Li-ion Battery Technology vs. VRLA

Less Footprint

60%

Less Weight

70%

Expected Life

4X # of Cycles

10X

Initial CAPEX

Only

2X

TCO Savings over 12 years

50% AND

Page 3: Robert Strong P.E. - 7x24 Exchange Rocky Mountain Chapter7x24exchangerm.org/images/downloads/2017_Presentations/4_7x24... · 2 Rack Level MCCB with UVR Fuse X Rack Level BMS (Vol/Current/temp)

Food and Beverage

Large data centers -and

other critical sites- are

striving to improve their

competitiveness

…improvements in

backup storage

technology are a key

enabler

Page 3 Confidential Property of Schneider Electric |

Improve battery lifetime/reduce

maintenance

Improve backup storage

predictability and manageability

Reduce footprint

Reduce weight

Reduce cooling constraints

Reduce TCO

What can be improved from the

current VRLA battery solution?

Page 4: Robert Strong P.E. - 7x24 Exchange Rocky Mountain Chapter7x24exchangerm.org/images/downloads/2017_Presentations/4_7x24... · 2 Rack Level MCCB with UVR Fuse X Rack Level BMS (Vol/Current/temp)

Collaboration History between Samsung and Schneider

Page 4 Confidential Property of Schneider Electric |

Page 5: Robert Strong P.E. - 7x24 Exchange Rocky Mountain Chapter7x24exchangerm.org/images/downloads/2017_Presentations/4_7x24... · 2 Rack Level MCCB with UVR Fuse X Rack Level BMS (Vol/Current/temp)

Customer needs/pain points of lead-acid batteries (esp. large

data centers & semiconductor fabs)

• Footprint (m2)

• Life time (year)

• Operating temp. (°C)

• Reliability/predictability

• Maintenance

• Weight (kg)

• High # of cycles (>3,000)

• Fast recharge time

• Extremely high # of cycles (>50,000)

Frequent

& Important

Rare

Possible

Example: « need 2min » 600KW VRLA

(EMEA)

(5 min)

Flywheel

(20s) (2min)

Ultracaps

(20s) (2min)

Li-ion

(7 min) Customer Needs:

● CAPEX ($)

● TCO (10-year) ($) (**)

4.3 1.6 2.3 8.1 1.8 9.0

5 12 15 15 15 15

20-25 °C 0-35 °C -20-40 °C -20-40 °C -40-40 °C -40-40 °C

Medium High High High High High

Medium Low Medium Medium Low Low

10,500 1,920 3,400 11,900 3,000 15,000

500 >5,000 >30,000 >30,000 >100,000 >100,000

Low Medium High High High High

500 >5,000 >30,000 >30,000 >100,000 >100,000

1X 1.9X 8.5X 29.6X 6.7X 33.4X

1X 0.75X 3.1X 10.0X 2.2X 11.0X

Page 6: Robert Strong P.E. - 7x24 Exchange Rocky Mountain Chapter7x24exchangerm.org/images/downloads/2017_Presentations/4_7x24... · 2 Rack Level MCCB with UVR Fuse X Rack Level BMS (Vol/Current/temp)

Key Difference between Li-ion Battery Technologies

Page 6 Confidential Property of Schneider Electric |

Cell phone Industrial (ours)

Chemistry LCO LMO/NMC

Form factor Pouch cell Prismatic cells (sealed aluminum can)

Number of battery 1 Over 100 (104 or 136) per cabinet

BMS system Very simple Three layers of sophisticated BMS system

(module, rack, system level)

R&D Period 3-6 months 2-3 years

Design Priority High energy density Safety (considering car accidents)

Experience Industry average Long time leader

Page 7: Robert Strong P.E. - 7x24 Exchange Rocky Mountain Chapter7x24exchangerm.org/images/downloads/2017_Presentations/4_7x24... · 2 Rack Level MCCB with UVR Fuse X Rack Level BMS (Vol/Current/temp)

Retainer Prevent Internal Short on Crush

Anode Design Safety Functional Layer

to prevent Electrical Short

Separator Design Multi-layered Separator

Fuse Internal fuse to prevent

external short circuit / overcharge

(Non-arching at high potential)

Vent Vent at internal pressure

of 0.85±0.1Pa

OSD (Overcharge Safety Device)

