Replacement kit for Hiquel TCP-M2, TCP-M2A and TCP-M2B. The Hiquel TCP-M2 and its successors TCP-M2A and TCP-M2B are combined Phase Failure and Thermistor Motor Over-temperature protection relays which were manufactured for many years for a UK based manufacturer of Traction and Hydraulic Lift Electrical Control Panels. Charter Controls was instrumental in the development of the TCP-M2 which was manufactured in Austria by Hiquel Elektronic GmbH for our customer Liftstore, later Thames Valley Controls Limited (TVCL) The TCP-M2/A/B is no longer manufactured but it is easy for a competent suitably qualified engineer to replace using individual Phase Failure relays and Thermistor Motor Over-temperature relays. These do not have to be supplied by Charter Controls however we recommend the two items in this kit. DO NOT ATTEMPT THIS MODIFICATION UNLESS YOU ARE SUITABLY QUALIFIED. CHARTER CONTROLS, ITS OFFICERS AND EMPLOYEES CANNOT BE HELD LIABLE FOR ANY DAMAGE, INJURY OR DEATH CAUSED BY INCORRECT FITTING. This information is for guidance only and may not suit all TCP-M2, TCP-M2A & TCP-M2B installations. The TCP-M2 was supplied from the three phases, which internally powered the Phase Failure function and the Thermistor function. The MG21DH and MJ93BK have separate supply connections. Phase Failure function The GIC MG21DH 3-phase 3-wire Voltage Relay (Phase Failure Relay) will provide Phase Failure protection. It should be set to measure the correct three-phase supply voltage using the rotary switch on the front plate The Three-phase connections L1-L2-L3 on the TCP-M2 are connected to L1-L2-L3 on the MG21DH. The alarm relay connections 15 (Common), 16 (NC), 18(NO) replace connections 11 (Common), 12(NC), 14(NO) on the TCP-M2. NOTE: After a Phase fault the MG21DH will auto-reset when the 3-phase supply voltage returns to normal. Check the DIP Switch setting on your TCP-M2 and verify that this is acceptable. Thermistor Motor Over-temperature function The GIC MJ93BK PTC Thermistor Relay will provide Motor Over-temperature protection It must be connected to a supply voltage between 220-440Vac The Thermistor connections T1 and T2 on the TCP-M2 must be connected to P1 and P2 on the MJ93BK The alarm relay 1 connections 15 (Common), 16 (NC), 18(NO) replace connections 21(Common), 22(NC), 24(NO) on the TCP-M2 The alarm relay 2 connections 25 (Common), 26 (NC), 28(NO) replace connections 31(Common), 32(NC), 34(NO) on the TCP-M2. NOTE: Connections Y1 and Y2 are used to select Manual or Auto-reset after a Thermistor alarm. Check the DIP switch settings on your TCP-M2 and verify the required function. IF YOU ARE NOT SUITABLY QUALIFIED TO REPLACE YOUR TCP-M2 WITH THIS KIT YOU ARE STRONGLY ADVISED TO FIND A COMPETENT ENGINEER.

Replacement kit for Hiquel TCP-M2, TCP-M2A and TCP-M2B. · Replacement kit for Hiquel TCP-M2, TCP-M2A and TCP-M2B. ... TCP-M2A & TCP-M2B installations. ... NOTE: Connections Y1 and

  • Upload
    others

  • View
    48

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Replacement kit for Hiquel TCP-M2, TCP-M2A and TCP-M2B. · Replacement kit for Hiquel TCP-M2, TCP-M2A and TCP-M2B. ... TCP-M2A & TCP-M2B installations. ... NOTE: Connections Y1 and

Replacement kit for Hiquel TCP-M2, TCP-M2A and TCP-M2B.

The Hiquel TCP-M2 and its successors TCP-M2A and TCP-M2B are combined Phase Failure and Thermistor Motor

Over-temperature protection relays which were manufactured for many years for a UK based manufacturer of

Traction and Hydraulic Lift Electrical Control Panels.

Charter Controls was instrumental in the development of the TCP-M2 which was manufactured in Austria by Hiquel

Elektronic GmbH for our customer Liftstore, later Thames Valley Controls Limited (TVCL)

The TCP-M2/A/B is no longer manufactured but it is easy for a competent suitably qualified engineer to replace

using individual Phase Failure relays and Thermistor Motor Over-temperature relays. These do not have to be

supplied by Charter Controls however we recommend the two items in this kit.

DO NOT ATTEMPT THIS MODIFICATION UNLESS YOU ARE SUITABLY QUALIFIED. CHARTER CONTROLS, ITS OFFICERS

AND EMPLOYEES CANNOT BE HELD LIABLE FOR ANY DAMAGE, INJURY OR DEATH CAUSED BY INCORRECT FITTING.

This information is for guidance only and may not suit all TCP-M2, TCP-M2A & TCP-M2B installations.

The TCP-M2 was supplied from the three phases, which internally powered the Phase Failure function and the

Thermistor function. The MG21DH and MJ93BK have separate supply connections.

Phase Failure function

The GIC MG21DH 3-phase 3-wire Voltage Relay (Phase Failure Relay) will provide Phase Failure protection. It should

be set to measure the correct three-phase supply voltage using the rotary switch on the front plate

The Three-phase connections L1-L2-L3 on the TCP-M2 are connected to L1-L2-L3 on the MG21DH.

