depth (H) 1550/1630 2270/2460

Body Height (I) / Overall Height (J) 1200/1300 1750/1850

Weight (kg) 610 880

SPIGOT SIZES (mm)

Supply Air (C x D1) 1450 x 380 1450 x 380

Return Air (A x B2) 1900 x 440 1625 x 720

Exhaust Air (C x D2) 1450 x 560 1450 x 560

Outdoor Air (A x B1) 1900 x 610 1625 x 620

CLEARANCE REQUIREMENT (mm)

Minimum LHS Requirement 1200 1200

Minimum RHS Requirement 1000 1000

Base Frame (Standard Unit) Base Frame (with Economy Cycle) Base Frame (Standard Unit) Base Frame (with Economy) Cycle)

Page 6: ROOFTOP PACKAGED UNITS - Air Change · Exhaust Air – (RA + CA) L/s 800 Compressor Qty 1 Refrigerant Charge (R407C) kg ... Outdoor Air (A x B1) 1650 x 520 1425 x 330 CLEARANCE REQUIREMENT

Air Change Australia Pty Ltd accept no responsibility for possible errors in catalogues, brochures and other printed material. Air Change Australia Pty Ltd reserves the right to alter its products without notice.

ROOFTOP PACKAGED UNITS

ACS32RCRTP TECHNICAL SPECIFICATIONS UNIT VALUE

Supply Air L/s 1400

Return Air L/s 1400

Outdoor Air L/s 1400

Condenser Air L/s 840

Exhaust Air – (RA + CA) L/s 2240

Compressor Qty 1

Refrigerant Charge (R407C) kg/Comp 5.6

Total Compressor Capacity kWr 32

OUTDOOR AIR TO SUPPLY AIR

Pressure Drop Heat Exchanger Pa 148

Pressure Drop Evaporator Coil Pa 160

External Static Pressure Up to Pa 200

Total Pressure on Supply Fan Pa 508

SUPPLY FAN

Fan Speed (max) rpm 2000

Motor Power kW 2.2

Motor Poles 4

Motor Torques Nm 14.7

RETURN AIR TO EXHAUST AIR

Pressure Drop Heat Exchanger Pa 148

Pressure Drop Condenser Coil Pa 105

External Static Pressure Up to Pa 200

Total Pressure on Exhaust Fan Pa 453

EXHAUST FAN

Fan Speed (max) rpm 2000

Motor Power kW 3

Motor Poles 4

Motor Torques Nm 20.0

CONDENSER AIR

Fan Qty 0

Air Flow L/s 840

Fan Speed N/A

COIL SIZE

Condenser Coil mm 1500 X 584

Evaporator Coil mm 1500 X 432

Face Velocity Coil Evap m/s 2.16

ELECTRICAL POWERING 415/3/50

Compressor (RLA / FLA) A 16.5/29.0

Supply Fan (FLA) A 4.7

Exhaust Fan (FLA) A 6.2

Condenser Fan (FLA) A N/A

Nominal Running Current A 28.4/27.4/27.4

Total Full Load Amps A 40.9/39.9/39.9

SOUND LEVEL

Sound Pressure Level Intake @ 4m dB (A) 67

Sound Pressure Level Exhaust @ 1m dB (A) 75

ROOFTOP SCHEMATICS & DIMENSIONS

Standard With Economy Cycle

UNIT DIMENSION (mm) and Weight (kg)

Body Width (E) / Overall Width (F) 2000/2200 2050/2250

Body Depth (G) / Overall Depth (H) 1550/1630 2270/2460

Body Height (I) / Overall Height (J) 1200/1300 1750/1850

Weight (kg) 660 900

SPIGOT SIZES (mm)

Supply Air (C x D1) 1450 x 380 1450 x 380

Return Air (A x B2) 1900 x 440 1625 x 720

Exhaust Air (C x D2) 1450 x 560 1450 x 560

Outdoor Air (A x B1) 1900 x 610 1625 x 620

CLEARANCE REQUIREMENT (mm)

Minimum LHS Requirement 1200 1200

Minimum RHS Requirement 1000 1000

Base Frame (Standard Unit) Base Frame (with Economy Cycle)

Page 7: ROOFTOP PACKAGED UNITS - Air Change · Exhaust Air – (RA + CA) L/s 800 Compressor Qty 1 Refrigerant Charge (R407C) kg ... Outdoor Air (A x B1) 1650 x 520 1425 x 330 CLEARANCE REQUIREMENT

Air Change Australia Pty Ltd accept no responsibility for possible errors in catalogues, brochures and other printed material. Air Change Australia Pty Ltd reserves the right to alter its products without notice.

