  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Brief Introduction for Automated Relay Testing

    Kamin DaveManager Marketing & Protection Applications

    DOBLE ENGINEERING COMPANY, INDIA

    [email protected]

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Protection Relay Testing:

    Testing of Generator Protection Relay type SEL300G

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Relay Details: SEL300G

    Under & Over Voltage Protection (27/59)Negative sequence Protection (46)Reverse & Low Forward Power Protection (32)Over Excitation Protection (24)Over & Under Freq. Protection (81O/81U)Under Impedance Protection (21) Loss of Excitation Protection (40G) 100% Stator E/F Protection (27TN/64G2)

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Relay Details: SEL300G

    Out of Step Protection (78)Voltage Restrained O/C Protection (51VR)Voltage Controlled O/C Protection (51VC)Rotor E/F Protection (64R)Breaker Failure ProtectionGenerator Differential Protection (87D)Ground differential Protection (87N) 95% Stator E/F Protection (59GN/64G1)

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Relay Details: SEL300G

    Primary & Backup Protection

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Relay Details: SEL300G

    Rotor Earth Fault Protection

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Relay Details: SEL300G

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Relay Details: SEL300G

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Relay Details: SEL300G

    Characteristic plotted in F6TEST2.21 software for testing

    Load Encroachment characteristic plotted

    Zone2 Reach

    Zone1 Reach

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Relay Details: SEL300G

    Select D from List

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Relay Details: SEL300G

    GCB Status Close Input

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Relay Details: SEL300G

    Breaker close input & VT fuse fail input

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Relay Details: SEL300G

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Relay Details: SEL300G

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Relay Details: SEL300G

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Relay Details: SEL300G

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Relay Details: SEL300G

    VT fuse fail Status Input

    Characteristic selection

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Relay Details: SEL300G

    V/Hz Curve1

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Relay Details: SEL300G

    V/Hz Curve2

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Relay Details: SEL300G

    V/Hz Curve3

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Relay Details: SEL300G

    Selection of Curve

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Relay Details: SEL300G

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Relay Details: SEL300G

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Relay Details: SEL300G

    Set as a Low Forward Power threshold range

    Set as a Reverse Power threshold range

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Relay Details: SEL300G

    Set as Reverse Power function

    VT Fuse fail Input

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Relay Details: SEL300GRelay Logic for Reverse Power Function

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Relay Details: SEL300G

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Relay Details: SEL300G

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Relay Details: SEL300G

    VT fuse fail Status Input

    Offset reactance for Zone1

    Zone1

    Zone2

    Offset reactance for Zone2

    Directional Angle for Zone2

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Relay Details: SEL300G

    Directional Angle for Zone2

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Relay Details: SEL300G

    Relay Logic for Loss of Excitation Function

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Relay Details: SEL300G

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Relay Details: SEL300G

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Relay Details: SEL300G

    Enter Setting of NPS Threshold

    Enter Time Dial Setting

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Relay Details: SEL300GRelay Logic for Negative Sequence current Function

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Relay Details: SEL300G

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Relay Details: SEL300G

    Select function V

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Relay Details: SEL300G

    Threshold value

    Curve selection C1

    VT fuse fail status input

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Relay Details: SEL300G

    K = 0.25Normal Inverse Curve

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Relay Details: SEL300G

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Relay Details: SEL300G

    Select function C

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Relay Details: SEL300G

    Threshold value

    Curve selection C1

    VT fuse fail status input

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Relay Details: SEL300G

    K = 0.2Normal Inverse Curve

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Relay Details: SEL300G

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Relay Details: SEL300G

    0-95% SEF

    100% SEF

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Relay Details: SEL300G

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Relay Details: SEL300G

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Relay Details: SEL300G

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Relay Details: SEL300G

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Relay Details: SEL300G

    Under Freq. function

    Under Freq. function

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Test Equipment

    Make : DOBLE

    Model : F6150

    Software

    F6TesT Version 2.21-1165

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    F6150 Connections:

    CT ConnectionsPT Connections

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    SEL300 Connections:PT ConnectionsCT Connections

    Connections of 4th Voltage for 100% SEF

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Testing of Over Excitation Function (24)

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    VA

    VB

    VC

    I1

    I2

    I3

    SEL

    Test Circuit: Over Excitation Function Test

    Source Configurations:3V X 3I

    CT Inputs

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Inverse Time Curve Test

    Tests conducted:

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Use VFChar Module for Characteristic Search Test

