technical data
SplitSky Air
air cond
itioning
systems
RKS-E2V1B
Het ISO14001 assures an effective environmental management system in order to help protect human health and the environment from potential impact of our activities, products and services and to assist in maintaining and improving the quality of the environment.
Daikin units comply with the European regulations that guarantee the safety of the product.
Daikin Europe N.V. is approved by LRQA for its Quality Management System in accordance with the ISO9001 standard. ISO9001 pertains to quality assurance regarding design, development, manufacturing as well as to services related to the product.
Daikin Europe N.V. participates in the Eurovent Certification Programme for Air Conditioners (AC), Liquid Chilling Packages (LCP) and Fan Coil Units (FC); the certified data of certified models are listed in the Eurovent Directory.
“ The present publication is drawn up by way of informa-tion only and does not constitute an offer binding upon Daikin Europe N.V.. Daikin Europe N.V. has compiled the content of this publication to the best of its knowledge. No express or implied warranty is given for the complete-ness, accuracy, reliability or fitness for particular purpose of its content and the products and services presented therein. Specifications are subject to change without prior notice. Daikin Europe N.V. explicitly rejects any liability for any direct or indirect damage, In the broadest sense, aris-ing from or related to the use and/or interpretation of this publication. All content is copyrighted by Daikin Europe N.V..”
Split - Sky Air
03/2
007
Prin
ted
in B
elgi
um b
y G
oeki
nt G
raph
ics
Copy
right
© D
aiki
n
EEDEN07
Naamloze VennootschapZandvoordestraat 300B-8400 Oostende, Belgiumwww.daikin.euBTW: BE 0412 120 336RPR Oostende
technical data
SplitSky Air
air cond
itioning
systems
RKS-E2V1B
• Split Sky Air • Outdoor Units 4
• Outdoor Units • R-410A • RKS-E2V1B
TABLE OF CONTENTSRKS-E2V1B
1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6Nominal Capacity and Nominal Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3 Electrical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4 Capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15Cooling capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
5 Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . . 21Dimensional drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21Centre of gravity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
6 Piping diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
7 Wiring diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
8 Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25Sound pressure spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
9 Operation range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
• Outdoor Units • R-410A • RKS-E2V1B
11
• Split Sky Air • Outdoor Units5
1 Features
Outdoor Uni Split Sky RKS-E2V1B R-410a • Outdoor units for pair application
• Daikin outdoor units are neat and sturdy and can be mounted easily on a roof or terrace or simply placed against an outside wall.
• Outdoor units are fitted with a swing compressor, renowned for its low noise and high energy efficiency
3
12
• Split Sky Air • Outdoor Units 6
• Outdoor Units • R-410A • RKS-E2V1B
2 Specifications
2-1 NOMINAL CAPACITY AND NOMINAL INPUT RKS20E2V1B RKS25E2V1B RKS35E2V1B
For combination indoor units + outdoor units
Indoor Units FTKS20D3VMW FTKS25D3VMW FTKS35D3VMW
Cooling capacity
Minimum kW 1.2 1.2 1.2Standard kW 2.0 2.5 3.4Maximum kW 2.6 3.0 3.8
Nominal input Cooling Minimum kW 0.30 0.3 0.30Standard kW 0.48 0.6 1.00Maximum kW 0.82 0.8 1.22
For combination indoor units + outdoor units
EER Nominal 4.17 4.17 3.40Energy Labeling Directive
