Upload
others
View
0
Download
0
Embed Size (px)
Citation preview
03/2010
ROBUST Project – over-roofing and vertical extension
1
ROBUST – Renovation Of Buildings Using Steel Technologies
Vertical steel extension – Solar roof compatibility
London’s meeting presentation – 2010
CTICM: J.LAUQUIN
03-2010
03/2010
ROBUST Project – over-roofing and vertical extension
2
Feasibility of a Photovoltaic System on a vertical extension.
1 Introduction
The vertical extension project consists of the design and construction of new residentials to be built on an existing building. The project provides a prime opportunity for architects and engineers to design in a sustainable manner by considering incorporating an alternative energy system into the design. Such a system would provide energy costs reductions and would also serve to make a positive, visible statement about the ethics of all organisations involved.
The technology to be investigated is photovoltaic cells, which convert the sun’s solar energy into electrical energy to supplement power obtained from the national grid. In this report, it has been proposed that the modules could be situated on the roof. This report intends to assess the feasibility of the proposal by considering the options available, associated costs, structural impact and associated benefits.
2 Case study
It is important that this assessment of photovoltaic systems is performed with specific relation to the Vertical extension design criteria. There are many options available for PV systems where the type of cell and the mounting structure vary greatly and the appropriate combination for this project must be chosen. The deciding factors will be the available budget, the energy output required and the location and design of the roof.
The extension consists of a kind of multi-storey building in Paris, rectangular in shape(30m*12m), and although at present the roof design has not been specified, it is likely that it will consist of a two-part slope with some roof lights.
03/2010
ROBUST Project – over-roofing and vertical extension
3
Some pros and cons of PVs are listed below.
Advantages Disadvantages
• No moving parts • Ultra-low maintenance • Extremely long life
• Non-corrosive parts • Easy Installation • Modular design • Universal application • Simple controls
• High initial cost • Sensitive to shading • Variable generation
• Lowest output during winter • Low voltage output difficult to
transmit • Lack of affordable power
storage technologies that
could help offset the intermittent generation aspects of PV
They also have the advantages of a long life (over 50 years), remote application, free operation and the ability to be used as a building component, such as roof tiles. With technological developments their use in buildings is becoming increasingly attractive.
The two main impediments to the use of PV are the high cost and the relatively high environmental impact associated with their manufacture. Other sources suggest that it takes around 3 years of use for a PV panel to repay the embodied energy from
manufacture and transport.
The optimum angle of elevation of a PV cell is 20 degrees less than the latitude of the location. This suggests that the optimum angle of elevation of a PV panel located in Paris is approximately 35 degrees. This tilt has been change to 25 degrees for architectural and structural design reasons; a higher tilt would have created a large lost space under the roof. It has been observed however that the efficiency of all PV
cells varies by as little as 15% with lateral orientation.
03/2010
ROBUST Project – over-roofing and vertical extension
4
In order to have a realistic study, two kinds of panels from SYSTAIC have been used. (cf product criteria)
E140
135 W silicone crystalline panels which allow really high quality integration
S230
225 W silicone crystalline panels which allow a classic integration
At this stage it is only possible to perform a very rough calculation since details of the internal services are not known; however, an implantation exercise has been carried out with 5 scenarios:
� Scenario 1: 30.9 kW Monocrystalline E140 system south orientated
� Scenario 2: 33.8 kW Monocrystalline E140 system :16.9kW East orientated / 16.9kW West orientated
� Scenario 3: 35.5 kW Monocrystalline S230 system south orientated � Scenario 4: 35.5kW Monocrystalline S230 system :17.78kW East orientated /
17.78kW West orientated � Scenario 5: 4.72 kW Monocrystalline S230 system south orientated
A detail of the products used and of the system specifications are as adjuncted documents at the end of this note.
03/2010
ROBUST Project – over-roofing and vertical extension
5
2.1 Scenario 1
30.9 kW SOUTH
Location: 48°49'43" North, 2°24'6" East, Elevation: 48 mètres u.sea,
Nearest city: Paris, France (2 km)
Nominal power of the PV system : 30.9 kW (silicone cristallin)
Module tilt : 25.0° Module orientation (azimuth) : 0.0° Temperature losses : 7.5% (using local temperature datas)
Tilt losses : 3.2% Other losses (cables, etc): 14.0%
PV system losses: 24.7%
03/2010
ROBUST Project – over-roofing and vertical extension
6
ANNUAL GENERATION
Electrical PV generation for: Nominal Power =30.9 kW, System losses=14.0% Tilt=25 deg., Orient.=0 deg.
Month Monthly generation (kWh) Daily generation (kWh)
Jan 924 30 kWh
Feb 1479 53 kWh
Mar 2458 79 kWh
Apr 3205 107 kWh
Mai 3551 115 kWh
June 3651 122 kWh
Jul 4016 130 kWh
Aug 3626 117 kWh
Sep 2824 94 kWh
Oct 2041 66 kWh
Nov 1229 41 kWh
Dec 738 24 kWh
Annual average 2478 81
Total yearly generation(kWh) 29742
29742 kWh
03/2010
ROBUST Project – over-roofing and vertical extension
7
SYSTEM SPECIFICATION
Quantity Cost Total exc. VAT
MATERIAL (power supply and cables inc.)
