Upload
duongdat
View
223
Download
3
Embed Size (px)
Citation preview
RESIDUAL LIFE ASSESSMENT OF GENERATOR TRANSFORMERS IN
OLD HYDRO POWER PLANTS
Authored by: Sanjay Srivastava, Chief Engineer (HE&RM), Rakesh Kumar, Director (HE&RM),
R.K. Jayaswal, Dy. Director (HE&RM) & Amit Roy Singal, Asst. Director (HE&RM).
Presented by: Rakesh Kumar, Director (HE&RM), CEA
INTRODUCTION
• Renovation, Modernization, Uprating and Life Extension
(RMU&LE) has been recognized worldwide as a well proven
cost effective technique for improving the performance,
efficiency and reliability of old Hydro Power Plants (HPPs).
• Generator Transformer is one of the most important and costly
component of power generation next only to the generator.
• Any discussion on the topic of Life Extension of the generating
station will not be complete without discussing the ways and
means of Life Extension of the Generator Transformers.
AGEING OF GENERATOR TRANSFORMERS
• Ageing of solid insulation materials like Paper, Press Board,Wood based laminates etc.
• Ageing and degradation of Insulating Oil.
• Wear and tear of moving parts like Tap Changing Mechanism, Pressure Relief Device,
Monitoring equipments etc.
• Corrosion of metallic parts exposed to atmosphere.
In addition to the above, accelerated ageing taking place in the transformer on account of
the following abnormal operating conditions:
• Overloading of Transformers.
• Operation under overvoltage conditions.
• Impact of lightning/ switching surges from the system.
• Operation under short circuit conditions.
TESTS ON GENERATOR TRANSFORMERS• Dissolved Gas Analysis (DGA) of transformer oil.
• Monitoring of water content in transformer oil.
• Monitoring of Capacitance and Tan-Delta values of Condenser Bushing.
• Partial Discharge (PD) measurement.
• Winding Resistance Measurement
• Percentage Impedance Measurement
• Insulation Resistance Test
• Furan Analysis
• Magnetizing Current Test
• Sweep Frequency Response Analysis (SFRA)
• DIRANA Test
• Harmonics Measurement
DISSOLVED GAS ANALYSIS (DGA)
Number of gases are produced as by-products of the
ageing taking place in the insulating materials
1. Hydrogen 5. Acetylene
2. Methane 6. Carbon Dioxide
3. Ethane 7. Carbon Monoxide
4. Ethylene 8. Oxygen
MECHANISM OF GAS GENERATION IN TRANSFORMERS
Partial Discharge in OilLarge amount of H2 and little CH4
Arcing in Oil (Power Discharge)Large amount of H2 and C2H2
Oil Overheating
CH4, C2H6, C2H4 are formed in increasing order of severity
Traces of C2H2 in case of very high temperatures
Cellulose Overheating by Electric Fault
Large quantities of CO & CO2
DISSOLVED GAS ANALYSIS (DGA)Method recommended by CIGRE Task force
Ratio Value Indication
C2H2/C2H6
H2/ CH4
CO2/ CO
C2H2/ H2
>1
>10
>10
<3
>2 (with C2H2>30)
Discharge
Partial discharge
Cellulose overheating
Cellulose degradation
by electric fault
Fault gases diffusing
into main tank from
OLTC
Gas Concentration Ratios
DISSOLVED GAS ANALYSIS (DGA)Method recommended by IEC 60599 (1999)
Case Characteristic fault C2H2/C2H4 CH4/H2 C2H4/C2H6 CO2/CO C2H2/H2 O2/N2
PD Partial discharges (*) < 0.1 <0.2 - - -
D1 Low energy discharges >1 0.1-0.5 >1 - - -
D2 High energy discharges 0.6-2.5 0.1-1 >2 - - -
T1 Thermal fault (<300oC) (*) (*) <1 - - -
T2 Thermal fault (300,700oC) <0.1 >1 1,4 - - -
T3 Thermal fault (>700oC) <0.2 >1 >4 - - -
Cellulose (paper) degradation by
electric fault
- - - <3 - -
Fault gases diffusing into main tank
from OLTC
- - - - >2to3 -
Excessive consumption of oxygen as
a result of oil oxidation and/or paper
ageing
- - - - - <0.3
(*) Not significant
Note: In some countries, the ratio CH4/H2 is used instead of C2H4/C2H6.
Concentration ratio between gases
WATER CONTENT MEASUREMENT
• Hydrogen generated during ageing combines with the free oxygen
present in the oil and forms water. A part of this is absorbed by the
cellulose insulation and the balance remains as moisture in oil.
• As paper is highly hygroscopic in nature, when transformer is filled
with oil, it absorbs the moisture from oil, which affects its insulation
properties as well as reduces its life
System Voltage of Transformer kV Water content ppm, max.
Above Up to and including
- 72.5 20
72.5 245 15
245 420 10
420 800 10
TAN DELTA AND CAPACITANCE ON WINDINGS AND BUSHINGS
• This test is used to assess the condition of the oil and cellulose in terms of
moisture, insulation, etc.
• The advantage of this method is that it identifies the winding (HV or LV)
that has a possible problem.
• Dissipation factor of 0.5% is considered high whereas value of 1% is
considered hazardous for operation of transformer and may require its
replacement if completed its normal operating life.
• Capacitance value of bushing in service need to be compared with
factory test result value for deciding the extent of degradation.
WINDING RESISTANCE MEASUREMENT
• Transformer winding resistance measurement is carried out to
calculate the I2R losses and to calculate winding temperature
at the end of a temperature rise test.
• Winding resistance result should not vary by 5% with factory
test results or duplicate transformer result.
