Upload
others
View
3
Download
0
Embed Size (px)
Citation preview
Relion® 615 series
Transformer Protection and ControlRET615 ANSIApplication Manual
Document ID: 1MAC201230-MBIssued: 01/20/2010
Revision: AProduct version: 2.0
© Copyright 2010 ABB. All rights reserved
CopyrightThis document and parts thereof must not be reproduced or copied without writtenpermission from ABB, and the contents thereof must not be imparted to a third party,nor used for any unauthorized purpose.
The software or hardware described in this document is furnished under a license andmay be used, copied, or disclosed only in accordance with the terms of such license.
TrademarksABB and Relion are registered trademarks of ABB Group. All other brand or productnames mentioned in this document may be trademarks or registered trademarks of theirrespective holders.
WarrantyPlease inquire about the terms of warranty from your nearest ABB representative.
ABB Inc.
Distribution Automation
4300 Coral Ridge Drive
Coral Springs, FL 33065, USA
Toll-free: 1 (800) 523-2620
Phone: +1 954-752-6700
Fax: +1 954 345-5329
http://www.abb.com/substationautomation
DisclaimerThe data, examples and diagrams in this manual are included solely for the concept orproduct description and are not to be deemed as a statement of guaranteed properties.All persons responsible for applying the equipment addressed in this manual mustsatisfy themselves that each intended application is suitable and acceptable, includingthat any applicable safety or other operational requirements are complied with. Inparticular, any risks in applications where a system failure and/or product failure wouldcreate a risk for harm to property or persons (including but not limited to personalinjuries or death) shall be the sole responsibility of the person or entity applying theequipment, and those so responsible are hereby requested to ensure that all measuresare taken to exclude or mitigate such risks.
This document has been carefully checked by ABB but deviations cannot becompletely ruled out. In case any errors are detected, the reader is kindly requested tonotify the manufacturer. Other than under explicit contractual commitments, in noevent shall ABB be responsible or liable for any loss or damage resulting from the useof this manual or the application of the equipment.
ConformityThis product complies with the directive of the Council of the European Communitieson the approximation of the laws of the Member States relating to electromagneticcompatibility (EMC Directive 2004/108/EC) and concerning electrical equipment foruse within specified voltage limits (Low-voltage directive 2006/95/EC). Thisconformity is the result of tests conducted by ABB in accordance with the productstandards EN 50263 and EN 60255-26 for the EMC directive, and with the productstandards EN 60255-6 and EN 60255-27 for the low voltage directive. The IED isdesigned in accordance with the international standards of the IEC 60255 series andANSI C37.90.
Table of contents
Section 1 Introduction............................................................................3This manual..............................................................................................3Intended audience....................................................................................3Product documentation.............................................................................4
Product documentation set..................................................................4Document revision history...................................................................5Related documentation........................................................................6
Symbols and conventions.........................................................................6Safety indication symbols....................................................................6Manual conventions.............................................................................7Functions, codes and symbols............................................................7
Section 2 RET615 overview................................................................11Overview.................................................................................................11
Product version history......................................................................11PCM600 and IED connectivity package version................................11
Operation functionality............................................................................12Optional features...............................................................................12
Physical hardware..................................................................................12Local HMI................................................................................................14
LCD....................................................................................................15LEDs..................................................................................................15Keypad..............................................................................................16
Web HMI.................................................................................................16Authorization...........................................................................................17Communication.......................................................................................18
Section 3 RET615 variants..................................................................21RET615 variant list.................................................................................21Presentation of standard configurations.................................................21
Standard configurations.....................................................................22Connection diagrams ........................................................................25
Standard configuration TA01: Current inputs only..................................27Applications.......................................................................................27Functions...........................................................................................27
Default I/O connections................................................................29
Table of contents
RET615 ANSI 1Application Manual
Functional diagrams..........................................................................30Functional diagrams for protection...............................................31Functional diagrams for digital fault recorder and trip circuitmonitoring.....................................................................................36Functional diagrams for control and interlocking..........................39Functional diagram for optional ARC flash detection...................43
Standard configuration TA02: Current and voltage inputs......................45Applications.......................................................................................45Functions...........................................................................................45
Default I/O connections................................................................47Functional diagrams..........................................................................48
Functional diagrams for protection...............................................49Functional diagrams for digital fault recorder and trip circuitmonitoring.....................................................................................55Functional diagrams for control and interlocking..........................58Functional diagram for voltage protections...................................62Functional diagram for optional ARC flash detection...................63
Section 4 Requirements for measurement transformers.....................65Current transformers...............................................................................65
Current transformer requirements for non-directionalovercurrent protection........................................................................65
Current transformer accuracy class and accuracy limitfactor.............................................................................................65Non-directional overcurrent protection.........................................66Example for non-directional overcurrent protection......................68
Section 5 IED physical connections....................................................69Inputs......................................................................................................69
Energizing inputs...............................................................................69Phase currents.............................................................................69Ground current.............................................................................69
Auxiliary supply voltage input............................................................69Binary inputs......................................................................................70Optional light sensor inputs...............................................................71
Outputs...................................................................................................71Outputs for tripping and controlling....................................................71Outputs for signalling.........................................................................72IRF.....................................................................................................73
Section 6 Glossary..............................................................................75
Table of contents
2 RET615 ANSIApplication Manual
Section 1 Introduction
1.1 This manual
The application manual contains application descriptions and setting guidelines sortedper function. The manual can be used to find out when and for what purpose a typicalprotection function can be used. The manual can also be used when calculating settings.
1.2 Intended audience
This manual addresses the protection and control engineer responsible for planning, pre-engineering and engineering.
The protection and control engineer must be experienced in electrical powerengineering and have knowledge of related technology, such as communication andprotocols.
1MAC201230-MB A Section 1Introduction
RET615 ANSI 3Application Manual
1.3 Product documentation
1.3.1 Product documentation set
Pla
nnin
g &
pur
chas
e
Eng
inee
ring
Inst
allin
g
Com
mis
sion
ing
Ope
ratio
n
Mai
nten
ance
Dec
omm
issi
onin
gde
inst
allin
g&
dis
posa
l
Application manual
Operation manual
Installation manual
Service manual
Engineering manual
Commissioning manual
Communication protocolmanual
Technical manual
Pla
nnin
g &
pur
chas
e
Eng
inee
ring
Inst
allin
g
Com
mis
sion
ing
Ope
ratio
n
Mai
nten
ance
Dec
omm
issi
onin
gde
inst
allin
g&
dis
posa
l
Pla
nnin
g &
pur
chas
e
Eng
inee
ring
Inst
allin
g
Com
mis
sion
ing
Ope
ratio
n
Mai
nten
ance
Dec
omm
issi
onin
gde
inst
allin
g&
dis
posa
l
Application manualApplication manual
Operation manualOperation manual
Installation manualInstallation manual
Service manualService manual
Engineering manualEngineering manual
Commissioning manualCommissioning manual
Communication protocolmanualCommunication protocolmanual
Technical manualTechnical manual
en07000220.vsd
IEC07000220 V1 EN
Figure 1: The intended use of manuals in different lifecycles
The engineering manual contains instructions on how to engineer the IEDs using thedifferent tools in PCM600. The manual provides instructions on how to set up aPCM600 project and insert IEDs to the project structure. The manual also recommendsa sequence for engineering of protection and control functions, LHMI functions as wellas communication engineering for IEC 61850 and DNP3.
The installation manual contains instructions on how to install the IED. The manualprovides procedures for mechanical and electrical installation. The chapters areorganized in chronological order in which the IED should be installed.
The commissioning manual contains instructions on how to commission the IED. Themanual can also be used by system engineers and maintenance personnel for assistance
Section 1 1MAC201230-MB AIntroduction
4 RET615 ANSIApplication Manual
during the testing phase. The manual provides procedures for checking of externalcircuitry and energizing the IED, parameter setting and configuration as well asverifying settings by secondary injection. The manual describes the process of testingan IED in a substation which is not in service. The chapters are organized inchronological order in which the IED should be commissioned.
The operation manual contains instructions on how to operate the IED once it has beencommissioned. The manual provides instructions for monitoring, controlling andsetting the IED. The manual also describes how to identify disturbances and how toview calculated and measured power grid data to determine the cause of a fault.
The service manual contains instructions on how to service and maintain the IED. Themanual also provides procedures for de-energizing, de-commissioning and disposal ofthe IED.
The application manual contains application descriptions and setting guidelines sortedper function. The manual can be used to find out when and for what purpose a typicalprotection function can be used. The manual can also be used when calculating settings.
The technical manual contains application and functionality descriptions and listsfunction blocks, logic diagrams, input and output signals, setting parameters andtechnical data sorted per function. The manual can be used as a technical referenceduring the engineering phase, installation and commissioning phase, and during normalservice.
The communication protocol manual describes a communication protocol supported bythe IED. The manual concentrates on vendor-specific implementations.
The point list manual describes the outlook and properties of the data points specific tothe IED. The manual should be used in conjunction with the correspondingcommunication protocol manual.
Some of the manuals are not available yet.
1.3.2 Document revision historyDocument revision/date Product series version HistoryA/01/20/2010 2.0 First release
Download the latest documents from the ABB web site http://www.abb.com/substationautomation.
1MAC201230-MB A Section 1Introduction
RET615 ANSI 5Application Manual
1.3.3 Related documentationName of the document Document IDModbus Communication Protocol Manual 1MAC052634-MB
DNP3 Communication Protocol Manual 1MAC052460-MB
IEC 61850 Engineering Guide 1MAC106231-MB
Installation Manual 1MAC051065-MB
Operation Manual 1MAC050592-MB
Technical Manual 1MAC050144-MB
1.4 Symbols and conventions
1.4.1 Safety indication symbols
The electrical warning icon indicates the presence of a hazard whichcould result in electrical shock.
The warning icon indicates the presence of a hazard which could resultin personal injury.
The caution icon indicates important information or warning related tothe concept discussed in the text. It might indicate the presence of ahazard which could result in corruption of software or damage toequipment or property.
The information icon alerts the reader to important facts and conditions.
The tip icon indicates advice on, for example, how to design yourproject or how to use a certain function.
Although warning hazards are related to personal injury, it should be understood thatoperation of damaged equipment could, under certain operational conditions, result in
Section 1 1MAC201230-MB AIntroduction
6 RET615 ANSIApplication Manual
degraded process performance leading to personal injury or death. Therefore, complyfully with all warning and caution notices.
1.4.2 Manual conventionsConventions used in IED manuals. A particular convention may not be used in thismanual.
• Abbreviations and acronyms in this manual are spelled out in the glossary. Theglossary also contains definitions of important terms.
• Push button navigation in the LHMI menu structure is presented by using the pushbutton icons, for example:To navigate between the options, use and .
• HMI menu paths are presented in bold, for example:Select Main menu/Settings.
• LHMI messages are shown in Courier font, for example:To save the changes in non-volatile memory, select Yes and press .
• Parameter names are shown in italics, for example:The function can be enabled and disabled with the Operation setting.
• Parameter values are indicated with quotation marks, for example:The corresponding parameter values are "Enabled" and "Disabled".
• IED input/output messages and monitored data names are shown in Courier font,for example:When the function picks up, the PICKUP output is set to TRUE.
• Dimensions are provided both in inches and mm. If it is not specifically mentionedthen the dimension is in mm.
