reg. naming data sheet
EHA4 - actuators PARICHHA
1 Operating instructions
EC Declaration by the manufacturer
2 Connection diagram HS-A11-N680
3 Circuit diagram HS-A11-N674
4 Parts list UH01-08004-5313-B
5 Actuator drawing CGE1MF3... D901272CGE1MF3... D901273CGE1MF3... D901274
CGE1MF3... D901275
6 2- way cartridge valves
type: LC32 A40E7X/Vtype: LFA 32 WEA27-7X/V
RE 21010
7 3/2 and 4/2- way directional poppet valves with solenoidoperation
type: M-3SEW 6 C3X/420MG24N9Z2/B08V SO864type: M-3SEW 6 U3X/420MG24N9K4/V
RE 22058
8 Servo directional valve in 4- way design
type: 4WS2EM10-5X/60B11T315K31CV-114
RE 29583
9 High pressure filters
type: DFP W 060 QB 25BM1.X/-V-Wtype: DFP BH/HC 060 QB 10BM1.X/-V-W
mfr Fa. Hydac
10 Transsonar transducer
type: BTL5-E10-M-0100-K-K02type: BTL5-E10-M-0150-K-K02
mfr Fa.Balluff
11 Sales and service network RDE 02000
7/22/2019 Rexroth Manual for Actuators
3/265
IndustrialHydraulics
Electric Drivesand Controls
Linear Motion andAssembly Technologies Pneumatics
ServiceAutomation
MobileHydraulics
Electrohydraulic Actuator - Steam
Type: CGE1...2X/... ; CXE12x/Operating Instructions
7/22/2019 Rexroth Manual for Actuators
4/265
2 / 45 cce_antriebe-dt-cxe1-2x_bal_v10_en
These instructions must be read and applied by everybody who isentrusted with work on the actuator:
In particular, you have to read and observe the safety regulations inchapter 3.
A copy of these instructions must always be available in the vicinityof the electrohydraulic actuator.
Bosch Rexroth AG
Industrial Hydraulics
Systems & Engineering
Zum Eisengieer 1
D-97816 Lohr am Main
Tel.: +49 (0) 9352/18-1178FAX: +49 (0) 9352/18-1054
CCE_ANTRIEBE-DT-CXE1-2X_BAL_V10_DE.doc
07.06.
Bosch Rexroth AG 2006
The contents of this brochure must not be handed over whetherin whole or in part - to third parties without the written permissionby Bosch Rexroth. All technical data, drawings, etc. are subject tocopyright laws.
Publisher
Document no.
Date of issue
Copyright
7/22/2019 Rexroth Manual for Actuators
5/265
Contents
cce_antriebe-dt-cxe1-2x_bal_v10_en 3 / 45
Table of contents
1 Identification of the product.....................................................................................61.1 Verifying the consignment..................................................................................6
Scope ..............................................................................................................................6Condition when supplied .................................................................................................6
1.2 Identifying the electrohydraulic actuator.............................................................7Nameplate.......................................................................................................................7
1.3 Use according to the intended purpose .............................................................71.4 Wrongful use......................................................................................................8
2 Product documentation ............................................................................................92.1 About the operating Instructions ........................................................................ 9
Signs and symbols used .................................................................................................9Safety and warning notes..............................................................................................10
2.2 Technical drawings ..........................................................................................112.3 Parts list / spare parts list.................................................................................11
3 General safety regulations .....................................................................................133.1 General principles............................................................................................133.2 Important notes on the installation ...................................................................143.3 Safety during operation....................................................................................143.4 Working on the electrohydraulic actuator.........................................................14
Qualification of personnel..............................................................................................14Personal protective equipment......................................................................................15Installation, maintenance, repair ...................................................................................15
3.5 Structural modifications....................................................................................173.6 Residual risks arising out of the electrohydraulic actuator ...............................17
4 Technical description .............................................................................................19
7/22/2019 Rexroth Manual for Actuators
6/265
Inhalt
4 / 45 cce_antriebe-dt-cxe1-2x_bal_v10_en
4.1 Fields of application .........................................................................................194.2 Electrohydraulic actuator .................................................................................19
Components The schematic structure of an electrohydraulic actuator with its mostimportant components is shown on Fig. 4.1..................................................................19Function of control actuator and trip actuator................................................................21
5 Transport and storage ............................................................................................245.1 Storing / preserving electrohydraulic actuators ................................................ 24
Type of storing...............................................................................................................24Type of preservation......................................................................................................24
5.2 Lifting and transporting electrohydraulic actuators...........................................25Weight data The weight of the electrohydraulic actuator can be found on, amongothers, the installation drawing......................................................................................25Lifting gear and lifting accessories/lifting points ............................................................25
6 Installation and commissioning.............................................................................286.1 Preparations for installation..............................................................................286.2 Mounting the electrohydraulic actuator to the valve.........................................29
Mounting, aligning and fitting the actuator to the lantern. ...........................................29
6.3 Connecting the electrohydraulic actuator to the pressure line..........................306.4 Making the electrical connections of the electrohydraulic actuator ..................316.5 Commissioning the electrohydraulic actuator...................................................32
7 Operation .................................................................................................................357.1 Normal operation .............................................................................................35
8 Inspection and maintenance work.........................................................................378.1 General ............................................................................................................378.2 Inspection and maintenance schedule.............................................................398.3 Maintenance work on the electrohydraulic actuator .........................................41
9 Service addresses...................................................................................................439.1 Service points in Europe ..................................................................................43
7/22/2019 Rexroth Manual for Actuators
7/265
Contents
cce_antriebe-dt-cxe1-2x_bal_v10_en 5 / 45
9.2 Service points in America.................................................................................439.3 Service points in Asia.......................................................................................43
10 Waste disposal ........................................................................................................44Own notes
7/22/2019 Rexroth Manual for Actuators
8/265
1 Identification of the product
6 / 45 CCE_ANTRIEBE-DT-CXE1-2X_BAL_V10_EN.doc
1 Identification of the product
These operating instructions are valid for electrohydraulic
actuators of types"CGE1 2X /and CXE1...2X/...", manufactured by.Bosch Rexroth AG, Lohr am Main.
1.1 Verifying the consignment
Scope
Before mounting the electrohydraulic actuator to the valve, you
have to verify that the following parts are included in the transportpackaging:
Electrohydraulic actuator
Accessories according to packing list
Provision of documentation
If contractually agreed, the documentation and operating in-structions are delivered separately on a CD. If no separatedelivery on a CD was agreed, the documentation and the
operating instructions are delivered together with the actua-tor.
Documentation:
Scope according to table of contents
Condition when supplied
Depending on the variant ordered, the electrohydraulic actuator isshipped with the piston rod retracted or extended the limit stop byspring force. The relevant version is given in the type designation
or on the installation drawing.When shipped, the electrohydraulic actuator contains a residualamount of hydraulic oil.
Any accessory parts supplied according to the packing list are in-stalled or must be mounted by you to the electrohydraulic actuator.
A nameplate is attached to the actuators housing. It shows theexact type designation, the serial number/job order number andother important data.
Compare the serial number/job order number on the nameplate
with the serial number/job order number on the test report, which is
Check compliance ofthe delivered parts
7/22/2019 Rexroth Manual for Actuators
9/265
Identification of the product 1
cce_antriebe-dt-cxe1-2x_bal_v10_en 7 / 45
attached as Annex to these operating instructions (see chapter 1and documentation).
Inform Bosch Rexroth immediately, if
the consignment is not complete the delivered items deviate from the delivery note or the packing
list
the details on the nameplate differ from those given on the tech-nical drawing or the parts list
the serial number/job order number specified on the electrohy-draulic actuator differs from the number indicated in the test re-port.
Operating instructions, technical drawings, test reports and partslists must always be kept together.
1.2 Identifying the electrohydraulic actuator
Nameplate
Electrohydraulic actuators of types " CGE1...2X/... (extending) and CXE12X/ (retracting)can be clearly identified with the help of the nameplate.
1.3 Use according to the intended purpose
These electrohydraulic actuators serve as control or trip actuatorsfor control or trip valves on steam turbines.
They may only be used:
at places of operation, for which the design of the electrohy-draulic actuator is suitable
with the forces (on the spring package) described in the manu-facturers documents
at temperatures specified in the manufacturers documents
in rooms, for which they are suitable
in conjunction with valves for which the electrohydraulic actua-tor is rated according to the technical planning.
7/22/2019 Rexroth Manual for Actuators
10/265
1 Identification of the product
8 / 45 CCE_ANTRIEBE-DT-CXE1-2X_BAL_V10_EN.doc
1.4 Wrongful use
Any application that does not comply with the specifications is re-
garded as wrongful use.
This includes:
Places of operation, for which the electrohydraulic actuator wasnot designed
Forces (on the spring package) which do not correspond to thespecified requirements
Temperatures other than those specified in the manufacturersdocuments
Valves for which the electrohydraulic actuator is not rated ac-cording to the technical planning.
Wrongful use can result in personal injury of the operator or thirdparties. Moreover, the electrohydraulic actuator itself or other prop-erty may be damaged.
7/22/2019 Rexroth Manual for Actuators
11/265
Product documentation 2
cce_antriebe-dt-cxe1-2x_bal_v10_en 9 / 45
2 Product documentation
The following documents accompany the electrohydraulic actuator:
Scope according to table of contents
2.1 About the operating Instructions
The operating instructions include important notes on the safe andproper operation of the electrohydraulic actuator. Observing thesenotes helps to:
avoid risks
reduce repair and downtime costs
increase the reliability and service life of the actuator
The operating instructions include information about
Installation / removal
Operation
Maintenance
Repair
Transport
Waste disposal
Signs and symbols used
The text following this sign describes activities that must usuallybe carried out in the given order.
The text following this symbol describes the result of an action.
Note: After the introducing word "Note" you will find notes anduseful tips on the optimum use of the electrohydraulicactuator.
7/22/2019 Rexroth Manual for Actuators
12/265
2 Product documentation
10 / 45 CCE_ANTRIEBE-DT-CXE1-2X_BAL_V10_EN.doc
Safety and warning notes
Special safety regulations may become applicable for the individualwork to be carried out. These safety notes can be found in the op-
erating instructions for the relevant activity. They are clearly high-lighted with a warning sign (pictogram). Depending on the degreeof hazard, various signal words are used.
Signalword
Possible consequences, if safety note is not observed:
DANGER Death or severest injuries!
WARNING Death or severest injuries are possible!
