Rigid PVCConduitPipe & FittingsA system for residential, industrial, commercial and institutional applications.
Product Description - Features and Benefits 1
Installation Guidelines - Solvent Welding Joints 2
Solvent Welding Joints/Pipe Dimensions/Specs 3
Solvent Cementing 4
Expansion and Contraction 5
Setting the Piston Opening 6
Fittings - Bends (Bell End) 7-8
Fittings - Miscellaneous 9-18
Table ofContents
Note: This brochure is not intended to assume the authority of the Design Engineer. Actual jobsite conditions will vary significantly. The sole responsibility for all design and installation decisions lies with the Design Engineer. All local health and safety regulations must be followed.
1
Product Description & ApplicationsRoyal Building Products® Electrical Solutions manufactures a complete line of Rigid PVC Conduit pipe and fittings for electrical applications. Our products are designed to reduce labour and maintenance costs, while offering superior performance.
Products are certified by the Canadian Standards Association (CSA) and Underwriters Laboratories (UL) for use in above and below ground applications. Our Rigid PVC conduit pipe and fittings are available in 12 to 150mm (½- to 6-inch) diameters and 3- or 6-metre (10- or 20-foot) lengths.
Standards and Codes Royal Electrical Solutions Rigid PVC Conduit pipe and fittings are certified to CSA Standards as noted below. Our Rigid PVC conduit pipe and fittings shall be installed according to the Canadian Electrical Code (CEC) Part I, Rules 12-1100 - 12-1122 and the National Electrical Code (NEC) Article 352.
Features and BenefitsSaves Labour Rigid PVC Conduit pipe and fittings are easy to install, cut and join.
Easy Wire PullsThe conduit’s smooth interior surface reduces friction and prevents damage to wires when pulling wire and conductors for long runs and even through 90° bends.
Lightweight MaterialsRigid PVC Conduit is easier to move and handle because it is approximately one-fifth the weight of steel and half the weight of aluminum.
Simplifies Direct Burial Royal Electrical Solutions Rigid PVC Conduit does not require additional protection for direct burial installations according to the Canadian Electrical Code (CEC) and the National Electrical Code (NEC). Normal construction practices should be followed for trenching and backfill operations.
Non-Conductive Rigid PVC Conduit is non-conductive.
Long LifeRoyal Rigid PVC Conduit and fittings resist acids, alkalis, salt solutions and most other chemicals. (Refer to the Royal Chemical Resistance Guide for detailed information.) There is no risk of corrosion when exposed to naturally corrosive soil conditions, electrochemical or galvanic environments. Royal’s Rigid PVC Conduit has achieved sunlight resistance as per the requirements of the Electrical Code.
FT-4 Rating Rigid PVC Conduit pipe has an FT-4 Rating and can be used in non-combustible construction as per Part 3 of the National Building Code of Canada (NBC).
Rigid PVCConduitPipe & FittingsA system for residential, industrial, commercial and institutional applications.
C22.2 No. 211.2 UL 651
Pipe Fittings
C22.2 No. 18.2, 85 (Boxes) No. 40 (Electrical Encl.)No. 42.1 (Covers)No. 85 (Fittings)
UL 514C (Boxes)UL 50 (Electrical Encl.)UL 514D (Covers)UL 651 (Fittings)
Conforms to NEMA TC2
Sizemm (in)
PVClb/100ft (kg/m)
Aluminumlb/100ft (kg/m)
Steellb/100ft (kg/m)
12 (½)19 (¾)25 (1)32 (1¼)38 (1½)50 (2)63 (2½)75 (3)90 (3½)100 (4)125 (5)150 (6)
16.1 (0.24)21.5 (0.32)31.9 (0.47)43.8 (0.65)52.3 (0.78)70.3 (1.05)
112.0 (1.61)146.7 (2.18)176.4 (2.63)208.9 (3.11)283.4 (4.22)368.0 (5.48)
27 (0.40)37 (0.55)53 (0.80)70 (1.05)86 (1.30)
116 (1.75)183 (2.75)239 (3.55)288 (4.30)340 (5.10)465 (6.90)613 (9.10)
79 (1.20)105 (1.55)153 (2.30)201 (3.00)249 (3.70)334 (5.00)527 (7.85)
690 (10.25)831 (12.40)982 (14.60)
1,344 (20.40)1,771 (26.35)
Approximate Weight Comparison
2
Procedure for Solvent Welding Joints• Use solvent cement and primer prior to expiration date marked on container.• Above 0° C ambient temperature, joints may be assembled without the use of primer, provided adequate penetration and softening of the pipe/fitting surface can be achieved with solvent cement alone.
1. Assemble materials for the job, including correct solvent cement, primer and correctly sized applicator.
2. Cut pipe as square as possible using a hand saw and miter box or mechanical saw. Do not use a diagonal cut, as it reduces the bonding area in the joint.
3. If plastic tubing cutters are used, care must be taken to remove any raised bead at the end of the pipe, caused by cutting. A file or reamer may be used to remove the bead.
4. Use a knife, file or reamer to remove burrs from the inside and outside of the pipe end, as these will hinder the integrity of the joint. All sharp edges should be removed from the inside and outside edges of the pipe to prevent the pipe from pushing the solvent cement into the fitting socket, thereby causing a weak spot to form. The pipe end should be chamfered, as shown below.
Nominal Sizemm (in)
Min. Radius to Centre of Conduit or Tubingmm (in)
16 (½)21 (¾)27 (1)35 (1¼)41 (1½)53 (2)63 (2½)78 (3)91 (3½)103 (4)129 (5)155 (6)
102 (4.016)114 (4.489)146 (5.748)184 (7.244)210 (8.268)241 (9.488)267 (10.512)330 (12.992)381 (14.606)406 (15.984)610 (24.016)762 (30.000)
Installation Guidelines
CuttingRoyal Rigid PVC Conduit can easily be cut with a hacksaw, a fine-toothed handsaw or PVC conduit cutters. For conduit with more than a 50mm (2-inch) diameter, use a mitre box or saw guide to ensure a square cut. Deburr the end using a knife or file.