The alarm relay connections 15 (Common), 16 (NC), 18(NO) replace connections 11 (Common), 12(NC), 14(NO) on

the TCP-M2.

NOTE: After a Phase fault the MG21DH will auto-reset when the 3-phase supply voltage returns to normal. Check

the DIP Switch setting on your TCP-M2 and verify that this is acceptable.

Thermistor Motor Over-temperature function

The GIC MJ93BK PTC Thermistor Relay will provide Motor Over-temperature protection

It must be connected to a supply voltage between 220-440Vac

The Thermistor connections T1 and T2 on the TCP-M2 must be connected to P1 and P2 on the MJ93BK

The alarm relay 1 connections 15 (Common), 16 (NC), 18(NO) replace connections 21(Common), 22(NC), 24(NO) on

the TCP-M2

The alarm relay 2 connections 25 (Common), 26 (NC), 28(NO) replace connections 31(Common), 32(NC), 34(NO) on

the TCP-M2.

NOTE: Connections Y1 and Y2 are used to select Manual or Auto-reset after a Thermistor alarm. Check the DIP

switch settings on your TCP-M2 and verify the required function.

IF YOU ARE NOT SUITABLY QUALIFIED TO REPLACE YOUR TCP-M2 WITH THIS KIT YOU ARE

STRONGLY ADVISED TO FIND A COMPETENT ENGINEER.

Page 2: Replacement kit for Hiquel TCP-M2, TCP-M2A and TCP-M2B. · Replacement kit for Hiquel TCP-M2, TCP-M2A and TCP-M2B. ... TCP-M2A & TCP-M2B installations. ... NOTE: Connections Y1 and

Cat. No.Parameters

Supply Monitoring Series SM 175

ORDERING INFORMA TION

MK21D5 MA21DN MD21DF MG21DH

DescriptionCat. No.

MA21DN

MC21D5

MD21DFMG21DH

MK21D5

MG21DF

Phase Sequence, Asymmetry & Phase Loss Monitoring, 1 C/O Phase Sequence, 1 C/OPhase Sequence & Asymmetry Monitoring, 1 C/OPhase Sequence, Under Voltage & Over Voltage Monitoring, 1 C/OPhase Sequence, Asymmetry & Voltage Monitoring with Fixed OFF Delay (5 s), 1 C/O Phase Sequence, Asymmetry & Voltage Monitoring with Fixed ON Delay (5 s), 1 C/O

MC21D5

3 Phase 3 Wire, 208 - 480 VAC, 45 - 65 HzSupply Voltage Un

3 VA

o o- 15 C to +60 Co o- 20 C to +70 C

Max. 95%

Base / DIN rail

Power Consumption

Time DelaySetting Accuracy:+/- 10% of Full Scale

Operating Temperature Storage Temperature Humidity (Non Condensing Limits)

LED Indications

Degree of Protection Terminals - IP 20, Housing - IP 30, Pollution Degree - 2Dimension (W x H x D)WeightMounting

Certification

Supply Variation -12% to + 10%

Settable Nominal Voltage (Un)Under VoltageOver Voltage Asymmetry 30% Fixed

+/- 5% of full scale Setting Accuracy

208 - 220 - 380 - 400 - 415 - 440 - 480 VAC

Trip Levels :5% to 15% 10% Fixed

-2% to -20% (Un) -5% to -25% (Un)+2% to +20% (Un) +5% to +25% (Un)

ON Delay

OFF Delay

~ 500 ms 5 s (Fixed) 5 s (Fixed)

~ 100 ms 0.5 to 15 s 5 s (Fixed)

1 C/O (SPDT) 5A (Resistive) @ 250 VAC / 30 VDC

63 x 10 Operations 51 x 10 Operations

Healthy Phase Reverse Asymmetry

Relay (R)

OVUVAS

AllLEDs

OFFFlashing

Relay LED Continuous ON (Red Colour) Power LED Continuous ON (Green Colour)Relay LED Flashing (Red Colour) Power LED Flashing (Green Colour)

Relay LED Off (Red Colour)OV - Red Colour LED ON

Phase Fail Un Pot changed in running conditions

UV - Red Colour LED ON AS-Red Colour LED ON

18 X 90 X 59 (in mm)70 g (unpacked)

0.5 to 15 s

0.5 to 100 s

Utilization Category AC - 15DC - 13

Rated Voltage (Ue): - 120/240 V, Rated Current (Ie) :- 3/1.5 ARated Voltage (Ue): - 24/125/250 V, Rated Current (Ie) :- 2/0.22/0.1 A

In the event of phase sequence or phase loss fault, OFF delay is ~100ms

P CIS R 14-1 Class BIEC 61000-4-2 Level III

0- l VIEC-6100 4-4 Leve I 0- l VIEC-6100 4-5 Leve I 0- LIEC-6100 4-11 All 7 evels

t o w 55Tes v ltage bet een input & output - IEC 602 -5, 2kV

EMI/ EMCRadio Interference SuppressionESDElectrical Fast TransientsSurgesVoltage Dips, Interruptions Isolation