Cut-off current and prevent

arc at overpotential

Guaranteed cell-level safety : Physical protection mechanism

※ Cathode Material : LMO/NCM based - Thermally Stable Materials

Safety – Cell Design

Page 8: Robert Strong P.E. - 7x24 Exchange Rocky Mountain Chapter7x24exchangerm.org/images/downloads/2017_Presentations/4_7x24... · 2 Rack Level MCCB with UVR Fuse X Rack Level BMS (Vol/Current/temp)

Same Battery as BMW i8 & i3

Page 9: Robert Strong P.E. - 7x24 Exchange Rocky Mountain Chapter7x24exchangerm.org/images/downloads/2017_Presentations/4_7x24... · 2 Rack Level MCCB with UVR Fuse X Rack Level BMS (Vol/Current/temp)

Solution Overview

Page 9 Confidential Property of Schneider Electric |

Schneider Electric UPS & LIB Battery Racks

Lithium-ion battery racks

Galaxy 7000 and Symmetra MW Galaxy VM

Galaxy VX

2016 H1 H2

Samsung SDI LIB

Page 10: Robert Strong P.E. - 7x24 Exchange Rocky Mountain Chapter7x24exchangerm.org/images/downloads/2017_Presentations/4_7x24... · 2 Rack Level MCCB with UVR Fuse X Rack Level BMS (Vol/Current/temp)

Ambient Temperature vs. Calendar Life

Page 10 Confidential Property of Schneider Electric |

Page 11: Robert Strong P.E. - 7x24 Exchange Rocky Mountain Chapter7x24exchangerm.org/images/downloads/2017_Presentations/4_7x24... · 2 Rack Level MCCB with UVR Fuse X Rack Level BMS (Vol/Current/temp)

Major UPS Projects with Samsung

Page 11 Confidential Property of Schneider Electric |

Page 12: Robert Strong P.E. - 7x24 Exchange Rocky Mountain Chapter7x24exchangerm.org/images/downloads/2017_Presentations/4_7x24... · 2 Rack Level MCCB with UVR Fuse X Rack Level BMS (Vol/Current/temp)

System

Component

Configuration 1S1P 8S1P 136S1P 104S1P

Dimension (mm) 125.7x173.9x45.6 414x216x163 650Wx600Dx2055H 650Wx600Dx2055H

Weight (kg) 1.88 kg 17 kg 550 kg 480 kg

Nominal Voltage (V) 3.8V 30.4V 517V 395V

Nominal Current (A) 460 A

Operating Range (V) 2.7V – 4.2V 24.0V – 33.6V 408V – 571V 312V – 437V

Capacity (Ah) 67 Ah

Capacity (kWh) 0.254 kWh 2.04 kWh 34.6 kWh 26.5kWh

Nominal Power (kW) 1.7 kW 13.6 kW 231 kW 177 kW

System Component Specs.

Cell Module Rack

Type G Type S

Page 13: Robert Strong P.E. - 7x24 Exchange Rocky Mountain Chapter7x24exchangerm.org/images/downloads/2017_Presentations/4_7x24... · 2 Rack Level MCCB with UVR Fuse X Rack Level BMS (Vol/Current/temp)

Schneider Electric’s LIB Solution

Page 13 Confidential Property of Schneider Electric |

A modular solution accomodating a wider range of needs

13 or 17

per rack

Cell Module

(8 cells)

Switch Gear &

Rack BMS

LIB Rack (W600xD650xH2100mm)

LIB Requirements

for UPS application

• Top safety technology

• High energy and power density:

35kWh and up to 230kW per rack

• Backup time from 5/6min to

30+min

• 15-years design life

• Competitive CapEx (~2X VRLA)

• Breakthrough TCO (-10-40%)

• Partnership with leading li-ion

manufacturer

From 1-32 racks

depending on power

and backup time

SMPS &

System BMS

1 Gateway (System BMS)

per system

(1U, fit in one of the LIB racks)

Page 14: Robert Strong P.E. - 7x24 Exchange Rocky Mountain Chapter7x24exchangerm.org/images/downloads/2017_Presentations/4_7x24... · 2 Rack Level MCCB with UVR Fuse X Rack Level BMS (Vol/Current/temp)

Actual 750kW Application in Colorado

• VRLA Batteries:

• H:=77.00in. W:=160.00in. D:=34.00in.

Weight:=20,800.00Lbs.

• Lithium Ion Batteries:

• H:=80.90in. W:=76.80in. D:=23.60in.