1.4.3 Functions, codes and symbolsTable 1: Functions included in the RET615 standard configuration
Function IEC 61850 IEC 60617 ANSIProtection
Three-phase non-directional time overcurrentprotection, low stage, high-voltage side
PHLPTOC1 3I>(1) 51P (1)
Three-phase non-directional time overcurrentprotection, high stage 1, high-voltage side
PHHPTOC1 3I>>(1) 50P (1)
Three-phase non-directional time overcurrentprotection, low stage, low-voltage side
PHLPTOC2 3I>(2) 51P (2)
Three-phase non-directional time overcurrentprotection, high stage 1, low-voltage side
PHHPTOC3 3I>>(3) 50P (2)
Ground non-directional time overcurrent protection,low stage (Calculated), high-voltage side
EFLPTOC2 I0>(2) 51N (1)
Table continues on next page
1MAC201230-MB A Section 1Introduction
RET615 ANSI 7Application Manual
Function IEC 61850 IEC 60617 ANSIGround non-directional time overcurrent protection,high stage 1 (Calculated), high-voltage side
EFHPTOC3 I0>> (3) 50N (1)
Ground non-directional time overcurrent protection,high stage 1 (Calculated), low-voltage side
EFHPTOC5 I0>> (5) 50N (2)
Three-phase thermal overload protection, two timeconstants, high-voltage side
T2PTTR1 3Ith>T 49T (1)
Loss of load protection, high-voltage side LOFLPTUC1 3I< 37 (1)
Circuit breaker failure protection, low-voltage side CCBRBRF1 3I>/IoBF(1) 50BF (2)
Low impedance restricted ground fault protection,low-voltage side
LREFPNDF1 dIoLo> 87LOZREF (2)
Transformer differential protection for two windingtransformers
TR2PTDF1 3dI>T 87T
Three-phase overvoltage protection, stage 1, low-voltage side
PHPTOV1 3U>(1) 59 (2)
Three-phase undervoltage protection, stage 1, low-voltage side
PHPTUV1 3U<(1) 27 (2)
Ground overvoltage protection, low-voltage side ROVPTOV1 U0>(1) 59G (2)
Negative sequence overvoltage protection, low-voltage side
NSPTOV1 U2> 47 (2)
Directional ground-fault protection, low stage, low-voltage side
DEFLPDEF1 I0>->(1) 67/51N (2)
Three-phase directional overcurrent protection, lowstage, low-voltage side
DPHLPDOC1 3I>->(1) 67/51P (2)
Ground non-directional time overcurrent protection,low stage (Measured)
EFLPTOC1 I0>(1) 51G
Ground non-directional time overcurrent protection,high stage 1 (Measured)
EFHPTOC1 I0>> (1) 50G
Ground non-directional time overcurrent protection,low stage (Calculated), low-voltage side
EFLPTOC3 I0>(3) 51N (2)
Arc flash detector 1, low-voltage side ARCSARC1 ARC(1) AFD-1 (2)
Arc flash detector 2, low-voltage side ARCSARC2 ARC(2) AFD-2 (2)
Arc flash detector 3, low-voltage side ARCSARC3 ARC(3) AFD-3 (2)
Control
Circuit breaker control, low-voltage side CBXCBR1 I<->O CB 52 (2)
Supervision and monitoring
Circuit breaker condition monitoring, low-voltage side SSCBR1 CBCM 52CM (2)
Trip circuit monitoring 1 TCSSCBR1 TCS(1) TCM-1
Trip circuit monitoring 2 TCSSCBR2 TCS(2) TCM-2
Fuse failure supervision, low-voltage side SEQRFUF1 FUSEF 60 (2)
Measurement
Three-phase current measurement, high-voltageside
CMMXU1 3I IA,IB,IC (1)
Table continues on next page
Section 1 1MAC201230-MB AIntroduction
8 RET615 ANSIApplication Manual
Function IEC 61850 IEC 60617 ANSIThree-phase current measurement, low-voltage side CMMXU2 3I(B) IA,IB,IC (2)
Three-phase voltage measurement, low-voltage side VMMXU1 3U VA,VB,VC (2)
Sequence current measurement , high-voltage side CSMSQI1 I1,I2,I0 I1, I2, I0 (1)
Sequence current measurement , low-voltage side CSMSQI2 I1,I2,I0(B) I1, I2, I0 (2)
Sequence voltage measurement, low-voltage side VSMSQI1 U1,U2,U0 V1,V2,V0 (2)
Three-phase power and energy measurement, low-voltage side
PEMMXU1 P,E P,E (2)
Ground current measurement RESCMMXU1 I0 IG
Ground voltage measurement RESVMMXU1 U0 VG
Tap position TPOSSLTC1 TPOSM 84T
Digital fault recorder RDRE1 DR DFR
Sequence of events recorder SER SER SER
Fault recorder FLTMSTA FR FLR
Electrically latched/self resetting trip output 1 TRPPTRC1 Trip(1) 86/94-1
Electrically latched/self resetting trip output 2 TRPPTRC2 Trip(2) 86/94-2
1MAC201230-MB A Section 1Introduction
RET615 ANSI 9Application Manual
10
Section 2 RET615 overview
2.1 Overview
RET615 is a dedicated transformer protection and control IED (intelligent electronicdevice) for power transformers, unit and step-up transformers including power generator-transformer blocks in utility and industry power distribution systems. RET615 is amember of ABB’s Relion® product family and part of its 615 protection and controlproduct series. The 615 series IEDs are characterized by their compactness andwithdrawable design.
Re-engineered from the ground up, the 615 series has been designed to unleash the fullpotential of the IEC 61850 standard for communication and interoperability betweensubstation automation devices. Once the standard configuration IED has been given theapplication-specific settings, it can directly be put into service.
The 615 series IEDs support a range of communication protocols including IEC 61850with GOOSE messaging, Modbus® and DNP3.
2.1.1 Product version historyProduct version Product history2.0 Product released
2.1.2 PCM600 and IED connectivity package version• Protection and Control IED Manager PCM600 Ver. 2.0 SP2 or later• IED Connectivity Package RET615 ANSI Ver. 1.0 or later
• Parameter Setting• Firmware Update• Disturbance Handling• Signal Monitoring• Lifecycle Traceability• Signal Matrix• Communication Management• Configuration Wizard• Label Printing
1MAC201230-MB A Section 2RET615 overview
RET615 ANSI 11Application Manual
• IED User Management• Differential Characteristics Tool• IED Users
Download connectivity packages from the ABB web site http://www.abb.com/substationautomation
2.2 Operation functionality
2.2.1 Optional features• Arc flash detector with three sensors
• Optional arc flash detectors can be added to all standard configurations.• Additional BIOs: 7BI+3BO
• Optional BIO (7 BI + 3 BO) can be added to all standard configurations.• Autorecloser
2.3 Physical hardware
The IED consists of two main parts: plug-in unit and case. The plug-in unit contentdepends on the ordered functionality.
Table 2: Plug-in unit and case
Main unit Slot ID Content optionsPlug-inunit
- HMI Large (8 lines, 16 characters)
X100 Auxiliary power/BO module 48-250 V DC/100-240 V AC; or 24-60 V DC2 normally-open PO contacts1 change-over SO contact1 normally-open SO contact2 double-pole PO contacts with TCS1 dedicated internal fault output contact
X110 BIO module 8 binary inputs4 signal output contacts
X120 AI/BI module 6 phase current inputs (1/5A)1 residual current input (1/5A)
Table continues on next page
Section 2 1MAC201230-MB ARET615 overview
12 RET615 ANSIApplication Manual
Main unit Slot ID Content optionsCase X130 Optional BIO module With configuration TA01
6 binary inputs3 signal output contacts
AI/BI module With configuration TA023 phase voltage inputs (100, 110, 115 or 120 V)1 residual voltage input (100, 110, 115 or 120 V)4 binary inputs
X000 Optional communicationmodule
See the technical manual for details about differenttypes of communication modules.
The rated input levels are selected in the IED software for phase current and groundcurrent. The binary input thresholds 18...176 V DC are selected by adjusting the IED'sparameter settings.
The optional BIO module can be added in the IED to all standardconfigurations.
The connection diagrams of different hardware modules are presented in this manual.
See the installation manual for more information about the case and theplug-in unit.
Table 3: Number of physical connections in standard configurations
Conf. Analog channels Binary channels CT VT BI BO
TA01 7 0 8 or 14 10 or 13
TA02 7 4 12 10
1MAC201230-MB A Section 2RET615 overview
RET615 ANSI 13Application Manual
2.4 Local HMI
A070704-ANSI V1 EN
Figure 2: LHMI
The LHMI of the IED contains the following elements:
• Display• Buttons• LED indicators• Communication port
The LHMI is used for setting, monitoring and controlling.
Section 2 1MAC201230-MB ARET615 overview
14 RET615 ANSIApplication Manual
2.4.1 LCDThe LHMI includes a graphical LCD that supports two character sizes. The charactersize depends on the selected language.
Table 4: Characters and rows on the view
Character size Rows in view Characters on rowLarge, variable width (13x14pixels)
4 rows8 rows with large screen
min 8
The display view is divided into four basic areas.
1 2
3 4
A070705-ANSI V2 EN
Figure 3: Display layout
1 Header
2 Icon
3 Content
4 Scroll bar (displayed when needed)
2.4.2 LEDsThe LHMI includes three protection indicators above the display: Normal, Pickup andTrip.
There are also 11 matrix programmable alarm LEDs on front of the LHMI. The LEDscan be configured with PCM600 and the operation mode can be selected with theLHMI, WHMI or PCM600.
1MAC201230-MB A Section 2RET615 overview
RET615 ANSI 15Application Manual
There are two additional LEDs which are embedded into the control buttons and. They represent the status of the circuit breaker.
2.4.3 KeypadThe LHMI keypad contains push-buttons which are used to navigate in different viewsor menus. With the push-buttons you can give open or close commands to one primaryobject, for example, a circuit breaker, disconnector or switch. The push-buttons arealso used to acknowledge alarms, reset indications, provide help and switch betweenlocal and remote control mode.
A071176-ANSI V1 EN
Figure 4: LHMI keypad with object control, navigation and command push-buttons and RJ-45 communication port
2.5 Web HMI
The WHMI enables the user to access the IED via a web browser. The supported webbrowser version is Internet Explorer 7.0 or later.
WHMI is enabled by default.
WHMI offers several functions.
• Alarm indications and event lists• System supervision• Parameter settings
Section 2 1MAC201230-MB ARET615 overview
16 RET615 ANSIApplication Manual
• Measurement display• Oscillographic records• Phasor diagram
The menu tree structure on the WHMI is almost identical to the one on the LHMI.
A070754-ANSI V1 EN
Figure 5: Example view of the WHMI
The WHMI can be accessed locally and remotely.
• Locally by connecting your laptop to the IED via the front communication port.• Remotely over LAN/WAN.
2.6 Authorization
The user categories have been predefined for the LHMI and the WHMI, each withdifferent rights and default passwords.
The default passwords can be changed with Administrator user rights.
User authorization is disabled by default but WHMI always usesauthorization.
1MAC201230-MB A Section 2RET615 overview
RET615 ANSI 17Application Manual
Table 5: Predefined user categories
Username User rightsVIEWER Read only access
OPERATOR • Selecting remote or local state with (only locally)• Changing setting groups• Controlling• Clearing alarm and indication LEDs and textual indications
ENGINEER • Changing settings• Clearing event list• Clearing DFRs• Changing system settings such as IP address, serial baud rate or
DFR settings• Setting the IED to test mode• Selecting language
ADMINISTRATOR • All listed above• Changing password• Factory default activation
For user authorization for PCM600, see PCM600 documentation.
2.7 Communication
The IED supports different communication protocols: IEC 61850, Modbus® and DNP3.0 Level 2 - all using TCP/IP. DNP3 and Modbus also support serial communication.Operational information and controls are available through these protocols.
The IEC 61850 communication implementation supports all monitoring and controlfunctions. Additionally, parameter setting and DFR records can be accessed using theIEC 61850 protocol. Oscillographic files are available to any Ethernet-basedapplication in the standard COMTRADE format. Further, the IED can send andreceive binary signals from other IEDs (so called horizontal communication) using theIEC61850-8-1 GOOSE profile, where the highest performance class with a totaltransmission time of 3 ms is supported. The IED meets the GOOSE performancerequirements for tripping applications in distribution substations, as defined by the IEC61850 standard. The IED can simultaneously report events to five different clients onthe station bus.
All communication connectors, except for the front port connector, are placed onintegrated optional communication modules. The IED can be connected to Ethernet-
Section 2 1MAC201230-MB ARET615 overview
18 RET615 ANSIApplication Manual
based communication systems via the RJ-45 connector (100BASE-TX) or the fiber-optic LC connector (100BASE-FX).
1MAC201230-MB A Section 2RET615 overview
RET615 ANSI 19Application Manual
20
Section 3 RET615 variants
3.1 RET615 variant list
3.2 Presentation of standard configurations
Functional diagramsThe functional diagrams describe the IED's functionality from the protection,measuring, condition monitoring, recording, control and interlocking perspective.Diagrams show the default functionality with simple symbol logics forming principlediagrams. The external connections to primary devices are also shown, stating thedefault connections to measuring transformers. The positive measuring direction istowards the outgoing feeder, away from the bus bar.
The functional diagrams are divided into sections with each section constituting onefunctional entity. The external connections are also divided into sections. Only therelevant connections for a particular functional entity are presented in each section.
Protection function blocks are part of the functional diagram. They are identified basedon their ANSI function number/acronym, but the IEC based symbol and the IEC 61850names are also included. Some function blocks are used several times in theconfiguration. To separate the blocks from each other, the IEC 61850 name and ANSIfunction number are appended with a running number, that is an instance number, fromone upwards. The IED’s internal functionality and the external connections areseparated with a dashed line presenting the IED’s physical casing.
Signal MatrixWith Signal Matrix in PCM600 the user can modify the standard configurationaccording to the actual needs. The IED is delivered from the factory with defaultconnections described in the functional diagrams for BI's, BO's, function to functionconnections and alarm LEDs. Signal Matrix has a number of different page views,designated as follows:
• Binary input• Binary output• Functions
1MAC201230-MB A Section 3RET615 variants
RET615 ANSI 21Application Manual
There are four IED variant-specific setting groups. Parameters can be set independentlyfor each setting group.
The active setting group (1...4) can be changed with a parameter. The active settinggroup can also be changed via a binary input if the binary input is enabled for this. Toenable the change of the active setting group via a binary input, connect a free binaryinput with PCM600 to the ActSG input of the SGCB-block.
Table 6: Binary input states and corresponding active setting groups
BI state Active setting groupOFF 1
ON 2
The active setting group defined by a parameter is overridden when a binary input isenabled for changing the active setting group.
3.2.1 Standard configurationsThe transformer protection and control IED RET615 is available with two alternativestandard configurations.
