Upload
jamie-frost
View
157
Download
15
Tags:
Embed Size (px)
DESCRIPTION
RNC Base Station Alarms (7000-7900) - NSN
Citation preview
Nokia Siemens Networks WCDMA RAN, Rel. RU20, Operating Documentation, Issue 04
RNC Base Station Alarms (7000-7900)
DN99580892
Issue 08DApproval Date 2010-09-30
Confidential
2 DN99580892Issue 08D
RNC Base Station Alarms (7000-7900)
Id:0900d805807cc259Confidential
The information in this document is subject to change without notice and describes only the product defined in the introduction of this documentation. This documentation is intended for the use of Nokia Siemens Networks customers only for the purposes of the agreement under which the document is submitted, and no part of it may be used, reproduced, modified or transmitted in any form or means without the prior written permission of Nokia Siemens Networks. The documentation has been prepared to be used by professional and properly trained personnel, and the customer assumes full responsibility when using it. Nokia Siemens Networks welcomes customer comments as part of the process of continuous development and improvement of the documentation.
The information or statements given in this documentation concerning the suitability, capacity, or performance of the mentioned hardware or software products are given "as is" and all liability arising in connection with such hardware or software products shall be defined conclusively and finally in a separate agreement between Nokia Siemens Networks and the customer. However, Nokia Siemens Networks has made all reasonable efforts to ensure that the instructions contained in the document are adequate and free of material errors and omissions. Nokia Siemens Networks will, if deemed necessary by Nokia Siemens Networks, explain issues which may not be covered by the document.
Nokia Siemens Networks will correct errors in this documentation as soon as possible. IN NO EVENT WILL Nokia Siemens Networks BE LIABLE FOR ERRORS IN THIS DOCUMENTA-TION OR FOR ANY DAMAGES, INCLUDING BUT NOT LIMITED TO SPECIAL, DIRECT, INDI-RECT, INCIDENTAL OR CONSEQUENTIAL OR ANY LOSSES, SUCH AS BUT NOT LIMITED TO LOSS OF PROFIT, REVENUE, BUSINESS INTERRUPTION, BUSINESS OPPORTUNITY OR DATA,THAT MAY ARISE FROM THE USE OF THIS DOCUMENT OR THE INFORMATION IN IT.
This documentation and the product it describes are considered protected by copyrights and other intellectual property rights according to the applicable laws.
The wave logo is a trademark of Nokia Siemens Networks Oy. Nokia is a registered trademark of Nokia Corporation. Siemens is a registered trademark of Siemens AG.
Other product names mentioned in this document may be trademarks of their respective owners, and they are mentioned for identification purposes only.
Copyright Nokia Siemens Networks 2010. All rights reserved
f Important Notice on Product Safety Elevated voltages are inevitably present at specific points in this electrical equipment. Some of the parts may also have elevated operating temperatures.
Non-observance of these conditions and the safety instructions can result in personal injury or in property damage.
Therefore, only trained and qualified personnel may install and maintain the system.
The system complies with the standard EN 60950 / IEC 60950. All equipment connected has to comply with the applicable safety standards.
The same text in German:
Wichtiger Hinweis zur Produktsicherheit
In elektrischen Anlagen stehen zwangslufig bestimmte Teile der Gerte unter Span-nung. Einige Teile knnen auch eine hohe Betriebstemperatur aufweisen.
Eine Nichtbeachtung dieser Situation und der Warnungshinweise kann zu Krperverlet-zungen und Sachschden fhren.
Deshalb wird vorausgesetzt, dass nur geschultes und qualifiziertes Personal die Anlagen installiert und wartet.
Das System entspricht den Anforderungen der EN 60950 / IEC 60950. Angeschlossene Gerte mssen die zutreffenden Sicherheitsbestimmungen erfllen.
DN99580892Issue 08D
3
RNC Base Station Alarms (7000-7900)
Id:0900d805807cc259Confidential
Table of contentsThis document has 195 pages.
Summary of Changes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1 Default alarm indication preventions in the system . . . . . . . . . . . . . . . . . 6
2 List of Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3 7401 EXTERNAL AL 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
4 7402 EXTERNAL AL 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
5 7403 EXTERNAL AL 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
6 7404 EXTERNAL AL 4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
7 7405 EXTERNAL AL 5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
8 7406 EXTERNAL AL 6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
9 7407 EXTERNAL AL 7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
10 7408 EXTERNAL AL 8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
11 7409 EXTERNAL AL 9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
12 7410 EXTERNAL AL 10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
13 7411 EXTERNAL AL 11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
14 7412 EXTERNAL AL 12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
15 7413 EXTERNAL AL 13 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
16 7414 EXTERNAL AL 14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
17 7415 EXTERNAL AL 15 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
18 7416 EXTERNAL AL 16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
19 7417 EXTERNAL AL 17 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
20 7418 EXTERNAL AL 18 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
21 7419 EXTERNAL AL 19 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
22 7420 EXTERNAL AL 20 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
23 7421 EXTERNAL AL 21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
24 7422 EXTERNAL AL 22 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
25 7423 EXTERNAL AL 23 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
26 7424 EXTERNAL AL 24 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
27 7425 EXTERNAL AL 25 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
28 7650 BASE STATION FAULTY. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
29 7652 BASE STATION NOTIFICATION . . . . . . . . . . . . . . . . . . . . . . . . . 61
30 7653 CELL FAULTY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
4 DN99580892Issue 08D
RNC Base Station Alarms (7000-7900)
Id:0900d805807cc259Confidential
31 7654 CELL OPERATION DEGRADED . . . . . . . . . . . . . . . . . . . . . . . . 104
32 7655 CELL NOTIFICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
33 7660 BASE STATION LICENCE EXPIRED . . . . . . . . . . . . . . . . . . . . . 132
34 7661 BASE STATION LICENCE NOTIFICATION . . . . . . . . . . . . . . . . 133
35 7665 BASE STATION TRANSMISSION ALARM . . . . . . . . . . . . . . . . . 135
36 7740 BEATING WCDMA BTS ALARM. . . . . . . . . . . . . . . . . . . . . . . . . 148
37 7750 FAILURE IN WCDMA WBTS O&M CONNECTION . . . . . . . . . . 149
38 7761 RNW O&M SCENARIO FAILURE . . . . . . . . . . . . . . . . . . . . . . . . 154
39 7762 RNW DATABASE OPERATION FAILURE . . . . . . . . . . . . . . . . . 159
40 7771 WCDMA CELL OUT OF USE . . . . . . . . . . . . . . . . . . . . . . . . . . . 162
41 7772 HSDPA CONFIGURATION FAILED . . . . . . . . . . . . . . . . . . . . . . 165
42 7775 INCONSISTENCY IN WCEL CONFIGURATION PARAMETERS . .169
43 7776 HSDPA FAILURE IN WCEL . . . . . . . . . . . . . . . . . . . . . . . . . . . . 171
44 7778 WCDMA BTS DEDICATED MEASUREMENT FAILURE . . . . . . 173
45 7779 RECOVERY ACTIONS ONGOING . . . . . . . . . . . . . . . . . . . . . . . 175
46 7780 HSUPA FAILURE IN WCEL . . . . . . . . . . . . . . . . . . . . . . . . . . . . 177
47 7781 NETWORK ELEMENT CONFIGURATION ERROR . . . . . . . . . . 179
48 7782 HSUPA CONFIGURATION FAILED . . . . . . . . . . . . . . . . . . . . . . 181
49 7783 IP BASED D-NBAP LINK FAILURE. . . . . . . . . . . . . . . . . . . . . . . 186
50 7784 RECOVERY ACTION FAILURE . . . . . . . . . . . . . . . . . . . . . . . . . 187
51 7786 WCDMA BASE STATION OUT OF USE. . . . . . . . . . . . . . . . . . . 190
52 7795 INCONSISTENCY IN HIGH PEAK RATE HSPA CONFIG . . . . . 192
53 7799 RNC RADIO NETWORK TEST ALARM . . . . . . . . . . . . . . . . . . . 195
DN99580892Issue 08D
5
RNC Base Station Alarms (7000-7900) Summary of Changes
Id:0900d805807dbb82Confidential
Summary of ChangesChanges between document issues are cumulative. Therefore, the latest document issue contains all changes made to previous issues.
Changes made between issues 08C and 08D
Modified alarms
Changes made between issues 08B and 08C
Modified alarms
Changes made between issues 08A and 08B
New alarms
Modified alarms
7650 7653 7660 7795
7651 7654 7661
7652 7655 7665
7795
7795
7650 7653 7660 7772
7651 7654 7661 7782
7652 7655 7665
6 DN99580892Issue 08D
RNC Base Station Alarms (7000-7900)
Id:0900d805807dbb82Confidential
Default alarm indication preventions in the system
1 Default alarm indication preventions in the systemAlarm indication preventions for certain alarms have been set by default in RNC. This has been done to reduce the amount of alarm indications that RNC reports to NetAct. The list of alarms below shows the affected alarms that are indication-prevented by default in RNC.
The alarms 7775 and 7795 are indication prevented in RNC because alarm 3325 informs about WCEL parameter inconsistencies in RNC level. For more information, see the instructions given for alarms 7775, 7795, and 3325. Alarm 7799 is an old test alarm for RNC testing purposes which is not set by RNC in any situation anymore.