Relay OutputContact RatingMechanical Life Electrical Life

N A

N A

• Compact 17.5 mm wide• Multi-voltage from 3 x 208 to 3 x 480 V • Controls correct sequence of three phases & own supply voltage • LED indication for all faults & for change in settings during run time for better security• 1 C/O configuration

,IEC 60255RoHS Compliant

N AN A

N AN A

N A

N AN AN AN A

50

Page 3: Replacement kit for Hiquel TCP-M2, TCP-M2A and TCP-M2B. · Replacement kit for Hiquel TCP-M2, TCP-M2A and TCP-M2B. ... TCP-M2A & TCP-M2B installations. ... NOTE: Connections Y1 and

Suitability for use :

These are products with Auto reset and

Auto Switch On, hence never use the

products for an application involving

significant risk to life without ensuring

that the system as a whole has been designed

to address the risks and that our products are

properly rated and installed for the intended

use within the entire system or equipment.

MK21D5MC21D5MA21DNMD21DFMG21DHMG21DF

MLL024 - 05

SUPPLY MONITORING DEVICE

SERIES SM175

1) Do not touch the terminals while power

is being supplied.

2) Tighten terminal screws with the

specified torque.

3) Always follow instructions stated in

product leaflet.

4) Before installation, check to ensure that

specifications agree with intended

application.

5) Installation to be done by skilled

electrician.

6) Suitable dampers should be provided in

the event of excessive vibrations.

Caution :

RoHS

TECHNICAL SPECIFICATION:

Pollution Degree

Frequency

Function

Cat. No.:

Cat. No.:

Power Consumption

Adjustable Nominal Voltage ( )

Asymmetry

Operate TimeTime Delay

Setting Accuracy

Trip Levels

Setting Accuracy

+/- 10 % of Full

scale Release Time

Supply Voltage ( )

MA21DN

Phase and Voltage Control

MD21DF

2

3 VA (Max.)

30% fixed 5% to 15%

(< 0.5 to

15) s

5 s fixed

In the event of phase sequence or phase loss fault, release time is ~100 ms

5 s fixed

2% to 20% of

-2% to -20% of

208 - 220 - 380 - 400 - 415 - 440 - 480 VAC

MG21DH

-5% to -25% of

( 0.5 to 100) s<

5 s fixed

10% fixed

5% to 25% of

R Continuous ON Continuous ON

Phase Reverse

Healthy

Flashing

Relay

Phase Fail / Supply Voltage > 577. 5 VACALL

LEDS Pot changed during running conditions

AS

OFF

UV

OV

LED Indications

Asymmetry

Degree of Protection

18 x 59 x 9 0

95 % (Rh)

-20 C to +70 C

-15 C to +60 C

1 x 10 Operations5

3 x 10 Operations6

Ag Alloy

Mechanical Life Expectancy

Output

Electrical Life Expectancy

Operating Temperature

Storage Temperature

Housing Flame Retardant UL 94-V0

Humidity (Non-Condensing)

Contact Material

Certifications

Max. Operating Altitude

Weight (Unpacked)

Dimensions in mm (WxHxD)

CE , RoHS

2000 m

70 g Approx.

IP-20 for Terminals ; IP-30 for Housing

1 C/O , 5A (Res.) @ 250 VAC / 30 VDC

Utilization

Category

Rated Voltage (Ue): 120/240 V; Rated Current (Ie): 3.0/1.5 A

Asymmetry R OFFN.A.

R/FlashingR Flashing

208 to 480 VAC, 3-Ph -3Wire (-12% to +10% of )

45 to 65 Hz

AC - 15

DC - 13 Rated Voltage (Ue): 24/125/250 V; Rated Current (Ie): 2.0/0.22/0.1 A

100 ms fixed

500 ms fixed

Phase Control

MK21D5 MC21D5

( 0.5 to 15) s<

N.A.

N.A.

N.A.

N.A.

N.A.

Over Voltage

Under Voltage

R OFF

MG21DF

( 0.5 to 100) s<

5 s fixed

N.A.N.A.

N.A.

N.A.

N.A.

+/- 5% of full scale

Under Voltage

Over Voltage

º º

º º

Mounting Base / Din-Rail (35 mm Symmetrical)

Notice :

Product innovation being a continuous process,

we reserve the right to alter specifications

without any prior notice.

MalcolmG
Highlight
MalcolmG
Highlight
Page 4: Replacement kit for Hiquel TCP-M2, TCP-M2A and TCP-M2B. · Replacement kit for Hiquel TCP-M2, TCP-M2A and TCP-M2B. ... TCP-M2A & TCP-M2B installations. ... NOTE: Connections Y1 and

Multi-voltage from 3x208 to

3x480 V

Controls own supply voltage.

LED status indication.

SPDT Relay output

(5 A resistive)

Din Rail & Base mounting.

Controls:-

1. Correct sequence of the three phases.

2. Failure of any of the three phases.

3. Failure due to Asymmetry fixed at 30%.

Controls:-

1. Correct sequence of the three phases.

2. Failure of any of the three phases.

3. Under & Over Voltage adjustable from 2 to 20%

of Un (Up to - 12% across 3x208 V Range;

Up to +10% across 3x480 V Range)

Up to - 16% across 3x220 V Range;

MD21DF

MG21DH/MG21DFControls:-

1. Correct sequence of the three phases.

2. Failure of any of the three phases.

3. Under & Over Voltage adjustable from 5 to 25%

of Un (Up to - 12% across 3x208 V Range;

Up to +20% across 3x440 V Range;

)

4.