BendingIt may be necessary to create bends in the field by heating and deforming Rigid PVC Conduit. To accomplish this, the following guidelines should be followed:
• For heating the Rigid PVC Conduit, use a heat gun or some other flameless heat source. Do not use an open flame to heat the conduit. Rigid PVC Conduit must be heated to approximately 127˚C (260˚F) in order to bend without kinking.
• Heat a length of conduit equal to approximately 10 times the nominal diameter.
• Once the Rigid PVC Conduit has been adequately heated, bend it to the required angle plus 3 extra degrees. The additional angle will accommodate the “spring back” which will occur during cooling.
• After bending of the conduit is completed, immediately cool the bend using water or cold air.
• According to the Canadian Electrical Code (CEC) and the National Electrical Code (NEC), the minimum bending radius for rigid conduit is as shown in the table below.
Chamfered Pipe
10° - 15°
3
Procedure for Solvent Welding Joints Continued
5. All dirt, grease and moisture should be removed from the pipe and socket by thoroughly wiping with a clean, dry cloth.
6. Dry fit pipe and fitting joints prior to cementing. For proper interference fit, the pipe should go easily into the socket approximately ⅓ to ⅔ of the socket depth. If this is not the case, other pipe or fittings should be used.
7. The applicator should be sized according to the size of pipe and fittings being joined. The brush width of the applicator should be equal to approximately ½ of the pipe diameter.
8. Primer is used to penetrate and soften the surfaces so that they will fuse together under a wide variety of conditions. The penetration or softening can be checked by dragging the edge of a knife or sharp object over the coated surface. If a few thousandths of an inch of the primed surface can be scratched or scraped away, proper penetration has occurred. Varying weather conditions affect priming and cementing action and may require more time or repeated applications to either or both surfaces.
9. If using primer, use the correct applicator size (see #7) and aggressively work the primer into the socket, keeping the surface and applicator wet until the surface has softened, re-dipping the applicator as required. When the surface is primed, remove any puddles of primer from the socket.
10. Aggressively work the primer on to the end of the pipe, to a point ½” beyond the depth of the socket.
11. Perform a second application of primer in the socket.
12. While the surfaces are still wet, the appropriate solvent cement should be applied.
13. Using the correct applicator size, aggressively work a full, even layer of cement onto the pipe end to a point equal to the depth of the socket. Do not brush out to a thin paint type layer, as this will dry within a few seconds.
14. Aggressively work a medium layer of cement into the fitting socket; avoid puddling cement in the socket. On the pipe end, do not coat beyond the socket depth or allow cement to run down into the pipe beyond the socket.
15. Apply a second full, even layer of cement on the pipe.
16. Immediately, while the cement is still wet, assemble the joint. Use enough force to ensure that the pipe is fully inserted into the
socket. Twist the pipe a ¼ turn as it is being inserted.
17. Hold the joint together for approximately 30 seconds to avoid push out.
18. After assembly, inspect the joint to ensure that there is a ring or bead of cement completely around the juncture of the pipe and socket. If there are voids in this ring, sufficient cement was not applied and the joint may be defective.
19. Remove the excess cement from the pipe and socket (including the ring or bead) using a cloth. Avoid disturbing or moving the joint.
20. Handle newly cemented joints with care until initial set has taken place. Follow set and cure times before handling or testing the system.
Pipe Dimensions
Specification All wiring shall be installed in Royal Electrical Solutions Rigid PVC Conduit and secured with proper fittings. All conduit and fittings shall be manufactured by Royal Building Products, Pipe & Fittings Solutions. All outlets, pull boxes and junction points shall be Royal products.
Exposed conduit shall be securely attached and supported with straps that are installed at the recommended spacing specified in CEC Section 12-1114. The straps must allow for linear expansion and contraction of the conduit due to temperature change. If the variance in temperature exceeds 14°C (25°F), expansion joints shall be installed according to the manufacturer’s recommendations.
If Rigid PVC Conduit is embedded in concrete or direct buried, support straps are not required.
NominalSize
mm (in)
Avg. OutsideDiametermm (in)
12 (½)19 (¾)25 (1)
32 (1¼)38 (1½)
50 (2)63 (2½)
75 (3)90 (3½)100 (4)125 (5)150 (6)
21 (0.840)27 (1.050)33 (1.315)42 (1.660)48 (1.900)60 (2.375)73 (2.875)89 (3.500)
102 (4.000)114 (4.500)141 (5.565)168 (6.625)
Avg. InsideDiametermm (in)
15 (0.608)21 (0.810)26 (1.033)35 (1.362)40 (1.592)52 (2.049)62 (2.445)77 (3.042)89 (3.520)
102 (3.998)127 (5.017)153 (6.031)
Avg. WallThicknessmm (in)
3 (0.116)3 (0.120)4 (0.141)4 (0.149)4 (0.154)4 (0.163)5 (0.215)6 (0.229)6 (0.240)6 (0.251)7 (0.274)8 (0.297)
Approx. Weightlb/100ft (kg/m)
16.1 (0.24)21.5 (0.32)31.9 (0.47)43.8 (0.65)52.3 (0.78)70.3 (1.05)
112.0 (1.61)146.7 (2.18)176.4 (2.63)208.9 (3.11)283.4 (4.22)368.0 (5.48)
4
Solvent CementingAll connections should be made using and applying Royal Electrical Solutions solvent cement.
Set Times
Joint Cure Schedule
In damp or humid weather allow 50% more cure time.
Estimated Solvent Cement Requirements
Estimated Primer Requirements
Solvent Cementing in Cold Weather:• Store pipe and fittings in a heated area. Prefabricate as much of the system as possible in a heated area.• When not in use, store sealed solvent cement and primer between 5°C and 21°C. Do not use open flame or electric heaters to warm cements and primers.• Take care to remove moisture, ice and snow from the mating surfaces.