Base Station Alarms
7775 INCONSISTENCY IN WCEL CONFIGURATION PARAMETERS 7795 INCONSISTENCY IN HIGH PEAK RATE HSPA CONFIG 7799 RNC RADIO NETWORK TEST ALARM
DN99580892Issue 08D
7
RNC Base Station Alarms (7000-7900) List of Alarms
Id:0900d805807dbb82Confidential
2 List of Alarms7401 EXTERNAL AL 1
7402 EXTERNAL AL 2
7403 EXTERNAL AL 3
7404 EXTERNAL AL 4
7405 EXTERNAL AL 5
7406 EXTERNAL AL 6
7407 EXTERNAL AL 7
7408 EXTERNAL AL 8
7409 EXTERNAL AL 9
7410 EXTERNAL AL 10
7411 EXTERNAL AL 11
7412 EXTERNAL AL 12
7413 EXTERNAL AL 13
7414 EXTERNAL AL 14
7415 EXTERNAL AL 15
7416 EXTERNAL AL 16
7417 EXTERNAL AL 17
7418 EXTERNAL AL 18
7419 EXTERNAL AL 19
7420 EXTERNAL AL 20
7421 EXTERNAL AL 21
7422 EXTERNAL AL 22
7423 EXTERNAL AL 23
7424 EXTERNAL AL 24
7425 EXTERNAL AL 25
7650 BASE STATION FAULTY
7652 BASE STATION NOTIFICATION
7653 CELL FAULTY
7654 CELL OPERATION DEGRADED
7655 CELL NOTIFICATION
7660 BASE STATION LICENCE EXPIRED
7661 BASE STATION LICENCE NOTIFICATION
7665 BASE STATION TRANSMISSION ALARM
7740 BEATING WCDMA BTS ALARM
7750 FAILURE IN WCDMA WBTS O&M CONNECTION
7761 RNW O&M SCENARIO FAILURE
7762 RNW DATABASE OPERATION FAILURE
8 DN99580892Issue 08D
RNC Base Station Alarms (7000-7900)
Id:0900d805807dbb82Confidential
List of Alarms
7771 WCDMA CELL OUT OF USE
7772 HSDPA CONFIGURATION FAILED
7775 INCONSISTENCY IN WCEL CONFIGURATION PARAMETERS
7776 HSDPA FAILURE IN WCEL
7778 WCDMA BTS DEDICATED MEASUREMENT FAILURE
7779 RECOVERY ACTIONS ONGOING
7780 HSUPA FAILURE IN WCEL
7781 NETWORK ELEMENT CONFIGURATION ERROR
7782 HSUPA CONFIGURATION FAILED
7783 IP BASED D-NBAP LINK FAILURE
7784 RECOVERY ACTION FAILURE
7786 WCDMA BASE STATION OUT OF USE
7795 INCONSISTENCY IN HIGH PEAK RATE HSPA CONFIG
7799 RNC RADIO NETWORK TEST ALARM
Alarm parametersThe following parameter settings are the default settings. The operator can modify them with an MML command.
The following listing also contains alarm event types. Please note that this information is not part of the alarm parameter listing and it is not possible to change those values using MML commands. The information here is for documentation purposes only.
NR TEXT CLS OUT SDC SDD CDL LVT--------------------------------------------------------------------------------
7401 EXTERNAL AL 1 * NONE 00:10 - 00:10 - EVENT TYPE: ENVIRONMENTAL
7402 EXTERNAL AL 2 * NONE 00:10 - 00:10 - EVENT TYPE: ENVIRONMENTAL
7403 EXTERNAL AL 3 * NONE 00:10 - 00:10 - EVENT TYPE: ENVIRONMENTAL
7404 EXTERNAL AL 4 * NONE 00:10 - 00:10 - EVENT TYPE: ENVIRONMENTAL
7405 EXTERNAL AL 5 * NONE 00:10 - 00:10 - EVENT TYPE: ENVIRONMENTAL
7406 EXTERNAL AL 6 * NONE
DN99580892Issue 08D
9
RNC Base Station Alarms (7000-7900) List of Alarms
Id:0900d805807dbb82Confidential
00:10 - 00:10 - EVENT TYPE: ENVIRONMENTAL
7407 EXTERNAL AL 7 * NONE 00:10 - 00:10 - EVENT TYPE: ENVIRONMENTAL
7408 EXTERNAL AL 8 * NONE 00:10 - 00:10 - EVENT TYPE: ENVIRONMENTAL
7409 EXTERNAL AL 9 * NONE 00:10 - 00:10 - EVENT TYPE: ENVIRONMENTAL
7410 EXTERNAL AL 10 * NONE 00:10 - 00:10 - EVENT TYPE: ENVIRONMENTAL
7411 EXTERNAL AL 11 * NONE 00:10 - 00:10 - EVENT TYPE: ENVIRONMENTAL
7412 EXTERNAL AL 12 * NONE 00:10 - 00:10 - EVENT TYPE: ENVIRONMENTAL
7413 EXTERNAL AL 13 * NONE 00:10 - 00:10 - EVENT TYPE: ENVIRONMENTAL
7414 EXTERNAL AL 14 * NONE 00:10 - 00:10 - EVENT TYPE: ENVIRONMENTAL
7415 EXTERNAL AL 15 * NONE 00:10 - 00:10 - EVENT TYPE: ENVIRONMENTAL
7416 EXTERNAL AL 16 * NONE 00:10 - 00:10 - EVENT TYPE: ENVIRONMENTAL
7417 EXTERNAL AL 17 * NONE 00:10 - 00:10 - EVENT TYPE: ENVIRONMENTAL
7418 EXTERNAL AL 18 * NONE 00:10 - 00:10 - EVENT TYPE: ENVIRONMENTAL
10 DN99580892Issue 08D
RNC Base Station Alarms (7000-7900)
Id:0900d805807dbb82Confidential
List of Alarms
7419 EXTERNAL AL 19 * NONE 00:10 - 00:10 - EVENT TYPE: ENVIRONMENTAL
7420 EXTERNAL AL 20 * NONE 00:10 - 00:10 - EVENT TYPE: ENVIRONMENTAL
7421 EXTERNAL AL 21 * NONE 00:10 - 00:10 - EVENT TYPE: ENVIRONMENTAL
7422 EXTERNAL AL 22 * NONE 00:10 - 00:10 - EVENT TYPE: ENVIRONMENTAL
7423 EXTERNAL AL 23 * NONE 00:10 - 00:10 - EVENT TYPE: ENVIRONMENTAL
7424 EXTERNAL AL 24 * NONE 00:10 - 00:10 - EVENT TYPE: ENVIRONMENTAL
7425 EXTERNAL AL 25 * NONE 00:10 - 00:10 - EVENT TYPE: ENVIRONMENTAL
7650 BASE STATION FAULTY *** 3 00:10 - 00:10 - EVENT TYPE: QUALITY OF SERVICE
7651 BASE STATION OPERATION DEGRADED ** 5 00:10 - 00:10 - EVENT TYPE: QUALITY OF SERVICE
7652 BASE STATION NOTIFICATION * NONE 00:10 - 00:10 - EVENT TYPE: QUALITY OF SERVICE
7653 CELL FAULTY *** 3 00:10 - 00:10 - EVENT TYPE: QUALITY OF SERVICE
7654 CELL OPERATION DEGRADED ** 5 00:10 - 00:10 - EVENT TYPE: QUALITY OF SERVICE
7655 CELL NOTIFICATION * NONE 00:10 - 00:10 - EVENT TYPE: QUALITY OF SERVICE
DN99580892Issue 08D
11
RNC Base Station Alarms (7000-7900) List of Alarms
Id:0900d805807dbb82Confidential
7660 BASE STATION LICENCE EXPIRED *** 3 00:10 - 00:10 - EVENT TYPE: QUALITY OF SERVICE
7661 BASE STATION LICENCE NOTIFICATION * NONE 00:10 - 00:10 - EVENT TYPE: QUALITY OF SERVICE
7665 BASE STATION TRANSMISSION ALARM * NONE 00:10 - 00:10 - EVENT TYPE: QUALITY OF SERVICE
7740 BEATING WCDMA BTS ALARM ** 5 00:00 - 00:00 - EVENT TYPE: PROCESSING ERROR
7750 FAILURE IN WCDMA WBTS O&M CONNECTION * NONE 00:10 - 00:10 - EVENT TYPE: COMMUNICATIONS
7761 RNW O&M SCENARIO FAILURE ** 5 00:40 - 00:00 - EVENT TYPE: QUALITY OF SERVICE
7762 RNW DATABASE OPERATION FAILURE ** 5 00:05 - 00:00 - EVENT TYPE: PROCESSING ERROR
7771 WCDMA CELL OUT OF USE ** 5 02:00 - 00:20 - EVENT TYPE: QUALITY OF SERVICE
7772 HSDPA CONFIGURATION FAILED ** 5 00:05 - 00:05 - EVENT TYPE: QUALITY OF SERVICE
7775 INCONSISTENCY IN WCEL CONFIGURATION PARAMETERS * NONE 00:00 - 00:00 - EVENT TYPE: PROCESSING ERROR
7776 HSDPA FAILURE IN WCEL ** 5 00:05 - 00:00 - EVENT TYPE: QUALITY OF SERVICE
7778 WCDMA BTS DEDICATED MEASUREMENT FAILURE ** 5 00:00 - 00:00 - EVENT TYPE: QUALITY OF SERVICE
7779 RECOVERY ACTIONS ONGOING * NONE 00:00 - 00:00 -
12 DN99580892Issue 08D
RNC Base Station Alarms (7000-7900)
Id:0900d805807dbb82Confidential
List of Alarms
EVENT TYPE: QUALITY OF SERVICE
7780 HSUPA FAILURE IN WCEL ** 5 00:05 - 00:00 - EVENT TYPE: QUALITY OF SERVICE
7781 NETWORK ELEMENT CONFIGURATION ERROR *** 2 00:00 - 00:00 - EVENT TYPE: PROCESSING ERROR
7782 HSUPA CONFIGURATION FAILED ** 5 00:05 - 00:05 - EVENT TYPE: QUALITY OF SERVICE
7783 IP BASED D-NBAP LINK FAILURE ** 5 00:30 - 00:30 - EVENT TYPE: COMMUNICATIONS
7784 RECOVERY ACTION FAILURE ** 5 00:00 - 00:00 - EVENT TYPE: COMMUNICATIONS
7786 WCDMA BASE STATION OUT OF USE ** 5 00:30 - 00:15 - EVENT TYPE: QUALITY OF SERVICE
7795 INCONSISTENCY IN HIGH PEAK RATE HSPA CONFIG * NONE 00:00 - 00:00 - EVENT TYPE: PROCESSING ERROR
7799 RNC RADIO NETWORK TEST ALARM * NONE 00:10 - 00:10 - EVENT TYPE: ENVIRONMENTAL
DN99580892Issue 08D
13
RNC Base Station Alarms (7000-7900) 7401 EXTERNAL AL 1
Id:0900d805807dbb82Confidential
3 7401 EXTERNAL AL 1Meaning
This is an external user-defined alarm. The alarm is defined bythe user in an HW database.