ROOFTOP PACKAGED UNITS

ACS36RCRTP TECHNICAL SPECIFICATIONS UNIT VALUE

Supply Air L/s 1700

Return Air L/s 1700

Outdoor Air L/s 1700

Condenser Air L/s 1020

Exhaust Air – (RA + CA) L/s 2720

Compressor Qty 1

Refrigerant Charge (R407C) kg/Comp 5.6

Total Compressor Capacity kWr 36

OUTDOOR AIR TO SUPPLY AIR

Pressure Drop Heat Exchanger Pa 167

Pressure Drop Evaporator Coil Pa 127

External Static Pressure Up to Pa 250

Total Pressure on Supply Fan Pa 544

SUPPLY FAN

Fan Speed (max) rpm 2000

Motor Power kW 3

Motor Poles 4

Motor Torques Nm 20

RETURN AIR TO EXHAUST AIR

Pressure Drop Heat Exchanger Pa 167

Pressure Drop Condenser Coil Pa 140

External Static Pressure Up to Pa 200

Total Pressure on Exhaust Fan Pa 507

EXHAUST FAN

Fan Speed (max) Rpm 1800

Motor Power kW 4

Motor Poles 4

Motor Torques Nm 26.6

CONDENSER AIR

Fan Qty 0

Air Flow L/s 1020

Fan Speed N/A

COIL SIZE

Condenser Coil mm 1500 X 584

Evaporator Coil mm 1500 X 432

Face Velocity Coil Evap m/s 2.62

ELECTRICAL POWERING 415/3/50

Compressor (RLA / FLA) A 18/32

Supply Fan (FLA) A 6.2

Exhaust Fan (FLA) A 8

Condenser Fan (FLA) A N/A

Nominal Running Current A 33.2/32.2/32.2

Total Full Load Amps A 47.2/46.2/46.2

SOUND LEVEL

Sound Pressure Level Intake @ 4m dB (A) 67

Sound Pressure Level Exhaust @ 1m dB (A) 75

ROOFTOP SCHEMATICS & DIMENSIONS

Standard With Economy Cycle

UNIT DIMENSION (mm) and Weight (kg)

Body Width (E) / Overall Width (F) 2000/2200 2050/2250

Body Depth (G) / Overall Depth (H) 1550/1630 2270/2460

Body Height (I) / Overall Height (J) 1200/1300 1750/1850

Weight (kg) 780 1020

SPIGOT SIZES (mm)

Supply Air (C x D1) 1450 x 380 1450 x 380

Return Air (A x B2) 1900 x 440 1625 x 720

Exhaust Air (C x D2) 1450 x 560 1450 x 560

Outdoor Air (A x B1) 1900 x 610 1625 x 620

CLEARANCE REQUIREMENT (mm)

Minimum LHS Requirement 1200 1200

Minimum RHS Requirement 1000 1000

Base Frame (Standard Unit) Base Frame (with Economy Cycle)

Page 8: ROOFTOP PACKAGED UNITS - Air Change · Exhaust Air – (RA + CA) L/s 800 Compressor Qty 1 Refrigerant Charge (R407C) kg ... Outdoor Air (A x B1) 1650 x 520 1425 x 330 CLEARANCE REQUIREMENT

Air Change Australia Pty Ltd accept no responsibility for possible errors in catalogues, brochures and other printed material. Air Change Australia Pty Ltd reserves the right to alter its products without notice.

