16
reflex ’servitec 30’ Vacuum spray degassing unit Assembly, operation and maintenance manual dated 09/11

reflex ’servitec 30’ Vacuum spray degassing unit Assembly ...reflexch.ch/fileadmin/user_upload/pdf_en/SI1129en_9119398_servitec... · reflex ’servitec 30’ Vacuum spray degassing

  • Upload
    lynhi

  • View
    226

  • Download
    1

Embed Size (px)

Citation preview

Page 1: reflex ’servitec 30’ Vacuum spray degassing unit Assembly ...reflexch.ch/fileadmin/user_upload/pdf_en/SI1129en_9119398_servitec... · reflex ’servitec 30’ Vacuum spray degassing

reflex ’servitec 30’Vacuum spray degassing unit

Assembly, operation and maintenance manualdated 09/11

Page 2: reflex ’servitec 30’ Vacuum spray degassing unit Assembly ...reflexch.ch/fileadmin/user_upload/pdf_en/SI1129en_9119398_servitec... · reflex ’servitec 30’ Vacuum spray degassing

’servitec 30’ is a degassing and make-up station for heating and cooling systems that mainly consists of a control unit and a special pump.

Assembly and operationAssembly and operation are performed according to national regulations; in Germany this is the Ordinance on Industrial Health and Safety (Betriebssicherheitsverordnung). In keeping with this, assembly and operation must be performed according to the state of the art by qualified personnel and specially trained staff. Important: ’servitec 30’ is designed for stationary, not for mobile system opera-tion. The set warranty periods are only valid if a maximum of 10,000 degassing intervals per year are observed.

Adherence to parametersDetails concerning the manufacturer, year of manufacture, and serial number as well as technical data are provided on the name plate. Suitable temperature and pressure protection measures must be implemented in the supply system to ensure adherence to the specified permissible maximum and minimum operating parameters. This system may only be used in systems with nontoxic waters.

Thermal protectionCare must be exercised when working on a hot system. There is a risk of scalding from water escaping at the screw connections, the bleed screw for the pump, and the dipstick-tube degassing unit in particular. A risk of injury due to high tempera-tures arises especially from touching the pump casing.

Electrical connectionElectrical wiring and connection must be performed by a qualified electrician according to the applicable local regulations (electricity board, VDE and EN). The system must be de-energized before any work is carried out on electrical compo-nents.

Failure to keep to these instructions, in particular the safety instructions, may result in the destruction of and defects in the ’servitec 30’, personal injury and impaired operation. Any and all claims for warranty or liability are excluded if these regulations are violated.

Note: Please check that the delivery is complete and undamaged immediately upon receipt of goods. Transport damage must be reported immediately.The scope of delivery is described on the delivery slip and the contents are indicated on the cardboard box. 1 cardboard box with - ’servitec 30’ (preassembled) - casing (upper and lower part) - dipstick-tube degassing unit (preassembled) - screw connections (preassembled) - assembly, operation and maintenance manual

Possible accessories:1 cardboard box - ’fillset’ with water meter (enclosed in the cardboard box) - ’fillset compact’ without water meter (enclosed in the cardboard box)

General Safety Instructions

Scope of delivery

Table of contents

General informationGeneral safety instructions 2Scope of delivery 2Overview 3Control panel 3Technical data 4

AssemblyAssembly 5Electrical connection 6Terminal diagram 6

Initial start-UpRequirements for start-Up 7Initial start-up Start-up steps 7System-specific parameter 8 - 11Setting in customer menuCleaning the dirt traps 11

OperationMode of operation 12Automatic mode 13Manual mode 13Stop mode 13Customer menu 14Password-protected standard 14Settings in the service menuMessages 14 - 15

Maintenance, disassemblyMaintenance instructions 15Disassembly 15

Reflex service 16

Declaration of conformity 16

reflex ’servitec 30’General information

Page 3: reflex ’servitec 30’ Vacuum spray degassing unit Assembly ...reflexch.ch/fileadmin/user_upload/pdf_en/SI1129en_9119398_servitec... · reflex ’servitec 30’ Vacuum spray degassing

3

In automatic, manual and stop modes, Display of current system pressureflashes if there is a problem with the pressureIn the customer menuDescription of ParametersProgram selection- ’magcontrol’- ’levelcontrol’

Info displayDisplay of messagesDisplay of parameter values

Overview

from thesystem

Selected operating mode (here: auto)

