Refrigerator Air Conditioner

Embed Size (px)

Citation preview

  • 8/2/2019 Refrigerator Air Conditioner

    1/61

  • 8/2/2019 Refrigerator Air Conditioner

    2/61

    CONTENTS

    1. ACKNOWLEDGEMENT

    2. SYNOPSIS

    3. INTRODUCTION

    4. BLOCK DIAGRAM

    5. WORKING PROCEDURE

    6. APPLICATIONS AND ADVANTAGES

    7. LIST OF MATERIALS

    8. COST ESTIMATION

    9. CONCLUSION

    10. BIBLIOGRAPHY

    11. PHOTOGRAPHY

  • 8/2/2019 Refrigerator Air Conditioner

    3/61

  • 8/2/2019 Refrigerator Air Conditioner

    4/61

  • 8/2/2019 Refrigerator Air Conditioner

    5/61

    SYNOPSIS

    A refrigerant heating type air conditioner operable in a cooling mode and a heating mode

    includes a first external heat exchanger which works as a condenser in the cooling mode and a

    second external heat-exchanger which works as an evaporator. Bypass means is disposed

    between a discharge side of a compressor and the second external heat-exchanger. An expansion

    valve is connected to an inner heat-exchanger, which works as a condenser in the heating mode,

    and to both the first and second external heat-exchangers. A control valve is disposed between a

    suction port side of the second external heat-exchanger for preventing the refrigerant from

    flowing to the second external heat-exchanger in the cooling mode. Pressure of the refrigerant

    which is trapped between the control valve and the expansion valve is increased by applying

    heat, by heating means, to the second external heat-exchanger. The heated refrigerant is released

    to the bypass means when its pressure exceeds to the pressure of discharged refrigerant from the

    compressor.

  • 8/2/2019 Refrigerator Air Conditioner

    6/61

  • 8/2/2019 Refrigerator Air Conditioner

    7/61

    INTRODUCTION

    What is Refrigeration and Air ConditioningRefrigeration and air conditioning is used to cool products or a building environment. The

    refrigeration or air conditioning system (R) transfers heat from a cooler low-energy reservoir

    to a warmer high-energy reservoir (see figure 1).

    High Temperature Reservoir

    Low Temperature Reservoir

    R

    Work Input

    Heat Absorbed

    Heat Rejected

    Figure 1. Schematic representation of refrigeration system

    Electrical Energy Equipment: Refrigeration and Air Conditioning Energy Efficiency Guide for

    Industry in Asia www.energyefficiencyasia.org UNEP 2

  • 8/2/2019 Refrigerator Air Conditioner

    8/61

    There are several heat transfer loops in a refrigeration system as shown in Figure 2. Thermal

    energy moves from left to right as it is extracted from the space and expelled into theoutdoors through five loops of heat transfer:

    Indoor air loop. In the left loop, indoor air is driven by the supply air fan through a

    cooling coil, where it transfers its heat to chilled water. The cool air then cools thebuilding space.

    Chilled water loop. Driven by the chilled water pump, water returns from the cooling coil

    to the chillers evaporator to be re-cooled.

    Refrigerant loop. Using a phase-change refrigerant, the chillers compressor pumps heatfrom the chilled water to the condenser water.

    Condenser water loop. Water absorbs heat from the chillers condenser, and the

    condenser water pump sends it to the cooling tower.

    Cooling tower loop. The cooling towers fan drives air across an open flow of the hot

    condenser water, transferring the heat to the outdoors.

    1.2 Air-Conditioning Systems

    Depending on applications, there are several options / combinations of air conditioning,

    which are available for use:

    Air conditioning (for space or machines)

    Split air conditioners

    Fan coil units in a larger system

    Air handling units in a larger system

    1.3 Refrigeration Systems (for processes)

    The following refrigeration systems exists for industrial processes (e.g. chilling plants) and

    domestic purposes (modular units, i.e. refrigerators):

    Small capacity modular units of the direct expansion type similar to domestic

    refrigerators.

    Centralized chilled water plants with chilled water as a secondary coolant for a

    temperature range over typically 5 oC. They can also be used for ice bank formation.

  • 8/2/2019 Refrigerator Air Conditioner

    9/61

    Brine plants, which use brines as a lower temperature, secondary coolant for typically

    sub- zero temperature applications, which come as modular unit capacities as well as large

    centralized plant capacities.

    The plant capacities up to 50 TR (tons of refrigeration) are usually considered as small

    capacity, 50250 TR as medium capacity and over 250 TR as large capacity units.

    A large company may have a bank of units, often with common chilled water pumps,

    condenser water pumps, cooling towers, as an off site utility. The same company may also

    have two or three levels of refrigeration and air conditioning such as a combination of:

    Comfort air conditioning (2025 oC)

    Chilled water system (80100 C)

    Brine system (sub-zero applications)

    TYPES OF REFRIGERATION AND AIR CONDITIONING

    This section describes the two principle types of refrigeration plants found in industry:

    Vapour Compression Refrigeration (VCR) and Vapour Absorption Refrigeration (VAR).VCR uses mechanical energy as the driving force for refrigeration, while VAR uses thermal

    energy as the driving force for refrigeration.

    2.1 Vapour Compression Refrigeration System

    2.1.1 Description

    Compression refrigeration cycles take advantage of the fact that highly compressed fluids at a

    certain temperature tend to get colder when they are allowed to expand. If the pressurechange is high enough, then the compressed gas will be hotter than our source of cooling

    (outside air, for instance) and the expand ed gas will be cooler than our desired cold

    temperature. In this case, fluid is used to cool a low temperature environment and reject the

    heat to a high temperature environment.

    Vapour compression refrigeration cycles have two advantages. First, a large amount of

    thermal energy is required to change a liquid to a vapor, and therefore a lot of heat can be

    removed from the air-conditioned space. Second, the isothermal nature of the vaporizationallows extraction of heat without raising the temperature of the working fluid to the

    temperature of whatever is being cooled. This means that the heat transfer rate remains high,

    because the closer the working fluid temperature approaches that of the surroundings, thelower the rate of heat transfer.

    The refrigeration cycle is shown in Figure 3 and 4 and can be broken down into the followingstages:

  • 8/2/2019 Refrigerator Air Conditioner

    10/61

    12. Low-pressure liquid refrigerant in the evaporator absorbs heat from its

    surroundings, usually air, water or some other process liquid. During this process itchanges its state from a liquid to a gas, and at the evaporator exit is slightly superheated.

    23. The superheated vapour enters the compressor where its pressure is raised. The

    temperature will also increase, because a proportion of the energy put into the compressionprocess is transferred to the refrigerant.

    34. The high pressure superheated gas passes from the compressor into the condenser.

    The initial part of the cooling process (3-3a) de-superheats the gas before it is then turned back

    into liquid (3a-3b). The cooling for this process is usually achieved by using air or water. A

    further reduction in temperature happens in the pipe work and liquid receiver (3b - 4), so that the

    refrigerant liquid is sub-cooled as it enters the expansion device.

    4 - 1 The high-pressure sub-cooled liquid passes through the expansion device, which

    both reduces its pressure and controls the flow into the evaporator.

    Schematic representation of the vapour compression refrigeration cycle

  • 8/2/2019 Refrigerator Air Conditioner

    11/61

    The condenser has to be capable of rejecting the combined heat inputs of the evaporator and

    the compressor. In other words: (1 - 2) + (2 - 3) has to be the same as (3 - 4). There is no heat

    loss or gain through the expansion device.

    Types of refrigerant used in vapour compression systems

    A variety of refrigerants are used in vapor compression systems. The required cooling

    temperature largely determines the choice of fluid. Commonly used refrigerants are in thefamily of chlorinated fluorocarbons (CFCs, also called Freons): R-11, R-12, R-21, R-22 and

    R-502. The properties of these refrigerants are summarized in Table 1 and the performance of

    these refrigerants is given in Table 2 below.

    Vapour Absorption Refrigeration System

    2.2.1 Description

    The vapour absorption refrigeration system consists of:

    Absorber: Absorption of refrigerant vapour by a suitable absorbent or adsorbent, forming

    a strong or rich solution of the refrigerant in the absorbent/ adsorbent

    Pump: Pumping of the rich solution and raising its pressure to the pressure of the

    Condenser

    Generator: Distillation of the vapour from the rich solution leaving the poor solution forRecycling

    The absorption chiller is a machine, which produces chilled water by using heat such as

    steam, hot water, gas, oil etc. Chilled water is produced based on the principle that liquid (i.e.

    refrigerant, which evaporates at a low temperature) absorbs heat from its surroundings when

    it evaporates. Pure water is used as refrigerant and lithium bromide solution is used asabsorbent.

    Heat for the vapour absorption refrigeration system can be provided by waste heat extracted

    from the process, diesel generator sets etc. In that case absorption systems require electricity

    for running pumps only. Depending on the temperature required and the power cost, it mayeven be economical to generate heat / steam to operate the absorption system.