Up to - 16% across 3x220 V Range;

Up to +10% across 3x480 V Range

Failure due to Asymmetry fixed at 10%.

Controls:-

1. Correct sequence of the three phases.2. Failure of any of the three phases .

3. Failure due to Asymmetry adjustable f

to 15%.

rom 5%

MA21DN

MK21D5

MC21D5

MAIN FEATURES :

Controls:-

1. Correct sequence of three phases.

2. Failure of any of three phases when voltage

falls below rated minimum of threshold.

FUNCTION DIAGRAM

MK21D5

Note:

1. In case of MC21D5, MG21DH/MG21DF, phase

imbalance levels are fixed. So, for very large

motors with excessive back e.m.f. relay suitability

to be checked by the user.

MA21DN / MC21D5

t

MD21DF

t

MG21DH/MG21DF

t

RT

OVERALL & MOUNTING

DIMENSIONS (in mm)

SUPPLY MONITORING DEVICE

SERIES SM175

CERTIFICATION :

Terminal Details :

2. Minimum threshold supply voltage of tripping is

140 VAC for MK21D5,MC21D5.

1.1 N.m (10 Lb.in)

Terminal screw - M3.5

2 x0.2 ...2.5 mm

Solid Wire / Signal

Wire Ferrule

²

1 x 24 to 10AWG

3.5....5.0mm0

MalcolmG
Highlight
MalcolmG
Highlight
MalcolmG
Highlight
Page 5: Replacement kit for Hiquel TCP-M2, TCP-M2A and TCP-M2B. · Replacement kit for Hiquel TCP-M2, TCP-M2A and TCP-M2B. ... TCP-M2A & TCP-M2B installations. ... NOTE: Connections Y1 and

Cat. No.Parameters

MJ83BK MJ93BK MJA3BK

110 - 240 VAC

50/60 Hz

Supply Variation

Frequency

-20% to + 10%

220 - 440 VAC 24 VAC/DCSupply Voltage ( )

(of )

4 VAPower Consumption (Max.)

Trip Level

Sensor Short

Hysterisis

2 VA

Reset Level

Sensor Open

< 1.5 Max Cold Res( ) of Sensor Chain

Reset Mode

Repeat Accuracy 1%

Auto, Manual, Remote

Trip Settings

ON Delay 500 ms

100 ms

150 ms

OFF Delay

Reset Time

TimeDelay

Utilization Category AC - 15

DC - 13

Rated Voltage (Ue): 120/240 V, Rated Current (Ie): 3.0/1.5 A

Rated Voltage (Ue): 24/125/250 V, Rated Current (Ie): 2.0/0.22/0.1 A

51 x 10 63 x 10

5A (Resistive) @ 250 VAC / 28 VDC

2 C/O 2 C/O 2 C/O Relay Output

OutputContact Rating

Electrical Life

Mechanical Life

Operating Temperature Storage Temperature

o o- 15 C to +60 Co o- 25 C to +80 C

LED Indications

All LEDs OFF

Green LED

Red LED

Power Supply Fail

Healthy Continuous ON Sensor OpenFlashing

Relay ON Continuous ON Sensor ShortFlashing

ORDERING INFORMATION

Enclosure

Degree of Protection IP 20 for Terminals, IP 40 for Enclosure

Base / DIN rail

Dimension (W x H x D) (in mm)

Weight (unpacked)

Mounting

Certification

22.5 X 83 X 100.5

120 g

Flame Retardant UL94-V0

Humidity (Non Condensing) 95% (Rh)

RoHS Compliant

UL Approval not applicable for Cat Nos. MJ83BK & MJ93BK.

Cat. No. Description

MJ83BK 110 - 240 VAC, PTC Thermistor Relay, 2 C/O

MJ93BK 220 - 440 VAC, PTC Thermistor Relay, 2 C/O

MJA3BK 24 VAC/DC, PTC Thermistor Relay, 2 C/O

MJ81BK 110 - 240 VAC, PTC Thermistor Relay, 1 C/O

MJ91BK 220 - 440 VAC, PTC Thermistor Relay, 1 C/O

EMI / EMCHarmonic Current Emissions IEC 61000-3-2ESD IEC 61000-4-2Radiated Susceptibility IEC 61000-4-3Electrical Fast Transients IEC 61000-4-4Surges IEC 61000-4-5Conducted Susceptibility IEC 61000-4-6Voltage Dips & Interruptions (AC) IEC 61000-4-11Voltage Dips & Interruptions (DC) IEC 61000-4-29Conducted Emission CISPR 14-1Radiated Emission CISPR 14-1

EnvironmentalCold Heat IEC 60068-2-1Dry Heat IEC 60068-2-2Vibration IEC 60068-2-6Repetitive Shock IEC 60068-2-27Non-Repetitive Shock IEC 60068-2-27

