INTRODUCTION
The Rickard Remote Digital Wall Mounted Thermostat/Controller is
fitted with a Room Sensor and LCD display. The Thermostat/
Controller is supplied in an aesthetically pleasing, slim 121mm by
78mm plastic enclosure. The unit provides for Setpoint Temperature
adjustment and Room Temperature display. Further advanced func-
tionality is available for commissioning and set-up purposes. The unit
is designed to mount into a standard 2x4 draw-box. The MLM wall
controller is designed to work with Rickard PC based MLM software
for further functionality.
OPERATION PANEL GENERAL LAYOUT
DISPLAY BUTTONS
IMPORTANT: Make ensure that zoning and commissioning of diffus-
ers is done in the Rickard MLM Software Application before opera-
tion of the Wall Thermostat can start. Please request or download
the application on Rickard website.
GENERAL OPERATION
1. On start-up (power on), the following screen will be displayed.
• The software initiates and communicates with all other controllers
and interface boards connected on the same circuit.
• Previously stored information is collected from all controllers and
interface boards.
•The software version number is displayed while the software initi-
ates.
2. Diffuser limit detection:
• After software initiation the diffuser will drive to the fully closed
position.
• During this process the limit indicators on the display will flash and
the direction arrow will show that the diffuser is driving closed.
•When the motor drives into the end stop, the software will remem-
ber that position as the fully open position.
RIGHT SIDE
LEFT SIDE
3. Control mode:
• After limits are detected, the controller will enter control mode.
Room temperature is displayed.
•The letters “Cr” indicate the Remote Wall Thermostat temperature as
a Source for temperature display. When “CO” is displayed the Source
for temperature display is the Onboard controller & sensor. “CE” is
displayed to indicate Control Temperature Error i.e. Wall stat temper-
ature is displayed, but no temperature is selected for control purpos-
es.
• The controller will now drive the diffuser in the direction to control
room conditions.
• In PICTURE 1 the display indicates that cooling mode is required to
get room conditions under control and the diffuser is busy driving
open.
• In this mode Room temperature is displayed. If Room temperature
was colder than set-point, heating mode would have been required
to get room conditions under control.
• PICTURE 2 indicates the diffuser has reached the fully open posi-
tion.
• PICTURE 3 indicates the diffuser is in heating mode and has
reached the minimum stop position for heating. The neck heater is
on as displayed. The diffuser could also be in heating mode without
the neck heater activated. The heater (if fitted) will only be activated
when the control disc reaches the correct position for heating.
(Factory set at 30% flow)
4) Set-point adjustment:
• To adjust the set-point, either the “UP” or “DOWN” buttons must
be pressed.
• After one of these buttons have been pressed, the current set-point
will be displayed.
• While in this screen, press either the “UP” or “DOWN” button to
adjust the set-point value.
The value displayed will now flash.
• Press the “ENTER/ACCEPT” button to be automatically accepted or
wait for the new setpoint.
• The 2 top left digits will indicate the Source of the set-point and
which set-point is Active respectively. If the display shows “r1”, this
indicates the Wall thermostat set-point is the source and setpoint 1,
ie “normal control” is active. Should the digits show “o2” then the
setpoint is active on the onboard controller and the back-off set-
point is active.
PICTURE 2
PICTURE 1
COOLING MODE
INDICATOR
HEATING MODE
INDICATOR
RE-HEATING MODE
INDICATOR
PICTURE 3
ADVANCED SETUP OPTIONS
If the Wall Thermostats setup menu is required and has been ena-
bled on the MLM application or if you have purchased a setup mod-
ule, the following display/setup options will be available (long press
the menu button until the unit beeps and release to enter the setup
menu on the wall thermostat). If adjustable, the menu items value
can be adjusted with the up/down buttons and entered using the
enter button. Each press of the menu button cycles through each
option available.
1. Supply Air Temperature Display (CO)
2. Room Temperature Display (r)
3. Motor Manual Mode and Adjust
4. Maximum Motor Limit Adjust (dr)
5. Minimum Motor Limit Adjust (dr)
6. Heater Manual Mode and Adjust (Ht)
7. Control Zone Setup
a. Loop Select (LS)
b. Control Input Select (rS)
8. Set Point Adjust
WALL THERMOSTAT DISPLAY OPTIONS
The following display options are available. Each option is available
individually or as a combination of options:
Edit Setpoint Disable
Setpoint Display
Enable Setup Menu
To activate, connect to the relevant diffuser on the MLM app, max-
imise the diffuser, select the wall thermostat and click on Display
Setup as shown in the pictures below. Select the option required and
press enter or click write.
Edit Setpoint Disable
Edit Setpoint Disable prevents the user from editing the Setpoint on
the Wall thermostat.
Setpoint Display
Setpoint Display, displays the setpoint instead of the room tempera-
ture.
Enable Setup Menu
Enable Setup Menu activates the advanced setup options. See Setup
Menu Options instructions below.