ROOFTOP PACKAGED UNITS

ACL45RCRTP TECHNICAL SPECIFICATIONS UNIT VALUE

Supply Air L/s 2000

Return Air L/s 2000

Outdoor Air L/s 2000

Condenser Air L/s 1500

Exhaust Air – (RA + CA) L/s 3500

Compressor Qty 2

Refrigerant Charge (R407C) kg/Comp 4.6

Total Compressor Capacity kWr 45

OUTDOOR AIR TO SUPPLY AIR

Pressure Drop Heat Exchanger Pa 183

Pressure Drop Evaporator Coil Pa 80

External Static Pressure Up to Pa 250

Total Pressure on Supply Fan Pa 513

SUPPLY FAN

Fan Speed (max) rpm 1800

Motor Power kW 2.2

Motor Poles 4

Motor Torques Nm 14.7

RETURN AIR TO EXHAUST AIR

Pressure Drop Heat Exchanger Pa 183

Pressure Drop Condenser Coil Pa 105

External Static Pressure Up to Pa 200

Total Pressure on Exhaust Fan Pa 488

EXHAUST FAN

Fan Speed (max) rpm 1800

Motor Power kW 2.2

Motor Poles 4

Motor Torques Nm 14.7

CONDENSER AIR

Fan Qty 1

Air Flow L/s 1500

Fan Speed 1360

COIL SIZE

Condenser Coil mm 1500 X 762

Evaporator Coil mm 1500 X 635

Face Velocity Coil Evap m/s 2.10

ELECTRICAL POWERING 415/3/50

Compressor (RLA / FLA) A 23/34

Supply Fan (FLA) A 4.7

Exhaust Fan (FLA) A 4.7

Condenser Fan (FLA) A 1.5

Nominal Running Current A 34.9/33.9/33.9

Total Full Load Amps A 45.9/44.9/44.9

SOUND LEVEL

Sound Pressure Level Intake @ 4m dB (A) 67

Sound Pressure Level Exhaust @ 1m dB (A) 75

R O O F T O P S C H E M A T I C S & D I M E N S I O N S

Standard With Economy Cycle

UNIT DIMENSION (mm) and Weight (kg)

Body Width (E) / Overall Width (F) 2050 / 2250 2700 / 2900

Body Depth (G) / Overall Depth (H) 2270 / 2350 2270 / 2460

Body Height (I) / Overall Height (J) 1750 / 1850 1865 / 1965

Weight (kg) 1060 1400

SPIGOT SIZES (mm)

Supply Air (C x D1) 1450 x 580 1450 x 580

Return Air (A x B2) 1950 x 720 2275 x 740

Exhaust Air (C x D2) 1450 x 730 1450 x 730

Outdoor Air (A x B1) 1950 x 880 2275 x 975

CLEARANCE REQUIREMENT (mm)

Minimum LHS Requirement 1200 1200

Minimum RHS Requirement 1000 1000

Base Frame (Standard Unit) Base Frame (with Economy Cycle)

Page 9: ROOFTOP PACKAGED UNITS - Air Change · Exhaust Air – (RA + CA) L/s 800 Compressor Qty 1 Refrigerant Charge (R407C) kg ... Outdoor Air (A x B1) 1650 x 520 1425 x 330 CLEARANCE REQUIREMENT

Air Change Australia Pty Ltd accept no responsibility for possible errors in catalogues, brochures and other printed material. Air Change Australia Pty Ltd reserves the right to alter its products without notice.

ROOFTOP PACKAGED UNITS

ACL52RCRTP TECHNICAL SPECIFICATIONS UNIT VALUE

Supply Air L/s 2300

Return Air L/s 2300

Outdoor Air L/s 2300

Condenser Air L/s 1500

Exhaust Air – (RA + CA) L/s 3800

Compressor Qty 2

Refrigerant Charge (R407C) kg/Comp 4.5

Total Compressor Capacity kWr 52

OUTDOOR AIR TO SUPPLY AIR

Pressure Drop Heat Exchanger Pa 202

Pressure Drop Evaporator Coil Pa 110

External Static Pressure Up to Pa 300

Total Pressure on Supply Fan Pa 612

SUPPLY FAN

Fan Speed (max) rpm 1800

Motor Power kW 3

Motor Poles 4

Motor Torques Nm 20

RETURN AIR TO EXHAUST AIR

Pressure Drop Heat Exchanger Pa 202

Pressure Drop Condenser Coil Pa 135

External Static Pressure Up to Pa 200

Total Pressure on Exhaust Fan Pa 537

EXHAUST FAN

Fan Speed (max) rpm 1800

Motor Power kW 3

Motor Poles 4

Motor Torques Nm 20

CONDENSER AIR

Fan Qty 1

Air Flow L/s 1500

Fan Speed 1360

COIL SIZE

Condenser Coil mm 1500 X 762

Evaporator Coil mm 1500 X 635

Face Velocity Coil Evap m/s 2.41

ELECTRICAL POWERING 415/3/50

Compressor (RLA / FLA) A 27/40

Supply Fan (FLA) A 6.2

Exhaust Fan (FLA) A 6.2

Condenser Fan (FLA) A 1.5

Nominal Running Current A 41.9/40.9/40.9

Total Full Load Amps A 54.9/53.9/53.9

SOUND LEVEL

Sound Pressure Level Intake @ 4m dB (A) 67

Sound Pressure Level Exhaust @ 1m dB (A) 76

R O O F T O P S C H E M A T I C S & D I M E N S I O N S

Standard With Economy Cycle

UNIT DIMENSION (mm) and Weight (kg)

