Upload
ivosaputra
View
221
Download
0
Embed Size (px)
Citation preview
7/23/2019 Rekomendasi Setting 6 New Engines KSO BBC - HA - PK
http://slidepdf.com/reader/full/rekomendasi-setting-6-new-engines-kso-bbc-ha-pk 1/2
ENJINIRING PROTEKSI P3B SUMATERA
PLTMG PT BBC – PT HA – PT PK
TD 3 - GI TEL. LEMBU
DIBUAT OLEH : DIEVALUASI OLEH: DIESETUJUI OLEH : Page 1 of 2
IVO ASTUTY AMIRUDDIN
SETTING PROTEKSI TAMBAHAN 6 (ENAM) ENGINE PLTMG KSO BBC – HA –PK
Lokasi
KubikelProteksi
High/Low
SettCT Ratio
Proposal setting Rekomendasi setting PLN
Nilai
SettingKurva TMS Nilai Primer Nilai Sekunder Kurva TMS
Coupling di
Gardu
Induk
OCR
I> 2000/5 0.9 x In S INVERSE 2.51080 A (1,2 x CCC
kabel) 2.7 A (0.54 x In) IEC - SI 0.2
I>> 2000/5 1.5 x In S INVERSE 0.3 9000 A 22.5 A (4.5 x In) Definite(Instantaneous)
OCGR
Io> 2000/5 0.1 x In S INVERSE 0.5 50 A0.125 A (0.025 x
In)IEC - SI 0.1
Io>> 2000/5 0.3 x In S INVERSE 0.1 200 A 0.5 A (0.1 x In)Definite
(Instantaneous)
Incoming
dari GarduInduk
OCRI> 1250/5 0.6 x In S INVERSE 2 460 A (1,2 x CCC kabel) 1.84 A (0.368 x In) IEC - SI 0.23
I>> 1250/5 1.5 x In S INVERSE 0.5 BLOCKED BLOCKED BLOCKED
OCGRIo> 1250/5 0.1 x In S INVERSE 0.5 50 A 0.2 A (0.04 x In) IEC - SI 0.1
Io>> 1250/5 0.3 x In S INVERSE 0.1 BLOCKED BLOCKED BLOCKED
7/23/2019 Rekomendasi Setting 6 New Engines KSO BBC - HA - PK
http://slidepdf.com/reader/full/rekomendasi-setting-6-new-engines-kso-bbc-ha-pk 2/2
ENJINIRING PROTEKSI P3B SUMATERA
PLTMG PT BBC – PT HA – PT PK
TD 3 - GI TEL. LEMBU
DIBUAT OLEH : DIEVALUASI OLEH: DIESETUJUI OLEH : Page 2 of 2
IVO ASTUTY AMIRUDDIN
PROTEKSI ENGINEPROPOSAL REKOMENDASI PLN
SETTING WAKTU TUNDA SETTING WAKTU TUNDA
Overload power monitoring :
Overload power threshold 105% 0.1 sec 120% 5 sec
Monitor of load unbalance :
Load unbalance threshold 30% 0.1 sec 30% 10 sec
Overcurrent monitoring on:
Overcurrent threshold step 1 94% 60 sec 120% 60 sec
Overcurrent threshold step 2 103% 0.2 sec 130% 5 sec
Mains frequency monitoring:
Overfrequency f> threshold 51.5 Hz 0.5 sec 52 Hz 0.5 sec
Underfrequency f< threshold 47.5 hz 0.5 sec Confirmed
Main voltage monitoring:
Overvoltage V> threshold 440V 0.5 sec 440 V 5 sec
Undervoltage < threshold 340 V 0.5 sec 340 V 5 sec
Asymetry monitoring on ON OFF
Phase shift monitoring on ON OFF