Table 7: Standard configurations
Description Std conf.Current input only TA01
Current and voltage inputs TA02
Table 8: Supported functions
Standard configuration functionality Stdconfig.TA01
Stdconfig.TA02
Protection
Three-phase non-directional time overcurrent protection, low stage, high voltage side ● ●
Three-phase non-directional time overcurrent protection, high stage 1, high voltageside
● ●
Three-phase non-directional time overcurrent protection, low stage, low voltage side ● ●
Three-phase non-directional time overcurrent protection, high stage 1, low voltageside
● ●
Ground non-directional time overcurrent protection, low stage (Measured) ● ●
Ground non-directional time overcurrent protection, low stage (Calculated), lowvoltage side
● ●
Ground non-directional time overcurrent protection, high stage 1 (Measured) ● ●
Table continues on next page
Section 3 1MAC201230-MB ARET615 variants
22 RET615 ANSIApplication Manual
Standard configuration functionality Stdconfig.TA01
Stdconfig.TA02
Ground non-directional time overcurrent protection, low stage(Calculated), highvoltage side
● ●
Ground non-directional time overcurrent protection, high stage 1 (Calculated), highvoltage side
● ●
Ground non-directional time overcurrent protection, high stage 1 (Calculated), lowvoltage side
● ●
Three-phase thermal overload protection, two time constants, high voltage side ● ●
Three-phase overvoltage protection, stage 1, low voltage side ●
Three-phase undervoltage protection, stage 1, low voltage side ●
Ground overvoltage protection, low voltage side ●
Negative sequence overvoltage protection, low voltage side ●
Directional ground-fault protection, low stage, low voltage side ●
Three-phase directional overcurrent protection, low stage, low voltage side ●
Loss of load protection, high voltage side ●
Low impedance restricted ground fault protection, low voltage side ● ●
Transformer differential protection for two winding transformers ● ●
Arc flash detection with three sensors ○ ○
Circuit breaker failure protection, low voltage side ● ●
Control
Circuit breaker control, low voltage side ● ●
Supervision and monitoring
Circuit breaker condition monitoring, low voltage side ● ●
Trip-circuit monitoring of two trip circuits ● ●
Fuse failure supervision, low voltage side ●
Measurement
Three-phase current measurement, high voltage side ● ●
Three-phase current measurement, low voltage side ● ●
Three-phase voltage measurement, low voltage side ●
Sequence current measurement , high voltage side ● ●
Sequence current measurement , low voltage side ● ●
Sequence voltage measurement, low voltage side ●
Ground current measurement ● ●
Ground voltage measurement ●
Three-phase power and energy measurement, low voltage side ●
Tap position ● ●
Disturbance recorder ● ●
Table continues on next page
1MAC201230-MB A Section 3RET615 variants
RET615 ANSI 23Application Manual
Standard configuration functionality Stdconfig.TA01
Stdconfig.TA02
Sequence of events recorder ● ●
Fault recorder ● ●
Electrically latched/self resetting trip output 1 and 2 ● ●
● = Included, ○ = Optional at the time of the order
Section 3 1MAC201230-MB ARET615 variants
24 RET615 ANSIApplication Manual
3.2.2 Connection diagrams
16
151918
10
111213
14
22
23
24
SO2
TCM-2
PO4
SO1
TCM-1
PO317
21
20
X120
1
23
45
67
89
1011
1213
14IG_A
IA_A
IB_A
IC_A
X110
12
56
7
89
10 BI 6
BI 5
BI 4
BI 3
BI 1
BI 8
BI 712
13
11
ABC
S1
S2
P1
P2
X100
67
89
10
2
1
3
45
PO2
PO1
IRF
+
-Vaux
X110
16
14
15
19
17
18
22
20
21
SO3
SO2
SO1
24
23SO4
X130
12
10
11
15
13
14
18
16SO3
SO2
SO1
17
1)
4 BI 23
X13012
3
45
6 BI 4
BI 3
BI 2
BI 1
BI 6
BI 58
9
7
X13Light sensor input 1
1)
X14Light sensor input 2
1)
X15Light sensor input 3
1)
1) Optional
1)
52
IC_B
IA_B
IB_B
S2
S1
52
abc
P2
P1
S2
S1
PositiveCurrentDirection
P2
P1
2) 100BaseFX / LC or 100BaseTX / RJ-45
GUID-7A4484F0-D803-4B11-8C2D-E10E4D6B07F6 V1 EN
Figure 6: Connection diagram for configuration TA01: current inputs only
1MAC201230-MB A Section 3RET615 variants
RET615 ANSI 25Application Manual
16
151918
10
111213
14
22
23
24
SO2
TCM-2
PO4
SO1
TCM-1
PO317
21
20
X120
1
23
45
67
89
1011
1213
14IG_A
IA_A
IB_A
IC_A
S1
S2
P1
P2
X100
67
89
10
2
1
3
45
PO2
PO1
IRF
+
-Vaux
X110
16
14
15
19
17
18
22
20
21
SO3
SO2
SO1
24
23SO4
X11012
3
45
6 BI 4
BI 3
BI 2
BI 1
BI 6
BI 58
9
7
X13Light sensor input 1
1)
X14Light sensor input 2
1)
X15Light sensor input 3
1)
1) Optional
52
IC_B
IA_B
IB_B
S2
S1
52
abc
P2
P1
S2
S1
PositiveCurrentDirection
P2
P1
X13012
56
78
9
10
VB
VA
BI 4
BI 3
BI 1
VG
VC
1213
11
ABC
4 BI 23
Not in use
16
15
18
17
14
dnda
a
nN
A
2) 100BaseFX / LC or 100BaseTX / RJ-45
GUID-CB8FEE82-9CA3-4293-A06C-F93C1F887DBB V1 EN
Figure 7: Connection diagram for configuration TA02: current and voltage inputs
Section 3 1MAC201230-MB ARET615 variants
26 RET615 ANSIApplication Manual
3.3 Standard configuration TA01: Current inputs only
3.3.1 ApplicationsThe standard configuration includes three-phase differential, short-circuit, overcurrent,earth-fault, thermal overload and negative phase-sequence protection in powertransformer feeders. The standard configuration is mainly intended for protection of the2W-power transformer at medium voltage applications.
The IED with this standard configuration is delivered from the factory with defaultsettings and parameters. The end-user flexibility for incoming, outgoing and internalsignal designation within the IED enables this configuration to be further adapted todifferent primary circuit layouts and the related functionality needs by modifying theinternal functionality using PCM600.
3.3.2 FunctionsTable 9: Functions included in the RET615 standard configuration TA01
Function IEC 61850 IEC 60617 ANSIIncluded functions
Three-phase current measurement, high-voltageside
CMMXU1 3I IA,IB,IC (1)
Three-phase current measurement, low-voltageside
CMMXU2 3I(B) IA,IB,IC (2)
Sequence current measurement , high-voltageside
CSMSQI1 I1,I2,I0 I1, I2, I0 (1)
Sequence current measurement , low-voltage side CSMSQI2 I1,I2,I0(B) I1, I2, I0 (2)
Three-phase non-directional time overcurrentprotection, low stage, high-voltage side
PHLPTOC1 3I>(1) 51P (1)
Three-phase non-directional time overcurrentprotection, high stage 1, high-voltage side
PHHPTOC1 3I>>(1) 50P (1)
Three-phase non-directional time overcurrentprotection, low stage, low-voltage side
PHLPTOC2 3I>(2) 51P (2)
Three-phase non-directional time overcurrentprotection, high stage 1, low-voltage side
PHHPTOC3 3I>>(3) 50P (2)
Ground non-directional time overcurrentprotection, low stage (Calculated), high-voltageside
EFLPTOC2 I0>(2) 51N (1)
Ground non-directional time overcurrentprotection, high stage 1 (Calculated), high-voltage side
EFHPTOC3 I0>> (3) 50N (1)
Ground non-directional time overcurrentprotection, high stage 1 (Calculated), low-voltageside
EFHPTOC5 I0>> (5) 50N (2)
Table continues on next page
1MAC201230-MB A Section 3RET615 variants
RET615 ANSI 27Application Manual
Function IEC 61850 IEC 60617 ANSIThree-phase thermal overload protection, twotime constants, high-voltage side
T2PTTR1 3Ith>T 49T (1)
Circuit-breaker failure protection, low-voltage side CCBRBRF1 3I>/IoBF(1) 50BF (2)
Trip circuit monitoring 1 TCSSCBR1 TCS(1) TCM-1
Trip circuit monitoring 2 TCSSCBR2 TCS(2) TCM-2
Electrically latched/self-resetting trip output 1 TRPPTRC1 Trip(1) 86/94-1
Electrically latched/self-resetting trip output 2 TRPPTRC2 Trip(2) 86/94-2
Disturbance recorder RDRE1 DR DFR
Sequence of events recorder SER SER SER
Fault recorder FLTMSTA FR FLR
Circuit-breaker control, low-voltage side CBXCBR1 I<->O CB 52 (2)
Loss of load protection, high-voltage side LOFLPTUC1 3I< 37 (1)
Circuit-breaker condition monitoring, low-voltageside
SSCBR1 CBCM 52CM (2)
Low impedance restricted ground fault protection,low-voltage side
LREFPNDF1 dIoLo> 87LOZREF (2)
Transformer differential protection for two windingtransformers
TR2PTDF1 3dI>T 87T
Tap position TPOSSLTC1 TPOSM 84T
Ground current measurement RESCMMXU1 I0 IG
Ground non-directional time overcurrentprotection, low stage (Measured)
EFLPTOC1 I0>(1) 51G
Ground non-directional time overcurrentprotection, high stage 1 (Measured)
EFHPTOC1 I0>> (1) 50G
Ground non-directional time overcurrentprotection, low stage (Calculated), low-voltageside
EFLPTOC3 I0>(3) 51N (2)
Optional functions
Arc flash detector 1, low-voltage side ARCSARC1 ARC(1) AFD-1 (2)
Arc flash detector 2, low-voltage side ARCSARC2 ARC(2) AFD-2 (2)
Arc flash detector 3, low-voltage side ARCSARC3 ARC(3) AFD-3 (2)
Section 3 1MAC201230-MB ARET615 variants
28 RET615 ANSIApplication Manual
3.3.2.1 Default I/O connections
Table 10: Default connections for binary inputs
Binary input Description Connector pinsX110-BI1 Blocking of O/C high stage (high voltage) and instantaneous
stage (low voltage)X110-1,2
X110-BI2 External protection trip X110-3,4
X110-BI3 Circuit breaker low gas pressure indication X110-5,6
X110-BI4 Circuit breaker spring charged indication X110-7,6
X110-BI5 High-voltage side disconnector closed X110-8,9
X110-BI6 High-voltage side disconnector open X110-10,9
X110-BI7 High-voltage side circuit breaker closed X110-11,12
X110-BI8 High-voltage side circuit breaker open X110-13,12
X130-BI1 BCD sign bit (tap changer position) X130-1,2
X130-BI2 BCD bit 1 LSB X130-2,3
X130-BI3 BCD bit 2 X130-4,5
X130-BI4 BCD bit 3 X130-5,6
X130-BI5 BCD bit 4 X130-7,8
X130-BI6 BCD bit 5 MSB X130-8,9
Table 11: Default connections for binary outputs
Binary output Description Connector pinsX100-PO1 Close high-voltage circuit breaker X100-6,7
X100-PO2 Breaker failure backup trip to upstream breaker X100-8,9
X100-SO1 General start indication X100-10,11,(12)
X100-SO2 General operate indication X100-13,14
X100-PO3 Open circuit breaker/trip coil 1 high voltage X100-15-19
X100-PO4 Open circuit breaker/trip coil 2 low voltage X100-20-24
X110-SO1 Overcurrent operate alarm X110-14,15,16
X110-SO2 Differential protection operate alarm X110-17,18,19
X110-SO3 Earth fault operate alarm X110-20,21,22
X110-SO4Thermal overload and negative phase-sequence protectionoperate alarm X110-23,24
1MAC201230-MB A Section 3RET615 variants
RET615 ANSI 29Application Manual
Table 12: Order codes
LED label Order code optionsLED label 1 HATAAAAxxAE1BNNxXC
HATAAAAxxBE1BNNxXC
HATAAAAxx3E1BNNxXC
LED label 2 HATAAAAxxFE1BNNxXC
HATAAAAxxGE1BNNxXC
Table 13: Configuration option LED assignments
LED label 1 LED label 2LED1 Phase A Phase A
LED2 Phase B Phase B
LED3 Phase C Phase C
LED4 Neutral/Ground Neutral/Ground
LED5 Time Time
LED6 Instantaneous Instantaneous
LED7 Differential/REF Differential/REF
LED8
LED9 Breaker failure/Alarm Breaker failure/Alarm
LED10 Overload alarm/Trip Overload alarm/Trip
LED11 Arc flash detection
3.3.3 Functional diagramsThe functional diagrams describe the default input, output, alarm LED and function-to-function connections. The default connections can be viewed and changed withPCM600 according to the application requirements, if necessary.
The analog channels have fixed connections towards the different function blocksinside the IED’s standard configuration.
The analog channels are assigned to different functions as shown in the functionaldiagrams. The common signal marked with IA,IB,IC(1) represents the three phasecurrents of the high-voltage side of the transformer and IA,IB,IC(2) represents thethree phase currents of the low-voltage side of the transformer. The signal marked withIG represents the measured neutral current measured between the neutral point of thetransformer and grounding.
Section 3 1MAC201230-MB ARET615 variants
30 RET615 ANSIApplication Manual
3.3.3.1 Functional diagrams for protection
The functional diagrams describe the IED’s protection functionality in detail andaccording to the factory set default connections.