Degassing programs (p. 13)

If “info” appears, there is a messageExternal 230 V signal presentMotorized ball valve make-upPump

to the system

1 EPP casing 2 3-way motorized ball valve 3 Dirt trap 4 Control box IP 54 5 Dipstick-tube degassing unit 6 Pump 7 Nozzle connection (internal) 8 Pressure transducer 9 Assembly holes

1

23

4

5

6

7

8

O

9

WM

P

Note: In the assembly, operation and maintenance manual,this symbol stands for “press button”

Manual mode (p. 9)

Stop mode (p. 9)System out of operation

Automatic mode (p. 9)

Calling up customer menu (p. 10)

In the customer menu,end parameter input,exit the customer menu

In auto, manual, stop modesacknowledge messages (e.g. “ER 06 make-up time exceeded”)

Scroll through the customer menu,change parameter

Select parameter,confirm input

Operating mode buttons

Control Panel

Control Buttons

Symbols

reflex ’servitec 30’ General Information

2

1

3

Page 4: reflex ’servitec 30’ Vacuum spray degassing unit Assembly ...reflexch.ch/fileadmin/user_upload/pdf_en/SI1129en_9119398_servitec... · reflex ’servitec 30’ Vacuum spray degassing

4

Persuasive: Degassing, Make-Up, Pressure Monitoring

Degassing: - No circulation problems from bubbles in the circuit water - Reduced corrosion risk

Make-up: - The make-up volume is calculated and monitored

electronically. If the set make-up time or number of cycles per hour is exceeded, a message is trig-gered and the make-up is interrupted.

SafeControl: - Controlled make-up using reliable 3-way motor-

ized ball valve. This is controlled via an integrated system pressure evaluation or an external 230 V signal (e.g. from a pressure-maintaining station)

Monitor pressure: - Permanent pressure indicator on display - No direct drawing in of air, thanks to monitored pressure maintenance

Technical data

Item no. : 6830720Perm. excess operating pressure : 8 barPerm. operating temperature : System degassing 70 °C Make-up 30 °COperating pressure : 0.5 - 3.0 barMax. system volume : 8 m³Make-up output : 0.05 m³/hMax. intake pressure in theMake-up

: 6 bar:

Heating connection : DN 15Potable water connection : DN 15Width x depth x height : 255 x 280 x 650 mmWeight : 13 kgElectrical connection : 230 V, 50 Hz, 470 W

Shock-proof plug with 2 m cableEnergy consumption Ø per day : 0.04 kWhFloating output (changeover switch) for common message

: 230 V, 4 A

reflex ’servitec 30’General information

Fresh water

to the system

from thesystem

reflex ’servitec 30’ pressure detection

If the system filling or initial pressure are ex-ceeded, the internal switch signal from the pressure transducer PIS causes a make-up.The pressure history in the pump is also moni-tored via this signal.

2

4

3

5

6

8

Floatingoutput

Page 5: reflex ’servitec 30’ Vacuum spray degassing unit Assembly ...reflexch.ch/fileadmin/user_upload/pdf_en/SI1129en_9119398_servitec... · reflex ’servitec 30’ Vacuum spray degassing

5

Assembly

’servitec 30’ is to be mounted on the wall level to the holes provided.

The system and potable water system are to be shut off on site.

Important: Integration into the pipelines (see close-up of integration point) must take place from above or to the side in such a way as to prevent coarse dirt from entering the ’servitec’.

reflex ’servitec 30’ Assembly

’servitec 30 - Detailed View

Potable water make-up

Potable water make-up

reflex ’servitec 30’ in ’magcontrol’ modefor systems with expansion vessels

reflex ’servitec 30’ in the ’levelcontrol’ mode for systems with pump or compressor-controlled pressure-maintaining stations

500

Main current V circuit water

500

Main current V circuit water

Rich in gas

Low in gas

Rich in gas

Low in gas

From above

From below as an immersion tube

Butt-welded from the bottom not permitted

50

0

Rich in gas

Low in gas

At the side(horizontal and vertical assembly possible)

Mai

n cu

rren

t V

circ

uit w

ater

Close-up of integration point

Page 6: reflex ’servitec 30’ Vacuum spray degassing unit Assembly ...reflexch.ch/fileadmin/user_upload/pdf_en/SI1129en_9119398_servitec... · reflex ’servitec 30’ Vacuum spray degassing

6

Terminal diagram

Electrical connection

Connect the on-site cable in the control box (6):

– Remove 2 cross-head screws from the lower control box cover– Open the cover– Pass all cables to be installed through the PG fitting

Important: Only use PG screw connections suitable for the respective cable.– Connect all cables (also see the following terminal diagram)

Important:Despite removing the mains plug, 230 V may still be present at terminal 10, 11 12, 13 and 14, and at parts of the circuit board.