Body Width (E) / Overall Width (F) 2050 / 2250 2700 / 2900

Body Depth (G) / Overall Depth (H) 2270 / 2350 2270 / 2460

Body Height (I) / Overall Height (J) 1750 / 1850 1865 / 1965

Weight (kg) 1130 1450

SPIGOT SIZES (mm)

Supply Air (C x D1) 1450 x 580 1450 x 580

Return Air (A x B2) 1950 x 720 2275 x 740

Exhaust Air (C x D2) 1450 x 730 1450 x 730

Outdoor Air (A x B1) 1950 x 880 2275 x 975

CLEARANCE REQUIREMENT (mm)

Minimum LHS Requirement 1200 1200

Minimum RHS Requirement 1000 1000

Base Frame (Standard Unit) Base Frame (with Economy Cycle)

Page 10: ROOFTOP PACKAGED UNITS - Air Change · Exhaust Air – (RA + CA) L/s 800 Compressor Qty 1 Refrigerant Charge (R407C) kg ... Outdoor Air (A x B1) 1650 x 520 1425 x 330 CLEARANCE REQUIREMENT

Air Change Australia Pty Ltd accept no responsibility for possible errors in catalogues, brochures and other printed material. Air Change Australia Pty Ltd reserves the right to alter its products without notice.

ROOFTOP PACKAGED UNITS

ACL60RCRTP TECHNICAL SPECIFICATIONS UNIT VALUE

Supply Air L/s 2700

Return Air L/s 2700

Outdoor Air L/s 2700

Condenser Air L/s 1500

Exhaust Air – (RA + CA) L/s 4200

Compressor Qty 2

Refrigerant Charge (R407C) kg/Comp 4.5

Total Compressor Capacity kWr 60

OUTDOOR AIR TO SUPPLY AIR

Pressure Drop Heat Exchanger Pa 226

Pressure Drop Evaporator Coil Pa 82

External Static Pressure Up to Pa 300

Total Pressure on Supply Fan Pa 608

SUPPLY FAN

Fan Speed (max) rpm 1800

Motor Power kW 4

Motor Poles 4

Motor Torques Nm 26.6

RETURN AIR TO EXHAUST AIR

Pressure Drop Heat Exchanger Pa 226

Pressure Drop Condenser Coil Pa 110

External Static Pressure Up to Pa 250

Total Pressure on Exhaust Fan Pa 586

EXHAUST FAN

Fan Speed (max) rpm 1800

Motor Power kW 4

Motor Poles 4

Motor Torques Nm 26.6

CONDENSER AIR

Fan Qty 1

Air Flow L/s 1500

Fan Speed 1360

COIL SIZE

Condenser Coil mm 1500 X 762

Evaporator Coil mm 1500 X 635

Face Velocity Coil Evap m/s 2.83

ELECTRICAL POWERING 415/3/50

Compressor (RLA / FLA) A 33/58

Supply Fan (FLA) A 8

Exhaust Fan (FLA) A 8

Condenser Fan (FLA) A 1.5

Nominal Running Current A 51.5/50.5/50.5

Total Full Load Amps A 76.5/75.5/75.5

SOUND LEVEL

Sound Pressure Level Intake @ 4m dB (A) 67

Sound Pressure Level Exhaust @ 1m dB (A) 76

R O O F T O P S C H E M A T I C S & D I M E N S I O N S

Standard With Economy Cycle

UNIT DIMENSION (mm) and Weight (kg)

Body Width (E) / Overall Width (F) 2050 / 2250 2700 / 2900

Body Depth (G) / Overall Depth (H) 2270 / 2350 2270 / 2460

Body Height (I) / Overall Height (J) 1750 / 1850 1865 / 1965

Weight (kg) 1320 1650

SPIGOT SIZES (mm)