Supplementary information fields
InstructionsThe operation depends on what kind of alarm is used as externalalarm no. 1.
CancellingDo not cancel the alarm. The system cancels the alarm automaticallywhen the fault has been corrected.
14 DN99580892Issue 08D
RNC Base Station Alarms (7000-7900)
Id:0900d805807dbb82Confidential
7402 EXTERNAL AL 2
4 7402 EXTERNAL AL 2Meaning
This is an external user-defined alarm. The alarm is defined bythe user in a HW database.
Supplementary information fields
InstructionsThe operation depends on what kind of alarm is used as externalalarm no. 2.
CancellingDo not cancel the alarm. The system cancels the alarm automaticallywhen the fault has been corrected.
DN99580892Issue 08D
15
RNC Base Station Alarms (7000-7900) 7403 EXTERNAL AL 3
Id:0900d805807dbb82Confidential
5 7403 EXTERNAL AL 3Meaning
This is an external user-defined alarm. The alarm is defined bythe user in a HW database.
Supplementary information fields
InstructionsThe operation depends on what kind of alarm is used as externalalarm no. 3.
CancellingDo not cancel the alarm. The system cancels the alarm automaticallywhen the fault has been corrected.
16 DN99580892Issue 08D
RNC Base Station Alarms (7000-7900)
Id:0900d805807dbb82Confidential
7404 EXTERNAL AL 4
6 7404 EXTERNAL AL 4Meaning
This is an external user-defined alarm. The alarm is defined bythe user in a HW database.
Supplementary information fields
InstructionsThe operation depends on what kind of alarm is used as externalalarm no. 4.
CancellingDo not cancel the alarm. The system cancels the alarm automaticallywhen the fault has been corrected.
DN99580892Issue 08D
17
RNC Base Station Alarms (7000-7900) 7405 EXTERNAL AL 5
Id:0900d805807dbb82Confidential
7 7405 EXTERNAL AL 5Meaning
This is an external user-defined alarm. The alarm is defined bythe user in a HW database.
Supplementary information fields
InstructionsThe operation depends on what kind of alarm is used as externalalarm no. 5.
CancellingDo not cancel the alarm. The system cancels the alarm automaticallywhen the fault has been corrected.
18 DN99580892Issue 08D
RNC Base Station Alarms (7000-7900)
Id:0900d805807dbb82Confidential
7406 EXTERNAL AL 6
8 7406 EXTERNAL AL 6Meaning
This is an external user-defined alarm. The alarm is defined bythe user in a HW database.
Supplementary information fields
InstructionsThe operation depends on what kind of alarm is used as externalalarm no. 6.
CancellingDo not cancel the alarm. The system cancels the alarm automaticallywhen the fault has been corrected.
DN99580892Issue 08D
19
RNC Base Station Alarms (7000-7900) 7407 EXTERNAL AL 7
Id:0900d805807dbb82Confidential
9 7407 EXTERNAL AL 7Meaning
This is an external user-defined alarm. The alarm is defined bythe user in a HW database.
Supplementary information fields
InstructionsThe operation depends on what kind of alarm is used as externalalarm no. 7.
CancellingDo not cancel the alarm. The system cancels the alarm automaticallywhen the fault has been corrected.
20 DN99580892Issue 08D
RNC Base Station Alarms (7000-7900)
Id:0900d805807dbb82Confidential
7408 EXTERNAL AL 8
10 7408 EXTERNAL AL 8Meaning
This is an external user-defined alarm. The alarm is defined bythe user in a HW database.
Supplementary information fields
InstructionsThe operation depends on what kind of alarm is used as externalalarm no. 8.
CancellingDo not cancel the alarm. The system cancels the alarm automaticallywhen the fault has been corrected.
DN99580892Issue 08D
21
RNC Base Station Alarms (7000-7900) 7409 EXTERNAL AL 9
Id:0900d805807dbb82Confidential
11 7409 EXTERNAL AL 9Meaning
This is an external user-defined alarm. The alarm is defined bythe user in a HW database.
Supplementary information fields
InstructionsThe operation depends on what kind of alarm is used as externalalarm no. 9.
CancellingDo not cancel the alarm. The system cancels the alarm automaticallywhen the fault has been corrected.
22 DN99580892Issue 08D
RNC Base Station Alarms (7000-7900)
Id:0900d805807dbb82Confidential
7410 EXTERNAL AL 10
12 7410 EXTERNAL AL 10Meaning
This is an external user-defined alarm. The alarm is defined bythe user in a HW database.
Supplementary information fields
InstructionsThe operation depends on what kind of alarm is used as externalalarm no. 10.
CancellingDo not cancel the alarm. The system cancels the alarm automaticallywhen the fault has been corrected.
DN99580892Issue 08D
23
RNC Base Station Alarms (7000-7900) 7411 EXTERNAL AL 11
Id:0900d805807dbb82Confidential
13 7411 EXTERNAL AL 11Meaning
This is an external user-defined alarm. The alarm is defined bythe user in a HW database.
Supplementary information fields
InstructionsThe operation depends on what kind of alarm is used as externalalarm no. 11.
CancellingDo not cancel the alarm. The system cancels the alarm automaticallywhen the fault has been corrected.
24 DN99580892Issue 08D
RNC Base Station Alarms (7000-7900)
Id:0900d805807dbb82Confidential
7412 EXTERNAL AL 12
14 7412 EXTERNAL AL 12Meaning
This is an external user-defined alarm. The alarm is defined bythe user in a HW database.
Supplementary information fields
InstructionsThe operation depends on what kind of alarm is used as externalalarm no. 12.
CancellingDo not cancel the alarm. The system cancels the alarm automaticallywhen the fault has been corrected.
DN99580892Issue 08D
25
RNC Base Station Alarms (7000-7900) 7413 EXTERNAL AL 13
Id:0900d805807dbb82Confidential
15 7413 EXTERNAL AL 13Meaning
This is an external user-defined alarm. The alarm is defined bythe user in a HW database.
Supplementary information fields
InstructionsThe operation depends on what kind of alarm is used as externalalarm no. 13.
CancellingDo not cancel the alarm. The system cancels the alarm automaticallywhen the fault has been corrected.
26 DN99580892Issue 08D
RNC Base Station Alarms (7000-7900)
Id:0900d805807dbb82Confidential
7414 EXTERNAL AL 14
16 7414 EXTERNAL AL 14Meaning
This is an external user-defined alarm. The alarm is defined bythe user in a HW database.
Supplementary information fields
InstructionsThe operation depends on what kind of alarm is used as externalalarm no. 14.
CancellingDo not cancel the alarm. The system cancels the alarm automaticallywhen the fault has been corrected.
DN99580892Issue 08D
27
RNC Base Station Alarms (7000-7900) 7415 EXTERNAL AL 15
Id:0900d805807dbb82Confidential
17 7415 EXTERNAL AL 15Meaning
This is an external user-defined alarm. The alarm is defined bythe user in a HW database.
Supplementary information fields
InstructionsThe operation depends on what kind of alarm is used as externalalarm no. 15.
CancellingDo not cancel the alarm. The system cancels the alarm automaticallywhen the fault has been corrected.
28 DN99580892Issue 08D
RNC Base Station Alarms (7000-7900)
Id:0900d805807dbb82Confidential
7416 EXTERNAL AL 16
18 7416 EXTERNAL AL 16Meaning
This is an external user-defined alarm. The alarm is defined bythe user in a HW database.
Supplementary information fields
InstructionsThe operation depends on what kind of alarm is used as externalalarm no. 16.
CancellingDo not cancel the alarm. The system cancels the alarm automaticallywhen the fault has been corrected.
