RM-DCM-2Quick Start
Installation Guide
Version H0Document Part Number UM-215
March 2018
OVERVIEW The RM-DCM-2 is a UL294 Listed and UL1076 Listed door control module that includes the RM-4E Reader Module (RM-4E) and enclosure. The RM-DCM-2 is designed to support up to two RM-4E modules, providing a single enclosure for doors with IN and OUT readers.
The enclosure also has space for up to three I/8 and/or R/8 boards, for a total of four boards. The RM-DCM-2 supports an optional battery (12 VDC, 4A), which will be recharged by the RM-4E battery charging circuit.
The RM-4E board provides the hardware interface between Magnetic signaling read heads or Wiegand signaling read heads and the apC/8X, iSTAR, and iSTAR Pro hardware. The RM-4E also provides inputs and outputs that communicate between door components and the apC/8X, iSTAR, and iSTAR Pro hardware.
The I/8 module provides eight supervised inputs and the R/8 module provides eight dry contact, Form C relay outputs.
The RM-DCM-2 system consists of two subassemblies:
Model RM-DCM-CAN enclosure Model RM-4E board
NOTE For information about the RM-4E, I/8, or R/8 modules, refer to the Quick Start guides listed in Table 13.
NOTE All interconnecting products or devices must be UL Listed.
1
Overview
Table 1 lists the RM-DCM-2 board and enclosure offered by Software House. You can install an RM-DCM-2 up to 4000 feet (1219 meters) from the apC/8X, iStar or iSTAR Pro hardware.
TABLE 1. RM-DCM-2 Product Offering
Product Description Enclosure
RM-DCM-2 RM-4E module, with connectors, LEDs, on-board relays, and battery charger
Factory mounted in metal junction box with mountings for optional hardware available from Software House.
TABLE 2. UL294 Levels
Feature Level
Destructive Attack 1
Line Security 1
Endurance 4
Standby Power 1
2
RM-DCM-2 Unit
RM-DCM-2 UNIT Figure 1 shows the RM-DCM-2 unit with one RM-4E board, an optional battery, and LCD.
NOTE UL has evaluated this configuration only.
FIGURE 1. RM-DCM-2 with Battery and LCD
FEATURES RM-DCM-2 features include:
LED status indicators – display RS-485, inputs, outputs, and power status.
Maglock component – for use with door objects. Bypass component – connects to a release switch on a door secured
by a magnetic lock. On-board battery charger – supplies power to an optional battery for
memory retention in the event of a power failure.
NOTE The on-board battery is for memory retention only. UL has not evaluated the battery for the Standby Power requirements of the UL294 Standard.
RM-4E
Battery
LCD
3
Features
Optional Equipment
Optional equipment for the RM-DCM-2 includes:
Backup battery kit – provides the RM-4E with backup power for memory retention in the event of a power failure. The kit includes a cable assembly that connects the battery to the RM-DCM-2 battery component.
LCD component – displays diagnostic information and status messages for readers attached to the RM-4E. The optional LCD is attached to the J1 (LCD) connector on the RM-4E board.
Read Head Interfaces
The RM-4E supports Wiegand signaling or Magnetic read heads. Select the interface you want by setting S5 position 1 on the RM-4E board.
Set S5-1 to the On (Closed) position for Wiegand read heads Set S5-1 to the Off (Open) position for Magnetic read heads
NOTE The RM-DCM-2 has been evaluated by Underwriters Laboratories Inc. (UL) for compatibility with HID Model 30387 and HID 5355 readers only.
RM-DCM-2 with RM-4E,I/8, R/8, and Battery
The RM-4E Reader Module (RM-4E) simplifies installation by providing clearly labeled termination points to identify functionality and device information. The RM-4E also features LEDs for output, RS-485, power, and input status to make it easier to install and service the system.
The RM-4E board is installed and mounted at the top of the door. Another RM-4E board and any combination of I/8 and R/8 modules, up to a total of four boards, can be mounted on the door and within the enclosure.
Figure 2 shows an RM-DCM-2 unit with one RM-4E, R/8, I/8, and battery. There could also be another RM-4E board, I/8, or R/8 mounted in the space provided within the enclosure.