FuseElectronics

FuseMotor

reflex ’servitec 30’ Assembly

Designation Terminal Signal NoteSupply 1 PE(230 V) 2 N ’servitec’ is fully wired with a shock-proof plug

3 LMake-up motorized ball valve

4 Y15 N connected6 PE

Pump 7 M18 N connected9 PE

External make-up control

10 only for ’servitec levelcontrol’ mode 230 V wire on site11

Common message 12 NC(fl oating) 13 COM wire on site (optional)

14 NONot confi gured 15 +24 V DC not wired up16 E1Water shortage 17 +24 V DC not connected (jumper)switch 18 E1Pressure measure-ment transducer

19 +18 V connected20 AE

The power supply is wired as plug-ready. Only one 230 V socket for a shock-proof plug need be supplied on site. Electric wiring and connection of the floating common message contact by qualified electrician according to the applicable local regulations (electricity board) and VDE guidelines.

The terminal diagram (→ p. 6) must be observed.

The power supply plug must be disconnected or the system de-energized before any work is carried out on electrical components.

Page 7: reflex ’servitec 30’ Vacuum spray degassing unit Assembly ...reflexch.ch/fileadmin/user_upload/pdf_en/SI1129en_9119398_servitec... · reflex ’servitec 30’ Vacuum spray degassing

7

Requirements for initial start-up

Initial start-up

– Installation of ’servitec 30’ is complete.– The water connection to the system has been established.– The system has been connected to the electrical mains system according to the applicable VDE and local

electricity board regulations.– The pipeline to ’servitec 30’ muss be cleaned, and cleared of dirt and welding residues.– At a make-up pressure > 6 bar, a pressure reducing valve must be installed on site.

Making the water connectionBefore the controller can be parametrized, the on-site shut-offs on the input and output sides must be opened.

System-specific parameter settingThe controller has two operating levels; the password-protected service menu (see p. 14) and the customer menu (→ p. 8). During initial start-up, the factory settings must be adapted to the system-specific conditions.

Start-up steps

reflex ’servitec 30’ Initial start-up

Page 8: reflex ’servitec 30’ Vacuum spray degassing unit Assembly ...reflexch.ch/fileadmin/user_upload/pdf_en/SI1129en_9119398_servitec... · reflex ’servitec 30’ Vacuum spray degassing

8

reflex ’servitec 30’ Initial start-up

Time

Start by setting the current hour (here: 09) with the arrow buttons and confirm with “ok”. Continue by setting the minutes (here: 05) and seconds (here: 35).

Selectparameter

Confirmparameter

Exitthe menu

Selectparameter

(flashing value)

ok ok quit

Change menu item

Now press to go to the customer menu:menu

After the supply voltage has been established (shock-proof plug), the current system pressure appears on the display. The operating mode is active.stop

System-specific parameter setting in customer menu

Min. operating pressure Message appears in ’magcontrol’ operating mode only.

Here, set the minimum operating pressure according to the static height of your system (also see diagram) and confirm with “ok”.This value must be identical to the pre-set pressure p0 of the expansion vessel.1.0 bar = factory setting on the controller

ok

ok

* Message if pressure is exceeded or is not reached** p0 must correspond to the pre-set gas pressure of the

expansion vessel

*

pSV [bar] = Safety valve response pressure at the heat generator

pmax [bar]0.5 bar

pe [bar] = Final pressure of the expansion vessel 0.3 bar

pa [bar] = Make-up if pressure not reachedpa [bar] = Initial pressure or filling pressure pF of the expansion vessel 0.2 bar

Solenoid valve CLOSEDCompressor OFF

p0** [bar] = pstatic + pevaporation + 0.2 bar (recommendation) 0.3 bar

0...0.2 barpst [bar] = Static pressure (= static height / 10 m)

*

System type

The display shows the ’servitec’ type selected; ’servitec magcontrol’ or ’servitec levelcontrol’. The system type can be specified here (→ p. 5).