DN99580892Issue 08D
29
RNC Base Station Alarms (7000-7900) 7417 EXTERNAL AL 17
Id:0900d805807dbb82Confidential
19 7417 EXTERNAL AL 17Meaning
This is an external user-defined alarm. The alarm is defined bythe user in a HW database.
Supplementary information fields
InstructionsThe operation depends on what kind of alarm is used as externalalarm no. 17.
CancellingDo not cancel the alarm. The system cancels the alarm automaticallywhen the fault has been corrected.
30 DN99580892Issue 08D
RNC Base Station Alarms (7000-7900)
Id:0900d805807dbb82Confidential
7418 EXTERNAL AL 18
20 7418 EXTERNAL AL 18Meaning
This is an external user-defined alarm. The alarm is defined bythe user in a HW database.
Supplementary information fields
InstructionsThe operation depends on what kind of alarm is used as externalalarm no. 18.
CancellingDo not cancel the alarm. The system cancels the alarm automaticallywhen the fault has been corrected.
DN99580892Issue 08D
31
RNC Base Station Alarms (7000-7900) 7419 EXTERNAL AL 19
Id:0900d805807dbb82Confidential
21 7419 EXTERNAL AL 19Meaning
This is an external user-defined alarm. The alarm is defined bythe user in a HW database.
Supplementary information fields
InstructionsThe operation depends on what kind of alarm is used as externalalarm no. 19.
CancellingDo not cancel the alarm. The system cancels the alarm automaticallywhen the fault has been corrected.
32 DN99580892Issue 08D
RNC Base Station Alarms (7000-7900)
Id:0900d805807dbb82Confidential
7420 EXTERNAL AL 20
22 7420 EXTERNAL AL 20Meaning
This is an external user-defined alarm. The alarm is defined bythe user in a HW database.
Supplementary information fields
InstructionsThe operation depends on what kind of alarm is used as externalalarm no. 20.
CancellingDo not cancel the alarm. The system cancels the alarm automaticallywhen the fault has been corrected.
DN99580892Issue 08D
33
RNC Base Station Alarms (7000-7900) 7421 EXTERNAL AL 21
Id:0900d805807dbb82Confidential
23 7421 EXTERNAL AL 21Meaning
This is an external user-defined alarm. The alarm is defined bythe user in a HW database.
Supplementary information fields
InstructionsThe operation depends on what kind of alarm is used as externalalarm no. 21.
CancellingDo not cancel the alarm. The system cancels the alarm automaticallywhen the fault has been corrected.
34 DN99580892Issue 08D
RNC Base Station Alarms (7000-7900)
Id:0900d805807dbb82Confidential
7422 EXTERNAL AL 22
24 7422 EXTERNAL AL 22Meaning
This is an external user-defined alarm. The alarm is defined bythe user in a HW database.
Supplementary information fields
InstructionsThe operation depends on what kind of alarm is used as externalalarm no. 22.
CancellingDo not cancel the alarm. The system cancels the alarm automaticallywhen the fault has been corrected.
DN99580892Issue 08D
35
RNC Base Station Alarms (7000-7900) 7423 EXTERNAL AL 23
Id:0900d805807dbb82Confidential
25 7423 EXTERNAL AL 23Meaning
This is an external user-defined alarm. The alarm is defined bythe user in a HW database.
Supplementary information fields
InstructionsThe operation depends on what kind of alarm is used as externalalarm no. 23.
CancellingDo not cancel the alarm. The system cancels the alarm automaticallywhen the fault has been corrected.
36 DN99580892Issue 08D
RNC Base Station Alarms (7000-7900)
Id:0900d805807dbb82Confidential
7424 EXTERNAL AL 24
26 7424 EXTERNAL AL 24Meaning
This is an external user-defined alarm. The alarm is defined bythe user in a HW database.
Supplementary information fields
InstructionsThe operation depends on what kind of alarm is used as externalalarm no. 24.
CancellingDo not cancel the alarm. The system cancels the alarm automaticallywhen the fault has been corrected.
DN99580892Issue 08D
37
RNC Base Station Alarms (7000-7900) 7425 EXTERNAL AL 25
Id:0900d805807dbb82Confidential
27 7425 EXTERNAL AL 25Meaning
This is an external user-defined alarm. The alarm is defined bythe user in a HW database.
Supplementary information fields
InstructionsThe operation depends on what kind of alarm is used as externalalarm no. 25.
CancellingDo not cancel the alarm. The system cancels the alarm automaticallywhen the fault has been corrected.
38 DN99580892Issue 08D
RNC Base Station Alarms (7000-7900)
Id:0900d805807dbb82Confidential
7650 BASE STATION FAULTY
28 7650 BASE STATION FAULTYMeaning
A critical fault (or faults) has occurred in the base station.
Check the reason for the fault from the supplementary text field ofthe alarm.
The effect of the fault on the functioning of the network elementdepends on the fault description. For more information, see basestation fault descriptions in WCDMA RAN and I-HSPA System Libraries.
Supplementary information fields1 rack (cabinet) number
2 shelf number
3 slot
4 type of unit
5 unit number
6 subunit number
For more information, see instructions on Alarm Structure.
InstructionsVerify the configuration of a BTS by checking the commissioning, cablingand correct installation of the units/modules at the BTS. Make sure theenvironment does not cause the fault.
Before a unit/module is replaced at the BTS, the site should be reset torecover from any temporary faults which might have caused themalfunctioning of the unit/module. When an active alarm is a 'Start'alarm, a site reset is required to cancel the alarm. If the site reset ormodule block/unblock does not help, replace the faulty unit/module (seethe source of the alarm and instructions fields of the correspondingalarms).
Below is the list of BTS fault(s) which might have caused this alarm inBTS WN6.0_EP1 release. In case of earlier SW release and in case you needmore detailed fault descriptions refer to WCDMA RAN and I-HSPA SystemLibraries. The BTS fault descriptions are also included in BTS SW releasedocumentation. If that does not help, contact your local Nokia SiemensNetworks representative.
DN99580892Issue 08D
39
RNC Base Station Alarms (7000-7900) 7650 BASE STATION FAULTY
Id:0900d805807dbb82Confidential
FAULT NAME : ATM faultyMEANING : A WAM internal failure.INSTRUCTIONS : 1. If ping to the BTS is working, restart the BTS remotely.
2. Ping the BTS. If it is not working but ping to the AXC is working, then restart the AXC remotely so that the BTS is also restarted automatically.
3. Ping the AXC. If it is not working, visit the site and restart the BTS. If this does not help, replace the alarming WAM unit.
FAULT NAME : ATM processor faultyMEANING : UltraSite, MetroSite, MetroSite 50, Triple-mode:
There is a fault in the WAM processor SFN interrupt or the SFN is not being updated in the WSPC MCU.
There is a MCU failure in the WAM or the ATM loop test at start-up has failed.
FlexiBTS:
There is such a fault in the FSM that the SFN is not being updated in the FSP MCU.INSTRUCTIONS : UltraSite, MetroSite, MetroSite 50, Triple-mode:
1. If ping to the BTS is working, restart the BTS remotely.
2. Ping the BTS. If it is not working but ping to the AXC is working, restart the AXC remotely so that the BTS is also automatically restarted.
3. Ping the AXC. If it is not working, visit the site and restart the BTS. If this does not help, replace the alarming WAM unit.
FlexiBTS:
1. Reset the BTS.
2. If the BTS reset does not help, change the alarming module.
FAULT NAME : Antenna link is downMEANING : Antenna (RP3) link is down: transmitter or receiver drops from synchronization.INSTRUCTIONS : FlexiBTS:
1. If the alarming module is the Extension System Module (FSM2), restart it. If the alarming module is the System Module (FSM1), restart BTS.
40 DN99580892Issue 08D
RNC Base Station Alarms (7000-7900)
Id:0900d805807dbb82Confidential
7650 BASE STATION FAULTY
2. If that does not help, replace the alarming FSM.
UltraSite/EUBB:
1. If the alarming module is WSPF, restart it. If the alarming module is WSPF, restart BTS.
2. If that does not help, replace the alarming WSPF.
FAULT NAME : BB bus message collision errorMEANING : Routed RF baseband bus messages have collided and the data in the output baseband internal link is lost because the baseband bus is incorrectly configured.INSTRUCTIONS : 1. Check antenna mapping to the local cells in the commissioning file.
2. Check the cables between the System Module and RF Module.
3. Replace the alarming module.
FAULT NAME : BB bus reception error (summing device)MEANING : The master frame in the received baseband bus frame is not in the correct place related to the internally generated master frame pulse. Either the frame has been set into the wrong place (PI delay) or the data itself is in the wrong place.INSTRUCTIONS : FlexiBTS:
1. Check the cables between the Master System Module and RF Module/Extension System Module.
2. Replace the unit that causes the fault (Master System Module, Extension System Module, RF Module, FBIA).
UltraSite/EUBB:
1. Replace the unit that causes the fault (WSPF, WSMF).
FAULT NAME : BB bus transmission errorMEANING : A decoding error has been detected in the baseband internal link. The data packet is lost or the content is corrupted.
This situation is also triggered when the links do not synchronize with each other.INSTRUCTIONS : FlexiBTS:
1. Check the cables between the Master System Module and RF Module/Extension System Module.
2. Replace the alarming unit (System Module).
DN99580892Issue 08D
41
RNC Base Station Alarms (7000-7900) 7650 BASE STATION FAULTY
Id:0900d805807dbb82Confidential
UltraSite/EUBB:
1. Replace the alarming unit (WSMF).
FAULT NAME : BOFU Post failedMEANING : The unit or module has been tested during BTS power-on self test (POST) and a failure has been detected.INSTRUCTIONS : 1. Block/unblock the alarming unit/module.