4
Features
FIGURE 2. RM-DCM-2 with RM-4E, R/8, I/8, and Battery
Tamper Switch
The RM-DCM-2 provides a tamper switch as part of the enclosure.1. Verify or connect the normally closed tamper switch in the enclosure to the
2-pin connector labeled TAMPER (SW2) on the RM-4E board. See Figure 2.
2. Verify or set DIP switch SW5-4 (Tamper Override) to Off (Closed) on the RM-4E. See Figure 5.
3. To configure the tamper:
C•CURE 800 - use the Reader Configuration Advanced dialog box. C•CURE 9000 - use the Reader I/O tab.
NOTE The switch is normally closed so that when the door is closed the tamper is secure. If the door is forced, the switch will open causing an alarm event.
NOTE The tamper switch must be connected to comply with UL requirements.
Tamper Input (SW2)
Tamper Switch
5
RM-4E Reader Interface
RM-4E READERINTERFACE
You can interface read heads that supply Wiegand signaling or magnetic (ABA) signaling to the apC/8X, iSTAR, and iSTAR Pro using RM-4E boards.
Figure 3 indicates how an RM-4E board interfaces with Wiegand and Magnetic signaling read heads.
FIGURE 3. RM-4E Interface
NOTE UL has not evaluated magnetic (ABA) signaling read heads.
6
RM-4E Reader Interface
RM-4E Layout Figure 4 shows the photograph of an RM-4E board with LCD.
FIGURE 4. Photograph of RM-4E Board
7
RM-4E Components
RM-4ECOMPONENTS
Figure 5 shows the location of connection points, switches, and LEDs on the RM-4E board.
RM-4E Board Layout
FIGURE 5. RM-4E Board Layout
This section lists the RM-4E components — starting from the upper right corner of Figure 5 and moving in a clockwise direction.
Tamper
The RM-DCM-2 tamper input twisted pair wires, shown in Figure 2, are connected to the TAMPER (SW2) input pins.
8
RM-4E Components
Power In There are two ways to power an RM-4E:
Method A - from the Power In connector using an external power supply, which also charges the battery through the BATTERY connector.
Method B - from the RS 485 connector using the apC or iSTAR power supply.
NOTE: Do not use both power connection methods at the same time.
NOTE A UL Listed power-limited access control or burglar alarm power supply, capable of four hours standby, must be used when the unit is powered from a source other than the apC or iSTAR.
FIGURE 6. RM-4E Power Wiring - Method A
Method A - via Power In
Connect +12 or +24 VDC to Pin 2 of the Power IN connector. Connect the ground side of the supply to either Pin 1, 3, or 4. Because
the three grounds are all tied together, you can connect the negative side of the supply to any of the three pins.
Do not use +24 VDC unless all devices on the bus are RM-4Es. RM-4s, I/8s, R/8s and MRMs must be powered with +12 VDC.
NOTE The battery charger only works if you power through the Power IN connector.
+12/24 VDC
9
RM-4E Components
Method B - via RS-485 (RM Bus Connector)
Connect +12 VDC to Pin 1 of the RS-485 connector on the bottom right side.
Connect Ground (Gnd) to Pin 4 of the RS-485 connector.
NOTE The +12 VDC input on Pin 1 has a protection diode that prevents you from using the RS-485 connector as a source of +12 VDC if you power through the Power IN connector.
Battery
Connect the plus and minus sides of the 12 VDC battery to the Battery connector. The battery provides power for memory retention in the event of a power failure. When power is restored, the battery is charged by the power supplied through the Power In connector.
LED Connector Table 2 lists LED Connector Signals and Functions on the RM-4E board.
NOTE UL has not evaluated using Pin 5 to drive an external beeper.
Typical LED Scenarios
One wire Bi-Color - Attach the brown wire from the read head to the Yellow LED drive on the RM-4E.
Two wire Red and Green - Attach the brown wire from the read head to Red LED drive. Attach the orange wire from the read head to the Green LED drive.
Three wire Red, Green, Yellow - Attach each LED drive to the associated color LED.