Solvent Cementing in Hot Weather:• At the time of assembly, the surface temperature of the mating surfaces should not exceed 45°C. Shade or shelter the joint surfaces from direct sunlight for at least 1 hour prior to joining and during the joining process. If necessary, swab the mating surfaces with clean, wet rags to reduce the surface temperature (thoroughly dry surfaces before applying primer or cement).• Make joints during the cooler early morning hours.• Apply cement quickly and join pipe to fitting as quickly as possible after applying the cement.• Keep solvent cement container closed or covered when not in use, to minimize solvent loss.
Solvent Cementing in Wet Conditions:• Mating surfaces must be dry when the joint is made.• Work under a cover or canopy to keep rain off pipe and fittings.• Work quickly after drying the pipe and fitting to avoid condensation.• Allow a longer cure time before the system is tested or used.
Storage and Handling of Solvent Cement and Primer:• Solvent cement and primer contain highly flammable solvents. Follow all specific safety precautions provided on container label and Material Safety Data Sheet.• Keep primer and solvent cement away from heat, sparks and open flame.• Keep containers tightly closed except when in use.• Ensure proper ventilation of work area and avoid inhaling solvent vapours.• Where the possibility of splashing exists, wear proper eye protection or a face shield.• Avoid contact with skin.
Support Straps Rigid PVC conduit must be supported with straps when installed in above ground applications. These straps should be installed snugly, while allowing linear movement of the conduit. See the table below for recommended maximum spacing of support straps.
Temperature RangeDuring Assembly & Cure Periods
Pipe Sizes½” to 1¼”
15˚C to 40˚C5˚C to 15˚C-16˚C to 5˚C
2 min.5 min.
10 min.
Pipe Sizes1½” to 2”5 min.
10 min.15 min.
Pipe Sizes2½” to 6”30 min.2 hrs.
12 hrs.
Average Joint Cure Times
Temperature Range Pipe Sizes½” to 1¼”
15˚C to 40˚C5˚C to 15˚C-16˚C to 5˚C
2 min.5 min.
10 min.
Pipe Sizes1½” to 2”5 min.
10 min.15 min.
Pipe Sizes2½” to 6”30 min.2 hrs.
12 hrs.
Average Initial Set Times
200 125 90 60 40 40 30
Pipe/FittingDiameter
Number ofJoints
300
½” ¾” 1” 1½” 2” 2½” 3” 4”
10
6”
Average Number of Joints per Litre of Solvent Cement
400 250 180 120 80 80 60
Pipe/FittingDiameter
Number ofJoints
600
½” ¾” 1” 1½” 2” 2½” 3” 4”
20
6”
Average Number of Joints per Litre of Primer
Nominal Sizemm (in)
CEC RecommendedSpacing ft (m)
NEC RecommendedSpacing ft (m)
16 (½)21 (¾)27 (1)
35 (1¼)41 (1½)53 (2)
63 (2½)78 (3)-129 (5)
155 (6)
2½ (0.75)2½ (0.75)2½ (0.75)
4 (1.20)4 (1.20)6 (1.80)6 (1.80)7 (2.10)8 (2.50)
3 (0.91)3 (0.91)3 (0.91)5 (1.50)5 (1.50)5 (1.50)
3 - 6 (1.80)3½ - 5 (2.10)
8 (2.50)
Maximum Recommended Spacing of Support Straps
5
Storing Conduit Pipe and FittingsStore Rigid PVC conduit pipe and fittings at the same temperature. Otherwise they may expand and contract at different rates and become incompatible.
Maximum Operating TemperaturesAccording to the Canadian Electrical Code (CEC), Rigid PVC conduit is intended for use at a continuous operating temperature of 75°C (167°F). For US applications, our Rigid PVC conduit is rated for use with 90°C wiring, according to the requirements of the NEC.
Ambient TemperaturesRoyal Electrical Solutions Rigid PVC Conduit and fittings can be installed in locations with an ambient temperature not exceeding 50°C (122°F).
Expansion JointsAccording to the CEC, if the amount of expansion expected due to temperature variance during and after construction is more than 45mm, expansion joints must be used.
Expected ExpansionThe coefficient of linear expansion for Rigid PVC conduit is as follows:
3 x 10-5 in (expansion/contraction) / in (pipe length) /°F (change in temperature),
5.4 x 10-5 mm (expansion/contraction)/mm (pipe length)/°C (change in temperature)
Note:The following chart shows the amount of expansion expected with various pipe lengths/temperature changes. If the Rigid PVC Conduit is installed in an exposed location, 17°C (30°F) should be added to the amount of temperature change (∆T) due to the effects of radiant heat.
Required Number of Expansion JointsThe following table shows the amount of travel that is available with each trade size of Royal Electrical Solutions Rigid PVC conduit expansion joints:
Length of Pipe Run (m)
Expansion/Contraction of PVC (mm)
0.541.081.622.162.703.243.784.324.865.40
1.082.163.244.325.406.487.568.649.72
10.80
1.623.244.866.488.109.72
11.3412.9614.5816.20
2.164.326.488.64
10.8012.9615.1217.2819.4421.60
2.705.408.10
10.8013.5016.2018.9021.6024.3027.00
3.246.489.72
12.9616.2019.4422.6825.9229.1632.40
3.787.56
11.3415.1218.9022.6826.4630.2434.0237.80
4.328.64
12.9617.2821.6025.9230.2434.5638.8843.20
4.869.72
14.5819.4424.3029.1634.0238.8843.7448.60
5.4010.8016.2021.6027.0032.4037.8043.2048.6054.00
∆ T (˚C) 2 4 6 8 10 12 14 16 18 205
101520253035404550
Length of Pipe Run (ft)
Expansion/Contraction of PVC (in)
∆ T (˚F) 5 10 15 20 25 30 35 40 45 505
101520253035404550
0.010.020.030.040.050.050.060.070.080.09
0.020.040.050.070.090.110.130.140.160.18
0.030.050.080.110.140.160.190.220.240.27
0.040.070.110.140.180.220.250.290.320.36
0.050.090.140.180.230.270.320.360.410.45
0.050.110.160.220.270.320.380.430.490.54
0.060.130.190.250.320.380.440.500.570.63
0.070.140.220.290.360.430.500.580.650.72
0.080.160.240.320.410.490.570.650.730.81
0.090.180.270.360.450.540.630.720.810.90
PartNumber
Descriptionin
Travel Allowancemm (in)
REJ10REJ15REJ20REJ25REJ30REJ35REJ40REJ45REJ50REJ55REJ60REJ65
½” Expansion Joint¾” Expansion Joint1” Expansion Joint1¼” Expansion Joint1½” Expansion Joint2” Expansion Joint2½” Expansion Joint3” Expansion Joint3½” Expansion Joint4” Expansion Joint5” Expansion Joint6” Expansion Joint
102 (4)102 (4)102 (4)102 (4)102 (4)102 (4)102 (4)204 (8)204 (8)204 (8)204 (8)204 (8)
The required number of expansion joints can be calculated using the following formula:
The number of expansion joints calculated above should be rounded up to the nearest whole number.
