24

READY Limit Controls and Thermostat Chapter · The current from the control to the thermo-stat heater circuit should be measured with an amperage meter and the anticipator set to

  • Upload
    others

  • View
    5

  • Download
    0

Embed Size (px)

Citation preview

Page 1: READY Limit Controls and Thermostat Chapter · The current from the control to the thermo-stat heater circuit should be measured with an amperage meter and the anticipator set to
Page 2: READY Limit Controls and Thermostat Chapter · The current from the control to the thermo-stat heater circuit should be measured with an amperage meter and the anticipator set to
Page 3: READY Limit Controls and Thermostat Chapter · The current from the control to the thermo-stat heater circuit should be measured with an amperage meter and the anticipator set to

Limit Controlsand Thermostats

Chapter 12

Chapter 12—Limit Controls and Thermostats 12-3

There are a large variety of limitcontrols, thermostats, and switching relaysused in oil-fired heating systems. At firstglance, it can be confusing. Remember,these devices are just switches that turnthings on and off.

Some of these switches are turned onand off by the warping or flexing action ofbimetal blades. Some use magnets andsprings. Some are controlled by a fluid thatexpands and contracts quickly. Some areline voltage and some are low voltage.Some need transformers to change thevoltage so that low voltage switches cancontrol line voltage loads. Some controlsnow use solid-state microprocessors andother electronic devices.

No matter what they look like, limitcontrols are just switches. You may want toreview the section on switches in the basicelectricity chapter before you go anyfurther.

Electrical control circuitThe hot (L1) electric power wire for the

basic oilburner circuit begins at the servicepanel fuse, or circuit breaker, travels to themain switch, then to a junction box that isusually located on the ceiling near theburner. Many states and local codes requirea thermal or Firomatic® switch at thisjunction box. From the junction box, thehot line (which is a black wire) runs to theserviceman’s switch, through the high limit

Figure 12-1: Basicoil burner controlcircuit

Basic Oilburner Circuit ShowingSwitches, Motor, and Ignition Transformer

L1

L2

Fuse EmergencySwitch 1

LineSwitch 2

High-Limit PrimaryControl

Chapter 12Limit Controls/Thermostats

Page 4: READY Limit Controls and Thermostat Chapter · The current from the control to the thermo-stat heater circuit should be measured with an amperage meter and the anticipator set to

12-4 Limit Controls and Thermostats

control and then to terminal #1 or the blacklead wire of the primary control. From theprimary control, wires are connected to theoilburner motor and ignition transformer.All wires up to this point carry 120 voltline voltage.

The neutral white (L2) wire of thecontrol circuit also starts at the mainentrance service panel, and passes toterminal #2 or the white lead of theprimary control. On a modern circuit, thereshould never be any switches or fuses inthe neutral side of the circuit. Older homeswith knob and tubing wiring often havefuses on both the hot side and the neutralside of the circuit. And sometimes switches,limits, and fuses are put on both sides bymistake. Never assume anything when itcomes to electricity. Always test!Also, before doing any wiring, check with

the local fire marshal or other authority tomake sure that your installation complieswith all local requirements. In some areas,only licensed electricians are allowed toinstall line voltage wiring.

The low voltage (24 volt) side of theoilburner control circuit usually starts at thestep down transformer in the primarycontrol. The low voltage circuit turns theburner, circulator, or blower on and off, andopens and closes valves in response totemperature changes in the heated spaceand the appliance.

See Figures 12-1 and 12-2.

Burner switchThe burner switch is used to shut off the

burner in an emergency or as a convenienceswitch when servicing the oilburner. There

Figure 12-2:Circuit wiring

Chapter 12Limit Controls/Thermostats

HighLimit

Thermostat

LineSw.

EmergencySw.

Fuse

JunctionBox

Motor Trans

Primary

H N

Page 5: READY Limit Controls and Thermostat Chapter · The current from the control to the thermo-stat heater circuit should be measured with an amperage meter and the anticipator set to

Chapter 12—Limit Controls and Thermostats 12-5

are usually two disconnect switches. Thefirst is called a customer or emergencyswitch and it is normally located at thehead of the basement stairs or at theentrance to the heater room. The secondswitch is a serviceman’s switch and mayinclude a fuse. This switch is located on ornear the furnace or boiler.

ThermostatsPrinciples and designA thermostat is a mechanical or electronicswitch that automatically opens or closes acircuit as room temperature changes. Thethermostat’s purpose is to start the burnerand/or circulator or blower when thetemperature is below the established setting,and to shut them off when the heat demandis satisfied. Thermostats must be extremelysensitive to temperature changes. In olderthermostats, a bimetal element warps orunwinds in response to temperature changeto open or close a switch. In the solid-statethermostat, the room temperature changesthe resistance of an electronic device thatwill act in various methods to open and closecircuits.