See “LED Control” on page 22 for information.
TABLE 3. LED Connector Signals and Functions
Pin Signal Function
6 Gnd Ground
5 Beep Used to drive an external beeper on a reader connected to the unit.
4 Grn Green LED drive
3 Yel Yellow LED drive
2 Red Red LED drive
1 +5 VDC + 5 VDC, if required
10
RM-4E Components
NOTE When the wiring gauge is too small or the wiring runs are too long, the Yellow LED drive oscillation can cause cross-talk and result in misreads.
RS 485 Reader Bus RS 485 is the reader bus connection to the apC or iSTAR.
It is two wire, half duplex RS 485. Connect Tx+ / Rx+ to Pin 2 and connect Tx- / Rx- to Pin 3. The pins are numbered right to left on the connector.
Connecting ReadHeads
Connect read heads to the Read Head connector.
Connect either a Wiegand signaling device or a magnetic (ABA) signaling device. Wiegand signaling uses Data 1 and Data 0 lines and magnetic signaling uses Clock and Data.
Wiegand Signaling
For Wiegand signaling, use the following pinout; set SW5-1 to ON.
TABLE 4. RS 485 Reader Bus Connections
Pin Signal Function
4 Gnd Ground
3 D- Tx- / Rx- (usually green)
2 D+ Tx+ / Rx+ (usually white)
1 +12 +12 VDC (if required)
TABLE 5. Wiegand Signaling Pinout
Pin Signal Function
1 D1 Data 1 line (white)
2 D0 Data 0 line (green)
3 N/C No connection
4 +5 VDC +5 VDC if required
5 GND Ground
6 +12 VDC +12 VDC if required
11
RM-4E Components
Magnetic (ABA) Signaling
For Magnetic (ABA) signaling, use the following pinout; set SW5-1 to OFF.
NOTE UL has not evaluated magnetic (ABA) signaling read heads.
Relay 1, Relay 2,MagLock, and Bypass
The RM-4E provides lock components that facilitate connecting magnetic and electric strike locks.
Relay 1 is a standard Form C, dry contact relay, identical to the relays found on the iSTAR ACM.
Relay 2, along with the MagLock and Bypass connectors have internal etch connections for wiring magnetic and electric strike locks
Tie Point (TP1/TP2) connector pins are not connected to the circuitry. They are used as connection points to avoid field splices when connecting locks to Relay1. TP1-1 is tied to TP1-2, and TP2-1 is tied to TP2-2.
Lock Connectors The Lock Connector pinouts are shown below.
TABLE 6. Magnetic (ABA) Signaling Pinout
Pin Signal Function
1 CRD N/A
2 STRB Strobe signal
3 DAT Data signal
4 +5 VDC +5 VDC if required
5 GND Ground
6 +12 VDC +12 VDC if required (not used by Software House magnetic read heads)
12
Lock Wiring Configurations
FIGURE 7. Lock Connectors
LOCK WIRINGCONFIGURATIONS
RM-4E lock connectors support the following wiring configurations:
Magnetic Lock using Relay 2 Electric Strike using Relay 2 Electric Strike using Relay 1
The following sections describe how to connect each configuration. The electric strike examples are shown as Fail-Secure.
Magnetic Locks The normal state of a magnetic lock has current flowing through an electromagnet on the lock that pulls a strike plate with a force of 500-2000 lbs.
Safety codes usually require a bypass switch for emergency egress. This is not the Request to Exit (REX) switch.
Note the internal etch connections between Relay 2, Maglock, and the Bypass connector.
Connecting a MagneticLock
The following figure shows an example of connecting the power supply, magnetic lock, and bypass switch.
13
Lock Wiring Configurations
FIGURE 8. Magnetic Lock Wiring with Jumper Options
14
Lock Wiring Configurations
Magnetic LockComponents
This section describes the components and connections for magnetic lock wiring.
Power Supply
The power for a magnetic lock must be filtered, regulated direct current (DC) voltage. Alternating current (AC) does not work and half wave rectified DC does not work reliably.