Supply Air (C x D1) 1450 x 580 1450 x 580

Return Air (A x B2) 1950 x 720 2275 x 740

Exhaust Air (C x D2) 1450 x 730 1450 x 730

Outdoor Air (A x B1) 1950 x 880 2275 x 975

CLEARANCE REQUIREMENT (mm)

Minimum LHS Requirement 1200 1200

Minimum RHS Requirement 1000 1000

Base Frame (Standard Unit) Base Frame (with Economy Cycle)

Page 11: ROOFTOP PACKAGED UNITS - Air Change · Exhaust Air – (RA + CA) L/s 800 Compressor Qty 1 Refrigerant Charge (R407C) kg ... Outdoor Air (A x B1) 1650 x 520 1425 x 330 CLEARANCE REQUIREMENT

Air Change Australia Pty Ltd accept no responsibility for possible errors in catalogues, brochures and other printed material. Air Change Australia Pty Ltd reserves the right to alter its products without notice.

ROOFTOP PACKAGED UNITS

ACL65RCRTP TECHNICAL SPECIFICATIONS UNIT VALUE

Supply Air L/s 2800

Return Air L/s 2800

Outdoor Air L/s 2800

Condenser Air L/s 3000

Exhaust Air – (RA + CA) L/s 5800

Compressor Qty 2

Refrigerant Charge (R407C) kg/Comp 6.5

Total Compressor Capacity kWr 65

OUTDOOR AIR TO SUPPLY AIR

Pressure Drop Heat Exchanger Pa 189

Pressure Drop Evaporator Coil Pa 95

External Static Pressure Up to Pa 300

Total Pressure on Supply Fan Pa 584

SUPPLY FAN

Fan Speed (max) rpm 1800

Motor Power kW 4

Motor Poles 4

Motor Torques Nm 26.6

RETURN AIR TO EXHAUST AIR

Pressure Drop Heat Exchanger Pa 189

Pressure Drop Condenser Coil Pa 95

External Static Pressure Up to Pa 250

Total Pressure on Exhaust Fan Pa 534

EXHAUST FAN

Fan Speed (max) rpm 1800

Motor Power kW 4

Motor Poles 4

Motor Torques Nm 26.6

CONDENSER AIR

Fan Qty 2

Air Flow L/s 3000

Fan Speed 1360

COIL SIZE

Condenser Coil mm 2110 X 914

Evaporator Coil mm 2110 X 762

Face Velocity Coil Evap m/s 1.74

ELECTRICAL POWERING 415/3/50

Compressor (RLA / FLA) A 33/58

Supply Fan (FLA) A 8

Exhaust Fan (FLA) A 8

Condenser Fan (FLA) A 3

Nominal Running Current A 53/52/52

Total Full Load Amps A 78/77/77

SOUND LEVEL

Sound Pressure Level Intake @ 4m dB (A) 67

Sound Pressure Level Exhaust @ 1m dB (A) 79

R O O F T O P S C H E M A T I C S & D I M E N S I O N S

Standard With Economy Cycle

UNIT DIMENSION (mm) and Weight (kg)

Body Width (E) / Overall Width (F) 2700 / 2900 2700 / 2900

Body Depth (G) / Overall Depth (H) 2270 / 2350 2270 / 2460

Body Height (I) / Overall Height (J) 1865 / 1965 1865 / 1965

Weight (kg) 1650 1680

SPIGOT SIZES (mm)

Supply Air (C x D1) 2060 x 700 2060 x 700

Return Air (A x B2) 2600 x 740 2275 x 740

Exhaust Air (C x D2) 2060 x 880 2060 x 880

Outdoor Air (A x B1) 2600 x 975 2275 x 975

CLEARANCE REQUIREMENT (mm)

Minimum LHS Requirement 1200 1200

Minimum RHS Requirement 1000 1000

Base Frame (Standard Unit) Base Frame (with Economy Cycle)

Page 12: ROOFTOP PACKAGED UNITS - Air Change · Exhaust Air – (RA + CA) L/s 800 Compressor Qty 1 Refrigerant Charge (R407C) kg ... Outdoor Air (A x B1) 1650 x 520 1425 x 330 CLEARANCE REQUIREMENT

Air Change Australia Pty Ltd accept no responsibility for possible errors in catalogues, brochures and other printed material. Air Change Australia Pty Ltd reserves the right to alter its products without notice.

