ROAD LIGHTING PELINDO III (GRESIK)SECTION TYPICAL ROW 22 TYPE BDate: 05-02-2012
Designer: Syaiful Fikri
CalcuLuX Road 7.6.1.0
The nominal values shown in this report are the result of precision calculations, based upon precisely positioned luminaires in a fixedrelationship to each other and to the area under examination. In practice the values may vary due to tolerances on luminaires, luminairepositioning, reflection properties and electrical supply.
ROAD LIGHTING PELINDO III (GRESIK)SECTION TYPICAL ROW 22 TYPE B Date: 05-02-2012
1. Project Description
1.1 3-D Project Overview
C BRP372 LED141NW 150W 22
C
C
X
YZ
Philips Lighting B.V. - CalcuLuX Road 7.6.1.0 Page: 2/21
ROAD LIGHTING PELINDO III (GRESIK)SECTION TYPICAL ROW 22 TYPE B Date: 05-02-2012
1.2 Top Project Overview
C BRP372 LED141NW 150W 22
-22 -17 -12 -7 -2 3 8 13 18
X(m)
-6-1
49
1419
2429
3439
44Y
(m)
C
C
Scale1:250
Philips Lighting B.V. - CalcuLuX Road 7.6.1.0 Page: 3/21
ROAD LIGHTING PELINDO III (GRESIK)SECTION TYPICAL ROW 22 TYPE B Date: 05-02-2012
2. Summary
2.1 Main Road
Luminaire Type : BRP372 LED141NW 150W 220-240V DM2ELamp Type : 1 * Luxeon R x72LEDs Ra75.1Lamp Flux : 15163 lumenTilt90 (T) : 5.0 degGrid Method : CEN LuminanceProject Maintenance Factor : 0.90
T
O
H
WW C
S
Carriageway : Dual CarriagewayCentral Reserve (C) : 2.00 mRoad Width (W) : 5.00 mNumber of Lanes : 3Reflection Table : CIE C1Q0 of Table : 0.100Maintenance Factor : 0.90Installation : Single Sided LeftHeight (H) : 13.00 mSpacing (S) : 40.00 mOverhang (O) : 2.00 m
Overall quality figures for the above road scheme.
LuminanceAverage = 1.53 cd/m2Minimum = 1.20 cd/m2Maximum = 2.07 cd/m2Minimum/Maximum = 0.56Minimum/Average = 0.77Ul = 0.72
GlareTI = 5.9 %
Horizontal IlluminanceAverage = 15.9 luxMinimum = 12.2 luxMaximum = 22.9 luxMinimum/Maximum = 0.53
Philips Lighting B.V. - CalcuLuX Road 7.6.1.0 Page: 4/21
ROAD LIGHTING PELINDO III (GRESIK)SECTION TYPICAL ROW 22 TYPE B Date: 05-02-2012
2.2 Additional Calculations
(Il)luminance Calculations:CalculationMain1
TypeTypeSurface Illuminance
UnitUnitlux
AveAve 17.2
Min/AveMin/Ave0.55
Min/MaxMin/Max0.35
Philips Lighting B.V. - CalcuLuX Road 7.6.1.0 Page: 5/21
ROAD LIGHTING PELINDO III (GRESIK)SECTION TYPICAL ROW 22 TYPE B Date: 05-02-2012
3. Calculation Results
3.1 Main L (O1): Graphical Table
TI ( 0.83,-31.63, 1.50) = 5.9%Grid : Main at Z = -0.00 mCalculation : Luminance towards CEN Observer (O1) (0.83,
-60.00, 1.50) (cd/m2)Road Surface : CIE C1 with Q0 = 0.100