Units 1045 mm x 1045 mm 184 803.00 €
Finishing 24 916.00 €
Roof windows 1045 mm x 1045 mm 8 000.00 €
Electricity features 1295.00 €
TOTAL MATERIAL Public cost w. VAT. 219 014.00 €
discount 20% 43 802.80 €
Cost w. VAT. 175 211.20 €
TOTAL FITTING Cost w. VAT. 42 690
TOTAL Cost w. VAT 217 900.70 €
VAT 19.60% 42 708.54 €
Cost VAT inc. 260 609.24 €
260 609.24 €
03/2010
ROBUST Project – over-roofing and vertical extension
8
BUY-BACK PV ELECTRICITY RATES
Building type Cond. Buy-back
Residential
Residential buildings « integrated » 58 c€/kWh
Professionnels buildings
les bâtiments d'enseignement ou de santé
« integrated » 58 c€/kWh
Offices, Industrials, commercial or farming buildings « enhanced integration » 50 c€/kWh
Other new buildings
« simplified integration » 42 c€/kWh
58.0
c€/kWh
PAYBACK
Annual generation 29742 kWh
Total VAT inc. 260 609.24 €
Buy-back
58.0
c€/kWh
Payback
15.11
year(s)
03/2010
ROBUST Project – over-roofing and vertical extension
9
2.2 Scenario 2
PARIS EAST/WEST
EST
Location: 48°49'43" North, 2°24'6" East, Elevation: 48 mètres u.sea,
Nearest city: Paris, France (2 km)
Nominal power of the PV system : 16.9 kW (silicone cristallin) Module tilt : 25.0°
Module orientation (azimuth) : -90° Temperature losses : 7.5% (using local temperature datas) Tilt losses : 3.2%
Other losses (cables, etc): 14.0%
PV system losses: 24.7%
03/2010
ROBUST Project – over-roofing and vertical extension
10
ANNUAL GENERATION
Electrical PV generation for: Nominal Power =16.9 kW, System losses =14.0% Inclin.=25 deg., Orient.=-90 deg.
Month Monthly generation (kWh) Daily generation (kWh)
Jan 328 11 kWh
Feb 562 20 kWh
Mar 1069 34 kWh
Apr 1542 51 kWh
Mai 1823 59 kWh
Jun 1943 65 kWh
Jul 2099 68 kWh
Aug 1786 58 kWh
Sep 1255 42 kWh
Oct 805 26 kWh
Nov 422 14 kWh
Dec 257 8 kWh
Annual average 1158 38
Total yearly generation(kWh) 13893
13893 kWh
OUEST
03/2010
ROBUST Project – over-roofing and vertical extension
11
Location: 48°49'43" North, 2°24'6" East, Elevation: 48 mètres u.sea,
Nearest city: Paris, France (2 km)
Nominal power of the PV system : 16.9 kW (silicone cristallin)
Module tilt : 25.0° Module orientation (azimuth) : 90°
Temperature losses : 7.5% (using local temperature datas) Tilt losses : 3.2% Other losses (cables, etc): 14.0%
PV system losses: 24.7%
03/2010
ROBUST Project – over-roofing and vertical extension
12
ANNUAL GENERATION
Electrical PV generation for: Nominal Power =16.9 kW, System losses =14.0% Inclin.=25 deg., Orient.=90 deg. Month Monthly generation (kWh) Daily generation (kWh)
Jan 330 11 kWh
Feb 562 20 kWh
Mar 1065 34 kWh
Apr 1540 51 kWh
Mai 1818 59 kWh
Jun 1936 65 kWh
Jul 2090 67 kWh
Aug 1780 57 kWh
Sep 1252 42 kWh
Oct 802 26 kWh
Nov 423 14 kWh
Dec 259 8 kWh
Annual average 1155 38
Total yearly generation(kWh) 13857
13857 kWh
Total 27750 kWh
03/2010
ROBUST Project – over-roofing and vertical extension
13
SYSTEM SPECIFICATION
Quantity Cost Cost exc. VAT.
MATERIAL (power supply and cables inc.) 201 750.00 €
Units 1045 mm x 1045 mm 201 750.00 €
Finishing 46 582.00 €
Roof windows 1045 mm x 1045 mm 16 000.00 €
Electricity features 1295.00 €
TOTAL MATERIAL Public cost w. VAT.. 265 627.00 €
Discount 20% 53 125.40 €
Cost w. VAT.. 212 501.60 €
TOTAL FITTING Cost w. VAT... 48 875
TOTAL CHANTIER Cost w. VAT... 261 376.60 €
VAT 19.60% 51 229.81 €
Cost inc. VAT. 312 606.41 €
312 606.41 €
03/2010
ROBUST Project – over-roofing and vertical extension
14
BUY-BACK PV ELECTRICITY RATES
Building type Cond. Buy-back
Residential
Residential buildings « integrated » 58 c€/kWh
Professionnels buildings
les bâtiments d'enseignement ou de santé
« integrated » 58 c€/kWh
Offices, Industrials, commercial or farming buildings « enhanced integration » 50 c€/kWh
Other new buildings
« simplified integration » 42 c€/kWh
58.0 c€/kWh
PAYBACK
Annual generation 27750 kWh
Cost inc. VAT. 312 606.41 €
Buy-buy 58.0 c€/kWh
Payback
19.42 year(s)
03/2010
ROBUST Project – over-roofing and vertical extension
15
2.3 Scenario 3
PARIS South 35.55 kW
SOUTH
Location: 48°49'43" North, 2°24'6" East, Elevation: 48 mètres u.sea,
Nearest city: Paris, France (2 km)
Nominal power of the PV system : 35.55 kW (silicone cristallin) Module tilt : 25.0° Module orientation (azimuth) : 0.0°
Temperature losses : 7.5% (using local temperature datas) Tilt losses : 3.2% Other losses (cables, etc): 14.0%
PV system losses: 24.7%
03/2010
ROBUST Project – over-roofing and vertical extension
16
ANNUAL GENERATION
Electrical PV generation for: Nominal Power =35.55 kW, System losses =14.0% tilt.=25 deg., Orient.=0 deg.