Setting the Piston OpeningExpansion joints must be installed such that they allow for both expansion and contraction of the conduit. The piston of the expansion joint must be set at the correct position to allow for this linear movement. To determine the correct position for the piston at the time and temperature of installation, the following formula should be used:
Installation Guidelines• Securely fasten the expansion joint barrel so that it does not shift. Loosely connect the conduit so that it is free to move.
• To function properly, expansion joints should be installed near a fixed point.
• It is better to use more expansion joints than not enough, since problems are difficult to correct after conductors and wires have been pulled through the conduit.
• Ensure that the barrel and piston are aligned and level.
• For vertical installations of expansion joints, install with the piston at the bottom to prevent dirt and water from getting inside the joint and causing it to malfunction.
If one expansion joint is required:Securely fasten the barrel of the expansion joint close to one of the boxes. Support the conduit with straps, but allow free movement of the conduit for expansion and contraction. (See Drawing 1)
If two expansion joints are required:There are two options available:
1. Firmly fasten one expansion joint near each end of the run and firmly fasten the conduit at the centre. Support the rest of the conduit with straps allowing for movement of the conduit. (See Drawing 2)
2. Firmly fasten the expansion joints back-to-back at the centre of the run. The conduit should be supported with straps to allow free movements as it expands and contracts. (See Drawing 3)
If three or more expansion joints are required:Evenly space the expansion joints along the run of Rigid PVC conduit. Tightly fasten each expansion joint and support the conduit with straps. Do not restrict the movement of the conduit.
*For information on Maximum Recommended Spacing of Support Straps, see page 4.
Total Expected Amount of Expansion (in)Expansion Joint Travel Allowance (in)
# Expansion Joints Required =
Total Expected Amount of Expansion (mm)Expansion Joint Travel Allowance (mm)
# Expansion Joints Required =
Support Straploosely holding conduit in place
Support Straptightly holding expansion joint
Expansion Joint
Conduit
Solvent Weld Joint Solvent Weld Joint
Piston Opening
Installation Example
Drawings 1 - 4
6
(Max. Temp. (˚F) – Install. Temp. (˚F))Total Expected Temperature Change (˚F)
Expansion JointExpansion Allow. (in)
x=PistonSetting
(in)
(Max. Temp. (˚C) – Install. Temp. (˚C))Total Expected Temperature Change (˚C)
Expansion JointExpansion Allow. (mm)
x=PistonSetting(mm)
Drawing 1.
Drawing 2.
BOX BOX
Expansion Jointrigidly fastened
Support Strapsloosely fastened
Drawing 4.
BOX BOX
Expansion Jointrigidly fastened
Support Strapsloosely fastened
Expansion Jointrigidly fastened
Expansion Jointrigidly fastened
Support Strapscentre strap rigidly fastened
BOX BOX
Support Strapsloosely fastened
Drawing 3.
Expansion Jointrigidly fastened
BOX BOX
Support Strapsloosely fastened
7
FITTINGS - Bends (Bell Ends)
90˚ Elbows - Bell End
R
D
L
Sizes(in)
ProductCode
UPCNumber
Diameter (D)(in)
Length (L)(in)
Radius (R)(in)
½¾11¼1½22½33½456
REE1090REE1590REE2090REE2590REE3090REE3590REE4090REE4590REE5090REE5590REE6090REE6590
461204615046180462104624046270463304636046390464204644046460
0.8401.0501.3151.6601.9002.3752.8753.5004.0004.5005.5656.625
1.5001.5001.8752.0002.0002.0003.0003.1253.2503.3753.6223.740
4.004.505.757.258.259.5010.5013.0015.0016.0024.0030.00
D
L
R
R
L
D
½¾11¼1½22½33½456
REE1045REE1545REE2045REE2545REE3045REE3545REE4045REE4545REE5045REE5545REE6045REE6545
461204615046180462104624046270463304636046390464204644046460
0.8401.0501.3151.6601.9002.3752.8753.5004.0004.5005.5656.625
1.5001.5001.8752.0002.0002.0003.0003.1253.2503.3753.6253.750
4.004.505.757.258.259.5010.5013.0015.0016.0024.0030.00
½¾11¼1½22½33½456
REE1030REE1530REE2030REE2530REE3030REE3530REE4030REE4530REE5030REE5530REE6030REE6530
461004613046160461904622046274463104634046375464004642546442
0.8401.0501.3151.6601.9002.3752.8753.5004.0004.5005.5656.625
1.5001.5001.8752.0002.0002.0003.0003.1253.2503.3753.6253.750
4.004.505.757.258.259.5010.5013.0015.0016.0024.0030.00
Sizes(in)
ProductCode
UPCNumber
Diameter (D)(in)
Length (L)(in)
Radius (R)(in)
45˚ Elbows - Bell End
Sizes(in)
ProductCode
UPCNumber
Diameter (D)(in)
Length (L)(in)
Radius (R)(in)
30˚ Elbows - Bell End
