7
Review of TADS Data for 2011 Voltage Class Name Metric AC Transmission Outages - Failed Protection System Equipment AC Transmissi on Outages - Human Error AC Transmission Outages - Failed AC Substation Equipment AC Transmission Outages - Failed AC Circuit Equipment AC Transmissi on Outages - Lightning AC Transmissi on Outages - Contaminat ion AC Transmiss ion Outages - Foreign Interfere nce Total Element Availabil ity Percentag e (APC) Transmiss ion System Unavailab ility AC Circuit 300-399 kV Outages per Circuit 0.0305 0.0677 00.1320 0.0508 0.2067 0.1667 0.0567 0.9300 98.0276 1.9724 AC Circuit 300-399 kV Outages per 100 miles per year 0.0933 0.2073 0.4042 0.1555 0.6426 0.5183 0.1762 300-399 kV Jan-11 Dec-11 # Circuits 290 310 Circuit Miles 9601.0 9845.6 Multi-circuit Structure Miles 2755.3 Automatic Outages Circuit Data Outage Information Count Duration (hrs) Automatic 279 1908.7 Non-Automatic 788 48190.3 Outage Data FaultTypes Count % Count % Duration % No fault 10 6.80% 50 37.88% 652.07 34.16% P-P fault 0 0.00% 7 5.30% 677.6 35.50% P-G fault 135 91.84% 68 51.52% 547.45 28.68% P-P-G, 3P, or3P-G fault 2 1.36% 6 4.55% 30.02 1.57% Unknow n 0 0.00% 1 0.76% 1.53 0.08% Total 147 132 1908.67 Mom entary Sustained Outage Information Count Duratio n (hrs) Two Elements 18 319.03 Three Elements 1 13.10 Four or More Elements 2 58.75 Multiple Element Automatic Outages

Review of TADS Data for 2011

  • Upload
    franz

  • View
    40

  • Download
    0

Embed Size (px)

DESCRIPTION

Circuit Data. Outage Data. Review of TADS Data for 2011. Automatic Outages. Multiple Element Automatic Outages. Review of TADS Automatic Outage Data for 2011. Review of TADS Planned Outage Data for 2011. Review of TADS Planned Outage Data for 2011. TADS Comparison, 2011 vs 2010. - PowerPoint PPT Presentation

Citation preview

Page 1: Review of TADS Data for 2011

Review of TADS Data for 2011

Voltage Class Name Metric

AC Transmission Outages - Failed

Protection System

Equipment

AC Transmission

Outages - Human Error

AC Transmission Outages - Failed AC Substation

Equipment

AC Transmission Outages - Failed

AC Circuit Equipment

AC Transmission

Outages - Lightning

AC Transmission

Outages - Contamination

AC Transmission

Outages - Foreign

Interference

Total

Element Availability Percentage

(APC)

Transmission System

Unavailability

AC Circuit 300-399 kV

Outages per Circuit 0.0305 0.0677 00.1320 0.0508 0.2067 0.1667 0.0567 0.9300 98.0276 1.9724

AC Circuit 300-399 kV

Outages per 100 miles per year 0.0933 0.2073 0.4042 0.1555 0.6426 0.5183 0.1762 2.8918

300-399 kV Jan-11 Dec-11

# Circuits 290 310

Circuit Miles 9601.0 9845.6

Multi-circuit Structure Miles 2755.3

Automatic Outages

Circuit Data

Outage Information Count Duration (hrs)

Automatic 279 1908.7

Non-Automatic 788 48190.3

Outage Data

Fault Types Count % Count % Duration %No fault 10 6.80% 50 37.88% 652.07 34.16%P-P fault 0 0.00% 7 5.30% 677.6 35.50%P-G fault 135 91.84% 68 51.52% 547.45 28.68%P-P-G, 3P, or 3P-G fault 2 1.36% 6 4.55% 30.02 1.57%Unknown 0 0.00% 1 0.76% 1.53 0.08%Total 147 132 1908.67

Momentary Sustained

Outage Information CountDuration

(hrs)