Month Monthly generation (kWh) Daily generation (kWh)
Jan 907 29 kWh
Feb 1453 52 kWh
Mar 2415 78 kWh
Apr 3149 105 kWh
Mai 3489 113 kWh
Jun 3588 120 kWh
Jul 3946 127 kWh
Aug 3562 115 kWh
Sep 2775 92 kWh
Oct 2005 65 kWh
Nov 1207 40 kWh
Dec 725 23 kWh
Annual average 2435 80 Total yearly generation(kWh) 29222
29222 kWh
SYSTEM SPECIFICATION
03/2010
ROBUST Project – over-roofing and vertical extension
17
Quantity Cost
Cost exc.
VAT.
MATERIAL (power
supply and cables inc.)
Solar panels 92072.00 €
Integration features 32257.00 €
Electricity features 13304.00 €
TOTAL MATERIAL
Public cost w.
VAT.
137 636.26
€
Discount 10% 13 763.63 €
cost w. VAT..
123 872.64
€
FITTING 46 215
TOTAL CHANTIER cost w. VAT.
170 087.64
€
VAT 19.60% 33 337.18 €
cost inc. VAT.
203 424.81
€
203 424.81
€
BUY-BACK PV ELECTRICITY RATES
Building type Cond. Buy-back
Residential
Residential buildings « integrated » 58 c€/kWh
Professionnels buildings
les bâtiments d'enseignement ou de santé
« integrated » 58 c€/kWh
Offices, Industrials, commercial or farming buildings « enhanced integration » 50 c€/kWh
Other new buildings
« simplified integration » 42 c€/kWh
50.0
c€/kWh
PAYBACK
Annual generation 29222 kWh
03/2010
ROBUST Project – over-roofing and vertical extension
18
System cost inc. VAT. 203 424.81 €
Buy-back 50.0 c€/kWh 14611
Payback
13.92 year(s)
03/2010
ROBUST Project – over-roofing and vertical extension
19
2.4 Scenario 4
PARIS EAST/WEST
EST
Location: 48°49'43" North, 2°24'6" East, Elevation: 48 mètres u.sea,
Nearest city: Paris, France (2 km)
Nominal power of the PV system : 17.775 kW (silicone cristallin) Module tilt : 25.0°
Module orientation (azimuth) : -90° Temperature losses : 7.5% (using local temperature datas) Tilt losses : 3.2%
Other losses (cables, etc): 14.0%
PV system losses: 24.7%
03/2010
ROBUST Project – over-roofing and vertical extension
20
ANNUAL GENERATION
Electrical PV generation for: Nominal Power =17.775 kW, System losses =14.0% Tilt.=25 deg., Orient.=-90 deg.
Month Monthly generation (kWh) Daily generation
(kWh)
Jan 346 11 kWh
Feb 592 21 kWh
Mar 1126 36 kWh
Apr 1624 54 kWh
Mai 1920 62 kWh
Jun 2046 68 kWh
Jul 2211 71 kWh
Aug 1882 61 kWh
Sep 1322 44 kWh
Oct 848 27 kWh
Nov 445 15 kWh
Dec 271 9 kWh
Annual average 1219 40
Total yearly generation(kWh) 14634
14634 kWh
OUEST
03/2010
ROBUST Project – over-roofing and vertical extension
21
Location: 48°49'43" North, 2°24'6" East, Elevation: 48 mètres u.sea,
Nearest city: Paris, France (2 km)
Nominal power of the PV system : 17.775 kW (silicone cristallin)
Module tilt : 25.0° Module orientation (azimuth) : 90° Temperature losses : 7.5% (using local temperature datas)
Tilt losses : 3.2% Other losses (cables, etc): 14.0%
PV system losses: 24.7%
03/2010
ROBUST Project – over-roofing and vertical extension
22
Electrical PV generation for: Nominal Power =17.775 kW, System losses =14.0% Tilt.=25 deg., Orient.=90 deg.
Month Monthly generation (kWh) Daily generation (kWh)
Jan 348 11 kWh
Feb 592 21 kWh
Mar 1122 36 kWh
Apr 1622 54 kWh
Mai 1915 62 kWh
Jun 2039 68 kWh
Jul 2202 71 kWh
Aug 1875 60 kWh
Sep 1318 44 kWh
Oct 845 27 kWh
Nov 446 15 kWh
Dec 273 9 kWh
Annual average 1216 40
Total yearly generation(kWh) 14596
14596 kWh
Total 29230 kWh
03/2010
ROBUST Project – over-roofing and vertical extension
23
SYSTEM SPECIFICATION
Quantity Cost
Cost exc.
VAT.
MATERIAL (power
supply and cables
inc.)
