15
ReLab Software, LLC -- Confidential Information

ReLab Software, LLC -- Confidential Informationftp.youngtec.com.tw/Temp/IEC61850/IEC-61850 Advantages 3_3_10.pdf · ReLab Software, LLC -- Confidential Information ReLab IEC 61850

Embed Size (px)

Citation preview

Page 1: ReLab Software, LLC -- Confidential Informationftp.youngtec.com.tw/Temp/IEC61850/IEC-61850 Advantages 3_3_10.pdf · ReLab Software, LLC -- Confidential Information ReLab IEC 61850

ReLab Software, LLC -- Confidential Information

Page 2: ReLab Software, LLC -- Confidential Informationftp.youngtec.com.tw/Temp/IEC61850/IEC-61850 Advantages 3_3_10.pdf · ReLab Software, LLC -- Confidential Information ReLab IEC 61850

ReLab Software, LLC -- Confidential Information

ReLab IEC 61850 OPC Solution Avantages

Full IEC 61850 (client) standard compliance  

Tested with Areva, ABB, GE, Siemens, SEL, and others

Scaleable: > 100 devices on a single system

High performance: SEL‐3351 12% CPU with 75 IED’s connected

Rapid development –

virtually not setup is required

Offline configuration – CID & SID files, Device replication

Simultaneous Poll & Buffered/Unbuffered reporting

Guarantied delivery of Buffered/Unbuffered reports (up to 4ms)

All MMS writes are supported (single bit write)

MMS timestamps and qualities are reported to OPC items

Simple GOOSE configuration

Page 3: ReLab Software, LLC -- Confidential Informationftp.youngtec.com.tw/Temp/IEC61850/IEC-61850 Advantages 3_3_10.pdf · ReLab Software, LLC -- Confidential Information ReLab IEC 61850

ReLab Software, LLC -- Confidential Information

ReLab IEC 61850 OPC Solution Special Features

Monitoring of OPC client load

Substitution of item timestamp with MMS message timestamp 

when device is incapable of delivering item timestamp

Device item quality substitution when device is incapable of 

delivering item qualities

Fully configurable ACSE parameter configuration for certain non‐

compliant devices 

Page 4: ReLab Software, LLC -- Confidential Informationftp.youngtec.com.tw/Temp/IEC61850/IEC-61850 Advantages 3_3_10.pdf · ReLab Software, LLC -- Confidential Information ReLab IEC 61850

ReLab Software, LLC -- Confidential Information

Rapid Development

For offline configuration select where your CID file is located

For online configuration specify Poll timeout and IP address

Page 5: ReLab Software, LLC -- Confidential Informationftp.youngtec.com.tw/Temp/IEC61850/IEC-61850 Advantages 3_3_10.pdf · ReLab Software, LLC -- Confidential Information ReLab IEC 61850

ReLab Software, LLC -- Confidential Information

Buffered & Unbuffered Reports Management

Configuration – set report enable bit (RptEna) to True trough OPC 

client and get your reports with guarantied delivery.

Page 6: ReLab Software, LLC -- Confidential Informationftp.youngtec.com.tw/Temp/IEC61850/IEC-61850 Advantages 3_3_10.pdf · ReLab Software, LLC -- Confidential Information ReLab IEC 61850

ReLab Software, LLC -- Confidential Information

MMS Write Management

Single Bit write to ctlVal

orIndent

populated automatically with system User name and 

computer name

orCat

determines type of write to be executed (for example SBO) 

Page 7: ReLab Software, LLC -- Confidential Informationftp.youngtec.com.tw/Temp/IEC61850/IEC-61850 Advantages 3_3_10.pdf · ReLab Software, LLC -- Confidential Information ReLab IEC 61850

ReLab Software, LLC -- Confidential Information

Simple Goose Configuration<?xml version="1.0" encoding="UTF‐8"?>

<RLBinding Version = "1.0">

<GoCB DomainName = "Dom1" LNName = "Node01" CBName = "GoCB01" Type = "Output" DSName = "Goose1" SendGoID = "true" Revision = 

"1" GoID = "GoCB01" >

<Address>

<P type="VLAN‐ID">002</P>

<P type="VLAN‐PRIORITY">4</P>

<P type="MAC‐Address">01‐0C‐CD‐01‐01‐11</P>

<P type="APPID">0000</P>

</Address>

</GoCB>

<GoCB DomainName = "Dom2" LNName = "Node02" CBName = "GoCB02" Type = "Input" DSName = "Goose2" >

