16
Accessories for Great Indian Market 01 RelayAux Electromechanical relays for auxiliary, tripping and control / supervision applications CUSTOMER BENEFITS • Plug-in compact design allows easy installation and replacement. • Heavy duty contacts. • High speed operation • Universal change over contacts design facilitates easy selection and inventory reduction. • Sturdy design for maximum reliability. • Zero maintenance. The auxiliary relays range offers varying levels of functionality to best suit the auxiliary, tripping and control/supervision application requirements, and allows the customers to choose the most cost effective solution to their various applications. The design, durability and quality of the RelayAux make them suitable for high responsibility controls such as: Electrical utilities Power generation Electrical substations Transportation Industry - Oil & Gas - Food & beverage - Water - Mining, Minerals, metals ... PM103544

RelayAux - Bipinkumarbipinkumar.com/pdf/Schneider_EM_Relays.pdf · • DC supply supervision relay, 4 contacts • Trip circuit supervision relay or trip coil supervision relay (single

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Page 1: RelayAux - Bipinkumarbipinkumar.com/pdf/Schneider_EM_Relays.pdf · • DC supply supervision relay, 4 contacts • Trip circuit supervision relay or trip coil supervision relay (single

Accessories for Great Indian Market 01

RelayAuxElectromechanical relays for auxiliary, tripping and control / supervision applications

CUSTOMER BENEFITS

• Plug-in compact design allows easy installation and replacement.

• Heavy duty contacts.

• High speed operation

• Universal change over contacts design facilitates easy selection and inventory reduction.

• Sturdy design for maximum reliability.

• Zero maintenance.

The auxiliary relays range offers varying levels of functionality to best suit the auxiliary, tripping and control/supervision application requirements, and allows the customers to choose the most cost effective solution to their various applications.

The design, durability and quality of the RelayAux make them suitable for high responsibility controls such as:

• Electrical utilities

• Power generation

• Electrical substations

• Transportation

• Industry - Oil & Gas - Food & beverage - Water - Mining, Minerals, metals ...

PM103544

Page 2: RelayAux - Bipinkumarbipinkumar.com/pdf/Schneider_EM_Relays.pdf · • DC supply supervision relay, 4 contacts • Trip circuit supervision relay or trip coil supervision relay (single

RelayAuxAccessories for Great Indian Market 02

Range of productsAUXILIARY RELAYSThe main applications for this auxiliary relays range include

control & alarm functions, contact multiplication, interlocking,

customizing of protection schemes, indications or any other

auxiliary duties.

Models :

• Self reset relay, 4 or 8 contacts• Self reset relay with hand reset flag, 4 or 8 contacts• Electrical reset relay with following flag, , 4 or 8 contacts

TRIPPING RELAYSThe main applications for this high speed trip relays range include

lock out / master trip functions or high speed tripping applications

where auto-recloser is involved, which demands high speed operations.

These relays are used as interface between protection relay and

circuit breaker due to their high capacity contacts

Models :

• Self reset trip relay with hand reset flag, low burden, 4 or 8 contacts• Self reset trip relay with hand reset flag, high burden, 4 or 8 contacts• Electrical reset trip relay with following flag, low burden, 4 or 8 contacts• Electrical reset trip relay with following flag, high burden, 4 or 8 contacts• Hand and electrical reset trip relay with following flag, low burden, 4 or 8

contacts• Hand and electrical reset trip relay with following flag, high burden, 4 or 8

contacts

SUPERVISION RELAYSThe main applications for this supervision relays range include the

continuous supervision of the trip circuit in Pre-closed & Post-closed

conditions of a circuit breaker, the supervision of the master trip relay coil

or the supervision of the DC auxiliary supply circuits of the protection

schemes, avoiding false alarms due to short time drops of supply.