Average Min/Ave Min/Max Project maintenance factor 1.53 0.78 0.58 0.90
C BRP372 LED141NW 150W 22
-18 -13 -8 -3 2 7 12 17 22
X(m)
-41
611
1621
2631
3641
Y(m
)
C
C
1.4
1.3
1.3
1.2
1.2
1.2
1.2
1.2
1.3
1.3
1.3
1.4
1.4
1.4
1.5
1.4
1.4
1.3
1.3
1.3
1.3
1.3
1.3
1.4
1.4
1.4
1.5
1.5
1.6
1.5
1.4
1.3
1.3
1.3
1.3
1.3
1.4
1.4
1.4
1.5
1.6
1.6
1.7
1.6
1.5
1.4
1.4
1.3
1.3
1.3
1.4
1.5
1.5
1.6
1.7
1.7
1.7
1.7
1.5
1.5
1.4
1.4
1.4
1.4
1.4
1.5
1.6
1.6
1.7
1.8
1.8
1.7
1.6
1.5
1.5
1.4
1.4
1.4
1.5
1.6
1.6
1.7
1.8
1.8
1.9
1.8
1.6
1.6
1.5
1.4
1.4
1.4
1.5
1.6
1.7
1.7
1.9
1.9
1.9
1.8
1.7
1.6
1.6
1.4
1.4
1.4
1.5
1.7
1.7
1.8
1.9
2.0
2.0
1.9
1.7
1.6
1.6
1.5
1.4
1.5
1.5
1.7
1.8
1.9
2.0
2.1
Scale1:250
Philips Lighting B.V. - CalcuLuX Road 7.6.1.0 Page: 6/21
ROAD LIGHTING PELINDO III (GRESIK)SECTION TYPICAL ROW 22 TYPE B Date: 05-02-2012
3.2 Main L (O1): Iso Contour
TI ( 0.83,-31.63, 1.50) = 5.9%Grid : Main at Z = -0.00 mCalculation : Luminance towards CEN Observer (O1) (0.83,
-60.00, 1.50) (cd/m2)Road Surface : CIE C1 with Q0 = 0.100
Average Min/Ave Min/Max Project maintenance factor 1.53 0.78 0.58 0.90
C BRP372 LED141NW 150W 22
-18 -13 -8 -3 2 7 12 17 22
X(m)
-41
611
1621
2631
3641
Y(m
)
1.2
1.4
1.4
1.6
1.6
1.8
1.82
2
C
C
Scale1:250
Philips Lighting B.V. - CalcuLuX Road 7.6.1.0 Page: 7/21
ROAD LIGHTING PELINDO III (GRESIK)SECTION TYPICAL ROW 22 TYPE B Date: 05-02-2012
3.3 Main L (O1): Filled Iso Contour
TI ( 0.83,-31.63, 1.50) = 5.9%Grid : Main at Z = -0.00 mCalculation : Luminance towards CEN Observer (O1) (0.83,
-60.00, 1.50) (cd/m2)Road Surface : CIE C1 with Q0 = 0.100
Average Min/Ave Min/Max Project maintenance factor 1.53 0.78 0.58 0.90
C BRP372 LED141NW 150W 22
2
1.8
1.6
1.4
1.2
-12 -7 -2 3 8 13 18
X(m)
-41
611
1621
2631
3641
Y(m
)
C
C
Scale1:250
Philips Lighting B.V. - CalcuLuX Road 7.6.1.0 Page: 8/21
ROAD LIGHTING PELINDO III (GRESIK)SECTION TYPICAL ROW 22 TYPE B Date: 05-02-2012
3.4 Main L (O2): Graphical Table
TI ( 2.50,-31.63, 1.50) = 5.2%Grid : Main at Z = -0.00 mCalculation : Luminance towards CEN Observer (O2) (2.50,
-60.00, 1.50) (cd/m2)Road Surface : CIE C1 with Q0 = 0.100
Average Min/Ave Min/Max Project maintenance factor 1.55 0.78 0.57 0.90
C BRP372 LED141NW 150W 22
-18 -13 -8 -3 2 7 12 17 22
X(m)
-41
611
1621
2631
3641
Y(m
)
C
C
1.4
1.4
1.3
1.2
1.2
1.2
1.2
1.2
1.3
1.3
1.3
1.4
1.4
1.4
1.5
1.4
1.4
1.3
1.3
1.3
1.3
1.3
1.3
1.4
1.4
1.5
1.5
1.5
1.6
1.5
1.4
1.4
1.3
1.3
1.3
1.3
1.4
1.5
1.5
1.5
1.6
1.6
1.7
1.6
1.5
1.4
1.4
1.4
1.3
1.4
1.4
1.5