CAUTION Light or minor injuries!
NOTE Material damage to the electrohydraulic actuator or the sur-roundings!
Table 2.1: Signal words and their use
Special safety notes are provided at the relevant locations. Theyare identified with the following symbols.
General hazard
This symbol refers to activities, which involve a risk of general per-sonal injury.
Risk of bruising
This symbol refers to activities, which involve the risk of bruising bytrapping fingers or hands
Suspended loads
This symbol refers to activities, where suspended load could falldown cause personal injury.
Damage to property
This symbol refers to activities, which involve the risk of compre-hensive damage to property.
Warning symbols
7/22/2019 Rexroth Manual for Actuators
13/265
Product documentation 2
cce_antriebe-dt-cxe1-2x_bal_v10_en 11 / 45
2.2 Technical drawings
The following technical drawings are included in the scope of sup-ply:
Installation drawing with dimensional data
The electrohydraulic actuator is shown completely on the instal-lation drawing. It includes all details with regard to dimensions,weights and technical data of the actuator. All dimensions arereferred to the system zero position (valve closed) of the ac-tuator. These dimensions can differ from the condition as sup-plied (actuator completely retracted or extended).
Hydraulic circuit diagram
The hydraulic circuit diagram explains the operating principle ofthe electrohydraulic actuator.
The specified item numbers are explained in the associatedparts list.
Terminal diagram
The terminal diagram explains the terminal assignment in theterminal box.
Spare parts list
(see section 2.3)
2.3 Parts list / spare parts list
The parts list is a separate list that accompanies the electrohydrau-lic actuator.It lists the components used for the relevant electrohydraulic actua-tor.
Spare components can be ordered according to the spare parts list.We recommend that corresponding spare parts be kept in stock.
7/22/2019 Rexroth Manual for Actuators
14/265
2 Product documentation
12 / 45 CCE_ANTRIEBE-DT-CXE1-2X_BAL_V10_EN.doc
Own notes
7/22/2019 Rexroth Manual for Actuators
15/265
General safety regulations 3
cce_antriebe-dt-cxe1-2x_bal_v10_en 13 / 45
3 General safety regulations
This chapter contains a summary of all important safety regula-
tions.
Everybody who is put in charge of carrying out work on theelectrohydraulic actuator must read and observe this chapter.
3.1 General principles
This electrohydraulic actuator was designed according to state ofthe art and recognized safety rules. The use of the hydraulic sys-
tem can nevertheless result in risks to life and limb of the user orthird parties or comprehensive damage to property, if:
the electrohydraulic actuator is not used according to the in-tended purpose
the electrohydraulic actuator is unauthorizedly changed ormodified
safety regulations and safety notes are not observed.
Operate the system only when it is in technically perfect conditionand in accordance with the intended use, being aware of safetyand risks and observing the present operating conditions!
Bosch Rexroth issued an EC manufacturers declaration in thesense of Directive 98/37/EC.The manufacturer declares that the supplied components / assem-blies were manufactured in accordance with applicable harmonizedstandards/specifications.Commissioning of these components / assemblies is prohibiteduntil it was established that the machine, into which these compo-nents / assembles are to be integrated, comply with the stipulationsof the EC Directive.
7/22/2019 Rexroth Manual for Actuators
16/265
3 General safety regulations
14 / 45 CCE_ANTRIEBE-DT-CXE1-2X_BAL_V10_EN.doc
3.2 Important notes on the installation
Ensure adherence to the maximum hydraulic pressure for the elec-trohydraulic actuator by taking suitable measures (e. g. pressurerelief valves).
Provide equipotential bonding!
3.3 Safety during operation
When the electrohydraulic actuator is ready for operation, do notreach into the area of the piston rod or the area, in which the actua-tor can be coupled to a steam valve! The operation of the driveinvolves a risk of injury by bruising fingers!
Never apply a hydraulic pressure to the electrohydraulic cylinderthat is higher than the permissible maximum operating pressureindicated on the electrohydraulic actuator: see installation drawing
Since hot media are transported in the system, do not touch the
electrohydraulic actuator! Risk of hand burns! If the cylinder bodyor attached parts must be touched, use heat-resistant protectivegloves!
Plug-in connections (e. g. connector sockets) may only be pluggedor unplugged when the system is disconnected from the powersupply!
3.4 Working on the electrohydraulic actuator
Qualification of personnel
Installation, maintenance, repair and troubleshooting require spe-cial knowledge and may only be carried out by qualified and spe-cifically trained personnel who are authorized to carry this work out!
Work on electrical equipment may only be carried out by anelectrical specialist or by instructed persons under the supervi-
Installation,maintenance and repair
7/22/2019 Rexroth Manual for Actuators
17/265
General safety regulations 3
cce_antriebe-dt-cxe1-2x_bal_v10_en 15 / 45
sion of an electrical specialist in accordance with electrotechni-cal rules.
Electrical specialists are persons who, due to their professionaltraining, knowledge and experience and knowledge of relevant
regulations can assess the work assigned to them, can recog-nize possible risks and take suitable precautionary measures.
Work on hydraulic componentsmay only be carried out byspecialist personnel having specific knowledge and experiencein the field of hydraulics!
Transport, assembly, installation, commissioning and waste dis-posal may only be carried out by assigned specialists.
Personal protective equipment
If required, wear suitable personal protective equipment when car-rying out work, e. g. protective gloves, helmet, protective clothing,protective goggles, safety shoes, etc.!
Installation, maintenance, repair
If work is carried out that is not authorized by Bosch Rexroththe warranty will become void!
Repairs may only be carried out by specialists of the manufac-turer! Before devices or components are opened, these andthe complete electrohydraulic actuator must be de-energized,depressurized and secured against restarting.
Servicing (maintenance and repair) on an electrohydraulic actuatorthat is installed in a system may only be carried out, if this was ex-pressly permitted by responsible persons!
Before carrying out work, depressurize system sections and pres-sure lines that are to be disconnected and let the medium drain!
Work on electrical components may only be carried out while thesystem is disconnected from the power supply.
Before installing or removing electrical connections, the latter mustbe disconnected from the power supply!
Plug-in connections: DO NOT DISCONNECT WHILE ENER-GIZED!
Transport, assembly,installation,
commissioning, wastedisposal
Before carrying outwork
7/22/2019 Rexroth Manual for Actuators
18/265
3 General safety regulations
16 / 45 CCE_ANTRIEBE-DT-CXE1-2X_BAL_V10_EN.doc
If it is required to remove protective guards or safety equipment formaintenance and repair work, these items have to be refitted andtheir function checked immediately after completion of the mainte-nance and repair work.
Before working on the electrohydraulic actuator, make sure that theactuator is disconnected from the hydraulic supply!
Let components of the electrohydraulic actuator cool down! If it isrequired to touch the electrohydraulic actuator, wear heat-resistantgloves!
Secure the electrohydraulic actuator against undesirable pressuri-zation or energization.
When transporting or removing the electrohydraulic actuator, neverstay under a suspended load.
Use lifting gear and tooling skillfully.
Use only suitable lifting gear and lifting accessories that can relia-bly hold the weight of the load!
Install and mount hydraulic lines properly. Do not mix up connec-tions! The length and quality of lines must meet the requirements.Only welded cone fittings or forming fitting systems with soft sealsand flanges are permitted.
The use of cutting ring fittings or hydraulic hoses is not per-mitted!
The springs on the electrohydraulic actuator are pretensioned. Riskof injury! The housing with integrated manifold may only be openedby specialists of the manufacturer using special accessories.
Spare parts must meet the technical requirements laid down by themanufacturer. This is ensured when genuine spare parts are used.Only genuine spare parts may therefore be used!
Always keep the warning signs on the electrohydraulic actuatorlegible! Replace damaged and illegible signs.
Strictly adhere to the maintenance and inspection intervals pre-scribed in these operating instructions and document any mainte-nance and inspections carried out.
When handling oils, greases or other chemical substances, ob-serve the safety instructions valid for the relevant product!
Never use benzene or other, easily inflammable substances for
cleaning!
While carrying outwork
7/22/2019 Rexroth Manual for Actuators
19/265
General safety regulations 3
cce_antriebe-dt-cxe1-2x_bal_v10_en 17 / 45
Do not use linty cleaning cloths!
Immediately after completion of maintenance and repair work anyremoved protective guards or safety equipment must be refittedand their function checked.
During commissioning, inspect the electrohydraulic actuator forleakage, loose connections and visible external damage. Immedi-ately rectify any detected defect!
Ensure a safe and environmentally compatible disposal of con-sumables, auxiliary materials or spilled fluids! Dispose of hazard-ous materials in accordance with their applicable operating instruc-tions!
After completion of any work, check all connections and fittings for
leakage.
After completion of all work, check the fittings on all components forproper fit.
3.5 Structural modifications
Unauthorized modifications on the electrohydraulic actuator are notpermitted for safety reasons.
Moreover, for reasons of compliance with EMC, no changes maybe carried out on the electrical installation (cables, connections,shield).
The parts and components used were specifically designed for thiselectrohydraulic actuator. We expressly point out that parts andspecial equipment that are not delivered by us are not approved byus. The installation and/or use of such products can impair safety.
3.6 Residual risks arising out of the electrohydraulic actuator
Risk of accident during transport, installation and removal of theelectrohydraulic actuator due to uncontrolled movements (e.g. fal-ling down) during lifting. Observe common safety regulations andregulations for the prevention of accidents!
Risk of injury due to contact with hot media or toxic vapors.
Risk of injury due to unintended retracting or extending of the pis-
ton rod opening/closing of the valve during commissioning,maintenance, repair or operation.
After work
7/22/2019 Rexroth Manual for Actuators
20/265
3 General safety regulations
18 / 45 CCE_ANTRIEBE-DT-CXE1-2X_BAL_V10_EN.doc
Injury caused by bruising of fingers and hands, if these are caughtbetween the electrohydraulic actuator and the valve during lower-ing. General risk of bruising when installing or removing the actua-tor from the valve.
Risk of scalding when hot oil gets into contact with the skin whenthe electrohydraulic actuator is uninstalled.
Risk of burning on hot solenoids during operation.
Work on the electrohydraulic actuator may only be carried out withsufficient lighting.
Environmental risks due to leaky points on the electrohydraulicactuator when substances that are toxic or harmful to the environ-ment escape (e.g. hydraulic oil, HFD phosphate ester) and get intothe soil or groundwater.