Models :

• DC supply supervision relay, 4 contacts• Trip circuit supervision relay or trip coil supervision relay (single phase

circuit breaker), 2 contacts• Trip circuit supervision relay (three phases circuit breaker), 2 contacts

PM103545

PM103546

PM103547

Page 3: RelayAux - Bipinkumarbipinkumar.com/pdf/Schneider_EM_Relays.pdf · • DC supply supervision relay, 4 contacts • Trip circuit supervision relay or trip coil supervision relay (single

RelayAuxAccessories for Great Indian Market 03

Auxiliary relays

Models Self reset relay Self reset relay with hand reset flag Self reset relay Self reset relay with

hand reset flagConstruction characteristicsContacts no. 4 Changeover 8 Changeover

Connections

Coil characteristicsStandard voltages 110, 220 Vdc

Voltage range +10% -20%

Coil burden 3.9 W / 6 W

Performance data

Operating time < 20 ms

Operating temperature - 10°C + 55°C

Storage temperature - 30°C + 70°C

Maximum humidity 93 % / + 40°C

Operating altitude < 2000 m

ContactsPermanent current 10 A

Instantaneous current 110 A during 100 ms / 160 A during 30 ms

Max. making capacity 40 A / 0,5 s / 110 Vdc

Mechanical endurance: Unloaded contacts > 10 operations

Mechanical endurance: Loaded contacts Minimum of 50 000 operations are guaranteed

Max. breaking capacity – Contact circuit voltage : 220 Vdc

0 ms 20 ms 40 ms

P (W) I (A) P (W) I (A) P (W) I (A)

150 0.68 115 0.52 66 0.30

Braeking capacity

L/R= 0 ms L/R= 40 msResistive load (220 Vdc) Highly inductive load (220 Vdc)

0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80

10 7

10 6

10 5

10 4

Current

0.00 0.05 020 0.15 0.20 0.25 0.30 0.35

10 7

10 6

10 5

10 4

Current

50 000operations

50 000operations

No.

ope

ratio

ns

No.

ope

ratio

ns

Page 4: RelayAux - Bipinkumarbipinkumar.com/pdf/Schneider_EM_Relays.pdf · • DC supply supervision relay, 4 contacts • Trip circuit supervision relay or trip coil supervision relay (single

RelayAuxAccessories for Great Indian Market 04

Auxiliary relays (cont.)

Models Electrical reset relay with following flagConstruction characteristicsContacts no. 4 Changeover 8 Changeover

Connections

Coil characteristicsStandard voltages 110, 220 Vdc

Voltage range +10% -20%

Coil burden 0 W (peak ≤ 15 W) / 0 W (peak ≤ 32 W)

Performance data

Operating time < 20 ms

Operating temperature - 40°C + 70°C

Storage temperature - 40°C + 70°C

Maximum humidity 93 % / + 40°C

Operating altitude < 2000 m

ContactsPermanent current 10 A

Instantaneous current 110 A during 100 ms / 160 A during 30 ms

Max. making capacity 40 A / 0,5 s / 110 Vdc

Mechanical endurance: Unloaded contacts > 10 operations

Mechanical endurance: Loaded contacts Minimum of 50 000 operations are guaranteed

Max. breaking capacity – Contact circuit voltage : 220 Vdc

0 ms 20 ms 40 ms

P (W) I (A) P (W) I (A) P (W) I (A)

150 0.68 115 0.52 66 0.30

Braeking capacity

L/R= 0 ms L/R= 40 msResistive load (220 Vdc) Highly inductive load (220 Vdc)

0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80

10 7

10 6

10 5

10 4

Current

0.00 0.05 020 0.15 0.20 0.25 0.30 0.35

10 7

10 6

10 5

10 4

Current

50 000operations

50 000operations

No.

ope

ratio

ns

No.

ope

ratio

ns

Page 5: RelayAux - Bipinkumarbipinkumar.com/pdf/Schneider_EM_Relays.pdf · • DC supply supervision relay, 4 contacts • Trip circuit supervision relay or trip coil supervision relay (single

RelayAuxAccessories for Great Indian Market 05

Tripping relaysModels Self reset trip relay with hand reset flagConstruction characteristicsContacts no. 4 Changeover 8 Changeover