ROOFTOP PACKAGED UNITS

ACL70RCRTP TECHNICAL SPECIFICATIONS UNIT VALUE

Supply Air L/s 3200

Return Air L/s 3200

Outdoor Air L/s 3200

Condenser Air L/s 3000

Exhaust Air – (RA + CA) L/s 6200

Compressor Qty 2

Refrigerant Charge (R407C) kg/Comp 6.9

Total Compressor Capacity kWr 70

OUTDOOR AIR TO SUPPLY AIR

Pressure Drop Heat Exchanger Pa 208

Pressure Drop Evaporator Coil Pa 120

External Static Pressure Up to Pa 300

Total Pressure on Supply Fan Pa 628

SUPPLY FAN

Fan Speed (max) rpm 1400

Motor Power kW 5.5

Motor Poles 4

Motor Torques Nm 36.4

RETURN AIR TO EXHAUST AIR

Pressure Drop Heat Exchanger Pa 208

Pressure Drop Condenser Coil Pa 120

External Static Pressure Up to Pa 250

Total Pressure on Exhaust Fan Pa 578

EXHAUST FAN

Fan Speed (max) rpm 1400

Motor Power kW 5.5

Motor Poles 4

Motor Torques Nm 36.4

CONDENSER AIR

Fan Qty 2

Air Flow L/s 3000

Fan Speed 1360

COIL SIZE

Condenser Coil mm 2110 X 914

Evaporator Coil mm 2110 X 762

Face Velocity Coil Evap m/s 1.99

ELECTRICAL POWERING 415/3/50

Compressor (RLA / FLA) A 36/64

Supply Fan (FLA) A 10.8

Exhaust Fan (FLA) A 10.8

Condenser Fan (FLA) A 3

Nominal Running Current A 61.6/60.6/60.6

Total Full Load Amps A 89.6/88.6/88.6

SOUND LEVEL

Sound Pressure Level Intake @ 4m dB (A) 67

Sound Pressure Level Exhaust @ 1m dB (A) 79

R O O F T O P S C H E M A T I C S & D I M E N S I O N S

Standard With Economy Cycle

UNIT DIMENSION (mm) and Weight (kg)

Body Width (E) / Overall Width (F) 2700 / 2900 3350 / 3550

Body Depth (G) / Overall Depth (H) 2270 / 2350 2270 / 2460

Body Height (I) / Overall Height (J) 1865 / 1965 1865 / 1965

Weight (kg) 1720 2000

SPIGOT SIZES (mm)

Supply Air (C x D1) 2060 x 700 2060 x 700

Return Air (A x B2) 2600 x 740 2925 x 740

Exhaust Air (C x D2) 2060 x 880 2060 x 880

Outdoor Air (A x B1) 2600 x 975 2925 x 975

CLEARANCE REQUIREMENT (mm)

Minimum LHS Requirement 1500 1500

Minimum RHS Requirement 1000 1000

Base Frame (Standard Unit) Base Frame (with Economy Cycle)

Page 13: ROOFTOP PACKAGED UNITS - Air Change · Exhaust Air – (RA + CA) L/s 800 Compressor Qty 1 Refrigerant Charge (R407C) kg ... Outdoor Air (A x B1) 1650 x 520 1425 x 330 CLEARANCE REQUIREMENT

Air Change Australia Pty Ltd accept no responsibility for possible errors in catalogues, brochures and other printed material. Air Change Australia Pty Ltd reserves the right to alter its products without notice.