2. Remove/reinsert the alarming unit/module.
3. Replace the alarming unit/module.
FAULT NAME : BTS BlockedMEANING : The BTS is blocked with BTS Site Manager. The meaning of the fault is to avoid alarms that may be raised during a BTS maintenance task.INSTRUCTIONS : To cancel the alarm, unblock the BTS. Unblocking the BTS causes a site reset.
FAULT NAME : BTS config error (WSMA and WSMB can not coexist)MEANING : WSMA and WSMB units are detected in the same cabinet. They cannot coexist in the BTS.INSTRUCTIONS : Replace the conflicting unit WSMA with the WSMB, or vice versa.
FAULT NAME : BTS file errorMEANING : UltraSite, MetroSite, MetroSite 50, Triple-mode, UltraSite/EUBB: The BTS unit properties data is invalid or missing.
FlexiBTS: The BTS module properties data or optical interface FPGA file is invalid or missing. The FSP MCU SW file is invalid or missing.INSTRUCTIONS : UltraSite, MetroSite, MetroSite 50, Triple-mode, UltraSite/EUBB:
1. Download two different SW packages so that the faulty file is removed from the BTS.
2. Download the SW again.
3. If the fault still exists after 10 minutes, replace the alarming unit.
FlexiBTS:
1. Download two different SW packages so that the faulty file is removed from the BTS.
42 DN99580892Issue 08D
RNC Base Station Alarms (7000-7900)
Id:0900d805807dbb82Confidential
7650 BASE STATION FAULTY
2. Download the SW again.
3. Replace the System Module.
FAULT NAME : BTS file errorMEANING : Telecom configuration file(s) are invalid, missing or not accessible.INSTRUCTIONS : UltraSite, MetroSite, MetroSite 50, Triple-mode, UltraSite/EUBB:
1. Download two different SW packages so that the faulty file is removed from the BTS.
2. Download the SW again.
3. If the fault still exists after 10 minutes, replace the alarming unit.
FlexiBTS:
1. Download two different SW packages so that the faulty file is removed from the BTS.
2. Download the SW again.
3. Replace the System Module or FBIA.
FAULT NAME : BTS internal SW management problemMEANING : A software update to a unit/module or subassembly has failed, or a corrupted SW file has been detected in the FLASH.INSTRUCTIONS : Note: Perform the steps below in the listed order until the BTS fault indication disappears.
FlexiBTS:
1. Check the other active BTS faults. If the ROM disk is corrupted, change the alarming module.
2. Reset the RF Module and/or System Module, depending on the alarm source: a. Reset the RF Module by blocking/unblocking it. b. Reset the System Module.
3. Update and activate the SW to the BTS.
4. Check the SW files.
5. Replace the alarming module/unit.
UltraSite/EUBB:
DN99580892Issue 08D
43
RNC Base Station Alarms (7000-7900) 7650 BASE STATION FAULTY
Id:0900d805807dbb82Confidential
1. Check the other active BTS faults. If the ROM disk is corrupted, change the alarming unit.
2. Reset the alarming unit.
3. Update and activate the SW to the BTS.
4. Check the SW files.
5. Replace the alarming unit.
FAULT NAME : Baseband Bus failureMEANING : The BTS has detected an abnormal operation or a failure in the BTS internal baseband bus. The failure cannot be pointed to a specific unit/module but there are several possible fault sources.INSTRUCTIONS : Note: Perform the steps below in the listed order until the alarm disappears.
FlexiBTS:
1. Check the other active BTS alarms and act accordingly.
2. Check the cables between the System Module and RF Module/Extension System Module.
3. Reset the RF Module and/or System Module, depending on the alarm source: a. Reset the RF Module by blocking/unblocking it. b. Reset the Extension System Module by blocking/unblocking it. c. Reset the master System Module.
4. Replace the alarming RF Module/Extension System Module.
5. If the master System Module is the source or replacing the RF Module/Extension System Module does not clear the fault situation, replace the alarming master System Module.
UltraSite/EUBB:
1. Check the other active BTS alarms and act accordingly.
2. Reset the alarming unit.
3. Check the cables in backplane.
4. Replace the alarming unit.
FAULT NAME : Baseband bus configuration of was rejectedMEANING : The baseband bus related configuration of was rejected by
44 DN99580892Issue 08D
RNC Base Station Alarms (7000-7900)
Id:0900d805807dbb82Confidential
7650 BASE STATION FAULTY
the HW, SW, DSP or LTX.INSTRUCTIONS : Replace the alarming module.
FAULT NAME : Baseband reference clock missing (WCI)MEANING : The WCI does not deliver the Baseband Reference Clock (BRCLK) for the relevant units, because either the transceiver circuit in the WSC or the bus is faulty, or the WSC does not distribute the clock source.INSTRUCTIONS : You have two alternative procedures:
1. If there is only one clock unit in the cabinet, replace the WSC.
2. If Step 1 does not help, replace the WCI.
OR
1. If there are two clock units in the cabinet, replace the WCI.
2. If Step 1 does not help, replace both WSC units.
FAULT NAME : Baseband reference clock missing (WSC)MEANING : The WSC is not able to deliver the clock signals required by the other units.INSTRUCTIONS : Replace the WSC.
FAULT NAME : Commissioning error: MEANING : Some of the commissioning parameters are either missing or faulty, or there is a mismatch between them.INSTRUCTIONS : Note: Perform the steps below in the listed order until the alarm disappears.
1. Check the commissioning parameters with the BTS Site Manager Commissioning Wizard.
2. Load the correct commissioning file to the BTS.
FAULT NAME : Communication failureMEANING : Communication with the application failed. It has not replied to the message that has been sent/resent to it.
FSP: Faraday has not sent a specific mandatory indication message in the start-up during the time limit the message is expected to arrive.INSTRUCTIONS : 1. Check that the unit/module is properly connected. If the unit/module LED does not light up, the unit/module is faulty. Check the alarming unit/module.
2. Check the fault history.
DN99580892Issue 08D
45
RNC Base Station Alarms (7000-7900) 7650 BASE STATION FAULTY
Id:0900d805807dbb82Confidential
FAULT NAME : Communication failureMEANING : An internal communication fault in the decoding process in the module, for example, a decode co-processor error.INSTRUCTIONS : 1. Reset the alarming unit/module.
2. Replace the alarming unit/module.
FAULT NAME : Communication failure inside WSPMEANING : An internal communication failure between the DSP processors.INSTRUCTIONS : UltraSite, MetroSite, MetroSite 50, Triple-mode:
1. Block the alarming WSP.
2. The fault might be in the WTR or WPA (see Troubleshooting instructions).
Otherwise, check for other alarms. If the " autonomous reset as recovery action" alarm has occurred for the alarming WSP, replace the alarming WSP unit.
FlexiBTS:
1. If only one FSP in BTS generates this alarm, the FSP is faulty.
2. If all FSPs generate this alarm, the FSM is faulty.
3. Block/unblock the FSM.
4. If that does not help, replace the faulty module (System Module).
FAULT NAME : Configuration error: MEANING : There is a compatibility problem in the BTS HW/SW versions or the HW/HW configuration. Another possibility is that there is a mismatch between the BTS configuration and the RNC/I-HSPA adapter parameters.INSTRUCTIONS : Note: Perform the steps below in the listed order until the BTS fault indication disappears.
1. Check the installed HW/SW version compatibility and the HW compatibility with the current BTS configuration.
2. Check that the BTS cell parameters from the RNC/I-HSPA adapter match the BTS HW configuration (for example frequency, power).
3. Check the RNC/I-HSPA adapter BTS faults for the alarming local cell (LCR).
4. Recommission the BTS to ensure that all parameters are
46 DN99580892Issue 08D
RNC Base Station Alarms (7000-7900)
Id:0900d805807dbb82Confidential
7650 BASE STATION FAULTY
correctly configured.
FAULT NAME : Configuration file is not supportedMEANING : BTS software does not support the commissioning file downloaded to the BTS.INSTRUCTIONS : 1. Check and correct the contents of the commissioning file.
2. Download the corrected commissioning file to the BTS and reset it.
FAULT NAME : Connection to transmission brokenMEANING : UltraSite, MetroSite, MetroSite 50, Triple-mode:
The AXC is missing, data or states are corrupted in the ATM, or there are possible hardware or transmission related failures.
FlexiBTS:
Data or states are corrupted in the ATM, or there are possible hardware or transmission related failures.INSTRUCTIONS : UltraSite, MetroSite, MetroSite 50, Triple-mode:
1. Check the transmission connections.
2. If the transmission type is the AXC, reset the WAM.
3. If that does not help, replace the alarming unit.
FlexiBTS:
1. Check the transmission connections.
2. Reset the site.
3. If that does not help, replace the alarming System Module.
FAULT NAME : DSC-bus failureMEANING : There is a failure in the bus between the WAM and WSP (DSC-bus), which means that messages do not get through via that DSC-bus.INSTRUCTIONS : 1. Block/unblock the alarming unit.
2. Replace the alarming unit.
FAULT NAME : DSC-bus failureMEANING : There are communication problems between the WAM and WSP. This fault might occur if the WSP is hot removed or the WSP crashes.INSTRUCTIONS : If the failure still exists after the site reset, replace the WAM unit.