Connections

Coil characteristicsStandard voltages 110, 220 Vdc

Voltage range +10% -20%

Coil burden≤ 2,5 W (peak ≤ 66 W, 2 ms)

≤ 5 W (peak ≤ 110 W, 2,5 ms)

Performance data

Operating time < 10 ms

Operating temperature - 10°C + 55°C

Storage temperature - 30°C + 70°C

Maximum humidity 93 % / + 40°C

Operating altitude < 2000 m

ContactsPermanent current 10 A

Instantaneous current 110 A during 100 ms / 160 A during 30 ms

Max. making capacity 40 A / 0,5 s / 110 Vdc

Mechanical endurance: Unloaded contacts > 10 operations

Mechanical endurance: Loaded contacts Minimum of 50 000 operations are guaranteed

Max. breaking capacity – Contact circuit voltage : 220 Vdc

0 ms 20 ms 40 ms

P (W) I (A) P (W) I (A) P (W) I (A)

125 0.57 104 0.47 60 0.27

Braeking capacity

L/R= 0 ms L/R= 40 msResistive load (220 Vdc) Highly inductive load (220 Vdc)

0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80

10 7

10 6

10 5

10 4

Current

0.00 0.05 0.10 0.15 0.20 0.25 0.30 0.35

10 7

10 6

10 5

10 4

Current

50 000operations

50 000operations

No.

ope

ratio

ns

No.

ope

ratio

ns

Page 6: RelayAux - Bipinkumarbipinkumar.com/pdf/Schneider_EM_Relays.pdf · • DC supply supervision relay, 4 contacts • Trip circuit supervision relay or trip coil supervision relay (single

RelayAuxAccessories for Great Indian Market 06

Tripping relays (cont.)

ModelsElectrical reset trip

relay with following flag

Hand and electrical reset trip relay with

following flag

Electrical reset trip relay with

following flag

Hand and electrical reset trip relay with

following flagConstruction characteristicsContacts no. 4 Changeover 8 Changeover

Connections

Coil characteristicsStandard voltages 110, 220 Vdc

Voltage range +10% -20%

Coil burden 0 W (peak ≤ 20 W) / 0 W (peak ≤ 40 W)

Performance data

Operating time < 10 ms

Operating temperature - 40°C + 70°C

Storage temperature - 40°C + 70°C

Maximum humidity 93 % / + 40°C

Operating altitude < 2000 m

ContactsPermanent current 10 A

Instantaneous current 110 A during 100 ms / 160 A during 30 ms

Max. making capacity 40 A / 0,5 s / 110 Vdc

Mechanical endurance: Unloaded contacts > 10 operations

Mechanical endurance: Loaded contacts Minimum of 50 000 operations are guaranteed

Max. breaking capacity – Contact circuit voltage : 220 Vdc

0 ms 20 ms 40 ms

P (W) I (A) P (W) I (A) P (W) I (A)

150 0.68 115 0.52 66 0.30

Braeking capacity

L/R= 0 ms L/R= 40 msResistive load (220 Vdc) Highly inductive load (220 Vdc)

0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80

10 7

10 6

10 5

10 4

Current

0.00 0.05 0.10 0.15 0.20 0.25 0.30 0.35

10 7

10 6

10 5

10 4

Current

50 000operations

50 000operations

No.

ope

ratio

ns

No.

ope

ratio

ns

Page 7: RelayAux - Bipinkumarbipinkumar.com/pdf/Schneider_EM_Relays.pdf · • DC supply supervision relay, 4 contacts • Trip circuit supervision relay or trip coil supervision relay (single

RelayAuxAccessories for Great Indian Market 07

Tripping relays (cont.)

HIGH / LOW BURDEN CONFIGURATIONLow burden high speed tripping relays can be used when the initiating contact is placed close to the tripping relay.