    Condenser

  • 8/2/2019 Refrigerator Air Conditioner

    12/61

    A simple schematic of a vapour absorption refrigeration system

    The absorption chiller is a machine, which produces chilled water by using heat such assteam, hot water, gas, oil etc. Chilled water is produced based on the principle that liquid (i.e.

    refrigerant, which evaporates at a low temperature) absorbs heat from its surroundings when

    it evaporates. Pure water is used as refrigerant and lithium bromide solution is used asabsorbent.

    Heat for the vapour absorption refrigeration system can be provided by waste heat extracted

    from the process, diesel generator sets etc. In that case absorption systems require electricityfor running pumps only. Depending on the temperature required and the power cost, it may

    even be economical to generate heat / steam to operate the absorption system.

    A description of the absorption refrigeration concept is given below (references for thepictures are unknown)

    Evaporator

    The refrigerant (water) evaporates at around 4oC under a high vacuum condition of 754 mm Hg

    in the evaporator. Chilled water goes through heat exchanger tubes in the evaporator and

    transfers heat to the evaporated refrigerant.

    The evaporated refrigerant (vapor) turns into liquid again, while the latent heat from thisvaporization process cools the chilled water (in the diagram from 12 oC to 7 oC). The chilled

    water is then used for cooling purpose.

  • 8/2/2019 Refrigerator Air Conditioner

    13/61

    Absorber

    In order to keep evaporating, the refrigerant vapor must be discharged from the evaporator and

    refrigerant (water) must be supplied. The refrigerant vapor is absorbed into lithium bromidesolution, which is convenient to absorb the refrigerant vapor in the absorber. The heat generated

    in the absorption process is continuously removed from the system by cooling water. The

    absorption also maintains the vacuum inside the evaporator

    High Pressure Generator

    As lithium bromide solution is diluted, the ability to absorb the refrigerant vapor reduces. In

    order to keep the absorption process going, the diluted lithium bromide solution must beconcentrated again..

    An absorption chiller is provided with a solution concentrating system, called a generator.

    Heating media such as steam, hot water, gas or oil perform the function of concentratingsolutions.

  • 8/2/2019 Refrigerator Air Conditioner

    14/61

    The concentrated solution is returned to the absorber to absorb refrigerant vapor again

    Condenser

    To complete the refrigeration cycle, and thereby ensuring the refrigeration takes place

    continuously, the following two functions are required.

    1. To concentrate and liquefy the evaporated refrigerant vapor, which is generated in the

    highpressure generator.

    2. To supply the condensed water to the evaporator as refrigerant (water) For these two functionsa condenser is installed.

  • 8/2/2019 Refrigerator Air Conditioner

    15/61

    Absorption refrigeration systems that use Li-Br-water as a refrigerant have a Coefficient of

    Performance (COP) in the range of 0.65 - 0.70 and can provide chilled water at 6.7 oC with acooling water temperature of 30 oC. Systems capable of providing chilled water at 3 oC are

    also available. Ammonia based systems operate at above atmospheric pressures and are

    capable of low temperature operation (below 0oC). Absorption machines are available with

    capacities in the range of 10-1500 tons. Although the initial cost of an absorption system ishigher than that of a compression system, operational costs are much lower if waste heat is

    used.

    Evaporative cooling in vapor absorption refrigeration systems.

    There are occasions where air conditioning, which stipulates control of humidity of up to

    50% for human comfort or for processes, can be replaced by a much cheaper and less energy

    intensive evaporative cooling.

    Sprinkling Water

  • 8/2/2019 Refrigerator Air Conditioner

    16/61

    The concept is very simple and is the same as that used in a cooling tower. Air is brought in

    close contact with water to cool it to a temperature close to the wet bulb temperature. Thecool air can be used for comfort or process cooling. The disadvantage is that the air is rich in

    moisture. Nevertheless, it is an extremely efficient means of cooling at very low cost. Large

    commercial systems employ cellulose filled pads over which water is sprayed. Thetemperature can be controlled by controlling the airflow and the water circula tion rate. The

    possibility of evaporative cooling is especially attractive for comfort cooling in dry regions.

    This principle is practiced in textile industries for certain processes.

    OF REFRIGERATION AND AIR CONDITIONING

    This section describes how the performance of refrigeration / air conditioning plants and be

    assessed.

    3.1 Assessment of Refrigeration

    3.1.1 TR

    We start with the definition of TR.

    TR: the cooling effect produced is quantified as tons of refrigeration, also referred to as

    chiller tonnage.

    TR = Q xCp x(TiTo) / 3024

    Where Q is mass flow rate of coolant in kg/hr

    Cp is coolant specific heat in kCal /kg deg CTi is inlet, temperature of coolant to evaporator (chiller) in 0C

    To is outlet temperature of coolant from evaporator (chiller) in 0C.

    1 TR of refrigeration = 3024 kCal/hr heat rejected

    3.1.2 Specific Power Consumption

    The specific power consumption kW/TR is a useful indicator of the performance of a

    refrigeration system. By measuring the refrigeration duty performed in TR and the kW

    inputs, kW/TR is used as an energy performance indicator.

    In a centralized chilled water system, apart from the compressor unit, power is also

    consumed by the chilled water (secondary) coolant pump, the condenser water pump (for

    heat rejection to cooling tower) and the fan in the cooling tower. Effectively, the overall

    energy consumption would be the sum of:

  • 8/2/2019 Refrigerator Air Conditioner

    17/61

    Compressor kW

    Chilled water pump kW

    Condenser water pump kW

    Cooling tower fan kW, for induced / forced draft towersThe kW/TR, or the specific power consumption for a certain TR output is the sum of:

    Compressor kW/TRChilled water pump kW/TR

    Condenser water pump kW/TR

    Cooling tower fan kW/TR

    Coefficient of Performance

    The theoretical Coefficient of Performance (Carnot), (COPCarnot, a standard measure of

    refrigeration efficiency of an ideal refrigeration system) depends on two key systemtemperatures: evaporator temperature Te and condenser temperature Tc. COP is given as:

    COPCarnot = Te/ (Tc - Te)

    This expression also indicates that higher COPCarnot is achieved with higher evaporator

    temperatures and lower condenser temperatures. But COPCarnot is only a ratio of

    temperatures, and does not take into account the type of compressor. Hence the COPnormally used in industry is calculated as follows:

    Cooling effect (kW)

    COP =Power input to compressor (kW)

    where the cooling effect is the difference in enthalpy across the evaporator and expressed

    as kW.

    Figure

  • 8/2/2019 Refrigerator Air Conditioner

    18/61

    Assessment of Air ConditioningFor air conditioning units, the airflow at the Fan Coil Units (FCU) or the Air Handling Units(AHU) can be measured with an anemometer. Dry bulb and wet bulb temperatures are

    measured at the inlet and outlet of the AHU or the FCU and the refrigeration load in TR isassessed as:

    Where, Q is the air flow in m3/h

    is density of air kg/m3hin is enthalpy of inlet air kCal/kg

    hout is enthalpy of outlet air kCal/kg

    Use of psychometric charts can help to calculate h in and hout from dry bulb and wet bulb

    temperature values which are measured during trials by a whirling psychrometer. Power

    measurements at compressor, pumps, AHU fans, cooling tower fans can be taken with aportable load analyzer.

    Estimation of the air conditioning load is also possible by calculating various heat loads,sensible and latent, based on inlet and outlet air parameters, air ingress factors, air flow,

    number of people and type of materials stored.

    An indicative TR load profile for air conditioning is presented as follows:

    Small office cabins = 0.1 TR/m2

    Medium size office i.e., = 0.06 TR/m2

    1030 people occupancywith central A/C

    Large multistoried office = 0.04 TR/m2

    complexes with central A/C

    3.3 Considerations when Assessing Performance

    3.3.1 Accuracy of flow and temperature measurements

    In a field performance assessment, accurate instruments are required to measure the inlet and

    outlet temperatures of chilled water and condenser water, preferably with a count of at least

    0.1 oC. Flow measurements of chilled water can be made with an ultrasonic flow meter

    directly or can be determined based on pump duty parameters. Adequacy checks of chilledwater are often needed and most units are designed for a typical 0.68 m3/hr per TR (3

    gpm/TR) chilled water flow. Condenser water flow can also be measured with a non-contactflow meter directly or determined by using pump duty parameters. Adequacy checks of

    condenser water are also needed often, and most units are designed for a typical 0.91 m 3/hr

    per TR (4 gpm / TR) condenser water flow.

  • 8/2/2019 Refrigerator Air Conditioner

    19/61

    3.3.2 Integrated Part Load Value (IPLV)

    Although the kW/ TR can serve as an initial reference, it should not be taken as an absolute

    since this value is based on a 100% equipment capacity level and on design conditions that

    are considered most critical. These conditions may only occur during % of the total time the

    equipment is in operation throughout the year. For this reason, it is essential to have data thatreflects how the equipment operates with partial loads or under conditions that demand less

    than 100% capacity. To overcome this, an average kW/TR with partial loads has to bedetermined, which is called the Integrated Part Load Value (IPLV).