X120
1
23
45
67
89
1011
1213
14IG
IA (2)
IB (2)
IC (2)
ABC
S1
S2
P1
P2
52
IC (1)
IA (1)
IB (1)
S2
S1
52
abc
P2
P1
S2
S1
PositiveCurrentDirection
P2
P1
LV
HV
TRANSFORMER DIFFERENTIAL PROTECTION
TR2PTDF1
TRIPIA,IB,IC (1)
87T3dI>T
OPR_LSIA,IB,IC (2)
OPR_HSBLOCK
BLKD2HBLK_OPR_LS-T
BLKDD5HBLK_OPR_HS-T
BLKDWAV
LED7
GUID-D739D833-1759-446D-A5B0-224D0DBC2F3D V1 EN
Figure 8: Stabilized and instantaneous differential protection for 2W-transformers
The stabilized differential protection for 2W-transformers (87T) provides protection ofpower transformer unit including, for example, winding short-circuit and interturnfaults. The IED compares the phase currents on both sides of the object to be protected.If the differential current of the phase currents in one of the phases exceed the settingof the stabilized operation characteristic or the instantaneous protection stage of thefunction, the function provides an operate signal.
For transformers having an on-line tap changer, the tap position information isrecommended to be used in differential protection, as the ratio difference of tapchanger movements can be corrected in 87T.
The position indication of the OLTC is recommended for differential protection toincrease sensitivity.
1MAC201230-MB A Section 3RET615 variants
RET615 ANSI 31Application Manual
All operate signals are connected to the Master Trip 1 and 2 and also to the alarm LEDs.
3I>(1)
PICKUPIA, IB, ICBLOCK
ENA_MULT
51P(1)
PHLPTOC2PICKUPIA, IB, IC
BLOCK
ENA_MULT
51P(2)
PHHPTOC3PICKUPIA, IB, IC
BLOCK
ENA_MULT
50P(2)
PHHPTOC1PICKUPIA, IB, IC
BLOCK
ENA_MULT
50P(1)INRPHAR1
BLK2HIA, IB, IC
BLOCK
INR
TRIP_PhA
86/94 LED
TRIP_PhA
OR
LED 1
86/94 LEDOR
LED 2
PHASE B TRIP
86/94 LEDOR
LED 3
PHASE C TRIP
TRIP_PhA
TRIP_PhB
TRIP_PhC
TRIP_PhBTRIP_PhB
TRIP_PhCTRIP_PhC
TRIP_PhA
TRIP_PhB
TRIP_PhC
TRIP_PhA
TRIP_PhB
TRIP_PhC
TRIP_PhA
TRIP_PhB
TRIP_PhC
PHASE A TRIP
Trip1
LEDPTRC
LEDPTRC
TRIP
TRIP
TRIP
TRIP
NOTE 1
NOTE 1
NOTE 1
NOTE 1
NOTE 1: AVAILABLE ONLY FOR LED INDICATION.
AVAILABLE FOR MAPPING USINGSMT TOOL IN PCM TO ANY PROTECTION,DEPENDING ON APPLICATION.
OR
LED 6
INSTANTANEOUS TRIP
PHASE OVERCURRENT PROTECTION INDICATION
OR
LED 5
TIME TRIP
symbolIEC60617
Number/AcronymANSI Device/Function
LEDPTRC
Trip1
Trip1
PHLPTOC1
3I>(2)
3I>>(1)
3I>>(3)
3I2f>
identificationIEC61850
GUID-666C5CBF-5EE1-46D4-86E2-A069FDD1061F V1 EN
Figure 9: Phase overcurrent protection
Two stages for both high-voltage and low-voltage sides as a total of four overcurrentstages are offered for overcurrent and short-circuit protection. The inrush detectionblock’s (INR) output BLK2H provides the possibility to either block the function ormultiply the active settings for any of the shown protection function blocks.
A selective backup overcurrent protection can be achieved by using blockings betweenhigh-voltage side and low-voltage side overcurrent stages. This kind of blockingscheme enables coordinated overlapping of overcurrent protection zones.
Section 3 1MAC201230-MB ARET615 variants
32 RET615 ANSIApplication Manual
EFLPTOC2PICKUP
BLOCK
51N(1)
EFLPTOC3PICKUP
BLOCK
51N(2)
EFHPTOC5PICKUP
BLOCK
50N(2)
PICKUP
BLOCK
50N(1)
ORTRIP
TRIP
TRIP
TRIP
EFHPTOC3
BI 1 (Blocking)
IA, IB, IC
BLOCK
ENA_MULT
IA, IB, IC
BLOCK
ENA_MULT
IA, IB, IC
BLOCK
ENA_MULT
IA, IB, IC
BLOCK
ENA_MULT
OR
TRIP_NEUT
86/94 LED
TRIP_NEUT
Trip 1
NEUTRAL OVERCURRENT PROTECTION
LED4
TRIPNEUTRAL/GROUND
LED 6
TRIPINSTANTANEOUS
LED 5
TIME TRIP
LEDPTRC
I0>(2)
I0>>(5)
I0>>(3)
I0>(3)
OR
GUID-4570E2D8-8FDD-4ABB-82B0-7CB64557E765 V1 EN
Figure 10: Non-directional ground-fault protection
EFLPTOC1PICKUPIG
BLOCK
ENA_MULT
51G
EFHPTOC1PICKUPIG
BLOCK
ENA_MULT
50G
TRIP_NEUT
86/94LED
TRIP_NEUT
OR
LED4
TRIP
TRIP
TRIPNEUTRAL / GROUND
TRIP(1)
LED6
TIME TRIP
INSTANTANEOUS
GROUND OVERCURRENT PROTECTION
BI 1 (Blocking)
LED5
TRIP
LEDPTRC
I0>(1)
I0>>(1)
GUID-EF0171DC-E505-4BE1-B4C9-5DEA35E48733 V1 EN
Figure 11: Ground overcurrent protection
1MAC201230-MB A Section 3RET615 variants
RET615 ANSI 33Application Manual
Two stages are offered for non-directional ground-fault protection for high and lowside of the transformers. In addition, there are two stages of ground fault protectionbased on measured ground current.
LREFPNDF1
PICKUP3I
IG
87LOZREF(2)
TRIP
dIoLo>
REF_PICKUP
REF_TRIP
LED4
RESTRICTED EARTH FAULT PROTECTION
LED7
GUID-58D2DD05-C1F9-47C0-8DBB-DA27BD8E1162 V1 EN
Figure 12: Restricted low-impedance earth-fault protection
The configuration includes restricted low-impedance earth-fault protection function forlow-voltage side of two-winding power transformers, 87LOZREF(2). The numericaldifferential current stage operates exclusively on earth faults occurring in the protectedarea, that is, in the area between the phase and neutral current transformers. A groundfault in this area appears as a differential current between the residual current of thephase currents and the neutral current of the conductor between the WYE-point of thetransformer and the ground.
Section 3 1MAC201230-MB ARET615 variants
34 RET615 ANSIApplication Manual
THERMAL OVERLOAD PROTECTION
T2PTTR1TRIP
ALARM
IA, IB, IC
BLK_CLOSE
PICKUP
BLK_OPR
ENA_MULT
LED10
OVERLOAD ALARM
OR
3Ith>T
GUID-156D07E7-E15D-481C-8A78-F9E7988F3568 V1 EN
Figure 13: Three-phase thermal overload protection for power transformers
Three-phase thermal overload protection for power transformers, 49T(1), providesindication on overload situations, and it is connected to the CT's on high side of thetransformer.
PO2
89
X100
BREAKER FAILURE PROTECTION
Circuit Breaker failureprotection trip toassociated breaker(s)
TRRET
TRBU
IA, IB, IC
PICKUP
POSCLOSE
BREAKER FAILURE
CB_FAULT_AL
CB_FAULT
IN
BLOCK
LED9
50BF(2)
51P(2) Trip
50P(2) Trip
51G Trip
51N(2) Trip
50G Trip
AFD-2(2) Trip
87T Trip
AFD-3(2) Trip
87LOZREF(2) Trip
50N(2) Trip
AFD-1(2) Trip
OR
NOTES: 1) DASHED LINE INDICATES OPTIONALINPUT BASED ON CONFIGURATION.
3I>/Io>BF(1)
BI 2 (Breaker Close Status)
CCBRBRF1
GUID-0DDB74B6-38CE-4A5A-8240-55A409B6AD91 V1 EN
Figure 14: Circuit-breaker failure protection
The circuit-breaker failure protection 50BF(2) is initiated via the start input by anumber of different protection stages in the IED. 50BF(2) offers different operating
1MAC201230-MB A Section 3RET615 variants
RET615 ANSI 35Application Manual
modes associated with the circuit-breaker position and the measured phase and residualcurrents.
50BF(2) has two operating outputs: TRRET and TRBU. The TRRET operate output isused for retripping its own circuit breaker. The TRBU output is used for retrippingboth the high-voltage and low-voltage side circuit breakers through Master Trip 1 and2. The TRBU operate output signal is connected to the output PO2 (X100: 8-9). LED 6is used for backup (TRBU) operate indication.
3.3.3.2 Functional diagrams for digital fault recorder and trip circuit monitoring
DIGITAL FAULT RECORDER
DREC
DFR
AI#2
AI#1
AI#4
AI#3
AI#6
AI#5
AI#8
AI#7
AI#10
AI#9
AI#12
AI#11
IA(1)-A
IB(1)-A
IC(1)-A
IG-A
IA(2)-A
IB(2)-A
IC(2)-A
Disabled
DR
Disabled
Disabled
Disabled
Disabled
GUID-6F8418F8-B7FB-4975-8FAC-1401809BE9C5 V1 EN
Figure 15: Digital fault recorder, AI#1...12
Section 3 1MAC201230-MB ARET615 variants
36 RET615 ANSIApplication Manual
DREC
DFR
BI#2
BI#1
BI#4
BI#3
BI#6
BI#5
BI#8
BI#7
BI#10
BI#9
BI#12
BI#11
BI#14
BI#13
BI#16
BI#15
BI#17
51P(1) Trip
50P(1) Trip
51P(2) Trip
50P(2) Trip
51G Trip
50N(2) Trip
Spare
Spare
49T(1) Trip
49T(1) AlmThm
50BF(2) OpEx
50BF(2) OpIn
BI#18
BI#20
BI#19
BI#22
BI#21
BI#24
BI#23
BI#25
AFD-1(2) FADet
AFD-2(2) FADet
AFD-3(2) FADet
AFD-2(2) Trip
AFD-1(2) Trip
Spare
AFD-3(3) Trip
Spare
BI#26
BI#27
BI#28
Spare
Spare
Spare
BI#30
BI#29
BI#31
BI#32Spare
TCM-1 Alarm
Spare
TCM-2 Alarm
Spare
DR
51N(1) Trip
51N(2) Trip
50G Trip
50N(1) Trip
NOTES: 1) DASHED LINE INDICATES OPTIONAL INPUT BASED ON CONFIGURATION.
GUID-8C5D6FC7-8639-4FCB-B3DC-87D6097A0342 V1 EN
Figure 16: Digital fault recorder, BI#1...32
1MAC201230-MB A Section 3RET615 variants
RET615 ANSI 37Application Manual
DREC
DFR
BI#34
BI#33
BI#36
BI#35
BI#38
BI#37
BI#40
BI#39
BI#42
BI#41
BI#44
BI#43
BI#46
BI#45
BI#48
BI#47
BI#49
Spare
52CM(2) TRV_T_OP_ALM
52CM(2) TRV_T_CL_ALM
52CM(2) Alarm
52CM(2) CB_LIFE_ALM
BI#50
BI#52
BI#51
BI#54
BI#53
BI#56
BI#55
BI#57
BI#58
BI#59
BI#60
BI#62
BI#61
BI#63
BI#64
X110-7X110-5X110-3
X110-6X110-4X110-2 X110-8
Spare
Spare
Spare
Spare
37(1) Trip
87LOZREF(2) Trip
87T Trip
DIGITAL FAULT RECORDER
DR
X110-1 X130-1
X130-2
X130-3
X130-4
X130-5
X130-6
Spare
Spare
Spare
Spare
NOTES: 1) DASHED LINE INDICATES OPTIONAL INPUT BASED ON CONFIGURATION.
Spare
Spare
GUID-832D1BCB-342C-4539-A6CF-45BE6B110E6F V1 EN
Figure 17: Digital fault recorder, BI#33...64
The digital fault recorder has 64 digital inputs. All pickup and trip signals from theprotection stages are routed to trigger the digital fault recorder or alternatively only tobe recorded by the digital fault recorder depending on the parameter settings.
Section 3 1MAC201230-MB ARET615 variants
38 RET615 ANSIApplication Manual
BI 2 (CB Close Status) OROR86/94-1 Trip
TRIP CIRCUIT MONITORING
TCM-1
ALARMBLOCK
TCSSCBR1
86/94-2 TripLED9
TRIP CIRCUIT FAILURE
TCM-2
ALARMBLOCK
TCSSCBR2
TCS(1)
TCS(2)
GUID-61C004AA-FD1D-4C9E-A63B-919119E20B62 V1 EN
Figure 18: Trip circuit monitoring
Two separate TCM functions have been included: TCM-1 for PO3 (X100:16-19) andTCM-2 for PO4 (X100:20-23).
3.3.3.3 Functional diagrams for control and interlocking
MASTER TRIP 1 LOGIC
16
151918TCM-1
PO317
51P(1) Trip50P(1) Trip51N(1) Trip50N(1) Trip49T(1) Trip87T Trip87LOZREF(2) Trip
X100+
OR
OpenSignal to
86/94-1
TRIPCL_LKOUT
BLOCKTRIP
RST_LKOUT
With lock-out mode selection
TRPPTRC1OR
BI4
52 (2) EXE_OP
Trip Coil 1
Breaker
2)
NOTES: 1) NON-LATCHED MODE AS DEFAULT.