PTC Thermistor Relay Series PD 225• Monitors and Protects Motors with Integrated PTC Resistor sensors • Protection against Over heating for Heavy Duty Load, High Switching Frequency, High operating temperature & Insufficient cooling conditions • Wide Auxiliary Supply Voltage: 24 VAC/DC, 110 - 240 VAC & 220 - 415 VAC • LED Indications for Healthy, Unhealthy, Sensor Open/Short conditions• 1 C/O & 2 C/O Configuration• Reset Options: Auto, Manual and Remote

2.7

1.71

( ± 5%)

> 20 ( ± 5%)

( ± 5%)

< ( ± )

40 ( ± )

112

MalcolmG
Highlight
MalcolmG
Highlight
MalcolmG
Highlight
MalcolmG
Highlight
MalcolmG
Highlight
Page 6: Replacement kit for Hiquel TCP-M2, TCP-M2A and TCP-M2B. · Replacement kit for Hiquel TCP-M2, TCP-M2A and TCP-M2B. ... TCP-M2A & TCP-M2B installations. ... NOTE: Connections Y1 and

Functional Description:

SENSOR SHORT:

SENSOR OPEN:

AUTO RESET:

MANUAL RESET:

REMOTE RESET:

ADVANTAGE OF REMOTE RESET:

Function Diagram:

Test Voltage between I/P and O/P

Test Voltage between all terminals andenclosureImpulse Voltage between I/P and O/P

Single Fault

Insulation Resistance

Leakage Current

IEC 60947-5-1 3.0 (2003-11) Level IV

IEC 61010-1 2.0 (2001-02)

UL 508 17 (1999-01)

UL 508 17 (1999-01) <3.5 mA

IEC 60947-5 3.0 (2002-12) 2 kV

IEC 60255-5 3.0 (2003-12) 4 kV

Conformity to Standards:

Product

Harmonic Current Emission

ESD Immunity

Radiated Susceptibility

Electrical Fast Transients

Surge Immunity

Conducted Susceptibility

Voltage Dips and Interruptions(AC)

Voltage Dips and Interruptions(DC)

IEC 61000-4-2 Ed. 1.2 (2001-04) Level III

IEC 61000-4-3 Ed. 3.0 (2006-02) Level III

IEC 61000-4-4 Ed. 2.0 (2004-07) Level IV

IEC 61000-4-5 Ed. 2.0 (2005-11) Level IV

2.2 IEC 61000-4-6 Ed. (2006-05) Level III

IEC

IEC

61000-4-11 2.0 (2004-03) All 7 Levels

61000-4-29 1.0 (2000-08) All 5 Levels

IEC 60255 1. (2005-12)

IEC 61000-3-2 3.0 (2005-11) Class A

EMC:

Conducted Emission

Radiated Emission

CISPR 14-1 Ed. 5.0 (2005-11) Class B

CISPR 14-1 5.0 (2005-11) Class B

Connections for Mode Selection:

Connection Diagram:

MJ81BK/MJ91BK

+ -

MJA3BK

Overall Product Dimensions and Mounting

Details: (in mm)

UNSPECIFIED TOLERANCE IS +/-0.1

Environmental:

Cold Heat

Dry Heat

Vibration

Repetitive Shock

Non-Repetitive Shock

IEC 60068-2-1 6.0 (2007-03)

IEC 60068-2-2 5.0 (2007-07)

IEC 60068-2-6 7.0 (2007-12), 5 g

IEC 60068-2-27 Ed. 4.0 (2008-02), 40 g, 6 ms

IEC 60068-2-27 Ed. 4.0 (2008-02), 30 g,15 ms

Safety:

Ed.

Ed.

For Remote reset operation connect a switch across Y1 and Y2 terminals, Device will be in Auto reset mode ,if switch is open ,other wise device will be in Manual reset mode.

If fault occurs and recovers while the device is in Manual Reset mode, then user can put the device in Auto mode temporarily and switch ON the realy and Put the device back in Manual Reset mode, So, attending the decive can be avoided.

For Auto reset operation, keep Y1 and Y2 terminals open . Device will reset automatically when the total loop resistance of the series connected thermistors drops below 1.6 k +/5%. Ù

Probe cable open Circuit detected by device if resistance is above 10k + and cannot reset until resistance is lower then 1.6 k + 5 % The resistance at 25C0 of probe circuit must be with in 40 < 1.5 k range.

ÙÙ

Ù

Thermistor Relay protects and controls motors and alternators fitted with PTC ther mistorsensors. Motorheating is directly measured by temperature sensors that are in corop orated in starter windings. This ensures a direct control in following, operating.Conditions: heavy duty high, switching frequence, single phasing, high ambient temperature and insufficient cooling. This really disconnects when probe resistance exceeds 3.6 k + 5% and cannot reset until resistance lower then 1.6 k,+5% Auxiliary supply voltage should be applied to device between terminals A1-B2 to product ,connection. The relay trips through probe heating, resetting may be AUTO ,MANUAL or REMOTE.

Ù

Probe cable short circuit is detected by device if resistance is lower then 20+4 and resets when probe resistance is greater then 40 + 4.

ÙÙ Ù

For Manual reset operation , keep Y1 and Y2 terminals short. Device will reset manually by pressing RESET key of device when the total loop resistance of the series connected thermistors drops Below 1.6 k +/-5%.