<Address>

<P type="VLAN‐ID">003</P>

<P type="VLAN‐PRIORITY">4</P>

<P type="MAC‐Address">01‐0C‐CD‐01‐01‐12</P>

<P type="APPID">0001</P>

</Address>

</GoCB>

<DatSet Name = "Goose1" >

<Element Name = "Name1$fltVal" Type = "FLOAT32" />

<Element Name = "Name1$q" Type = "Quality" />

<Element Name = "Name1$t" Type = "Timestamp" />

<Element Name = "boolVal" Type = "BOOLEAN" />

<Element Name = "charVal" Type = "INT8" />

<Element Name = "shortVal" Type = "INT16" />

Page 8: ReLab Software, LLC -- Confidential Informationftp.youngtec.com.tw/Temp/IEC61850/IEC-61850 Advantages 3_3_10.pdf · ReLab Software, LLC -- Confidential Information ReLab IEC 61850

ReLab Software, LLC -- Confidential Information

Advanced Features Implementation

OPC clients management

Timestamp substitution

Quality substitution

Page 9: ReLab Software, LLC -- Confidential Informationftp.youngtec.com.tw/Temp/IEC61850/IEC-61850 Advantages 3_3_10.pdf · ReLab Software, LLC -- Confidential Information ReLab IEC 61850

ReLab Software, LLC -- Confidential Information

Special Features Implementation

ASCE Called Party Parameters

ASCE Called Party Parameters

Page 10: ReLab Software, LLC -- Confidential Informationftp.youngtec.com.tw/Temp/IEC61850/IEC-61850 Advantages 3_3_10.pdf · ReLab Software, LLC -- Confidential Information ReLab IEC 61850

ReLab Software, LLC -- Confidential Information

Best Practices & Performance  Typical Substation Configuration

50 IED’s Substation System (RL61850 single instance) 

100 points per IED (5,000 items total)

Buffered & Unbuffered reports configuration

Computer System SEL‐3351 (CPU 1GHz, RAM 1GB)

CPU Usage <10% ‐

normal operating conditions

CPU Usage under major event conditions <25% (~ 4,000 

item update)

Page 11: ReLab Software, LLC -- Confidential Informationftp.youngtec.com.tw/Temp/IEC61850/IEC-61850 Advantages 3_3_10.pdf · ReLab Software, LLC -- Confidential Information ReLab IEC 61850

ReLab Software, LLC -- Confidential Information

Best Practices & Performance  Large Substation Configuration

80 IED’s Substation System (RL61850 single instance)  

100 points per IED (8,000 items total)

Buffered & Unbuffered reports configuration

Computer System SEL‐3354 (CPU 1.2GHz, RAM 2GB)

CPU Usage <15% ‐

normal operating conditions

CPU Usage under major event conditions <30% (~ 7,000 

item update)

Page 12: ReLab Software, LLC -- Confidential Informationftp.youngtec.com.tw/Temp/IEC61850/IEC-61850 Advantages 3_3_10.pdf · ReLab Software, LLC -- Confidential Information ReLab IEC 61850

ReLab Software, LLC -- Confidential Information

Performance  Enterprise  Solution Configuration

200 IED’s Enterprise System (RL61850 single instance)  

100 points per IED (20,000 items total)

Buffered & Unbuffered reports configuration

Computer System Dell Server (CPU 2 X 3GHz, RAM 4GB)

CPU Usage <20% ‐

normal operating conditions

CPU Usage under major event conditions <40% (~ 18,000 

item update)

Page 13: ReLab Software, LLC -- Confidential Informationftp.youngtec.com.tw/Temp/IEC61850/IEC-61850 Advantages 3_3_10.pdf · ReLab Software, LLC -- Confidential Information ReLab IEC 61850

ReLab Software, LLC -- Confidential Information

Best Practices OPC Client Configuration

When it is applicable Buffered/Unbuffered reports should 

be used to limit traffic to OPC Client

All data is reported in OPC Data Change Event (OPC 2.0) 

and therefore OPC synchronous  or asynchronous reads 

are not required

The OPC Client needs to support data arrays (OPC 2.0) in 

order to process MMS unsolicited reporting

Page 14: ReLab Software, LLC -- Confidential Informationftp.youngtec.com.tw/Temp/IEC61850/IEC-61850 Advantages 3_3_10.pdf · ReLab Software, LLC -- Confidential Information ReLab IEC 61850

ReLab Software, LLC -- Confidential Information

Best Practices OPC Client Configuration

OPC Group Update interval should be set to less than the 

RL61850 driver poll time

Unlimited number of OPC clients can be connected to OPC 

Server

Only one OPC Client is capable of enabling 

Buffered/Unbuffered reports. Multiple OPC Clients are 

capable of receiving unsolicited IEC 61850 reports

Page 15: ReLab Software, LLC -- Confidential Informationftp.youngtec.com.tw/Temp/IEC61850/IEC-61850 Advantages 3_3_10.pdf · ReLab Software, LLC -- Confidential Information ReLab IEC 61850

ReLab Software, LLC -- Confidential Information

Best Practices Redundancy Configuration

IEC 61850 Servers (IEDs) supports multiple connections 

and therefore the redundancy can be achieved via OPC 

Clients with built‐in redundancy module

RLSLC is capable of acting as redundant module to one or 

multiple instances