Upload
others
View
2
Download
0
Embed Size (px)
Citation preview
This report is for the exclusive use of Intertek's Client and is provided pursuant to the agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use of this report. Only the Client is authorized to copy or distribute this report and then only in its entirety. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material, product or service must first be approved in writing by Intertek. The observations and test results in this report are relevant only to the sample tested. This report by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program.
1
TEST
REP
OR
T
REPORT NUMBER: 102891256SAT-001 ORIGINAL ISSUE DATE: February 27, 2017
REVISED DATE: N/A
EVALUATION CENTER 16015 Shady Falls Road
Elmendorf, TX 78112 Phone: (210) 635-8100
Fax: (210) 635-8101 www.intertek.com
RENDERED TO
Structurlam Products LP 2176 Government Street Penticton, BC V2A 8B5
Canada
PRODUCT EVALUATED: CrossLam® CLT Un-restrained Load-Bearing Floor/Ceiling Assembly
EVALUATION PROPERTY: Fire Resistance
Report of Testing a CrossLam® CLT Un-restrained Load-Bearing Floor/Ceiling Assembly for compliance with the applicable requirements of the following criteria: ASTM E119�16a, Standard Test Methods for Fire Tests of Building Construction and Materials, and CAN/ULC S101, Standard Methods of Fire Endurance Tests of Building Construction and Materials, Fifth Edition, dated June 2014.
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 2 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
1 Table of Contents 1 Table of Contents ............................................................................................................... 2 2 Introduction ........................................................................................................................ 3 3 Test Samples ..................................................................................................................... 3
3.1. SAMPLE SELECTION ................................................................................................. 3 3.2. SAMPLE AND ASSEMBLY DESCRIPTION................................................................. 3
4 Testing and Evaluation Methods ........................................................................................ 4 4.1. INSTRUMENTATION .................................................................................................. 4 4.2. TEST STANDARD ....................................................................................................... 4 4.3. TEST STANDARD ....................................................................................................... 4
5 Testing and Evaluation Results .......................................................................................... 5 5.1. RESULTS AND OBSERVATIONS ............................................................................... 5 5.2. EXAMINATION OF RESULTS ..................................................................................... 7
5.2.1. Correction Factor for the Fire Endurance Test ...................................................... 7 6 Conclusion ......................................................................................................................... 8
Appendix A: Assembly Drawings ..9 Appendix B: Test Data ..12 Appendix C: Test Photographs 31 List of Calibrated Instrumentation Used for Testing .75 Revision Page, Last Page of Report ..76
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 3 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
2 Introduction Intertek Testing Services NA, Inc. (Intertek) has conducted testing for Structurlam Products LP, on their CrossLam® CLT Un-restrained Load-Bearing Floor/Ceiling Assembly, to evaluate its fire resistance. Testing was conducted in accordance with and following the standard methods of ASTM E119�16a, Standard Test Methods for Fire Tests of Building Construction and Materials, and CAN/ULC S101, Standard Methods of Fire Endurance Tests of Building Construction and Materials, Fifth Edition, dated June 2014. This evaluation was completed on February 22, 2017.
3 Test Samples 3.1. SAMPLE SELECTION
Samples were randomly selected between the dates of January 25-26, 2017 by Intertek representative Dan Lungu, at the Structurlam Products LP manufacturing facility, located at 1675 Maple Street, Okanagan Falls, BC, V0H 1R2, Canada. The three pre-built CLT floor assemblies were received at the Evaluation Center on February 2, 2017 (Intertek Sample ID No. SAT1702020808-001). Other materials for the gypcrete floor were received between the dates of February 1-2, 2017, and assigned Intertek Sample ID Nos. SAT1702011247-001, -002 (adhesive and fiberglass composite mesh); SAT1702021045-001 (mixing sand). The subject test specimen is a traceable sample selected from the manufacturer's facility. Intertek selected the specimen and has verified the composition, manufacturing techniques and quality assurance procedures.