Most magnetic locks consume about 3 watts, which is about 125 milli-amps @ 24 VDC or 250 milli-amps @ 12 VDC.
18 AWG wire is generally recommended. If the wire runs exceed 100 feet, use 16AWG wire instead.
The power supply to a magnetic lock must be isolated. Do not connect the output of the power supply or the negative side of the lock to earth ground. The connection from the minus side of the power supply must go to Maglock pin 3.
Bypass Switch
Connect a normally closed (NC) emergency Bypass switch as shown. Remove the J15 Bypass jumper for normal operation.
It will be necessary to connect the J15 Bypass jumper (closed) if you install an electric strike on Relay 2.
Diode Protection
An optional inductive kickback suppression diode is available by connecting the J13 Diode jumper (closed).
Some magnetic locks have the suppression circuitry built-in so in some cases the J13 Diode jumper should be removed (open).
RM-4E Power Failure
When using the configuration shown, the magnetic lock remains locked if the RM-4E loses connection to the apC or iSTAR because the normally closed (NC) connection of Relay 2 is used. The magnetic lock also remains locked if the RM-4E loses power.
15
Lock Wiring Configurations
You have the option of wiring to the normally open (NO) connector of Relay 2 if you want to have the Magnetic lock unlock under those conditions. If you use the normally open (NO) connector then Relay 2 will have to be normally energized using the C•CURE Administration application.
If the power supply fails, the magnetic lock will unlock regardless of whether the normally closed (NC) or normally open (NO) is used.
Electric Strikes Unlike magnetic locks, electric strike locks typically lock when not powered and unlock when powered.
You must decide if you want to wire for “fail-secure” or “fail-safe.” Fail-secure means that if there is a power failure, the door goes to a secure or locked state. Fail-safe (fail-open) means that the door is open if there is a failure. It is important that local codes be followed to avoid people getting trapped in an emergency situation. Usually fail-secure doors have crash bars to allow emergency egress.
Using Relay 2 for anElectric Strike
The same internal connections that are used for a magnetic lock can be used to wire an electric strike. Connect the plus side of the power supply to the normally open (NO) connection of Relay 2 and connect the remaining external connections the same as the magnetic lock
16
Lock Wiring Configurations
FIGURE 9. Relay 2 Fail Secure Wiring
17
Lock Wiring Configurations
Electric StrikeComponents
This section describes components and connections for electric strike wiring using Relay 2.
Bypass Switch
Connect the J15 Bypass jumper (closed) to provide the internal connection from Maglock Pin 1 to the C contact of Relay 2. Do not connect an external bypass switch.
Diode Protection
An optional surge suppression diode is available by connecting the J13 Diode jumper (closed). If the electric strike has a suppression diode built-in, disconnect the J13 Diode jumper (open).
Using Relay 1 for anElectric Strike
Relay 1 is a standard Form-C dry contact relay. Wiring door strikes using this relay on the RM-4E is the same as wiring them to apCs, iSTARs, R/8s etc.
Two pair of isolated tie points have been added to minimize splices. Connect the strike and the power supply as shown. There is no
internal etch to consider when using Relay 1.
In the example below, a fail-secure door is shown with the normally open (NO) contact. You can add an optional external suppression diode, if desired.
18
Inputs
FIGURE 10. Relay 1 - Fail Secure Wiring
INPUTS
Input 1 and Input 2 Connect inputs using the standard Software House supervision for either NO or NC. Figure 11 shows an example of wiring Normally Open (NO) and Normally Closed (NC) inputs.
FIGURE 11. Input Wiring
19
Inputs
NOTE To comply with UL requirements, use shielded, minimum 22 AWG stranded, twisted pair cable for monitor points, DSMS, and REXs. Use Belden 9462 or equivalent.
LED Input Status
Each input uses a Red, Yellow, or Green LED to show the input status. Only one color will be on at a time for each input.
Table 6 lists the LED color and the corresponding input status.
Red LED indicates alert (nominal 500 ohms or 2K ohms). Green LED indicates secure hardware state (nominal 1k ohms). Yellow LED indicates supervision error (open circuit, shorted, or line
fault). The RM-4E input status LEDs show flashing status if the RM-4E is
communicating with the apC or iSTAR and at least one input or output is configured, or the reader is being used on a door. (The apC or iSTAR needs a configured reason to communicate.)