Risk of accident or damage to the environment when residualamounts of oil drain during the installation and removal of the elec-trohydraulic actuator.
WARNING: The electrohydraulic actuator includes a pretensionedspring package. Sudden releasing of the spring package duringremoval can lead to severest injury or death!Caution! The maintenance intervals must be observed. Duringmaintenance, warning signs must be checked, cleaned and, if re-
quired, replaced. For the installation and removal of the actuator,special tools and qualified specialists are required. The manufac-turer must in any case be contacted.
Electrical shock! Cabling work may only be carried out bytrained electrical specialists observing common safety regula-tions.
Caution:
Incorrect connections can result in destruction of the valuable elec-tronics or in uncontrolled movements in conjunction with an acti-
vated hydraulic system. The closed control loops may only be put into operation by spe-
cialist personnel with the relevant qualification.
Incorrect connections can result in excessive housing voltage andhigh discharge currents.
Danger to life due to shock currents
Risk of injury due to electrical shock
Risk of injury due to burning
7/22/2019 Rexroth Manual for Actuators
21/265
Technical description 4
cce_antriebe-dt-cxe1-2x_bal_v10_en 19 / 45
4 Technical description
4.1 Fields of application
Electrohydraulic actuators of types "CGE1 2X /andCXE1...2X/..." are used as control or trip actuators for control ortrip valves on steam turbines.
4.2 Electrohydraulic actuator
Electrohydraulic actuators are cylinders and include a pretensionedspring package. They belong to the family of double rod cylinders.The direction of action of the spring is always towards valve clos-ing (mech. failsafe).The electrohydraulic actuator is mounted to the valve to ensurecompleteley tight closing of the valve when no hydraulic pressure isapplied.
Components The schematic structure of an electrohydraulic actuator with itsmost important components is shown on Fig. 4.1.
Fig. 4.1: Components of the electrohydraulic actuator (the exemplary illustration shows a trip actuator)
7/22/2019 Rexroth Manual for Actuators
22/265
4 Technical description
20 / 45 CCE_ANTRIEBE-DT-CXE1-2X_BAL_V10_EN.doc
Electrohydraulic actuators are designed as double rod cylinders. Acoupling half is provided at the end of the piston rod. The actuatoris fitted with two separate pipe connections for pressure X1 (P) andtank X2 (T) on the housing with integrated manifold.
The actuator is hydraulically controlled via the housing. This hous-ing includes all the functions required for controlling the actuator.
The actuators comprise a spring column consisting of disk springsthat are made up to form a package. The spring package is ratedaccording to customer specifications. The package is located in thefront part of the cylinder and ensures reliable closing (of the valve)in the event of a pressure failure.The spring column is protected against external influences by a
protective tube. Condensate that may enter the housing is largelydischarged by special constructive features. Additional precautionsagainst the ingress of humidity and steam must be taken by thecustomer.
An anti-rotation feature is not provided for this actuator version.
The electrohydraulic actuator is connected to the valve by meansof the coupling half fitted. The mating piece must be provided bythe customer.
2 lifting points are fitted to the housing of the electrohydraulic ac-
tuator and 4 additional lifting points on the flange, which are ratedaccording to the weight of the actuator.The actuator can be lifted and transported at these lifting pointsusing suitable lifting gear.
Position transducers signal the position of the piston rod to theopen/closed-loop control. The aperture of the valve can be deter-mined on the basis of the piston position. For the position trans-ducers used, see parts list. More detailed information can be foundin the operating instructions for the position transducers.
The limit switches indicate the position of the cylinder piston at an
upper and/or lower end point
More detailed information about optionally installed limit switchescan be found in the parts list and the description of the limit swit-ches.
Actuator
Hydraulic control
Spring column
Anti-rotation feature
Coupling
Lifting points
Position transducers
Limit switches
(optional)
7/22/2019 Rexroth Manual for Actuators
23/265
Technical description 4
cce_antriebe-dt-cxe1-2x_bal_v10_en 21 / 45
Function of control actuator and trip actuator
The electrohydraulic actuator consists of an actuating cylinder, thedisk plate column directly fitted, the built-on hydraulic control and
integrated or attached position transducers.
The pilot oil is supplied externally from a central supply unit.
Electric power is supplied and signals are transmitted via a terminalbox.
The actuator consists of a double rod cylinder.
In the opening direction of the steam valve, the piston rod is movedin the cylinder housing by hydraulic pressurization. At the sametime, the spring column is tensioned. In the closing direction of the
steam valve, the piston rod is moved exclusively by spring force.The incurring fluid is fed from the pressure chamber through inter-nal pipes in the cylinder housing into the tank chamber.
Position transducers (ultrasonic or inductive) as well as optionallimit switches are integrated or attached for position sensing. Theconnection to the central pilot oil supply is established through twoseparate pipe connections for pressure X1 (P) and tank X2 (T).
Depending on the version, the hydraulic control integrated in thecylinder housing includes
a servo-valve of special design (two or three coils and trimmed)
for closed-loop controlling or
a directional valve for starting up the valve for the trip function.
To prevent the ingress of dirt, an additional filter is installed in thepilot oil supply of the servo-valve for pressure port X1 (P) of thecontrol actuator. Moreover, the control actuator and the trip actua-tor are fitted with a further filter to prevent spontaneous failurecaused by coarse contamination in the hydraulic medium.
Control and trip actuators are both provided with a superimposedtrip function. The relevant version is given on the circuit diagram.All control parts are connected via internal channels in the housing
with the cylinder chambers (no pipes).
General
Actuators
Hydraulic control
7/22/2019 Rexroth Manual for Actuators
24/265
4 Technical description
22 / 45 CCE_ANTRIEBE-DT-CXE1-2X_BAL_V10_EN.doc
For the controlactuator,closed-loop controlling is performed bymeans of the servo-valve which is controlled on the basis of acommand value provided by the controller. The actual value is con-tinuously verified with the help of the position transducer of the ac-tuator in a command/actual value comparison. The associated con-trol and instrumentation technology must be provided by the cus-tomer.
For the trip actuator,controlling is performed by means of the di-rectional valve, which is energized or de-energized for slow open-ing or closing of the associated valve during normal starting orstopping of the system.
In the event of turbine emergency tripping, the directional valves,which operate according to the closed-circuit current principle, arede-energized to initiate emergency tripping.
The actuating time of the actuator in the closing direction is deter-mined by VM orifice(s) .
The permissible closing speed shortly before the end position ofthe steam valve is reached is ensured by hydraulic damping. It isdetermined by a VD orifice.
Further information can be found on the enclosed hydraulic circuitdiagram.
Operating principle
7/22/2019 Rexroth Manual for Actuators
25/265
Technical description 4
cce_antriebe-dt-cxe1-2x_bal_v10_en 23 / 45
Own notes
7/22/2019 Rexroth Manual for Actuators
26/265
5 Transport and storage
24 / 45 CCE_ANTRIEBE-DT-CXE1-2X_BAL_V10_EN.doc
5 Transport and storage
5.1 Storing / preserving electrohydraulic actuators
Type of storing
The electrohydraulic actuators must be stored as follows:
Do not store in the open air, but under a roof or in a well venti-lated room. Do not expose electrohydraulic actuators to sun-light.
Protect them against rising damp: Store them on a shelf or on a
wooden pallet. Cover them with a foil to protect them against dirt and dust.
All ports of the electrohydraulic actuator must be properly plug-ged.
After the transport packaging was opened, it must be properlyre-closed for storing.
Provide an oil drip tray under the place of storage, becauseelectrohydraulic actuators are always shipped with differentamounts of residual oil.
Leave sufficient space between the individual electrohydraulicactuators.
With regard to the storage time, the following must be observed:
Longer than 1 year.
Renew internal and external preservation
Longer than 2 years.
Additional functional test required
Type of preservation
With regard to preservation, we have to distinguish between inter-nal and external preservation (corrosion protection).
The electrohydraulic actuators are dispatched with a partial fill(walls and internal parts wetted with test fluid). This means thatinternal preservation is maintained by the test oil in the cylinder aslong as the cylinder remains airtight closed.
Note: Rests of the protective agents may only be present inthe hydraulic fluid up to a maximum concentration of0.1 %.
Internal preservation
7/22/2019 Rexroth Manual for Actuators
27/265
Transport and storage 5
cce_antriebe-dt-cxe1-2x_bal_v10_en 25 / 45
Further information with regard to internal preservation can be ob-tained from the manufacturer, if required.
The following is valid for external preservation of the electrohydrau-lic actuators:
External preservation is applied in the form of coating sub-stances according to the customers specifications.
In the case of a storing period of more than six months, a corre-sponding finish coating must be applied. The selection of thecoating system (single- or 2-component system) depends onthe substances that attack the protective surface.
Further information with regard to external preservation can be ob-tained from the manufacturer, if required.
5.2 Lifting and transporting electrohydraulic actuators
The packaging of electrohydraulic actuators depends on the size ofthe cylinder. They are delivered in boxes on pallets. The consign-ment must be secured during transport.
Notes are provided on the packaging
with regard to lifting of the load (lifting points and weight)
to indicate the top and bottom of the packaging
Weight data The weight of the electrohydraulic actuator can be found on,among others, the installation drawing.
Lifting gear and lifting accessories/lifting points
Depending on the place of installation and the weight of the elec-trohydraulic actuator, suitable lifting gear and lifting accessoriesmust be selected and made available (e. g. crane, forklift truck,rope, belt).
Use only lifting gear and lifting accessories that can reliably holdthe weight of the load!
External preservation
7/22/2019 Rexroth Manual for Actuators
28/265
5 Transport and storage
26 / 45 CCE_ANTRIEBE-DT-CXE1-2X_BAL_V10_EN.doc
If maintenance work is to be carried out or the actuator uninstalled,the lifting accessories must be checked, among others, for corro-sion and proper fit of the screws, etc.
How to lift the electrohydraulic actuator by means of a crane:
Fix the rope or lifting belt to the lifting points of the actuator.Take note of the maximum load carrying capacity of the liftingpoints. Make sure that the transport bolts and lifting accesso-ries fit properly and check them for corrosion.
NOTE!Risk of damage to the electrohydraulic actuator, if it is liftedtogether with the valve!
Lift or transport the actuator only at the lifting points.
Make sure that no attachments or cables get jammed.
Lift the electrohydraulic actuator carefully.
Observe valid safety regulations and the regulations for theprevention of accidents.
WARNING!
Suspended loads!