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Curve3 selection

    Enter Time Dial

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Curve3 for Testing

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Expected Curve

    Actual Curve from relay

    Phasor

    Select ABC Fault for testing

    Relay settings:V/Hz = 1PUCurve = 3Time Dial = 1

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Testing of Reverse Power Function (32)

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Reverse Power Protection (32R): Example1

    G D Y

    GTGCB

    Gen Set

    G D Y

    GTGCB

    Gen Set

    CB1

    CB2

    CB3

    CB4

    CB

    5

    TL Line

    TL Line

    MW

    MW

    Healthy Prime-mover

    Failed Prime-mover

    MVAR

    MVAR

    E

    E

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Reverse Power Protection (32R): Example2

    G D Y

    GTGCB

    Gen Set

    G D Y

    GTGCB

    Gen Set

    CB1

    CB2

    CB3

    CB4

    CB

    5

    TL Line

    TL Line

    MW

    MW

    Healthy Prime-mover

    Failed Prime-mover

    MVAR

    MVAR

    E

    E

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Reverse Power Protection (32R): Example3

    G D Y

    GTGCB

    Gen Set

    CB1 CB3

    CB

    5

    TL LineMW

    Failed Prime-mover

    MVAR

    E

    Active Power Import from Grid sources

    Grid

    GridMW

    MW

    MW

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Reverse Power Protection (32R): Example4

    GD YTR1

    GCB

    Gen Set

    Failed Prime-mover

    MVAR

    E

    Only Reactive Power Export to Loads

    CB1 CB2

    D YTR2

    CB3 CB4

    MC

    B

    5

    CB6

    L

    o

    a

    d

    s

    L

    o

    a

    d

    s

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    VA

    VB

    VC

    I1

    I2

    I3

    SEL

    Test Circuit: Reverse Power Function Test

    Source Configurations:3V X 3I

    CT Inputs

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Pickup Test

    Time Test

    Tests conducted:

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Use RAMP Module for Pickup Test

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Pickup Test @ Unity PF:

    MW- MW

    - MVAR

    MVAR

    Watts = VA = 952.87W

    - MVAR

    MVAR

    MW- MW

    IExpected = 1A

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Pickup Test @ Unity PF:Vn = 110V In = 5APF = 1 (Unity)PN = (1.7325*0.11*1000*5) = 952.87watts%PSet = 20% of PNPSet = (952.87 * 20)/(PF*100) = 190.5watts IExpected = (190.5)/(1.7325*0.11*1000*PF) = 1A

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Enter Expected Value = 1A Enter Actiondetails

    Pickup

    Actual Operating Values

    IA@180o

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Pickup Test @ 0.8 lag PF:

    MW- MW

    - MVAR

    MVAR

    Watts = 762.3W - MVAR

    MVAR

    MW- MW

    IExpected = 1.15A

    VA = 952.87VA

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Enter Expected Value = 1.15A Enter Actiondetails

    Pickup

    Actual Operating Values

    IA@150o

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Pickup Test @ 0.8 lead PF:

    MW- MW

    - MVAR

    MVAR

    Watts = 762.3W

    - MVAR

    MVAR

    MW- MW

    IExpected = 1.15AVA = 952.87VA

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Enter Expected Value = 1.15A Enter Actiondetails

    Pickup

    Actual Operating Values

    IA@210o

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Use SSIMUL Module for Time Test

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    TExp = 200msTAct = 262ms

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Testing of Loss of Excitation Function (40G)

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    VA

    VB

    VC

    IA

    IB

    IC

    SEL

    Test Circuit: Field Failure Function Test

    Source Configurations:3V & 3I

    3V

    3I

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Characteristic Search Test

    Characteristic Time Test

    RCA (MTA) Test

    Tests conducted:

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Use ZChar Module for Characteristic Search Test

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Zone1 setting = 20.4Ohms

    Zone2 setting = 30.5Ohms

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Show Phasors: fault voltage & current of ABC fault

    Blue color shows expected characteristic and pink color shows actual tested characteristic

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Click on Oscillograph: Shows, voltage & current waveform of ABC fault

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Zone1 setting = 20.4Ohms

    Zone2 setting = 30.5OhmsOffset = -3.5 Ohms

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Show Phasors: fault voltage & current of ABC fault

    Blue color shows expected characteristic and pink color shows actual tested characteristic

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Use ZTime Module for Characteristic Time Test

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Show Phasors: fault voltage & current of ABC fault

    Results Table shows; Zone1 time is 0.1s & Zone2 time is 0.4s

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    SEL300G: Field Failure Function Testing

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    SEL300G: Field Failure Function Testing

    LED Indicator operated

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Use ZMTA Module for Characteristic MTA (RCA) Test

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Fault type ABC selected for testing

    Angle Boundary (Theta1)

    Angle Boundary (Theta2)

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    SEL300G: Field Failure Function Testing

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Testing of Negative Sequence Function (46)

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Negative Sequence Protection (46)

    IaIc

    IbIa

    Ic

    Ib

    IaIc

    Ib

    +VE Seq. -VE Seq. Zero Seq.