3.2. SAMPLE AND ASSEMBLY DESCRIPTION The three pre-built floor/ceiling assemblies consisted of cross-laminated timber, plywood splines, connection hardware, fire caulk, and a commercial topping floor. 1. Floor Assembly � Structurlam Panel Type 175 E, PRG-320 Grade E1M5, 5 layer CrossLam®
CLT panels produced from a glued-up CLT Mass Timber combination of 2×6 SPF MSR 2100 in all major strength (span) direction layers, and 2×6 SPF #2 and better in all minor strength (cross span) direction layers. Three (3) separate CrossLam® CLT panels were fastened together via a spline connection (see #2 above and drawing in Appendix A). Prior
1 2 3
4
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 4 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
to securing each section to each other using ratchet straps, one side of each vertical step down joint was coated with Hilti FS-ONE MAX #2101531 High Performance Intumescent Firestop Sealant. The sealant was putty-knife applied to fully cover one side and be uniform in thickness as much as possible. The sections were then secured together using ratchet straps until the sealant smeared out of the joint (no gaps).
2. Plywood Splines � 19 mm thick × 139 mm wide (nominal 3/4 in. thick × 5-1/2 in. wide)
plywood splines were inserted into the open slots of each of the two sections.
3. Securing Hardware – SWG ASSY Plus VG CSK fully threaded, zinc coated, AW 40 screws with drill tips were installed at 100 mm on-center (oc), staggered, at 15° angles. The client supplied a jig for proper angle installation.
4. Commercial Topping – 40 mm (1-1/2 in.) thick of Maxxon® Corporation Gyp-Crete® 2000™
Special Gypsum Cement Board Underlayment Compound pumped onto the top of the sample. Small pieces of plywood board were used to dam the top of the floor section in order to obtain the 40 mm thickness. Before the underlayment compound was pumped, the top of the CLT floor was reinforce with Maxxon® Reinforcement underlayment mesh screen, fully stapled onto the CLT floor. Additionally, the CLT floor was prepared by spraying Maxxon Acrylic Adhesive on top of the mesh. Work was performed and completed by representatives from G.L. Nettles, Inc. on February 3, 2017.
A 6 in. × 6 in. steel reinforcing angle was welded together around the perimeter of the floor sample in order to properly lift and move it. The sample was left undisturbed and allowed to cure at laboratory ambient temperature.
4 Testing and Evaluation Methods
4.1. INSTRUMENTATION The unexposed surface of the assembly was instrumented with a total of eleven (11), 24 GA, Type K, fiberglass jacketed thermocouples: TCs 1 - 9 were evenly distributed across the floor assembly as described in the standards; TCs 10 and 11 were installed over each of the butt-joint sections. The output of the thermocouples and the furnace probes were monitored by a 300-channel Yokogawa, Inc., Darwin Data Acquisition Unit. The computer was programmed to save data every 30 seconds. Following the test, the files were imported into MS Excel for tabular and graphical display (presented in Appendix C).
4.2. TEST STANDARD Testing was conducted in general accordance with the applicable requirements of ASTM E119�16a, Standard Test Methods for Fire Tests of Building Construction and Materials.
4.3. TEST STANDARD Testing was conducted in general accordance with the applicable requirements of CAN/ULC
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 5 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
S101, Standard Methods of Fire Endurance Tests of Building Construction and Materials, Fifth Edition, dated June 2014. The assembly was installed on the full scale horizontal furnace with the cross-laminated timbers facing the exposed side of the furnace, and tested to the time-temperature curves outlined in ASTM E119-16a and CAN/ULC S101-14.