Solar panels 78685.50 €
Integration features 30094.00 €
Electricity features 13305.76 €
TOTAL MATERIAL Public cost w. VAT. 122 093.52 €
Discount 0% 0.00 €
cost w. VAT.. 122 093.52 €
FITTING 39 488
TOTAL SYSTEM cost w. VAT. 161 581.02 €
VAT 19.60% 31 669.88 €
cost inc. VAT 193 250.89 €
193 250.89 €
03/2010
ROBUST Project – over-roofing and vertical extension
24
BUY-BACK PV ELECTRICITY RATES
Building type Cond. Buy-back
Residential
Residential buildings « integrated » 58 c€/kWh
Professionnels buildings
les bâtiments d'enseignement ou de santé
« integrated » 58 c€/kWh
Offices, Industrials, commercial or farming buildings « enhanced integration » 50 c€/kWh
Other new buildings
« simplified integration » 42 c€/kWh
50.0
c€/kWh
PAYBACK
Annual generation 29230 kWh
cost inc. VAT 193 250.89 €
Buy-back 50.0 c€/kWh
Payback
13.22 year(s)
03/2010
ROBUST Project – over-roofing and vertical extension
25
2.5 Scenario 5
PARIS SOUTH 4.725 kW
SOUTH Location: 48°49'43" North, 2°24'6" East, Elevation: 48 mètres u.sea,
Nearest city: Paris, France (2 km)
Nominal power of the PV system : 17.775 kW (silicone cristallin)
Module tilt : 25.0° Module orientation (azimuth) : 0.0° Temperature losses : 7.5% (using local temperature datas)
Tilt losses : 3.2% Other losses (cables, etc): 14.0%
PV system losses: 24.7%
03/2010
ROBUST Project – over-roofing and vertical extension
26
ANNUAL GENERATION
Electrical PV generation for: Nominal Power =4.725kW, System losses =14.0%
Tilt.=25 deg., Orient.=0 deg. Month Monthly generation (kWh) Daily generation (kWh)
Jan 141 5 kWh
Feb 226 8 kWh
Mar 376 12 kWh
Apr 490 16 kWh
Mai 543 18 kWh
Jun 558 19 kWh
Jul 614 20 kWh
Augt 554 18 kWh
Sep 432 14 kWh
Oct 312 10 kWh
Nov 188 6 kWh
Dec 113 4 kWh
Annual average 379 12.5
Total yearly generation(kWh) 4546
4546 kWh
03/2010
ROBUST Project – over-roofing and vertical extension
27
SYSTEM SPECIFICATION
Quantity Cost
Cost exc.
VAT.
MATERIAL (power
supply and cables
inc.)
Générateur photovoltaique 12414.24
Intégration features 3151.82 €
Electricity features 3746.46 €
TOTAL MATERIAL Public cost exc. VAT 19 314.52 €
Discount 0% 0.00 €
cost exc. VAT 19 314.52 €
FITTING 6 143
TOTAL SYSTEM cost exc. VAT 25 457.02 €
VAT 19.60% 4 989.58 €
cost inc. VAT 30 446.60 €
BUY-BACK PV ELECTRICITY RATES
Building type Cond. Buy-back
Residential
Residential buildings « integrated » 58
c€/kWh
Professionnels buildings
les bâtiments d'enseignement ou de santé
« integrated » 58 c€/kWh
Offices, Industrials, commercial or farming buildings « enhanced integration » 50 c€/kWh
Other new buildings « simplified integration » 42
c€/kWh
50.0
c€/kWh
03/2010
ROBUST Project – over-roofing and vertical extension
28
PAYBACK
Annual generation 4546 kWh
cost inc. VAT 30 446.60 €
Buy-back 50.0 c€/kWh
Payback
13.39 years(s)
03/2010
ROBUST Project – over-roofing and vertical extension
29
ABSTRACT
Nb
Mod
el kWh €
c€/k
Wh payback
CONFIGURATION 1 229 E140
Puissance nominale du système PV: 30.9 kW
(silicone cristallin) 29742 260609 58 15.11
CONFIGURATION 2 250 E140
Puissance nominale du système PV: 16.9 kW
(silicone cristallin) 27750 312606 58 19.42
Puissance nominale du système PV: 16.9 kW
(silicone cristallin)
CONFIGURATION 3 158 S 230
Puissance nominale du système PV: 35.55 kW
(silicone cristallin) 29222 203425 50 13.92
CONFIGURATION 4 135 S 230
Puissance nominale du système PV: 17.775 kW
(silicone cristallin) 29230 193251 50 13.22
Puissance nominale du système PV: 17.775 kW
(silicone cristallin)
CONFIGURATION 5 21 S 230
Puissance nominale du système PV: 4.725 kW
(silicone cristallin) 4546 30447 50 13.39
The budget available for such technology is not known but it should be noted there
are many available grants for alternative energy. Such funding cannot be relied upon at this stage, however it is worth considering
Nb Model L l S Stot Instal. Cost Cost rat.
(u)
(m) (m) (m²) (m²) (€) (€/m² inst.)
CONFIGURATION 1 229 E140 1.045 1.045 1.09 250.07 260609.24 1042.13
CONFIGURATION 2 250 E140 1.045 1.045 1.09 273.01 312606.41 1145.05
CONFIGURATION 3 158 S 230 1.68 0.99 1.66 262.79 203424.81 774.11
0.00
CONFIGURATION 4 135 S 230 1.68 0.99 1.66 224.53 193250.89 860.68
CONFIGURATION 5 21 S 230 1.68 0.99 1.66 34.93 30446.60 871.72
03/2010
ROBUST Project – over-roofing and vertical extension
30
3 Summary
The capital cost of any PV installation would naturally be high, due to the current
expense of the PV arrays. However, with the areas of roof available for potential use with building integrated PVs, a significant amount of useful electricity could be produced. PVs will also have a visual impact that will promote this king of project as a low energy and efficient building. The cost analysis should prove useful in determining whether a PV system is feasible.