Ù

Ed.

Ed.

Ed.

Ed.

Ed.

Ed.

Ed.

Ed.

Ed.

Ed.

Ed.

Ed.

MalcolmG
Text Box
NOTE; MJ93BK as per MJA3BK but supply voltage 220-440vac
MalcolmG
Highlight
MalcolmG
Highlight
MalcolmG
Line
Page 7: Replacement kit for Hiquel TCP-M2, TCP-M2A and TCP-M2B. · Replacement kit for Hiquel TCP-M2, TCP-M2A and TCP-M2B. ... TCP-M2A & TCP-M2B installations. ... NOTE: Connections Y1 and

MLL026-01

Relative Humidity

Operating Position

Maximum Operating Altitude

Degree of Protection

Pollution Degree

95% (without condensation)

Any

2000 m

IP 40 (Enclosure); IP 20 (Terminals)

2

Technical Characteristics :

Supply Characteristics:Cat. Nos.

Supply Voltage (Un)

Supply Tolerance

Power Consumption

Relay O/P Characteristics:

Contact Rating

Contact Arrangement

Utilization Category

Utilization Category

Contact Material

Mechanical Life Expectancy

Electrical Life Expectancy

Feature Characteristics:

6 A @ 250 VAC / 28 VDC

1 C/O 2 C/O

MJ81BK MJ91BK MJA3BK

Ag alloy6

3 X 10 operations 5

1 X 10 operations

3.6 kÙ, +/- 5 %

1.6 kÙ, +/- 5 %

< 20 Ù, +/- 4 Ù< 40 , - 4 +/

> 10 k -Ù, +/ 5%

Trip level

Reset Level

Sensor ShortHysterisis

Sensor Open

Max. Cold resistance of sensor chain

Reset Selector

Manual Reset mode

<1.5 k

Manual reset / Auto Reset / Remote Reset Selection.

-20% to +10% of Un

3 VA 2 VA

(110 to 240) VAC, (220 to 440) VAC, 24 V AC/DC, (48 to 62) Hz (48 to 62) Hz (48 to 62) Hz

Ue rated voltage VIe rated current A

DC-13

AC-15120/2403.0/1.5

Ue rated voltage VIe rated current A

24/125/2502.0/0.22/0.1

PTC Thermistor Relay Series - PD 225

Cat. Nos. MJ81BK

MJ91BK

MJA3BK Caution:

Features:Response Time

LED Indications Continuous ON

Continuous OFF

Flashing

Continuous ON

Continuous OFF

Flashing

Operate Time (OT)

Release Time (RT)

Reset Time

Mounting / Dimensions (W X H X D)

Weight (Unpacked)

Certifications

~ 500 ms

~ 100 ms

~ 150 ms ~ 200 ms

Power supply healthy

Power fail

Sensor open

Relay ON

Relay OFF

Sensor Short

Base Or / Din-Rail / (22.5 X 83 X 100.5)

~ 120 g

CE, RoHS, IEC 60255 Ed. 1 (2005-12)

Repeat Accuracy 1% + -

Ambient Conditions:Operating Temperature

Storage Temperature -25 C to +80 C

-15 C to +60 C

Manual reset using RESET key

RoHS

Terminal Details:

0

Terminal Screw - M3

1...6

Ù Ù

Ù

1.Always follow instructions stated in this product leaflet.2.Before installation, check to ensure that.3.the specifications agree with the intended application.4.Installation to be done by skilled electrician.5.Automation and control devices must be Automation and control devices must be against any risk of involuntary actuations.6.Suitable dampers should be provided in the event of excessive vibrations.

Note: Product innovation being a continuous process, we reserve the right to alter specifications without any prior notice.

Operable in various supply voltage conditions By selecting proper model. Various mode selection like AUTO, MANUAL, And REMOTE RESET. SPDT / DPDT Relay output. LED indications for healthy, unhealthy, Sensor open / short conditions. DIN Rail & Base Mounting.

Page 8: Replacement kit for Hiquel TCP-M2, TCP-M2A and TCP-M2B. · Replacement kit for Hiquel TCP-M2, TCP-M2A and TCP-M2B. ... TCP-M2A & TCP-M2B installations. ... NOTE: Connections Y1 and

Note: Product innovation being a continuous

process, we reserve the right to alter

specifications without any prior notice.

Before installation, check to ensure that the

specifications agree with the intended

4. Installation to be done by skilled electrician.

Automation and control devices must be

installed properly so that they are protected

against any risk of involuntary actuations.

6. Suitable dampers should be provided in the

Technical Characteristics:

Supply Characteristics

Cat. Nos.