The majority of thermostats installed inthe field still use a bimetal element andmercury switch to function. Thefollowing text covers this typeof thermostat, Figure 12-3shows the most commontype in use. The replace-ments are mostlyelectronic and will bediscussed later.

The bimetallicelement comprises twodissimilar metal strips,bonded together, whichexpand or contract with achange in temperature at differentrates of speed. This difference in expansion

Figure 12-3

Figure 12-4:T-87 thermostat

rate will cause thebonded bimetallicelement to bend orwarp with temperaturechanges. By bending ormoving when heat isapplied to it or takenaway, it creates amechanical force thatflips a mercury switchto make or break a pairof switch contacts.Making or breaking acontact means closingor opening a circuit.Remember, as with allmercury switches, suchthermostats must beinstalled level. Figure12-4 shows how tolevel the T87 thermo-stat. 3 wire thermostats vs.2 wire thermostats

Very old stylethermostats neededthree wires to operate.When replacing an oldthree wire thermostat with a new two wire,

eliminate the red wire. Today thereare some three wire thermostats

that operate some zone valvemotors and dampers. Acircuit is necessary to drivethe valve or damper openand another circuit mustdrive it closed. The switch-ing action of these thermo-

stats is single pole, doublethrow as opposed to a single

pole, single throw switch forthe two wire circuits. Thermostats

of this type are never connected toprimary controls.

Chapter 12Limit Controls/Thermostats

MountingSlots

Be SureWallHole isPlugged

R

TerminalScrews

WPlumbLine

MountingSlots

Spirit Level

Spirit Level

PlumbLine Diamond

Guides (2)

MountingSlotsOpening for

ThermostatWiring

LevelingPost (2)

Page 6: READY Limit Controls and Thermostat Chapter · The current from the control to the thermo-stat heater circuit should be measured with an amperage meter and the anticipator set to

12-6 Limit Controls and Thermostats

Low voltage and line voltagethermostats

In some older systems, line voltagethermostats were used to directly controlthe circulator without the use of a switch-ing relay. Line voltage thermostats are notas sensitive as low voltage types and thisoften leads to wide fluctuations in the roomtemperature. If open blade contacts areused in the line voltage controller, thecontacts will eventually burn, and pitting ofthe contacts is the result. At this point wecan lose control of the room temperature.Line voltage thermostats are mostly used incommercial and industrial applications.

Heat anticipating principleThe differential of a thermostat is the

number of degrees temperature change thatare required to cause its bimetal or bellowsto move the required distance to close oropen its electrical contacts. The number ofdegrees difference between the openingand closing of a thermostat is called themechanical differential. For example, if athermostat opened at 70°F, and its contactsclosed at 68°F, its mechanical differentialwould be 2°.

Manufacturers incorporate an anticipat-

ing heater to increase the sensitivity of thethermostat. It reduces the mechanicaldifferential. The heat anticipator is a smallelectrical resistance heater that fools thethermostat into thinking it is warmer in theroom than it actually is.

The heater is wired so that electriccurrent flows through it when the thermo-stat calls for heat. The anticipator heatercreates heat within the thermostat near thebimetallic element. This causes the thermo-stat to break its contacts prior to the roomair reaching the temperature of the dialsetting, so the burner is turned off slightlyahead of the time that the room air tempera-ture increases to the dial setting of thethermostat. The blower in a warm airsystem continues to operate, bringing theroom air temperature up to the dial setting.With a hot water or steam system the heatin the radiators or baseboard will raise theroom temperature after the thermostat shutsoff the burner and circulator.

The anticipating heater must be adjustedto match the current that is supplied to thethermostat. We must adjust for the numberof amps supplied to the heater, because thegreater the number of amps, the quicker theheater will heat up. Current flow in this 24volt circuit generally varies from 0.05amperes to 0.6 amperes, depending on themake and model of control. When settingthe heat anticipator, consider the length ofthe wire and other resistances in the circuit.The current from the control to the thermo-stat heater circuit should be measured withan amperage meter and the anticipator setto the amps in the low voltage circuit.

If an ammeter is not available, set theanticipator to the amp rating found insidethe cover of the control to which thethermostat is directly connected.

Figure 12-5 shows the location of theheat anticipator in a heating and coolingthermostat. Notice the anticipator in the R

Figure 12-5:T-87F heatanticipator

Chapter 12Limit Controls/Thermostats

Page 7: READY Limit Controls and Thermostat Chapter · The current from the control to the thermo-stat heater circuit should be measured with an amperage meter and the anticipator set to

Chapter 12—Limit Controls and Thermostats 12-7

Location of the thermostat A thermostat should be installed about

5 feet from the floor on an inside living ordining room wall, or a wall where there isgood natural air circulation. It may be wiseto select several good locations, pointingthem out to the homeowner, and then letthem choose from the suggested locations.