Trip(1)
GUID-15DD976C-E8B7-4D23-B156-A41CDB744C8B V1 EN
Figure 19: Master trip 1 logic
1MAC201230-MB A Section 3RET615 variants
RET615 ANSI 39Application Manual
22
23
24TCM-2
PO421
20
MASTER TRIP 2 LOGIC
51P(2) Trip50P(2) Trip51G Trip51N(2) Trip50G Trip
AFD-2(2) Trip
50BF(2) TripAFD-3(2) Trip
87T Trip87LOZREF(2) Trip
50N(2) TripAFD-1(2) Trip
20X100
+
OR
OpenSignal to
86/94-2
TRIP
CL_LKOUT
BLOCK
TRIP
RST_LKOUT
With lock-out mode selection
TRPPTRC2OR
BI4
52 (2) EXE_OP
Trip Coil 2
Breaker
2)
NOTES: 1) DASHED LINE INDICATES OPTIONALINPUT BASED ON CONFIGURATION.
2) NON-LATCHED MODE AS DEFAULT.
Trip(2)
GUID-A5B923B1-6134-43A7-A264-9A934A522CA2 V1 EN
Figure 20: Master trip 2 logic
The trip signals from the protections are connected to the two trip output contacts PO3(X100:15-19) and PO4 (X100:20-24) via the corresponding Master Trips 86/94-1 and86/94-2. Open control commands to the circuit breaker from local or remote CBXCBR1-exe_op are connected directly to the output PO3 (X100:16-19).
86/94-1 and 2 provide the lockout/latching function, event generation and the tripsignal duration setting. If the lockout operation mode is selected, one binary input canbe reassigned to the RST_LKOUT input of the Master Trip to enable external resetwith a push button.
BI 3 (Breaker Open Status)BI 2 (Breaker Close Status)
Always True
OR
67
PO1
+
X100
79 CLOSE_CB
CIRCUIT BREAKER CONTROL AND INTERLOCKING52 EXE_OP
52(2)
SELECTEDENA_OPEN
ENA_CLOSE
BLK_OPEN
BLK_CLOSE
EXE_OP
EXE_CL
OPENPOS
CLOSEPOS
EXE_OP
EXE_CL
OPENPOS
CLOSEPOS
OKPOS
CBXCBR1
CloseBreaker
X110
56
7BI 4
BI 3PRES_ALM_INPRES_LO_INSPR_CHR_STSPR_CHRRST_IPOW
TRV_T_OP_ALMTRV_T_CL_ALMDIFTRVTOPALMDIFTRVTCLALMSPR_CHR_ALM
OPR_ALMOPR_LO
IPOW_ALMIPOW_LO
CB_LIFE_ALMMON_ALM
PRES_ALMPRES_LO
OPENPOSINTERMPOSCLOSEPOS
BLOCKPOSOPEN
52CM(2)CBCM
OR
LED9
(CB CONDMONITOR)
POSCLOSE
RST_CB_WEAR
CB Spring Charged
GAS Pressure Alarm
SSCBR1
I<->O CB
GUID-E0814F4D-61DD-4324-BF97-41D502857F55 V1 EN
Figure 21: Circuit breaker control and interlocking
Section 3 1MAC201230-MB ARET615 variants
40 RET615 ANSIApplication Manual
The circuit breaker closing is enabled when the ENA_CLOSE input is activated. TheENA_CLOSE input can be activated by the configuration logic, which is acombination of the status of the Master Trip Logics. The open operation is always enabled.
If the ENA_CLOSE and BLK_CLOSE signals are completely removedfrom the breaker control function block 52(2) with PCM600, thefunction assumes that the breaker close commands are allowedcontinuously.
The circuit breaker condition monitoring function (52CM) supervises the circuitbreaker status based on the binary input information connected and measured currentlevels. The function introduces various supervision methods. The correspondingsupervision alarm signals are routed to LED 9.
COMMON PICKUP SIGNAL
LEDPTRC1
86/94 LED
TPGAPC1
TP-1
PICKUP
TRIP
PICKUP
TRIP
PICKUP
TRIP
PICKUP
TRIP
Pickup SignalSO#1 (X100:10-11-12)
1) THERE ARE FOUR PULSE TIMERS AVAILABLE-ONE OF THEM IS USED FOR DEFAULT CONFIGURATIONS.ALL PULSE TIMERS INCLUDING TP-1 CAN BE MAPPEDFOR SPECIFIC APPLICATIONS USING SMT IN PCM TOOLS.
NOTE:
1)
Trip1 TP-1
GUID-B48DB1BC-8B98-4413-8D58-9980404EB9AD V1 EN
Figure 22: Common pickup signal
1MAC201230-MB A Section 3RET615 variants
RET615 ANSI 41Application Manual
TRPPTRC1
PICKUP
TRIP
PICKUP
TRIP
TRPPTRC2
PICKUP
TRIP
PICKUP
TRIP
Trip SignalSO#2 (X100:13-14-15)
Trip(1)
Trip(2)
GUID-C56EFFDC-0D03-4F95-A632-4D1D33E2BB1A V1 EN
Figure 23: Common trip signal
The signal outputs from the IED are connected to give dedicated information onpickups and trips.
• Pickup of any protection function SO1 (X100:10-12)• Trip of any protection function SO2 (X100:13-15).
The TP-1 is a timer and used for setting the minimum pulse length for the outputs.
Section 3 1MAC201230-MB ARET615 variants
42 RET615 ANSIApplication Manual
TAP CHANGER POSITION INDICATION
TPOSSLTC1
SIGN_BIT
BI1BI0
BI4BI5
BI2BI3
TPOSM
X130
12
3
45
6BI 4
BI 3
BI 2
BI 1
BI 6
BI 58
9
7
BCD BIT 5
BCD BIT 4
BCD BIT 3
BCD BIT 2
BCD BIT 1
BCD SIGN BIT
GUID-952728EB-55D7-4D9B-A85C-A0A9314E4827 V1 EN
Figure 24: Tap changer position indication
To increase the sensitivity of the stabilized differential function, the tap positioninformation from the tap changer is connected to the IED via the tap changer positionindication function 84T. 84T is connected to the binary inputs of the X130 BIO card.84T uses binary-coded methods to generate the integer value of the tap changer position.
3.3.3.4 Functional diagram for optional ARC flash detection
Optional ARC flash detectors (AFD 1-3) are included in the standard configuration.The ARC flash detection offers individual function blocks for each of the three ARCsensors that can be connected to the IED. Each ARC protection function block has twodifferent operation modes, with or without the phase current check.
1MAC201230-MB A Section 3RET615 variants
RET615 ANSI 43Application Manual
ARCSARC1
TRIP
ARC_FLT_DET
IA, IB, IC
BLOCK
OPR_MODE
REM_FLT_ARC
IG
ARCSARC2
TRIP
ARC_FLT_DET
IA, IB, IC
BLOCK
OPR_MODEREM_FLT_ARC
IG
ARCSARC3
TRIP
ARC_FLT_DET
IA, IB, IC
BLOCK
OPR_MODE
REM_FLT_ARC
IG
LED11
ARC(1)
ARC(2)
ARC(3)
GUID-14D00EE3-5F20-4E67-9174-675DB88AAA02 V1 EN
Figure 25: Arc flash detection
Trip signals from the ARC protection function blocks are connected to the Master TripLogic and also to the alarm LED 11 as a common arc flash detection.
Section 3 1MAC201230-MB ARET615 variants
44 RET615 ANSIApplication Manual
3.4 Standard configuration TA02: Current and voltageinputs
3.4.1 ApplicationsThe standard configuration includes three-phase differential, short-circuit, overcurrent,earth-fault, thermal overload and negative phase-sequence protection in powertransformer feeders. The standard configuration is mainly intended for protection of the2W-power transformer at medium voltage applications.
The IED with this standard configuration is delivered from the factory with defaultsettings and parameters. The end-user flexibility for incoming, outgoing and internalsignal designation within the IED enables this configuration to be further adapted todifferent primary circuit layouts and the related functionality needs by modifying theinternal functionality using PCM600.
3.4.2 FunctionsTable 14: Functions included in the RET615 standard configuration TA02
Function IEC 61850 IEC 60617 ANSIIncluded functions
Three-phase current measurement, high voltageside
CMMXU1 3I IA,IB,IC (1)
Three-phase current measurement, low voltageside
CMMXU2 3I(B) IA,IB,IC (2)
Three-phase voltage measurement, low voltageside
VMMXU1 3U VA,VB,VC (2)
Sequence current measurement, high voltage side CSMSQI1 I1,I2,I0 I1, I2, I0 (1)
Sequence current measurement, low voltage side CSMSQI2 I1,I2,I0(B) I1, I2, I0 (2)
Sequence voltage measurement, low voltage side VSMSQI1 U1,U2,U0 V1,V2,V0 (2)
Three-phase power and energy measurement,low voltage side
PEMMXU1 P,E P,E (2)
Three-phase non-directional time overcurrentprotection, low stage, high voltage side
PHLPTOC1 3I>(1) 51P (1)
Three-phase non-directional time overcurrentprotection, high stage 1, high voltage side
PHHPTOC1 3I>>(1) 50P (1)
Three-phase non-directional time overcurrentprotection, low stage, low-voltage side
PHLPTOC2 3I>(2) 51P (2)
Three-phase non-directional time overcurrentprotection, high stage 1, low-voltage side
PHHPTOC3 3I>>(3) 50P (2)
Table continues on next page
1MAC201230-MB A Section 3RET615 variants
RET615 ANSI 45Application Manual
Function IEC 61850 IEC 60617 ANSIGround non-directional time overcurrentprotection, low stage(Calculated), high-voltageside
EFLPTOC2 I0>(2) 51N (1)
Ground non-directional time overcurrentprotection, high stage 1 (Calculated), high-voltage side
EFHPTOC3 I0>> (3) 50N (1)
Ground non-directional time overcurrentprotection, high stage 1 (Calculated), low voltageside
EFHPTOC5 I0>> (5) 50N (2)
Three-phase thermal overload protection, twotime constants, high-voltage side
T2PTTR1 3Ith>T 49T (1)
Circuit-breaker failure protection, low voltage side CCBRBRF1 3I>/IoBF(1) 50BF (2)
Trip circuit monitoring 1 TCSSCBR1 TCS(1) TCM-1
Trip circuit monitoring 2 TCSSCBR2 TCS(2) TCM-2
Electrically latched/self resetting trip output 1 TRPPTRC1 Trip(1) 86/94-1
Electrically latched/self resetting trip output 2 TRPPTRC2 Trip(2) 86/94-2
Disturbance recorder RDRE1 DR DFR
Sequence of events recorder SER SER SER
Fault recorder FLTMSTA FR FLR
Circuit breaker control, low-voltage side CBXCBR1 I<->O CB 52 (2)
Circuit-breaker condition monitoring, low-voltageside
SSCBR1 CBCM 52CM (2)
Low impedance restricted ground fault protection,low-voltage side
LREFPNDF1 dIoLo> 87LOZREF (2)
Transformer differential protection for twowinding transformers
TR2PTDF1 3dI>T 87T
Tap position TPOSSLTC1 TPOSM 84T
Three-phase overvoltage protection, stage 1, low-voltage side
PHPTOV1 3U>(1) 59 (2)
Three-phase undervoltage protection, stage 1,low-voltage side
PHPTUV1 3U<(1) 27 (2)
Ground overvoltage protection, low-voltage side ROVPTOV1 U0>(1) 59G (2)
Negative sequence overvoltage protection, low-voltage side
NSPTOV1 U2> 47 (2)
Directional ground-fault protection – low stage,low voltage side
DEFLPDEF1 I0>->(1) 67/51N (2)
Three-phase directional overcurrent protection,low stage, low-voltage side
DPHLPDOC1 3I>->(1) 67/51P (2)
Fuse failure supervision, low-voltage side SEQRFUF1 FUSEF 60 (2)
Ground current measurement RESCMMXU1 I0 IG
Ground voltage measurement RESVMMXU1 U0 VG
Table continues on next page
Section 3 1MAC201230-MB ARET615 variants
46 RET615 ANSIApplication Manual
Function IEC 61850 IEC 60617 ANSIGround non-directional time overcurrentprotection, low stage (Measured)
EFLPTOC1 I0>(1) 51G
Ground non-directional time overcurrentprotection, high stage 1 (Measured)
EFHPTOC1 I0>> (1) 50G
Ground non-directional time overcurrentprotection, low stage (Calculated), low-voltageside
EFLPTOC3 I0>(3) 51N (2)
Optional functions
Arc flash detector 1, low-voltage side ARCSARC1 ARC(1) AFD-1 (2)
Arc flash detector 2, low-voltage side ARCSARC2 ARC(2) AFD-2 (2)
Arc flash detector 3, low-voltage side ARCSARC3 ARC(3) AFD-3 (2)
3.4.2.1 Default I/O connections
Table 15: Default connections for binary inputs
Binary input Description Connector pinsX110-BI1 Blocking of O/C high stage (high voltage) and instantaneous
stage (low voltage)X110-1,2
X110-BI2 External protection trip X110-3,4
X110-BI3 Circuit breaker low gas pressure indication X110-5,6
X110-BI4 Circuit breaker spring charged indication X110-7,6
X110-BI5 High-voltage side disconnector closed X110-8,9
X110-BI6 High-voltage side disconnector open X110-10,9
X110-BI7 High-voltage side circuit breaker closed X110-11,12
X110-BI8 High-voltage side circuit breaker open X110-13,12
X130-BI1 BCD sign bit (tap changer position) X130-1,2
X130-BI2 BCD bit 1 LSB X130-2,3
X130-BI3 BCD bit 2 X130-4,5
X130-BI4 BCD bit 3 X130-5,6
X130-BI5 BCD bit 4 X130-7,8
X130-BI6 BCD bit 5 MSB X130-8,9
Table 16: Default connections for binary outputs
Binary output Description Connector pinsX100-PO1 Close high-voltage circuit breaker X100-6,7
X100-PO2 Breaker failure backup trip to upstream breaker X100-8,9
X100-SO1 General start indication X100-10,11,(12)
Table continues on next page
1MAC201230-MB A Section 3RET615 variants
RET615 ANSI 47Application Manual
Binary output Description Connector pinsX100-SO2 General operate indication X100-13,14
X100-PO3 Open circuit breaker/trip coil 1 high voltage X100-15-19
X100-PO4 Open circuit breaker/trip coil 2 low voltage X100-20-24
X110-SO1 Overcurrent operate alarm X110-14,15,16
X110-SO2 Differential protection operate alarm X110-17,18,19
X110-SO3 Earth fault operate alarm X110-20,21,22
X110-SO4Thermal overload and negative phase-sequence protectionoperate alarm X110-23,24
Table 17: Order codes
LED label Order code optionsLED label 1 HATBBABAxAE1BNNxXC
HATBBABAxBE1BNNxXC
HATBBABAx3E1BNNxXC
LED label 2 HATBBABAxFE1BNNxXC
HATBBABAxGE1BNNxXC
Table 18: Configuration option LED assignments
LED label 1 LED label 2LED1 Phase A Phase A
LED2 Phase B Phase B
LED3 Phase C Phase C
LED4 Neutral/Ground Neutral/Ground
LED5 Time Time
LED6 Instantaneous Instantaneous
LED7 Differential/REF Differential/REF
LED8 Voltage Voltage
LED9 Breaker failure/Alarm Breaker failure/Alarm
LED10 Overload alarm/Trip Overload alarm/Trip
LED11 Arc flash detection
3.4.3 Functional diagramsThe functional diagrams describe the default input, output, alarm LED and function-to-function connections. The default connections can be viewed and changed withPCM600 according to the application requirements, if necessary.