R
D
L
Sizes(in)
ProductCode
UPCNumber
Diameter (D)(in)
Length (L)(in)
Radius (R)(in)
Utilities 90˚ Elbows - Bell End
22334456
REE2-24REE2-36REE3-24REE3-36REE4-36REE4-48REE5-36REE6-36
4650146502465034650446465465054650646507
2.3752.3753.5003.5004.5004.5005.5656.625
41.2031.7041.2031.7031.7031.7031.7031.70
24.0036.0024.0036.0036.0048.0036.0036.00
8
R
L
D
L
R
L
R
D
L
R
D
Fittings - Bends (Plain Ends)
90˚ Elbows - Plain End Sizes(in)
ProductCode
UPCNumber
Diameter (D)(in)
Length (L)(in)
Radius (R)(in)
½¾11¼1½22½33½456
REE1090PEREE1590PEREE2090PEREE2590PEREE3090PEREE3590PEREE4090PEREE4590PEREE5090PEREE5590PEREE6090PEREE6590PE
461204615046180462104624046270463304636046390464204644046460
0.8401.0501.3151.6601.9002.3752.8753.5004.0004.5005.5656.625
1.5001.5001.8752.0002.0002.0003.0003.1253.2503.3753.6223.740
4.004.505.757.258.259.5010.5013.0015.0016.0024.0030.00
45˚ Elbows - Plain End Sizes(in)
ProductCode
UPCNumber
Diameter (D)(in)
Length (L)(in)
Radius (R)(in)
½¾11¼1½22½33½456
REE1045PEREE1545PEREE2045PEREE2545PEREE3045PEREE3545PEREE4045PEREE4545PEREE5045PEREE5545PEREE6045PEREE6545PE
461104614046170462004623046280463204635046380464154643046450
0.8401.0501.3151.6601.9002.3752.8753.5004.0004.5005.5656.625
1.5001.5001.8752.0002.0002.0003.0003.1253.2503.3753.6223.740
4.004.505.757.258.259.5010.5013.0015.0016.0024.0030.00
30˚ Elbows - Plain End Sizes(in)
ProductCode
UPCNumber
Diameter (D)(in)
Length (L)(in)
Radius (R)(in)
½¾11¼1½22½33½456
REE1030PEREE1530PEREE2030PEREE2530PEREE3030PEREE3530PEREE4030PEREE4530PEREE5030PEREE5530PEREE6030PEREE6530PE
461004613046160461904622046274463104634046375464004642546442
0.8401.0501.3151.6601.9002.3752.8753.5004.0004.5005.5656.625
1.5001.5001.8752.0002.0002.0003.0003.1253.2503.3753.6223.740
4.004.505.757.258.259.5010.5013.0015.0016.0024.0030.00
45˚ Elbows - Extended Plain End Sizes(in)
ProductCode
UPCNumber
Diameter (D)(in)
Length (L)(in)
Radius (R)(in)
1¼1½2
REE2590EREE3090EREE3590E
461254626043290
1.6601.9002.375
14.75014.75014.750
7.258.259.50
9
Fittings - Couplings and Adapters
OD ID
L
L
IDOD
LBA
ID
B
ID
LA
½¾11¼1½22½33½456
RTA10RTA15RTA20RTA25RTA30RTA35RTA40RTA45RTA50RTA55RTA60RTA65
457304574045750457604577045780457904580045810458204583045840
0.7501.0001.1151.3001.4251.1501.9002.0001.7151.9902.0002.130
0.5910.7901.0001.3111.5301.9702.3462.9153.3853.8505.0156.025
1.5501.7501.8602.1252.2502.1002.9303.0553.0553.2155.9856.500
½¾11¼1½22½33½456
RFA10RFA15RFA20RFA25RFA30RFA35RFA40RFA45RFA50RFA55RFA60RFA65
449904500045010450204503045040450504506045070450804509045100
0.8000.8001.0001.0151.0501.0751.6751.6301.8001.7552.0652.065
0.6200.8201.0651.3951.5752.0502.4703.0903.5404.0255.0356.045
1.7251.9002.3002.4252.4402.5503.7604.1003.9854.2105.2405.235
Couplings Sizes(in)
ProductCode
UPCNumber
Outside Diameter(OD) (in)
Inside Diameter(ID) (in)
Length(L) (in)
Sizes(in)
ProductCode
UPCNumber
Outside Diameter(OD) (in)
Inside Diameter(ID) (in)
Length(L) (in)
½¾11¼1½22½33½456
REC10REC15REC20REC25REC30REC35REC40REC45REC50REC55REC60REC65
459504596045970459804599046000460104602046030460604608046090
1.0801.3001.5902.0002.2302.7203.3204.0004.5005.0006.1207.370
0.8401.0501.3151.6601.9002.3752.8753.5004.0004.5005.5656.625
1.4371.7032.0312.1562.2812.4063.1873.4373.6253.7504.1874.562
5˚ Couplings (*Fabricated)
Sizes(in)
ProductCode
UPCNumber
A(in)
Inside Diameter(ID) (in)
Thread(in)
Terminal Adapters (½” - 1¼” Tapered Thread, 6” NPT)
Sizes(in)
ProductCode
UPCNumber
A(in)
Inside Diameter(ID) (in)
0.7000.6750.6250.6400.7250.8000.8000.8151.0000.8151.7251.875
0.8251.0001.2001.3001.2901.3751.9852.1502.0002.1853.0003.000
B(in)
B(in)
Thread(in)
Female Adapters (Npt Tapered Thread)
22½33½456
R5EC35R5EC40R5EC45R5EC50R5EC55R5EC60R5EC65
46800468054681046815468204682546830
2.3753.5003.5004.5004.5005.5656.625
2.0492.4453.0423.5213.9985.0186.031
4.05.56.07.07.07.511.0
10
Fittings - Expansions Joints, Straps and Meter Accessories
Expansion Joints Sizes(in)
ProductCode
UPCNumber
Expanded Length(E) (in)
Contracted Length(C) (in)
Travel(in)
½¾11¼1½22½33½456
REJ10REJ15REJ20REJ25REJ30REJ35REJ40REJ45REJ50REJ55REJ60REJ65
448704488044890449004491044920449304494044950449604496344966
12.0012.0012.5013.0013.0013.2513.2522.2522.2522.2522.2522.25
8.008.008.509.009.009.259.25
14.2514.2514.2514.2514.25
4.004.004.004.004.004.004.008.008.008.008.008.00E
C
Expansion Joints
PVC2 Hole
PVC Coated Steel2 Hole
PVC Coated Steel1 Hole
Sizes (in) Product No. UPC No. Sizes (in) Product No. UPC No. Sizes (in) Product No. UPC No.