Some locations that will cause trouble are:1. Above a TV, stereo, computer,

or lamp2. On or near an outside wall3. Near a radiator or air register4. In line with the air

stream from a register5. On a wall containing

steam pipes, hot waterpipes, warm air risers,or chimneys

6. On a wall with highinternal air movement

7. Behind a door orother obstructionto free air circulation

8. In an over radiated orunder radiated room

9. Near a window ordoor frequently

opened to the outside10. In a room with a

heat source suchas refrigerator, stove,or fireplace

11. On a wall or partitionsubject to excessive vibration

to W circuit. This is because the anticipatoris only used for heating and not in thecircuit R and Y that would be used if thisthermostat were used for air conditioning.Figure 12-6 shows the heater indicator andthe scale in a thermostat.

In some installations, longer operationsmay be needed to assure delivery of heatthroughout the house. To lengthen opera-tions, move the heater indicator preferablynot more than half a division in the direc-tion of the scale arrow. To shorten opera-tions, move the indicator in the oppositedirection.

If the operating control supplies 0.4amps to the thermostat circuit and theanticipating heater of the thermostat is setat 0.8 amps, the burning cycle will be long.However, if the heat anticipator of thethermostat is set at 0.2 amps while thecontrol is supplying .4 amps, then theburner cycle will be short. In the latter case,the burner will operate on and off for shortperiods of time (short cycling).

Electronic thermostatsFigure 12-7 shows some examples of

electronic thermostats. These thermostatsrely on solid-state technology to not onlyoperate the equipment, but to maintain andstore temperature settings, day and date,and number of cycles. Unlike the earliermechanical thermostats that had only oneday per operation cycle, many of thesethermostats can have four different settingsfor all seven days of the week.

The difference in electronic thermostatsover manual and mechanical clock types isthe lack of an adjustable anticipator.Instead the electronic thermostat must beprogrammed according to ‘cycle rateadjustment’. Once these settings are madeat the time of installation, the thermostat,and its circuitry accommodate for thecorrect number of cycles.

Figure 12-6:T-87F heateradjustment

Figure 12-7:Electronic thermostats

Hole Suitable forPencil Point toMove Indicator

HeatAnticipatorIndicator

Scale

Chapter 12Limit Controls/Thermostats

Page 8: READY Limit Controls and Thermostat Chapter · The current from the control to the thermo-stat heater circuit should be measured with an amperage meter and the anticipator set to

Mounting thermostats• Servicing or installing a thermostat is

a job for clean hands. Do not mar or soilwall surfaces.

• Be absolutely sure that all wires areconnected to their proper terminals and thatall connections are tight. If a color code isbeing used, be certain that it is followed.

• If mercury switches are used in thethermostat, be absolutely certain thethermostat back plate and/or the thermostatitself are level.

• All excess wire should be pushedback into the hole in the wall, and the holeshould be plugged with putty to preventcool air drafts from affecting the thermo-stat performance. Limit controlsA limit control is a temperature or pressureactuated switch. Limit controls are gener-ally divided into two groups: the high limitor safety controls and the low limit oroperating controls. Limit controls are ofeither the direct acting or reverse actingtype. Direct acting controls break (open)their contact on temperature rise while thereverse acting controls make (close) theircontacts on temperature rise. Remember, inelectricity, open means that there will be noflow of electricity and closed meanselectricity can flow through the switch.

The high limit is a safety device thatturns off the burner should temperaturesget too high within the furnace or boiler, orsteam pressure become excessive in a steamboiler. This control should be line voltage,wired in series with the primary control sothat it can turn off only the oilburner, neverthe circulator or system fan. The circulatoror fan must stay on to remove the excessiveheat produced. A low limit or operatingcontrol is a limit that is used to control theoperation of the burner and blower orcirculator.

Warm air limit controlsWarm air limit controls protect the

furnace heat exchanger from excessivelyhigh temperatures and operate the blower.Both the high limit control and the fancontrol may be operated by a bimetallicelement inserted in the plenum, or throughan electronic control panel. The linevoltage high limit control in series with theprimary control may employ either metalto metal contacts or a mercury switch tomake or break the circuit.

Fan and limit controls are usuallycombined into one housing. In this in-stance, the helix type bimetallic elementoperates both the fan control switch and thehigh limit control switch. Figure 12-8shows a combination fan and limit control.A single dial as shown in Figure 12-9 (old

12-8 Limit Controls and Thermostats

Remember, in electricity, openmeans that there will be no

flow of electricity and closedmeans electricity can flow

through the switch.