TABLE 7. LED Input Status
LED Color Input Status
Red Alert (nominal 500 ohms or 2K ohms).
Green Secure hardware state (nominal 1k ohms).
Yellow Supervision error (open circuit, shorted, or line fault)
20
Inputs
SW 5 DIP Switch Functions
The SW 5 DIP switch on the RM-4E is similar to the SW 3 DIP switch on the RM-4.
Note: On = Closed, Off = Open
TABLE 8. SW 5 DIP Switch on RM-4E and SW 3 DIP Switch on RM-4
SW 5 DIP Switch on RM-4E Function Value Equivalent DIP
Switch on RM-4
SW 5-1 Reader Type Off = Magnetic (ABA) signaling, On = Wiegand signaling,
SW 3-1
SW 5-2 LED Control Off = Normal,On = One-Wire (A,B,C)
SW 3-6
SW 5-3 LED Control Off = Normal, On = External Bi-color
SW 3-3
SW 5-4 Tamper Off = Normal Tamper, On = Inhibit Tamper
SW 3-4
SW 5-5 RS-485 Termination Off = Not last in line, On = Last in line
SW 3-5
SW 5-6 Input 1 and Input 2 LED Control
Off = Do not display LEDs, On = Display LEDs
N/A
SW 5-7 Not Used Not Used N/A
SW 5-8 Not Used Not Used N/A
21
LED Control
LED CONTROL SW5-3 and SW5-2 control the reader LED display.
SW5-3 and SW5-2 provide the same LED control that is available on the RM-4 and the iSTAR ACM.
Table 8 shows the possible settings of SW5-3 and SW5-2.TABLE 9. SW5 LED Control
Three Wire LED Control When both SW5-3 and SW5-2 are Off, it specifies Three wire LED control. In this case, the Red, Green, and Yellow LED drives are wired to the associated LED of the same color as shown in Figure 12.
FIGURE 12. Three wire LED control
SW5-3 SW5-2 Function
OFF OFF 3-wire (R,G,Y)
ON OFF External Bi-color(Normal External Bi-color)
OFF ON 1 Wire (A,B,C)
ON ON Special RM-4E 1-Wire LED Control
22
LED Control
RM LEDs
Table 9 describes the various conditions indicated by the red, green, and yellow RM reader LEDs.
TABLE 10. RM Reader LED Indications
Red LED Yellow Green Indication
Brief flash Brief flash Brief flash Power up
Off Off Off Online (software flag enabled)
Off On Off Online
On Off Off Offline or reader tamper
Solid for 1 sec. Off Off Access denied
Fast flash for 2 sec. Off Off Access denied (Software Flag Enabled)
Off Off On Access granted or door unlocked (Software Flag Enabled)
Off Off Fast flash Access granted
Off Off Slow flash Door unlocked
Off Slow flash Off Enter second card (escorted access only)
Off Fast flash Off Enter PIN
Off Fast flash Off Enter floor # (systems configured for elevator control only)
Flash w/ each key press
Unchanged Flash w/ each key press
Keypad input
Slow flash Off Off Reader not configured
Fast flash Fast flash Fast flash Alarm: door forced/held open
On On On Error condition: Remove power to prevent damage to RM
23
LED Control
External Bi-color LEDControl
When SW 5-3 is On and SW5-2 is Off, the function is External Bi-color because there are two LEDs (Red and Green) in the reader.
The LEDs will appear as Yellow when both Red and Green are on, making the function essentially a Tri-color (Red, Green, Yellow).
Two Wire (Red and Green)
There are two cases of External Bi-color — two wire and one wire. With two wire, the Red and Green LED drives are wired as shown in Figure 13
FIGURE 13. External Bi-color (2 wire)
24
LED Control
One Wire (Yellow)
With one wire, the Yellow drive is wired as shown in Figure 14.