1.5
1.6
1.7
1.7
1.7
1.7
1.6
1.5
1.4
1.4
1.4
1.4
1.5
1.6
1.6
1.7
1.8
1.8
1.8
1.7
1.6
1.5
1.5
1.4
1.4
1.4
1.5
1.6
1.7
1.7
1.8
1.9
1.9
1.8
1.7
1.6
1.5
1.5
1.4
1.4
1.5
1.6
1.7
1.8
1.9
1.9
2.0
1.9
1.7
1.6
1.6
1.5
1.4
1.5
1.5
1.7
1.8
1.8
2.0
2.0
2.1
1.9
1.8
1.7
1.6
1.5
1.5
1.5
1.5
1.7
1.8
1.9
2.1
2.1
Scale1:250
Philips Lighting B.V. - CalcuLuX Road 7.6.1.0 Page: 9/21
ROAD LIGHTING PELINDO III (GRESIK)SECTION TYPICAL ROW 22 TYPE B Date: 05-02-2012
3.5 Main L (O2): Iso Contour
TI ( 2.50,-31.63, 1.50) = 5.2%Grid : Main at Z = -0.00 mCalculation : Luminance towards CEN Observer (O2) (2.50,
-60.00, 1.50) (cd/m2)Road Surface : CIE C1 with Q0 = 0.100
Average Min/Ave Min/Max Project maintenance factor 1.55 0.78 0.57 0.90
C BRP372 LED141NW 150W 22
-18 -13 -8 -3 2 7 12 17 22
X(m)
-41
611
1621
2631
3641
Y(m
)
1.4
1.4
1.6
1.6
1.8
1.82
2
C
C
Scale1:250
Philips Lighting B.V. - CalcuLuX Road 7.6.1.0 Page: 10/21
ROAD LIGHTING PELINDO III (GRESIK)SECTION TYPICAL ROW 22 TYPE B Date: 05-02-2012
3.6 Main L (O2): Filled Iso Contour
TI ( 2.50,-31.63, 1.50) = 5.2%Grid : Main at Z = -0.00 mCalculation : Luminance towards CEN Observer (O2) (2.50,
-60.00, 1.50) (cd/m2)Road Surface : CIE C1 with Q0 = 0.100
Average Min/Ave Min/Max Project maintenance factor 1.55 0.78 0.57 0.90
C BRP372 LED141NW 150W 22
2
1.8
1.6
1.4
-12 -7 -2 3 8 13 18
X(m)
-41
611
1621
2631
3641
Y(m
)
C
C
Scale1:250
Philips Lighting B.V. - CalcuLuX Road 7.6.1.0 Page: 11/21
ROAD LIGHTING PELINDO III (GRESIK)SECTION TYPICAL ROW 22 TYPE B Date: 05-02-2012
3.7 Main L (O3): Graphical Table
TI ( 4.17,-31.63, 1.50) = 4.3%Grid : Main at Z = -0.00 mCalculation : Luminance towards CEN Observer (O3) (4.17,
-60.00, 1.50) (cd/m2)Road Surface : CIE C1 with Q0 = 0.100
Average Min/Ave Min/Max Project maintenance factor 1.57 0.77 0.56 0.90
C BRP372 LED141NW 150W 22
-18 -13 -8 -3 2 7 12 17 22
X(m)
-41
611
1621
2631
3641
Y(m
)
C
C
1.4
1.4
1.3
1.2
1.2
1.2
1.2
1.3
1.3
1.3
1.3
1.4
1.4
1.4
1.5
1.5
1.4
1.3
1.3
1.3
1.3
1.3
1.3
1.4
1.4
1.5
1.5
1.5
1.6
1.5
1.5
1.4
1.4
1.3
1.3
1.4
1.4
1.5
1.5
1.6
1.6
1.6
1.7
1.6
1.5
1.4
1.4
1.4
1.4
1.4
1.5
1.5
1.6
1.6
1.7
1.7
1.8
1.7
1.6
1.5
1.5
1.4
1.4
1.4
1.5
1.6
1.6
1.7
1.8
1.8
1.8
1.8
1.6
1.6
1.5
1.5
1.4
1.5
1.5
1.6
1.7
1.7
1.9
1.9
1.9
1.8
1.7
1.6
1.6
1.5
1.5
1.5
1.6
1.7
1.7
1.8
2.0
2.0
2.0
1.9
1.7
1.7
1.6
1.5
1.5
1.5
1.6
1.7
1.8
1.9
2.0
2.1
2.1
2.0
1.8
1.7
1.6
1.5
1.5
1.5
1.6
1.8
1.8
1.9
2.1
2.2
Scale1:250
Philips Lighting B.V. - CalcuLuX Road 7.6.1.0 Page: 12/21