ROOFTOP PACKAGED UNITS

ACL82RCRTP TECHNICAL SPECIFICATIONS UNIT VALUE

Supply Air L/s 3700

Return Air L/s 3700

Outdoor Air L/s 3700

Condenser Air L/s 3000

Exhaust Air – (RA + CA) L/s 6700

Compressor Qty 2

Refrigerant Charge (R407C) kg/Comp 7.3

Total Compressor Capacity kWr 82

OUTDOOR AIR TO SUPPLY AIR

Pressure Drop Heat Exchanger Pa 231

Pressure Drop Evaporator Coil Pa 102

External Static Pressure Up to Pa 340

Total Pressure on Supply Fan Pa 583

SUPPLY FAN

Fan Speed (max) rpm 1400

Motor Power kW 5.5

Motor Poles 4

Motor Torques Nm 36.4

RETURN AIR TO EXHAUST AIR

Pressure Drop Heat Exchanger Pa 231

Pressure Drop Condenser Coil Pa 102

External Static Pressure Up to Pa 250

Total Pressure on Exhaust Fan Pa 583

EXHAUST FAN

Fan Speed (max) rpm 1400

Motor Power kW 5.5

Motor Poles 4

Motor Torques Nm 36.4

CONDENSER AIR

Fan Qty 2

Air Flow L/s 3000

Fan Speed 1360

COIL SIZE

Condenser Coil mm 2110 X 914

Evaporator Coil mm 2110 X 762

Face Velocity Coil Evap m/s 2.30

ELECTRICAL POWERING 415/3/50

Compressor (RLA / FLA) A 38/64

Supply Fan (FLA) A 10.8

Exhaust Fan (FLA) A 10.8

Condenser Fan (FLA) A 3

Nominal Running Current A 63.6/62.6/62.6

Total Full Load Amps A 89.6/88.6/88.6

SOUND LEVEL

Sound Pressure Level Intake @ 4m dB (A) 67

Sound Pressure Level Exhaust @ 1m dB (A) 79

R O O F T O P S C H E M A T I C S & D I M E N S I O N S

Standard With Economy Cycle

UNIT DIMENSION (mm) and Weight (kg)

Body Width (E) / Overall Width (F) 2700 / 2900 3350 / 3550

Body Depth (G) / Overall Depth (H) 2270 / 2350 2270 / 2460

Body Height (I) / Overall Height (J) 1865 / 1965 1865 / 1965

Weight (kg) 1760 2000

SPIGOT SIZES (mm)

Supply Air (C x D1) 2060 x 700 2060 x 700

Return Air (A x B2) 2600 x 740 2925 x 740

Exhaust Air (C x D2) 2060 x 880 2060 x 880

Outdoor Air (A x B1) 2600 x 975 2925 x 975

CLEARANCE REQUIREMENT (mm)

Minimum LHS Requirement 1500 1500

Minimum RHS Requirement 1000 1000

Base Frame (Standard Unit) Base Frame (with Economy Cycle)

Page 14: ROOFTOP PACKAGED UNITS - Air Change · Exhaust Air – (RA + CA) L/s 800 Compressor Qty 1 Refrigerant Charge (R407C) kg ... Outdoor Air (A x B1) 1650 x 520 1425 x 330 CLEARANCE REQUIREMENT

Air Change Australia Pty Ltd accept no responsibility for possible errors in catalogues, brochures and other printed material. Air Change Australia Pty Ltd reserves the right to alter its products without notice.

ROOFTOP PACKAGED UNITS

ACL96RCRTP TECHNICAL SPECIFICATIONS UNIT VALUE

Supply Air L/s 4200

Return Air L/s 4200

Outdoor Air L/s 4200

Condenser Air L/s 3000

Exhaust Air – (RA + CA) L/s 7200

Compressor Qty 2

Refrigerant Charge (R407C) kg/Comp 8

Total Compressor Capacity kWr 96

OUTDOOR AIR TO SUPPLY AIR

Pressure Drop Heat Exchanger Pa 254

Pressure Drop Evaporator Coil Pa 139

External Static Pressure Up to Pa 340

Total Pressure on Supply Fan Pa 733

SUPPLY FAN

Fan Speed (max) rpm 1400

Motor Power kW 7.5

Motor Poles 4

Motor Torques Nm 49.6

RETURN AIR TO EXHAUST AIR

Pressure Drop Heat Exchanger Pa 254

Pressure Drop Condenser Coil Pa 139

External Static Pressure Up to Pa 250

Total Pressure on Exhaust Fan Pa 643

EXHAUST FAN

Fan Speed (max) rpm 1400

Motor Power kW 7.5

Motor Poles 4

Motor Torques Nm 49.6

CONDENSER AIR

Fan Qty 2

Air Flow L/s 3000

Fan Speed 1360

COIL SIZE

Condenser Coil mm 2110 X 914

Evaporator Coil mm 2110 X 762

Face Velocity Coil Evap m/s 2.61

ELECTRICAL POWERING 415/3/50

Compressor (RLA / FLA) A 45.6/70

Supply Fan (FLA) A 14.2

Exhaust Fan (FLA) A 14.2

Condenser Fan (FLA) A 3

Nominal Running Current A 78/77/77

Total Full Load Amps A 102.4/101.4/101.4

SOUND LEVEL

Sound Pressure Level Intake @ 4m dB (A) 63

Sound Pressure Level Exhaust @ 1m dB (A) 78

R O O F T O P S C H E M A T I C S & D I M E N S I O N S

Standard With Economy Cycle

UNIT DIMENSION (mm) and Weight (kg)