Figure 12-8:Combination fan and limit control

Chapter 12Limit Controls/Thermostats

Page 9: READY Limit Controls and Thermostat Chapter · The current from the control to the thermo-stat heater circuit should be measured with an amperage meter and the anticipator set to

and newer version) has indicators for thefan on position and the fan off position aswell as an indicator for the high limitsetting.

The function of the fan control is tooperate the system blower when the airtemperature is within the fan control dialsettings. The fan control will permit the fanto operate when the air temperature in thefurnace rises above the fan on setting asprescribed for the specific system or themanufacturer’s requirements. The fancontrol will also prevent blower operationin the event the air temperature is below thefan off setting of the fan control. Thisprevents cool air from being forced into theliving area during cold weather.

Many fan controls provide for manualoperation to provide for summer aircirculation. After the burner has been onfor a short period, the element of the fancontrol will sense the desired amount ofheat in the plenum or bonnet of thefurnace, and start the blower. The blowerwill then run as long as there is heat, whichcan be for some time after the burner hasstopped.

Limit terminals and fan terminals (oldand new) connect the line voltage wires ofthe heating system electrical circuit. Asshown in Figure 12-10 on following page.

The heat sensing element, or bimetallicelement, expands and contracts with achange in furnace temperature. Since theelement is helical in shape, it turns with acircular motion, either clockwise orcounterclockwise, depending upon whetherthe furnace air is being heated or it iscooling off.

The operation of the fan switch controlas shown in Figure 12-10 is as follows:

1. If the furnace temperature is the sameas the room temperature and the fan onindicator is set at 140ºF, the fan offindicator set at 110ºF and the thermostatthen calls for heat, the burner is turned on.

2. As the burner produces heat, the air inthe furnace begins to rise in temperatureand the helical element reacts to this changein temperature. In its attempt to expand,the bimetal causes the scale plate to turn ina clockwise direction. Once the scale plate

Chapter 12—Limit Controls and Thermostats 12-9

Figure 12-9:High limit

Chapter 12Limit Controls/Thermostats

Left HandPointer

(Fan Off)

CenterPointer

(Fan On)

Right HandPointer

(Limit Opens)

Safety Stop

Scaleplate

Fan OffSet Point Lever

Fan OnSet Point Lever

To Release Stop, PressStiff Wire In Hole

AdjustableLimit Stop

Limit Set Point Lever(Factory-Set

at 200°F (93C)

Page 10: READY Limit Controls and Thermostat Chapter · The current from the control to the thermo-stat heater circuit should be measured with an amperage meter and the anticipator set to

has reached the fan on position, 140ºF, thefan switch will close its contacts and thefan will be turned on, forcing warm air intothe living area.

3. The burner will continue to operateuntil the room thermostat is satisfied, atwhich time it will turn off. However, the fanwill continue to operate until the airtemperature has dropped below the mini-mum setting or the fan off indicator setting.Once this point has been reached, the fancontrol will then “open” its electricalcontacts, and the fan will stop.

The heat exchanger of the furnace is stillhot, although the burner, controlled by thethermostat, is not running; warm aircurrents will continue to rise to the bonnet.Under certain conditions this heat may besufficient to again elevate the temperatureto 140ºF, and the fan switch will againoperate the fan until all of this heated air isdelivered to the living area.

In the event that the fan fails to operate,the air filters are clogged, or a blower beltis broken; the temperature in the furnacewould continue to rise, going beyond thefan on position and ultimately reaching thehigh limit indicator setting of 200ºF asshown in Figure 12-10.

Upon reaching this point, the limitcontrol would open its electrical contactand prevent line voltage from reaching theprimary control. This in turn would preventline voltage from reaching the oilburnermotor and ignition transformer thuscausing the oilburner to go off. The highlimit control would continue to hold itselectrical switch contacts open until the airtemperature inthe bonnet had dropped below the 200ºFmark minus the differential of the switch.(Normally 25º). The helical element wouldat the same time cool, rotating in a counter-clockwise direction, causing the limitindicator to also rotate in a counterclock-

12-10 Limit Controls and Thermostats

Figure 12-10:Limit and fanterminals

Chapter 12Limit Controls/Thermostats

Page 11: READY Limit Controls and Thermostat Chapter · The current from the control to the thermo-stat heater circuit should be measured with an amperage meter and the anticipator set to

wise direction until the scale plate hadtraveled below 175ºF. Once this point hasbeen reached, line voltage power wouldonce again be restored to the primarycontrol and if the room thermostat is stillcalling for heat, the burner would onceagain operate.

Always consult local codes and ordi-nances or regulations and manufacturer’sinstructions before installing a fan limitcontrol. The helical element of the fanlimit control must belocated in the furnaceplenum or at alocation where it willbe subjected to arepresentative airflowand temperature. Itmust not be locatednear cold air returnsor the humidifier, nor in a dead air spotwhere there is poor circulation. It mustdefinitely not touch any internal parts ofthe furnace.