    Sequence Components

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    G D Y

    GTGCB

    Gen Set

    MWMVAR

    E

    3

    46Operate: I2Measure>I2Set

    Sys

    MVARMW

    F1

    Negative Sequence Protection (46)

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    G D Y

    GTGCB

    Gen Set3

    46Operate: I2Measure>I2Set

    F1

    Negative Sequence Protection (46)

    3

    3

    IR @ 0o

    IY @ 120O

    IB @ 240O

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    I1@0o

    I2@120o

    I3@240o

    SEL

    Test Circuit: Negative Phase Seq. Function Testing

    Source Configurations:3I

    3I

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Inverse Time Curve Test

    Tests conducted:

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Use IChar Module for Characteristic Search Test

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Curve selection

    Enter Time Dial

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Inverse Curve for Testing

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Blue color line shows Expected curve & Pink color line shows Actual tested curve

    Phasors shows symmetrical componentsvalue (i.e. I1, I0 & I2)

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Testing of Voltage Controlled Over Current Function (51VC)

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Voltage Controlled over current function (51VC):

    Normally Protection applied for Directly connected Generators where system voltage collapse drastically falls below set value (VSet) during faults.

    Voltage Dependent Over Current Protection (51V)

    G GCB

    D Y

    3

    51VC Y Y

    CB1

    3

    51

    D YCB2 3

    51

    CB23

    MotproMVT

    F1F2

    6.37 MVA11KVPF = 0.8, Xd=36.4%, Xd=26%Xd = 231%

    1.5MVA, 11KV/0.415KV, %Z = 4.9%

    1.5MVA, 11KV/0.415KV, %Z = 4.9%

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    V/Vs

    I*/ [I>]

    0.2 0.8

    0.2

    1.0

    51V-Voltage Controlled

    Vmeasured < VsetIpickup = (k*Iset)T = (0.14*T) / ((Ipickup)0.02-1)

    Vmeasured > VsetIpickup = (Iset)T = (0.14*T) / ((Ipickup)0.02-1)

    Voltage Dependent Over Current Protection (51V)

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    VA

    VB

    VC

    IA

    IB

    IC

    SEL

    Test Circuit: Voltage Controlled O/C Function Testing

    Source Configurations:3V & 3I

    3V

    3I

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Inverse Time Curve Test

    Tests conducted:

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Use IChar Module for Characteristic Search Test

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Curve selection

    Enter Time Dial

    Relay Settings:I> = 0.5*InCurve = C1Time Dial = 1V1 = 50VL-NV2 = 25VL-N

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Characteristic created for testing

    Relay Settings:I> = 0.5*InCurve = C1Time Dial = 1V1 = 50VL-NV2 = 25VL-N

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Injected Voltage to relay

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Display Phasors

    Blue color shows expected characteristic and pink color shows actual tested characteristic

    Right click on check box to enable voltage O/P

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Testing of Voltage Restrained Over Current Function (51VR)

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Voltage Restrained over current function (51VR):

    Normally Protection is applicable when Generator is connected to system through GT.

    Voltage Dependent Over Current Protection (51V)

    G GCB3

    51VC Y YVT

    D Y

    D YCB1 3

    51

    D YCB2 3

    51

    CB2

    3

    MotproM

    F1F2

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    VA

    VB

    VC

    IA

    IB

    IC

    SEL

    Test Circuit: Voltage Restrained O/C Function Testing

    Source Configurations:3V & 3I

    3V

    3I

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    V/Vs

    I*/ [I>]

    0.2 0.8

    0.2

    1.0

    51V-Voltage restrained Vmeasured > Vset2Ipickup = (Iset)

    Vmeasured < Vset1Ipickup = (k*Iset)

    Vset1 < Vmeasured < Vset2Slop

    e region

    Voltage Dependent Over Current Protection (51V)

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Inverse Time Curve Test

    Tests conducted:

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Use IChar Module for Characteristic Search Test

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Curve selection

    Enter Time Dial

    Relay Settings:I> = 1*InCurve = C1Time Dial = 1V1 = 50VL-NV2 = 25VL-N

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Characteristic created for testing