PERCENTAGE IMPEDANCE MEASUREMENT
• The percentage impedance of a transformer is the volt drop
on full load due to the winding resistance and leakage
reactance expressed as a percentage of the rated voltage.
• Test results must verify the nameplate rating. Percentage
error should be within 3%.
INSULATION RESISTANCE TEST
• Insulation resistance tests are made to determine insulation
resistance between individual windings to ground or
between individual windings.
• It shows the condition of insulation.
POLARIZATION INDEX TEST
• It is a ratio of the Insulation Resistance Measured for 10 minutes
to the insulation resistance value measured after 1 minute.
• PI is a good indication of winding contamination, moisture
ingress (leakage currents), and/or bulk insulation damage
(conduction currents).
• Acceptable PI for Power Transformers is greater than 1.5. For
Distribution Transformer, it should be at least 1.3.
DEGREE OF POLYMERISATION (DP)
• Remnant life of a transformer in service depends mainly on the
degree of degradation of the insulating materials
• DP is the average molecule size and closely relates to the
mechanical properties of paper
• Early and precise diagnosis of degradation not possible through
DGA.
• IEEE C57.91 loading guide mentions that one should be able to
operate a transformer well dried, oxygen free, and with 110 deg C
hotspot for 135,000 hours until 25% of retained tensile strength
(75% loss), or 150,000 hours until a DP of 200 is reached (80% loss
of tensile strength).
DEGREE OF POLYMERISATION (DP)
• Test is invasive in nature.
• Sample can be taken only after taking the equipment out of
service.
• Taking paper sample is a tedious job.
• Collected sample may not be representative of entire insulation.
Limitations
FURAN ANALYSIS
• The concentration of furans in the mineral oil of a power transformer
is a good indicator of the condition of the cellulose materials such as
paper, pressboard and cotton tapes used for insulation.
• Not an oil quality test.
• Historically used as a major input for RLA of transformers.
• Furan analysis is used as a supplement along with DGA & DP
tests
• Limiting value of total furanic content is
Good Health : <3mg/Kg
Satisfactory health : 3-5 mg/Kg
Deteriorated health : >5mg/Kg
MAGNETIZING CURRENT TEST
• Magnetizing current test of Transformer is performed to locate
defects in the magnetic core structure, shifting of windings, failure
in turn-to-turn insulation or problem in tap changers.
• Useful in distinguishing between severe and less severe cases.
• An agreement to within 25% of the measured exciting current with
the previous test is usually considered satisfactory.
• If the measured exciting current value is 50% higher than the value
measured during pre-commissioning checks, then the winding
needs further analysis.
SWEEP FREQUENCY RESPONSE ANALYSIS (SFRA)
• This test passes a range of frequencies (between 10 Hz to 2 MHz)
through the transformer and then calculates the transfer function.
From these responses, the mechanical condition can be assessed.
• Reliable and sensitive method to evaluate the mechanical and
electrical integrity of transformers active part.
• FRA is also carried out periodically for detection of deformation of
smaller magnitude, when transformer experiences several short
circuit forces.
• Helps in monitoring health and condition assessment of
transformers.
DIELECTRIC RESPONSE ANALYSER (DIRANA) TEST
• DIRANA determines the water content in paper without the need of oil sampling.
• It combines Frequency Domain Spectroscopy (FDS) and Polarization Depolarization
Current (PDC+)
• The power dissipation factor of the insulation is measured over a wide frequency
ranging from the µHz to the kHz region. The resulting curve contains information
about the insulation condition.
• The very low frequencies contain information on moisture in the solid insulation, while
the position of the slope in the mid-range frequencies indicates the conductivity of the
liquid insulation.
• DIRANA is the only device which compensates the influence of ageing by-
products. Otherwise, this would lead to an overestimation of the water content in
aged transformers.
HARMONICS MEASUREMENT
• The harmful effects of harmonic voltages and currents on
transformer performance often go unnoticed until an actual failure
occurs.
• Application of non-sinusoidal excitation voltages to transformers
increase the iron losses in the magnetic core of the transformer.
• A more serious effect of harmonic loads served by transformers is
due to an increase in eddy current losses.
• The increase in transformer eddy current loss due to harmonics
has a significant effect on the operating temperature of the
transformer.
TYPICAL CASE STUDY
Insulation section
Insulation
Resistance
60sec (G)
Polarization
Index
Tan
(%)
Moisture content
(%)
HV Winding versus LV
Winding connected to
Grounded Tank
0.0724 0.98 11.016 5.11
HV Winding versus LV
Winding (Ungrounded)0.0907 0.99 11.474 5.40
LV Winding versus HV
Winding connected to
Grounded Tank
0.0367 1.00 9.786 5.65
Oil Test Parameters within permissible limits
DGA High concentration of ethylene
Furan Analysis 4.8 mg/Kg
Test Results
RLA Study on 5.888MVA, 6.6/66kV Generator Transformer in about 40 Year Old Hydro Power Plant
OBSERVATIONS ON TEST RESULTS• Insulation Resistance shows poor condition of insulation. PI values less than 1
are questionable.
• Limit of Tan Delta for aged transformer is 1%. Tan Delta values for this
transformer are very poor. Results largely exceed normal limits as per service
life and indicate over ageing of transformers.
• Moisture content shows that the transformer is in wet condition.
• The oil test results are normal and the oil parameters are within permissible
limits as per IS 1866:2000.
• The DGA results exhibits high concentration of ethylene gas indicating
possible overheating or thermal fault in the transformer.
• Furan analysis shows presence of high quantity (4.8 mg/Kg) of furanic
compounds.This shows poor health of paper insulation.