ROAD LIGHTING PELINDO III (GRESIK)SECTION TYPICAL ROW 22 TYPE B Date: 05-02-2012
3.8 Main L (O3): Iso Contour
TI ( 4.17,-31.63, 1.50) = 4.3%Grid : Main at Z = -0.00 mCalculation : Luminance towards CEN Observer (O3) (4.17,
-60.00, 1.50) (cd/m2)Road Surface : CIE C1 with Q0 = 0.100
Average Min/Ave Min/Max Project maintenance factor 1.57 0.77 0.56 0.90
C BRP372 LED141NW 150W 22
-18 -13 -8 -3 2 7 12 17 22
X(m)
-41
611
1621
2631
3641
Y(m
)
1.4
1.4
1.6
1.6
1.8
1.822
C
C
Scale1:250
Philips Lighting B.V. - CalcuLuX Road 7.6.1.0 Page: 13/21
ROAD LIGHTING PELINDO III (GRESIK)SECTION TYPICAL ROW 22 TYPE B Date: 05-02-2012
3.9 Main L (O3): Filled Iso Contour
TI ( 4.17,-31.63, 1.50) = 4.3%Grid : Main at Z = -0.00 mCalculation : Luminance towards CEN Observer (O3) (4.17,
-60.00, 1.50) (cd/m2)Road Surface : CIE C1 with Q0 = 0.100
Average Min/Ave Min/Max Project maintenance factor 1.57 0.77 0.56 0.90
C BRP372 LED141NW 150W 22
2
1.8
1.6
1.4
-12 -7 -2 3 8 13 18
X(m)
-41
611
1621
2631
3641
Y(m
)
C
C
Scale1:250
Philips Lighting B.V. - CalcuLuX Road 7.6.1.0 Page: 14/21
ROAD LIGHTING PELINDO III (GRESIK)SECTION TYPICAL ROW 22 TYPE B Date: 05-02-2012
3.10 Main Eh: Graphical Table
Grid : Main at Z = -0.00 mCalculation : Horizontal Illuminance (lux)
Average Min/Ave Min/Max Project maintenance factor 15.9 0.77 0.53 0.90
C BRP372 LED141NW 150W 22
-18 -13 -8 -3 2 7 12 17 22
X(m)
-6-1
49
1419
2429
3439
44Y
(m)
C
C
17
16
15
14
13
13
12
12
13
13
14
15
16
17
18
17
16
14
14
13
13
13
13
14
14
16
17
18
19
18
16
15
14
13
13
13
13
14
15
16
18
19
20
18
17
15
14
13
13
13
13
14
15
17
18
20
20
19
17
16
15
13
13
13
13
15
16
17
19
20
21
20
18
16
15
13
13
13
13
15
16
18
20
21
22
20
18
16
15
13
13
13
13
15
16
18
20
22
22
21
18
16
15
13
12
12
13
15
16
18
21
22
23
21
19
16
15
13
12
12
13
15
16
19
21
23
Scale1:250
Philips Lighting B.V. - CalcuLuX Road 7.6.1.0 Page: 15/21
ROAD LIGHTING PELINDO III (GRESIK)SECTION TYPICAL ROW 22 TYPE B Date: 05-02-2012
3.11 Main Eh: Iso Contour
Grid : Main at Z = -0.00 mCalculation : Horizontal Illuminance (lux)
Average Min/Ave Min/Max Project maintenance factor 15.9 0.77 0.53 0.90
C BRP372 LED141NW 150W 22
-18 -13 -8 -3 2 7 12 17 22
X(m)
-6-1
49
1419
2429
3439
44Y
(m)
14
14
16
1618
18
20
2022
22
C
C
Scale1:250
Philips Lighting B.V. - CalcuLuX Road 7.6.1.0 Page: 16/21
ROAD LIGHTING PELINDO III (GRESIK)SECTION TYPICAL ROW 22 TYPE B Date: 05-02-2012
3.12 Main Eh: Filled Iso Contour
Grid : Main at Z = -0.00 mCalculation : Horizontal Illuminance (lux)