Weight:=3638.00Lbs. Page 14 Confidential Property of Schneider Electric |

• TPPL Batteries:

• H:=82.00in. W:=135.00in. D:=30.00in.

Weight:=16,080.00Lbs.

Page 15: Robert Strong P.E. - 7x24 Exchange Rocky Mountain Chapter7x24exchangerm.org/images/downloads/2017_Presentations/4_7x24... · 2 Rack Level MCCB with UVR Fuse X Rack Level BMS (Vol/Current/temp)

BMS (Battery Management System) Main Function : Measure, Calculation, Control, Communication

Page 15 Confidential Property of Schneider Electric |

Function System BMS Rack BMS Module BMS

Measurement Rack Voltage / Current - ○ -

Cell Voltage / Temp - - ○

Calculation SOC Estimation - ○ -

SOH Estimation - ○ -

Control Switching Control - ○ -

Cell Balancing - ○ ○

Communication

UART - ○ ○

CAN - ○ -

RS-485 or MODbus-TCP/IP ○ - -

Dry Contact ○ - -

Page 16: Robert Strong P.E. - 7x24 Exchange Rocky Mountain Chapter7x24exchangerm.org/images/downloads/2017_Presentations/4_7x24... · 2 Rack Level MCCB with UVR Fuse X Rack Level BMS (Vol/Current/temp)

BMS Software

Page 16 Confidential Property of Schneider Electric |

Page 17: Robert Strong P.E. - 7x24 Exchange Rocky Mountain Chapter7x24exchangerm.org/images/downloads/2017_Presentations/4_7x24... · 2 Rack Level MCCB with UVR Fuse X Rack Level BMS (Vol/Current/temp)

BMS Software Cont.

Page 17 Confidential Property of Schneider Electric |

Page 18: Robert Strong P.E. - 7x24 Exchange Rocky Mountain Chapter7x24exchangerm.org/images/downloads/2017_Presentations/4_7x24... · 2 Rack Level MCCB with UVR Fuse X Rack Level BMS (Vol/Current/temp)

Page 18 Confidential Property of Schneider Electric |

# Protection

Level

Description Li-Ion VRLA

1 System Level System BMS (SOC, SOH) X

2 Rack Level MCCB with UVR

Fuse X

Rack Level BMS (Vol/Current/temp) X

(134 Voltage/51 Temp Points

/Rack Current Monitoring)

X

3 Module Level Module BMS (Voltage/Temp) X

(8 Voltage/3 Temp Points

Monitoring)

X

4 Cell Level Fuse, OSD, Multilayer Separator,

Vent, Safety Functional Layer

X

Multi-Layer Protection for Li-Ion

Page 19: Robert Strong P.E. - 7x24 Exchange Rocky Mountain Chapter7x24exchangerm.org/images/downloads/2017_Presentations/4_7x24... · 2 Rack Level MCCB with UVR Fuse X Rack Level BMS (Vol/Current/temp)

MCCB

Main Fuse

Guaranteed rack-level safety : MCCB & Fuses

Module Fuse

Switch Gear Rack

Safety – Rack Design

Page 20: Robert Strong P.E. - 7x24 Exchange Rocky Mountain Chapter7x24exchangerm.org/images/downloads/2017_Presentations/4_7x24... · 2 Rack Level MCCB with UVR Fuse X Rack Level BMS (Vol/Current/temp)

1st level protection

- Current path

disconnection by BMS

2nd level protection

-Passive protection

3rd level protection

-Cell protection

Lithium-Ion Battery System MCCB

Fuse

(Main → module fuse)

Overpotential : OSD

Overcurrent : Cell-fuse

(And safety devices)

VRLA Battery System MCCB N/A N/A

Potential safety risks in UPS batteries : Over-potential / Short-circuit

Risk of Over-Potential

- Main cause : Abnormal battery charger operation

- Protection : Disconnect battery → Cell protection

Risk of Short-Circuit

- Main cause : Decrepit equipment/cable, human fault

- Protection : Disconnect battery → Fuse → Cell protection

Maximized Safety

Safety – Mechanism

Page 21: Robert Strong P.E. - 7x24 Exchange Rocky Mountain Chapter7x24exchangerm.org/images/downloads/2017_Presentations/4_7x24... · 2 Rack Level MCCB with UVR Fuse X Rack Level BMS (Vol/Current/temp)

Basics of Batteries – Charge and Discharge Mechanism

Page 21 Confidential Property of Schneider Electric |