    The IPLV is the most appropriate reference, although not considered the best, because it only

    captures four points within the operational cycle: 100%, 75%, 50% and 25%. Furthermore, it

    assigns the same weight to each value, and most equipment operate between 50% and 75%

    oftheir capacity. This is why it is so important to prepare a specific analysis for each case that

    addresses the four points mentioned, as well as developing a profile of the heat exchanger's

    operations during the year.

    ENERGY EFFICIENCY OPPORTUNITIES

    This section includes areas for energy conservation in refrigeration plants.

    4.1 Optimization of Process Heat Exchangers

    There is a tendency to apply high safety margins to operations, which influence the

    compressor suction pressure / evaporator set point. For instance, a process-coolingrequirement of 15 oC would need chilled water at a lower temperature, but the range can vary

    from 6 oC to about 10 oC. At chilled water of 10 oC, the refrigerant side temperature has to be

    lower (about5oC to +5oC). The refrigerant temperature determines the correspondingsuction pressure of the refrigerant, which in turn determines the inlet duty conditions for the

    refrigerant compressor. Applying the optimum / minimum driving force (temperature

    difference) can thus help to reach the highest possible suction pressure at the compressor,

    thereby minimizing energy consumption. This requires proper sizing of heat transfer areas ofprocess heat exchangers and evaporators as well as rationalizing the temperature requirement

    to highest possible value. A 1oC raise in evaporator temperature can save almost 3 % of the

    power consumed. The TR capacity of the same machine will also increase with the

    evaporator temperature, as given in the table below.

  • 8/2/2019 Refrigerator Air Conditioner

    20/61

    In order to rationalize the heat transfer areas, the heat transfer coefficient on the refrige rant

    side can range from 14002800 watts /m2K. The refrigerant side heat transfer areas are ofthe order of 0.5 m2/TR and above in evaporators.

    Condensers in a refrigeration plant are critical equipment that influence the TR capacity and

    power consumption demands. For any refrigerant, the condensation temperature andcorresponding condenser pressure are dependent on the heat transfer area, the effectiveness of

    heat exchange and the type of cooling chosen. A lower condensation temperature means that

    the compressor has to work between a lower pressure differential as the discharge pressure isfixed by design and performance of the condenser.

    The choice of condensers in practice is between air-cooled, air-cooled with water spray, and

    heat exchanger cooled. Larger shell and tube heat exchangers that are used as condensers and

    that are equipped with good cooling tower operations allow operation at low discharge pressure

    values and improve the TR capacity of the refrigeration plant.

    If the refrigerant R22 is used in a water-cooled shell and tube condenser then the dischargepressure is 15 kg/cm2. If the same refrigerant is used in an air-cooled condenser then thedischarge pressure is 20 kg/cm2. This shows how much additional compression duty is

    required, which results in almost 30 % additional energy consumption by the plant.

    One of the best options at the design stage would be to select large sized (0.65 m 2/TR andabove) shell and tube condensers with water-cooling, rather than less expensive alternatives

    like air cooled condensers or water spray atmospheric condenser units.

    Maintenance of Heat Exchanger Surfaces

    Once compressors have been purchased, effective maintenance is the key to optimizingpower consumption. Heat transfe r can also be improved by ensuring proper separation of the

    lubricating oil and the refrigerant, timely defrosting of coils, and increasing the velocity of

    the secondary coolant (air, water, etc.). However, increased velocity results in larger pressuredrops in the distribution system and higher power consumption in pumps / fans. Therefore,

    careful analysis is required to determine the optimum velocity.

    Fouled condenser tubes force the compressor to work harder to attain the desired capacity.

    For example, a 0.8 mm scale build-up in condenser tubes can increase energy consumption

    by as much as 35 %. Similarly, fouled evaporators (due to residual lubricating oil or

    infiltration of air) result in increased power consumption. Equally important is properselection, sizing, and maintenance of cooling towers. A reduction of 0.55oC in temperature

    of the water returning from the cooling tower reduces compressor power consumption by 3%.

    * 15 ton reciprocating compressor based system. The power consumption is lower than that for

    systems typically available in India. However, the percentage change in power consumption is

    indicative of the effect of poor maintenance

  • 8/2/2019 Refrigerator Air Conditioner

    21/61

    Multi -Staging For Efficiency

    Efficient compressor operation requires that the compression ratio be kept low, to reduce

    discharge pressure and temperature. For low temperature applications involving highcompression ratios, and for wide temperature range requirements, it is preferable (due toequipment design limitations) and often economical to employ multi-stage reciprocating

    machines or centrifugal / screw compressors.

    There are two types of multi-staging systems, which are applicable to all types of

    compressors: compound and cascade. With reciprocating or rotary compressors, two-stage

    compressors are preferable for load temperatures from20oC to58oC, and with centrifugal

    machines for temperatures around43oC.

    In a multi-stage operation, a first-stage compressor that sized to meet the cooling load, feeds

    into the suction of a second-stage compressor after inter-cooling of the gas. A part of thehigh-pressure liquid from the condenser is flashed and used for liquid sub-cooling. The

    second compressor, therefore, has to meet the load of the evaporator and the flash gas. A

    single refrigerant is used in the system, and the two compressors share the compression task

    equally. Therefore, a combination of two compressors with low compression ratios canprovide a high compression ratio.

    For temperatures in the range of46oC to101oC, cascaded systems are preferable. In thissystem, two separate systems using different refrigerants are connected so that one rejects

    heat to the other. The main advantage of this system is that a low temperature refrigerant,

    which has a high suction temperature and low specific volume, can be selected for the lowstage

    to meet very low temperature requirements.

    4.4 Matching Capacity to System Load

    During part- load operation, the evaporator temperature rises and the condenser temperature

    falls, effectively increasing the COP. But at the same time, deviation from the design

    operation point and the fact that mechanical losses form a greater proportion of the totalpower negate the effect of improved COP, resulting in lower part- load efficiency.

    Therefore, consideration of part-load operation is important, because most refrigeration

    applications have varying loads. The load may vary due to variations in temperature and

    process cooling needs. Matching refrigeration capacity to the load is a difficult exercise,

    requiring knowledge of compressor performance, and variations in ambient conditions, anddetailed knowledge of the cooling load.

  • 8/2/2019 Refrigerator Air Conditioner

    22/61

    4.5 Capacity Control and Energy Efficiency

    The capacity of compressors is controlled in a number of ways. Capacity control of

    reciprocating compressors through cylinder unloading results in incremental (step-by-step)

    modulation. In contrast, continuous modulation occurs in centrifugal compressors through

    vane control and in screw compressors through sliding valves. Therefore, temperature controlrequires careful system design. Usually, when using reciprocating compressors in applications

    with widely varying loads, it is desirable to control the compressor by monitoring the returnwater (or other secondary coolant) temperature rather than the temperature of the water leaving

    the chiller.

    This prevents excessive on-off cycling or unnecessary loading / unloading of the compressor.

    However, if load fluctuations are not high, the temperature of the water leaving the chiller should

    be monitored. This has the advantage of preventing operation at very low water temperatures,

    especially when flow reduces at low loads. The outgoing water temperature should be monitoredfor centrifugal and screw chillers.

    Capacity regulation through speed control is the most efficient option. However, when

    employing speed control for reciprocating compressors, it should be ensured that thelubrication system is not affected. In the case of centrifugal compressors, it is usually

    desirable to restrict speed control to about 50 % of the capacity to prevent surging. Below

    50%, vane control or hot gas bypass can be used for capacity modulation.

    The efficiency of screw compressors operating at part load is generally higher than either

    centrifugal compressors or reciprocating compressors, which may make them attractive in

    situations where part-load operation is common. Screw compressor performance can beoptimized by changing the volume ratio. In some cases, this may result in higher full-load

    efficiencies as compared to reciprocating and centrifugal compressors. Also, the ability ofscrew compressors to tolerate oil and liquid refrigerant slugs makes them preferred in somesituations.

    4.6 Multi -level Refrigeration for Plant Needs

    The selection of refrigeration systems also depends on the range of temperatures required inthe plant. For diverse applications requiring a wide range of temperatures, it is generally

    more economical to provide several packaged units (several units distributed throughout the

    plant) instead of one large central plant. Another advantage would be the flexibility and

    reliability. The selection of packaged units could also be made depending on the distance at

    which cooling loads need to be met. Packaged units at load centers reduce distribution lossesin the system. Despite the advantages of packaged units, central plants generally have lower

    power consumption since at reduced loads power consumption can reduce significantly due

    to the large condenser and evaporator surfaces.

  • 8/2/2019 Refrigerator Air Conditioner

    23/61

    Many industries use a bank of compressors at a central location to meet the load. Usually

    the chillers feed into a common header from which branch lines are taken to differentlocations in the plant. In such situations, operation at part- load requires extreme care. For

    efficient operation, the cooling load, and the load on each chiller must be monitored closely.