However, in order to avoid unwanted trip relay operation due to pickup or transients, particularly if the relay operating coil is connected to extensive wiring, high burden high speed tripping relays can be used.High burden high speed tripping relays complies with ESI 48-4 international standard, as EB2 class relays.These EB2 class relays are suitable for use in high security circuit breaker tripping circuits, increasing their immunity to capacitance discharge currents.

For relays with rated voltage of 110 V, the relays will withstand, without operating a discharge into their operate circuits of a 10μF capacitor charged to 120% of the higher rated voltage for the relay, i.e 145.2 V.

For relays with rated voltage of 220 V, the relays will withstand, without operating a discharge into their operate circuits of a 10μF capacitor charged to 100% of the higher rated voltage for the relay, i.e 242 V.

Page 8: RelayAux - Bipinkumarbipinkumar.com/pdf/Schneider_EM_Relays.pdf · • DC supply supervision relay, 4 contacts • Trip circuit supervision relay or trip coil supervision relay (single

RelayAuxAccessories for Great Indian Market 08

Supervision relaysModels DC supply supervision relayConstruction characteristicsContacts no. 4 Changeover

Connections

Coil characteristicsStandard voltages 110, 220 Vdc

Voltage range +10% -20%

Coil burden 3,9 W

Performance data

Operating time: Pick-up time < 20 ms

Operating time: Drop-out time > 200 ms

Operating temperature - 10°C + 55°C

Storage temperature - 30°C + 70°C

Maximum humidity 93 % / + 40°C

Operating altitude < 2000 m

ContactsPermanent current 10 A

Instantaneous current 15 A during 4 s

Max. making capacity 15 A during 4 s

Max. breaking capacity 0,3 A / 110 Vdc

Durability Relay designed to be permanently energized

Page 9: RelayAux - Bipinkumarbipinkumar.com/pdf/Schneider_EM_Relays.pdf · • DC supply supervision relay, 4 contacts • Trip circuit supervision relay or trip coil supervision relay (single

RelayAuxAccessories for Great Indian Market 09

Supervision relays (cont.)

TRIP SUPPLY +

M +B

TRIP CONTACT

1

11

K1 K2 K1 K2

B1

12 8 2

2

2

2 9 813 129 13

4 55 1 4

TRIP CONTACT

SET RESET

TRIP SUPPLY -

TRIP SUPPLY +

TRIP SUPPLY -

Trip circuit supervision relay can also be used to supervise the trip circuit of the high speed tripping relays. If the circuit being supervised becomes an open circuit, the supervision relay will be de-energized and its output contacts will provide the related indications. In order to achieve this function, the relays should be connected as shown on the schemes :

Models Trip circuit supervision relay (single phase circuit breaker)

Trip circuit supervision relay (three phases circuit breaker)

Construction characteristicsContacts no. 2 Changeover

Connections

Coil characteristicsStandard voltages 110, 220 Vdc

Voltage range +10% -20%

Coil burden 3,1 W 3,6 W

Performance data

Operating time: Pick-up time < 20 ms

Operating time: Drop-out time > 200 ms

Operating temperature - 10°C + 55°C

Storage temperature - 30°C + 70°C

Maximum humidity 93 % / + 40°C

Operating altitude < 2000 m

ContactsPermanent current 8 A

Instantaneous current 15 A during 4 s

Max. making capacity 15 A during 4 s

Max. breaking capacity 0,3 A / 110 Vdc

Durability Relay designed to be permanently energized

Page 10: RelayAux - Bipinkumarbipinkumar.com/pdf/Schneider_EM_Relays.pdf · • DC supply supervision relay, 4 contacts • Trip circuit supervision relay or trip coil supervision relay (single

RelayAuxAccessories for Great Indian Market 10

Environmental characteristics• Functional test : IEC 61810-7

• Electrical security standards : IEC 60255

• Environmental / Climatic standards : IEC 60068-2

• Vibration and shock stress standards : IEC 60068-2

• ESI 48-4 EB1 : 1983 Low Burden

• ESI 48-4 EB2 : 1983 High Burden

Page 11: RelayAux - Bipinkumarbipinkumar.com/pdf/Schneider_EM_Relays.pdf · • DC supply supervision relay, 4 contacts • Trip circuit supervision relay or trip coil supervision relay (single