Average Min/Ave Min/Max Project maintenance factor 15.9 0.77 0.53 0.90
C BRP372 LED141NW 150W 22
22
20
18
16
14
-12 -7 -2 3 8 13 18
X(m)
-6-1
49
1419
2429
3439
44Y
(m)
C
C
Scale1:250
Philips Lighting B.V. - CalcuLuX Road 7.6.1.0 Page: 17/21
ROAD LIGHTING PELINDO III (GRESIK)SECTION TYPICAL ROW 22 TYPE B Date: 05-02-2012
3.13 Main1: Graphical Table
Grid : Main1 at Z = -0.00 mCalculation : Surface Illuminance (lux)
Average Min/Ave Min/Max Project maintenance factor 17.2 0.55 0.35 0.90
C BRP372 LED141NW 150W 22
-22 -17 -12 -7 -2 3 8 13 18
X(m)
-6-1
49
1419
2429
3439
44Y
(m)
C
C
17
16
14
13
12
12
13
14
16
17
19
18
16
14
13
13
14
16
18
19
21
19
17
14
13
13
14
17
19
21
23
21
17
15
13
13
15
17
21
23
24
22
17
15
12
12
15
17
22
24
26
23
18
15
12
12
15
18
23
26
27
23
18
14
12
12
14
18
23
27
27
23
17
14
11
11
14
17
23
27
26
23
17
13
11
11
13
17
23
26
24
21
15
11
9
9
11
15
21
24
Scale1:250
Philips Lighting B.V. - CalcuLuX Road 7.6.1.0 Page: 18/21
ROAD LIGHTING PELINDO III (GRESIK)SECTION TYPICAL ROW 22 TYPE B Date: 05-02-2012
3.14 Main1: Iso Contour
Grid : Main1 at Z = -0.00 mCalculation : Surface Illuminance (lux)
Average Min/Ave Min/Max Project maintenance factor 17.2 0.55 0.35 0.90
C BRP372 LED141NW 150W 22
-22 -17 -12 -7 -2 3 8 13 18
X(m)
-6-1
49
1419
2429
3439
44Y
(m) 10
12.5
12.5
15
15
17.5
17.5
20
20
22.5
22.5
25
25
C
C
Scale1:250
Philips Lighting B.V. - CalcuLuX Road 7.6.1.0 Page: 19/21
ROAD LIGHTING PELINDO III (GRESIK)SECTION TYPICAL ROW 22 TYPE B Date: 05-02-2012
3.15 Main1: Filled Iso Contour
Grid : Main1 at Z = -0.00 mCalculation : Surface Illuminance (lux)
Average Min/Ave Min/Max Project maintenance factor 17.2 0.55 0.35 0.90
C BRP372 LED141NW 150W 22
25
22.5
20
17.5
15
12.5
10
-16 -11 -6 -1 4 9 14
X(m)
-6-1
49
1419
2429
3439
44Y
(m)
C
C
Scale1:250
Philips Lighting B.V. - CalcuLuX Road 7.6.1.0 Page: 20/21
ROAD LIGHTING PELINDO III (GRESIK)SECTION TYPICAL ROW 22 TYPE B Date: 05-02-2012
4. Luminaire Details
4.1 Project Luminaires
Xceed Medium FOT Sample(72LED700)BRP372 LED141NW 150W 220-240V 1xLuxeon R x72LEDs Ra75.1/3934
Light output ratios DLOR : 1.00 ULOR : 0.00 TLOR : 1.00Ballast : 700mA Global DriverLamp flux : 15163 lmLuminaire wattage : 154.0 WMeasurement code : LVC1121498
Note: Luminaire data not from database.
750
750
0o 30o30o
60o 60o
90o 90o
120o 120o150o 150o180o
C = 180o C = 0o C = 270o C = 90o C = 195o Imax C = 15o
Luminous Intensity Diagram (candela/1000 lumen)
Philips Lighting B.V. - CalcuLuX Road 7.6.1.0 Page: 21/21