    It is more efficient to operate a single chiller at full load than to operate two chillers at partload.The distribution system should be designed such that individual chillers can feed all branch lines.

    Isolation valves must be provided to ensure that chilled water (or other coolant) does not flow

    through chillers not in operation. Valves should also be provided on branch lines to isolatesections where cooling is not required. This reduces pressure drops in the system and reduces

    power consumption in the pumping system.

    Individual compressors should be loaded to their full capacity before operating the second

    compressor. In some cases it is economical to provide a separate smaller capacity chiller,

    which can be operated on an on-off control to meet peak demands, with larger chillers

    meeting the base load.

    Flow control is also commonly used to meet varying demands. In such cases the savings inpumping at reduced flow should be weighed against the reduced heat transfer in coils due to

    reduced velocity. In some cases, operation at normal flow rates, with subsequent longer

    periods of no- load (or shut-off) operation of the compressor, may result in larger savings.

    4.7 Chilled Water Storage

    Depending on the nature of the load, it is economical to provide a chilled water storagefacility with very good cold insulation. Also, the storage facility can be fully filled to meet

    the process requirements so that chillers need not be operated continuously. This system is

    usually economical if small variations in temperature are acceptable. This system has the

    added advantage of allowing the chillers to be operated at periods of low electricity demandto reduce peak demand charges. Low tariffs offered by some electric utilities for operation at

    nighttime can also be taken advantage of by using a storage facility. An added benefit is that

    lower ambient temperature at night lowers condenser temperature and thereby increases theCOP.

    If temperature variations cannot be tolerated, it may not be economical to provide a storagefacility since the secondary coolant would have to be stored at a temperature much lower than

    required to provide for heat gain. The additional cost of cooling to a lower temperature may

    offset the benefits. The solutions are case specific. For example, in some cases it may be

    possible to employ large heat exchangers, at a lower cost burden than low temperature chiller

    operation, to take advantage of the storage facility even when temperature variations are notacceptable. Ice bank systems, which store ice rather than water, are often economical.

  • 8/2/2019 Refrigerator Air Conditioner

    24/61

    4.8 System Design Features

    In overall plant design, adoption of good practices improves the energy efficiency

    significantly. Some areas for consideration are:

    Design of cooling towers with FRP impellers and film fills, PVC drift eliminators, etc.

    Use of softened water for condensers in place of raw water.

    Use of economic insulation thickness on cold lines, heat exchangers, considering cost of

    heat gains and adopting practices like infrared thermography for monitoring - applicableespecially in large chemical / fertilizer / process industry.

    Adoption of roof coatings / cooling systems, false ceilings / as applicable, to minimize

    refrigeration load.

    Adoption of energy efficient heat recovery devices like air to air heat exchangers to precoolthe fresh air by indirect heat exchange; control of relative humidity through indirect

    heat exchange rather than use of duct heaters after chilling.

    Adopting of variable air volume systems; adopting of sun film application for heat reflection;

    optimizing lighting loads in the air conditioned areas; optimizing number of air changes in

    the air conditioned areas are few other examples.

    OPTION CHECKLIST

    This section includes most important energy efficiency options.

    Cold Insulation: Insulate all cold lines / vessels using economic insulation thickness to

    minimize heat gains; and choose appropriate (correct) insulation.

    Building Envelope: Optimize air conditioning volumes by measures such as use of false

    ceiling and segregation of critical areas for air conditioning by air curtains.

    Building Heat Loads Minimization: minimize the air conditioning loads by measures such

    as roof cooling, roof painting, efficient lighting, pre-cooling of fresh air by air- to-air heat

    exchangers, variable volume air system, optimal thermo-static setting of temperature ofair conditioned spaces, sun film applications, etc.

    Process Heat Loads Minimization: Minimize process heat loads in terms of TR capacityas well as refrigeration level, i.e., temperature required, by way of:

  • 8/2/2019 Refrigerator Air Conditioner

    25/61

    Flow optimization

    Heat transfer area increase to accept higher temperature coolant

    Avoiding wastages like heat gains, loss of chilled water, idle flows.

    Frequent cleaning / de-scaling of all heat exchangers

    At the Refrigeration A/C Plant Area:

    Ensure regular maintenance of all A/C plant components as per manufacturerguidelines.

    Ensure adequate quantity of chilled water and cooling water flows and avoidbypass flows by closing valves of idle equipment.

    Minimize part load operations by matching loads and plant capacity on lineand adopt variable speed drives for varying process load.

    Make efforts to continuously optimize condenser and evaporator parametersfor minimizing specific energy consumption and maximizing capacity.

    Adopt a VAR system where economics permit as a non-CFC solution.

    Ensure that the AC does not get overloaded and check the fuse or circuit breaker if theAC does not operate.

    Replace or clean the filter and clean the evaporator and condenser coils regularly, for theair conditioner to cool efficiently.

    Clean the thermostat regularly and replace it if necessary.

    If a compressor does not work properly, call a service person immediately

    Any noise that your AC makes needs to be checked by your mechanic.

    A good air filter will extend the life of your air conditioner because the important parts,

    like the blower assembly, the cooling coil, and other inner parts will stay cleaner, operatemore efficiently and last longer.

    Avoid frequent opening of doors/windows. A door kept open can result in doubling the

    power consumption of your AC.

    Ensure direct sunlight and heat do not enter the air-conditioned space, particularly in the

    afternoons.

    Most people believe that a thermostat set to a lower temperature than desired will forceyour air-conditioner to cool faster, not really, all it does, is make your air-conditioner

    operate for longer. Moreover, you will have an unnecessarily chilly room and wastedpower. Every degree lower on the temperature setting results in an extra 3-4% of power

    consumed. Hence, once you found yourself a comfortable temperature and set the

    thermostat at that level, avoid changing the thermostat settings.

  • 8/2/2019 Refrigerator Air Conditioner

    26/61

    Once an air-conditioning system has been designed and installed avoid any major change

    in the heat-load on the AC. This will add to wasted power

    A clogged drain line is usually caused by algae (the green moss- like stuff!) build-up

    inside the drain line. The air handler provides a cool, damp environment for development

    of molds and mildew and if left untreated these growths can spread into your ductwork.Get rid of these molds by using a disinfectant (consult your dealer). Make sure that the

    face of the cooling or evaporator coil is clean so that air can pass through freely.

    If you have an air return duct in a hot area such as an attic or garage, make sure that this

    duct is not broken, split, or disconnected and sucking in hot air.

    Window unit should tilt down slightly on the outside. The part that removes humidity

    (where water accumulates) is the front coil, which is inside your home. Normally, there is

    a trough and/or a drain tube that lets the water run to the rear of the unit. If the drain gets

    clogged, water will back up and leak inside. Ask your mechanic to clean the chassis and

    make sure all screws are tight.

    Heat load can be reduced by keeping a false ceiling in offices. Curtains/ blinds /sun filmon windows reduces heat input into the room. Insulating the ceiling, which is exposed to

    the sun with 50- mm thermocole drastically, reduces heat input into the room.

    Check for duct leaks and crushed ductwork. All air leaks should be sealed with a good

    quality duct sealant (not duct tape).

    Inspect the chiller as recommended by the chiller manufacturer. Typically, this should bedone at least quarterly.

    Routinely inspect for refrigerant leaks.

    Check the compressor operating pressures.

    Check all oil levels and pressures.

    Examine all motor voltages and amps.

    Check all electrical starters, contactors, and relays.

    Check all hot gas and unloader operations.

    Use superheat and subcooling temperature readings to obtain a chiller's maximum

    efficiency.

    Take discharge line temperature readings.

    Some Rules of Thumb are:

  • 8/2/2019 Refrigerator Air Conditioner

    27/61

    Refrigeration capacity reduces by 6 percent for every 3.5 C increase in condensing

    temperature.

    Reducing condensing temperature by 5.5 C results in a 2025 percent decrease in

    compressor power consumption.

    A reduction of 0.55 C in cooling water temperature at condenser inlet reduces

    compressor power consumption by 3 percent.

    1 mm scale build-up on condenser tubes can increase energy consumption by 40 percent.

    5.5 C increase in evaporator temperature reduces compressor power consumption by 20

    25 percent.

    The condensed refrigerant in the condenser is in condition A which lies on the line for theboiling point of the liquid. The liquid has thus a temperature tc, a pressure pc also called

    saturated temperature and pressure.

    The condensed liquid in the condenser is further cooled down in the condenser to a lower

    temperature A1 and now has a temperature tl and an enthalpy h0. The liquid is now sub-cooled

    which means that it is cooled to a lower temperature than the saturated temperature.

    The condensed liquid in the receiver is in condition A1 which is sub-cooled liquid. This liquid

    temperature can change if the receiver and liquid is either heated or cooled by the ambient

    temperature. If the liquid is cooled the sub-cooling will increase and visa versa.