Section 3 1MAC201230-MB ARET615 variants
48 RET615 ANSIApplication Manual
The analog channels have fixed connections towards the different function blocksinside the IED’s standard configuration.
The analog channels are assigned to different functions as shown in the functionaldiagrams. The common signal marked with IA,IB,IC(1) represents the three phasecurrents of the high-voltage side of the transformer and IA,IB,IC(2) represents thethree phase currents of the low-voltage side of the transformer. The signal marked withIG represents the measured neutral current measured between the neutral point of thetransformer and grounding.
3.4.3.1 Functional diagrams for protection
The functional diagrams describe the IED’s protection functionality in detail andaccording to the factory set default connections.
X120
1
23
45
67
89
1011
1213
14IG
IA (2)
IB (2)
IC (2)
ABC
S1
S2
P1
P2
52
IC (1)
IA (1)
IB (1)
S2
S1
52
abc
P2
P1
S2
S1
PositiveCurrentDirection
P2
P1
LV
HV
TRANSFORMER DIFFERENTIAL PROTECTION
TR2PTDF1
TRIPIA,IB,IC (1)
87T3dI>T
OPR_LSIA,IB,IC (2)
OPR_HSBLOCK
BLKD2HBLK_OPR_LS-T
BLKDD5HBLK_OPR_HS-T
BLKDWAV
LED7
GUID-D739D833-1759-446D-A5B0-224D0DBC2F3D V1 EN
Figure 26: Stabilized and instantaneous differential protection for 2W-transformers
The stabilized differential protection for 2W-transformers (87T) provides protection ofpower transformer unit including, for example, winding short-circuit and interturnfaults. The IED compares the phase currents on both sides of the object to be protected.
1MAC201230-MB A Section 3RET615 variants
RET615 ANSI 49Application Manual
If the differential current of the phase currents in one of the phases exceed the settingof the stabilized operation characteristic or the instantaneous protection stage of thefunction, the function provides an operate signal.
For transformers having an on-line tap changer, the tap position information isrecommended to be used in differential protection, as the ratio difference of tapchanger movements can be corrected in 87T.
The position indication of the OLTC is recommended for differential protection toincrease sensitivity.
All operate signals are connected to the Master Trip 1 and 2 and also to the alarm LEDs.
3I>(1)
PICKUPIA, IB, ICBLOCK
ENA_MULT
51P(1)
PHLPTOC2PICKUPIA, IB, IC
BLOCK
ENA_MULT
51P(2)
PHHPTOC3PICKUPIA, IB, IC
BLOCK
ENA_MULT
50P(2)
PHHPTOC1PICKUPIA, IB, IC
BLOCK
ENA_MULT
50P(1)INRPHAR1
BLK2HIA, IB, IC
BLOCK
INR
TRIP_PhA
86/94 LED
TRIP_PhA
OR
LED1
86/94 LEDOR
LED 2
PHASE B TRIP
86/94 LEDOR
LED 3
PHASE C TRIP
TRIP_PhA
TRIP_PhB
TRIP_PhC
TRIP_PhBTRIP_PhB
TRIP_PhCTRIP_PhC
TRIP_PhA
TRIP_PhB
TRIP_PhC
TRIP_PhA
TRIP_PhB
TRIP_PhC
TRIP_PhA
TRIP_PhB
TRIP_PhC
PHASE A TRIP
Trip1
LEDPTRC
LEDPTRC
TRIP
TRIP
TRIP
TRIP
NOTE 1
NOTE 1
NOTE 1
NOTE 1
NOTE 1: AVAILABLE ONLY FOR LED INDICATION.
AVAILABLE FOR MAPPING USINGSMT TOOL IN PCM TO ANY PROTECTION,DEPENDING ON APPLICATION.
OR
LED6
INSTANTANEOUS TRIP
PHASE OVERCURRENT PROTECTION INDICATION
OR
LED5
TIME TRIP
symbolIEC60617
Number/AcronymANSI Device/Function
LEDPTRC
Trip1
Trip1
PHLPTOC1
3I>(2)
3I>>(1)
3I>>(3)
3I2f>
identificationIEC61850
DPHLPDOC1PICKUPIA, IB, IC
BLOCK
ENA_MULT
67/51P(2)TRIP_PhA
TRIP_PhB
TRIP_PhC
TRIP
NOTE 1
3I>->(1)
GUID-CC5F6801-F1D1-45C5-B315-261F724291CB V1 EN
Figure 27: Phase overcurrent protection
Two stages for both high-voltage and low-voltage sides as a total of four overcurrentstages are offered for overcurrent and short-circuit protection. The inrush detection
Section 3 1MAC201230-MB ARET615 variants
50 RET615 ANSIApplication Manual
block’s (INR) output BLK2H provides the possibility to either block the function ormultiply the active settings for any of the shown protection function blocks.
A selective backup overcurrent protection can be achieved by using blockings betweenhigh-voltage side and low-voltage side overcurrent stages. This kind of blockingscheme enables coordinated overlapping of overcurrent protection zones. In addition,there is one directional overcurrent protection provided on the low side of the transformer.
EFLPTOC2PICKUP
BLOCK
51N(1)
EFLPTOC3PICKUP
BLOCK
51N(2)
EFHPTOC5PICKUP
BLOCK
50N(2)
PICKUP
BLOCK
50N(1)
ORTRIP
TRIP
TRIP
TRIP
EFHPTOC3
BI 1 (Blocking)
IA, IB, IC
BLOCK
ENA_MULT
IA, IB, IC
BLOCK
ENA_MULT
IA, IB, IC
BLOCK
ENA_MULT
IA, IB, IC
BLOCK
ENA_MULT
OR
TRIP_NEUT
86/94 LED
TRIP_NEUT
Trip 1
NEUTRAL OVERCURRENT PROTECTION
LED4
TRIPNEUTRAL/GROUND
LED 6
TRIPINSTANTANEOUS
LED 5
TIME TRIP
LEDPTRC
I0>(2)
I0>>(5)
I0>>(3)
I0>(3)
OR
GUID-4570E2D8-8FDD-4ABB-82B0-7CB64557E765 V1 EN
Figure 28: Non-directional ground-fault protection
1MAC201230-MB A Section 3RET615 variants
RET615 ANSI 51Application Manual
EFLPTOC1PICKUPIG
BLOCK
ENA_MULT
51G
EFHPTOC1PICKUPIG
BLOCK
ENA_MULT
50G
TRIP_NEUT
86/94LED
TRIP_NEUT
OR
LED4
TRIP
TRIP
TRIPNEUTRAL / GROUND
TRIP(1)
LED6
TIME TRIP
INSTANTANEOUS
GROUND OVERCURRENT PROTECTION
BI 1 (Blocking)
LED5
TRIP
LEDPTRC
I0>(1)
I0>>(1)
I0>->(1)
PICKUP
TRIP
I0
U0
ENA_MULT
RCA_CTL
BLOCK
DEFLPDEF1
67/51N(2)
OR
GUID-C61E777D-5FB0-4E90-99C7-AFA81839FA20 V1 EN
Figure 29: Ground overcurrent protection
Two stages are offered for non-directional ground-fault protection for high and lowside of the transformers. In addition, there are two stages of ground-fault protectionbased on measured ground current. One directional ground overcurrent protection isalso provided on the low side of the transformer.
Section 3 1MAC201230-MB ARET615 variants
52 RET615 ANSIApplication Manual
LREFPNDF1
PICKUP3I
IG
87LOZREF(2)
TRIP
dIoLo>
REF_PICKUP
REF_TRIP
LED4
RESTRICTED EARTH FAULT PROTECTION
LED7
GUID-58D2DD05-C1F9-47C0-8DBB-DA27BD8E1162 V1 EN
Figure 30: Restricted low-impedance earth-fault protection
The configuration includes restricted low-impedance earth-fault protection function forlow-voltage side of two-winding power transformers, 87LOZREF(2). The numericaldifferential current stage operates exclusively on ground faults occurring in theprotected area, that is, in the area between the phase and neutral current transformers.A ground fault in this area appears as a differential current between the residual currentof the phase currents and the neutral current of the conductor between the star-point ofthe transformer and earth.
THERMAL OVERLOAD PROTECTION
T2PTTR1TRIP
ALARM
IA, IB, IC
BLK_CLOSE
PICKUP
BLK_OPR
ENA_MULT
LED10
OVERLOAD ALARM
OR
3Ith>T
GUID-156D07E7-E15D-481C-8A78-F9E7988F3568 V1 EN
Figure 31: Three-phase thermal overload protection for power transformers
1MAC201230-MB A Section 3RET615 variants
RET615 ANSI 53Application Manual
Three-phase thermal overload protection for power transformers, 49T(1), providesindication on overload situations, and it is connected to the CT's on high side of thetransformer.
PO2
89
X100
BREAKER FAILURE PROTECTION
Circuit Breaker failureprotection trip toassociated breaker(s)
TRRET
TRBU
IA, IB, IC
PICKUP
POSCLOSE
BREAKER FAILURE
CB_FAULT_AL
CB_FAULT
IN
BLOCK
LED9
50BF(2)
51P(2) Trip
50P(2) Trip
51G Trip
51N(2) Trip
50G Trip
AFD-2(2) Trip
87T Trip
AFD-3(2) Trip
87LOZREF(2) Trip
50N(2) Trip
AFD-1(2) Trip
OR
NOTES: 1) DASHED LINE INDICATES OPTIONALINPUT BASED ON CONFIGURATION.
3I>/Io>BF(1)
BI 2 (Breaker Close Status)
67/51P(2) Trip
67/51N(2) Trip
CCBRBRF1
GUID-A4F87E7F-EC8C-48AF-978F-489028D08CD4 V1 EN
Figure 32: Circuit-breaker failure protection
The circuit-breaker failure protection 50BF(2) is initiated via the start input by anumber of different protection stages in the IED. 50BF(2) offers different operatingmodes associated with the circuit-breaker position and the measured phase and residualcurrents.
50BF(2) has two operating outputs: TRRET and TRBU. The TRRET operate output isused for retripping its own circuit breaker. The TRBU output is used for retrippingboth the high-voltage and low-voltage side circuit breakers through Master Trip 1 and2. The TRBU operate output signal is connected to the output PO2 (X100: 8-9). LED 6is used for backup (TRBU) operate indication.