Combination of Display Options
Select any combination of the above options if required.
SETUP OPTIONS
1. Supply Air Temperature Display (CO)
• When a Supply Air (Change Over) sensor is fitted the supply air
temperature will be displayed.
• When no sensor is fitted, a zero value will be displayed.
2. Room Temperature Display (r)
• Wall Thermostat/Controller sensor value is displayed.
• “r” indicates the source of control is the Wall Controller.
3. Motor Manual Mode and Adjust
• The % control disc opening is displayed. 0% is fully closed. 100% is
fully open.
• Select the required control disc % position with “UP” or “DOWN”
buttons. Press “ENTER” to move control disc to selected position.
• Pressing “MENU” button deactives the manual mode and moves to
the next option.
4. Maximum Motor Limit Adjust (dr)
• Adjust using the “UP” button to change the maximum motor limit.
• Press the ENTER button to set the value after you have adjusted it.
5. Minimum Motor Limit Adjust (dr)
• Adjust using the “DOWN” button to change the minimum motor
limit.
• Press the ENTER button to set the value after you have adjusted it.
6. Heater Manual Mode and Adjust (Ht)
• The current re-heater output value is displayed as a % of maximum.
• “Ht” indicates the unit is in Heater Manual mode.
• Select the required output with the “UP” and “DOWN” buttons.
Press “ENTER” to activate heater at the required level.
• Pressing the “MENU” button deactives manual mode and moves to
next feature.
7. Control Zone Setup
NOTE: Rickard recommends the MLM Application loaded on a PC
to zone diffusers. See the MLM Commissioning Guide for more
information.
a. Loop Select (LS)
To bind a diffuser to a control zone the following steps is required:
• The top left character display will indicate ‘LS’ for Loop Select.
• Keep the enter button pressed until the unit beeps.
• The menu will display ‘L and a zone number, ‘00’. If the zone has
been set up previously, that particular zone number will display in-
stead of ‘00’.
• Press enter again and the zone number will flash.
• Use the up/down arrow to select a zone number. A new installation
should always start with zone ‘1’.
•Press enter and observe the ‘L’ flashing.
• Go to the first diffuser in that zone and press the button on the
MLM Diffuser Controller board, this is normally situated on the trim
disk.
• After a few seconds the Setup Module will beep and the flashing
LED on the MLM DC board will stay switched on momentarily this
indicates the diffuser is set up for that control zone.
• Go to the next diffuser in that zone and press the button again and
observe the same result. During this time the ‘L’ indicator will flash
and the zone number will be on displayed.
• Continue the process until all the diffusers in the control zone have
been selected.
•Press the enter button and observe the ‘L’ steady and the zone
number flashing.
• Using the up/down arrows, select the next zone number and con-
firm by pressing enter.
• Using the same procedure, set each diffuser in the control zone.
• A maximum of fifteen control zones (one diffuser per zone) can be
set. A minimum of one zone with one to fifteen diffusers (slaves) can
be set up.
• Press enter again to exit the last zone that was set.
• To advance to the next menu, press the menu button.
b. Control Input Select (rS)
The next function is to select the setpoint, control and supply air
temperatures for a particular control zone. As mentioned, to use this
function the setup module must be connected to a diffuser in the
control zone of interest. In a default system with only one wall-stat
or one analog module connected to a control zone this function will
not be required.
• The display will indicate ‘tS’ in the top left character display.
• The character display will indicate the current status of the three
control inputs as follows:
‘o’ - indicates ‘on-board’ for analog module.
‘r’ - indicates ‘remote’ for wall-stat
‘-‘ - indicates not selected
• Press and hold the enter button until the unit beeps. The first char-
acter will flash with the display indicating ‘t’ for control temperature
selection.
• Pressing the up/down arrows will toggle between remote or on-
board temperature selections. Be sure to select a valid option, i.e.
when selecting ‘remote’ there must be a wall-stat connected to that
particular control zone.
• Press enter and the character ‘S’ will show to indicate setpoint se-
lection. The up/down arrows will toggle this function.
• Press enter to select the supply air input, character ‘C’. The arrow
buttons will toggle between ‘o’, ‘r’ and ‘-‘ if supply air measurement
is not required.
• On pressing enter again the three characters will flash until the
system has accepted the new setup.
• Press the menu button to exit this function.
•To advance to the next menu, press the menu button.
8. Set Point Adjust
The next function displayed is setpoint adjust with the ‘SP’ icon on.
♦ Note the setup module must be plugged into the control zone of
interest for this function.
♦ The top left character display will indicate ‘S1’ for setpoint 1. Set-
point
2, or the back off setpoint is not adjustable with this unit.
♦ Press the up/down arrow to select the required setpoint. The digits
will flash.
♦ Press enter. The display will flash ‘---‘ until the new setpoint has
been accepted.
♦ Press the menu button to exit this function and revert to the main
menu.