Figure 12-11 is a schematic wiringdiagram showing how a Honeywell L4064B

combination control is wired into theheating system electrical circuit. In thisillustration, the limit control is wireddirectly into the hot line of the line voltagecircuit and is in series with the primarycontrol. The high limit control should neverbe wired to the neutral wire of the furnaceunit.

Figure 12-12 lists some typical warm airlimit settings and fan control on and offsettings; the lower these settings can be

without creating uncomfortably cool airdelivery into the living area, the moreeconomical the operation of the heatingsystem will be.

Referring to Figure 12-11, note that thefan motor is wired into the system circuit

Chapter 12—Limit Controls and Thermostats 12-11

Warm Air Limit Settings

Types of Systems Limit Fan = On Fan = Off

Average furnace, average system 200°F 140°F 110°F

Oversized furnace and/or oversized fan and/or short air ducts 170°F 130°F 90°F

Undersized furnace and/or undersized fan and/or long air ducts 230°F 160°F 130°F

Figure 12-12

Figure 12-11:Warm aircircuit

Chapter 12Limit Controls/Thermostats

Oil-Fired Forced Warm Air SystemStack Detector

Thermostat Primary Control Ignition Transformer

Fan and HighLimit Control

BurnerMotor

FanMotor

Lim

it

L2L1 (Hot)

Fa

n

Power Supply

Page 12: READY Limit Controls and Thermostat Chapter · The current from the control to the thermo-stat heater circuit should be measured with an amperage meter and the anticipator set to

12-12 Limit Controls and Thermostats

Figure 12-13:Electronic fantimer

in parallel with the primary control and thehigh limit control. The fan control shouldalways be connected on a warm air systemin this manner to enable the fan motor tooperate independently of the burner.

Electronic fan timer centerMost new warm air furnaces incorporate

air conditioning, heating, humidificationand air cleaning in one unit. They alsofeature multi-speed direct drive blowermotors. To operate all these devices, theyneed an electronic fan center. A goodexample of this device is the HoneywellST9103A Electronic FanTimer, Figure 12-13. Itintegrates the control of allburner and system fan

operations in anoil furnace.

This controlserves as thecentral wiringpoint for most ofthe electriccomponents of thefurnace. TheST9103A allowsthe thermostat tocontrol heating,cooling, and systemfan demands and runthe oilburner primary

control as well as upto a four speed circu-

lating fan. It alsomonitors a limit switchstring, which energizes thecirculating fan wheneverthe limit switch opens.Electronic air cleaner andhumidifier convenience

terminal connections are provided as anoption. A means for operating continuousindoor air circulation is also available as anoption. See Figure 12-14 for ST9103Awiring connections and Table 12-1 for theoperating sequence.

Steam system controlsPressure controls Limit controls that respond to changes insteam pressure are called pressure controls,or pressuretrols. As is the case with warmair limit controls and hot water controls,

Figure 12-14:Honeywell ST9103Awiring connections

Chapter 12Limit Controls/Thermostats

Page 13: READY Limit Controls and Thermostat Chapter · The current from the control to the thermo-stat heater circuit should be measured with an amperage meter and the anticipator set to

Chapter 12—Limit Controls and Thermostats 12-13

Action System Response

Thermostat calls for heat. • ST9103A closes oil primary control T-T connections.

• Ignition system and oil primary control start the furnace. Oil flows as long asoil primary control senses flame.

• Burner motor is energized and heat fan on delay timing begins. When timing iscomplete, the circulating fan is energized at heat speed and warm air isdelivered to the controlled space.

Thermostat ends call for heat • Oil primary control is de-energized, terminating the burner cycle.

• Heat fan off delay timing begins. When timing is complete, the circulating fanis de-energized.

• ST9103A returns to standby mode (oil primary control and circulating fan are off.

Burner fails to light • Oil primary control locks out within lockout timing (timing depends onoil primary control).

• Burner motor is de-energized.

• If heat fan has started, it continues through the selected delay period.

Established flame fails • Burner motor is de-energized and oil primary control goes into recycle mode.

• If selected heat fan off delay is longer than the recycle delay timing, the heat fancontinues to run through the next trial for ignition.

Thermostat begins call for cool • Circulating fan is energized at cool speed.

• Cooling compressor turns on immediately.

Thermostat ends call for cool • Circulating fan and cooling compressor turn off immediately.(G and Y terminals are de-energized)

Thermostat begins call for fan • Circulating fan is energized immediately at cool speed.

• ST9103A may be factory-configured to operate heat speed in this mode.

Thermostat ends call for fan • Circulating fan is de-energized.(G terminal is de-energized)

Limit switch string opens • Oil primary controls shuts off burner.

• Circulating fan is energized immediately at heat speed.