Cooling A A
Annual energy consumption kWh 240 300 500Indoor Units FTKS20D3VML FTKS25D3VML FTKS35DVML
Cooling capacity
Minimum kW 1.2 1.2 1.2Standard kW 2.0 2.5 3.4Maximum kW 2.6 3.0 3.8
Nominal input Cooling Minimum kW 0.30 0.3 0.30Standard kW 0.48 0.6 1.00Maximum kW 0.82 0.8 1.22
For combination indoor units + outdoor units
EER Nominal 4.17 3.40COP Nominal 4.17Energy Labeling Directive
Cooling A A
Annual energy consumption kWh 240 300 500Indoor Units FLKS25BAVMB FDKS35EAVMB
Cooling capacity
Minimum kW 1.2 1.4Standard kW 2.5 3.4Maximum kW 3.0 3.8
Nominal input Cooling Minimum kW 0.30Standard kW 0.65 1.09Maximum kW 0.86
For combination indoor units + outdoor units
EER Nominal 3.85 3.12Energy Labeling Directive
Cooling A B
Annual energy consumption kWh 325 545Indoor Units FDKS25EAVMB FLKS35BAVMB
Cooling capacity
Minimum kW 1.3 1.2Standard kW 2.4 3.5Maximum kW 3.0 3.8
Nominal input Cooling Standard kW 0.69 1.13For combination indoor units + outdoor units
EER Nominal 3.48 3.10Energy Labeling Directive
Cooling A B
Annual energy consumption kWh 345 565Indoor Units FFQ25B8V1B FFQ35B8V1B
Cooling capacity
Standard kW 2.5 3.4
Nominal input Cooling Standard kW 0.73 1.10For combination indoor units + outdoor units
EER Nominal 3.42 3.09Energy Labeling Directive
Cooling A B
Annual energy consumption kWh 365 550Indoor Units FBQ35B8V1
• Outdoor Units • R-410A • RKS-E2V1B
12
• Split Sky Air • Outdoor Units7
2 Specifications
Cooling capacity
Standard kW 3.4
Nominal input Cooling Standard kW 1.17For combination indoor units + outdoor units
EER Nominal 2.91Energy Labeling Directive
Cooling C
Annual energy consumption kWh 585Indoor Units FHQ35BVV1B
Cooling capacity
Minimum kW 1.4Standard kW 3.4Maximum kW 3.7
Nominal input Cooling Standard kW 1.05For combination indoor units + outdoor units
EER Nominal 3.24Energy Labeling Directive
Cooling A
Annual energy consumption kWh 525
2-2 TECHNICAL SPECIFICATIONS RKS20E2V1B RKS25E2V1B RKS35E2V1B
Casing Colour Ivory WhiteDimensions Unit Height mm 550 550 550
Width mm 765 765 765Depth mm 285 285 285
Packing Height mm 589 617 617Width mm 882 882 882Depth mm 363 363 363
Weight Unit kg 30 32 32Packed Unit kg 35 38 38
Heat Exchanger
Dimensions Length mm 828 805 805Nr of Rows 1 2 2Fin Pitch mm 1.4 1.4 1.4Nr of Stages 24 24 24
Tube type Hi-Xa(7)Fin Type Waffle fin
Treatment Anti-corrosion treatment (PE)Fan Type Propeller
Quantity 1 1Air Flow Rate (nominal at 230V)
Cooling m³/min 36.2(H) - 25.7(L) 33.5(H) - 23.4(L) 33.5(H) - 23.4(L)
Motor Quantity 1 1 1Model D238-28
Motor Speed (nominal)
Cooling rpm 860(H) - 620(L) 860(H) - 620(L)
Fan Motor Output W 50 50 50Compressor Quantity 1 1 1
Motor Model 1YC23NXD#CType Hermetically sealed swing compressorMotor Output
W 600 600 600
Operation Range
Cooling Min °CDB -10 -10 -10Max °CDB +46 +46 +46
Sound Level (nominal)
Cooling Sound Power
dBA 61(H) 61(H) 62(H)
Sound Pressure
dBA 46(H) - 43(L) 46(H) - 43(L) 47(H) - 44(L)
Refrigerant Type R-410ACharge kg 0.8 1.0 1.0
2-1 NOMINAL CAPACITY AND NOMINAL INPUT RKS20E2V1B RKS25E2V1B RKS35E2V1B
3
12
• Split Sky Air • Outdoor Units 8
• Outdoor Units • R-410A • RKS-E2V1B
2 Specifications
Refrigerant Oil Type FVC50KCharged Volume l 0.375 0.375 0.375
Piping connections
Liquid (OD) Diameter (OD)
mm 6.35 6.35 6.35
Gas Diameter (OD)
mm 9.5 9.5 9.5
Drain Diameter (OD)
mm 18 18 18
Piping Length Maximum m 20 20 20Chargeless
m 10 10
Additional Refrigerant Charge
kg/m 0.02/>10m
Installation height difference
Maximum m 15 15 15
Heat Insulation Both liquid and gas pipesStandard Accessories
Item Installation manualQuantity 1 1 1
Notes Nominal cooling capacities are based on : indoor temperature : 270CDB, 190CWB, outdoor temperature : 350CDB, equivalent refrigerant piping : 7.5m, level difference : 0m.