Supply Voltage (Un)

Supply Tolerance

Power Consumption

Relay O/P Characteristics

Contact Rating

Contact Arrangement

Utilization Category

Utilization Category

Contact Material

Mechanical Life Expectancy

Electrical Life Expectancy

Feature Characteristics

6A@250 VAC / 28 VDC

MLB4BK MLC4BK

AgSnO alloy2

3 X 10 operations6

1 X 10 operations5

3.6 kΩ, +/- 5 %

1.6 kΩ, +/- 5 %

< 20 Ω Ω, +/- 4< 40 , - 4Ω Ω+/

> 10 k -Ω, +/ 5%

Trip level

Reset Level

Sensor ShortHysterisis

Sensor Open

Max. Cold resistance of sensor chain <1.5 kΩ

-20% to +10% of Un

12 VA

3 Ph - 3 Wire 3 Ph - 3 Wire380 VAC - 480 VAC 380 VAC - 480 VAC

Ue rated voltage VIe rated current A

DC-13

AC-15120/2403.0/1.5

Ue rated voltage VIe rated current A

24/125/2502.0/0.22/0.1

PHASE SEQUENCE &THERMISTOR RELAYSeries: PD 225

Cat. Nos. MLB4BK

MLC4BK

1. Always follow instructions stated in this

product leaflet.

2.

application.

5.

event of excessive vibrations.

Caution:

Features:

LED indications for healthy, unhealthy, Sensor

open / short conditions, Phase reverse conditions.

Trip by phase reverse or temperature.

2 independent SPST Relay output.

AUTO/MANUAL RESET MODE selection for thermistor.

DIN RAIL and Base mounting.

Reset mode

Response Time

LED Indications Continuous ON

Continuous OFF

Flashing

Continuous ON

Continuous ON

Continuous OFF

Continuous OFF

Flashing

Operate Time (OT)

Release Time (RT)

Reset Time

Terminal Capacity

Torque

Mounting / Dimensions (W X H X D)

Weight (Unpacked)

Certifications

< 500 ms

~ 100 ms

~ 150 ms

Power supply healthy

Power fail

Sensor open

Thermistor Relay ON

Phase Sequence Relay ON

Thermistor Relay OFF

Phase Sequence Relay OFF

Sensor Short

(1 to 4) mm2

0.6 N-m

BASE / DIN-RAIL / (36 X 60 X 90) mm

~ 120 g (approx.)

CE, RoHS, IEC 60255 Ed. 1 (2005-12)

Repeat Accuracy 1%+-

Ambient Conditions

Operating Temperature

Storage Temperature

Relative Humidity

Operating Position

Maximum Operating Altitude

Degree of Protection

Pollution Degree

95% (without condensation)

Any

2000 m

IP 40 (Enclosure); IP 20 (Terminals)

2

-25 C to +80 C

-15 C to +60 C

Auto/Manual

MLL027-00-002

RoHS(47-53) Hz (58-62) Hz

2 Relays with 1 NO

Page 9: Replacement kit for Hiquel TCP-M2, TCP-M2A and TCP-M2B. · Replacement kit for Hiquel TCP-M2, TCP-M2A and TCP-M2B. ... TCP-M2A & TCP-M2B installations. ... NOTE: Connections Y1 and

Functional Description: Function Diagrams:

Connection Diagram:Test Voltage between I/P and O/P

Test Voltage between all terminals andenclosure

Safety

Impulse Voltage between I/P and O/P

Single Fault

Insulation Resistance

Leakage Current

Environmental

Cold Heat

Dry Heat

Vibration

Repetitive Shock

Non-Repetitive Shock

IEC 60947-5-1 Ed. 3.0 (2003-11) Level IV

IEC 61010-1 Ed. 2.0 (2001-02)

UL 508 Ed. 17 (1999-01)

UL 508 Ed. 17 (1999-01) <3.5 mA

IEC 60068-2-1 Ed. 6.0 (2007-03)

IEC 60068-2-2 Ed. 5.0 (2007-07)

IEC 60068-2-6 Ed. 7.0 (2007-12), 5 g

IEC 60068-2-27 Ed. 4.0 (2008-02), 40 g, 6 ms

IEC 60068-2-27 Ed. 4.0 (2008-02), 30 g, 15 ms

IEC 60947-5 Ed.3.0 (2002-12) 2 kV

IEC 60255-5 Ed.3.0 (2003-12) 4 kV

Conformity to Standards:

Product

Harmonic Current Emission

ESD Immunity

Radiated Susceptibility

Electrical Fast Transients

Surge Immunity

Conducted Susceptibility

Voltage Dips and Interruptions(AC)

IEC 61000-4-2 Ed.1.2 (2001-04) Level II

IEC 61000-4-3 Ed.3.0 (2006-02) Level III

IEC 61000-4-4 Ed. 2.0 (2004-07) Level IV

IEC 61000-4-5 Ed. 2.0 (2005-11) Level IV

2.2IEC 61000-4-6 Ed. (2006-05) Level III

IEC 61000-4-11 Ed. 2.0 (2004-03) All 7 Levels

IEC 60255 Ed.1 (2005-12)

IEC 61000-3-2 Ed. 3.0 (2005-11) Class A

EMC

Conducted Emission

Radiated Emission

CISPR 14-1 Ed. 5.0 (2005-11) Class A

CISPR 14-1 Ed. 5.0 (2005-11) Class A

Overall product dimensions and mountingdetails: (in mm)

Thermistor Relay protects and controls motors

and alternators fitted with PTC thermistor sensors.

Motor heating is directly measured by temperature

sensors that are incorporated in starter windings.