Death or severest injuries, if persons are hit by falling loads.
Never stay under suspended loads!
Use only suitable lifting gear and lifting accessories that canreliably hold the weight of the load!
Wear protective equipment (helmet, safety shoes)!
Now you can carefully transport the electrohydraulic actuator tothe place of installation: During transport, protect the electrohy-draulic actuator against impacts and percussion.
7/22/2019 Rexroth Manual for Actuators
29/265
Transport and storage 5
cce_antriebe-dt-cxe1-2x_bal_v10_en 27 / 45
Own notes
7/22/2019 Rexroth Manual for Actuators
30/265
6 Installation and commissioning
28 / 45 CCE_ANTRIEBE-DT-CXE1-2X_BAL_V10_EN.doc
6 Installation and commissioning
6.1 Preparations for installation
How to prepare the installation of the electrohydraulic actua-tor:
Have the technical drawing and the hydraulic circuit diagram athand: Check whether the type designation and serial num-ber/job order number are identical on the nameplate and on thedrawings.
Place tools and aids ready.
Carefully lift the electrohydraulic actuator from its transport pa-ckaging.
Check, whether all accessories are available.
Mount the accessories, unless they were fitted by the manufac-turer.
Information on how to mount accessory items can be found inthe relevant instructions.
Clean the mounting faces:
The mounting faces must be thoroughly cleaned. Check, whether all fittings on the electrohydraulic actuator are
properly tightened.
Now you can start to mount the electrohydraulic actuator.
Note: Transport brackets and bolts must be kept (in casethe actuator must be returned). If required, consult themanufacturer.
7/22/2019 Rexroth Manual for Actuators
31/265
Installation and commissioning 6
cce_antriebe-dt-cxe1-2x_bal_v10_en 29 / 45
6.2 Mounting the electrohydraulic actuator to the valve
Mounting, aligning and fitting the actuator to the lantern.
The electrohydraulic actuator must be installed in the speci-fied installation orientation, with the piston rod and the valvescrew having to be aligned.
This version of the electrohydraulic actuator can and may onlybe installed according to the installation, coupling and ad-justment instructions of the customer (e. g. turbine manufac-
turer).
The installation, coupling and adjustment may only be carriedout by the manufacturer or specialists specifically trained bythe manufacturer (e. g. turbine manufacturer).
NOTE!
- Damage to property, if the electrohydraulic actuator isinstalled without being correctly aligned!
- Observe correct dimensioning of bolts!
- Adhere to minimum pretension forces (see also installa-tion drawing)
Installation of the extending version of the actuator:
Mount the coupling part provided by the customer to the valvescrew and align it to the actuator coupling according to the in-stallation instructions of the turbine manufacturer.
Insert actuator into seat/fixture.
Tighten the bolts of the flange evenly (cross-wise) while furthertensioning the spring.
This ensures that the actuator is mounted to the valve and, atthe same time, brought from the stroke end position (see over-stroke) to the system 0 position (valve closed).
Tighten the bolts on the coupling.
Observe the tightening torques given in the installation instruc-tions of the turbine manufacturer.
Mechanical mounting to the valve is now completed.
7/22/2019 Rexroth Manual for Actuators
32/265
6 Installation and commissioning
30 / 45 CCE_ANTRIEBE-DT-CXE1-2X_BAL_V10_EN.doc
Installation of the retracting version of the actuator:
Mount the coupling part provided by the customer to the valvescrew and align it to the actuator coupling according to the in-stallation instructions of the turbine manufacturer.
Insert actuator into seat/fixture and screw it on.
Tighten the bolts of the coupling evenly (cross-wise) while fur-ther tensioning the spring.
This ensures that the actuator is brought from the stroke endposition (see overstroke) to the system 0 position (valveclosed).
Observe the tightening torques given in the installation instruc-
tions of the turbine manufacturer. Mechanical mounting to the valve is now completed.
6.3 Connecting the electrohydraulic actuator to the pressureline
When connecting the electrohydraulic actuator to the pressure line,take care that the connections on the actuator housing are not in-terchanged.
NOTE!Before operating the electrohydraulic actuator for the firsttime, clean the pipes!
Foreign particles could get into the cylinder chambers, damageseals or valves and thus cause malfunction.
The actuator may only be connected, if the supply lines are clean.
Hydraulic fluid: Mineral oil (HL, HLP) to DIN 51524 orFire-resistant fluid (HFDR)depending on version
Max. permissible degree of contamination of the hydraulic
fluid to ISO / DIN 4406 (C): 18 / 16 / 13
Note: The supply lines must be flushed for cleaning. (seeseparate flushing procedure)
7/22/2019 Rexroth Manual for Actuators
33/265
Installation and commissioning 6
cce_antriebe-dt-cxe1-2x_bal_v10_en 31 / 45
During flushing or while pressure tests are being carried out,nobody is allowed to stay in the vicinity of the actuator,If necessary, take suitable precautions.
How to connect the electrohydraulic actuator to the hydraulicpipes:
Connect the ports on the actuator with the corresponding hy-draulic pipes.
Note: Pressure port: X1( P)Tank port: X2 (T)
Tighten the connections according to the valid instructions.
The electrohydraulic actuator is now connected to the hydraulic
pipes. You can pressurize the actuator.
6.4 Making the electrical connections of the electrohydraulicactuator
The electrical connections are established exclusively on the fac-tory-installed terminal box.
The electrohydraulic actuator comes with a mounted terminal box,onto which all electrical components of the electrohydraulic actua-tor were wired by Bosch Rexroth.
After transport, all plug-in connections and terminal connectionsmust be inspected for proper fit and reliable contacting. Check theexisting terminal connection diagram and the available machinedocumentation or plant documentation for plausibility. Or: The ter-minal connection diagram provided by the client and the availablemachine or plant documentation must be checked for plausibilityand observed.
The terminals are suitable for connecting copper wires of havingcross-section of 0.2 to 2.5 mm2.Other cable cross-section or otherconductor material must not be used. Select suitable conductorcross-sections!
The cable material must be appropriate for the ambient conditions.The cable sheath must be resistant to the foreseeable ambienttemperatures and the hydraulic oil used. The cables must berouted into the terminal housing through a fitting cable gland in or-der to ensure compliance with the required type of protection. Thecable must be installed properly in accordance with the require-
ments.
7/22/2019 Rexroth Manual for Actuators
34/265
6 Installation and commissioning
32 / 45 CCE_ANTRIEBE-DT-CXE1-2X_BAL_V10_EN.doc
Ensure equipotential bonding of the machine or system. A corre-sponding connection option is provided and marked accordinglywith a symbol.
PE conductors must be connected.
Cable shields must be provided in accordance with EMC require-ments (or according to the customers specifications).
EN 60204-1 must be observed! In addition, local legal stipulationsand standards as well as other applicable special regulations mustbe observed.
WARNING!Electrical shock! Cabling work may only be carried out bytrained electrical specialists observing common safety regula-tions.
Caution:
Incorrect connections can result in destruction of the valuable elec-tronics or in uncontrolled movements in conjunction with the acti-vated hydraulic system.
The closed control loops may only be put into operation by spe-cialist personnel with the relevant qualification.
Incorrect connections can result in excessive housing voltage andhigh discharge currents.
Danger to life due to shock currents
Risk of injury due to electrical shock
Risk of injury due to burning
To avert risks caused by electric current, at least the followingsafety rules must be observed:
1. Safety disconnection
2. Secure against unauthorized reclosing:
3. Make sure that the system is de-energized
4. Cover or fence off neighboring live parts
5. Ground and short-circuit
6.5 Commissioning the electrohydraulic actuator
Before commissioning, read the safety regulations in chapterFehler! Verweisquelle konnte nicht gefunden werden."Generalsafety regulations". Follow the instructions given there.
7/22/2019 Rexroth Manual for Actuators
35/265
Installation and commissioning 6
cce_antriebe-dt-cxe1-2x_bal_v10_en 33 / 45
Work on hydraulic components may only be carried out by special-ist personnel having specific knowledge and experience in the fieldof hydraulics!
Work on electrical components may only be carried out by special-ist personnel having specific knowledge and experience in the fieldof electrics!
How to commission the electrohydraulic actuator:
Check that all pipes and components are correctly connectedaccording to the installation drawing / circuit diagram.
Verify that all flanges and fittings are properly tightened.
WARNING!
Oil jets of hydraulic oil caused by incorrect connection of hy-draulic pipes!
Hydraulic oil escaping under high pressure and parts flying a-round can cause serious injury!
Before carrying out tests check the hydraulic pipes for proper fit.
Make sure that nobody stays in the direct vicinity of the elec-trohydraulic actuator while tests are being carried out.
If required, get these persons to leave the danger zone. Stopthe test, if necessary.
In the case of position transducers mounted at the side, the
protective sheet must not be removed.
Apply pressure to the pressure port of the supply pipe (port X1(P). Start with low pressure.
Verify that the electrohydraulic actuator, the hydraulic connec-tion and hydraulic pipes are leak-free.
Immediately remedy any detected defects.
If applicable, connect electrical control accessories.
Bleed the electrohydraulic actuator. As far as required, the ac-
tuator chambers can be bled via the minimess ports at both ac-tuator chambers. Work carefully.
Test the actuator for function.
The functions provided are indicated on the hydraulic circuit dia-gram.
Immediately remedy any detected defects.
Repeat the functional test, if necessary.
If required, adjust the limit switch position. Do not remove anyprotective panels. Exception: Control actuators of the extending
7/22/2019 Rexroth Manual for Actuators
36/265
6 Installation and commissioning
34 / 45 CCE_ANTRIEBE-DT-CXE1-2X_BAL_V10_EN.doc
type (position transducer fitted at the side and limit switch typeGO switch). Work carefully.
Make sure that the steam control valve or steam trip valve fittedclose absolutely leak-free and there is no other leakage. This
must be tested by a suitable leakage test and be documented.
If no deficiencies are detected and the valve closes leak-free,the electrohydraulic actuator can be commissioned.
7/22/2019 Rexroth Manual for Actuators
37/265
Operation 7
cce_antriebe-dt-cxe1-2x_bal_v10_en 35 / 45
7 Operation
7.1 Normal operation
During normal operation, no interventions by the operator are re-quired directly on the electrohydraulic actuator.
The electrohydraulic actuator is open or closed-loop controlled viathe control and instrumentation equipment of the customer.