However, this cost analysis give a realistic approximation of an important implantation improving the energetic balance and diminishing the carbon footprint of the overall building. There is much scope for obtaining further grants or scaling down the system to meet the available budget. More importantly, such a method of cost analysis does not fully evaluate the value of a sustainable system such as this. The system
offers educational value, image marketing value for all involved and very importantly is valuable move towards a sustainable way of building. A detailed analysis of the solar path is needed to identify any problems there might be with the roof being shaded by the surroundings or adjacent buildings however in principle there is no barrier to successfully implementing a PV system within the
current project proposal. It will be of importance to study the lifespan of the vertical extension, even if the Payback is around 15 years for this kind of solar installation, the Solar arrays are warranty for 25 years at 80% of their power and have a life expected of 50 years.
The vertical extension lifespan being itself dependent of the lifespan of the existing building, he main concern for such a system is then the lifespan of the combined building (existing + vertical extension).
03/2010
ROBUST Project – over-roofing and vertical extension
31
4 APPENDIX
Fiche technique | Equipement
SYSTAIC UNITÉ ENERGÉTIQUE ELECTRIQUE FICHE TECHNIQUE (VERSION 24.09.2009) 135 Wp
DESCRIPTION DU PRODUIT • Rendement maximal grâce à l’intégration de cellules solaires monocristallines de haut
rendement • Tolérance de puissance -1 W/+4 W • Haute fiabilité et qualité • Cellules et unités énergétiques fabriquées en Allemagne • Verre solaire ultra transparent traité anti-reflet de 4 mm d´épaisseur • Cadre profilé pour une meilleure stabilité et une longue durée de vie
• Degré de protection IP 65 CARACTÉRISTIQUES TECHNIQUES Cellules 36 cellules monocristallines Taille des cellules 156 x 156 mm
Taille 1.045 x 1.045 x 39 mm Poids 18,6 kg Face avant Verre solaire de 4 mm, trempé, renforcé Encapsulation EVA – Cellule solaire – EVA Face arrière Film composite PVF-Polyester Cadre profilé métal/plastifié (Polyuréthane)
Connexion Système „click & connect“ Diodes By-pass 3 pièces CARACTERISTIQUES ELECTRIQUES Puissance nominale PMPP 135 W Tension à puissance max. (V) 17,97
Intensité à puissance max. (A) 7,70 Tension circuit ouvert (V) 22,02
03/2010
ROBUST Project – over-roofing and vertical extension
32
Courant de court circuit (A) 8,27 Conditions d'essai standard – irradiance de 1000W/m2 à un spectre solaire AM1.5G et une température de 25° C.
CARACTERISTIQUES ELECTRIQUES SPECIALES Temp. Coeff. Puissance (%/K) -0,51 Temp. Coeff. Courant (mA/oC) +0,03 Temp. Coeff. Tension (%/K) -0,37 VALEURS MAXIMALES Températures maximales de fonctionnement -40 à +80° C Mise en oeuvre Instructions de montage Tension maxi. du système 1.000 V Limite du courant inverse 16 A GARANTIE* Garantie du matériel 5 ans Puissance garantie 12 ans 90 %, 25 ans 80 % *Les conditions et garanties détaillées sont disponibles dans nos conditions générales de ventes Certifié conforme aux normes IEC 61215:2005, IEC 61730-2
Centre de production certifié ISO 9001 INFORMATION ET DISTRIBUTION
systaic France SARL 24 Avenue de la Baltique ZA Courtaboeuf 1 91140 Villebon/Yvette
03/2010
ROBUST Project – over-roofing and vertical extension
33
SYSTAIC Unité Energétique Electrique Laminé 225W/230W (avec cadre ) Fiche technique (versi on: 17.12.2009) 140 Wp
DESCRIPTION DU PRODUIT • Rendement maximal grâce à l’intégration de cellules solaires monocristallines de haut rendement • Tolérance de puissance -1 W/+4 W • Haute fiabilité et qualité • Cellules et unités énergétiques fabriquées en Allemagne • Verre solaire ultra transparent traité anti-reflet de 4 mm d’épaisseur
• Cadre profilé pour une meilleure stabilité et une longue durée de vie
Caractéristiques techniques Cellules 10 x 6 cellules monocristallines Taille des cellules 156 x 156 mm Taille 1.680 x 990 x 50 mm