2-3 ELECTRICAL SPECIFICATIONS RKS20E2V1B RKS25E2V1B RKS35E2V1B
Power Supply Name V1Phase 1 1 1Frequency Hz 50 50 50Voltage V 220-240
Current Nominal running current (RLA)
Cooling (A)
A 2.44 3.14 4.42
Starting current(cooling/heating)
A 2.8 3.5 4.8
Maximum Running Current A 3.33 4.61Wiring connections
For Power Supply
Quantity 3 3 3
For connection with indoor
Quantity 4 4 4Remark (including earth wiring)
2-2 TECHNICAL SPECIFICATIONS RKS20E2V1B RKS25E2V1B RKS35E2V1B
• Outdoor Units • R-410A • RKS-E2V1B
13
• Split Sky Air • Outdoor Units9
3 Electrical data
Representative unit combination Power supply Comp. OFM IFMIndoor unit Outdoor unit Hz-volts Voltage range MCA MFA RHz RLA W FLA W FLA
FTKS20D3VMW/L RKS20E2V1B50 - 22050 - 23050 - 240
Max. 50Hz 264VMin. 50Hz 198V 9.75 10 40
2.323 0.20 40 0.142.1
2.0
3D055006
SYMBOLSMCA : Min. Circuit Amps (A)MFA : Max. Fuse Amps (A)RHz : Rated operating frequency (Hz)RLA : Rated Load Amps (A)OFM : Outdoor Fan MotorIFM : Indoor Fan MotorFLA : Full Load Amps (A)W : Rated motor output (W)
NOTES1. RLA is based on the following conditions:
Indoor temp.: 27°CDB/19.0°CWBOutdoor temp. : 35°CDB
2. Maximum allowable voltage unbalance between phases is 2%3. Select wire size based on the larger value of MCA.4. Instead of fuse, use circuit breaker.5. For more details concerning conditional connections, see
http://extranet.daikineurope.com, select ’’E-Data Books’’. Finally, click onthe document title of your choice.
Representative unit combination Power supply Comp. OFM IFMIndoor unit Outdoor unit Hz-volts Voltage range MCA MFA RHz RLA W FLA W FLA
FTKS25D3VMW/L RKS25E2V1B50 - 22050 - 23050 - 240
Max. 50Hz 264VMin. 50Hz 198V 9.75 10 48.5
3.023 0.22 40 0.142.8
2.7
3D055008
SYMBOLSMCA : Min. Circuit Amps (A)MFA : Max. Fuse Amps (A)RHz : Rated operating frequency (Hz)RLA : Rated Load Amps (A)OFM : Outdoor Fan MotorIFM : Indoor Fan MotorFLA : Full Load Amps (A)W : Rated motor output (W)
NOTES1. RLA is based on the following conditions:
Indoor temp.: 27°CDB/19.0°CWBOutdoor temp. : 35°CDB
2. Maximum allowable voltage unbalance between phases is 2%3. Select wire size based on the larger value of MCA.4. Instead of fuse, use circuit breaker.5. For more details concerning conditional connections, see
http://extranet.daikineurope.com, select ’’E-Data Books’’. Finally, click onthe document title of your choice.
3
13
• Split Sky Air • Outdoor Units 10
• Outdoor Units • R-410A • RKS-E2V1B
3 Electrical data
Representative unit combination Power supply Comp. OFM IFMIndoor unit Outdoor unit Hz-volts Voltage range MCA MFA RHz RLA W FLA W FLA
FLKS25BAVMB RKS25E2V1B50 - 22050 - 23050 - 240
Max. 50Hz 264VMin. 50Hz 198V 9.75 10 50
3.223 0.16 34 0.343.1
2.9
3D055010B
SYMBOLSMCA : Min. Circuit Amps (A)MFA : Max. Fuse Amps (A)RHz : Rated operating frequency (Hz)RLA : Rated Load Amps (A)OFM : Outdoor Fan MotorIFM : Indoor Fan MotorFLA : Full Load Amps (A)W : Rated motor output (W)
NOTES1. RLA is based on the following conditions:
Indoor temp.: 27°CDB/19.0°CWBOutdoor temp. : 35°CDB
2. Maximum allowable voltage unbalance between phases is 2%3. Select wire size based on the larger value of MCA.4. Instead of fuse, use circuit breaker.5. For more details concerning conditional connections, see
http://extranet.daikineurope.com, select ’’E-Data Books’’. Finally, click onthe document title of your choice.
Representative unit combination Power supply Comp. OFM IFMIndoor unit Outdoor unit Hz-volts Voltage range MCA MFA RHz RLA W FLA W FLA
FDKS25EAVMB RKS25E2V1B50 - 22050 - 23050 - 240
Max. 50Hz 264VMin. 50Hz 198V 9.75 10 54.5
3.523 0.16 62 0.53.3
3.2
3D055010B
SYMBOLSMCA : Min. Circuit Amps (A)MFA : Max. Fuse Amps (A)RHz : Rated operating frequency (Hz)RLA : Rated Load Amps (A)OFM : Outdoor Fan MotorIFM : Indoor Fan MotorFLA : Full Load Amps (A)W : Rated motor output (W)
NOTES1. RLA is based on the following conditions:
Indoor temp.: 27°CDB/19.0°CWBOutdoor temp. : 35°CDB
2. Maximum allowable voltage unbalance between phases is 2%3. Select wire size based on the larger value of MCA.4. Instead of fuse, use circuit breaker.5. For more details concerning conditional connections, see
http://extranet.daikineurope.com, select ’’E-Data Books’’. Finally, click onthe document title of your choice.