Body Width (E) / Overall Width (F) 2700 / 2900 3350 / 3550

Body Depth (G) / Overall Depth (H) 2270 / 2350 2270 / 2460

Body Height (I) / Overall Height (J) 1865 / 1965 1865 / 1965

Weight (kg) 1920 2000

SPIGOT SIZES (mm)

Supply Air (C x D1) 2060 x 700 2060 x 700

Return Air (A x B2) 2600 x 740 2925 x 740

Exhaust Air (C x D2) 2060 x 880 2060 x 880

Outdoor Air (A x B1) 2600 x 975 2925 x 975

CLEARANCE REQUIREMENT (mm)

Minimum LHS Requirement 1500 1500

Minimum RHS Requirement 1000 1000

Base Frame (Standard Unit) Base Frame (with Economy Cycle)

Page 15: ROOFTOP PACKAGED UNITS - Air Change · Exhaust Air – (RA + CA) L/s 800 Compressor Qty 1 Refrigerant Charge (R407C) kg ... Outdoor Air (A x B1) 1650 x 520 1425 x 330 CLEARANCE REQUIREMENT

Air Change Australia Pty Ltd accept no responsibility for possible errors in catalogues, brochures and other printed material. Air Change Australia Pty Ltd reserves the right to alter its products without notice.

ROOFTOP PACKAGED UNITS

ACL125RCRTP TECHNICAL SPECIFICATIONS UNIT VALUE

Supply Air L/s 5000

Return Air L/s 5000

Outdoor Air L/s 5000

Condenser Air L/s 3000

Exhaust Air – (RA + CA) L/s 8000

Compressor Qty 2

Refrigerant Charge (R407C) kg/Comp 11.8

Total Compressor Capacity kWr 125

OUTDOOR AIR TO SUPPLY AIR

Pressure Drop Heat Exchanger Pa 245

Pressure Drop Evaporator Coil Pa 134

External Static Pressure Up to Pa 300

Total Pressure on Supply Fan Pa 679

SUPPLY FAN

Fan Speed (max) rpm 1100

Motor Power kW 7.5

Motor Poles 6

Motor Torque Nm 74

RETURN AIR TO EXHAUST AIR

Pressure Drop Heat Exchanger Pa 245

Pressure Drop Condenser Coil Pa 128

External Static Pressure Up to Pa 300

Total Pressure on Exhaust Fan Pa 673

EXHAUST FAN

Fan Speed (max) rpm 1100

Motor Power kW 7.5

Motor Poles 6

Motor Torques Nm 74

CONDENSER AIR

Fan Qty 2

Air Flow L/s 3000

Fan Speed 1360

COIL SIZE

Condenser Coil mm 2550 X 1118

Evaporator Coil mm 2550 X 794

Face Velocity Coil Evap m/s 2.57

ELECTRICAL POWERING 415/3/50

Compressor (RLA / FLA) A 54/100

Supply Fan (FLA) A 15.6

Exhaust Fan (FLA) A 15.6

Condenser Fan (FLA) A 3

Nominal Running Current A 89.2/88.2/88.2

Total Full Load Amps A 135.2/134.2/134.2

SOUND LEVEL

Sound Pressure Level Intake @ 4m dB (A) 63

Sound Pressure Level Exhaust @ 1m dB (A) 77

R O O F T O P S C H E M A T I C S & D I M E N S I O N S

Standard With Economy Cycle

UNIT DIMENSION (mm) and Weight (kg)

Body Width (E) / Overall Width (F) 3350 / 3550 4650 / 4850

Body Depth (G) / Overall Depth (H) 2270 / 2350 2270 / 2460

Body Height (I) / Overall Height (J) 2110 / 2210 2110 / 2260

Weight (kg) 1850 2100

SPIGOT SIZES (mm)

Supply Air (C x D1) 2500 x 740 2500 x 740

Return Air (A x B2) 3250 x 800 3900 x 800

Exhaust Air (C x D2) 2500 x 1060 2500 x 1020

Outdoor Air (A x B1) 3250 x 975 3900 x 975

CLEARANCE REQUIREMENT (mm)

Minimum LHS Requirement 2000 2000

Minimum RHS Requirement 1000 1000

Base Frame (Standard Unit) Base Frame (with Economy Cycle)