Two Elements 18 319.03

Three Elements 1 13.10

Four or More Elements 2 58.75

Multiple Element Automatic Outages

Page 2: Review of TADS Data for 2011

Review of TADS Automatic Outage Data for 2011

8.2%

29.9%

22.4%

10.9%

3.4%

8.8%

0.7%2.7%

0.0%

0.7%12.2%

0.0%

Momentary Outage Cause Weather, excluding lightning

Lightning

Contamination

Foreign Interference

Fire

Failed AC Substation Equipment

Failed Protection System Equipment

Failed AC Circuit Equipment

Power System Condition

Human Error

Unknown

Other

7.6%

13.6%

12.9%

0.8%

10.6%19.7%

6.1%

8.3%

0.0%

14.4%

3.8% 2.3%

Sustained Outage Cause Weather, excluding lightning

Lightning

Contamination

Foreign Interference

Fire

Failed AC Substation Equipment

Failed Protection System Equipment

Failed AC Circuit Equipment

Power System Condition

Human Error

Unknown

Other

0.2% 1.5% 3.1%0.1%

36.2%

11.8%1.3%

23.3%

12.3%

8.2%

0.1% 1.8%

Sustained Outage DurationWeather, excluding lightning

Lightning

Contamination

Foreign Interference

Fire

Failed AC Substation Equipment

Failed Protection SystemEquipmentFailed AC Circuit Equipment

Power System Condition

Human Error

Unknown

Other

0

10

20

30

40

50

60

70Sustained Outages Momentary Outages

Automatic Outages By Month

Page 3: Review of TADS Data for 2011

Review of TADS Planned Outage Data for 2011

0

20

40

60

80

100

120

140

Planned & Operational Outages by Month

010002000300040005000600070008000

Planned & Operational Outage Duration by Month (Hours)

62779.6%

9411.9%

10.1%

486.1%

141.8%

00.0%

40.5%

Planned & Operational Outage CauseMaintenance andConstruction3rd Party Request

Other Planned Outage

Emergency

System Voltage LimitMitigationSystem Operating LimitMitigationOther Operational Outage 39564.23

82%

1314.973%

215.020%

320.421%

6762.0314%

00% 13.63

0%

Planned & Operational Outage Duration (Hours) Maintenance and

Construction3rd Party Request

Other Planned Outage

Emergency

System Voltage LimitMitigationSystem Operating LimitMitigationOther Operational Outage

Page 4: Review of TADS Data for 2011

Review of TADS Planned Outage Data for 2011

0.1% 0.5% 0.9%3.8%

66.1%

8.1%

20.4%

Planned & Operational Outage Count by Duration

1-5 minutes

6-10 minutes

11-30 minutes

31-120 minutes

121 minutes to 24 hours

>24 hours to 48 hours

> 48 hours

Page 5: Review of TADS Data for 2011

TADS Comparison, 2011 vs 2010

2010 2011

Outage Information Count Duration (hrs) Count Duration (hrs)

Automatic 194 1089.53 279 1908.65

Non-Automatic 572 32467.77 787 46712.4

2010 2011 2010 2011Voltage Class 300-399 kV 300-399 kV 300-399 kV 300-399 kV

Metric Outages/Number of circuits Outages/100 mi/year

AC Transmission Outages - Failed Protection System Equipment 0.0601 0.0305 0.1506 0.0926

AC Transmission Outages - Human Error 0.0141 0.0677 0.0430 0.2057

AC Transmission Outages - Failed AC Substation Equipment 0.0955 0.1320 0.2474 0.4011

AC Transmission Outages - Failed AC Circuit Equipment 0.0354 0.0508 0.0860 0.1543

AC Transmission Outages - Lightning 0.1314 0.2067 0.3872 0.6376

AC Transmission Outages - Contamination 0.1387 0.1667 0.4087 0.5142

AC Transmission Outages - Foreign Interference 0.1131 0.0567 0.3334 0.1748

Total 0.7080 0.9300 2.0865 2.8694

Element Availability Percentage (APC) 98.6450 98.0625

Transmission System Unavailability 1.3550 1.9375

Page 6: Review of TADS Data for 2011

TADS Comparison, 2011 vs 2010

0

10

20

30

40

50

60

702010 2011

Automatic Outages by Month

0

20

40

60

80

100

120

1402010 2011

Planned and Operational Outages by Month

0

1000

2000

3000

4000

5000

6000

7000

8000

9000

100002010 2011

Planned and Operational Outage Duration by Month

Page 7: Review of TADS Data for 2011

TADS Comparison, 2011 vs 2010

0

5

10

15

20

25

30

35

40

45

502010 2011

Momentary Outages by Cause

0

5

10

15

20

25

302010 2011

Sustained Outages by Cause

0

100

200

300

400

500

600

700

8002010 2011

Sustained Outage Duration by Cause