    When the liquid passes through the expansion valve its condition will change from A1 to B. Thisconditional change is brought about by the boiling liquid because of the drop in pressure to p0.

    At the same time a lower boiling point is produced, t0, because of the drop in pressure. In theexpansion valve the enthalpy is constant h0, as heat is neither applied nor removed.

    At the evaporator inlet, point B, there is a mixture of liquid and vapour while in the evaporator atC there is saturated vapour. At the evaporator outlet.

    4. Refrigeration process, pressure/enthalpy diagram

    point C1 there is super-heated vapour which means that the suction gas is heated to a higher

    temperature than the saturated temperature. Pressure and temperature are the same at point Band at outlet point C1 where the gas is super-heated the evaporator has absorbed heat from thesurroundings and the enthalpy has changed to h1.

  • 8/2/2019 Refrigerator Air Conditioner

    28/61

    When the refrigerant passes through the compressor its condition changes from C1 to D.

    Pressure rises to condensing pressure pc. The temperature rises to thot-gas which is higher thanthe condensing temperature tc because the vapour has been strongly superheated. More energy

    (from the electrical motor) in the form of heat has also been introduced and the enthalpy

    therefore changes to h2.

    At the condenser inlet, point D, the condition is thus one of superheated vapour at pressure pc.

    Heat is given off from the condenser to the surroundings so that the enthalpy again changes to

    main point A1. First in the condenser there occurs a conditional change from stronglysuperheated vapour to saturated vapour (point E), then a condensation of the saturated vapour.

    From point E to point A the temperature (condensing temperature) remains the same, in that

    condensation and evaporation occurs at constant temperature.

    From point A to point A1 in the condenser the condensed liquid is further cooled down, but the

    pressure remains the same and the liquid is now sub-cooled.

    tc = condensing temperaturepc = condensing pressure

    tl = liquid temperaturet0 = evaporating temperature

    p0 = evaporating pressure

    Expansionvalve

    Receiver

    Pressure

    Heat

    Refrigeration plant main components

    The job of the compressor is to suck vapour from the evaporator and force it into the condenser.

    The most common type is the piston compressor, but other types have won acceptance, e.g.

    centrifugal scroll and screw compressors.

    The piston compressor covers a very large capacity range, right from small single cylinder

    modeIs for household refrigerators up to 8 to 12 cylinder modeIs with a large swept volume for

    industrial applications.

    In the smallest applications the hermetic compressor is used, where compressor and

    motor are built together as a complete hermetic unit.

  • 8/2/2019 Refrigerator Air Conditioner

    29/61

    For medium sized plants one of the most common compressors is the larger sizes of

    hermetic compressors in either piston or scroll versions. The applications are both airconditioning, general commercial refrigeration and chillers.

    For larger plants the most common is the semihermetic compressor. The advantage here is that

    shaft glands can be avoided; these are very difficult to replace when they begin to leak.However, the design cannot be used on ammonia plants since this refrigerant attacks motor

    windings.

    Still larger HFC compressors, and all ammonia compressors, are designed as opencompressors, i.e. with the motor outside the crankcase. Power transmission can be direct to the

    crankshaft or through a V-belt drive.

    For quite special applications there is the oil-free compressor. But lubrication of bearings and

    cylinder walls with oil is normally always necessary. On large refrigeration compressors oil is

    circulated by an oil pump.

    Vapor compression refrigeration, as the name suggests, employs a compression process to

    raise the pressure of a refrigerant vapor flowing from an evaporator at pressurep1 top2, as

    shown in Figure 8.2. The refrigerant then flows through a heat exchanger called a condenserat

    the high pressure,p2 =p3, through a throttling device, and back to the low pressure, p1, in theevaporator. The pressuresp2 =p3 andp4 =p1 correspond to refrigerant saturation temperatures,T3 and T1 = T4, respectively. These temperatures allow natural heat exchange with adjacent hot

    and cold regions from high temperature to low. That is, T1 is less than TL; so that heat, QL, willflow from the cold region into the evaporatorto vaporize the working fluid. Similarly, the

    temperature T3 allows heat, QH, to be transferred from the working fluid in the condenserto the

    hot region at TH.

    This is indicated by the arrows of Figure 8.2.

    Thus the resulting device is one in which heat is transferred from a low temperature, TL, to ahigh temperature, TH, using a compressor that receives work from the surroundings, therein

    satisfying the Clausius statement.

    The throttling device, as shown in Figure 8.2, restrains the flow of refrigerant from the

    condenser to the evaporator. Its primary purpose is to provide the flow resistance necessary to

    maintain the pressure difference between the two heat exchangers. It also serves to control the

    rate of flow from condenser to evaporator. The throttling device may be a thermostatic

    expansion valve (TEV) controlled by evaporator exit temperature or a long, fine-bore pipe calleda capillary tube.

  • 8/2/2019 Refrigerator Air Conditioner

    30/61

    For an adiabatic throttling device, the First Law of Thermodynamics requires that h3 = h4 forthe irreversible process, because Q and Ware zero and kinetic energy change is negligible. Thus

    saturated liquid at T3 flashes to a mixture of liquid and vapor at the evaporator inlet at the

    enthalpy h4 = h3 and pressurep4 =p1. Also the evaporator entrance has the qualityx4 and

    temperature T4 = T1. Heat from the cold source at TL > T4 boils the mixture in the evaporator toa saturated or slightly superheated vapor that passes to the suction side of the compressor.

    The compressor in small and medium-sized refrigeration units is usually a reciprocating orother positive-displacement type, but centrifugal compressors often are used in large systems

    designed for commercial and industrial service.

    It may be noted from the T-s diagram in Figure 8.2 that the vapor compression cycle is a

    reversed Rankine cycle, except that the pressure drop occurs through a throttling device rather

    than a turbine. In principle, a turbine or expansion device of some kind could be used to

    simultaneously lower the refrigerant pressure and produce work to reduce the net work required

    to operate the compressor. This is very unlikely because of the difficulty of deriving work from amixture of liquid and vapor and because of the low cost and simplicity of refrigeration throttling

    devices.

    An exploded view of a through-the-wall type room air conditioner commonly used in motels

    and businesses is shown in Figure 8.3. A fan coil unit on the space side is the evaporator. Athermally insulating barrier separates a hermetically sealed, electric-motor-driven positive

    displacement compressor unit and a finned-tube heat exchanger condenser from the room on the

    outdoor side.

  • 8/2/2019 Refrigerator Air Conditioner

    31/61

    Figure 8.4 shows a packaged air-conditioning unit designed for in-space use or for a nearby

    space with short duct runs. Units sometimes are designed to operate with either one or twocompressors, coils, and fans to better accommodate varying cooling demands. A unit with

    watercooled condensers such as that shown requires an external heat sink, usually provided by a

    nearby ground-level or rooftop evaporative cooling tower.

    Rather than being combined in a single enclosure, refrigeration units frequently are installed

    as split systems. Figure 8.5 shows an uncovered rooftop condensing unitthat contains acompressor and air cooled condenser. Such units are, of course, covered to resist the outdoorenvironment over many years. Cooled refrigerant is piped in a closed circuit to remote air

    distribution units that contain cooling coils (evaporators) and throttling devices. Figure 8.6

    shows a skid-mounted air-cooled condensing unit also designed to function with remote

    evaporators in applications such as walk-in coolers.

  • 8/2/2019 Refrigerator Air Conditioner

    32/61

    Refrigerants

    Refrigerants are specially selected substances that have certain important characteristics

    including good refrigeration performance, low flammability and toxicity, compatibility with

    compressor lubricating oils and metals, and good heat transfer characteristics. They are usually

    identified by a number that relates to their molecular composition.

  • 8/2/2019 Refrigerator Air Conditioner

    33/61

    The ASHRAE Handbook (ref. 1) identifies a large number of refrigerants by number, as

    shown in Table 8.1. Inorganic refrigerants are designated by 700, plus their molecular weight.For hydrocarbon and halocarbon refrigerants, the number schemeXYZworks as follows: (1)Z,

    on the right is the number of fluorine atoms; (2) Yis the number of hydrogen atoms plus one; and

    (3) the leftmost digit,X, is one less than the number of carbon atoms in the compound.

    Two important examples are refrigerants R-12 and R-22. R-12, dichlorodifluoromethane, has

    two fluorine, one carbon, and two chlorine atoms in a methane-type structure. Thus the halogens

  • 8/2/2019 Refrigerator Air Conditioner

    34/61

  • 8/2/2019 Refrigerator Air Conditioner

    35/61

  • 8/2/2019 Refrigerator Air Conditioner

    36/61

    chlorine and fluorine, replace hydrogen atoms in the CH4 molecular structure as shown in Figure

    8.7. R-22, monochlorodifluoromethane, has a similar structure to R-12, except for a singlehydrogen atom replacing a chlorine atom. Charts of the thermodynamic properties of these

    refrigerants are given in Appendix F.