• Outdoor Units • R-410A • RKS-E2V1B
13
• Split Sky Air • Outdoor Units11
3 Electrical data
Representative unit combination Power supply Comp. OFM IFMIndoor unit Outdoor unit Hz-volts Voltage range MCA MFA RHz RLA W FLA W FLA
FFQ25B8V1B RKS25E2V1B50 - 22050 - 23050 - 240
Max. 50Hz 264VMin. 50Hz 198V 9.75 10 55
3.723 0.16 55 0.63.5
3.4
3D055010B
SYMBOLSMCA : Min. Circuit Amps (A)MFA : Max. Fuse Amps (A)RHz : Rated operating frequency (Hz)RLA : Rated Load Amps (A)OFM : Outdoor Fan MotorIFM : Indoor Fan MotorFLA : Full Load Amps (A)W : Rated motor output (W)
NOTES1. RLA is based on the following conditions:
Indoor temp.: 27°CDB/19.0°CWBOutdoor temp. : 35°CDB
2. Maximum allowable voltage unbalance between phases is 2%3. Select wire size based on the larger value of MCA.4. Instead of fuse, use circuit breaker.5. For more details concerning conditional connections, see
http://extranet.daikineurope.com, select ’’E-Data Books’’. Finally, click onthe document title of your choice.
Representative unit combination Power supply Comp. OFM IFMIndoor unit Outdoor unit Hz-volts Voltage range MCA MFA RHz RLA W FLA W FLA
FTKS35D3VMW/L RKS35E2V1B50 - 22050 - 23050 - 240
Max. 50Hz 264VMin. 50Hz 198V 9.75 10 75
4.323 0.22 40 0.144.1
3.9
3D055009
SYMBOLSMCA : Min. Circuit Amps (A)MFA : Max. Fuse Amps (A)RHz : Rated operating frequency (Hz)RLA : Rated Load Amps (A)OFM : Outdoor Fan MotorIFM : Indoor Fan MotorFLA : Full Load Amps (A)W : Rated motor output (W)
NOTES1. RLA is based on the following conditions:
Indoor temp.: 27°CDB/19.0°CWBOutdoor temp. : 35°CDB
2. Maximum allowable voltage unbalance between phases is 2%3. Select wire size based on the larger value of MCA.4. Instead of fuse, use circuit breaker.5. For more details concerning conditional connections, see
http://extranet.daikineurope.com, select ’’E-Data Books’’. Finally, click onthe document title of your choice.
3
13
• Split Sky Air • Outdoor Units 12
• Outdoor Units • R-410A • RKS-E2V1B
3 Electrical data
Representative unit combination Power supply Comp. OFM IFMIndoor unit Outdoor unit Hz-volts Voltage range MCA MFA RHz RLA W FLA W FLA
FLKS35BAVMB RKS35E2V1B50 - 22050 - 23050 - 240
Max. 50Hz 264VMin. 50Hz 198V 9.75 10 82
4.823 0.22 34 0.384.6
4.4
3D055011B
SYMBOLSMCA : Min. Circuit Amps (A)MFA : Max. Fuse Amps (A)RHz : Rated operating frequency (Hz)RLA : Rated Load Amps (A)OFM : Outdoor Fan MotorIFM : Indoor Fan MotorFLA : Full Load Amps (A)W : Rated motor output (W)
NOTES1. RLA is based on the following conditions:
Indoor temp.: 27°CDB/19.0°CWBOutdoor temp. : 35°CDB
2. Maximum allowable voltage unbalance between phases is 2%3. Select wire size based on the larger value of MCA.4. Instead of fuse, use circuit breaker.5. For more details concerning conditional connections, see
http://extranet.daikineurope.com, select ’’E-Data Books’’. Finally, click onthe document title of your choice.
Representative unit combination Power supply Comp. OFM IFMIndoor unit Outdoor unit Hz-volts Voltage range MCA MFA RHz RLA W FLA W FLA
FDKS35EAVMB RKS35E2V1B50 - 22050 - 23050 - 240
Max. 50Hz 264VMin. 50Hz 198V 9.75 10 78
4.723 0.22 62 0.54.5
4.3
3D055011B
SYMBOLSMCA : Min. Circuit Amps (A)MFA : Max. Fuse Amps (A)RHz : Rated operating frequency (Hz)RLA : Rated Load Amps (A)OFM : Outdoor Fan MotorIFM : Indoor Fan MotorFLA : Full Load Amps (A)W : Rated motor output (W)
NOTES1. RLA is based on the following conditions:
Indoor temp.: 27°CDB/19.0°CWBOutdoor temp. : 35°CDB
2. Maximum allowable voltage unbalance between phases is 2%3. Select wire size based on the larger value of MCA.4. Instead of fuse, use circuit breaker.5. For more details concerning conditional connections, see
http://extranet.daikineurope.com, select ’’E-Data Books’’. Finally, click onthe document title of your choice.
