Reference Cable Schedule _ JGS 320 _ Non-Grid Synchronization

Embed Size (px)

Citation preview

  • 8/16/2019 Reference Cable Schedule _ JGS 320 _ Non-Grid Synchronization

    1/2

    Sr. No. Cable Identification Cable Specifications Cable Type Cable Description

    1 W.E81.A 5 core, 2.5 sqmm standard flexible control cable Emergency stop

    2 W.E1.A 5 core, 10 sqmm standard flexible control cable M Panel Power Supply

    3 W.E12.B 2 core, 1.5 sqmm standard flexible control cable Voltage Matching

    4 W.E12.C 5 core, 4 sqmm standard flexible control cable M Panel Power Supply

    5 W.E13.C 1 core, 16 sqmm flexible earthing cable earthing cable

    6 W.M120.A 3 core, 1.5 sqmm shielded flexible control cable Engine cooling water temperature

    7 W.E33.A CAN-BUS Cable GEJ Supplied CAN Bus communication

    8 W.I4.A X2X GEJ Supplied PLC communication

    1 W.E70.A 5 core, 2.5 sqmm standard flexible control cable IS Panel Power Supply

    2 W.E89.A 12 core, 1.5 sqmm standard flexible control cable

    3 W.E90.A 18 core, 1.5 sqmm standard flexible control cable

    4 W.E72.A 2 core, 1.5 sqmm shielded flexible control cable Load Sharing Line

    1 W.E10.C 4 core, 2.5 sqmm standard flexible control cable water pump

    2 W.E11A 3 core, 1.5 sqmm shielded flexible control cable Electrical TCV

    3 W.E92.A 2 core, 1.5 sqmm standard flexible control cable pressure switch

    1 W.E143.A 3 core, 1.5 sqmm shielded flexible control cable Gas Temperature Gas Train

    2 W.E144.A 3 core, 1.5 sqmm shielded flexible control cable Gas Pressure Gas Train

    3 W.E29.A 2 core, 1.5 sqmm shielded flexible control cable Gas Counter

    4 W.E30.A 2 core, 1.5 sqmm shielded flexible control cable Gas Counter

    Status / Control Signals

    Reference Control Cable Schedule for JGS 320 (non-grid synchronization)

    Module Control Panel (A) to Module Interface Cubical Panel (M)

    Module Control Panel (A) to Interlock Panel (IS)

    Module Control Panel (A) to Aftercooler Circuit

    Module Control Panel (A) to Gas Train

  • 8/16/2019 Reference Cable Schedule _ JGS 320 _ Non-Grid Synchronization

    2/2

    1 W.E30.A 4 core, 2.5 sqmm standard flexible control cable Gas valve, Gas train

    2 W.E20.A 2 core, 1.5 sqmm standard flexible control cable Gas pressure min. Gas train

    1 W.SSL8 7 core, 2.5 sqmm standard flexible control cable Generator current

    2 W.SSL13 5 core, 1.5 sqmm standard flexible control cable Generator Voltage

    3 W.SSL75 5 core, 1.5 sqmm standard flexible control cable Busbar Voltage

    W.SSL78.1 2 core, 2.5 sqmm standard flexible control cable GCB Switch on Coil

    W.SSL78.2 2 core, 2.5 sqmm standard flexible control cable GCB Shunt Trip Coil

    W.SSL79 2 core, 2.5 sqmm standard flexible control cable GCB UVT Coil

    W.SSL80 2 core, 1.5 sqmm standard flexible control cable GCB Close

    W.SSL81 2 core, 1.5 sqmm standard flexible control cable GCB Open

    W.SSL82 2 core, 1.5 sqmm standard flexible control cable GCB Ready

    W.SSL84 2 core, 1.5 sqmm standard flexible control cable GCB OL / SC

    1 W.SSL33 2 core, 2.5 sqmm standard flexible control cable Rotation Light

    2 W.SSL34 2 core, 2.5 sqmm standard flexible control cable Horn

    1 W.SSL6 5 core, 25 sqmm Flexible Power Cable Power Supply for A Panel

    1 W.E5.A Single core, 120 sqmm standard flexible power cable Battery +

    2 W.E6.A Single core, 120 sqmm standard flexible power cable Battery -

    Single Core, PVC/PVC 300 Sqmm Power Cables (Copper Conductor): 5 Cables/Phase, 3 Cable for Neutral & 2 Cables for Star Point

    4

    5

    All cables, to be terminated in GEJ Control Panels should be flexible and copper conductor cables.Note:

    Genset Starting Batteries

    This cable schedule is only for reference.

    Module Interface Cubical Panel (M) to Gas Train

    Module Control Panel (A) to Generator Incoming Panel

    Alarm Indication System

    MCC Panel to Module Control Panel (A)

    Power Cables