ok

ok

Page 9: reflex ’servitec 30’ Vacuum spray degassing unit Assembly ...reflexch.ch/fileadmin/user_upload/pdf_en/SI1129en_9119398_servitec... · reflex ’servitec 30’ Vacuum spray degassing

reflex ’servitec 30’ Initial start-up

Degassing program

Select the degassing program(→ p. 13) and confirm with the “ok” button.

ok ok

Make-up pressure

Select the make-up pressure hereand confirm with the “ok” button.0 = Make-up pressure > system pressure (standard)1 = Make-up pressure < system pressure

ok ok

Degassing time

Select here the time for continuous degassing (see p. 13). Confirm with “ok”.

5 h = factory setting

ok

ok

Vacuum test

This menu item operated the vacuum test for the spray-tube. It is mandatory to perform a vacuum test during initial start-up and maintenance.Perform the vacuum test as follows:- Spray-tube must be filled with water (system pressure)- Close the intake-side shut-off (on site) to the spray-tube- Perform vacuum test (select “1” and confirm with “ok”)The behavior of the pressure is monitored and evaluated in two time intervals (countdown to 0 s). This test takes 2 min.

If it is successful, “UP ok” appears on the display. If this happens, continue with:

If the test was unsuccessful, “UP not ok” appears. Rectify the error (see p. 14, Messages) and perform the vacuum test again until it is successful.

ok

ok

ok

Safety valve response pressure

Set the safety valve response pressure of the heat generator and confirm with “ok”.

3.0 bar = factory setting

ok

ok

9

Page 10: reflex ’servitec 30’ Vacuum spray degassing unit Assembly ...reflexch.ch/fileadmin/user_upload/pdf_en/SI1129en_9119398_servitec... · reflex ’servitec 30’ Vacuum spray degassing

10

reflex ’servitec 30’ Initial start-up

Make-up

Display of the total make-up volume used in liters. This value is calculated within the controller and can be reset to 0 (CnC = 1).

Here: 252 liters

ok

ok

Water meterConfigure the setting here for whether a water meter is to be evaluated, e.g. when using reflex ’fillset’ with contact water meter.

0 = Value is calculated mathematically1 = With evaluation of contact water meter ( appears on display)

ok

ok

Maintenance intervalThe setting is configured here for when the message “SrV” (maintenance interval expired) is triggered. The timer counts backwards, i.e. when displaying 10 months the next mainte-nance will be due in 10 months’ time. Maintenance monitoring can be switched off.012 months = Factory setting

ok

ok

Max. make-up volume

A max. make-up volume can be set here. If this is exceeded, message Er 20 is triggered.

1,000 liters = Factory setting

ok ok

Floating signal contact

Here you can select whether all faults that occur should switch the floating contact (pfK).

0 Only alarms (see p. 14) = Factory setting1 All messages

ok

ok

Page 11: reflex ’servitec 30’ Vacuum spray degassing unit Assembly ...reflexch.ch/fileadmin/user_upload/pdf_en/SI1129en_9119398_servitec... · reflex ’servitec 30’ Vacuum spray degassing

11

Cleaning the dirt traps

The dirt traps (3) in the fresh water intake and in front of the nozzle entry must be cleaned. In the event of problems, see the chapter on “Maintenance”, p. 15.

Initial start-up is now completed.

reflex ’servitec 30’ Initial start-up

ok

Software version

Display of the software version.

Software version 1:26ok ok

auto

manual

stop

You have run through the entire customer menu once. You can now switch to the desired operating mode (see p. 13). or

or

Error memory

The last 20 errors including error code (e.g. ER01, → p. 14) are shown here as well as the relevant operating hours until the mes-sage occurs. E01 is the most recent error, E20 is the oldest.

ok

quit

Page 12: reflex ’servitec 30’ Vacuum spray degassing unit Assembly ...reflexch.ch/fileadmin/user_upload/pdf_en/SI1129en_9119398_servitec... · reflex ’servitec 30’ Vacuum spray degassing

12

Mode of operation

General description’servitec 30’ is a degassing and make-up station. It can be used in a wide range of system conditions. The main field of application is heating and cooling circuits and wherever air problems in the form of dissolved or free gases cause problems in systems.The ’servitec’ vacuum spray-tube degassing system removes up to 90 % of the dissolved gases from the system water. Vacuum degassing of a part flow of the circuit water takes place accord-ing to an optimized schedule using selectable degassing programs (→ p. 13).A part flow of the circuit water is sprayed through the nozzle (7). The vac-uum is created by the pump (6). The large surface area of the sprayed water and the intense vacuum result in the extremely high degassing per-formance. The degassed water is returned to the system. There the water is again able to dissolve gases. The gases separated in the pump (6) are expelled using the dipstick-tube degassing unit (5). This degassing inter-val is repeated and free as well as dissolved gases are removed from the circuit water.