• Outdoor Units • R-410A • RKS-E2V1B
13
• Split Sky Air • Outdoor Units13
3 Electrical data
Representative unit combination Power supply Comp. OFM IFMIndoor unit Outdoor unit Hz-volts Voltage range MCA MFA RHz RLA W FLA W FLA
FBQ35B8V1 RKS35E2V1B50 - 22050 - 23050 - 240
Max. 50Hz 264VMin. 50Hz 198V 9.75 10 80
5.123 0.16 65 0.54.9
4.7
3D055011B
SYMBOLSMCA : Min. Circuit Amps (A)MFA : Max. Fuse Amps (A)RHz : Rated operating frequency (Hz)RLA : Rated Load Amps (A)OFM : Outdoor Fan MotorIFM : Indoor Fan MotorFLA : Full Load Amps (A)W : Rated motor output (W)
NOTES1. RLA is based on the following conditions:
Indoor temp.: 27°CDB/19.0°CWBOutdoor temp. : 35°CDB
2. Maximum allowable voltage unbalance between phases is 2%3. Select wire size based on the larger value of MCA.4. Instead of fuse, use circuit breaker.5. For more details concerning conditional connections, see
http://extranet.daikineurope.com, select ’’E-Data Books’’. Finally, click onthe document title of your choice.
Representative unit combination Power supply Comp. OFM IFMIndoor unit Outdoor unit Hz-volts Voltage range MCA MFA RHz RLA W FLA W FLA
FCQ35B8V1 RKS35E2V1B50 - 22050 - 23050 - 240
Max. 50Hz 264VMin. 50Hz 198V 9.75 10 78
4.823 0.16 45 0.64.5
4.3
3D055011B
SYMBOLSMCA : Min. Circuit Amps (A)MFA : Max. Fuse Amps (A)RHz : Rated operating frequency (Hz)RLA : Rated Load Amps (A)OFM : Outdoor Fan MotorIFM : Indoor Fan MotorFLA : Full Load Amps (A)W : Rated motor output (W)
NOTES1. RLA is based on the following conditions:
Indoor temp.: 27°CDB/19.0°CWBOutdoor temp. : 35°CDB
2. Maximum allowable voltage unbalance between phases is 2%3. Select wire size based on the larger value of MCA.4. Instead of fuse, use circuit breaker.5. For more details concerning conditional connections, see
http://extranet.daikineurope.com, select ’’E-Data Books’’. Finally, click onthe document title of your choice.
3
13
• Split Sky Air • Outdoor Units 14
• Outdoor Units • R-410A • RKS-E2V1B
3 Electrical data
Representative unit combination Power supply Comp. OFM IFMIndoor unit Outdoor unit Hz-volts Voltage range MCA MFA RHz RLA W FLA W FLA
FFQ35B8V1B RKS35E2V1B50 - 22050 - 23050 - 240
Max. 50Hz 264VMin. 50Hz 198V 9.75 10 79
4.823 0.16 55 0.64.6
4.4
3D055011B
SYMBOLSMCA : Min. Circuit Amps (A)MFA : Max. Fuse Amps (A)RHz : Rated operating frequency (Hz)RLA : Rated Load Amps (A)OFM : Outdoor Fan MotorIFM : Indoor Fan MotorFLA : Full Load Amps (A)W : Rated motor output (W)
NOTES1. RLA is based on the following conditions:
Indoor temp.: 27°CDB/19.0°CWBOutdoor temp. : 35°CDB
2. Maximum allowable voltage unbalance between phases is 2%3. Select wire size based on the larger value of MCA.4. Instead of fuse, use circuit breaker.5. For more details concerning conditional connections, see
http://extranet.daikineurope.com, select ’’E-Data Books’’. Finally, click onthe document title of your choice.
Representative unit combination Power supply Comp. OFM IFMIndoor unit Outdoor unit Hz-volts Voltage range MCA MFA RHz RLA W FLA W FLA
FHQ35BVV1B RKS35E2V1B50 - 22050 - 23050 - 240
Max. 50Hz 264VMin. 50Hz 198V 9.75 10 76
4.523 0.22 62 0.64.3
4.1
3D055011B
SYMBOLSMCA : Min. Circuit Amps (A)MFA : Max. Fuse Amps (A)RHz : Rated operating frequency (Hz)RLA : Rated Load Amps (A)OFM : Outdoor Fan MotorIFM : Indoor Fan MotorFLA : Full Load Amps (A)W : Rated motor output (W)
NOTES1. RLA is based on the following conditions:
Indoor temp.: 27°CDB/19.0°CWBOutdoor temp. : 35°CDB
2. Maximum allowable voltage unbalance between phases is 2%3. Select wire size based on the larger value of MCA.4. Instead of fuse, use circuit breaker.5. For more details concerning conditional connections, see
http://extranet.daikineurope.com, select ’’E-Data Books’’. Finally, click onthe document title of your choice.