    The commonly used chlorofluorocarbon (CFC) refrigerants are a cause of great concern,

    because their accumulation in the upper atmosphere creates a .hole. in the ozone layer that

    normally shields the earth from solar ultraviolet radiation (refs. 8 and 9). In 1987, more than 35

    countries, including the United States, signed the Montreal Protocol on Substances that Depletethe Ozone Layer. The Montreal Protocol called for a freeze in 1989 and reductions in the 1990s

    on the production levels of R-11, R-12, R-113, R-114, and R-115. The halocarbon refrigerants,

    some of which are also widely used as aerosol propellants, foams, and solvents, are nowcategorized as chlorofluorocarbons (CFCs), hydrochlorofluorocarbons (HCFCs), or

    hydrofluorocarbons (HFCs). The HFCs, lacking chlorine, are no threat to the ozone layer but are

    not in common usage as refrigerants. CFCs, which contain more chlorine than do HCFCs, are the

    most serious offenders, are very stable, and do not break down rapidly in the lower atmosphere.

    The Clean Air Act of 1990 (ref. 15) mandated termination of production in the United States of

    all CFCs such as R-12 by the year 2000. Government data indicate that, because of the structuraldifference between them, R-12 has twenty times the ozone-depletion potential in the upper

    atmosphere of R-22. Nevertheless, R-22 and other HCFCs are also scheduled by the law for

    phaseout of production by the year 2030.

  • 8/2/2019 Refrigerator Air Conditioner

    37/61

    Thus, the search for alternate refrigerants to replace those used in existing applications

    (worth hundreds of billions of dollars) has assumed enormous importance. It is a difficult,expensive, and continuing task to which industry is vigorously applying its efforts. Charts of

    thermodynamic properties for two of the newer refrigerants, R-123 and R134a, are given in

    Appendix F.

    Vapor-Compression Cycle Analysis

    A vapor-compression cycle was shown in Figure 8.2, The work required by the refrigeration

    compressor, assuming adiabatic compression, is given by the First Law of Thermodynamics:w = h1 . h2 [Btu/lbm | kJ/kg] (8.1)

    where the usual thermodynamic sign convention has been employed. The enthalpies h1 and h2

    usually are related to the temperatures and pressures of the cycle through the use of charts ofrefrigerant thermodynamic properties such as those given in Appendix F.

    In the ideal vapor compression cycle, the compressor suction state 1 is assumed to be a

    saturated vapor. The state is determined when the evaporator temperature or pressure is given.For the ideal cycle, for which compression is isentropic, and for cycles for which the

    compression is determined using a compressor efficiency, state 2 may be defined from state 1

    and the condensing temperature or pressure by using the chart of refrigerant thermodynamicproperties.

    Assuming no heat exchanger pressure losses, the evaporator and condenser heat transfers are

    easily determined per unit mass of refrigerant by application of the First Law ofThermodynamics:

    qL = h1 . h4 [Btu/lbm | kJ/kg] (8.2)qH = h3 . h2 [Btu/lbm | kJ/kg] (8.3)

    The evaporator heat transferred, qL, is commonly referred to as the refrigeration effect, RE.The product of the refrigerant mass flow rate and RE, the rate of cooling produced by the unit, is

    called the refrigeration capacity [Btu/hr | kW].

    Applying the First Law to the refrigerant in the system as a whole, we find that the work andheat-transfer terms are related by

    qL + qH = w [Btu/lbm | kJ/kg] (8.4)

    where qH and w are negative for both refrigerators and heat pumps. HenceqL + |w| = |qH| [Btu/lbm | kJ/kg] (8.5)

    Equation (8.5) is written here with absolute values to show that the sum of the compressor work

    and the heat from the low-temperature source is the energy transferred by the condenser to thehigh-temperature region.

  • 8/2/2019 Refrigerator Air Conditioner

    38/61

    This may be seen graphically by addition of the enthalpy increments representing Equations (8.1)

    to (8.3) in the pressure-enthalpy diagram shown in Figure 8.8. The p.h diagram is applied oftenin refrigeration work because of its ease of use in dealing with enthalpy differences and constant-

    pressure processes.

  • 8/2/2019 Refrigerator Air Conditioner

    39/61

    For an ideal vapor compression refrigeration system operating with refrigerant 22 at an

    evaporator temperature of 0F and condensing at 100F, find the following: the compressorsuction and discharge pressures, enthalpies, and specific volumes; the condenser discharge

    pressure and enthalpy; the refrigeration COP; and the refrigerant mass flow rate and power

    requirement for a 10-ton refrigeration unit.

    Solution

    Following the notation of Figures 8.2 and 8.8, from the chart (Appendix F) for refrigerant 22

    at T1 = 0F, the other properties at state 1 arep1 = 38 psia, h1 = 104 Btu/lbm, v1 = 1.4 ft3/lbm,and s1 = 0.229 Btu/lbm-R.

    The saturated-liquid condenser discharge properties at T3 = 100F arep3 = 210 psia and h3 =

    39 Btu/lbm.

    The compressor discharge-state properties at s2 = s1 andp2 =p3 = 210 psia are h2 = 123

    Btu/lbm, T2 = 155F, and v2 = 0.31 ft3/lbm.

    The evaporator inlet enthalpy is the same as that at condenser discharge, h4 = h3 = 39

    Btu/lbm.

    The refrigeration effect and the compressor work are then

    RE = h1 . h4 = 104 . 39 = 65 Btu/lbm

    w = h2 . h1 = 123 - 104 = 19 Btu/lbm

    Thus

    COPr = RE /w = 65/19 = 3.42.The rate of cooling, or cooling capacity, for a 10-ton unit is 10200 = 2000 Btu/min. The

    refrigerant mass flow rate is the capacity divided by the refrigeration effect = 2000/65 = 30.8lbm/min.

    The power required by the compressor is the product of the mass flow rate and thecompressor work = 30.819 = 585.2 Btu/min, or 585.260/ 3.413 = 10,290 W, or 10.29 kW.

    The ideal EER may then be calculated from the capacity and power as 200060/10,290 =

    11.7 Btu/Watt-hr, or from the COP as 3.4133.42 = 11.7 Btu/Watt-hr.

  • 8/2/2019 Refrigerator Air Conditioner

    40/61

    Compressors

    While most small- and medium-capacity refrigeration systems use hermetically sealed,

    electricmotor- driven compressor units or open (externally powered) reciprocating compressors,

    centrifugal compressors are frequently found in large units for cooling buildings and for

    industrial applications.

    The reciprocating compressor has much in common geometrically with a simple two-strokereciprocating engine with intake and exhaust valves. As in that case, the compressor clearance

    volume Vc is the volume at top center, and the piston sweeps out the displacement volume, as

    indicated in Figure 8.9. The processes 1-2-3-4-1 on the idealized pressure-volume diagramrepresent the following:

    _ 1.2 Both valves are closed. Compression of the maximum cylinder volume V1 = Vc + Vd

    of refrigerant vapor through the pressure ratiop2/p1 to a volume V2._ 2.3 Exhaust valve is open. Discharge of refrigerant through the exhaust valve at

    condenser pressurep3 until only the clearance volume V3 = Vc remains when the piston isat top center.

    _ 3.4 Both valves are closed. Expansion of the clearance gas with both valves closed fromV3 to V4. Note that the inlet valve cannot open until the cylinder pressure drops to p4 =p1

    without discharging refrigerant back into the evaporator.

    _ 4.1 Intake valve is open. Refrigerant is drawn from the evaporator into the cylinder at

    constant pressurep1 through an intake valve by the motion of piston. Refrigerant in the

    amount V1 . V4 is processed per cycle.

    Assuming polytropic compression and expansion processes with the same exponent k:V4 = V3(p3/p4)1/ k = Vc(p2/p1)1/

  • 8/2/2019 Refrigerator Air Conditioner

    41/61

  • 8/2/2019 Refrigerator Air Conditioner

    42/61

    Then the volume of refrigerant vapor processed per cycle (or per shaft revolution)V1 . V4 = Vd + Vc . Vc (p2/p1)1/ k= Vd . Vc [(p2/p1)1/ k. 1] is less than the displacement volume anddepends on the compressor pressure ratio.

    Neglecting the difference between the refrigerant density leaving the evaporator and that in thecompressor cylinder just before compression, we may write the compressor volumetric

    efficiency as the ratio ofV1 . V4 to the displacement:

    _v = (V1 . V4)/Vd = 1 . (Vc/Vd) [(p2/p1)1/ k. 1]Examination of the compressor processes for different pressure ratios, as in Figure 8.9 (p2 /p1,for example), shows that the refrigerant volume processed per cycle, and thus the volumetric

    298 efficiency, decreases with increasing pressure ratio. It is also evident that the clearance

    volume must be kept small to attain high volumetric efficiency. It is clear that, for a given

    positive displacement compressor, the volumetric efficiency limits the usable pressure ratio and

    thus the difference between the condensing and evaporating temperatures.