Degassing intervalThe degassing interval is a time-controlled, pre-programmed process that consists of the degassing time, expulsion time, and idle time. The time periods can only be changed in the service menu by Reflex Service.The degassing intervals are repeated according to the continuous degassing mode (standard = 5 h a day) or interval degassing mode(standard = 16 x a day).

Injection timeThe pump (6) starts. A vacuum (dependent on temperature) can be read off the display (→ p. 3) after a short time. This is possible because the pump (6) draws more water from the pump casing than is able to flow in via the pressure supply port with nozzle (7). Spraying via the nozzle commences as soon as the vacuum begins to be established.The water level in the pump casing (6) drops continuously while the pump (6) is running. The timing program and pressure setting have been selected so that the pump does not become low in water.

Expulsion timeThe pump (6) switches off. The water continues to be sprayed into the pump casing by the system pressure (at least 0.5 bar). The water column in the pump casing rises gradually during the expulsion time. The vacuum is still maintained during this phase of the interval. At the end of the expulsion phase, the rising water column compresses the removed gas within a few seconds, expelling it into the atmosphere via the dipstick-tube degassing unit (5).

Idle timeThis is followed by the idle time during which redegassing takes place.

Make-upIn the case of the ’servitec 30’, the pressure in the heating or cooling system is registered and monitored with the help of the pressure transducer (8). If the fill pressure drops below pF = p0 + 0.2 bar, make-up degassing is activated until pF = p0 + 0.3 bar has been reached. Time (20 min default setting), cycle (3 in 2 hours) and volume monitoring are active during this process.The motorized ball valve (2) opens during make-up. During pump operation, a pressure of approx. - 0.6 bar is set in the pump casing (pressure indicator display). In the event of a cyclical pump stop, the system pressure is checked and made up if necessary.

reflex ’servitec 30’ Operation

5

2

6

8

7

Page 13: reflex ’servitec 30’ Vacuum spray degassing unit Assembly ...reflexch.ch/fileadmin/user_upload/pdf_en/SI1129en_9119398_servitec... · reflex ’servitec 30’ Vacuum spray degassing

13

Automatic mode

Automatic mode may only be activated after initial start-up has been successfully completed. If you are in automatic mode, you can select from three degassing programs, if required. System monitoring is active with all three programs. Make-up takes place automatically. Selection in customer menu (→ p. 9) Continuous degassing – Intensive degassing following start-up and

repairs The degassing cycles are executed successively for the set

continuous degassing time (basic setting: 5 h). The controller then automatically proceeds with interval degassing. In the case of water systems, at least half the system volume should flow through the ’servitec’ unit once during start-up. Based on a system volume of 8 m3, this is equivalent to approx. 22 h of continuous degassing. In systems that are particularly rich in gas, a continuous degassing period of 48 h is completely sufficient. As a result of the subsequent interval degassing, 10,000 intervals are made per year. This number per year must not be exceeded in order to avoid unnecessary wear to the ’servitec’. The controller registers the total number of intervals that have passed.

Interval degassing – Economy mode in automatic mode After 8 intervals (standard), a break (standard 23 h) is observed

before the next 8 degassing intervals are started. This program is automatically started upon completion of continuous degassing or can be selected manually for systems already degassed. Interval degassing then starts at 08:00 each day.

No degassing – Only make-up The system water is not degassed. This operating mode is practical

during summer operation or if general degassing of the system water is not required.

auto

Stop mode

In stop mode, ’servitec 30’ is without function except for indica-tion in the LCD display. Operation monitoring does not take place. The pump is shut off. The adjacent display appears when the “stop” button is pressed.

stop

Automatic mode display with con-tinuous degassing

Automatic mode display with interval degassing

Automatic mode display with no degassingonly make-up

reflex ’servitec 30’ Operation

Manual mode

Manual mode may only be be used after the initial start-up has been completed. This operating mode is primarily a means of performing functional checks of the pump and the make-up solenoid valve.