• Outdoor Units • R-410A • RKS-E2V1B
14
• Split Sky Air • Outdoor Units15
4 Capacity tables4 - 1 Cooling capacity tablesFTKS20D3VMW/L+RKS20E2V1B
Cooling 220-240V [50Hz]
AFR 8.7BF 0.21
Indoor Outdoor temperature (°CDB)EWB EDB 20 25 30 32 35 40(°C) (°C) TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
3D055186
SYMBOLSAFR: Air flow rate (m3/min)BF: Bypass factorEWB: Entering wet bulb temp. (°C)EDB: Entering dry bulb temp. (°C)TC: Total capacity (kW)SHC: Sensible heating capacity (kW)PI: Power input (kW)
NOTES1. Capacities are based on the following conditions:
(1) Corresponding refrigerant piping length: 7.5 m(2) Level difference: 0 m
2. shows nominal (rated) capacities and power input.
FTKS25D3VMW/L+RKS25E2V1B
Cooling 220-240V [50Hz]
AFR 8.7BF 0.24
Indoor Outdoor temperature (°CDB)EWB EDB 20 25 30 32 35 40(°C) (°C) TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
3D055187
SYMBOLSAFR: Air flow rate (m3/min)BF: Bypass factorEWB: Entering wet bulb temp. (°C)EDB: Entering dry bulb temp. (°C)TC: Total capacity (kW)SHC: Sensible heating capacity (kW)PI: Power input (kW)
NOTES1. Capacities are based on the following conditions:
(1) Corresponding refrigerant piping length: 7.5 m(2) Level difference: 0 m
2. shows nominal (rated) capacities and power input.
3
14
• Split Sky Air • Outdoor Units 16
• Outdoor Units • R-410A • RKS-E2V1B
4 Capacity tables4 - 1 Cooling capacity tablesFLKS25BAVMB+RKS25E2V1B
Cooling 220-240V [50Hz]
AFR 7.6BF 0.32
Indoor Outdoor temperature (°CDB)EWB EDB 20 25 30 32 35 40(°C) (°C) TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
3D055191
SYMBOLSAFR: Air flow rate (m3/min)BF: Bypass factorEWB: Entering wet bulb temp. (°C)EDB: Entering dry bulb temp. (°C)TC: Total capacity (kW)SHC: Sensible heating capacity (kW)PI: Power input (kW)
NOTES1. Capacities are based on the following conditions:
(1) Corresponding refrigerant piping length: 7.5 m(2) Level difference: 0 m
2. shows nominal (rated) capacities and power input.
FDKS25EAVMB+RKS25E2V1B
Cooling 220-240V [50Hz]
AFR 8.7BF 0.17
Indoor Outdoor temperature (°CDB)EWB EDB 20 25 30 32 35 40(°C) (°C) TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
3D055193
SYMBOLSAFR: Air flow rate (m3/min)BF: Bypass factorEWB: Entering wet bulb temp. (°C)EDB: Entering dry bulb temp. (°C)TC: Total capacity (kW)SHC: Sensible heating capacity (kW)PI: Power input (kW)
NOTES1. Capacities are based on the following conditions:
(1) Corresponding refrigerant piping length: 7.5 m(2) Level difference: 0 m
2. shows nominal (rated) capacities and power input.
• Outdoor Units • R-410A • RKS-E2V1B
14
• Split Sky Air • Outdoor Units17
4 Capacity tables4 - 1 Cooling capacity tablesFFQ25B8V1B+RKS25E2V1B
Cooling 220-240V [50Hz]
AFR 9BF 0.24
Indoor Outdoor temperature (°CDB)EWB EDB 20 25 30 32 35 40(°C) (°C) TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
3D055488
SYMBOLSAFR: Air flow rate (m3/min)BF: Bypass factorEWB: Entering wet bulb temp. (°C)EDB: Entering dry bulb temp. (°C)TC: Total capacity (kW)SHC: Sensible heating capacity (kW)PI: Power input (kW)
NOTES1. Capacities are based on the following conditions:
(1) Corresponding refrigerant piping length: 7.5 m(2) Level difference: 0 m
2. shows nominal (rated) capacities and power input.
FTKS35D3VMW/L+RKS35E2V1B
Cooling 220-240V [50Hz]
AFR 8.9BF 0.24
Indoor Outdoor temperature (°CDB)EWB EDB 20 25 30 32 35 40(°C) (°C) TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
3D055188
SYMBOLSAFR: Air flow rate (m3/min)BF: Bypass factorEWB: Entering wet bulb temp. (°C)EDB: Entering dry bulb temp. (°C)TC: Total capacity (kW)SHC: Sensible heating capacity (kW)PI: Power input (kW)
NOTES1. Capacities are based on the following conditions:
(1) Corresponding refrigerant piping length: 7.5 m(2) Level difference: 0 m
2. shows nominal (rated) capacities and power input.