Note: Please note that the servo-valve requires a superim-posed dither signal.Recommendations with regard to frequency and am-plitude can be found in the data sheet of the servo-valve.Frequency and amplitude must be optimized to therelevant application.The servo-valve must not assume safety functions(exclusively control function).
7/22/2019 Rexroth Manual for Actuators
38/265
7 Operation
36 / 45 CCE_ANTRIEBE-DT-CXE1-2X_BAL_V10_EN.doc
Own notes
7/22/2019 Rexroth Manual for Actuators
39/265
Inspection and maintenance work 8
cce_antriebe-dt-cxe1-2x_bal_v10_en 37 / 45
8 Inspection and maintenance work
This chapter describes inspection and maintenance work that must
exclusivelybe carried out by specifically trainedand qualifiedpersonnel.
8.1 General
Before carrying out any maintenance work, read the safetyregulations in chapter Fehler! Verweisquelle konnte nicht gefun-
den werden.General safety regulations. Follow the instruc-tions given there.
Work on hydraulic components may only be carried out by special-ist personnel having specific knowledge and experience in the fieldof hydraulics!
Work on electrical components may only be carried out by special-ist personnel having specific knowledge and experience in the fieldof electrics!
DANGER!Hydraulic oil squirting out!
Hydraulic oil squirting out under high pressure can penetrate theskin or cause severe injuries.
Before disconnecting system sections that have to be opened,switch the system off, depressurize and protect it against re-starting!
Settings for pressure switches and pressure relief valves are givenon the relevant hydraulic circuit diagrams and drawings.
Immediately report any faults detected in order that they canquickly be rectified. Take into account that small defects canturn into major defects, if they are not rectified in due time.
Notes on adjustments
7/22/2019 Rexroth Manual for Actuators
40/265
8 Inspection and maintenance work
38 / 45 CCE_ANTRIEBE-DT-CXE1-2X_BAL_V10_EN.doc
Never use the following for cleaning:
Benzene or other, easily inflammable substances
Compressed air (dirt can get into sensitive parts of the electro-hydraulic actuator)
High-pressure cleaner (dirt and humidity can get into sensitiveparts of the electrohydraulic actuator)
Large amounts of water or cleaning agents
Lint-free and clean floor cloths or rags (if required, wetted).
Common cleaning agents
Cleaning aids
7/22/2019 Rexroth Manual for Actuators
41/265
Inspection and maintenance work 8
cce_antriebe-dt-cxe1-2x_bal_v10_en 39 / 45
8.2 Inspection and maintenance schedule
The table below lists the individual activities sorted by maintenanceintervals and by assemblies/components.All maintenance and repair work must be documented.
When? Where? What? Remarks
Hydraulic componentsof the electrohydraulicactuator
Every 3months
Hydraulic pipes andfittings
Visual inspection Leakage must be immediatelyeliminated.
Remove parts that lie around.
Spilled fluid must be immediatelyremoved. Risk of slipping!
Electrical connections,cables,plug-in connectors andsockets, power cables
Visual inspection If damaged, have them replacedimmediately. Ensure correctmounting.
Visual clogging indica-tors on filters
Visual inspection When the visual clogging indicatoron a filter responds, the filter ele-ment is clogged and must be re-placed.
Every 6months
Hydraulic componentsof the electrohydraulicactuator
Hydraulic pipes andfittings
Visual inspection Leakage must be immediatelyeliminated.
Remove parts that lie around.
Spilled fluid must be immediatelyremoved. Risk of slipping!
Terminal box, electricalconnections, cables,plug-in connectors andsockets, power cables
Visual inspection If damaged, have them replacedimmediately.
Ensure correct mounting.
Visual clogging indica-tors on filters
Visual inspection When the visual clogging indicatoron a filter responds, the filter ele-ment is clogged and must be re-placed.
All components Clean dirty parts (if required,
remove any accumulated dust)
Wipe off oil immediately usinga cloth.
This simplify the detection of leak-
age and its observance.
Continued on next page
7/22/2019 Rexroth Manual for Actuators
42/265
8 Inspection and maintenance work
40 / 45 CCE_ANTRIEBE-DT-CXE1-2X_BAL_V10_EN.doc
When? Where? What? Remarks
Every 24months(not later than
every 36months)
Filters Change filter elements
Poppet, directional andservo-valves (as far asinstalled)
Check of- switching times- function
Position transducers Functional check
Limit switches Functional check
Hydraulic pipes Check all pipes and fittings forleakage and externally visibledamage!
Have any damage immediatelyrepaired!
Splashing oil can cause inju-ries!
Initiate the immediate replacementof hydraulic pipes in the case of:
- damage
- leaky spots
Hydraulic componentsof the electrohydraulicactuator
Visual inspection Leakage must be immediatelyeliminated.
Remove parts that lie around.
Spilled fluid must be immediatelyremoved. Risk of slipping!
Electrical connections,
cables,plug-in connectors andsockets, power cables,all electrical devices
Visual inspection In the case of damage (or appar-
ent signs of aging) have themimmediately replaced.
Ensure correct mounting.
Disk spring column,spring forces and guides(as far as provided)
Check for proper function
Inspection and maintenance
Take note of traces of corrosion.In the case of severe corrosion,replace.
The spring package may only bechanged at the manufacturersend!
Clogging indicators Visual inspection
Possibly functional check
Every 5 years,but not laterthan every 6years
All seals Change seals Seals may only be changed atthe manufacturers end!
In addition, same sco-pe as
Every 24 months
In addition, same scope asEvery 24 months
In addition, same scope as Every24 months
Table 8.1: Inspection and maintenance schedule
7/22/2019 Rexroth Manual for Actuators
43/265
Inspection and maintenance work 8
cce_antriebe-dt-cxe1-2x_bal_v10_en 41 / 45
8.3 Maintenance work on the electrohydraulic actuator
The complete maintenance work and repairs must be carried outby the manufacturer or specifically trained (by the manufacturer)personnel and the work carried out must be documented(see chapter 8.2).
Spare parts must meet the technical requirements laid down by the
manufacturer. This is ensured when genuine spare parts are used.
Only genuine spare partsmay be used and their use must beproven (documented).
Spare parts can be ordered from Bosch Rexroth stating the detailsgiven in the parts and spare parts lists.
For carrying out the work, you require:
usual fitters tools
floor cloths
Spare parts
Tools and aids
7/22/2019 Rexroth Manual for Actuators
44/265
8 Inspection and maintenance work
42 / 45 CCE_ANTRIEBE-DT-CXE1-2X_BAL_V10_EN.doc
Own notes
7/22/2019 Rexroth Manual for Actuators
45/265
Service addresses 9
cce_antriebe-dt-cxe1-2x_bal_v10_en 43 / 45
9 Service addresses
9.1 Service points in Europe
Bosch Rexroth AG
Service Automation
Brgermeister-Dr.-Nebel-Str. 8
D-97816 Lohr am Main
Tel.: +49 (9352) 18-1164
Fax: +49 (9352) 18-3363
9.2 Service points in America
Bosch Rexroth Corp.
Service Automation
2315 City Line Road
Bethlehem, PA 18017-2131
Tel.: +1 (610) 694- 8453Fax: +1 (610) 654- 8670
9.3 Service points in Asia
Bosch Rexroth Corporation
Service Department
Tsuchiura Head Office and Plant
5 1, Nakanuki-machi,
Tsuchiura-shi, Ibaraki-ken, 300-8588, Japan
Tel.: +81-(0)29-834-8151Fax: +81-(0)29-834-8150
7/22/2019 Rexroth Manual for Actuators
46/265
10 Waste disposal
44 / 45 CCE_ANTRIEBE-DT-CXE1-2X_BAL_V10_EN.doc
10 Waste disposal
The springs on the electrohydraulic actuator are pretensioned. Riskof injury! The housing with integrated manifold may only be openedusing special tools. If required, consult the manufacturer to obtainmore detailed information.
The actuator should only be disposed of by a certified disposalcompany in accordance with applicable laws and regulations.
Note: Take note of residual oil!Waste / non-recyclable waste / hazardous substancesmust be disposed of according to their relevant type.
7/22/2019 Rexroth Manual for Actuators
47/265
Bosch Rexroth AGZum Eisengieer 1D-97816 Lohr am MainTelefon +49 (0) 93 52/18-0Fax +49 (0) 93 52/18-1040
www.boschrexroth.de
7/22/2019 Rexroth Manual for Actuators
48/265
7/22/2019 Rexroth Manual for Actuators
49/265
7/22/2019 Rexroth Manual for Actuators
50/265
7/22/2019 Rexroth Manual for Actuators
51/265
7/22/2019 Rexroth Manual for Actuators
52/265
7/22/2019 Rexroth Manual for Actuators
53/265
7/22/2019 Rexroth Manual for Actuators
54/265
7/22/2019 Rexroth Manual for Actuators
55/265
7/22/2019 Rexroth Manual for Actuators
56/265
7/22/2019 Rexroth Manual for Actuators
57/265
7/22/2019 Rexroth Manual for Actuators
58/265
7/22/2019 Rexroth Manual for Actuators
59/265
7/22/2019 Rexroth Manual for Actuators
60/265
7/22/2019 Rexroth Manual for Actuators
61/265
7/22/2019 Rexroth Manual for Actuators
62/265
7/22/2019 Rexroth Manual for Actuators
63/265
7/22/2019 Rexroth Manual for Actuators
64/265
7/22/2019 Rexroth Manual for Actuators
65/265
7/22/2019 Rexroth Manual for Actuators
66/265
7/22/2019 Rexroth Manual for Actuators
67/265
7/22/2019 Rexroth Manual for Actuators
68/265
7/22/2019 Rexroth Manual for Actuators
69/265
7/22/2019 Rexroth Manual for Actuators
70/265
7/22/2019 Rexroth Manual for Actuators
71/265
7/22/2019 Rexroth Manual for Actuators
72/265
7/22/2019 Rexroth Manual for Actuators
73/265
7/22/2019 Rexroth Manual for Actuators
74/265
7/22/2019 Rexroth Manual for Actuators
75/265
7/22/2019 Rexroth Manual for Actuators
76/265
7/22/2019 Rexroth Manual for Actuators
77/265
7/22/2019 Rexroth Manual for Actuators
78/265
7/22/2019 Rexroth Manual for Actuators
79/265
7/22/2019 Rexroth Manual for Actuators
80/265
Item No. Ident No. Qty. Description Type
BOSCH REXROTH
BRH/ESL Hydr.Antriebstechn. - Zum Eisengieer 1 - 97816 Lohr am Main - Phone 09352/18-117
PARTS LIST FOR HYDRAULIC CIRCUIT NO.: HS-A11-N674- Key word: Docu.BHEL -
Name
Orig.:
Processor:
Quot at i on No. : UH01- 0804- 5313- B
Or der No. : 0000900005
Cust omer : Bharat Heavy El ect r i cal s Lt d.