RelayAuxAccessories for Great Indian Market 11

Order Codes and Dimensions Auxiliary relays

ORDER CODESSchneider Electric

RelayAux Reference

RelayAuxType Contacts no. Aux. Supply Relay + Flush mounting socket

Self rest relay 4 changeover110 Vdc RELRAAS4110

220 Vdc RELRAAS4220

Self reset relay with hand reset flag 4 changeover110 Vdc RELRAAS4F110

220 Vdc RELRAAS4F220

Dimensions (mm) Panel Cut-Out (mm)

DIMENSIONS AND CUT-OUT

ORDER CODESSchneider Electric

RelayAux Reference

RelayAuxType Contacts no. Aux. Supply Relay + Flush mounting socket

Self rest relay 8 changeover110 Vdc RELRAAS8110

220 Vdc RELRAAS8220

Self reset relay with hand reset flag 8 changeover110 Vdc RELRAAS8F110

220 Vdc RELRAAS8F220

Dimensions (mm) Panel Cut-Out (mm)

DIMENSIONS AND CUT-OUT

Page 12: RelayAux - Bipinkumarbipinkumar.com/pdf/Schneider_EM_Relays.pdf · • DC supply supervision relay, 4 contacts • Trip circuit supervision relay or trip coil supervision relay (single

RelayAuxAccessories for Great Indian Market 12

Order Codes and Dimensions (cont.)

Auxiliary relays

Schneider Electric RelayAux Reference

RelayAuxType Contacts no. Aux. Supply Relay + Flush mounting socket

Electrical reset relay with following flag 4 changeover

110 Vdc RELBAAE4110

220 Vdc RELBAAE4220

ORDER CODES

Dimensions (mm) Panel Cut-Out (mm)

DIMENSIONS AND CUT-OUT

Dimensions (mm) Panel Cut-Out (mm)

DIMENSIONS AND CUT-OUT

ORDER CODES Schneider Electric RelayAux Reference

RelayAuxType Contacts no. Aux. Supply Relay + Flush mounting socket

Electrical reset relay with following flag 8 changeover

110 Vdc RELBAAE8110

220 Vdc RELBAAE8220

Page 13: RelayAux - Bipinkumarbipinkumar.com/pdf/Schneider_EM_Relays.pdf · • DC supply supervision relay, 4 contacts • Trip circuit supervision relay or trip coil supervision relay (single

RelayAuxAccessories for Great Indian Market 13

Order Codes and Dimensions (cont.)

Tripping relays

Schneider Electric RelayAux Reference

RelayAuxType Contacts no. Aux. Supply Relay + Flush mounting socket

Self reset trip relay with hand reset flag - Low burden 4 changeover

110 Vdc RELRAXSL4110

220 Vdc RELRAXSL4220

Self reset trip relay with hand reset flag - High burden 4 changeover

110 Vdc RELRAXSH4110

220 Vdc RELRAXSH4220

Schneider Electric RelayAux Reference

RelayAuxType Contacts no. Aux. Supply Relay + Flush mounting socket

Self reset trip relay with hand reset flag - Low burden 8 changeover

110 Vdc RELRAXSL8110

220 Vdc RELRAXSL8220

Self reset trip relay with hand reset flag - High burden 8 changeover

110 Vdc RELRAXSH8110

220 Vdc RELRAXSH8220

ORDER CODES

ORDER CODES

Dimensions (mm) Panel Cut-Out (mm)

DIMENSIONS AND CUT-OUT

Dimensions (mm) Panel Cut-Out (mm)

DIMENSIONS AND CUT-OUT

Page 14: RelayAux - Bipinkumarbipinkumar.com/pdf/Schneider_EM_Relays.pdf · • DC supply supervision relay, 4 contacts • Trip circuit supervision relay or trip coil supervision relay (single

RelayAuxAccessories for Great Indian Market 14

Order Codes and Dimensions (cont.)

