Recloser Control M‑7679
CONTROL
• NextgenerationRecloser ControlandProtectionSystem forAdvancedDistributionGrids
• FastandeasyretrofittingformostpopularreclosersusingBeckwith'sAdapterPanelTechnology™
• Easy-to-UseIPScom® CommunicationSoftwareandIPSlogic®ProgrammableLogic
• Compatiblewiththreephaseandtriple-singlereclosers(optional)
• SettingsWizardassistsincreatingthemostcommonlyusedsettings
• Graphicaltooldisplaysrealtimeorrecordedreclosingsequenceandtiming
• WithSamplingRateof128samples/cycleprovidesAdvancedandrealtimePowerQualityMetering;includingTHD(TotalHarmonicDistortion),CBEMAEvents,detectionofSags,SwellsandLoadProfiletrending
• Integratedpowerqualitymeteringincludingvoltageandcurrentharmonicsuptothe63rd,THD,detectionofsagsandswells
• Advanceddatalogging,sequenceofeventsandDigitalFault(waveform)recorder • FrontpanelUSBandSDCardportsforlocalprogramminganddatatransfer • Onestandardandanoptionalsecondserialport • OptionaldualMACcapableEthernetportsofferingmulti-userand
multi-protocolsupport • ProtocolssupportedincludeMODBUS,DNP3.0,SmartP2P;
OptionalIEC61850andIEC60870-5-104 • ComprehensivecybersecuritytoolstohelpwithNERCCIPcompliance • FouruserprogrammableInputsandOutputs,expandabletotwelve • Userprogrammablefront-panelLEDsandpushbuttons
Industry Leader Since 1969Made in the USA
–2–
M‑7679 Recloser Control
M-7679 Recloser Control
4I1, I2, I3, Ig
Or ISEF
25
79
51N50N 67NResidual (3 IO)
59Vx
27Vx
ResidualDirectionalOvercurrent
Residual TimeOvercurrent
Residual InverseTime Overcurrent
RecloserRelay
Sync Check
Overvoltage Undervoltage
52Recloser
V1, V2, V3
3
VX
1
Three PhaseTriple/Single (optional)
46
OUR
81
Frequency• Over• Under• ROCOF
59
Overvoltage• Phase• Phase-to-Phase• Residual
PPPR
Undervoltage• Phase• Phase-to-Phase
PPP27
60FL
VT FuseLoss
Directional TimeOvercurrent • Phase • Ground • Neg. Seq.
PGQ
67
BreakerFailure
50BF
DirectionalPower
32
TimeOvercurrent • Phase • Ground
Inverse TimeOvercurrent • Phase • Ground
Port 1 TIA-232TIA-485
Serial Fiber
Port 2+
EthernetFiber Optic
orCopper
Port 3+
EthernetFiber Optic
orCopper
Front PortType B USB
SD Card
IRIG-BPort 4+
TIA-232TIA-485
Serial Fiber
Hot-Line Tag
Trip/Close Coil Monitor
Settings Wizard
Synchrophasors(C37.118-2)**
Trip and TargetCounters*
Digital 86 Lockout*
Web Browser Interface**
Load EncroachmentSupervision
Self Diagnostics
IRIG-B TimeSynchronization (TTL)
Cold Load Pickup
Power/Battery Monitor
Arc Flash Detection
Reclosing SequenceMonitor**
Digital Fault (Waveform)Recording
CBEMA Countersand Recording
Eight SettingProfiles
RecloserWear Monitor**
Data Logging
Fault Locator*
High Impedance FaultDetection**
IPScom®
CommunicationsSoftware
IPSlogic®
Programmable Logic
PQ Metering*
Demand/EnergyMetering
Phantom Voltage
Sequence ofEvents Recording
ProtocolsMODBUS
DNP 3.0 SAv2*Smart P2P (Peer-to-Peer)**
IEC 61850 (Optional)*IEC 60870-5-104 (Optional)**
* Feature available 3Q2013 via firmware update** Feature available 4Q2013 via firmware update+ Optional Feature
NegativeSequence
Overvoltage
47
Or 3**
NegativeSequence
Overcurrent
PG50P
G51
Figure 1 M-7679 Recloser Control
–3–
M‑7679 Recloser Control
Standard Control Features • Over20protectionfunctions
• IPSCom®CommunicationsSoftware
• IPSLogic®ProgrammableLogic*
• SettingsWizard