    Suction and Subcooling Considerations

    Lets examine two items of concern with respect to some vapor compression systems. In systems

    with reciprocating compressors, there is a danger that, due to changing cooling loads, that theliquid refrigerant in the evaporator may not be completely vaporized, causing slugs of liquid to

    299 enter the compressor.

    Because liquids are essentially incompressible, positive-displacement compressors with fixed

    clearance volumes can be damaged when such "slugging" occurs.

    The use of a thermostatic expansion valve (TEV) that responds to change in the degree ofsuperheat in the suction line provides one solution to this problem. A bulb filled with refrigerant

    attached to the suction line, when heated by superheated vapor, transmits an increasing pressure

    signal to a diaphragm in the TEV, which adjusts the valve flow area and in turn changes the mass

  • 8/2/2019 Refrigerator Air Conditioner

    43/61

  • 8/2/2019 Refrigerator Air Conditioner

    44/61

    flow rate of refrigerant. This control is usually set to maintain a minimum of about five degrees

    of superheat to avoid liquid slugs entering the compressor inlet.

    A second concern is the possibility of entry of vapor into the throttling valve if the refrigerant

    at the condenser exit is not completely condensed. Because vapor occupies much more spacethan liquid, the throttling valve will not function properly if vapor can enter from the condenser.

    One approach to dealing with this is to locate a liquid receiver downstream of the condenser to

    assure the availability of liquid to the expansion device.

    Both of the above concerns may be dealt with simultaneously by the addition of a suction-line

    heat exchanger that superheats the evaporator discharge about five degrees, ensuring that only

    vapor enters the compressor. The heat exchanger that provides suction superheat from state 6 to

    state 1 in Figure 8.12 may be set up to receive heat from the subcooling of the condenserdischarge from state 3 to state 4. This ensures the absence both of vapor entering the throttling

    valve and of liquid slugs entering the compressor. Note that the subcooling also tends to increase

    the refrigeration effect over that of the ideal cycle by decreasing the enthalpy entering the

    Combining Heating and Cooling in a Single System

    It is possible to combine both heating and cooling functions in a single system by providing heatexchangers that can operate as both evaporator and condenser and a control system that can

    reroute the flow of refrigerant when switching functions is required. Figure 8-13 presents a

    302

    schematic diagram for such a system, commonly called a heat pump (context usually determines

    whether the term .heat pump. refers to a device that heats only or that combines heating and

    cooling functions). The key component in a commercial heat pump is a reversing valve. With thevalve shown in the figure, rotation through an angle of 90 reroutes the flow of refrigerant from

    the indoor coil to the outdoor coil, and vice versa. As a result of this change, the indoor coil that

    served as a condenser in the winter becomes an evaporator in the summer. The outdoor coil

    changes accordingly. Separate throttling devices may be used to accommodate differing loadconditions in winter and summer. One-way check valves ensure that refrigerant flow is through

    the appropriate throttling device during each season.

    8.3 Absorption RefrigerationExample 8.3 shows that vapor compression refrigeration requires a significant supply of workfrom an electric motor or other source of mechanical power. Absorption refrigeration is an

    alternate approach to cooling that is largely thermally driven and requires little external work.

    This form of refrigeration is growing in importance as energy conservation considerations

    demand.

  • 8/2/2019 Refrigerator Air Conditioner

    45/61

    closer scrutiny of the disposition of heat rejection from thermal processes. Absorption

    refrigeration provides a constructive means of utilizing waste heat or heat from inexpensivesources at a temperature of a few hundred degrees, as well as directly from fossil fuels. The

    eventual abolition of the use of CFCs may also boost absorption refrigeration technology.

    This system relies on the fact that certain refrigerant vapors may be dissolved in liquids called

    absorbents. For instance, water vapor is a refrigerantthat tends to dissolve in liquid lithium

    bromide, an absorbent. Just as when they condense, vapors release heat when they go intosolution. This heat must be removed from the system in order to maintain a constant temperature.

    Thus, cooling causes vapor to be absorbed in absorbents, just as cooling causes vapor to

    condense. On the other hand, heating tends to drive vapor out of solution just as it turns liquid tovapor. This solution phenomenon and the fact that pumping liquid requires a relatively small

    amount of work compared with that required to compress a gas are the secrets of absorption

    refrigeration.

    Consider the schematic diagram in Figure 8.14, which shows a basic absorption refrigerationunit. The condenser / throttling valve / evaporator subsystem is essentially the same as in the

    vapor compression system diagram of Figure 8.2. The major difference is the replacement of thecompressor with a different form of pressurization system. This system consists primarily of an

    absorberat the pressure of the evaporator, a vapor generatorat the pressure of the condenser,

    and a solution pump. A second throttling valve maintains the pressure difference between theabsorber and the generator.

    The system operates as follows: Refrigerant vapor from the evaporator flows into the

    absorber, where it mixes with the absorbent. The mixture is cooled by heat transfer QA to air orwater at the temperature of the environment, causing the vapor to go into solution. The

    refrigerant-absorbent solution flows to the solution pump where it is pressurized to the pressure

    level of the generator and condenser. Heat from an energy source, QG, then drives the vapor from

    the cold liquid solution.

  • 8/2/2019 Refrigerator Air Conditioner

    46/61

  • 8/2/2019 Refrigerator Air Conditioner

    47/61

    BLOCK DIAGRAM

  • 8/2/2019 Refrigerator Air Conditioner

    48/61

  • 8/2/2019 Refrigerator Air Conditioner

    49/61

    WORKING PROCEDURE

    Refrigeration cycle

    In the refrigeration cycle, aheat pumptransfers heat from a lower-temperatureheat source into a

    higher-temperatureheat sink. Heat would naturally flow in the opposite direction. This is the

    most common type of air conditioning. Arefrigeratorworks in much the same way, as it pumpsthe heat out of the interior and into the room in which it stands.

    This cycle takes advantage of the wayphase changeswork, wherelatent heatis released at a

    constant temperature during aliquid/gasphase change, and where varying thepressureof a pure

    substance also varies itscondensation/boiling point.

    The most common refrigeration cycle uses anelectric motorto drive acompressor. In an

    automobile, the compressor is driven by abeltover apulley, the belt being driven by the engine'scrankshaft(similar to the driving of the pulleys for thealternator,power steering, etc.). Whetherin a car or building, both use electric fan motors for air circulation. Since evaporationoccurs

    when heat is absorbed, and condensation occurs when heat is released, air conditioners use a

    compressor to causepressurechanges between two compartments, and actively condense and

    pump arefrigerantaround. A refrigerant is pumped into theevaporatorcoil, located in thecompartment to be cooled, where the low pressure causes the refrigerant to evaporate into a

    vapor, taking heat with it. At the opposite side of the cycle is thecondenser, which is located

    outside of the cooled compartment, where the refrigerant vapor is compressed and forcedthrough another heat exchange coil, condensing the refrigerant into a liquid, thus rejecting the

    heat previously absorbed from the cooled space.

    By placing the condenser (where the heat is rejected) inside a compartment, and the evaporator

    (which absorbs heat) in the ambient environment (such as outside), or merely running a normal

    air conditioner's refrigerant in the opposite direction, the overall effect is the opposite, and thecompartment is heated. This is usually called aheat pump, and is capable of heating a home to

    comfortable temperatures (25 C; 70 F), even when the outside air is below the freezing point of

    water (0 C; 32 F).

    Cylinder unloaders are a method of load control used mainly in commercial air conditioning

    systems. On a semi-hermetic(or open) compressor, the heads can be fitted with unloaders which

    remove a portion of the load from the compressor so that it can run better when full cooling is

    not needed. Unloaders can be electrical or mechanical.

    ] Humidity

    Air conditioning equipment usually reduces thehumidityof the air processed by the system. Therelatively cold (below thedew point) evaporator coil condenseswater vaporfrom the processed

    air, much as a cold drink will condense water on the outside of a glass. The water is drained,

    removing water vapor from the cooled space and thereby lowering itsrelative humidity.