    Relay Settings:I> = 1*InCurve = C1Time Dial = 1V1 = 50VL-NV2 = 25VL-N

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Injected Voltage to relay

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Display Phasors

    Blue color shows expected characteristic and pink color shows actual tested characteristic

    Right click on check box to enable voltage O/P

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Testing of 0-95% Stator Earth Fault Function (64R1/59GN)

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Stator Ground Fault Protection (59GN): Resistor Ground

    Maximum Ground Fault Amps = (Line to Neutral Voltage)-------------------------------------

    (NGR Resistance)

    VLN = 21000/1.7325

    100 Ohms, 10s

    IFIF PTR = 21000/240VCTR = 20/1A

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Stator Ground Fault Protection (59GN): Impedance Ground (NGT)

    VLN = 21000/1.7325KVPri = 21kVKVSec = 0.240kVKVA = 70KVA R = 0.913 Ohms Full Load current in Primary wdg = 3.33A Ground Fault Impedance = 3640.004 Ohms

    IF

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    VA

    VB

    VC

    VN

    SEL

    Test Circuit: 0-95% SEF Function Testing

    Source Configurations:4V

    3V

    4th V@50Hz

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Pickup Test

    Time Test

    Tests conducted:

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Use RAMP Module for Pickup Test

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    4th Voltage used

    Expected value = 5VActual value = 5.3V

    Pickup Value = 5V

    Action details for Voltage Ramp

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Use SSIMUL Module for Time Test

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Ground Fault condition

    Display Phasor

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Ground Fault condition

    Display Waveforms (Analogue & Digital Channels)

    4th Voltage

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Actual trip time = 1s

    Relay Output (Open to Close contact)

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Testing of 100% Stator Earth Fault Function (64R2/27TN)

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Stator Ground Fault Protection (27TN)

    3rd HarmonicCurrent circulate

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Stator Ground Fault Protection (27TN): 3RDHarmonic Under Voltage Method

    3rd Harmonic Under voltage relay

    3rd Harmonic Voltage at Neutral End reduced

    3rd Harmonic Voltage at Neutral End reduced

    IF

    3rd harmonic voltage dropBecause capacitanceIs shorted

    IF

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    VA

    VB

    VC

    VN

    SEL

    Test Circuit: 100% SEF Function Test

    Source Configurations:4V

    3V

    4th V@150Hz

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Pickup Test

    Time Test

    Tests conducted:

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Use RAMP Module for Pickup Test

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    4th Voltage used @ 150Hz Freq.

    Expected value = 1VActual value = 1.2V

    Pickup Value = 1.2V

    Action details for Voltage Ramp

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Use SSIMUL Module for Time Test

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Ground Fault condition close to Neutral

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Actual trip time = 0.55s

    Relay Output (Open to Close contact)

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    SEL300G: 100%SEF Function Testing

    LED Indicator operated

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Testing of Under Frequency Function (81UF)

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    VA

    VB

    VC

    IA

    IB

    IC

    SEL

    Test Circuit: Under Freq. Function Test

    Source Configurations:3V & 3I

    3V

    3I

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Pickup Test

    Time Test

    Tests conducted:

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Use RAMP Module for Pickup Test

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Freq. of Voltage sources

    Expected value = 48.5HzActual value = 48.498Hz

    Pickup Value = 48.5Hz

    Action details for Freq. Ramp

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Use SSIMUL Module for Time Test

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Under Frequency condition (48Hz Freq. for Voltage sources)

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Actual trip time = 0.33s

    Relay Output (Open to Close contact)

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Testing of Over Frequency Function (81O/F)

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    VA

    VB

    VC

    IA

    IB

    IC

    SEL

    Test Circuit: Over Freq. Function Test

    Source Configurations:3V & 3I

    3V

    3I

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Pickup Test

    Time Test

    Tests conducted:

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Use RAMP Module for Pickup Test

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Freq. of Voltage sources

    Expected value = 51HzActual value = 51.0002Hz

    Pickup Value = 51.0002Hz

    Action details for Freq. Ramp

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Use SSIMUL Module for Time Test

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Over Frequency condition (51Hz Freq. of Voltage sources)

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Actual trip time = 93.9ms

    Relay Output (Open to Close contact)

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    SEL300G: 100%SEF Function Testing

    LED Indicator operated

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Training to L&T Power at Doble Training Center

  • Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    DOBLE ENGINEERING COMPANY2nd Floor Suvidhi Pride, Gorwa-Refinery RoadOpposite Shell Petrol PumpVADODARAINDIA. Cell:- +91 98980 55956EMAIL ID:- [email protected]:- www.doble.com