• HighImpedanceFault(HIZ)**
• Synchrophasors(IEEEC37.118-2)**
• LoadEncroachmentSupervision
• PhantomVoltage
• Digital86Lockout*
• I/OMap*
• SmartFuseCoordination*
• CustomCurveDesigner*
• Hot-LineTag
• FaultLocator*
• EightSettingProfiles
• CompareSettingsTool**
• Three-PhaseRecloseOperation
• SequenceCoordination
• ColdLoadPickup
• ReclosingSequenceMonitor&Recorder**
• Recloser/BreakerWearMonitor*
• PowerQualityMetering
• CBEMA Curve Violation Counters andRecording*
• DemandandEnergyMetering
• PowerSupplyMonitor
• Trip/CloseCoilMonitor
• DataLogging
• SequenceofEventsRecording
• TripandTargetCounters*
• DigitalFault(Waveform)Recording
• FaultEventRecords**
• Self-Diagnostics
• Three Phase Current Inputs plus oneGroundCurrentInput
• ThreePhaseVoltageInputsplusoneSyncCheckVoltageInput
• IRIG-BTimeSynchronization(TTL)
• FrontPanelUSBandSDCardports
• PORT1:RearTIA-232
• ProtocolsSupported:
–MODBUS®
–DNP3.0SAv2*
–SmartP2P**(Peer-To-Peer)
• FourUserProgrammableDigitalInputs
• FourUserProgrammableDigitalOutputs
• Conformalcoatedcircuitboards
• Configurable Front HMI LEDs andPushbuttons
• 12VdcBackupPowerInput
• SMTPE-mailserver**
• WebBrowserInterface**
• IEEE1686Passwords
• Wide Variety of CommunicationsAccessories
Optional Features • TripleSingleRecloserOperation*
• PORT2–RearEthernetFiberOpticorCopper
• PORT3 -RearEthernetFiberOpticorCopper*
• PORT4–TIA-232,TIA-485,orFiberOptic
• DNP3.0SAv5*
• OptionalProtocols:
–IEC61850*
–IEC60870-5-104**
–2179
• Sensitive EarthGroundCT (Isef) Inputoption
• Sensi t ive Ground InstantaneousOvercurrent(50GS)
• Sensitive Ground Time Overcurrent(51GS)
• DirectionalSensitiveGroundOvercurrentprotection(67GS)
• ArcFlash detection (Hardware optionavailable4Q2013)
• Expanded I/O – Additional eight digitalInputsandeightdigitalOutputsforatotalof12each
• Low Energy Analog Inputs (LEA) 4, 6,3+1,(Hardwareoptionavailable4Q2013)MeetsC37.92Standard:
–DynamicRange:0.05to2.0timesrated voltage –Nominal:(Vnor1P.U.)outputlevel, 4Vrms
–MaximumOutput:4.0•2.0•1.414= 11.3Vpeak*Featureavailable3Q2013viafirmwareupdate
**Featureavailable4Q2013viafirmwareupdate
–4–
M‑7679 Recloser Control
© 2012 Beckwith Electric Co. All Rights Reserved.Printed in U.S.A. (1.15.03)
800‑7679‑BR‑00( ) 0/13
BECKWITH ELECTRIC CO., INC.6190 - 118th Avenue North • Largo, Florida 33773-3724 U.S.A.
PHONE (727) 544-2326 • FAX (727) [email protected]
www.beckwithelectric.comISO 9001:2008
PORT 1 PORT 4
1 2 31 2 3
PORT 2 PORT 3
ETHERNET
P/S= 18-6080-300
1
Figure 2 M-7679 External Connections
Enclosure Features • NEMA 4R powder coated aluminum
enclosure
• MoldedLexan
• StainlessSteel
• Singleexteriorgasketeddoor
• Internalstainlesssteelhinge
• Holdopenarmanddocumentholder
• Quarter-turn 3-point padlockable latchhandle
• Interior latchingswingdoorwith120Vacconveniencereceptacle
• Foldout/Slideoutshelfforlaptoprest
• Polemountingbracketandliftingeyes
• Electricalconnections
• DIN rail mounted terminal blocks with40W12Vdcaccessorysupply
• Standardplugconnectors forcontrolandmeasurementinterface,sensor,andpowercabling
• Widevarietyofcommunicationaccessories
• DINmountedfuseprotectionofcomponentswithLEDindication
• 24Vdc,8AH,sealedlead-acidbattery
• TemperaturecompensatedbatterychargerwithmonitorandloadtestfunctionviaHMIorremotecommand