Select the pump or motorized ball valve, activate the flashing symbol with the “ok” button

Pump starts/motorized ball valve opens

Pressing the “ok” button again stops the pump or closes the motorized ball valve. Alternatively, the “quit” button can also be pressed directly. The pump and motorized ball valve then switch off after each other.

manual

okok

Page 14: reflex ’servitec 30’ Vacuum spray degassing unit Assembly ...reflexch.ch/fileadmin/user_upload/pdf_en/SI1129en_9119398_servitec... · reflex ’servitec 30’ Vacuum spray degassing

14

menuCustomer menu

The purpose of the customer menu is to enter and change the key ’servitec’ operating param-eters. These are adapted during initial start-up (see p. 7). Press the “menu” button to access the customer menu. Here you can change operating parameters or view current statuses. Press to exit the customer menu.

Messages

Messages are indicated on the display by the “info” symbol. At the same time, “Er” and the relevant error code (e.g. Er 06) are shown on the info display. If there are several messages present, these may be displayed using the symbols.Most of the messages are automatically acknowledged once the cause has been remedied (see table). Errors such as “Make-up time 06” or “Make-up cycle 07” must be acknowledged manually. For remote transmission, it is possible to use the floating changeover switch for the common message. In the customer menu (→ p. 10), you can select whether only those messages characterized as alarms or all messages should be output using the floating contact.

quit

Password-protected standardsettings in the service menu

Parameters and switching hysteresis based on empirical values collected during research and operation have been preset in the data memory of the ’servitec 30’. The most important, password-protected settings are described in the following table.

Parameter Setting Comment Pressure Make-up ON p0 + 0.2 bar p0 (minimum operating pressure→ p. 8) make-up OFF p0 + 0.3 bar Minimum operating pressure not attained = p0 Maximum operating pressure exceeded pSV – 0.2 bar pSV (response pressure of the SV (→ p. 8) Make-up Max. make-up time 20 min If the make-up time or number of cycles is exceeded, Max. make-up cycles in 2 h 3 the corresponding message is triggered. Degassing interval Injection time 10 s / 8 s* Pump is running, spraying taking place at same time Max. expulsion time 120 s Expulsion phase: pump off, spraying, and gas expulsion

quit

reflex ’servitec 30’ Operation

* 3 bar version

ER-Code

Type of error Cause of error TroubleshootingFault elimination

01 Min. pressure p0not attained (alarm)

– Water loss in the system– Pressure maintenance facility incorrectly set or defective

– Fix leak– Check pre-set pressure p0, reset if necessary

02.1Dry-running protection pressure too low (alarm)

– No water in the pump, pressure < 0.1 bar– Dirt trap is dirty– Shut-off closed on inlet side

– Open shut-off– Clean dirt traps– Open shut-off

02.2 Dry-running protection faulty pressurebehavior during the degassing process (Alarm)

– Vacuum not created quickly enough– ’servitec’ was temporarily operated at temperatures over 70 °C– Vacuum is not low enoughAccumulation of gas in the pump

Pumpe is stuck

Dipstick-tube degassing draws air

– Acknowledge message, activate automatic operation– Check the ’servitec’ integration point

– Start pump in manual mode (see p. 13) Check screw connections on the pump suction side, reseal if necessary, perform vacuum testTurn on pump, perform vacuum testCheck dipstick-tube degassing, clean if necessary, perform vacuum test

02.3Dry-running protection Time exceeded (alarm)

– Break tank (optional) is empty– Low water cut-off switch not wired– Clamp 17/18 jumper is missing

– Check supply (shut-off opened?)– Connect low water cut-off switch

02.4Dry-running protectionMake-up process (alarm)

– During make-up, a vacuum that is too low is created in the spray-tube– Make-up motorized ball valve does not open

– Check function of motorized ball valve and clean if necessary (see p. 13), acknowledge message

06Make-up timeexceeded (standard 20 min)

– Minor leaks in the system– Integration line from ’servitec’ to system is too long or too short

– Eliminate leaks, acknowledge message– Increase make-up time, possibly consult Reflex Service

Page 15: reflex ’servitec 30’ Vacuum spray degassing unit Assembly ...reflexch.ch/fileadmin/user_upload/pdf_en/SI1129en_9119398_servitec... · reflex ’servitec 30’ Vacuum spray degassing