3
14
• Split Sky Air • Outdoor Units 18
• Outdoor Units • R-410A • RKS-E2V1B
4 Capacity tables4 - 1 Cooling capacity tablesFLKS35BAVMB+RKS35E2V1B
Cooling 220-240V [50Hz]
AFR 8.6BF 0.35
Indoor Outdoor temperature (°CDB)EWB EDB 20 25 30 32 35 40(°C) (°C) TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
3D055192
SYMBOLSAFR: Air flow rate (m3/min)BF: Bypass factorEWB: Entering wet bulb temp. (°C)EDB: Entering dry bulb temp. (°C)TC: Total capacity (kW)SHC: Sensible heating capacity (kW)PI: Power input (kW)
NOTES1. Capacities are based on the following conditions:
(1) Corresponding refrigerant piping length: 7.5 m(2) Level difference: 0 m
2. shows nominal (rated) capacities and power input.
FDKS35EAVMB+RKS35E2V1B
Cooling 220-240V [50Hz]
AFR 8.7BF 0.17
Indoor Outdoor temperature (°CDB)EWB EDB 20 25 30 32 35 40(°C) (°C) TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
3D055194
SYMBOLSAFR: Air flow rate (m3/min)BF: Bypass factorEWB: Entering wet bulb temp. (°C)EDB: Entering dry bulb temp. (°C)TC: Total capacity (kW)SHC: Sensible heating capacity (kW)PI: Power input (kW)
NOTES1. Capacities are based on the following conditions:
(1) Corresponding refrigerant piping length: 7.5 m(2) Level difference: 0 m
2. shows nominal (rated) capacities and power input.
• Outdoor Units • R-410A • RKS-E2V1B
14
• Split Sky Air • Outdoor Units19
4 Capacity tables4 - 1 Cooling capacity tablesFBQ35B8V1+RKS35E2V1B
Cooling 220-240V [50Hz]
AFR 11.5BF 0.15
Indoor Outdoor temperature (°CDB)EWB EDB 20 25 30 32 35 40(°C) (°C) TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
3D055494
SYMBOLSAFR: Air flow rate (m3/min)BF: Bypass factorEWB: Entering wet bulb temp. (°C)EDB: Entering dry bulb temp. (°C)TC: Total capacity (kW)SHC: Sensible heating capacity (kW)PI: Power input (kW)
NOTES1. Capacities are based on the following conditions:
(1) Corresponding refrigerant piping length: 7.5 m(2) Level difference: 0 m
2. shows nominal (rated) capacities and power input.
FCQ35B8V1+RKS35E2V1B
Cooling 220-240V [50Hz]
AFR 14BF 0.16
Indoor Outdoor temperature (°CDB)EWB EDB 20 25 30 32 35 40(°C) (°C) TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
3D055492
SYMBOLSAFR: Air flow rate (m3/min)BF: Bypass factorEWB: Entering wet bulb temp. (°C)EDB: Entering dry bulb temp. (°C)TC: Total capacity (kW)SHC: Sensible heating capacity (kW)PI: Power input (kW)
NOTES1. Capacities are based on the following conditions:
(1) Corresponding refrigerant piping length: 7.5 m(2) Level difference: 0 m
2. shows nominal (rated) capacities and power input.
3
14
• Split Sky Air • Outdoor Units 20
• Outdoor Units • R-410A • RKS-E2V1B
4 Capacity tables4 - 1 Cooling capacity tablesFFQ35B8V1B+RKS35E2V1B
Cooling 220-240V [50Hz]
AFR 10BF 0.25
Indoor Outdoor temperature (°CDB)EWB EDB 20 25 30 32 35 40(°C) (°C) TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
3D055490
SYMBOLSAFR: Air flow rate (m3/min)BF: Bypass factorEWB: Entering wet bulb temp. (°C)EDB: Entering dry bulb temp. (°C)TC: Total capacity (kW)SHC: Sensible heating capacity (kW)PI: Power input (kW)
NOTES1. Capacities are based on the following conditions:
(1) Corresponding refrigerant piping length: 7.5 m(2) Level difference: 0 m
2. shows nominal (rated) capacities and power input.
FHQ35BVV1B+RKS35E2V1B
Cooling 220-240V [50Hz]
AFR 13BF 0.20
Indoor Outdoor temperature (°CDB)EWB EDB 20 25 30 32 35 40(°C) (°C) TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
3D055197
SYMBOLSAFR: Air flow rate (m3/min)BF: Bypass factorEWB: Entering wet bulb temp. (°C)EDB: Entering dry bulb temp. (°C)TC: Total capacity (kW)SHC: Sensible heating capacity (kW)PI: Power input (kW)
NOTES1. Capacities are based on the following conditions:
(1) Corresponding refrigerant piping length: 7.5 m(2) Level difference: 0 m
2. shows nominal (rated) capacities and power input.