• ST9103A opens oil primary control T-T connections.

• Circulating fan runs as long as limit string stays open.

• If there is a call for cooling or fan, the circulating fan switches from heat speedto cool speed.

Limit switch string closes • ST9103A begins heat fan off delay sequence.

• Circulating fan turns off after the selected heat fan off delay timing.

• ST9103A recloses oil primary control T-T connections.

• Oil primary control is energized, initiating burner light off.

Continuous circulating fan is connected • Circulating fan is energized at low speed when there is no call for heat,cool or fan.

• If fan operation is required by a call for heat, cool or fan, the ST9103Aswitches off the continuous fan speed tap before energizing the other fan speed.

Electronic air cleaner is connected • Electronic air cleaner (EAC) connections are energized when the heat or cool(Optional connectors are available speed of the circulating fan is energized. EAC connections are not energizedfor 120 Vac electronic air cleaner) when the optional continuous fan terminal is energized.

Humidity control connected • Humidifier connections are energized when burner motor is energized.(Optional connectors are availablefor 120 Vac humidifier)

(W terminal is energized)

(G and Y terminals are de-energized)

(G terminal is energized)

Table 12-1

Chapter 12Limit Controls/Thermostats

Page 14: READY Limit Controls and Thermostat Chapter · The current from the control to the thermo-stat heater circuit should be measured with an amperage meter and the anticipator set to

12-16 show a vapor control and a pressurecontrol.

In both cases the switching mechanism isactuated by a diaphragm—the steampressure counteracts the pressure exertedby the spring in the control. The tension ofthe spring is predetermined by the pressureadjustment screw, or main scale set pointscrew.

It is important to read the pressureadjustment instructions for the particularpressure controller being adjusted. On somecontrols, the differential is subtractive,meaning that if the pressure cut out is setfor 3 PSI and the differential is set for 2PSI, the cut in point will be 1 PSI. Onother controls, the differential is additiveand if the cut in point is set at 1 psi and thedifferential is set at 2 PSI, then addedtogether, it would give us a cut out point of3 PSI.

The cut out point is the pressure atwhich the oilburner will shut off. The cutin point is the pressure at which the burnerwill restart. It is very important to remem-

12-14 Limit Controls and Thermostats

pressure controls will also complete orbreak a circuit by opening or closing theircontacts. Their contacts may be constructedof the metal to metal design, or they may beof the mercury tube type. The operatingrange of a pressure control must neverexceed the design pressure of the boiler.All residential and most commercial boilersare of the low pressure type with a maxi-mum pressure range not to exceed 15 PSI;therefore, pressure controllers must belimited to the 0 to 15 PSI range.

Occasionally a steam system may berequired to maintain pressure and the useof an operating controller may be neces-sary. In this case, two separate pressurecontrollers are necessary, one acting as thesafety limit and the other as the operatinglimit. Residential steam systems requireless than 2 PSI.

Most pressure controls are not sensitiveenough for the low operating pressuresrequired for some residential steam sys-

tems. In these systems, youwill get better results witha Vapor Control thatoperates on ounces ofpressure instead of pounds.

As the steam pressurechanges, an expansion orcontraction of a bellowsactuates the switchingmechanism. The cut-in andcut-out pressures canusually be independentlyset to meet any require-ment. The snap-actingswitch type does notrequire leveling.

If mercury switches are employed, thecontrol must be leveled. Figures 12-15 and

Figure 12-15:Vaporstat

Figure 12-16:Pressuretrol

Chapter 12Limit Controls/Thermostats

Page 15: READY Limit Controls and Thermostat Chapter · The current from the control to the thermo-stat heater circuit should be measured with an amperage meter and the anticipator set to

ber that if the cut out point is changed andthe differential is left the same the cut inpoint will also change. The same thinghappens in reverse, if the cut in point ischanged, the cut out point also changes.

Figure 12-17 shows a mercury tubepressure switch with the cover off, indicat-ing various parts and adjustment points.

The pressure control must always beinstalled above the water level of the boiler,and a pigtail, or siphon, as shown in Figure12-18, must be installed between the boilerand the control. The siphon loop preventssteam from damaging the control bellows.

The pressure control should be installedin the fitting provided by the boilermanufacturer, or in the pressure controlmounting of the low-water cutoff. When

Chapter 12—Limit Controls and Thermostats 12-15

Figure 12-17:Mercury tubepressure switch

Installation of a Pressure Control

Chapter 12Limit Controls/Thermostats

Figure 12-18:Pressure control,siphon loop

Right Wrong

DifferentialAdjusting

Screw

Scale Plates

DifferentialSetting

Indicator

PressureSetting

Indicator

DifferentialLever

TravelLimit Slot Operating

Lever

DiaphragmAssembly

LevelingIndicator

MercurySwitch

ManualReset Lever

EccentricAdjustment

Screw

PressureAdjusting

Screw

Page 16: READY Limit Controls and Thermostat Chapter · The current from the control to the thermo-stat heater circuit should be measured with an amperage meter and the anticipator set to

making pipe connections, use pipe dopesparingly. Excess dope may clog the smallopening of the pressure control, thuspreventing it from operating properly.