Tripping relays

Schneider Electric RelayAux Reference

RelayAuxType Contacts no. Aux. Supply Relay + Flush mounting socket

Electrical reset trip relay with following flag – Low burden 4 changeover

110 Vdc RELBAXEL4110

220 Vdc RELBAXEL4220

Electrical reset trip relay with following flag – High burden 4 changeover

110 Vdc RELBAXEH4110

220 Vdc RELBAXEH4220

Hand & electrical reset trip relay with following flag – Low burden 4 changeover

110 Vdc RELBAXBL4110

220 Vdc RELBAXBL4220

Hand & electrical reset trip relay with following flag – High burden 4 changeover

110 Vdc RELBAXBH4110

220 Vdc RELBAXBH4220

ORDER CODES

Dimensions (mm) Panel Cut-Out (mm)

DIMENSIONS AND CUT-OUT

Page 15: RelayAux - Bipinkumarbipinkumar.com/pdf/Schneider_EM_Relays.pdf · • DC supply supervision relay, 4 contacts • Trip circuit supervision relay or trip coil supervision relay (single

RelayAuxAccessories for Great Indian Market 15

Order Codes and Dimensions (cont.)

Tripping relays

ORDER CODES

Dimensions (mm) Panel Cut-Out (mm)

DIMENSIONS AND CUT-OUT

Schneider Electric RelayAux Reference

RelayAuxType Contacts no. Aux. Supply Relay + Flush mounting socket

Electrical reset trip relay with following flag – Low burden 8 changeover

110 Vdc RELBAXEL8110

220 Vdc RELBAXEL8220

Electrical reset trip relay with following flag – High burden 8 changeover

110 Vdc RELBAXEH8110

220 Vdc RELBAXEH8220

Hand & electrical reset trip relay with following flag – Low burden 8 changeover

110 Vdc RELBAXBL8110

220 Vdc RELBAXBL8220

Hand & electrical reset trip relay with following flag – High burden 8 changeover

110 Vdc RELBAXBH8110

220 Vdc RELBAXBH8220

Page 16: RelayAux - Bipinkumarbipinkumar.com/pdf/Schneider_EM_Relays.pdf · • DC supply supervision relay, 4 contacts • Trip circuit supervision relay or trip coil supervision relay (single

RelayAuxAccessories for Great Indian Market 16

02-2014

© 2

014

Sch

neid

er E

lect

ric In

dust

ries

SA

S -

All

right

s re

serv

ed

As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication.

Design: Schneider Electric Industries SAS - SonovisionPhotos: Schneider Electric Industries SAS Printed: Altavia Connexion - Made in France

NRJED314593EN

This document has been printed on recycled paper.

Schneider Electric Industries SAS

35, rue Joseph Monier CS 30323 F - 92506 Rueil Malmaison Cedex (France)Tel.: +33 (0) 1 41 29 70 00RCS Nanterre 954 503 439 Capital social 896 313 776 €www.schneider-electric.com

ORDER CODES Schneider Electric RelayAux Reference

RelayAuxType Contacts no. Aux. Supply Relay + Flush mounting socket

Trip circuit supervision relay (Three phases circuit breaker) 2 changeover

110 Vdc RELVD9X110

220 Vdc RELVD9X220

Order Codes and Dimensions (cont.)

Supervision relaysSchneider Electric

RelayAux Reference

RelayAuxType Contacts no. Aux. Supply Relay + Flush mounting socket

DC supply supervision relay 4 changeover110 Vdc RELVD1X110

220 Vdc RELVD1X220

Trip circuit supervision relay (Single phase circuit breaker) 2 changeover

110 Vdc RELVD3X110

220 Vdc RELVD3X220

ORDER CODES

Dimensions (mm) Panel Cut-Out (mm)

DIMENSIONS AND CUT-OUT

DIMENSIONS AND CUT-OUT

Dimensions (mm) Panel Cut-Out (mm)