• Outdoor Units • R-410A • RKS-E2V1B
15
• Split Sky Air • Outdoor Units21
5 Dimensional drawing & centre of gravity5 - 1 Dimensional drawing
3D041800H
RKS20-35E2V1B unit (mm)
Minimum space for air passageWall height on air outlet side = less
than 1200Drain outlet
(I.D. J 15.9 hose for connection)
Handle
Wiring inlet
Gas stop valve(J 12.7 CuT)
Liquid stop valve(J 6.4 CuT)
Service port
Outdoor air thermistor
Brand name label
4 x holes for anchor bolts (M8or M10)
Name plate
In case of removingstop valve cover
3
15
• Split Sky Air • Outdoor Units 22
• Outdoor Units • R-410A • RKS-E2V1B
5 Dimensional drawing & centre of gravity5 - 2 Centre of gravity
4D044107M
RKS20-35E2V1B
• Outdoor Units • R-410A • RKS-E2V1B
16
• Split Sky Air • Outdoor Units23
6 Piping diagram
3D047317C
RKS20E2V1B
Outdoor temperature thermistorHeat exchanger
Propeller fan
Liquid stopvalve
Field piping
Field piping
Gas stopvalve
Compressor
Refrigerant flow
Cooling
Discharge pipethermistor
Heat exchangerthermistor
Muffler withfilter
Motor operated valve
Muffler withfilter
Outdoor unit
Muffler
Muffler
Four way valvenormally: OFF
Accumulator
Muffler withfilter
3D047318D
RKS25-35E2V1B
Outdoor temperature thermistorHeat exchanger
Propeller fan
Liquid stopvalve
Field piping
Field piping
Gas stopvalve
Compressor
Refrigerant flow
Cooling
Discharge pipethermistor
Heat exchangerthermistor
Muffler withfilter
Motor operatedvalve
Muffler withfilter
Outdoor unit
Muffler
Muffler
Four way valvenormally: OFF
Accumulator
Muffler withfilter
3
17
• Split Sky Air • Outdoor Units 24
• Outdoor Units • R-410A • RKS-E2V1B
7 Wiring diagram7 - 1 Wiring diagram
3D041707H
RKS20-35E2V1B
R : Protective earthC74,C75C94,C95,C100 : CapacitorDB1,DB2 : Diode bridgeFU1,FU2,FU3 : FuseIC11 : Solid state relayIPM1 : TriacL : LiveL1 : CoilL1R : ReactorM1C : Compressor motorM1F : Fan motorMRCW,MRM10,MRM20 : Magnetic relay
N : NeutralPCB1,PCB2 : Printed circuit boardQ1L : Overload protectorR1T,R2T,R3T,R12T : ThermistorS10,S11,S20S30,S40,S70S80,S90,S91HC3,HC4,HL3,HN3: Connector
gField wiringIndoor
Outdoor
(outdoor)(Condenser)
(discharge)
SA1 : Surge arresterV1,V2,V3 : VaristorX1M : Terminal stripY1E : Electronic expansion valve coilY1R : Reversing solenoide valve coilZ1C,Z2C : Ferrite core
In case of coolingonly type
In case of heatpump type
NOTE1. Refer to the nameplate for the power requirements.
• Outdoor Units • R-410A • RKS-E2V1B
18
• Split Sky Air • Outdoor Units25
8 Sound data8 - 1 Sound pressure spectrum
4D053221B
Oct
ave
band
soun
dpr
essu
rele
vel
Octave band center frequency (Hz)
RKS20-25E2V1B
approximatethreshold hearing for
continuous noise
NOTES1 Measure in anechoic room2 Operation noise differs with operation and
ambient conditions.3 The operation noise measuring method is in
accordance with JISC9612
Legend
50Hz, 220-240V
Location of microphone
4D053222B
Oct
ave
band
soun
dpr
essu
rele
vel
Octave band center frequency (Hz)
RKS35E2V1B
approximatethreshold hearing for
continuous noise
NOTES1 Measure in anechoic room2 Operation noise differs with operation and
ambient conditions.3 The operation noise measuring method is in
accordance with JISC9612
Legend
50Hz, 220-240V
Location of microphone
3
19
• Split Sky Air • Outdoor Units 26
• Outdoor Units • R-410A • RKS-E2V1B
9 Operation range
4D029297Q
RKS20-35E2V1B
Out
door
tem
p.(°
CDB)
Cont
inuo
usop
erat
ion
Pull-
dow
npe
riod
Indoor temp. (°CWB)
Notes:The graph is based on the following conditions:1. Equivalent piping length 7.5 m2. Level difference 0 m3. Air flow rate high
• Outdoor Units • R-410A • RKS-E2V1B
19
• Split Sky Air • Outdoor Units27
9 Operation range