When mounting the pressure control andthe pressure gauge to the same boilerfitting, follow the method shown in Figure12-18, previous page. Be certain to mountthem in such a manner that their faces areperpendicular to the siphon loop circumfer-ence. The reason for this is that the siphonloop tends to expand, thus causing aforward and backward motion that couldcause the mercury switch in the pressurecontrol to operate improperly if the faces ofthese instruments were mounted parallel tothe circumference of the loop.

Figure 12-19 is a wiring diagramshowing the pressure control. Like all other

high limit controls, it is wired into the hotline in series with the primary control.

Low-water cutoffThe low-water cutoff prevents a burner

from operating if the water level is too lowin the boiler. This device is required on allsteam boilers whether used for spaceheating or in a process application and mayalso be required on hot water systems. If ahot water boiler is installed above theradiation, or even at the same level, a low-water cutoff should be used to protect theboiler in the event of a loss of water.

Figure 12-20 shows a cutaway view ofan external low-water cutoff. It is a floatoperated device. There is also an internallow-water cutoff with the float locatedinside the boiler.

12-16 Limit Controls and Thermostats

Figure 12-19:Pressure controlwiring

PressureControl

Low WaterCutoff

Low VoltageThermostat

Low VoltageAquastat

BurnerMotor

IgnitionTransformer

Chapter 12Limit Controls/Thermostats

Page 17: READY Limit Controls and Thermostat Chapter · The current from the control to the thermo-stat heater circuit should be measured with an amperage meter and the anticipator set to

With either type, when the float is in alevel position, it holds a single-pole single-throw switch in a closed position. In theevent the water level inside the boiler dropsbelow the safe operating level, the floatwill also drop, thus opening the switch andbreaking the hot line circuit to the burner.

Probe type low-water cutoffs arebecoming very common on most boilers,replacing the float types. These cutoffs mayhave timing devices to prevent nuisanceshut downs should the boiler water surge.Probe type cutoffs send a low voltagecharge through the water to ground on theboiler’s metal. Don’t switch to a probecontrol without first getting the boilermanufacturer’s recommendations as towhere it should be installed.

In Figure 12-19 (opposite page), thewiring diagram shows how the low-watercutoff is connected into the main heatingplant circuit. The low-water cutoff isconnected in the hot line, preceding thepressure control and in series with it andthe primary control. Thus, the low-watercutoff may be called a low water linevoltage safety device. Low-water cutoffson steam boilers may be incorporated with,or wired to, electronic solenoid watervalves called automatic water feeders.

Chapter 12—Limit Controls and Thermostats 12-17

Figure 12-20

Figure 12-21:Single functionaquastat

Figure 12-22:Dual actingaquastat

Chapter 12Limit Controls/Thermostats

Hot water limit controlsHot water limit controls, sometimes

called aquastats, control the temperature ofthe water in the boiler, and the temperatureof the domestic hot water. They are all justswitches that function automatically. In abasic forced hot water system, thesecontrols must perform threefunctions:

1. They provide high limitprotection against excessiveboiler water temperatures.

2. They are employed forthe purpose of maintaining apre-determined boiler tempera-ture, especially in systems thatuse tankless heaters for domestichot water.

3. They are used to keepcirculators from lowering theboiler water temperature toolow.

Figure 12-21 shows a typicalsingle function aquastat, theL4006 with two terminals andFigure 12-22 shows a dual actingL6006 with three terminals.

The high limit protection controlprevents the boiler water temperaturefrom rising to unsafe levels thatcreate steam. Low (operating) limitprotection means that the boiler wateris not allowed to drop below a certaintemperature. In the event the boilerwater temperature falls below the dialsetting of the low limit control, theburner would be turned on. Hot watertemperature controls are either direct-acting or reverse-acting. As explainedearlier, a direct-acting control willmake its contacts, completing anelectric circuit, on a drop in temperature

Page 18: READY Limit Controls and Thermostat Chapter · The current from the control to the thermo-stat heater circuit should be measured with an amperage meter and the anticipator set to

12-18 Limit Controls and Thermostats

Figure 12-23:Hot water limit(aquastat),strap on type

Figure 12-24:Hot water limit(aquastat),Immersion type

Figure 12-25:Thermistor

and it will break its contacts on rise intemperature. Reverse-acting controls maketheir contacts on a rise, and will break theircontacts on a drop in temperature. Theletter A after the Honeywell model numbernormally indicates a control that will openits circuit on a rise in temperature. The Bcontrol will normally close its circuit on arise in temperature for use as a reversecontrol.