DN99580892Issue 08D
47
RNC Base Station Alarms (7000-7900) 7650 BASE STATION FAULTY
Id:0900d805807dbb82Confidential
FAULT NAME : DSP accelerator initialization failureMEANING : There is a signal processing (DSP) related malfunction in the BTS. This might affect the signal processor receiver functionality processed by the alarming unit/module.INSTRUCTIONS : FlexiBTS:
1. If the alarming module is the Extension System Module (FSM2), restart it. If the alarming module is the System Module (FSM1), restart the BTS.
2. If that does not help, replace the alarming FSM or alarming unit.
UltraSite/EUBB:
1. If the alarming unit is WSPF, restart it. If all WSPFs generate this alarm, restart the BTS.
2. If that does not help, replace the alarming unit.
FAULT NAME : DSP failure in radiolink creationMEANING : Radio link creation has failed repeatedly because of the DSP rejection.INSTRUCTIONS : UltraSite, MetroSite, MetroSite 50, Triple-mode, UltraSite/EUBB:
1. Block/unblock the alarming unit.
2. Replace the alarming unit.
FlexiBTS:
If the faulty FSP is in the extension module, block/unblock the extension module, otherwise block/unblock the BTS.
FAULT NAME : DSP mode change failedMEANING : DSP configuration to correct mode was not successful.INSTRUCTIONS : Replace the alarming module/unit.
FAULT NAME : FSP resetMEANING : FSP is undergoing a cold reset.INSTRUCTIONS : Note! Perform the steps below in the listed order until the fault disappears:
1. Reset the BTS.
2. Replace the faulty module/unit.
48 DN99580892Issue 08D
RNC Base Station Alarms (7000-7900)
Id:0900d805807dbb82Confidential
7650 BASE STATION FAULTY
FAULT NAME : FSP/WSP Frame synchronisation failedMEANING : The frame synchronization burst, SFN or SFCLK signal from the FCM/WSPF is missing.INSTRUCTIONS : 1. Reset the site.
2. If that does not help, replace the System Module.
FAULT NAME : Failure in optical RP3 interfaceMEANING : The BTS has detected an abnormal operation or a failure in an optical RP3 interface between two modules. The failure cannot be pointed to a specific module but there are several possible fault sources.INSTRUCTIONS : Note: Perform the steps below in the listed order until the alarm disappears.
1. Check the other active BTS alarms and act accordingly.
2. Check the cables between the System Module and RF Module/Extension System Module. Note that dirty optical connectors may cause the signal level to drop too low.
3. Depending on the alarm source, reset the RF Module, Extension System Module and/or System Module by blocking/unblocking it.
4. Replace the alarming module's Small Form Factor Pluggable (SFP). Check also the SFP in the other end and replace it, if needed.
5. Replace the alarming RF Module/Extension System Module.
6. If the System Module is the only alarming source or replacing the RF Module/Extension System Module does not clear the fault situation, replace the alarming System Module.
FAULT NAME : Failure in replaceable baseband unitMEANING : The BTS has detected an abnormal operation or a failure in the BTS replaceable baseband unit.INSTRUCTIONS : Note: Perform the steps below in the listed order until the BTS fault indication disappears.
1. Check the other active BTS faults and act accordingly.
2. Check the plug-in type baseband unit is installed correctly.
3. Reset the alarming baseband unit.
4. Replace the alarming baseband unit.
DN99580892Issue 08D
49
RNC Base Station Alarms (7000-7900) 7650 BASE STATION FAULTY
Id:0900d805807dbb82Confidential
FAULT NAME : Fatal OSE ErrorMEANING : The operating system (OSE) goes into the error handler with a fatal status. The cause can be, for example, out of memory situation.
If only one FSP in BTS generates this fault, there is malfunction in one of the FSP submodules. If all FSPs generate this fault, there is malfunction in the FSM.INSTRUCTIONS : FlexiBTS:
Note! Perform the steps below in the listed order until the fault disappears.
1. Reset the System Module.
2. Replace the System Module.
UltraSite/EUBB:
1. If only one WSPF in BTS generates this fault, the WSPF is faulty.
2. If all WSPFs generate this fault, BTS is faulty.
3. Block/unblock BTS.
4. If that does not help, replace the faulty module.
FAULT NAME : Fault between WAM and WSP SFN (WSP)MEANING : UltraSite, MetroSite, MetroSite 50, Triple-mode: Synchronization between the WAM and WSP is lost.
FlexiBTS: Synchronization between the FCM and FSP/FBIA is lost.
UltraSite/EUBB: Synchronization between the WAMF and WSPF is lost.INSTRUCTIONS : UltraSite, MetroSite, MetroSite 50, Triple-mode:
1. If only one WSP in the cabinet generates this alarm, the WSP is faulty.
2. If all WSPs in a subrack generate this alarm, the WAM is faulty.
3. If all WSPs generate this alarm, the WSC/WMC is faulty.
Otherwise, check for other alarms. If the " autonomous reset as a recovery action" alarm has occurred for the faulty WSP, replace the faulty WSP unit.
50 DN99580892Issue 08D
RNC Base Station Alarms (7000-7900)
Id:0900d805807dbb82Confidential
7650 BASE STATION FAULTY
FlexiBTS:
1. If only one FSP/FBIA in the BTS generates this alarm, the FSP/FBIA is faulty.
2. If all FSPs generate this alarm, the FSM is faulty.
3. Block/unblock the FSM.
4. If that does not help, replace the faulty module (System Module) or faulty FBIA.
UltraSite/EUBB: 1. If only one WSPF in the BTS generates this alarm, the WSPF is faulty.
2. If all WSPFs generate this alarm, the BTS is faulty.
3. Block/unblock the BTS.
4. If that does not help, replace the faulty module.
FAULT NAME : Fault in ATM interfaceMEANING : The WAM ATM interface is not responding correctly.INSTRUCTIONS : 1. Block/unblock the fault reporting unit. This resets the BTS.
2. If that does not help, replace the fault reporting unit.
FAULT NAME : Fault in ATM interfaceMEANING : WAM ATM interface, AXC or CIF bus failure. The AXC may have been reset.
WAM processor failure.INSTRUCTIONS : 1. Block/unblock the fault reporting unit. This resets the BTS.
2. Swap the WAM units between subracks and check if the fault follows the unit. Replace the fault reporting WAM unit.
3. Check the AXU.
4. Check the backplane connection between the WAM and AXU.
FAULT NAME : Fault in O&M and DSP SW interfaceMEANING : UltraSite, MetroSite, MetroSite 50, Triple-mode: Communication failure between the WAM and DSP.
FlexiBTS: Communication failure between the FCM and FSP/FBIA.
UltraSite/EUBB: Communication failure between the WSMF and
DN99580892Issue 08D
51
RNC Base Station Alarms (7000-7900) 7650 BASE STATION FAULTY
Id:0900d805807dbb82Confidential
WSPF.INSTRUCTIONS : UltraSite, MetroSite, MetroSite 50, Triple-mode, UltraSite/EUBB:
1. Block/unblock the alarming unit.
2. Replace the alarming unit.
FlexiBTS:
1. Block/unblock the alarming module.
2. Replace the System Module.
FAULT NAME : Frame clock deviation faultMEANING : Synchronization to the clock control unit frame pulse has been achieved earlier but it differs from the currently received frame pulse. The internally generated frame clock might have drifted.INSTRUCTIONS : FlexiBTS:
1. Check the cables between the System Module and RF Module/Extension System Module.
2. Reset the alarming System Module.
3. Replace the alarming System Module.
UltraSite/EUBB:
1. Reset the alarming WSMF.
2. Replace the alarming WSMF.
FAULT NAME : Frame number synchronisation error in optical interfaceMEANING : The timing of the new RP1 synchronization burst deviates from the present RP1 timing maintained in the BTS.INSTRUCTIONS : 1. Reset the System Module that causes the alarm.
2. If resetting of the module does not help, replace the System Module that causes the alarm.
FAULT NAME : Incompatible SW version detectedMEANING : A new unit with an incompatible SW has probably been inserted in the BTS.INSTRUCTIONS : Update compatible SW to the BTS (check the SW versions to see the active SW version, and update the active SW version), unless it is automatically updated by NetAct.
Related BTS - AXC interface: check the SW version of the BTS and AXC, and update compatible SW to the AXC or BTS.
52 DN99580892Issue 08D
RNC Base Station Alarms (7000-7900)
Id:0900d805807dbb82Confidential
7650 BASE STATION FAULTY
FAULT NAME : Incompatible unit detectedMEANING : An unsupported unit (for example a WSMA, WTRA, WSPA, WMCM or WTRB) has been detected in the cabinet.INSTRUCTIONS : Replace the unsupported unit with a unit of the correct type.
FAULT NAME : Internal MTU configuration failureMEANING : Internal Maximum Transfer Unit (MTU) configuration failed on FCM or FSP/FBIA.INSTRUCTIONS : 1. Reset the alarming System Module or unit.
2. Replace the alarming System Module or unit.
FAULT NAME : Internal delay measurement failureMEANING : An autonomous internal delay measurement has failed. The TCOM was not able to measure the internal delay for a cell for any of the RAKEs in a certain BB unit.INSTRUCTIONS : None
FAULT NAME : Invalid Configuration fileMEANING : The commissioning file is missing, or an incorrect commissioning file has been detected during BTS startup as follows: "Validation failed due to wrong BTS ID" or "Validation failed because of incompatible data"INSTRUCTIONS : 1. Check and correct the contents of the commissioning file.