Poids 23 kg Epaisseur du laminé 50 mm (incl. boitier de connexion) Face avant Verre solaire de 4 mm, trempé, renforcé Encapsulation EVA – Cellule solaire – EVA Face arrière Film composite PVF-Polyester Boitier de connexion Tyco Solarlock
Diodes By-pass 3 pièces
CARACTERISTIQUES ELECTRIQUES Puissance nominale PMPP 225 W* 230 W** Tension à puissance max. (V) 29,33 29,39 Intensité à puissance max. (A) 7,77 7,84 Tension circuit ouvert (V) 36,26 36,29
Courant de court circuit (A) 8,40 8,44 Conditions d'essai standard – irradiance de 1000 W/m2 à un spectre solaire AM1.5G et une température de 25°C. * Id-Nr. 3001 288; ** Id-Nr.: 3001 289
03/2010
ROBUST Project – over-roofing and vertical extension
34
VALEURS MAXIMALES Temp. Coeff. Puissance (% / K) -0,51 Temp. Coeff. Courant (% / K) 0,03 Temp. Coeff. Tension (% / K) -0,37
VALEURS MAXIMALES Températures maximales de fonctionnement de l’unité -40 à +80° C Mise en oeuvre Instructions de montage Tension maxi. du système 1.000 V
Garantie * Garantie du matériel 5 ans Puissance garantie 12 ans 90 %, 25 ans 80 % *Les conditions et garanties détaillées sont disponiblesdans nos conditions générales de ventesConforme aux normes IEC 61215 ed. 2,IEC 61730-1 ed. 1, IEC 61730-2 ed.1 Centre de production certifié ISO 9001
INFORMATION ET DISTRIBUTION systaic France SARL 24 Avenue de la Baltique ZA Courtaboeuf 1 91140 Villebon/Yvette
03/2010
ROBUST Project – over-roofing and vertical extension
35
4.1 Scenario 1
30.9 kW SUD
OFFRE POUR LE MATERIEL ET L’INSTALLATION D’UNE COUVERTURE
ENERGETIQUE SYSTAIC
Quantité Prix unitaire Total HT
MATERIEL (onduleurs et étanchéité inclus, câblage jusqu'aux
onduleurs)
Unités 1045 mm x 1045 mm
Energétique E140 E140 229 U 807.00 € 184 803.00 €
Thermique 0 U 692.00 € 0.00 €
Energétique Air/Air 0 U 700.00 € 0.00 €
Unité de décoration factice 0 U 173.00 € 0.00 €
Finitions
Faitage avec grille de ventilation (n x 1045
mm) 28 U
284.00 € 7 952.00 €
Chéneau avec gouttière intégrée et grille(n x
1045 mm) 28 U
320.00 € 8 960.00 €
Rives (n x 1045 mm) standard sans grille
d'aération 0 U
180.00 € 0.00 €
Rives (n x 1045 mm) standard avec grille
d'aération 19 U
324.00 € 6 156.00 €
Bordure pour rive de toit versant nord 0 U 373.00 € 0.00 €
Fronton de faitière 0 U 319.00 € 0.00 €
Angle de Rive 4 U 462.00 € 1 848.00 €
Grille d'aération et/ou de décoration sur
mesure 0 U
378.00 € 0.00 €
Fenêtre(s) de toit 1045 mm x 1045 mm
ouverture électrique 0 U 1 600.00 € 0.00 €
ouverture mécanique 5 U 1 600.00 € 8 000.00 €
Electricité à définir
Parafoudre 1 U 230.00 € 230.00 €
Câblage AC jusqu'au compteur en limite
propriété (m) 30 ml
10.00 € 300.00 €
Coffret de sécurité côté AC 1 U 765.00 € 765.00 €
TOTAL MATERIEL prix public H.T. 219 014.00 €
remise 20% 43 802.80 €
prix net H.T. 175 211.20 €
03/2010
ROBUST Project – over-roofing and vertical extension
36
POSE
TOTAL POSE prix H.T. 42 690
TOTAL CHANTIER prix H.T. 217 900.70 €
TVA 19.60% 42 708.54 €
prix TTC 260 609.24 €
260 609.24 €
TARIF DE RACHAT DE L'ELECTRICITE
PHOTOVOLTAIQUE
Type de batiment Cond. Tarif
Le résidentiel
les bâtiments résidentiels ''intégration au bâti'' 58
c€/kWh
Les bâtiments professionnels
les bâtiments d'enseignement ou de santé
''intégration au bâti'' 58 c€/kWh
les bâtiments de bureaux, industriels, commerciaux ou encore agricoles "intégration poussée" 50
c€/kWh les autres bâtiments professionnels neufs
''intégration simplifiée au bâti''
42 c€/kWh
Les centrales solaires
Puissance inférieure ou égale à 250 kWc
31.4
c€/kWh
puissance est supérieure à 250 kWc
31.4 c€/kWh
58.0
c€/kWh
RETOUR SUR INVESTISSEMENT
Production annuelle 29742 kWh
Cout de l'installation TTC 260 609.24 €
Tarif de rachat 58.0 c€/kWh
Payback
15.11 année(s)
03/2010
ROBUST Project – over-roofing and vertical extension
37
4.2 Scenario 2
PARIS EST/OUEST
OFFRE POUR LE MATERIEL ET L’INSTALLATION D’UNE
COUVERTURE ENERGETIQUE SYSTAIC
Quantité Prix unitaire Total HT
MATERIEL (onduleurs et étanchéité inclus, câblage jusqu'aux
onduleurs)
Unités 1045 mm x 1045 mm
Energétique E140 250 U 807.00 € 201 750.00 €
Thermique 0 U 692.00 € 0.00 €
Energétique Air/Air 0 U 700.00 € 0.00 €