Wei s ( SCL)
Wei s ( SCL)
El ect r ohydr aul i c act uat or EHA4 f orHPCV STV 160- 177 ( MAA12)
100 R901186386 1 HYDRAULI C CYLI NDER CGE1MF3/ 140/ 60/ . . 65F. 020 R901193252 1 PRESSURE FI LTER DRUCKFI LTER DF. 021 R901193256 1 CLOGGI NG I NDI CATOR VERSCHMUTZ- ANZEI GE VD. 030 R900716661 1 PRESSURE FI LTER DRUCKFI LTER DF. 031 R901193256 1 CLOGGI NG I NDI CATOR VERSCHMUTZ- ANZEI GE VD
. 040 R900772317 1 HY- SERVOWEGEVENTI L 4WS2EM10- 5X/ 60B11T315. 050 R900929926 1 HY- LOGI C CARTRI DGE VALVE LC 32 A40E7X/ V
. 051 R900965932 1 HY- LOGI C COVER LFA 32 WEA27- 7X/ V
. 060 R900929926 1 HY- LOGI C CARTRI DGE VALVE LC 32 A40E7X/ V
. 061 R900965932 1 HY- LOGI C COVER LFA 32 WEA27- 7X/ V
. 052 R900212093 1 HY- POPPET DI RECT VALVE DI RECT OPERATED M- 3SEW 6 C3X/ 420MG25N
. 062 R900212093 1 HY- POPPET DI RECT VALVE DI RECT OPERATED M- 3SEW 6 C3X/ 420MG25N
. 070 R900012297 1 SCREW PLUG VERSCHLUSSSCHRAUBE G
. 071 R900012297 1 SCREW PLUG VERSCHLUSSSCHRAUBE G
. 072 R900012297 1 SCREW PLUG VERSCHLUSSSCHRAUBE G
. 073 R900012297 1 SCREW PLUG VERSCHLUSSSCHRAUBE G
. 074 R900012297 1 SCREW PLUG VERSCHLUSSSCHRAUBE G
. 080 R901197075 1 OI L PAN OELWANNE 846X 360X 4
. 081 R900204613 1 PROXI MI TY SWI TCH NAEHERUNGSSCHALTER CB
7/22/2019 Rexroth Manual for Actuators
81/265
Item No. Ident No. Qty. Description Type
BOSCH REXROTH
BRH/ESL Hydr.Antriebstechn. - Zum Eisengieer 1 - 97816 Lohr am Main - Phone 09352/18-117
PARTS LIST FOR HYDRAULIC CIRCUIT NO.: HS-A11-N674- Key word: Docu.BHEL -
Name
Orig.:
Processor:
Quot at i on No. : UH01- 0804- 5313- B
Or der No. : 0000900005
Cust omer : Bharat Heavy El ect r i cal s Lt d.
Wei s ( SCL)
Wei s ( SCL)
El ect r ohydr aul i c act uat or EHA4 f orHPCV STV 160- 177 ( MAA22)
200 R901186386 1 HYDRAULI C CYLI NDER CGE1MF3/ 140/ 60/ . . 65F. 020 R901193252 1 PRESSURE FI LTER DRUCKFI LTER DF. 021 R901193256 1 CLOGGI NG I NDI CATOR VERSCHMUTZ- ANZEI GE VD. 030 R900716661 1 PRESSURE FI LTER DRUCKFI LTER DF. 031 R901193256 1 CLOGGI NG I NDI CATOR VERSCHMUTZ- ANZEI GE VD
. 040 R900772317 1 HY- SERVOWEGEVENTI L 4WS2EM10- 5X/ 60B11T315. 050 R900929926 1 HY- LOGI C CARTRI DGE VALVE LC 32 A40E7X/ V
. 051 R900965932 1 HY- LOGI C COVER LFA 32 WEA27- 7X/ V
. 060 R900929926 1 HY- LOGI C CARTRI DGE VALVE LC 32 A40E7X/ V
. 061 R900965932 1 HY- LOGI C COVER LFA 32 WEA27- 7X/ V
. 052 R900212093 1 HY- POPPET DI RECT VALVE DI RECT OPERATED M- 3SEW 6 C3X/ 420MG25N
. 062 R900212093 1 HY- POPPET DI RECT VALVE DI RECT OPERATED M- 3SEW 6 C3X/ 420MG25N
. 070 R900012297 1 SCREW PLUG VERSCHLUSSSCHRAUBE G
. 071 R900012297 1 SCREW PLUG VERSCHLUSSSCHRAUBE G
. 072 R900012297 1 SCREW PLUG VERSCHLUSSSCHRAUBE G
. 073 R900012297 1 SCREW PLUG VERSCHLUSSSCHRAUBE G
. 074 R900012297 1 SCREW PLUG VERSCHLUSSSCHRAUBE G
. 080 R901197075 1 OI L PAN OELWANNE 846X 360X 4
. 081 R900204613 1 PROXI MI TY SWI TCH NAEHERUNGSSCHALTER CB
7/22/2019 Rexroth Manual for Actuators
82/265
Item No. Ident No. Qty. Description Type
BOSCH REXROTH
BRH/ESL Hydr.Antriebstechn. - Zum Eisengieer 1 - 97816 Lohr am Main - Phone 09352/18-117
PARTS LIST FOR HYDRAULIC CIRCUIT NO.: HS-A11-N674- Key word: Docu.BHEL -
Name
Orig.:
Processor:
Quot at i on No. : UH01- 0804- 5313- B
Or der No. : 0000900005
Cust omer : Bharat Heavy El ect r i cal s Lt d.
Wei s ( SCL)
Wei s ( SCL)
El ect r ohydr aul i c act uat or EHA4 f orI PCV STV 360- 45 ( MAB12)
300 R901186387 1 HYDRAULI C CYLI NDER CGE1MF3/ 140/ 60/ . 125F. 020 R901193252 1 PRESSURE FI LTER DRUCKFI LTER DF. 021 R901193256 1 CLOGGI NG I NDI CATOR VERSCHMUTZ- ANZEI GE VD. 030 R900716661 1 PRESSURE FI LTER DRUCKFI LTER DF. 031 R901193256 1 CLOGGI NG I NDI CATOR VERSCHMUTZ- ANZEI GE VD
. 040 R900711077 1 SERVO DI RECTI ONAL VALVE 4WS2EM10- 5X/ 90B11T315. 050 R900929926 1 HY- LOGI C CARTRI DGE VALVE LC 32 A40E7X/ V
. 051 R900965932 1 HY- LOGI C COVER LFA 32 WEA27- 7X/ V
. 060 R900929926 1 HY- LOGI C CARTRI DGE VALVE LC 32 A40E7X/ V
. 061 R900965932 1 HY- LOGI C COVER LFA 32 WEA27- 7X/ V
. 052 R900212093 1 HY- POPPET DI RECT VALVE DI RECT OPERATED M- 3SEW 6 C3X/ 420MG25N
. 062 R900212093 1 HY- POPPET DI RECT VALVE DI RECT OPERATED M- 3SEW 6 C3X/ 420MG25N
. 070 R900012297 1 SCREW PLUG VERSCHLUSSSCHRAUBE G
. 071 R900012297 1 SCREW PLUG VERSCHLUSSSCHRAUBE G
. 072 R900012297 1 SCREW PLUG VERSCHLUSSSCHRAUBE G
. 073 R900012297 1 SCREW PLUG VERSCHLUSSSCHRAUBE G
. 074 R900012297 1 SCREW PLUG VERSCHLUSSSCHRAUBE G
. 080 R901198079 1 OI L PAN OELWANNE 1053X 360X 4
. 081 R900204613 1 PROXI MI TY SWI TCH NAEHERUNGSSCHALTER CB
7/22/2019 Rexroth Manual for Actuators
83/265
Item No. Ident No. Qty. Description Type
BOSCH REXROTH
BRH/ESL Hydr.Antriebstechn. - Zum Eisengieer 1 - 97816 Lohr am Main - Phone 09352/18-117
PARTS LIST FOR HYDRAULIC CIRCUIT NO.: HS-A11-N674- Key word: Docu.BHEL -
Name
Orig.:
Processor:
Quot at i on No. : UH01- 0804- 5313- B
Or der No. : 0000900005
Cust omer : Bharat Heavy El ect r i cal s Lt d.
Wei s ( SCL)
Wei s ( SCL)
El ect r ohydr aul i c act uat or EHA4 f orI PCV STV 360- 45 ( MAB22)
400 R901186387 1 HYDRAULI C CYLI NDER CGE1MF3/ 140/ 60/ . 125F. 020 R901193252 1 PRESSURE FI LTER DRUCKFI LTER DF. 021 R901193256 1 CLOGGI NG I NDI CATOR VERSCHMUTZ- ANZEI GE VD. 030 R900716661 1 PRESSURE FI LTER DRUCKFI LTER DF. 031 R901193256 1 CLOGGI NG I NDI CATOR VERSCHMUTZ- ANZEI GE VD
. 040 R900711077 1 SERVO DI RECTI ONAL VALVE 4WS2EM10- 5X/ 90B11T315. 050 R900929926 1 HY- LOGI C CARTRI DGE VALVE LC 32 A40E7X/ V
. 051 R900965932 1 HY- LOGI C COVER LFA 32 WEA27- 7X/ V
. 060 R900929926 1 HY- LOGI C CARTRI DGE VALVE LC 32 A40E7X/ V
. 061 R900965932 1 HY- LOGI C COVER LFA 32 WEA27- 7X/ V
. 052 R900212093 1 HY- POPPET DI RECT VALVE DI RECT OPERATED M- 3SEW 6 C3X/ 420MG25N
. 062 R900212093 1 HY- POPPET DI RECT VALVE DI RECT OPERATED M- 3SEW 6 C3X/ 420MG25N
. 070 R900012297 1 SCREW PLUG VERSCHLUSSSCHRAUBE G
. 071 R900012297 1 SCREW PLUG VERSCHLUSSSCHRAUBE G
. 072 R900012297 1 SCREW PLUG VERSCHLUSSSCHRAUBE G
. 073 R900012297 1 SCREW PLUG VERSCHLUSSSCHRAUBE G
. 074 R900012297 1 SCREW PLUG VERSCHLUSSSCHRAUBE G
. 080 R901198079 1 OI L PAN OELWANNE 1053X 360X 4
. 081 R900204613 1 PROXI MI TY SWI TCH NAEHERUNGSSCHALTER CB
7/22/2019 Rexroth Manual for Actuators
84/265
Item No. Ident No. Qty. Description Type
BOSCH REXROTH
BRH/ESL Hydr.Antriebstechn. - Zum Eisengieer 1 - 97816 Lohr am Main - Phone 09352/18-117
PARTS LIST FOR HYDRAULIC CIRCUIT NO.: HS-A11-N674- Key word: Docu.BHEL -
Name
Orig.:
Processor:
Quot at i on No. : UH01- 0804- 5313- B
Or der No. : 0000900005
Cust omer : Bharat Heavy El ect r i cal s Lt d.