Section 3 1MAC201230-MB ARET615 variants
54 RET615 ANSIApplication Manual
3.4.3.2 Functional diagrams for digital fault recorder and trip circuit monitoring
DIGITAL FAULT RECORDER
DREC
DFR
AI#2
AI#1
AI#4
AI#3
AI#6
AI#5
AI#8
AI#7
AI#10
AI#9
AI#12
AI#11
IA(1)-A
IB(1)-A
IC(1)-A
IG-A
IA(2)-A
IB(2)-A
IC(2)-A
Disabled
VA-kV
VB-kV
VC-kV
VG-kV
DR
GUID-59704261-9FCB-43C7-BB87-AD27711D70A2 V1 EN
Figure 33: Digital fault recorder, AI#1...12
1MAC201230-MB A Section 3RET615 variants
RET615 ANSI 55Application Manual
DIGITAL FAULT RECORDER
DREC
DFR
BI#2
BI#1
BI#4
BI#3
BI#6
BI#5
BI#8
BI#7
BI#10
BI#9
BI#12
BI#11
BI#14
BI#13
BI#16
BI#15
BI#17
51P(1) Trip
50P(1) Trip
51P(2) Trip
50P(2) Trip
51G Trip
50N(2) Trip
67/51P(2) Trip
67/51N(2) Trip
49T(1) Trip
49T(1) AlmThm
50BF(2) OpEx
50BF(2) OpIn
BI#18
BI#20
BI#19
BI#22
BI#21
BI#24
BI#23
BI#25
AFD-1(2) FADet
AFD-2(2) FADet
AFD-3(2) FADet
AFD-2(2) Trip
AFD-1(2) Trip
Spare
AFD-3(3) Trip
Spare
BI#26
BI#27
BI#28
Spare
Spare
Spare
BI#30
BI#29
BI#31
BI#32Spare
TCM-1 Alarm
Spare
TCM-2 Alarm
Spare
DR
51N(1) Trip
51N(2) Trip
50G Trip
50N(1) Trip
NOTES: 1) DASHED LINE INDICATES OPTIONAL INPUT BASED ON CONFIGURATION.
GUID-5EDB38A6-8216-4E32-B53F-DD5E3130C277 V1 EN
Figure 34: Digital fault recorder BI#1…32
Section 3 1MAC201230-MB ARET615 variants
56 RET615 ANSIApplication Manual
DREC
DFR
BI#34
BI#33
BI#36
BI#35
BI#38
BI#37
BI#40
BI#39
BI#42
BI#41
BI#44
BI#43
BI#46
BI#45
BI#48
BI#47
BI#49
59(2) Trip
52CM(2) TRV_T_OP_ALM
52CM(2) TRV_T_CL_ALM
52CM(2) Alarm
52CM(2) CB_LIFE_ALM
BI#50
BI#52
BI#51
BI#54
BI#53
BI#56
BI#55
BI#57
BI#58
BI#59
BI#60
BI#62
BI#61
BI#63
BI#64
X110-7X110-5X110-3
X110-6X110-4X110-2 X110-8
27(2) Trip
59G(2) Trip
47(2) Trip
60(2) Str
37(1) Trip
87LOZREF(2) Trip
87T Trip
DIGITAL FAULT RECORDER
DR
X110-1 XA130-1
XA130-2
XA130-3
XA130-4
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
GUID-54246FB6-5089-4330-A68D-69F46CF536AA V1 EN
Figure 35: Digital fault recorder BI#33…64
The digital fault recorder has 64 digital inputs. All pickup and trip signals from theprotection stages are routed to trigger the digital fault recorder or alternatively only tobe recorded by the digital fault recorder depending on the parameter settings.
1MAC201230-MB A Section 3RET615 variants
RET615 ANSI 57Application Manual
BI 2 (CB Close Status) OROR86/94-1 Trip
TRIP CIRCUIT MONITORING
TCM-1
ALARMBLOCK
TCSSCBR1
86/94-2 TripLED9
TRIP CIRCUIT FAILURE
TCM-2
ALARMBLOCK
TCSSCBR2
TCS(1)
TCS(2)
GUID-61C004AA-FD1D-4C9E-A63B-919119E20B62 V1 EN
Figure 36: Trip circuit monitoring
Two separate TCM functions have been included: TCM-1 for PO3 (X100:16-19) andTCM-2 for PO4 (X100:20-23).
3.4.3.3 Functional diagrams for control and interlocking
MASTER TRIP 1 LOGIC
16
151918TCM-1
PO317
51P(1) Trip50P(1) Trip51N(1) Trip50N(1) Trip49T(1) Trip87T Trip87LOZREF(2) Trip
X100+
OR
OpenSignal to
86/94-1
TRIPCL_LKOUT
BLOCKTRIP
RST_LKOUT
With lock-out mode selection
TRPPTRC1OR
BI4
52 (2) EXE_OP
Trip Coil 1
Breaker
2)
NOTES: 1) NON-LATCHED MODE AS DEFAULT.
Trip(1)
GUID-15DD976C-E8B7-4D23-B156-A41CDB744C8B V1 EN
Figure 37: Master trip 1 logic
Section 3 1MAC201230-MB ARET615 variants
58 RET615 ANSIApplication Manual
22
23
24TCM-2
PO421
20
MASTER TRIP 2 LOGIC
51P(2) Trip50P(2) Trip51G Trip51N(2) Trip50G Trip
AFD-2(2) Trip
50BF(2) TripAFD-3(2) Trip
87T Trip87LOZREF(2) Trip
50N(2) TripAFD-1(2) Trip
20X100
+
OR
OpenSignal to
86/94-2
TRIP
CL_LKOUT
BLOCK
TRIP
RST_LKOUT
With lock-out mode selection
TRPPTRC2OR
BI4
52 (2) EXE_OP
Trip Coil 2
Breaker
2)
NOTES: 1) DASHED LINE INDICATES OPTIONALINPUT BASED ON CONFIGURATION.
2) NON-LATCHED MODE AS DEFAULT.
Trip(2)
67/51N(2) Trip67/51P(2) Trip
GUID-4B8A34C2-BF8B-46C4-9CD8-0DE5EAFEAEE8 V1 EN
Figure 38: Master trip 2 logic
The operate signals from the protections are connected to the two trip output contactsPO3 (X100:15-19) and PO4 (X100:20-24) via the corresponding Master Trips 86/94-1and 86/94-2. Open control commands to the circuit breaker from local or remoteCBXCBR1-exe_op are connected directly to the output PO3 (X100:16-19).
86/94-1 and 2 provide the lockout/latching function, event generation and the tripsignal duration setting. If the lockout operation mode is selected, one binary input canbe reassigned to the RST_LKOUT input of the Master Trip to enable external resetwith a push button.
BI 3 (Breaker Open Status)BI 2 (Breaker Close Status)
Always True
OR
67
PO1
+
X100
79 CLOSE_CB
CIRCUIT BREAKER CONTROL AND INTERLOCKING52 EXE_OP
52(2)
SELECTEDENA_OPEN
ENA_CLOSE
BLK_OPEN
BLK_CLOSE
EXE_OP
EXE_CL
OPENPOS
CLOSEPOS
EXE_OP
EXE_CL
OPENPOS
CLOSEPOS
OKPOS
CBXCBR1
CloseBreaker
X110
56
7BI 4
BI 3PRES_ALM_INPRES_LO_INSPR_CHR_STSPR_CHRRST_IPOW
TRV_T_OP_ALMTRV_T_CL_ALMDIFTRVTOPALMDIFTRVTCLALMSPR_CHR_ALM
OPR_ALMOPR_LO
IPOW_ALMIPOW_LO
CB_LIFE_ALMMON_ALM
PRES_ALMPRES_LO
OPENPOSINTERMPOSCLOSEPOS
BLOCKPOSOPEN
52CM(2)CBCM
OR
LED9
(CB CONDMONITOR)
POSCLOSE
RST_CB_WEAR
CB Spring Charged
GAS Pressure Alarm
SSCBR1
I<->O CB
GUID-E0814F4D-61DD-4324-BF97-41D502857F55 V1 EN
Figure 39: Circuit breaker control and interlocking
1MAC201230-MB A Section 3RET615 variants
RET615 ANSI 59Application Manual
The circuit breaker closing is enabled when the ENA_CLOSE input is activated. TheENA_CLOSE input can be activated by the configuration logic, which is acombination of the status of the Master Trip Logics. The open operation is always enabled.
If the ENA_CLOSE and BLK_CLOSE signals are completely removedfrom the breaker control function block 52(2) with PCM600, thefunction assumes that the breaker close commands are allowedcontinuously.
The circuit breaker condition monitoring function (SSCBR) supervises the circuitbreaker status based on the binary input information connected and measured currentlevels. The function introduces various supervision methods. The correspondingsupervision alarm signals are routed to LED 9.
COMMON PICKUP SIGNAL
LEDPTRC1
86/94 LED
TPGAPC1
TP-1
PICKUP
TRIP
PICKUP
TRIP
PICKUP
TRIP
PICKUP
TRIP
Pickup SignalSO#1 (X100:10-11-12)
1) THERE ARE FOUR PULSE TIMERS AVAILABLE-ONE OF THEM IS USED FOR DEFAULT CONFIGURATIONS.ALL PULSE TIMERS INCLUDING TP-1 CAN BE MAPPEDFOR SPECIFIC APPLICATIONS USING SMT IN PCM TOOLS.
NOTE:
1)
Trip1 TP-1
GUID-B48DB1BC-8B98-4413-8D58-9980404EB9AD V1 EN
Figure 40: Common pickup signal
Section 3 1MAC201230-MB ARET615 variants
60 RET615 ANSIApplication Manual
TRPPTRC1
PICKUP
TRIP
PICKUP
TRIP
TRPPTRC2
PICKUP
TRIP
PICKUP
TRIP
Trip SignalSO#2 (X100:13-14-15)
Trip(1)
Trip(2)
GUID-C56EFFDC-0D03-4F95-A632-4D1D33E2BB1A V1 EN
Figure 41: Common trip signal
The signal outputs from the IED are connected to give dedicated information onpickups and trips.
• Pickup of any protection function SO1 (X100:10-12)• Trip of any protection function SO2 (X100:13-15).
The TP-1 is a timer and used for setting the minimum pulse length for the outputs.
1MAC201230-MB A Section 3RET615 variants
RET615 ANSI 61Application Manual
TAP CHANGER POSITION INDICATION
TPOSSLTC1
SIGN_BIT
BI1BI0
BI4BI5
BI2BI3
TPOSM
X130
12
3
45
6BI 4
BI 3
BI 2
BI 1
BI 8
BI 712
13
11
BCD BIT 5
BCD BIT 4
BCD BIT 3
BCD BIT 2
BCD BIT 1
BCD SIGN BIT
X110
GUID-3F69093C-4456-43C3-B7BC-CDEC293754EF V1 EN
Figure 42: Tap changer position indication
To increase the sensitivity of the stabilized differential function, the tap positioninformation from the tap changer is connected to the IED via the tap changer positionindication function 84T. 84T is connected to the binary inputs of the X130 BIO card.84T uses binary-coded methods to generate the integer value of the tap changer position.
3.4.3.4 Functional diagram for voltage protections
One overvoltage (59(2)), one undervoltage (27(2)), one residual overvoltage (59G(2))and one negative sequence undervoltage (47(2)) protections are provided for alarmpurpose only in default configuration. Users can select any or all of the protections fortripping using the Signal Matrix tool.
Section 3 1MAC201230-MB ARET615 variants
62 RET615 ANSIApplication Manual
OVER & UNDER VOLTAGE PROTECTION
OR
59G(2)
PICKUPBLOCK
TRIP
U0>(1)ROVPTOV1
27(2)
PICKUPBLOCK
TRIP
3U<(1)PHPTUV1
59(2)
PICKUPBLOCK
TRIP
3U>(1)PHPTOV1
47(2)
PICKUPBLOCK
TRIP
U2>NSPTOV1
LED8
OVER & UNDER VOLTAGE PROTECTION
60(2)Pickup
GUID-E6DCBFA8-7FED-45E7-9044-A9D58F17301E V1 EN
Figure 43: Overvoltage and undervoltage protection
3.4.3.5 Functional diagram for optional ARC flash detection
Optional ARC flash detectors (AFD 1-3) are included in the standard configuration.The ARC flash detection offers individual function blocks for each of the three ARCsensors that can be connected to the IED. Each ARC protection function block has twodifferent operation modes, with or without the phase current check.
1MAC201230-MB A Section 3RET615 variants
RET615 ANSI 63Application Manual
ARCSARC1
TRIP
ARC_FLT_DET
IA, IB, IC
BLOCK
OPR_MODE
REM_FLT_ARC
IG
ARCSARC2
TRIP
ARC_FLT_DET
IA, IB, IC
BLOCK
OPR_MODEREM_FLT_ARC
IG
ARCSARC3
TRIP
ARC_FLT_DET
IA, IB, IC
BLOCK
OPR_MODE
REM_FLT_ARC
IG
LED11
ARC(1)
ARC(2)
ARC(3)
GUID-14D00EE3-5F20-4E67-9174-675DB88AAA02 V1 EN
Figure 44: Arc flash detection
Trip signals from the ARC protection function blocks are connected to the Master TripLogic and also to the alarm LED 11 as a common arc flash detection.
Section 3 1MAC201230-MB ARET615 variants
64 RET615 ANSIApplication Manual
Section 4 Requirements for measurementtransformers
4.1 Current transformers
4.1.1 Current transformer requirements for non-directionalovercurrent protectionFor reliable and correct operation of the overcurrent protection, the CT has to bechosen carefully. The distortion of the secondary current of a saturated CT mayendanger the operation, selectivity, and co-ordination of protection. However, when theCT is correctly selected, a fast and reliable short circuit protection can be enabled.
The selection of a CT depends not only on the CT specifications but also on thenetwork fault current magnitude, desired protection objectives, and the actual CTburden. The protection settings of the IED should be defined in accordance with theCT performance as well as other factors.
Appropriate 'C' class CT should be used based on the total resistances of the CTsecondary circuit. If other accuracy class CTs are used then refer the followingdiscussions.