The Yellow LED drive gets inverted in the read head resulting in a Red LED when the signal is low and a Green LED when the signal is high. If the Yellow LED drive is oscillating, the Red and Green LEDs will be oscillating and will appear to the human eye that the LED is Yellow. The RM-4E will oscillate the Yellow drive at 1 KHz when a Yellow LED display is required.
FIGURE 14. External Bi-color (1 wire)
Special RM-4E 1-WireLED Control
Setting both SW5-3 and SW5-2 On results in a special RM-4E legacy mode that is equivalent to the 1-wire Bi-color mode on earlier versions of the RM-4E.
In the standard 1-wire Yellow drive connection, the drive will oscillate, resulting in the appearance of a Yellow LED. In the special mode, the drive does not oscillate and there is no Yellow indication.
25
LED Control
One Wire (A,B,C) LEDControl
When SW5-2 is On, it specifies One Wire (A,B,C) mode. In this case, a single LED drive (Red or Green or Yellow) is wired with varying results as shown in Figure 15.
One wire mode is typically used for older read heads with a single LED that is either On, Off, or flashing.
FIGURE 15. One Wire (A,B,C) LED control
26
Installation Requirements
INSTALLATIONREQUIREMENTS
The Software House RM-DCM-2 enclosure accommodates an RM-4E board, as well as three additional Software House boards. The enclosure door is hinged, for ease of installation, and includes a tamper switch and key lock.
This section describes the dimensions and installation requirements for the RM-DCM-2 enclosure and modules.
Installing the Enclosure
Make sure the installation location provides sufficient space for the RM-DCM-2 enclosure, and the necessary electrical conduit.
Figure 16 gives the dimensions in inches for mounting the RM-DCM-2 enclosure.
FIGURE 16. RM-DCM-2 Enclosure Dimensions (in Inches)
27
Installation Requirements
Module Dimensions Figure 17 shows the dimensions of the RM-4E, R/8, and I/8 modules. Maximum component height is 0.5 inches (12.7 mm).
FIGURE 17. RM-4E, R/8, and I/8 Mounting Hole Dimensions
Enclosures UL has approved the RM-DCM-2 enclosure for use with R/8, and I/8 boards.
Mounting the RM-4E, R/8, and I/8 Boards
To mount the RM-4E, R/8, and I/8 boards in an RM-DCM-2 enclosure, use four 1/4” 6-32 screws and star washers to secure the boards to the mounting studs in the enclosure (see Figure 18).
There are four possible mount positions for the three boards in the enclosure.
28
Installation Requirements
The design ensures that you maintain a minimum of 1/4” spacing between adjacent electronic components, and between electronic components and the enclosure.
FIGURE 18. Mounting RM-4E, R/8, and I/8 modules in an RM-DCM-2
Power Supply andWiring
Each module (RM-4E, I/8, R/8) has a typical rating of 125mA, plus another 25mA for each active relay. The need for an external power supply is based on the electrical current available from the apC panel or iSTAR controller power supply, the calculated draw of other boards in the system, and the voltage drop due to wiring length.
NOTE A UL-Listed power-limited access control or burglar alarm power supply, capable of four hours standby, must be used when the unit is powered from a source other than the apC or iSTAR.
NOTE Wiring methods shall be in accordance with the National Electric Code (ANSI/NFPA 70), local codes, and the authorities having jurisdiction.
Environment Operating temperature ranges for the RM-DCM-2 is 32-120° F (0-49° C); 85% relative humidity @ 86° F ± 3° (30° C ± 2°).
The RM-DCM-2 is suitable for indoor use, to be installed within the protected premises.
Connect the modules (RM-4E, I/8, R/8) to an RM reader bus on an iSTAR or apC. The modules must be within the maximum wire length range of 4000 ft. (1219 m).
MountingStuds
MountingStuds
MountingStuds
29
RM-DCM-2 Specifications
RM-DCM-2SPECIFICATIONS
This section includes physical specifications and optimal operating specifications for the RM-DCM-2.
NOTE UL has evaluated the RM-DCM-2 for indoor use with a range of 0° C to 49°C (32°F to 120°F).
Software and FirmwareSupport
Current versions of C•CURE 9000 and C•CURE 800/8000 system software and firmware support the RM-DCM-2 components.