2. Recommission the BTS with the valid commissioning file.
FAULT NAME : Master unit has lost connection to the slave unitMEANING : Connection to the DSP submodule has been lost or the submodule reports an error situation.INSTRUCTIONS : Note! Perform the steps below in the listed order until the fault disappears:
1. Reset the BTS. 2. Replace the faulty module/unit.
FAULT NAME : No baseband capacity for common channelsMEANING : There is not enough common channel capacity to set up any cells to the BTS, because Efficient Baseband or Full Baseband HSDPA is allocated (last WSP/FSP/Faraday card is fully reserved).INSTRUCTIONS : None
FAULT NAME : No connection to AXUMEANING : The master WAM detected that the AXU does not respond to polling messages.INSTRUCTIONS : 1. Check for alarms on the AXC.
2. Restart the AXC remotely. This will also cause a BTS
DN99580892Issue 08D
53
RNC Base Station Alarms (7000-7900) 7650 BASE STATION FAULTY
Id:0900d805807dbb82Confidential
restart.
3. Change the alarming AXC unit.
FAULT NAME : No connection to BTS transport submoduleMEANING : The connection to the BTS transport submodule is lost.INSTRUCTIONS : Note: Perform the steps below in the listed order until the alarm disappears.
1. Reset the site.
2. Replace the Transport submodule, which is located inside the System Module.
FAULT NAME : No connection to unitMEANING : The connection to a unit that belongs to the BTS configuration has been lost.INSTRUCTIONS : UltraSite, MetroSite, MetroSite 50, Triple-mode, UltraSite/EUBB:
1. Check the fault history, alarming unit and subrack. 2. If SW updates have been done recently, reload the SW. 3. If the WAF or WIC is alarming, try recommissioning the site. 4. Check that the unit is properly connected. If the unit LED does not light up, the unit is faulty. The fault might also be in the WPS unit or backplane. 5. Check the power cables and connectors as well as the I2C bus cables.
Cancel alarms: Removing and inserting the WIC, WSM or primary WAM causes a site reset. If both WSCs are removed, inserting the first removed WSC back into the cabinet causes a site reset.
If the 7650 BASE STATION FAULTY alarm is issued, reset the site. First try to reset the site with the software. If that does not help, replace the alarming unit.
If the WSMF unit is not present (replaced by WSMB)in BTS, alarming WSPFs are not used and should be removed from BTS. WSPFs can be removed because without unit BTS works as UltraSite not as EUBB.
FlexiBTS:
1. Check that the module is properly connected. If the module LED does not light up, the module is faulty. Check the alarming module. 2. Check the fault history.
54 DN99580892Issue 08D
RNC Base Station Alarms (7000-7900)
Id:0900d805807dbb82Confidential
7650 BASE STATION FAULTY
FAULT NAME : Not able to synchronize baseband bus with MEANING : The baseband bus synchronization towards failed.INSTRUCTIONS : Replace the alarming module.
FAULT NAME : Optical Interface Frame clock faultyMEANING : The VCXO does not get correct control voltage from the PLL filter of the clock cleaner. This may happen because of an unsuccessful clock recovery in the optical interface due to a missing or degraded input signal.INSTRUCTIONS : 1. Block/unblock the FSM.
2. Replace the FSM.
FAULT NAME : Optical interface FPGA sw crc check failedMEANING : The CRC check has failed in three consecutive optical interface FPGA SW downloading attempts.INSTRUCTIONS : Replace the alarming module.
FAULT NAME : Oven oscillator Missing PulseMEANING : The output signal of the OXCO has some problems and one or more clock pulses are missed.INSTRUCTIONS : 1. Block/unblock the FSM.
2. Replace the FSM.
FAULT NAME : Oven oscillator clock missingMEANING : The WSC is not able to deliver the clock signals required by the other units.INSTRUCTIONS : Replace the clock unit.
FAULT NAME : Oven oscillator clock missingMEANING : The output signal of the OXCO is missing and the FCM cannot deliver the 30.72 MHz System Clock required by the other units.INSTRUCTIONS : 1. Block/unblock the FSM.
2. Replace the FSM.
FAULT NAME : Oven oscillator heating failureMEANING : The OCXO warm-up takes too long and the OCXO does not become active within a period of eight minutes from the power-on. The ambient temperature can also be too low or it changes too fast.INSTRUCTIONS : Replace the alarming System Module.
FAULT NAME : PLL status not lockedMEANING : BTS monitors the FSP/FBIA/WSPF/WSMF PLL (Phase-Locked Loop) lock status and PLL locking fails.INSTRUCTIONS : FlexiBTS: 1. Block/unblock the FSM/FBIA. 2. If that does not help, replace the FSM/FBIA.
DN99580892Issue 08D
55
RNC Base Station Alarms (7000-7900) 7650 BASE STATION FAULTY
Id:0900d805807dbb82Confidential
UltraSite/EUBB: 1. Block/unblock the WSMF. 2. If that does not help, replace the WSMF. 3. Block/unblock the WSPF. 4. If that does not help, replace the WSPF.
FAULT NAME : POST test failedMEANING : The unit or module has been tested during the BTS power-on self test (POST) and a failure has been detected.INSTRUCTIONS : 1. Block/unblock the alarming unit/module.
2. Remove/reinsert the alarming unit/module.
3. Replace the alarming unit/module.
FAULT NAME : Power unit output voltage faultMEANING : The output voltage is too low or too high.
Usually the reason for the fault is the unit itself but in some cases the reason can be the unit that the WPS feeds.
If a short circuit occurs in the fed unit, it may affect the WPS and the "Output Voltage Fault" alarm is generated.INSTRUCTIONS : 1. Check the other active alarms.
2. Check the units that are supplied by the alarming WPS.
3. Check the backplane connectors and cables.
4. Replace the alarming WPS unit.
FAULT NAME : R-bus errorMEANING : UltraSite, MetroSite, MetroSite 50, Triple-mode: The bus between the WSP and WTR does not work. The R-bus errors are probably caused by a faulty WSM or WTR.
FlexiBTS: Error in the FSP or in the connection between the FSP and FCM.INSTRUCTIONS : UltraSite, MetroSite, MetroSite 50, Triple-mode:
1. If the WSM/WMC also generates an alarm from a WTR unit, check the WTR and WSM cable.
2. If there are no active WSM/WMC alarms, the reason for the alarm is a faulty WSM/WMC or WSP.
3. Run a WCDMA BTS loop test to locate the faulty unit.
4. If the WSP is faulty, block/unblock it.
56 DN99580892Issue 08D
RNC Base Station Alarms (7000-7900)
Id:0900d805807dbb82Confidential
7650 BASE STATION FAULTY
5. Replace the faulty unit.
FlexiBTS:
1. Check the cabling between the System Module and RF Module.
2. Check the active RF Module alarms and act accordingly.
3. Replace the faulty module (System Module).
FAULT NAME : RP1 synchronization burst errorMEANING : A new RP1 Frame Clock Burst (FCB) burst/message has been received from the RP3-01 interface while processing the previous burst/message.INSTRUCTIONS : 1. Reset the alarming Extension System Module by blocking/unblocking it.
2. If that does not clear the fault situation, replace the alarming Extension System Module.
3. If the System Module is the only alarming source or replacing the Extension System Module does not clear the fault situation, replace the alarming System Module.
FAULT NAME : SRIO chain configuration was rejectedMEANING : The platform SW rejected the baseband bus related SRIO configuration for Faraday core.INSTRUCTIONS : Replace the alarming unit/module.
FAULT NAME : Starting temperature below minimumMEANING : BTS cannot start properly, because FSPs cannot be powered up at too cold conditions.INSTRUCTIONS : 1. Wait until the module is automatically heated to the required start-up temperature.
2. If the fault is active for more than 2 hours, check the environmental conditions of the site.
FAULT NAME : Summing service release from reset failedMEANING : Summing service release from reset failed.INSTRUCTIONS : 1. Reset the System Module.
2. If a reset does not resolve the fault situation, replace the System Module.
FAULT NAME : Synchronization failure in Optical Interface MEANING : The RP3 channel has lost the frame synchronization state that it had achieved.INSTRUCTIONS : Swap the alarming and working links and then check where the alarm is now reported. If the alarming link remains the same,
DN99580892Issue 08D
57
RNC Base Station Alarms (7000-7900) 7650 BASE STATION FAULTY
Id:0900d805807dbb82Confidential
replace the System Module. If the alarming link changes, replace the RF Module behind that link.
FAULT NAME : System Module failureMEANING : The FlexiBTS has detected an abnormal operation or a failure in the internal functionality of the System Module.INSTRUCTIONS : Note: Perform the steps below in the listed order until the alarm disappears.
1. Reset the System Module.
2. Replace the System Module.
FAULT NAME : Telecom configuration failureMEANING : Telecom slave configurations or registrations failure. Unit RNW configuration failure. Telecom RNW reconfiguration failure.
Or
UltraSite, MetroSite, MetroSite 50, Triple-mode: WSP unit to WAM allocation failure.
FlexiBTS: - FSP unit to FCM allocation failure. - Faraday unit to FSP allocation failure.
UltraSite/EUBB: Faraday unit to WSPF allocation failure.INSTRUCTIONS : UltraSite, MetroSite, MetroSite 50, Triple-mode, UltraSite/EUBB:
Block/unblock the alarming unit. If there was an internal failure, the unit needs to be blocked/unblocked to get it initialized/configured again.