This ensures a direct control in following operating

conditions: Heavy duty, high switching frequency,

single phasing, high ambient temperature and

insufficient cooling. Relay connection between 15

and 18 disconnects when probe resistance exceeds

3.6 k and cannot reset until resistance lower

than 1.6 k . Auxiliary supply voltage should

be applied to device between terminals L1-L3 to

produce connection.

Ω 5

Ω, 5

, %

%

±±

90

.0

68

.0

45

.0

60.0

DIN

RA

ILD

INR

AIL

Ø4.2Ø4.2

36.0

100.0

C/C

100.0

C/

C

Thermistor Functionality:

3 Phase Functionality:

Product is designed to detect phase sequence in

three phase power system. When phase sequence of

three phase is correct (L2 with 120 lag with respect

to L1 and phase L3 with 120 lag with respect to L2),

then relay connection between terminals 25 and 28

closes. Otherwise contacts are open.

º

º

AUTO RESET: For AUTO Reset operation, keep pot

position on AUTO. Device will reset automatically

when total loop resistance of series connected

thermistors drops below 1.6 5%.kΩ ±

MANUAL RESET: Manual reset can be reached by

keeping the pot on MANUAL. Device will reset

manually by changing pot position to AUTO. When

the total loop resistance of series connected

thermistors drops below 1.6 k 5%.Ω±

15-18

SENSOR OPEN:Probe cable open circuit is detected

by device if resistance is above 10 k 5 and

cannot reset until resistance is lower than 1.6 k

5 . The resistance at 25 C of the probe circuit

must be Within 40 < Resistance < 1.5 k ange

Ω, %

Ω,

%

Ω r .

0

±

±

SENSOR SHORT: Probe cable short circuit is

detected by device if resistance is lower than 20

and resets when probe resistance is

greater than 40 .

Ω,

Ω

Ω, Ω

±

±

4

4

OT

25-28

RT

L1

L2

L3

OT: Operate Time

RT: Release Time

L3

L2

ON OFF ON

Page 10: Replacement kit for Hiquel TCP-M2, TCP-M2A and TCP-M2B. · Replacement kit for Hiquel TCP-M2, TCP-M2A and TCP-M2B. ... TCP-M2A & TCP-M2B installations. ... NOTE: Connections Y1 and

0:00

TCP-M2A

HIGH QUALITY ELECTRONICS

2011HIQUEL B01.00

specification

ordering information

3 p

hase fa

ilure

and th

erm

isto

r moto

r pro

tectio

n

3

DIN

3

PTC

overview

detects phase failure, phase sequence

phase asymmetry and over-temperature

using PTC sensors

detects phase failure with

regenerated voltage present

up to 6 PTC sensors in series

fixed asymmetry alarm >10%

no neutral connection required

LED indicators for power supply,

relay and reaction timer

45mm DIN rail mount housing

4000

R (Ohm)

1330

550

250

20

-20 0

TNF: nominal triggering temperature

TN

F-2

0

TN

F-5

TN

F+

5

TN

F+

15

°C

Function

Gehäusetypenpart no supply output

TCP-M2A 3x415Vac 3x 415V~ 2,5VA DPCO+SPCO

housing types

no D

supply voltage variation

frequency range

duty cycle

response/delay time

reset time

max. measuring voltage

max. resistance

triggering threshold

reset threshold

output relay specification

Ue/Ie AC-15

Ue/Ie DC-13

expected life time

operating conditions

nominal voltage +20% / -10%

48 - 63 Hz

100%

< 300ms

< 500ms

< 2,5V

1500 Ohm (6 sensors)

3100 Ohm

1650 Ohm

115V/1,5A 230V/1,5A

24V/1,5A

-20 to 60°C non condesning

mechanical

electrical

DPCO SPCO

1 x 107

resp. 1 x 107

operations

8 x 104

resp. 1 x 105

operations

* EN 60947-5-1

sup. galv. iso*

yes

* The measurement is galvanically isolated from the power supplyinput

U

R1PhaseFailure+

ThermistorMotorProtection

3x415VacTCP-M2A

0,1

10sec

t r

0

30min

te

R2

Manual esetR

Manual esetR

Auto esetR

Auto esetR

PTCPhaseUnused

R1

21

22

24T2

T11...

...6

PTCDIN44081 11 1

2

14

R2R1

31

32

34

L1

L2

L3

L1

100%

100%

100%

0%

0%

0%

L2

L3

R2

>+/-10%

tr

>10%

Asym.

tr tr tr

>+/-10%

Control relay for phase failure and thermistor protectionThe TCP-M2A monitors phase sequence, phase failure and phaseasymmetry, and is used with PTC sensors to provide over temperatureprotection for motors and other equipment.

If a failure is occured, the relays are deenergised after theadjustable time tr (0,1s..10s).

R2 switch on, when all phases are detected, the phase sequence is correct,all phase voltages are in the range of Un +/-10% and the phase asymmetryimbalance < 10%.

R1 switch on, when the resistance of the PTC sensors on the input T1 - T2is within the correct range.

R1 switch on, if the resistance of thePTC is in the correct range and afterthe time delay of te (0..30min).

R2 switch immediately on, if allparameters are in the specifiedrange.

The control relay will detect a phasefailure even with a regeneratedvoltage present on the failed phase(no detection on request).

Sym

bolfoto

>+/-10%