Power Requirementsand Specifications
Table 10 lists the power requirements and operating specifications of the RM-4E board in the RM-DCM-2 enclosure.
TABLE 11. RM-4E Power Requirements and Operating Specifications
Requirement Specification
RM-4E Power requirements +12/24 VDC280 mA without reader and relays
Maximum input (with full load) +12/24 VDC550 mA maximum with reader and relays
Relay contact power limits Up to 30 VAC/DC, 3.3 A maximum
Reader LED output control 4.0 VDC to 5.25 VDC, 20 mA maximum
Reader port output voltage 5 VDC or12 VDC
Reader port output maximum current
125 mA (at 5V or 12V)
NOTE Software House recommends local power when using the battery charging circuit and when the RM-4E is used with high-power, long-range readers. See “Power In” on page 9 for information.
30
RM-DCM-2 Specifications
TABLE 12. R/8 and I/8 Requirements and Operating Specifications
Requirement Specification/Contact Ratings
R/8 module power requirements 125mA at +12 VDC plus 25mA for each Active RelayR/8 relay contact rating - 2A at 30 VDC
I/8 module power requirements 125mA at +12 VDC
31
Parts List
Physical Specifications
TABLE 13. RM-DCM-2 Physical Dimensions
PARTS LIST Table 13 lists part numbers for the RM-DCM-2 product.
Compliance The RM-DCM-2 has been tested and certified for compliance with the standards listed below:
UL Listed
UL 294 UL 1076
Other
FCC Part 15B class A CE EN50081-1 EN50130-4
Requirement Specification
Enclosure dimensions 14 x 12 x 3.5 in.35.6 x 30.5 x 8.9 cm.
Weight (without battery) 10 lbs. (4.53 kg.)
TABLE 14. RM-DCM-2 Parts List
Description Quantity Part No.
RM-DCM-2 Enclosure with RM-4E Module
1 RM-DCM-2
RM-DCM-2 Quick Start Guide 1 UM-215
RM-4E Module optional RM-4E
I/8 Module optional AS-0073-000
I/8 Quick Start Guide optional UM-204
R/8 Module optional AS-0074-000
R/8 Quick Start Guide optional UM-205
32
Testing the RM-DCM-2
Testing the RM-DCM-2
This section describes the procedures that verify the RM-DCM-2 installation and operation.
Required Equipment
The following equipment is required.
Two 1K resistors An LCD display module (2 line x 16 character), Software House part
number RM-LCD Three LEDs A multi-meter to measure voltage and resistance
Configuration Requirements
You must complete the following configuration requirements before you test the RM-DCM-2:1. Install the RM-4E.
2. Install the LCD display module into the LCD connector on the RM-4E circuit board.
33
Testing the RM-DCM-2
Self-Test Mode
The RM-4E has a built-in self-test mode. Perform the steps in this section to run the self-test. 1. Remove power to the RM-4E.
2. Set Rotary Switch SW4 to position 0.
3. To test the reader LEDs, connect three LEDs to the Reader LED port as shown in Figure 19. Connect the anode (long lead) of each LED to Pin 1 (+5v). Cover the LED wires with heat shrink to prevent short circuits.
NOTE If you are using an older LED that does not have a built-in current-limiting resistor, add a 1K-ohm resistor in series.
FIGURE 19. Connecting LEDs for Self-Test Mode
4. Power up the RM-4E. When you power up the RM-4E:
Relays 1 and 2 toggle every second.
Reader LED lines Red, Green, and Yellow flash on and off.
The LCD displays the information shown in Figure 20.
34
Testing the RM-DCM-2
FIGURE 20. Self-Test LCD Display
5. To test the supervised inputs, attach a 1K resistor to each input (Input 1 and Input 2) as shown in Figure 21.
Prior to installing the resistors, the input state should be open (0). After installing the resistors, the input state should be secure (I1=1 and I2=1).
FIGURE 21. Attaching Resistors to the Supervised Inputs
6. To test each reader line, short to ground, one at a time, each of the three reader data lines (D0, D1, and DAT) on the Reader port.