5 Testing and Evaluation Results 5.1. RESULTS AND OBSERVATIONS The test was initiated on February 22, 2017. Nicholas Sills, representing Structurlam Products LP, was present to witness the test. The ambient temperature at the time of the test was 25 °C (77 qF) and the humidity was 33 % R.H. Prior to the start of the test, the relative humidity of the CLT was measured at 12 different locations and recorded to be between 8-9%. The test assembly was loaded to a client supplied reduced live load of 3.6 kPa (75 psf), evenly distributed over the whole assembly, using hydraulic cylinders [NOTE: The dead load supplied by the 40 mm (1-1/2 in.) thick topping of Gyp-Crete® was calculated to be 0.75 kPa (15 psf). In turn, the total load of the assembly was 4.35 kPa (90 psf) + the self weight of the assembly.]. The loading of the sample was conducted via the general guidelines of Section 7.2.1 of CAN/ULC S101-14. Once the load was fully applied, it was allowed to stabilize on the sample for a minimum 30 minutes prior to the start of the fire test. Observations made during the test are listed below: Time (min:sec) Observation(s)
0:00 The test was initiated at 11:23 a.m. 1:20 Smoke visible from un-exposed side. No visibility inside furnace 4:00 Light popping heard 5:00 High flaming inside furnace 10:00 Difficulty in controlling furnace curve due to high internal temperatures 11:30 All furnace burners off except one 13:00 Furnace burners cut off, blower left on at lowest speed. Sample cooling
naturally 25:00 Furnace burners still off, continuing to let sample cool down on its own 40:00 No visible changes 55:00 Deflection visible, 1/4 in. 60:00 Furnace burners back on (only 2), minimal gas flow. Slow climbing up 65:00 No changes, no visibility inside furnace, no hot spots on un-exposed side 90:00 No visible changes 95:00 Light pops heard
110:00 Smoke increasing form un-exposed side perimeter edges 120:00 Smoke from perimeter continuing to increase 125:00 Deflection more visible on sample from the un-exposed side 142:00 Pops heard 150:00 Test terminated per client request
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 6 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
The test was terminated at 150 minutes due to possible structural collapse of the floor. The floor/ceiling assembly withstood the fire endurance test without passage of flame or gasses hot enough to ignite cotton waste for the 150 minute duration. Transmission of heat through the floor/ceiling assembly during this duration did not raise the average temperature on the unexposed surface more than 140 °C (250 °F), nor any individual unexposed temperature more than 180 °C (325 °F) from the starting ambient temperature. The deflection of the floor assembly was measured at the mid-span of the sample. The deflection is presented in the table below:
Floor Deflection Measurements Prior to Fire Exposure Live Load (psf) Deflection (inches)
18.8 0 37.5 0 56.3 0
75 (initial) 1/8 75 (after 30 min) 1/4
Floor Deflection Measurements During Fire Exposure (not including cold loading)
Time (min)
Deflection (inches)
0:00 0 5:00 0
10:00 0 15:00 0 20:00 0 25:00 0 30:00 0 35:00 0 40:00 0 45:00 0 50:00 0 55:00 1/4 60:00 1/4 65:00 1/4 70:00 1/4 75:00 1/4 80:00 1/4 85:00 1/4 90:00 1/4 95:00 1/4 100:00 1/2 105:00 1/2 110:00 1/2 115:00 1/2 120:00 1/2 125:00 3/4 130:00 1-1/2 135:00 1-1/2 138:00 2
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 7 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
140:00 2-1/4 145:00 3 148:00 3-1/2
150:00 (end of test) 4-1/4
5.2. EXAMINATION OF RESULTS
5.2.1. Correction Factor for the Fire Endurance Test
In accordance with the test standards, a calculation for any correction to the indicated fire resistance period was done as shown in the following equation:
)(3)(2
LAAAI
Cs
s
��
(1)
In Equation 1, C is the correction factor, I is the indicated fire resistance period prior to modification with the correction factor, A is the area under the furnace average curve for the first 3/4 of the indicated fire resistance time, As is the area under the standard curve for the first 3/4 of the indicated fire resistance time, and L is a lag correction factor equal to 3240 °F•min. The correction factor was added to the indicated fire resistance period, yielding the corrected fire resistance period achieved by the specimen (see table below): Correction Factor for the Fire Endurance Test
ITEM
DESCRIPTION
TEST VALUE
C
correction factor
-1.36 minutes -81 second
I
indicated fire-resistance period
150 minutes
A area under the curve of indicated average furnace temperature for the first three fourths of the indicated period
169722 (°F•min)
As area under the standard furnace curve for the same part of the indicated period
172103 (°F•min)
ITEM
DESCRIPTION
TEST VALUE
L lag correction 3240
FIRE RESISTANCE PERIOD ACHIEVED BY THIS SPECIMEN ==>
150 minutes
Note: The standard specifies that the fire resistance be determined to the nearest integral minute. Consequently, if the correction factor is less than 30 seconds, and the test specimen met the criteria for the full indicated fire resistance period, no correction is deemed necessary.