15

Maintenance instructions

Maintenance work should only be carried out by specialists. As a reminder of the annual maintenance, the mes-sage “SrV” is shown in the display after a year of operation. This can be acknowledged with the “quit” button.Leak test– Check for external leaks– Seal, if requiredClean dirt trap– Clean the “blue ball valve” of the dirt trap (3)Perform vacuum test– p. 9Function test of pump, motorized ball valve– p. 13

Disassembly

Prior to disassembly of the ’servitec 30’ system or pressurized parts, these must be depressurized on the fresh water and system sides.1. On-site valves must be shut off to ’servitec 30’2. Run the controller in “manual mode” (→ p. 13) and open motorized ball valve (2) until pressure equalization with the atmosphere is achieved.

reflex ’servitec 30’ Operation, maintenance, disassembly

It is often of great use to know the sequence for assessing a mes-sage or understanding the cause. The information in the error memory can aid this (→ a. customer menu).

Scroll to the error memory display

This displays the last 20 errors with information from the error code (e.g. ER01) as well as the corresponding operating hour to the time that the message occurred. Error sequence E01 is the most recent error; E20 is the oldest error.

If the error memory is called up the most recent error (01) is shown

To scroll through the error memory use:

To quite the error memory use:

Error symbol Error sequence

Elapsed hours counter

ok

ok ok

menu

ER-Code

Type of error Cause of error TroubleshootingFault elimination

07Make-up cyclesexceeded(standard 3 in 2 h)

– Minor leaks in the system– Integration line from ’servitec’ to system is too long or too short

– Eliminate leaks, acknowledge message– Check integration line and lengthen or shorten if necessary

08 Pressure measurementFault

– Pressure transducer incorrectly connected or is defective

– Check wiring and replace if necessary

10Max. pressure exceeded

– Expansion vessel in the system has incorrect pre-set pressure– Safety valve response pressure PS in customer menu set too low

– Check expansion vessel pre-set pressure– Adjust PS setting with SV response pressure of system

14 Expulsion time exceeded

– Shut-off closed on input side– Dirt trap is dirty

– Open shut-off– Clean dirt traps– Acknowledge message

19Stop > 4 h – The controller is in stop mode for more

than 4 h – Activate automatic operation or acknowledge message if necessary

20Max. make-up volume Cn exceeded

– The max. make-up volume set in the customer menu under Cn was exceeded

– Acknowledge message

SrV Maintenance interval LGhas passed

– Reminder of the annual maintenance – Perform maintenance– Acknowledge message

Page 16: reflex ’servitec 30’ Vacuum spray degassing unit Assembly ...reflexch.ch/fileadmin/user_upload/pdf_en/SI1129en_9119398_servitec... · reflex ’servitec 30’ Vacuum spray degassing

SI1

129e

n / 0

9 - 1

1A

rt. N

o. 9

1193

98R

ight

of t

echn

ical

mod

ifica

tion

rese

rved Reflex Winkelmann GmbH

Gersteinstrasse 1959227 Ahlen, Germany

Tel.: +49 2382 7069-0Fax: +49 2382 7069-588www.reflex.de

Central Factory Service

Regional Service

Extension+49 2382 7069-...

Fax E-mail

Volker Lysk - 512 - 523 [email protected]

Please contact our central office in Ahlen to inquire about your regional service.

Declaration of Conformity for the electronic controller for the pressurization, make-up and degassing systems of reflex ’control P’, reflex ’magcontrol’, and ’servitec 30’1. This is to certify that the products conform to the essential protection requirements set forth in the Council Directives

on the harmonization of the laws of the Member States relating to electromagnetic compatibility (2004/108/EC). The following standards were used to evaluate the products: DIN EN 61326-1:2006-10

Hersteller:Manufacturer:

Reflex Winkelmann GmbHGersteinstrasse 1959227 Ahlen, GermanyTel.: +49 2382 7069-0Fax: +49 2382 7069-588E-mail: [email protected]

Der Hersteller erklärt, daß die Baugruppe die Anforderungen der Richtlinie 97/23/EG erfüllt. The manufacturer herewith certifies that this assembly is in conformity with Directive 97/23/EC.

Manfred Nussbaumer Volker MauelMitglieder der Geschäftsführung / Members of the Management

reflex ’servitec 30’ Reflex service, Declaration of Conformity