    http://en.wikipedia.org/wiki/Heat_pumphttp://en.wikipedia.org/wiki/Heat_pumphttp://en.wikipedia.org/wiki/Heat_pumphttp://en.wikipedia.org/wiki/Temperaturehttp://en.wikipedia.org/wiki/Temperaturehttp://en.wikipedia.org/wiki/Temperaturehttp://en.wikipedia.org/wiki/Heat_sinkhttp://en.wikipedia.org/wiki/Heat_sinkhttp://en.wikipedia.org/wiki/Heat_sinkhttp://en.wikipedia.org/wiki/Refrigeratorhttp://en.wikipedia.org/wiki/Refrigeratorhttp://en.wikipedia.org/wiki/Refrigeratorhttp://en.wikipedia.org/wiki/Phase_changehttp://en.wikipedia.org/wiki/Phase_changehttp://en.wikipedia.org/wiki/Phase_changehttp://en.wikipedia.org/wiki/Latent_heathttp://en.wikipedia.org/wiki/Latent_heathttp://en.wikipedia.org/wiki/Latent_heathttp://en.wikipedia.org/wiki/Liquidhttp://en.wikipedia.org/wiki/Liquidhttp://en.wikipedia.org/wiki/Gashttp://en.wikipedia.org/wiki/Gashttp://en.wikipedia.org/wiki/Gashttp://en.wikipedia.org/wiki/Pressurehttp://en.wikipedia.org/wiki/Pressurehttp://en.wikipedia.org/wiki/Pressurehttp://en.wikipedia.org/wiki/Condensationhttp://en.wikipedia.org/wiki/Condensationhttp://en.wikipedia.org/wiki/Boiling_pointhttp://en.wikipedia.org/wiki/Boiling_pointhttp://en.wikipedia.org/wiki/Boiling_pointhttp://en.wikipedia.org/wiki/Electric_motorhttp://en.wikipedia.org/wiki/Electric_motorhttp://en.wikipedia.org/wiki/Electric_motorhttp://en.wikipedia.org/wiki/Gas_compressorhttp://en.wikipedia.org/wiki/Gas_compressorhttp://en.wikipedia.org/wiki/Gas_compressorhttp://en.wikipedia.org/wiki/Belt_%28mechanical%29http://en.wikipedia.org/wiki/Belt_%28mechanical%29http://en.wikipedia.org/wiki/Belt_%28mechanical%29http://en.wikipedia.org/wiki/Pulleyhttp://en.wikipedia.org/wiki/Pulleyhttp://en.wikipedia.org/wiki/Pulleyhttp://en.wikipedia.org/wiki/Crankshafthttp://en.wikipedia.org/wiki/Crankshafthttp://en.wikipedia.org/wiki/Alternatorhttp://en.wikipedia.org/wiki/Alternatorhttp://en.wikipedia.org/wiki/Alternatorhttp://en.wikipedia.org/wiki/Power_steeringhttp://en.wikipedia.org/wiki/Power_steeringhttp://en.wikipedia.org/wiki/Power_steeringhttp://en.wikipedia.org/wiki/Evaporationhttp://en.wikipedia.org/wiki/Evaporationhttp://en.wikipedia.org/wiki/Evaporationhttp://en.wikipedia.org/wiki/Pressurehttp://en.wikipedia.org/wiki/Pressurehttp://en.wikipedia.org/wiki/Pressurehttp://en.wikipedia.org/wiki/Refrigeranthttp://en.wikipedia.org/wiki/Refrigeranthttp://en.wikipedia.org/wiki/Refrigeranthttp://en.wikipedia.org/wiki/Evaporatorhttp://en.wikipedia.org/wiki/Evaporatorhttp://en.wikipedia.org/wiki/Evaporatorhttp://en.wikipedia.org/wiki/Heat_exchanger#HVAC_air_coilshttp://en.wikipedia.org/wiki/Heat_exchanger#HVAC_air_coilshttp://en.wikipedia.org/wiki/Heat_exchanger#HVAC_air_coilshttp://en.wikipedia.org/wiki/Heat_pumphttp://en.wikipedia.org/wiki/Heat_pumphttp://en.wikipedia.org/wiki/Heat_pumphttp://en.wikipedia.org/wiki/Hermetic_sealhttp://en.wikipedia.org/wiki/Hermetic_sealhttp://en.wikipedia.org/wiki/Hermetic_sealhttp://en.wikipedia.org/wiki/Humidityhttp://en.wikipedia.org/wiki/Humidityhttp://en.wikipedia.org/wiki/Humidityhttp://en.wikipedia.org/wiki/Dew_pointhttp://en.wikipedia.org/wiki/Dew_pointhttp://en.wikipedia.org/wiki/Dew_pointhttp://en.wikipedia.org/wiki/Water_vaporhttp://en.wikipedia.org/wiki/Water_vaporhttp://en.wikipedia.org/wiki/Water_vaporhttp://en.wikipedia.org/wiki/Relative_humidityhttp://en.wikipedia.org/wiki/Relative_humidityhttp://en.wikipedia.org/wiki/Relative_humidityhttp://en.wikipedia.org/wiki/Relative_humidityhttp://en.wikipedia.org/wiki/Water_vaporhttp://en.wikipedia.org/wiki/Dew_pointhttp://en.wikipedia.org/wiki/Humidityhttp://en.wikipedia.org/wiki/Hermetic_sealhttp://en.wikipedia.org/wiki/Heat_pumphttp://en.wikipedia.org/wiki/Heat_exchanger#HVAC_air_coilshttp://en.wikipedia.org/wiki/Evaporatorhttp://en.wikipedia.org/wiki/Refrigeranthttp://en.wikipedia.org/wiki/Pressurehttp://en.wikipedia.org/wiki/Evaporationhttp://en.wikipedia.org/wiki/Power_steeringhttp://en.wikipedia.org/wiki/Alternatorhttp://en.wikipedia.org/wiki/Crankshafthttp://en.wikipedia.org/wiki/Pulleyhttp://en.wikipedia.org/wiki/Belt_%28mechanical%29http://en.wikipedia.org/wiki/Gas_compressorhttp://en.wikipedia.org/wiki/Electric_motorhttp://en.wikipedia.org/wiki/Boiling_pointhttp://en.wikipedia.org/wiki/Condensationhttp://en.wikipedia.org/wiki/Pressurehttp://en.wikipedia.org/wiki/Gashttp://en.wikipedia.org/wiki/Liquidhttp://en.wikipedia.org/wiki/Latent_heathttp://en.wikipedia.org/wiki/Phase_changehttp://en.wikipedia.org/wiki/Refrigeratorhttp://en.wikipedia.org/wiki/Heat_sinkhttp://en.wikipedia.org/wiki/Temperaturehttp://en.wikipedia.org/wiki/Heat_pump
  • 8/2/2019 Refrigerator Air Conditioner

    50/61

    Some air conditioning units dry the air without cooling it. These work like a normal air

    conditioner, except that aheat exchangeris placed between the intake and exhaust. Incombination withconvectionfans, they achieve a similar level of coolness as anair coolerin

    humidtropical climates, but only consume about one-third the energy.

    http://en.wikipedia.org/wiki/Heat_exchangerhttp://en.wikipedia.org/wiki/Heat_exchangerhttp://en.wikipedia.org/wiki/Heat_exchangerhttp://en.wikipedia.org/wiki/Convectionhttp://en.wikipedia.org/wiki/Convectionhttp://en.wikipedia.org/wiki/Fan_%28mechanical%29http://en.wikipedia.org/wiki/Fan_%28mechanical%29http://en.wikipedia.org/wiki/Fan_%28mechanical%29http://en.wikipedia.org/wiki/Air_coolerhttp://en.wikipedia.org/wiki/Air_coolerhttp://en.wikipedia.org/wiki/Air_coolerhttp://en.wikipedia.org/wiki/Tropical_climatehttp://en.wikipedia.org/wiki/Tropical_climatehttp://en.wikipedia.org/wiki/Tropical_climatehttp://en.wikipedia.org/wiki/Tropical_climatehttp://en.wikipedia.org/wiki/Air_coolerhttp://en.wikipedia.org/wiki/Fan_%28mechanical%29http://en.wikipedia.org/wiki/Convectionhttp://en.wikipedia.org/wiki/Heat_exchanger
  • 8/2/2019 Refrigerator Air Conditioner

    51/61

  • 8/2/2019 Refrigerator Air Conditioner

    52/61

    ADVANTAGES

  • 8/2/2019 Refrigerator Air Conditioner

    53/61

  • 8/2/2019 Refrigerator Air Conditioner

    54/61

  • 8/2/2019 Refrigerator Air Conditioner

    55/61

  • 8/2/2019 Refrigerator Air Conditioner

    56/61

  • 8/2/2019 Refrigerator Air Conditioner

    57/61

  • 8/2/2019 Refrigerator Air Conditioner

    58/61

  • 8/2/2019 Refrigerator Air Conditioner

    59/61

  • 8/2/2019 Refrigerator Air Conditioner

    60/61

    BIBLIOGRAPHY

    REFERENCESAmerican Society Heating Refrigeration and Air Conditioning.ASHRAE Hand Book. 2001

    Arora, C.P.Refrigeration and Air Conditioning. Second edition. Tata McGraw-Hill

    Publishing Company Ltd. 2000.Bureau of Energy Efficiency, Ministry of Power, India.HVAC and Refrigeration Systems. In:

    Energy Efficiency in Electrical Utilities, chapter 4. 2004Compare India. www.compareindia.com

    Munters. Pre-Cooling of Gas TurbinesEvaporative Cooling. 2001.

    www.munters.com/home.nsf/FS1?ReadForm&content=/products.nsf/ByKey/OHAA-

    55GSWHNational Productivity Council, Ministry of Industries, India. Technology Menu on Energy

    Efficiency.

    Plant Services Magazine. www.plantservices.com

    US Department of Energy, Energy Efficiency and Renewable Energy.

    www.eere.energy.gov

  • 8/2/2019 Refrigerator Air Conditioner

    61/61