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 8 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
6 Conclusion Intertek Testing Services NA, Inc. (Intertek) has conducted testing for Structurlam Products LP, on their CrossLam® CLT Un-restrained Load-Bearing Floor/Ceiling Assembly, to evaluate its fire resistance. Testing was conducted in accordance with and following the standard methods of ASTM E119�16a, Standard Test Methods for Fire Tests of Building Construction and Materials, and CAN/ULC S101, Standard Methods of Fire Endurance Tests of Building Construction and Materials, Fifth Edition, dated June 2014. This evaluation was completed on February 22, 2017. Based on the results of this test, the CrossLam® CLT Un-restrained Load-Bearing Floor/Ceiling Assembly described herein sustained an applied reduced live load of 3.6 kPa (75 psf) throughout the 150 minute test duration [NOTE: The dead load supplied by the 40 mm (1-1/2 in.) thick topping of Gyp-Crete® was calculated to be 0.75 kPa (15 psf). In turn, the total load of the assembly was 4.35 kPa (90 psf) + the self weight of the assembly]. Transmission of heat through the floor/ceiling assembly during this duration did not raise the average temperature on the unexposed surface more than 140 °C (250 °F), nor any individual unexposed temperature more than 180 °C (325 °F) from the starting ambient temperature. No flaming was observed on the unexposed side of the assembly for the 150 minute test duration. In turn, the assembly described herein achieved a fire resistance rating of 150 minutes. INTERTEK TESTING SERVICES NA, INC. Tested and Reported by: ______________________
Victor M. Burgos Engineering Team Leader, Fire Resistance
Reviewed by: _____________________ Herbert W. Stansberry II Engineering Supervisor
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 9 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
APPENDIX A Assembly Drawings
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 10 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 11 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
TC Layout
1 2 3
4 5 6
7 8 9
10
11
Furnace Door (South)
(North)
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 12 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
APPENDIX B Test Data
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 13 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 14 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 15 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 16 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 17 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 18 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 19 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 20 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 21 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 22 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 23 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 24 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 25 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 26 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 27 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 28 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 29 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 30 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 31 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
APPENDIX C Test Photographs
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 32 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
1. Construction Photos
1.
2.
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 33 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
3.
4.
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 34 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
5.
6.
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 35 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
7.
8.
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 36 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
9.
10.
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 37 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
11.
12.
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 38 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
13.
14.
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 39 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
15.
16.
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 40 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
17.
18.
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 41 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
19.
20.
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 42 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
21.
22.
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 43 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
23.
24.
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 44 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
25.
26.
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 45 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
27.
28.
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 46 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
29.
30.
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 47 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
31.
32.
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 48 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
33.
34.
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 49 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
Test Photos
35.
36.
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 50 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
37.
38.
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 51 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
39.
40.
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 52 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
41.
42.
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 53 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
43.
44.
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 54 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
45.
46.
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 55 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
47.
48.
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 56 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
49.
50.
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 57 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
51.
52.
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 58 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
53.
54.
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 59 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
55.
56.
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 60 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
57.
58.
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 61 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
59.
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 62 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
Post-Test Photos
60.
61.
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 63 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
62.
63.
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 64 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
64.
65.
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 65 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
66.
67.
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 66 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
68.
69.
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 67 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
70.
71.
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 68 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
72.
73.
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 69 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
74.
75.
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 70 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
76.
77.
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 71 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
78.
79.
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 72 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
80.
81.
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 73 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
82.
83.
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 74 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
84.
85.
Structurlam Products LP February 27, 2017 Report No. 102891256SAT-001 Page 75 of 76
RT-L-AMER-Test-613 Issued: 4/8/2014 Revised: 05/30/2016
CALIBRATED INSTRUMENTATION USED FOR TESTING
Description Serial No. Calibration Due Date
DAQ Unit 48JF0082 3/22/2017
Thermo/Hygrometer 140626113 9/18/2017
Stopwatch 150135668 2/27/2017
Digital Calipers 91111598 1/26/2018
Moisture Meter 2247 2/25/2017
Pressure Gauge 20TV76-3 5/2/2017