½¾11¼1½22½34
22½33½456
½¾11¼1½2
RCS10-1RCS15-1RCS20-1RCS25-1RCS30-1RCS35-1RCS40-1RCS10-1RCS10-1
RCS35RCS40RCS45RCS50RCS55RCS60RCS65
RPS10RPS15RPS20RPS25RPS30RPS35
468504685246854468564685846860468624686446866
44783447844478544786447874478844789
455404555045560455704558045590
Sizes (in) Product No. UPC No.
1¼2
RM025RM035
4550045510
Meter Offsets
Sizes (in) Product No. UPC No.
1¼1½2
RMHU25RMHU30RMHU35
454804548545490
Meter Hubs
Sizes (in) Product No. UPC No.
1¼1½2
RLM025RML030RML035
454724547445476
Long Meter Offsets (Fabricated)Sizes (in) Product No. UPC No.
234
RSEJ35RSEJ45RSEJ55
469904699246994
Expansion & Deflection Fittings Assembly
Sizes (in) Product No. UPC No.
½¾11¼1½22½33½4
REF10REF15REF20REF25REF30REF35REF40REF45REF50REF55
44795448004481044820448304484044842448444485244860
Service Entrance FittingsSizes (in) Product No. UPC No. Carton Qty.
250ml475ml950ml4L
RVOC250*RVOC475*RVOC950*RVOC4L
54790547955479754799
2412124
Ecovoc Solvent Cement (*c/w Screw Cap & Dauber)
Sizes (in) Product No. UPC No. Carton Qty.
250ml475ml950ml4L
RVOCPR250*RVOCPR475*RVOCPR950*RVOCPR4L
54800548025480454806
2412124
Privoc Solvent Cement (*c/w Screw Cap & Dauber)
11
Fittings - Access Fittings
Type C Sizes(in)
ProductCode
½¾11¼1½22½33½4
RSC10SRSC20SRSC30SRSC40SRSC50SRSC60SRSC70SRSC80SRSC90SRSC100S
UPCNumber
46600466054661046615466204560545606456074560945608
A(in)
5.6065.6066.5007.9008.500
10.87514.60014.60017.04017.040
B(in)
0.6390.8100.9101.0501.1251.1601.7501.9002.1252.125
C(in)
1.2681.5361.7002.3002.6753.1884.5004.5005.5365.536
D(in)
1.1001.3251.6002.2502.2502.8203.9503.9505.0005.000
E(in)
0.8401.0501.3351.1001.9002.3752.8703.5104.0004.530
A
B
B
CD
E
Type LB Sizes(in)
ProductCode
½¾11¼1½22½33½4
RSLB10SRSLB20SRSLB30SRSLB40SRSLB50SRSLB60SRSLB70SRSLB80SRSLB90SRSLB100S
UPCNumber
45620456304564045650456604567045675456804561045681
A(in)
4.3375.3956.2507.6258.250
10.53113.63013.63016.00016.000
B(in)
0.6390.8100.9101.0501.1251.1601.7501.9002.1252.125
C(in)
1.2681.5361.7002.3002.6753.1884.5004.5005.5365.536
D(in)
0.8401.0501.3351.1001.9002.3752.8703.5104.0004.530
E(in)
1.2971.2971.5001.7501.7502.3442.7333.8054.5354.535
F(in)
4.0954.0954.7505.7506.5008.1569.825
10.89711.46511.465
G(in)
2.4872.4872.0753.5753.9384.5356.2406.2407.5007.500
H(in)
1.0051.0051.1251.5621.6561.9682.6102.6102.9752.975
Sizes(in)
ProductCode
½¾11¼1½22½33½4
RSLL10SRSLL20SRSLL30SRSLL40SRSLL50SRSLL60SRSLL70SRSLL80SRSLL90SRSLL100S
UPCNumber
46650466554666046665466704568245672466744667846676
A(in)
4.3375.3956.2507.6258.250
10.53113.63013.63016.00016.000
B(in)
0.6390.8100.9101.0501.1251.1601.7501.9002.1252.125
C(in)
1.2681.5361.7002.3002.6753.1884.5004.5005.5365.536
D(in)
2.4872.4872.0753.5753.9384.5356.2406.2407.5007.500
E(in)
0.8401.0501.3351.1001.9002.3752.8703.5104.0004.530
F(in)
4.0954.0954.7505.7506.5008.1569.825
10.89711.46511.465
G(in)
1.2971.2971.5001.7501.7502.3443.8052.7334.5354.535
Sizes(in)
ProductCode
½¾11¼1½22½33½4
RSLR10SRSLR20SRSLR30SRSLR40SRSLR50SRSLR60SRSLR70SRSLR80SRSLR90SRSLR100S
UPCNumber
46700467054671046715467204568346725467284673846735
A(in)
4.3375.3956.2507.6258.250
10.53113.63013.63016.00016.000
B(in)
0.6390.8100.9101.0501.1251.1601.7501.9002.1252.125
C(in)
1.2681.5361.7002.3002.6753.1884.5004.5005.5365.536
D(in)
2.4872.4872.0753.5753.9384.5356.2406.2407.5007.500
E(in)
0.8401.0501.3351.1001.9002.3752.8703.5104.0004.530
F(in)
4.0954.0954.7505.7506.5008.1569.825
10.89711.46511.465
G(in)
1.2971.2971.5001.7501.7502.3443.8052.7334.5354.535
Type LL
Type LR
AF
E
D
C
B
B
HG
FA
D
G
CB
E
B
B
B C
F
G
D
E
A
12
Fittings - Access Fittings
Type E Sizes(in)
ProductCode
½¾11¼1½22½33½4
RSE10SRSE20SRSE30SRSE40SRSE50SRSE60SRSE70SRSE80SRSE90SRSE100S
UPCNumber
46630466324663446636466384664046642466444664846646
A(in)
