6
ENERGY DIVISION RICS Insulated adapter termination system for SF 6 -insulated switchgear up to 24 kV

RICS Insulated adapter termination system for SF6 ...raychem.net/pdf/RICS.pdf · RICS – Insulated adapter termination system for SF 6-insulated switchgear up to 24 kV The insulated

  • Upload
    vunhi

  • View
    220

  • Download
    0

Embed Size (px)

Citation preview

Page 1: RICS Insulated adapter termination system for SF6 ...raychem.net/pdf/RICS.pdf · RICS – Insulated adapter termination system for SF 6-insulated switchgear up to 24 kV The insulated

ENERGY DIVISION

RICSInsulated adapter termination system for SF6-insulated switchgear up to 24 kV

EPP0532-7/06.qxd 26.07.2006 10:43 Uhr Seite 6

Page 2: RICS Insulated adapter termination system for SF6 ...raychem.net/pdf/RICS.pdf · RICS – Insulated adapter termination system for SF 6-insulated switchgear up to 24 kV The insulated

RICS – Insulated adapter termination system for SF6-insulated switchgear up to 24 kV

Different cables...New materials and new productionmethods have changed the face ofmedium voltage cables completelyover the years, resulting in increasedcomplexity. Paper and plastic insu-lated cables with one or three cores, round or sector shape, and many different types of shielding, waterblocking systems, as well as varyinginsulation thickness can be found intoday's networks.

...need different terminations...Catering for a wide range of cableswith as few fittings as possible, while optimising the products forspecific applications and maximisingtheir reliability, was the logical consequence.

...or Tyco Electronics EnergyDivision flexibility.Heat-shrink technology makes it possible to use a single size of fittings for a large number of cable cross sections and types. This universal technology not onlyreduces the requirement for jointertraining but also the installation time, at the same time increasing the reliability, irrespectice of the type of cable used in the network.

The increasing popularity of gas insulated switchgear called for thedevelopment of an appropriate connection to the bushing. The Tyco Electronics Energy Divisionhas developed two systems for thispurpose. The RICS insulating adapter(630 A) is compatible with allRaychem terminations and can thusbe used to connect any type of cable,irrespective of whether it is paper orplastic insulated or has one or threecores.

Simplified installationThe compact design of the adaptersand their clear cut profiles simplifyinstallation. The electrical connectionwith the aid of a stud renders addi-tional fastening systems unnecessary.

ReliabilityTyco Electronics Energy Division hasseveral decades of experience in thefield of hermetically insulated termi-nation systems for medium voltageapplications. The adapters are water tight andguarantee uninterrupted operation,even under extreme environmentalconditions with severe pollution.

TestsThe adapters conform to IEC 540,VDE 0278 and ANSI IEEE 386 specifi-cations, as well as to the Raychemspecification PPS 3013.The test requirements and results aresummarized in Raychem Test ReportPPR 1106, which is available onrequest.

EPP0532-7/06.qxd 26.07.2006 10:43 Uhr Seite 1

Page 3: RICS Insulated adapter termination system for SF6 ...raychem.net/pdf/RICS.pdf · RICS – Insulated adapter termination system for SF 6-insulated switchgear up to 24 kV The insulated

EPP0532-7/06.qxd 26.07.2006 10:43 Uhr Seite 4

Page 4: RICS Insulated adapter termination system for SF6 ...raychem.net/pdf/RICS.pdf · RICS – Insulated adapter termination system for SF 6-insulated switchgear up to 24 kV The insulated

RICS – Insulated adapter termination system for SF6-insulated switchgear up to 24 kV

The insulated adapter terminationsystem provides perfect sealing, electrical insulation and an electricalconnection between Raychem termi-nations and SF6-insulated switchgearup to 24 kV. Its lead-in insulator (630 A) conformsto DIN 47636 and ANSI IEEE 386. The cable box of the switchgear must be provided with suitable protection against electric shock. The insulating adapter is compatiblewith all Raychem terminations. Details of the terminations can befound in the cable accessories catalogue.

T-adapter for perpendicular connection of the termination to SF6-insulated switchgear

T-adapter for perpendicular connection of termination and surge arrester to SF6-insulated switchgear

Straight adapter forvertical connection of the termination to SF6-insulated switchgear

Straight adapter

DesignA thick walled, heat-shrinkable insulating sleeve provides a hermetic seal over the cone of the bushing and the termination. The adapter area is smoothed with a meltable filler strip.

Scope of supply (for three phases)Heat-shrinkable insulating sleeving,filler strip, small accessories andinstallation instructions. Terminal stud and lug must be enclosed.

T-adapter with or without surge arrester

DesignThick walled insulator made of highquality elastomer with sealing faceover the termination, bushing coneand plug. The electrical connection is madewith a terminal stud and the cable lug of the termination. Two cable connection is possible. A special plugwhich allows cable testing without disconnecting the adapter is alsooffered. The design of the adapter for connecting the surge arrester isbasically identical. The elastomerinsulator has an additional lead-induct for the surge arrester. Details of the surge arresters can be found in the brochure EPP 0533.

Scope of supply (for three phases)Insulator, plug, terminal stud, smallaccessories and installation instruc-tions.

T-adapter fittedwith testing plug

EPP0532-7/06.qxd 26.07.2006 10:43 Uhr Seite 2

Page 5: RICS Insulated adapter termination system for SF6 ...raychem.net/pdf/RICS.pdf · RICS – Insulated adapter termination system for SF 6-insulated switchgear up to 24 kV The insulated

Siemens 8DJ10 Calor Emag Z L4

AEG FBA

Merlin Gerin RM6+

Driescher Minex C

GEC Alsthom T&D BTL

Felten & Guilleaume GA

Driescher Minex D

ABB CTC

EPP0532-7/06.qxd 26.07.2006 10:43 Uhr Seite 3

Page 6: RICS Insulated adapter termination system for SF6 ...raychem.net/pdf/RICS.pdf · RICS – Insulated adapter termination system for SF 6-insulated switchgear up to 24 kV The insulated

Tyco Electronics Raychem GmbHFinsinger Feld 1, 85521 Ottobrunn/Munich, GermanyPhone: +49-89-6089-0, Fax: +49-89-6096345http://energy.tycoelectronics.com

© Tyco Electronics EPP 0532 7/06

Energy Division – economical solutions for the electrical power industry: cable accessories,connectors & fittings, electrical equipment, instruments, lighting controls, insulators &insulation enhancement and surge arresters.

All of the above information, including drawings, illustrations and graphic designs, reflects our present understanding andis to the best of our knowledge and belief correct and reliable. Users, however, should independently evaluate the suitabilityof each product for the desired application. Under no circumstances does this constitute an assurance of any particular qualityor performance. Such an assurance is only provided in the context of our product specifications or explicit contractualarrangements. Our liability for these products is set forth in our standard terms and conditions of sale. RAYCHEM is a trademark.

R