4.1.1.1 Current transformer accuracy class and accuracy limit factor
The rated accuracy limit factor (Fn) is the ratio of the rated accuracy limit primarycurrent to the rated primary current. For example, a protective current transformer oftype 5P10 has the accuracy class 5P and the accuracy limit factor 10. For protectivecurrent transformers, the accuracy class is designed by the highest permissiblepercentage composite error at the rated accuracy limit primary current prescribed forthe accuracy class concerned, followed by the letter "P" (meaning protection).
Table 19: Limits of errors according to IEC 60044-1 for protective current transformers
Accuracy class Current error atrated primarycurrent (%)
Phase displacement at rated primarycurrent
Composite error atrated accuracy limitprimary current (%)minutes centiradians
5P ±1 ±60 ±1.8 5
10P ±3 - - 10
1MAC201230-MB A Section 4Requirements for measurement transformers
RET615 ANSI 65Application Manual
The accuracy classes 5P and 10P are both suitable for non-directional overcurrentprotection. The 5P class provides a better accuracy. This should be noted also if thereare accuracy requirements for the metering functions (current metering, powermetering, and so on) of the IED.
The CT accuracy primary limit current describes the highest fault current magnitude atwhich the CT fulfils the specified accuracy. Beyond this level, the secondary current ofthe CT is distorted and it might have severe effects on the performance of theprotection IED.
In practise, the actual accuracy limit factor (Fa) differs from the rated accuracy limitfactor (Fn) and is proportional to the ratio of the rated CT burden and the actual CT burden.
The actual accuracy limit factor is calculated using the formula:
F FS S
S Sa n
in n
in
≈ ×
+
+
A071141 V1 EN
Fn the accuracy limit factor with the nominal external burden Sn
Sin the internal secondary burden of the CT
S the actual external burden
4.1.1.2 Non-directional overcurrent protection
The current transformer selectionNon-directional overcurrent protection does not set high requirements on the accuracyclass or on the actual accuracy limit factor (Fa) of the CTs. It is, however,recommended to select a CT with Fa of at least 20.
The nominal primary current I1n should be chosen in such a way that the thermal anddynamic strength of the current measuring input of the IED is not exceeded. This isalways fulfilled when
I1n > Ikmax / 100,
Ikmax is the highest fault current.
The saturation of the CT protects the measuring circuit and the current input of theIED. For that reason, in practice, even a few times smaller nominal primary current canbe used than given by the formula.
Section 4 1MAC201230-MB ARequirements for measurement transformers
66 RET615 ANSIApplication Manual
Recommended pickup current settingsIf Ikmin is the lowest primary current at which the highest set overcurrent stage is totrip, the pickup current should be set using the formula:
Current pickup value < 0.7 x (Ikmin / I1n)
I1n is the nominal primary current of the CT.
The factor 0.7 takes into account the protection IED inaccuracy, current transformererrors, and imperfections of the short circuit calculations.
The adequate performance of the CT should be checked when the setting of the highset stage overcurrent protection is defined. The trip time delay caused by the CTsaturation is typically small enough when the overcurrent setting is noticeably lowerthan Fa.
When defining the setting values for the low set stages, the saturation of the CT doesnot need to be taken into account and the pickup current setting is simply according tothe formula.
Delay in operation caused by saturation of current transformersThe saturation of CT may cause a delayed IED operation. To ensure the timeselectivity, the delay must be taken into account when setting the trip times ofsuccessive IEDs.
With definite time mode of operation, the saturation of CT may cause a delay that is aslong as the time the constant of the DC component of the fault current, when thecurrent is only slightly higher than the pickup current. This depends on the accuracylimit factor of the CT, on the remanence flux of the core of the CT, and on the trip timesetting.
With inverse time mode of operation, the delay should always be considered as beingas long as the time constant of the DC component.
With inverse time mode of operation and when the high-set stages are not used, the ACcomponent of the fault current should not saturate the CT less than 20 times the pickupcurrent. Otherwise, the inverse operation time can be further prolonged. Therefore, theaccuracy limit factor Fa should be chosen using the formula:
Fa > 20*Current pickup value / I1n
The Current pickup value is the primary pickup current setting of the IED.
1MAC201230-MB A Section 4Requirements for measurement transformers
RET615 ANSI 67Application Manual
4.1.1.3 Example for non-directional overcurrent protection
The following figure describes a typical medium voltage feeder. The protection isimplemented as three-stage definite time non-directional overcurrent protection.
A071142-ANSI V2 EN
Figure 45: Example of three-stage overcurrent protection
The maximum three-phase fault current is 41.7 kA and the minimum three-phase shortcircuit current is 22.8 kA. The actual accuracy limit factor of the CT is calculated to be59.
The pickup current setting for low-set stage (51P) is selected to be about twice thenominal current of the cable. The trip time is selected so that it is selective with thenext IED (not visible in the figure above). The settings for the high-set stage andinstantaneous stage are defined also so that grading is ensured with the downstreamprotection. In addition, the pickup current settings have to be defined so that the IEDoperates with the minimum fault current and it does not trip with the maximum loadcurrent. The settings for all three stages are as in the figure above.
For the application point of view, the suitable setting for instantaneous stage (50P-3) inthis example is 3 500 A (5.83 x I2n). For the CT characteristics point of view, thecriteria given by the current transformer selection formula is fulfilled and also the IEDsetting is considerably below the Fa. In this application, the CT rated burden couldhave been selected much lower than 10 VA for economical reasons.
Section 4 1MAC201230-MB ARequirements for measurement transformers
68 RET615 ANSIApplication Manual
Section 5 IED physical connections
5.1 Inputs
5.1.1 Energizing inputs
5.1.1.1 Phase currents
The IED can also be used in single or two-phase applications byleaving one or two energizing inputs unoccupied. However, at leastterminals X120/7-8 must be connected.
Table 20: Inputs for phase currents
Terminal DescriptionX120-1, 2 IA2
X120-3, 4 IB2
X120-5, 6 IC2
X120-7, 8 IA
X120-9, 10 IB
X120-11, 12 IC
5.1.1.2 Ground current
Table 21: Inputs for ground current
Terminal DescriptionX120-13, 14 IG
5.1.2 Auxiliary supply voltage inputThe auxiliary voltage of the IED is connected to terminals X100/1-2. At DC supply,the positive lead is connected to terminal X100-1. The permitted auxiliary voltagerange is marked on the LHMI of the IED on the top of the HMI of the plug-in unit.
1MAC201230-MB A Section 5IED physical connections
RET615 ANSI 69Application Manual
Table 22: Auxiliary voltage supply
Terminal DescriptionX100-1 + Input
X100-2 - Input
5.1.3 Binary inputsThe binary inputs can be used, for example, to generate a blocking signal, to unlatchoutput contacts, to trigger the digital fault recorder or for remote control of IEDsettings.
Table 23: Binary input terminals X110-1...13Binary input terminals X110-1...13
Terminal DescriptionX110-1 BI1, +
X110-2 BI1, -
X110-3 BI2, +
X110-4 BI2, -
X110-5 BI3, +
X110-6 BI3, -
X110-6 BI4, -
X110-7 BI4, +
X110-8 BI5, +
X110-9 BI5, -
X110-9 BI6, -
X110-10 BI6, +
X110-11 BI7, +
X110-12 BI7, -
X110-12 BI8, -
X110-13 BI8, +
Table 24: Optional binary input terminals X130-1...9Binary input terminals X130-1...9
Terminal DescriptionX130-1 BI1, +
X130-2 BI1, -
X130-2 BI2, -
X130-3 BI2, +
X130-4 BI3, +
Table continues on next page
Section 5 1MAC201230-MB AIED physical connections
70 RET615 ANSIApplication Manual
Terminal DescriptionX130-5 BI3, -
X130-5 BI4, -
X130-6 BI4, +
X130-7 BI5, +
X130-8 BI5, -
X130-8 BI6, -
X130-9 BI6, +
5.1.4 Optional light sensor inputsIf the IED is provided with the optional communication module with light sensorinputs, the pre-manufactured lens-sensor fibers are connected to inputs X13, X14 andX15, see the terminal diagrams.For further information, see arc flash detector.
The IED is provided with connection sockets X13, X14 and X15 only ifthe optional communication module with light sensor inputs has beeninstalled. If the arc flash detector option is selected when ordering anIED, the light sensor inputs are included in the communication module.
Table 25: Light sensor input connectors
Terminal DescriptionX13 Input Light sensor 1
X14 Input Light sensor 2
X15 Input Light sensor 3
5.2 Outputs
5.2.1 Outputs for tripping and controllingOutput contacts PO1, PO2, PO3 and PO4 are heavy-duty trip contacts capable ofcontrolling most circuit breakers. On delivery from the factory, the trip signals from allthe protection stages are routed to PO3 and PO4.
1MAC201230-MB A Section 5IED physical connections
RET615 ANSI 71Application Manual
Table 26: Output contacts
Terminal DescriptionX100-6 PO1, NO
X100-7 PO1, NO
X100-8 PO2, NO
X100-9 PO2, NO
X100-15 PO3, NO (TCM resistor)
X100-16 PO3, NO
X100-17 PO3, NO
X100-18 PO3 (TCM1 input), NO
X100-19 PO3 (TCM1 inputr), NO
X100-20 PO4, NO (TCM resistor)
X100-21 PO4, NO
X100-22 PO4, NO
X100-23 PO4 (TCM2 input), NO
X100-24 PO4 (TCM2 input), NO
5.2.2 Outputs for signallingOutput contacts SO1 and SO2 in slot X100 or SO1, SO2, SO3 and SO4 in slot X110 orSO1, SO2 and SO3 in slot X130 (optional) can be used for signalling on pickup andtripping of the IED. On delivery from the factory, the pickup and alarm signals from allthe protection stages are routed to signalling outputs.
Output contacts of slot X110 are optional. Output contacts of slot X130 are available inthe optional BIO module (BIOB02A).
Table 27: Output contacts X100-10...14
Terminal DescriptionX100-10 SO1, common
X100-11 SO1, NC
X100-12 SO1, NO
X100-13 SO2, NO
X100-14 SO2, NO
Section 5 1MAC201230-MB AIED physical connections
72 RET615 ANSIApplication Manual
Table 28: Output contacts X110-14...24
Terminal DescriptionX110-14 SO1, common
X110-15 SO1, NO
X110-16 SO1, NC
X110-17 SO2, common
X110-18 SO2, NO
X110-19 SO2, NC
X110-20 SO3, common
X110-21 SO3, NO
X110-22 SO3, NC
X110-23 SO4, common
X110-24 SO4, NO
Table 29: Output contacts X130-10...18
Terminal DescriptionX130-10 SO1, common
X130-11 SO1, NO
X130-12 SO1, NC
X130-13 SO2, common
X130-14 SO2, NO
X130-15 SO2, NC
X130-16 SO3, common
X130-17 SO3, NO
X130-18 SO3, NC
5.2.3 IRFThe IRF contact functions as an output contact for the self-supervision system of theprotection IED. Under normal operating conditions, the IED is energized and thecontact is closed (X100/3-5). When a fault is detected by the self-supervision system orthe auxiliary voltage is disconnected, the output contact drops off and the contactcloses (X100/3-4).
Table 30: IRF contact
Terminal DescriptionX100-3 IRF, common
X100-4 Closed; IRF, or Vaux disconnected
X100-5 Closed; no IRF, and Vaux connected
1MAC201230-MB A Section 5IED physical connections
RET615 ANSI 73Application Manual
74
Section 6 Glossary
100BASE-FX A physical media defined in the IEEE 802.3 Ethernet standardfor local area networks (LANs) that uses fibre-optic cabling
100BASE-TX A physical media defined in the IEEE 802.3 Ethernet standardfor local area networks (LANs) that uses twisted-pair cablingcategory 5 or higher with RJ-45 connectors
ANSI American National Standards InstituteBI Binary inputBO Binary outputCT Current transformerDFR Digital fault recorderDNP3 A distributed network protocol originally developed by
Westronic. The DNP3 Users Group has the ownership of theprotocol and assumes responsibility for its evolution.
EMC Electromagnetic compatibilityGOOSE Generic Object Oriented Substation EventHMI Human-machine interfaceIEC 61850 International standard for substation communication and
modellingIED Intelligent electronic deviceIP address A set of four numbers between 0 and 255, separated by
periods. Each server connected to the Internet is assigned aunique IP address that specifies the location for the TCP/IPprotocol.
LAN Local area networkLC Connector type for glass fiber cableLCD Liquid crystal displayLED Light-emitting diodeLHMI Local human-machine interfaceModbus A serial communication protocol developed by the Modicon
company in 1979. Originally used for communication in PLCsand RTU devices.
1MAC201230-MB A Section 6Glossary
RET615 ANSI 75Application Manual
PCM600 Protection and Control IED ManagerRJ-45 Galvanic connector typeTCP/IP Transmission Control Protocol/Internet ProtocolWAN Wide area networkWHMI Web human-machine interface
Section 6 1MAC201230-MB AGlossary
76 RET615 ANSIApplication Manual
77
Contact us
ABB Inc.Distribution Automation4300 Coral Ridge DriveCoral Springs, FL 33065, USAPhone +1 (800) 523-2620Phone +1 954-752-6700Fax +1 954 345-5329
www.abb.com/substationautomation
1MA
C20
1230
-MB
A©
Cop
yrig
ht 2
010
AB
B. A
ll rig
hts
rese
rved
.