4.3375.3956.2507.6258.250
10.35113.63013.63016.00016.000
B(in)
0.6390.8100.9101.0501.1251.1601.7501.9002.1252.125
C(in)
1.2681.5361.7002.3002.6753.1884.5004.5005.5365.536
D(in)
0.8401.0501.3351.1001.9002.3752.8703.5104.0004.530
Sizes(in)
ProductCode
½¾11¼1½22½33½4
RST10SRST20SRST30SRST40SRST50SRST60SRST70SRST80SRST90SRST100S
UPCNumber
45690457004571045720457234572546745467484675246750
A(in)
2.2802.8033.2503.9504.2505.4387.3007.3008.5358.535
B(in)
0.6390.8100.9101.0501.1251.1601.7501.9002.1252.125
C(in)
1.1001.3251.6002.2502.2502.8203.9503.9505.0005.000
D(in)
0.8401.0501.3351.1001.9002.3752.8703.5104.0004.530
Type T
Sizes(in)
ProductCode
½¾11¼1½22½33½4
RSTB10SRSTB20SRSTB30SRSTB40SRSTB50SRSTB60SRSTB70SRSTB80SRSTB90SRSTB100S
UPCNumber
45692457024571245721457244572746760467624676646764
A(in)
2.2802.8033.2503.9504.2505.4387.3007.3008.5358.535
B(in)
0.6390.8100.9101.0501.1251.1601.7501.9002.1252.125
C(in)
1.2681.5361.7002.3002.6753.1884.5004.5005.5365.536
D(in)
1.1001.3251.6002.2502.2502.8203.9503.9505.0005.000
E(in)
0.8401.0501.3351.1001.9002.3752.8703.5104.0004.530
F(in)
2.4872.4872.0753.5753.9384.5356.2406.2407.5007.500
G(in)
1.0051.0051.1251.5621.6561.9682.6102.6102.9752.975
H(in)
0.7500.8101.1151.3001.4251.160
----
Type TB
A
A
DC
B
H
GF
E
B
A
B
C
D
A
A
B
B
C
DB
14
RTSC20-3 RDSDR20-3 RTSDC20-3 RDRC20-3 RBRC20-3 GASK20-3
R20RC15-10RDRC15-10RTSC15-10 R20-3RC15-10 R30-3RC15-10 RBRC15-10 GASK15-10
Fittings - Cover Plates
Single Gang Cover Plates - F Series
Description Product Code UPC Number
RTSC20-2 RTSDC20-2 RBRC20-2 GASK20-2RDRC20-2
Toggle SwitchDuplex ReceptacleSingle Receptacle - 15 AmpSingle Receptacle - 20 AmpSingle Receptacle - 30 AmpSingle Blank with GasketGasket
RTSC15-10RDRC15-10R20RC15-10R20-3RC15-10R30-3RC15-10RBRC15-10GASK15-10
45845446854703547036470374468044682
Double Gang Cover Plates - F Series
Description Product Code UPC Number
Double SwitchCombo Switch/ReceptacleDouble DuplexDouble Blank with GasketGasket
RTSC20-2RTSDC20-2RDRC20-2RBRC20-2GASK20-2
4584645847446864468145949
Triple Gang Cover Plates - F Series
Description Product Code UPC Number
Triple SwitchDouble Switch ReceptacleDouble Receptacle/SwitchTriple ReceptacleTriple Blank with GasketGasket
RTSC20-3RDSDR20-3RTSDC20-3RDRC20-3RBRC20-3GASK20-3
458574468945858446884468345859
15
Fittings - Weatherproof Cover Plates
Single Gang Weatherproof Cover Plates
Description Product Code UPC Number
Toggle Switch CoverPlunger Switch CoverToggleDuplex ReceptacleDuplex Receptacle - WhiteGround Fault ReceptacleGround Fault Receptacle - WhiteSingle Receptacle - 15 AmpSingle Receptacle - 20 AmpSingle Receptacle - 30 AmpSingle Receptacle - 50 AmpGasket
RVSC15-10RVPT15-10RWTG15-10RWDR15-10RWDR15-10WRWGF15-10RWGF15-10WRWTL15RWTL20RWTL30RWTL50GASK W
459404593045339450934509445095450984547045472454804548245484
GASK WRVSC15-10
GASK20-2RVSRR20-2RVSDR20-2RVSRC20-2RVSC20-2
RWTLRWGF15-10RWTG15-10RVSC15-10RVSC15-10
Double Gang Weatherproof Cover Plates
Description Product Code UPC Number
Double TogglePlunger/GFIPlunger/Duplex ReceptaclePlunger/Single ReceptacleGasket
RVSC20-2RVSRC20-2RVSDR20-2RVSRR20-2GASK20-2
4594145947459454594845949
16
Fittings - Slab Boxes
Single Gang Boxes - F Series
Description Product Code UPC Number
½” FS¾” FS½” FSS¾” FSS½” FSC¾” FSC½” FSCC¾” FSCC
RFS10RFS15RFSS10RFSS15RFSC10RFSC15RFSCC10RFSCC15
4520045210452404525045220452304523345235
Single Gang Deep Boxes - FD Series
Outside Dimensions: Length = 4.5”, Width = 6.6”, Height = 2.5”, except BLANK, L = 4.5”, W = 6.6”, H = 3.0”
Volume (in3)
17.017.017.517.516.316.317.017.0
Description Product Code UPC Number
½” FSC¾” FSC1” FSC½” FS¾” FS1” FSBLANK
RFSC3-10RFSC3-15RFSC3-20RFS3-10RFS3-15RFS3-20RFD-3
45224452324522845208452184521945155
Volume (in3)