Wei s ( SCL)
Wei s ( SCL)
El ect r ohydr aul i c act uat or EHA4 f orHP - SSV 200- 177 (MAA11)
500 R901186383 1 HYDRAULI C CYLI NDER CGE1MF3/ 140/ 60/ . 100F. 020 R901193252 1 PRESSURE FI LTER DRUCKFI LTER DF. 021 R901193256 1 CLOGGI NG I NDI CATOR VERSCHMUTZ- ANZEI GE VD. 030 R900767230 1 COVER PLATE HSA 99- 28086- ZA/ V00- D. 040 R900570174 1 HY- POPPET DI RECT VALVE DI RECT OPERATED M- 3SEW 6 U3X/ 420MG24N
. 042 R900156650 1 NOZZLE DUESE 2,. 043 R900156650 1 NOZZLE DUESE 2,
. 050 R900929926 1 HY- LOGI C CARTRI DGE VALVE LC 32 A40E7X/ V
. 051 R900965932 1 HY- LOGI C COVER LFA 32 WEA27- 7X/ V
. 060 R900929926 1 HY- LOGI C CARTRI DGE VALVE LC 32 A40E7X/ V
. 061 R900965932 1 HY- LOGI C COVER LFA 32 WEA27- 7X/ V
. 052 R900212093 1 HY- POPPET DI RECT VALVE DI RECT OPERATED M- 3SEW 6 C3X/ 420MG25N
. 062 R900212093 1 HY- POPPET DI RECT VALVE DI RECT OPERATED M- 3SEW 6 C3X/ 420MG25N
. 070 R900012297 1 SCREW PLUG VERSCHLUSSSCHRAUBE G
. 071 R900012297 1 SCREW PLUG VERSCHLUSSSCHRAUBE G
. 072 R900012297 1 SCREW PLUG VERSCHLUSSSCHRAUBE G
. 073 R900012297 1 SCREW PLUG VERSCHLUSSSCHRAUBE G
. 074 R900012297 1 SCREW PLUG VERSCHLUSSSCHRAUBE G
. 080 R901195498 1 OI L PAN OELWANNE 975X 360X 4
. 081 R900204613 1 PROXI MI TY SWI TCH NAEHERUNGSSCHALTER CB
7/22/2019 Rexroth Manual for Actuators
85/265
Item No. Ident No. Qty. Description Type
BOSCH REXROTH
BRH/ESL Hydr.Antriebstechn. - Zum Eisengieer 1 - 97816 Lohr am Main - Phone 09352/18-117
PARTS LIST FOR HYDRAULIC CIRCUIT NO.: HS-A11-N674- Key word: Docu.BHEL -
Name
Orig.:
Processor:
Quot at i on No. : UH01- 0804- 5313- B
Or der No. : 0000900005
Cust omer : Bharat Heavy El ect r i cal s Lt d.
Wei s ( SCL)
Wei s ( SCL)
El ect r ohydr aul i c act uat or EHA4 f orHP - SSV 200- 177 (MAA21)
600 R901186383 1 HYDRAULI C CYLI NDER CGE1MF3/ 140/ 60/ . 100F. 020 R901193252 1 PRESSURE FI LTER DRUCKFI LTER DF. 021 R901193256 1 CLOGGI NG I NDI CATOR VERSCHMUTZ- ANZEI GE VD. 030 R900767230 1 COVER PLATE HSA 99- 28086- ZA/ V00- D. 040 R900570174 1 HY- POPPET DI RECT VALVE DI RECT OPERATED M- 3SEW 6 U3X/ 420MG24N
. 042 R900156650 1 NOZZLE DUESE 2,. 043 R900156650 1 NOZZLE DUESE 2,
. 050 R900929926 1 HY- LOGI C CARTRI DGE VALVE LC 32 A40E7X/ V
. 051 R900965932 1 HY- LOGI C COVER LFA 32 WEA27- 7X/ V
. 060 R900929926 1 HY- LOGI C CARTRI DGE VALVE LC 32 A40E7X/ V
. 061 R900965932 1 HY- LOGI C COVER LFA 32 WEA27- 7X/ V
. 052 R900212093 1 HY- POPPET DI RECT VALVE DI RECT OPERATED M- 3SEW 6 C3X/ 420MG25N
. 062 R900212093 1 HY- POPPET DI RECT VALVE DI RECT OPERATED M- 3SEW 6 C3X/ 420MG25N
. 070 R900012297 1 SCREW PLUG VERSCHLUSSSCHRAUBE G
. 071 R900012297 1 SCREW PLUG VERSCHLUSSSCHRAUBE G
. 072 R900012297 1 SCREW PLUG VERSCHLUSSSCHRAUBE G
. 073 R900012297 1 SCREW PLUG VERSCHLUSSSCHRAUBE G
. 074 R900012297 1 SCREW PLUG VERSCHLUSSSCHRAUBE G
. 080 R901195498 1 OI L PAN OELWANNE 975X 360X 4
. 081 R900204613 1 PROXI MI TY SWI TCH NAEHERUNGSSCHALTER CB
7/22/2019 Rexroth Manual for Actuators
86/265
Item No. Ident No. Qty. Description Type
BOSCH REXROTH
BRH/ESL Hydr.Antriebstechn. - Zum Eisengieer 1 - 97816 Lohr am Main - Phone 09352/18-117
PARTS LIST FOR HYDRAULIC CIRCUIT NO.: HS-A11-N674- Key word: Docu.BHEL -
Name
Orig.:
Processor:
Quot at i on No. : UH01- 0804- 5313- B
Or der No. : 0000900005
Cust omer : Bharat Heavy El ect r i cal s Lt d.
Wei s ( SCL)
Wei s ( SCL)
El ect r ohydr aul i c act uat or EHA4 f orI PSV SSV 400- 45 ( MAB11)
700 R901186384 1 HYDRAULI C CYLI NDER CGE1MF3/ 125/ 60/ . 193F. 020 R901193252 1 PRESSURE FI LTER DRUCKFI LTER DF. 021 R901193256 1 CLOGGI NG I NDI CATOR VERSCHMUTZ- ANZEI GE VD. 030 R900767230 1 COVER PLATE HSA 99- 28086- ZA/ V00- D. 040 R900570174 1 HY- POPPET DI RECT VALVE DI RECT OPERATED M- 3SEW 6 U3X/ 420MG24N
. 042 R900156650 1 NOZZLE DUESE 2,. 043 R900156650 1 NOZZLE DUESE 2,
. 050 R900929926 1 HY- LOGI C CARTRI DGE VALVE LC 32 A40E7X/ V
. 051 R900965932 1 HY- LOGI C COVER LFA 32 WEA27- 7X/ V
. 060 R900929926 1 HY- LOGI C CARTRI DGE VALVE LC 32 A40E7X/ V
. 061 R900965932 1 HY- LOGI C COVER LFA 32 WEA27- 7X/ V
. 052 R900212093 1 HY- POPPET DI RECT VALVE DI RECT OPERATED M- 3SEW 6 C3X/ 420MG25N
. 062 R900212093 1 HY- POPPET DI RECT VALVE DI RECT OPERATED M- 3SEW 6 C3X/ 420MG25N
. 070 R900012297 1 SCREW PLUG VERSCHLUSSSCHRAUBE G
. 071 R900012297 1 SCREW PLUG VERSCHLUSSSCHRAUBE G
. 072 R900012297 1 SCREW PLUG VERSCHLUSSSCHRAUBE G
. 073 R900012297 1 SCREW PLUG VERSCHLUSSSCHRAUBE G
. 074 R900012297 1 SCREW PLUG VERSCHLUSSSCHRAUBE G
. 080 R901057391 1 OI L PAN OELWANNE 900X 600X 1
. 081 R900204613 1 PROXI MI TY SWI TCH NAEHERUNGSSCHALTER CB
7/22/2019 Rexroth Manual for Actuators
87/265
Item No. Ident No. Qty. Description Type
BOSCH REXROTH
BRH/ESL Hydr.Antriebstechn. - Zum Eisengieer 1 - 97816 Lohr am Main - Phone 09352/18-117
PARTS LIST FOR HYDRAULIC CIRCUIT NO.: HS-A11-N674- Key word: Docu.BHEL -
Name
Orig.:
Processor:
Quot at i on No. : UH01- 0804- 5313- B
Or der No. : 0000900005
Cust omer : Bharat Heavy El ect r i cal s Lt d.
