115 kVTRANSMISSIONCONDUCTORS
~5'
APP
RO
X. 3
6'-6
"7'
-0"
7'-0
"10
'-0"
6"
9'-0
" (T
YP.
)
15'-0"
DIST."X"
DIST."Y"
DIST."Z"
15'-0"MINIMUM DISTANCE
TO POLE CENTERLINETP-115
FRAMING
CONDUCTORBLOWOUTPOSITION ATMIDSPAN
100'-0" TO ROAD CENTERLINE(TYPICAL)
RIGHT-OF-WAYLINE
REV DATE DESCRIPTION
P:\0
4\19
1\15
\DW
G\F
IGU
RE
3A.D
WG
Plot
Dat
e:9/
4/20
19 1
0:41
:02
AM
Designer:Project Manager:
Phone: (712) 472-2531Project Number:
SHEET
FIGURE3A
115 kV TRANSMISSION LINESOUTH SUBSTATION
DETROIT LAKES PUBLICUTILITIES
DETROIT LAKES, MN
DJHJDL419115
ROW DETAILTYPICAL
115 kV STRUCTURETP-115
1. Conductor blowout analysis is conducted in accordance with thecriteria of the National Electric Safety Code (NESC).
2. Conductor blowout measurements are calculated at mid-span whereworst-case conductor displacement occurs.
3. Where total road ROW is less than 200' and poles are less than 15'from ROW line, TP-115B structures shall be installed.See Figure 3B for details.
4. Proposed conductor size is 336 kcmil ACSR, Linnet.
NOTES:
NESC CONDUCTOR BLOWOUT SUMMARY
POLE FRAMING = TP-115
WIND SPEED (MPH) = 48.5
APPROXIMATE MAXIMUMPOLE SPAN = 307.0 FT
"X" - BLOWOUT DISTANCE(FROM POLE CENTERLINE) = 9.07 FT
"Y" - BLOWOUT DISTANCE(FROM CONDUCTOR ATTACHMENT) = 4.07 FT
"Z" - CLEARANCE FROM ROW TODISPLACED CONDUCTOR = 5.93 FT
115 kVTRANSMISSIONCONDUCTORS
~5'
APP
RO
X. 3
4'-6
"8'
-0"
8'-0
"10
'-0"
6"
9'-0
" (T
YP.
)
10'-0"
DIST."X"
DIST."Y"
DIST."Z"
5'-0"MINIMUMDISTANCETO POLE
CENTERLINETP-115B
FRAMING
175'-0" TO ROAD CENTERLINE(TYPICAL)
RIGHT-OF-WAYLINE
CONDUCTORBLOWOUTPOSITION ATMIDSPAN
REV DATE DESCRIPTION
P:\0
4\19
1\15
\DW
G\F
IGU
RE
3B.D
WG
Plot
Dat
e:11
/6/2
019
8:58
:38
AM
Designer:Project Manager:
Phone: (712) 472-2531Project Number:
SHEET
FIGURE3B
115 kV TRANSMISSION LINESOUTH SUBSTATION
DETROIT LAKES PUBLICUTILITIES
DETROIT LAKES, MN
DJHJDL419115
ROW DETAILTYPICAL
115 kV STRUCTURETP-115B
1. Conductor blowout analysis is conducted in accordance with thecriteria of the National Electric Safety Code (NESC).
2. Conductor blowout measurements are calculated at mid-span whereworst-case conductor displacement occurs.
3. Where total road ROW is 200' or greater and poles are 15' or morefrom the ROW line, TP-115 structures shall be installed.See Figure 3A for details.
4. Proposed conductor size is 336 kcmil ACSR, Linnet.
NOTES:
NESC CONDUCTOR BLOWOUT SUMMARY
POLE FRAMING = TP-115B
WIND SPEED (MPH) = 48.5
APPROXIMATE MAXIMUMPOLE SPAN = 307.0 FT
"X" - BLOWOUT DISTANCE(FROM POLE CENTERLINE) = 0.93 FT
"Y" - BLOWOUT DISTANCE(FROM CONDUCTOR ATTACHMENT) = 4.07 FT
"Z" - CLEARANCE FROM ROW TODISPLACED CONDUCTOR = 10.93 FT
6"
10'-0
"8'
-0"
8'-0
"A
PPR
OX
. 34'
-6"
10'-0"
DIST."X"
DIST."Z"
100'-0" TO ROAD CENTERLINE(TYPICAL)
115 kVTRANSMISSIONCONDUCTORSCONDUCTOR
BLOWOUTPOSITION ATMIDSPAN
±59"
10'-0"MINIMUMDISTANCETO POLE
CENTERLINETP-115B
FRAMING
RIGHT-OF-WAYLINE
Ø=TBD
CONCRETEFOUNDATION
12" (TYP)
REV DATE DESCRIPTION
P:\0
4\19
1\15
\DW
G\F
IGU
RE
3C.D
WG
Plot
Dat
e:9/
20/2
019
2:59
:40
PM
Designer:Project Manager:
Phone: (712) 472-2531Project Number:
SHEET
FIGURE3C
115 kV TRANSMISSION LINESOUTH SUBSTATION
DETROIT LAKES PUBLICUTILITIES
DETROIT LAKES, MN
DJHJDL419115
ROW DETAILTYPICAL
115 kV STRUCTURETS-5G
1. Conductor blowout analysis is conducted in accordance with thecriteria of the National Electric Safety Code (NESC).
2. Conductor blowout measurements are calculated at mid-span whereworst-case conductor displacement occurs.
3. Proposed conductor size is 336 kcmil ACSR, Linnet.
NOTES:
NESC CONDUCTOR BLOWOUT SUMMARY
POLE FRAMING = TS-5G
WIND SPEED (MPH) = 48.5
APPROXIMATE MAXIMUMPOLE SPAN = 309.0 FT
"X" - BLOWOUT DISTANCE(FROM POLE CENTERLINE) = 6.12 FT
"Z" - CLEARANCE FROM ROW TODISPLACED CONDUCTOR = 3.88 FT
REV DATE DESCRIPTION
DETROIT LAKES PUBLIC UTILITIESDETROIT LAKES, MINNESOTA FUTURE SOUTH SUBSTATION LAYOUT
P:\0
4\19
1\15
\DW
G\F
IGU
RE
4.D
WG
Plot
Dat
e:6/
24/2
019
11:0
0:32
AM
Designer:
Project Manager:BRMPAD
Phone: (712) 472-2531Project Number: 419115
0 3-16-18 PRELIMINARY APPENDIX AFIGURE 4
LEGENDPROPERTY LINE
FENCE LINE
204'
140'
-5"
28' X 40'CONTROL
ENCLOSURE
CO
UN
TY H
IGH
WA
Y 1
7
US
HW
Y 5
9
20'-0"
30'-0
"M
IN.
X0
X1
X2
X3
H3
H2
H1
10'-0
"
161'-2"12
5'-0
"14
0'-0
"15
'-0"
140'-6"
10'-0"
142'-3"
PROPERTYLINE
40
SCALE (FT.)
0 10 20NORTH
17 16 15
20 21 22
29 28 27
32 33 34¬«34
£¤59
Lois
Ln
Stall Ln
Bayview Ln
Fairh
aven
Ln Nodaway Dr
Riverside Rd
Mead
ow Vi
ew Ln
Meadow Lake RdDako
tah Be
ach Rd
110th St
Ravenswood Beach Rd
N Melissa Dr
S Melissa Dr
130th St
260th
Ave
ST22
ST17
I0 1,000 2,000
FeetAnticipated 115kV Transmission Line Alignment
Proposed 115kV Substation Site
! ! Existing 115kV Transmission Line
Sections
Agricultural Vegetation
Aquatic Vegetation
Developed and Other Human Use
Forest and Woodland
Introduced and Semi Natural Vegetation
Nonvascular and Sparse Vascular Rock Vegetation
Open Water
Polar and High Montane Vegetation
Recently Disturbed or Modified
Semi-Desert
Shrubland and Grassland
Appendix A Figure 7Existing Land Use
Proposed 115 kV Transmission LineDetroit Lakes Public Utilites
Becker County, MN
Image Source: 2017 Farm Service Agency
R 41WT 1
38N
Project Location
28
P:\04
\191\1
5\GIS\
Land
Use
Map
.mxd
Gap Analysis Land Cover
Lake Melissa
LindLake
Meadow Lake
CottageLake
21
40
38
42
4648
44
6263
37
32
39
41
50
5455
565759 58
60
1819
24
272930 3332
35
6
36
64
52
61
5349
1
10
21
11
9
67
45
34
51
65
66
20
45
8
43
14
16
7
2826
47
1315
12
31
2223
17
25
I0 1,000 2,000
FeetAnticipated 115kV Transmission Line AlignmentProposed 115kV Substation Site
! ! Existing 115kV Transmission LineSections
ZoningNOT ZONEDAGRICULTURALRESIDENTIAL
Appendix A Figure 8County Zoning
Proposed 115 kV Transmission LineDetroit Lakes Public Utilites
Becker County, MN
Image Source: 2017 Farm Service Agency
R 41WT 1
38N
Project Location
28
P:\04
\191\1
5\GIS\
Coun
ty Zo
ning.m
xd
Lake Melissa
Meadow Lake
CottageLake
LindLake
APPENDIX A TABLE 1
ENDANGERED AND THREATENED SPECIES BECKER COUNTY
DLPU 115 kV HVLT
Common name Scientific name Group Federal status State status
A Caddisfly Oxyethira ecornuta insect none threatened
Beaked Spikerush Eleocharis rostellata vascular plant none threatened
Bog Adder's Mouth Malaxis paludosa vascular plant none endangered
Common Tern Sterna hirundo bird none threatened
Goblin Fern Botrychium mormo vascular plant none threatened
Hair-like Beak RushRhynchospora
capillaceavascular plant none threatened
Hidden-fruit
Bladderwort
Utricularia
geminiscapavascular plant none threatened
Horned Grebe Podiceps auritus bird none endangered
Louisiana
Broomrape
Orobanche ludoviciana var.
ludovicianavascular plant none threatened
Northern Long-eared
BatMyotis septentrionalis mammal threatened
special
concern
Oakes' PondweedPotamogeton
oakesianusvascular plant none endangered
Olivaceous
Spikerush
Eleocharis flavescens var.
olivaceavascular plant none threatened
Poweshiek
SkipperlingOarisma poweshiek insect endangered endangered
Pugnose Shiner Notropis anogenus fish none threatened
Ram's Head Orchid Cypripedium arietinum vascular plant none threatened
Rock Sandwort Minuartia dawsonensis vascular plant none threatened
Sheathed Pondweed Stuckenia vaginata vascular plant none endangered
Sterile Sedge Carex sterilis vascular plant none threatened
Stream Parsnip Berula erecta vascular plant none threatened
Whorled Nutrush Scleria verticillata vascular plant none threatened
Wilson's Phalarope Phalaropus tricolor bird none threatened