Unité de décoration factice 0 U 173.00 € 0.00 €
Finitions
Faitage avec grille de ventilation (n x 1045
mm) 56 U
284.00 € 15 904.00 €
Chéneau avec gouttière intégrée et grille(n
x 1045 mm) 56 U
320.00 € 17 920.00 €
Rives (n x 1045 mm) standard sans grille
d'aération 0 U
180.00 € 0.00 €
Rives (n x 1045 mm) standard avec grille
d'aération 26 U
324.00 € 8 424.00 €
Bordure pour rive de toit versant nord 0 U 373.00 € 0.00 €
Fronton de faitière 2 U 319.00 € 638.00 €
Angle de Rive 8 U 462.00 € 3 696.00 €
Grille d'aération et/ou de décoration sur
mesure 0 U
378.00 € 0.00 €
Fenêtre(s) de toit 1045 mm x 1045 mm
ouverture électrique 0 U 1 600.00 € 0.00 €
ouverture mécanique 10 U 1 600.00 € 16 000.00 €
Electricité à définir
Parafoudre 1 U 230.00 € 230.00 €
Câblage AC jusqu'au compteur en limite
propriété (m) 30 ml
10.00 € 300.00 €
Coffret de sécurité côté AC 1 U 765.00 € 765.00 €
TOTAL MATERIEL prix public H.T. 265 627.00 €
remise 20% 53 125.40 €
prix net H.T. 212 501.60 €
03/2010
ROBUST Project – over-roofing and vertical extension
38
POSE
TOTAL POSE prix H.T. 48 875
TOTAL CHANTIER prix H.T. 261 376.60 €
TVA 19.60% 51 229.81 €
prix TTC 312 606.41 €
312 606.41 €
TARIF DE RACHAT DE L'ELECTRICITE
PHOTOVOLTAIQUE
Type de batiment Cond. Tarif
Le résidentiel
les bâtiments résidentiels ''intégration au bâti'' 58
c€/kWh
Les bâtiments professionnels
les bâtiments d'enseignement ou de santé ''intégration au bâti'' 58
c€/kWh les bâtiments de bureaux, industriels, commerciaux ou encore agricoles "intégration poussée" 50
c€/kWh
les autres bâtiments professionnels neufs
''intégration simplifiée au bâti''
42 c€/kWh
Les centrales solaires
Puissance inférieure ou égale à 250 kWc
31.4 c€/kWh
puissance est supérieure à 250 kWc
31.4 c€/kWh
58.0
c€/kWh
RETOUR SUR INVESTISSEMENT
Production annuelle 27750 kWh
Cout de l'installation TTC 312 606.41 €
Tarif de rachat
58.0
c€/kWh
03/2010
ROBUST Project – over-roofing and vertical extension
39
Payback
19.42
année(s)
4.3 Scenario 3
PARIS SUD 35.55 kW
Quantité Prix unitaire Total HT
MATERIEL
Générateur photovoltaique
Modules S 230 158 U 2.50 €/Wc * 88875.00 €
Cables solaires DC 1264 ml 1.60 € 2022.40 €
Connecteurs 26 paires 9.31 € 245.16 €
Cables de mise à la terre 75 ml 1.86 € 139.50 €
Pont de contact 158 U 5.00 € 790.00 €
Support et Intégration
Bac aluminium (800*1000) 370 m² 26.60 € 9842.00 €
Cornieres de support 158 U 76.08 € 12020.64 €
Verrous de fixations 158 U 16.76 € 2648.08 €
Joint EPDM 15 rouleau(x) 19.95 € 299.25 €
Abergement latéral 80 ml 59.85 € 4788.00 €
Bande étanchéité 15 rouleau(x) 126.35 € 1895.25 €
Visserie
Alublok 2200 U 0.27 € 594.00 €
Vis CHC M8 L20 316 U 0.27 € 85.32 €
Ecrou embase M8 316 U 0.27 € 85.32 €
Electricité AC
Parafoudre 1 U 230.00 € 230.00 €
Onduleur SB 5000 TL 4 U 2584.19 € 10336.76 €
Coffret de sécurité côté AC 4 U 313.16 € 1252.64 €
Coffret de sécurité côté DC 4 U 288.61 € 1154.44 €
Câblage AC jusqu'au compteur 50 ml 6.65 € 332.50 €
* prix poseur
TOTAL MATERIEL prix public H.T. 137 636.26 €
remise 10% 13 763.63 €
prix net H.T. 123 872.64 €
POSE 46 215
TOTAL POSE prix H.T. 170 088
03/2010
ROBUST Project – over-roofing and vertical extension
40
TOTAL CHANTIER prix H.T. 170 087.64 €
TVA 19.60% 33 337.18 €
prix TTC 203 424.81 €
203 424.81 €
TARIF DE RACHAT DE L'ELECTRICITE
PHOTOVOLTAIQUE
Type de batiment Cond. Tarif
Le résidentiel
les bâtiments résidentiels ''intégration au bâti'' 58 c€/kWh
Les bâtiments professionnels
les bâtiments d'enseignement ou de santé
''intégration au bâti'' 58 c€/kWh
les bâtiments de bureaux, industriels, commerciaux ou encore agricoles "intégration poussée" 50 c€/kWh
les autres bâtiments professionnels neufs
''intégration simplifiée au bâti'' 42 c€/kWh
Les centrales solaires
Puissance inférieure ou égale à 250 kWc
31.4 c€/kWh
puissance est supérieure à 250 kWc 31.4 c€/kWh
50.0 c€/kWh
RETOUR SUR INVESTISSEMENT
Production annuelle 29222 kWh
Cout de l'installation TTC 203 424.81 €
Tarif de rachat 50.0 c€/kWh 14611
Payback
13.92 année(s)
03/2010
ROBUST Project – over-roofing and vertical extension
41
4.4 Scenario 4