Wei s ( SCL)
Wei s ( SCL)
El ect r ohydr aul i c act uat or EHA4 f orI PSV SSV 400- 45 ( MAB21)
800 R901186384 1 HYDRAULI C CYLI NDER CGE1MF3/ 125/ 60/ . 193F. 020 R901193252 1 PRESSURE FI LTER DRUCKFI LTER DF. 021 R901193256 1 CLOGGI NG I NDI CATOR VERSCHMUTZ- ANZEI GE VD. 030 R900767230 1 COVER PLATE HSA 99- 28086- ZA/ V00- D. 040 R900570174 1 HY- POPPET DI RECT VALVE DI RECT OPERATED M- 3SEW 6 U3X/ 420MG24N
. 042 R900156650 1 NOZZLE DUESE 2,. 043 R900156650 1 NOZZLE DUESE 2,
. 050 R900929926 1 HY- LOGI C CARTRI DGE VALVE LC 32 A40E7X/ V
. 051 R900965932 1 HY- LOGI C COVER LFA 32 WEA27- 7X/ V
. 060 R900929926 1 HY- LOGI C CARTRI DGE VALVE LC 32 A40E7X/ V
. 061 R900965932 1 HY- LOGI C COVER LFA 32 WEA27- 7X/ V
. 052 R900212093 1 HY- POPPET DI RECT VALVE DI RECT OPERATED M- 3SEW 6 C3X/ 420MG25N
. 062 R900212093 1 HY- POPPET DI RECT VALVE DI RECT OPERATED M- 3SEW 6 C3X/ 420MG25N
. 070 R900012297 1 SCREW PLUG VERSCHLUSSSCHRAUBE G
. 071 R900012297 1 SCREW PLUG VERSCHLUSSSCHRAUBE G
. 072 R900012297 1 SCREW PLUG VERSCHLUSSSCHRAUBE G
. 073 R900012297 1 SCREW PLUG VERSCHLUSSSCHRAUBE G
. 074 R900012297 1 SCREW PLUG VERSCHLUSSSCHRAUBE G
. 080 R901057391 1 OI L PAN OELWANNE 900X 600X 1
. 081 R900204613 1 PROXI MI TY SWI TCH NAEHERUNGSSCHALTER CB
7/22/2019 Rexroth Manual for Actuators
88/265
7/22/2019 Rexroth Manual for Actuators
89/265
7/22/2019 Rexroth Manual for Actuators
90/265
7/22/2019 Rexroth Manual for Actuators
91/265
7/22/2019 Rexroth Manual for Actuators
92/265
1/682-way cartridge valvesDirectional functions
Cartridge valves and control covers
Types LC and LFA
Sizes 16 to 160Component series 2X; 6X; 7XMaximum operating pressure 420 barMaximum flow 25000 L/min
RE 21010/03.05Replaces: 02.03
Cartridge valve type LC 25 A40E7X/Control cover type LFA 25 WEA-7X/with directional valve type 4WE 6D6X/EG24N9K4 and cable socket
H5455H5591
Table of contents
Contents see page 2
Features
Valve poppet with or without damping nose
2 area ratios
4 different springs
4 stroke limiters
Control cover with integrated poppet valve
Control cover with integrated shuttle valve
Control cover for mounting directional spool valves with orwithout integrated shuttle valve
Control cover with or without limit switch monitoring Further information:
Pilot control valves Size 6 Size 10
Directional spool valve type WE RE 23178 RE 23327
Directional poppet valve type SEW RE 22058 RE 22075
Directional poppet valve type SED RE 22049 RE 22045
7/22/2019 Rexroth Manual for Actuators
93/265
2/68 Bosch Rexroth AG Hydraulics LC; LFA RE 21010/03.05
Table of contents
Contents Page
Features 1
Function, sections, symbol 3
Mounting cavity and connection dimensions 4, 5
Technical data 6
Cartridge valve type LCOrdering code 7
Preferred types 7
Symbols 7
Technical data 8
Characteristic curves 9
Contents Page
Control cover type LFAGeneral notes on the ordering code 10, 11, 16
Preferred types 11
Basic symbols 12, 13Characteristic curves for the selection of nozzles 14
Material numbers of nozzles and plug screws 15
Fixing screws 16
Symbols and unit dimensions:
Type ..D 17, 18
Type ..H 19 to 21
Type ..G 22, 23
Type ..R; ..RF 24, 25
Type ..R; ..R2 26, 27
Type ..WEA, ..WEB 28 to 33
Type ..WEMA, ..WEMB 34 to 37
Type ..WEA8, ..WEB8 38, 39
Type ..WECA 40 to 42
Type ..WEA9 43
Type ..GWA, ..GWB 44 to 49
Type ..KWA, ..KWB 50 to 55
Type ..E 56, 57
Type ..EH2 58, 59
Type ..EWA, ..EWB 60 to 65
Inductive position switch type QM 66
Cable socket for inductive position switch type QM 66
7/22/2019 Rexroth Manual for Actuators
94/265
B
A
X
1
4
3
2
86
5; 7A1 100%
A2 7% (50%)
A3 107% (150%)
B
A
X
1
3
2
8
6
5; 7A1 100%
A2 7% (50%)
A3 107% (150%)
Hydraulics Bosch Rexroth AGRE 21010/03.05 LC; LFA 3/68
Function, sections, symbol
2-way cartridge valves are designed as elements for insertioninto compact blocks. The power part with ports A and B is in-stalled in a mounting cavity, which is standardised accordingto DlN ISO 7368, in the block and sealed by means of a cover.In most cases, the cover forms at the same time the connec-
tion between the control section of the power part and the pilotcontrol valves. By controlling the power part with appropriatepilot control valves, it can perform pressure control, directionaland throttling functions or a combination of these. Particularlyeconomic solutions can be achieved by adapting the sizes tothe different flows in the individual channels of an actuator. Avery cost-efficient solution can be obtained, if several functionsare assigned to the power part of an element.
Directional function
2-way cartridge valves mainly consist of a control cover (1) anda cartridge element (2). The control cover is provided with pi-lot bores and, depending on the required overall function, op-tionally a stroke limiter, a hydraulically controlled directional
poppet valve or a shuttle valve. Moreover, electrically oper-ated directional spool valves or directional poppet valves canbe mounted onto the control cover. The cartridge consists of abushing (3), a ring (4) (up to size 32 only), a valve poppet (5),optionally with damping nose (6) or without damping nose (7)and a closing spring (8).
Function
2-way cartridge valve operate in dependence upon pressure.Three pressurised areas are essential for the function: A1, A2,A3. The area of the valve seat is always taken as 100%. As aresult of the stepping, the annulus area A2 is 7% or 50% ofarea A2, depending on the version. Consequently, the area ra-tio A1: A2 is either 14.3:1 or 2:1. Area A3 is equal to the sum
of areas A1 + A2. Due to the different area ratios A1: A2 andthe resulting different annulus areas (A2), area A3 is either107% or 150% of area A1 on the seat that is assumed to be100%.
The following is generally valid:
Areas A1 and A2 act in the direction of opening. Area A3 andthe spring act in the direction of closing. The effective directionof the force resulting from the opening and closing forces de-termines the spool position of the 2-way cartridge valve.
The medium can flow through 2-way cartridge valves from A toB or from B to A. When area A3 is pressurised due to the pilotoil flow from channel B or external pilot oil supply, channel A isleak-free closed.
Sizes 16 to 32
Sizes 40 to 160
Type LFAD../FX..
Type LC..A
..E
../..B D
X X**
B
A
X
7/22/2019 Rexroth Manual for Actuators
95/265
9; 10
450,2
2150,2
2150,2
600,2 9; 1012 x M42; 74
400
0
,3
480
45
45
22
,5
45
45
22
,5
X
Y1
Y
5
5
R0,2 max.
62H11
R1
4,
5+0,1
40 max.(X, Y, Y1)
Rz1max 8 U Rz 20L Rz 12
Ptmax 20
L1
L20,2
L50,2D7H13; 10 4 x D5; H4
L20,2L
30,2
L40,2
L1
L40,2
L40,2L40,2 D6 max.(X, Y, Z1, Z2)
x Y
Z1
Z2
5
6
45
45
22,5
9; 10300,2
1650,2
1650,2
9; 10450,2
3000,3
380
32 max.(X, Y, Y1)
8 x M36; 62
5
X Y
5
Y1
Z1
Z2
AD1H7
WT
H8 1
5
H1(H1*)
D3(D3*)
15
H9
A
B
D2
D4H7
H7
H6
H5
H30,1
H2+0,1
A0,05
Y
7 1
7 13 2 4
X
Z
Y
Z
=
=
=
X
Y
Z
Rz1max 4
Rz1max 8
Rz1max 10
D7H13; 10
8 x D5; H4
D6 max. L20,3
L1X Y
Z2
Z15
(X, Y, Z1, Z2)
35 22,5
45
4/68 Bosch Rexroth AG Hydraulics LC; LFA RE 21010/03.05
Size 125
Sizes 80 and 100
Size 160
For indication of dimensions and explanation of positions,see page 9!
Mounting cavity and connection dimensions to DIN ISO 7368 (except for sizes 125 and 160)(nominal dimensions in mm)
Size 16 to 63
7/22/2019 Rexroth Manual for Actuators
96/265
Hydraulics Bosch Rexroth AGRE 21010/03.05 LC; LFA 5/68
Mounting cavity and connection dimensions to DIN ISO 7368(except for sizes 125 and 160)(nominal dimensions in mm)
1 Depth of fit
2 Reference dimension
3 For diameters other than D3 or (D3*) for port B, thedistance from the cover support surface to the centreof the bore must be calculated.
4 Port B can be arranged around the central axis of portA. However, care must be taken to ensure that themounting cavities and the pilot bores are not damaged.
5 Drilling for locating pin
6 Note on porting patter for size 16: Length L1 (xy axisof bores) for control cover with built-on directionalvalve is 80 mm.
7 For 45 mm fit H8 permitted!
1)Maximum dimension
Size 16 25 32 40 50 63 80 100 125 160
D1 32 45 60 75 90 120 145 180 225 300
D2 16 25 32 40 50 63 80 100 1501) 2001)
D3 16 25 32 40 50 63 80 100 125 200
(D3*) 25 32 40 50 63 80 100 125 150 2501)
D4 25 34 45 55 68 90 110 135 200 270
D5 M8 M12 M16 M20 M20 M30 M24 M30
D61) 4 6 8 10 10 12 16 20
D7 4 6 6 6 8 8 10 10
H1 34 44 52 64 72 95 130 155 192 268
(H1*) 29.5 40.5 48 59 65.5 86.5 120 142 180 243
H2 56 72 85 105 122 155 205 245 300+0.15 425+0.15
H3 43 58 70 87 100 130 1750.2 2100.2 2570.5 3700.5
H4 20 25 35 45 45 65 50 63
H5 11 12 13 15 17 20 25 29 31 45
H6 2 2.5 2.5 3 3 4 5 5 70.5 80.5
H7 20 30 30 30 35 40 40 50 40 50
H8 2 2.5 2.5 3 4 4 5 5 5.50.2 5.50.2
H9 0.5 1 1.5 2.5 2.5 3 4.5 4.5 2 2
L1 65/80 85 102 125 140 180 250 300
L2 46 58 70 85 100 125 200 245
L3 23 29 35 42.5 50 62.5
L4 25 33 41 50 58 75
L5 10.5 16 17 23 30 38
W 0.05 0.05 0.1 0.1 0.1 0.2 0.2 0.2 0.2 0.2