After shorting a data line, the display should show a “1” in the appropriate reader line position to indicate that the data line is low (for example, W=010 when you short the D1 line).
After removing the short from the data line, the display should revert to 0 for that reader line.
Indicates the state of supervised inputs Input 1 and Input 2: 0 = Open1 = Secure2 = Alarm3 = ShortT = Trouble (Line Fault)
Indicates the state of the reader port connections (D1 line, D0 line, and DAT line, in that order):0 = Closed1 = Open
Indicates the current position of switches 1, 2, and 3 on DIP switch S5:0 = On (Closed)1 = Off (Open)
Indicates the state of the Tamper enable switch:0 = Closed1 = Open
Indicates the state of the keypad input lines, where the number after “K” is the keypad input. The last change is displayed.0 = Closed1 = Open
35
Testing the RM-DCM-2
7. To test the tamper switch, short tamper connector SW2-2 to ground. The display should change to T=0.
Remove the short. The display should revert to T=1.
8. To test SW5 positions 1, 2, and 3, set each of these DIP switches to the Off (open) position.
The display should show S5=111. Set each of these DIP switches to the On (closed) position. The display should show S5=000.
9. To test the keypad, short to ground each of the eight keypad connectors on port J2 one at a time.
The display should indicate that a voltage level change was detected. For example, if you short keypad connector 3, the display should show K3=0, where K3 is the keypad connector number and 0 is the new state.
Manual Test Procedure
To manually test the RM-DCM-2:1. Measure the supply voltage to the RM-4E.
The voltage can be measured between pin 1 (ground) and pin 2 (supply) on the Power-In connector. The voltage must be +12 Volts (+/-5%) or +24 Volts (+/- 10%).
2. Check the RM-4E address setting.
The RM-4E must be set to an unused address when connected to the apC or ISTAR. The LCD will display the switch setting upon power-up.
Verify that the displayed reader address is correct for your installation.
3. Check the board for communications to the apC or iSTAR.
Observe LEDs DS1 and DS2 on the lower right corner of the RM-4E board. The LEDs should blink rapidly to indicate communication to and from the RM-4E.
If the LEDs are not blinking, the RM-4E may not be properly configured in C•CURE.
4. Check the supervised inputs.
With no switches or resistors connected to the “Input 1” and “Input 2” lines, the C•CURE Monitoring Program should report inputs as “Open Loop”.
When you connect the 1K resistor to the input terminals, the C•CURE Monitoring Program should report the input as “Open loop cleared”.
5. Check the outputs.
The outputs can be functionally tested by using the “momentary activate” feature in the C•CURE Monitoring Program.
When the outputs are momentarily activated, the relays energize for a few seconds.
36
CE Notice
The corresponding LED (DS3 for output #1 and DS10 for output #2) will light.
The multi-meter can be used to check for continuity between the C and NO pins on connectors Relay1 and Relay2.
6. Check the reader interface.
The reader interface can only be tested with the reader chosen for the installation.
Reading a card will cause the display to show “Access Granted” or “Access Denied”, depending upon the clearance of the card.
CE NOTICE This product is in compliance with the CE EMC and Electrical Safety Directives of the European Community when used with the Software House apC or iSTAR products. This unit must be enclosed in a box similar to the units noted in the “Enclosures” on page 28 in order to be in compliance.
37
CE Notice
C•CURE and Software House, are registered trademarks of Tyco International Ltd. and its Respective Companies.
Certain Product names mentioned herein may be trade names and/or registered trademarks of other companies. Information about other products furnished by Software House is believed to be accurate. However, no responsibility is assumed by Software House for the use of these products, or for an infringement of rights of the other companies that may result from their use.
RM-DCM-2 Quick Start Installation GuideDocument Number: UM-215Revision: H0Print Date: March 2018
This manual is proprietary information of Software House. Unauthorized reproduction of any portion of this manual is prohibited. The material in this manual is for information purposes only. It is subject to change without notice. Software House assumes no responsibility for incorrect information this manual may contain.
Copyright ©2007-2018 Tyco International Ltd.
All rights reserved.
38