56.056.056.054.054.054.073.8
RFS RFSS RFSC RFSCC
RFDS RFDC BLANK 347 VOLT
17
Fittings - Slab Boxes
Triple Gang Boxes - F Series
Outside Dimensions: Length = 4.5”, Width = 6.6”, Height = 2.5”, except BLANK, L = 4.5”, W = 6.6”, H = 3.0”
Description Product Code UPC Number
½” FSC¾” FSC1” FSC½” FS¾” FS1” FSBLANK
RFSC3-10RFSC3-15RFSC3-20RFS3-10RFS3-15RFS3-20RFD-3
45224452324522845208452184521945155
Volume (in3)
56.056.056.054.054.054.073.8
Double Gang Boxes - F Series
Outside Dimensions: Length = 4.5”, Width = 4.75”, Height = 2.5”, except BLANK, L=4.75”, W=4.75”, H=3.0”
Description Product Code UPC Number
½” FS¾” FS1” FS½” FSS¾” FSS1” FSS½” FSC¾” FSC1” FSC½” FSCC¾” FSCC1” FSCCBLANK
RFS2-10RFS2-15RFS2-20RFSS2-10RFSS2-15RFSS2-20RFSC2-10RFSC2-15RFSC2-20RFSCC2-10RFSCC2-15RFSCC2-20RFD-D
45205452154521645242452444524645222452314522645234452384523945150
Volume (in3)
39.539.539.537.037.037.037.037.037.036.036.036.052.0
BLANKFSFSC
BLANKFSCCFSCFSSFS
Size (in) Product No. UPC No.
12
RXR20RXR35
4649046495
Octagonal Box Extension Rings
Size (in) Product No. UPC No.
4 x 1½4 x 2¾1
ROB15/10ROB20RKO15RKO20
45520455254545045455
Octagonal Boxes
18
L LT
BB
H
Fittings - Slab Boxes
Highway Boxes
6 x 6 x 46 x 6 x 68 x 8 x 48 x 8 x 68 x 8 x 78 x 8 x 7
H664H666H884H886H887H887-A
470404704147042470434704447045
6.06.08.08.08.08.0
4.256.254.256.257.257.25
9.09.0
11.511.511.511.5
0.600.600.750.750.750.75
139.5209.3258.6400.0455.6418.4
Junction Boxes With Gasket
4 x 4 x 24 x 4 x 44 x 4 x 65 x 5 x 26 x 6 x 46 x 6 x 68 x 8 x 48 x 8 x 712 x 12 x 412 x 12 x 612 x 12 x 8
RJB442RJB444RJB446RJB552RJB664RJB666RJB884RJB887RJB12124RJB12126RJB12128
4530045310453154532045330453354534045350452804529045295
3.6753.6753.6754.6806.0006.0008.0758.100
12.08512.08512.085
4.0004.0004.0005.0006.3756.3758.6258.625
12.58012.58012.580
3.4503.4503.4504.4855.8135.8137.9967.996
11.87411.87411.874
2.1254.1886.2252.0004.1886.1884.2307.2504.2566.2408.250
2.0003.7506.0001.8454.0006.0004.0057.0354.0306.0258.025
25.447.576.138.7
139.5209.3258.6455.6578.3864.6
1151.6
8-328-328-328-32
10-3210-32¼-20¼-20¼-20¼-20¼-20
Size (in) Product No. UPC No.
4 x ¾2 x ¾, 2 x 1
PolycarbonateBronze Cover
RFDB4RFDB2
RFDBC
4698046982
46984
Duplex Floor Boxes & Cover (*Includes Leveling Ring)
Size (in) Product No. UPC No.
½¾11¼1½22½33½4
RJBA10RJBA15RJBA20RJBA25RJBA30RJBA35RJBA40RJBA45RJBA50RJBA55
45360453704538045390454004541045420454304543545440
Junction Box Adapters
ProductNumber
NominalSize (in)
UPCNumber
Inside Length& Width (A) (in)
Outside Length& Width (B) (in)
OutsideHeight (E) (in)
InsideHeight (D) (in)
ScrewSize (F)
Volume(in3)
Length Screw to Screw (C) (in)
ProductNumber
NominalSize (in)
UPCNumber
Box Inside Length& Width (B) (in)
Box Inside Depth(H) (in)
Thickness ofLid (T) (in)
Volume(in3)
Lid Length &Width (L) (in)
A
AB
B
C
CED
F
19
Notes:
E_RCPF_BRV4Printed 02.2014
Our various pipe and fittings solutions have been manufactured to meet the needs of ourcustomers and their applications. Contact one of the below Sales Centres for more information:
• Municipal Pipe & Fittings Solutions• Plumbing Pipe & Fittings Solutions• Electrical Pipe & Fittings Solutions• Industrial Pipe & Fittings Solutions• Irrigation Pipe & Fittings Solutions
Sales & Distribution Centres:
Langley, BC, CanadaT/F 1.800.663.0696F 1.800.663.6564.......................................
Woodbridge, ON, CanadaT/F 1.866.769.7473F 905.856.3986.......................................
Laval, QC, CanadaT/F 1.800.465.9754F 450.688.6624.......................................
Distribution Centres:
Calgary, AB, CanadaT/F 1.800.663.0696F 1.800.663.6564.......................................
Winnipeg, MB, CanadaT/F 1.800.663.0696F 1.800.663.6564.......................................
royalelectricalca.com