FlexiBTS:
If there was an internal failure, in the case of an FR, the module needs to be blocked/unblocked to get it initialized/configured again.
FAULT NAME : Temperature alarmMEANING : The internal temperature of the RF Module or System Module exceeds the threshold value, or the ambient temperature of the module(s) is outside the specified limits.INSTRUCTIONS : Note: Perform the steps below in the listed order until the BTS fault indication disappears.
1. Check the other BTS faults and act accordingly.
2. Check the ambient temperature of the BTS modules. If the
58 DN99580892Issue 08D
RNC Base Station Alarms (7000-7900)
Id:0900d805807dbb82Confidential
7650 BASE STATION FAULTY
ambient temperature is too high, make sure the airflow to the BTS modules is unobstructed, that is, the BTS modules are not covered with anything. If the ambient temperature is too low, it takes a while for the BTS modules to heat themselves to the threshold value.
3. Reset the alarming module/unit by blocking/unblocking it.
4. Replace the alarming module/unit.
FAULT NAME : Unit SW download failedMEANING : The software update to the unit or subunit has failed.INSTRUCTIONS : 1. Download the BTS SW again.
2. FCM: Reset the BTS.
3. If Step 2 does not help, replace the alarming module.
FAULT NAME : Unit SW download failedMEANING : Software update to a unit/subunit or module has failed.
UltraSite, MetroSite: The fault can also be caused by disconnected CIF bus cables.INSTRUCTIONS : UltraSite, MetroSite, MetroSite 50, Triple-mode, UltraSite/EUBB:
1. Download the BTS SW again. 2. If the alarming unit is WSP then block/unblock the WSP. 3. If the alarming unit is WAM or WPA then reset the BTS. 4. If does not help, replace the alarming unit.
FlexiBTS:
1. Download the BTS SW again. 2. FCM: Reset the BTS. 3. If Step 2 does not help, replace the alarming module.
FAULT NAME : Unit initialization failureMEANING : A unit/module or an IP address initialization has failed.INSTRUCTIONS : UltraSite, MetroSite, MetroSite 50, Triple-mode, UltraSite/EUBB:
1. Block/unblock the alarming unit.
2. Check if the non-commissioned WAM is the Master WAM. If so, this causes the fault. Check the fault history to know why the WAM switch-over occurred.
3. If the WAM is the fault source, check the RNC IP address in the commissioning file and modify the file if needed. If that does not help, perform a power-off reset.
DN99580892Issue 08D
59
RNC Base Station Alarms (7000-7900) 7650 BASE STATION FAULTY
Id:0900d805807dbb82Confidential
4. If step 3 does not help, replace the alarming unit.
FlexiBTS:
1. Block/unblock the alarming module. If that does not help, replace the alarming module.
2. If the FCM is the fault source, check the RNC IP address in the commissioning file and modify the file if needed. If that does not help, perform a power-off reset.
3. If Step 2 does not help, replace the alarming module.
FAULT NAME : Unit not supported by current BTS SW versionMEANING : An unsupported unit was found in the BTS. Typically this happens when a new unit version is installed and there is an older BTS SW in use that does not support the new unit version.INSTRUCTIONS : Replace the unit or upgrade the BTS SW.
FAULT NAME : Unit synchronization failedMEANING : The WAM/WSPC synchronization has failed.INSTRUCTIONS : 1. Block/unblock the alarming unit.
2. Replace the alarming unit.
FAULT NAME : Unknown HW resourceMEANING : A unit cannot be identified by its product code or by its physical device address (object ID).INSTRUCTIONS : Replace the alarming unit/module.
FAULT NAME : Unknown product codeMEANING : A module cannot be identified by its product code but is known by its physical device address (object_ID).INSTRUCTIONS : Replace the alarming module.
FAULT NAME : WAM internal errorMEANING : The Telecom SW does not communicate with the ATM SW because of a fault.INSTRUCTIONS : Replace the faulty unit
FAULT NAME : WCI baseband reference clock failureMEANING : The master or redundant WSC does not generate Baseband Reference Clock (BRCLK) to the WCI because of an internal failure or a clock driver failure in the WSC unit.INSTRUCTIONS : 1. Block/unblock the active WSC unit.
2. Replace the WCI unit.
3. Replace both WSC units.
60 DN99580892Issue 08D
RNC Base Station Alarms (7000-7900)
Id:0900d805807dbb82Confidential
7650 BASE STATION FAULTY
FAULT NAME : WIB unit AC line break faultMEANING : There is a mains break. The BTS power supply is cut off.INSTRUCTIONS : Check the power supply to the BTS.
FAULT NAME : WSM failureMEANING : The BTS has detected an abnormal operation or a failure in the internal functionality of the WSMF unit.INSTRUCTIONS : Note: Perform the steps below in the listed order until the alarm disappears.
1. Check the alarm history, alarming unit and subrack.
2. Check that the unit is properly connected. If the unit LED does not light up, the unit is faulty.
3. Reset the BTS.
4. Replace the alarming unit.
FAULT NAME : WSMF WAM Interconnection FailureMEANING : Connection failure between WAMA and WSMFINSTRUCTIONS : Check that cables are connected between WAMA-WSMF and WSMF-AXCF.
FAULT NAME : WSP PCI-bus failureMEANING : There is a fault in the internal WSP/FSP PCI bus target (DSP) connections. Some of the WSP/FSP DSP processors may be broken and out of use.INSTRUCTIONS : Replace the alarming unit/module.
CancellingDo not cancel the alarm. The system cancels the alarm automaticallywhen the fault has been corrected.
DN99580892Issue 08D
61
RNC Base Station Alarms (7000-7900) 7652 BASE STATION NOTIFICATION
Id:0900d805807dbb82Confidential
29 7652 BASE STATION NOTIFICATIONMeaning
A minor fault (or faults) has occurred in the base station.
Check the reason for the fault from the supplementary text fieldof the alarm.
The effect of the fault on the functioning of the network elementdepends on the fault description. For more information, see basestation fault descriptions in WCDMA RAN and I-HSPA System Libraries.
Supplementary information fields1 rack (cabinet) number
2 shelf number
3 slot
4 type of unit
5 unit number
6 subunit number
For more information, see instructions on Alarm Structure.
InstructionsVerify the configuration of a BTS by checking the commissioning, cablingand correct installation of the units/modules at the BTS. Make sure theenvironment does not cause the fault.
Before a unit/module is replaced at the BTS, the site should be reset torecover from any temporary faults which might have caused themalfunctioning of the unit/module. When an active alarm is a 'Start'alarm, a site reset is required to cancel the alarm. If the site reset ormodule block/unblock does not help, replace the faulty unit/module (seesource of the alarm and instructions fields of the corresponding alarms).
Below is the list of BTS fault(s) which might have caused this alarm inWN6.0_EP1 release. In case of earlier SW release and in case you need moredetailed fault descriptions refer to WCDMA RAN and I-HSPA System Libraries.The BTS fault descriptions are also included in BTS SW releasedocumentation. If that does not help, contact your local Nokia SiemensNetworks representative.
FAULT NAME : autonomous reset as recovery action
62 DN99580892Issue 08D
RNC Base Station Alarms (7000-7900)
Id:0900d805807dbb82Confidential
7652 BASE STATION NOTIFICATION
MEANING : The BTS tries to correct a fault situation by performing a recovery reset to a unit, the site or the BTS.INSTRUCTIONS : Check the alarm history and other active alarms of the unit.
Note! This alarm does not require any (special) actions.
FAULT NAME : 2M external reference missingMEANING : The reference clock monitoring has detected a loss of 2.048MHz signal received from an external reference source, connected to Sync In interface of the System Module.INSTRUCTIONS : Note! Perform the steps below in the listed order until the alarm disappears.
1. Check the cabling (connected to Sync In interface).
2. Check that the 2.048MHz reference source is working normally and the 2.048MHz signal is available.
3. Replace the alarming module.
FAULT NAME : ATM cell lossMEANING : ATM cells are lost. The cell loss can be caused by a traffic overload, by the WAM receiving an invalid ATM cell or AAL5 packet, or by the data corruption on the Iub (that is, a bad BER).
The most common causes for this fault are transmission network problems (causing unnecessary WAM changes).INSTRUCTIONS : 1. Check that bandwidths (cells/s) are the same at the BTS, AXC and RNC.
2. Check the data integrity from the incoming Iub (see Troubleshooting instructions).
3. Check the other transmission elements' active faults (see the Faults for AXC document).
4. Check the WAM, AXU and the cabling between them.
FAULT NAME : ATM, A2EA configuration errorMEANING : The RNC A2EA transport layer address does not comply with the given BTS A2EA address.
This fault is reported to the BTS Site Manager only.INSTRUCTIONS : Check and re-commission the AXC (if AAL2 multiplexing is in use), RNC or BTS with the correct BTS A2EA addresses.
FAULT NAME : Active clock tuning faultMEANING : The phase measurement cannot be performed in the active WSC or WMC.INSTRUCTIONS : 1. Run fast tuning with BTS Site Manager.
DN99580892Issue 08D
63
RNC Base Station Alarms (7000-7900) 7652 BASE STATION NOTIFICATION
Id:0900d805807dbb82Confidential
2. Block/unblock the alarming unit.
3. Replace the alarming unit.
Note that because o