PARIS EST/OUEST OFFRE POUR LE MATERIEL ET L’INSTALLATION D’UNE COUVERTURE
ENERGETIQUE SYSTAIC
Quantité Prix unitaire Total HT
MATERIEL
Générateur photovoltaique
Modules S 230 135 U 2.50 €/Wc * 75937.50 €
Cables solaires DC 1080 ml 1.60 € 1728.00 €
Connecteurs 23 paires 9.31 € 209.48 €
Cables de mise à la terre 75 ml 1.86 € 139.50 €
Pont de contact 135 U 5.00 € 675.00 €
Support et Intégration
Bac aluminium (800*1000) 370 m² 26.60 € 9842.00 €
Cornieres de support 135 U 76.08 € 10270.80 €
Verrous de fixations 135 U 16.76 € 2262.60 €
Joint EPDM 15 rouleau(x) 19.95 € 299.25 €
Abergement latéral 80 ml 59.85 € 4788.00 €
Bande étanchéité 15 rouleau(x) 126.35 € 1895.25 €
Visserie
Alublok 2200 U 0.27 € 594.00 €
Vis CHC M8 L20 270 U 0.27 € 72.90 €
Ecrou embase M8 270 U 0.27 € 72.90 €
Electricité AC
Parafoudre 1 U 230.00 € 230.00 €
Onduleur SB 5000 TL 4 U 2584.19 € 10336.76 €
Coffret de sécurité côté AC 4 U 313.16 € 1252.64 €
Coffret de sécurité côté DC 4 U 288.61 € 1154.44 €
Câblage AC jusqu'au compteur 50 ml 6.65 € 332.50 €
* prix poseur
TOTAL MATERIEL prix public H.T. 122 093.52 €
remise 0% 0.00 €
prix net H.T. 122 093.52 €
POSE 39 488
TOTAL CHANTIER prix H.T. 161 581.02 €
TVA 19.60% 31 669.88 €
03/2010
ROBUST Project – over-roofing and vertical extension
42
prix TTC 193 250.89 €
193 250.89 €
TARIF DE RACHAT DE L'ELECTRICITE
PHOTOVOLTAIQUE
Type de batiment Cond. Tarif
Le résidentiel
les bâtiments résidentiels ''intégration au bâti'' 58
c€/kWh
Les bâtiments professionnels
les bâtiments d'enseignement ou de santé
''intégration au bâti'' 58 c€/kWh
les bâtiments de bureaux, industriels, commerciaux ou encore agricoles "intégration poussée" 50
c€/kWh les autres bâtiments professionnels neufs
''intégration simplifiée au bâti''
42 c€/kWh
Les centrales solaires
Puissance inférieure ou égale à 250 kWc
31.4
c€/kWh
puissance est supérieure à 250 kWc
31.4 c€/kWh
50.0
c€/kWh
RETOUR SUR INVESTISSEMENT
Production annuelle 29230 kWh
Cout de l'installation TTC 193 250.89 €
Tarif de rachat 50.0 c€/kWh
Payback
13.22 année(s)
03/2010
ROBUST Project – over-roofing and vertical extension
43
4.5 Scenario 5
PARIS SUD 4.725 kW OFFRE POUR LE MATERIEL ET L’INSTALLATION D’UNE COUVERTURE
ENERGETIQUE SYSTAIC
Quantité Prix unitaire Total HT
MATERIEL
Générateur photovoltaique
Modules S 230 21 U 2.50 €/Wc * 11812.50 €
Cables solaires DC 200 ml 1.60 € 320.00 €
Connecteurs 4 paires 9.31 € 37.24 €
Cables de mise à la terre 75 ml 1.86 € 139.50 €
Pont de contact 21 U 5.00 € 105.00 €
Support et Intégration
Bac aluminium (800*1000) 40 m² 26.60 € 1064.00 €
Cornieres de support 21 U 76.08 € 1597.68 €
Verrous de fixations 21 U 16.76 € 351.96 €
Joint EPDM 2 rouleau(x) 19.95 € 39.90 €
Abergement latéral 0 ml 59.85 € 0.00 €
Bande étanchéité 0 rouleau(x) 126.35 € 0.00 €
Visserie
Alublok 280 U 0.27 € 75.60 €
Vis CHC M8 L20 42 U 0.27 € 11.34 €
Ecrou embase M8 42 U 0.27 € 11.34 €
Electricité AC
Parafoudre 1 U 230.00 € 230.00 €
Onduleur SB 5000 TL 1 U 2584.19 € 2584.19 €
Coffret de sécurité côté AC 1 U 313.16 € 313.16 €
Coffret de sécurité côté DC 1 U 288.61 € 288.61 €
Câblage AC jusqu'au compteur 50 ml 6.65 € 332.50 €
* prix poseur
TOTAL MATERIEL prix public H.T. 19 314.52 €
remise 0% 0.00 €
prix net H.T. 19 314.52 €
POSE 6 143
TOTAL CHANTIER prix H.T. 25 457.02 €
TVA 19.60% 4 989.58 €
prix TTC 30 446.60 €
03/2010
ROBUST Project – over-roofing and vertical extension
44
30 446.60 €
TARIF DE RACHAT DE L'ELECTRICITE
PHOTOVOLTAIQUE
Type de batiment Cond. Tarif
Le résidentiel
les bâtiments résidentiels ''intégration au bâti'' 58
c€/kWh
Les bâtiments professionnels
les bâtiments d'enseignement ou de santé
''intégration au bâti'' 58 c€/kWh
les bâtiments de bureaux, industriels, commerciaux ou encore agricoles "intégration poussée" 50
c€/kWh les autres bâtiments professionnels neufs
''intégration simplifiée au bâti''
42 c€/kWh
Les centrales solaires
Puissance inférieure ou égale à 250 kWc
31.4
c€/kWh
puissance est supérieure à 250 kWc
31.4 c€/kWh
50.0
c€/kWh
RETOUR SUR INVESTISSEMENT
Production annuelle 4546 kWh
Cout de l'installation TTC 30 446.60 €
Tarif de rachat 50.0 c€/kWh
Payback
13.39 année(s)