Hot water limits may be of the strap-ontype (Figure 12-23, or theimmersion type, (Figure 12-24).Normally, the strap-on limitcontrol is installed close to theboiler on the main supply riser. Itshould never be mounted on apipe fitting such as an elbow orcoupling. The strap-on type

control is not as sensitive to temperaturechange as the immersion type controls andshould not be used as a high limit control.Immersion controls should be installed inthe tapped holes recommended by theboiler manufacturer.

The temperature sensing element on hotwater controls may be electronic ther-mistors, thermocouples, liquid filledelements, or helical bimetal elements.Liquid filled elements, or capillary sensingbulbs, are the most popular. Volatile liquid

expands and contractsdramatically with changesin temperature. Thisexpansion and contractionoperates an internal

diaphragm to open and close theswitch. When installing the heatsensing bulb in the aquastat well,coat the bulb with the heatconductive compound,supplied with the control,to help transfer the heatfrom the well to thebulb. The immersioncontrol equipped with a

thermistor, (Figure 12-25), will respondfaster to rapid temperature changes than theold immersion control of the bi-metal typeor the capillary type. A thermistor is a heatsensitive device that increases or decreasesresistance based on temperature.

Reverse acting aquastatWhen the circulator is turned on by

action of the room thermostat, the burneroften starts simultaneously. When thecirculator starts, it pushes hot water out ofthe boiler to the radiators, and an equalvolume of cool return water from theradiators and system piping flows back tothe boiler. This causes a drop in boilerwater temperature. Starting the burner atthe same time as the circulator helps theburner match its output to the heat contentleaving the boiler.

Also, in the event that the water tem-perature goes too low, the reverse-actingcirculator control will function to stop thecirculator until burner operation canrestore effective boiler water temperature.Then the circulator limit will again close itscontacts to turn the circulator on.

Without the reverse acting aquastat, if athermostat calls for heat while someone istaking a shower, the circulator comes onand sends all the heat in the boiler into theradiation and the boiler temperature dropsbelow what is needed to produce hot water;the result is that the shower water tempera-ture change can be quite noticeable. Thereverse acting aquastat shuts the circulator

off until the burner can buildenough heat in the boiler tokeep the tankless coil hotand heat the radiation.

The second reason fora reverse acting aquastatis to keep the productsof combustion fromcondensing in a high

Chapter 12Limit Controls/Thermostats

Page 19: READY Limit Controls and Thermostat Chapter · The current from the control to the thermo-stat heater circuit should be measured with an amperage meter and the anticipator set to

Chapter 12—Limit Controls and Thermostats 12-19

efficiency boiler. The new, high efficiencyboilers extract so much heat from theproducts of combustion that they can lowertheir temperature below the dew point ofthe combustion gases. At this temperature,the water vapor turns to water. While itdoes this, it picks up the sulfuric oxides inthe gases and creates sulfuric acid. Thisresults in scale build-up on the heatexchanger.

The reverse acting aquastat minimizesthe scale build-up. When the boiler watertemperature falls below the set point, theaquastat shuts off the circulator and theheat from the burner raises the boiler watertemperature. This allows the temperature ofthe combustion gases to stay above the dewpoint. See the chapter on combustiontheory (Chapter 7) for more detail.

Immersion aquastats should bemounted as follows:

1. When mounting immersionaquastats, try to avoidusing bushings on the well.Bushings may prevent thetemperature sensingelement from extending farenough into the boilerwater to be in the directpath of the hot water.Locate the element infreely circulating water.

2. Handle the aquastatwith care. Do not damagethe sensing element.

3. The bulb of theimmersion aquastat shouldbottom in its well.

4. Be certain that thesealing washer is in place(remote control).

5. Make certain thecase is mounted level if amercury switch is em-ployed.

The domestic hot water

low limit (operating) control used forcontrolling the domestic hot water supplyshould be installed on the boiler as close aspossible to the hot water generator on atankless hot water heating unit. In the eventa tank is used for hot water storage, it maybe installed in the hot water tank. Withmost hot water producing boilers, thiscontrol must be wired in parallel with thethermostat.

The reverse-acting circulator controlshould be installed in the boiler where thewater returning from the circulator willsurround the temperature sensing element.Figure 12-26 shows all three types ofaquastats wired into a one zone circuit withthe use of a switching relay.

Switching relaysSwitching relays control a line voltage loadwith a low voltage thermostat. They are used

Figure 12-26

Aquastat Wiring with One Zone Circuit and Switching Relay

L1

L2

Chapter 12Limit Controls/Thermostats

T-Start LowLimit

HighLimit

ReverseActingLimit

Circ.Motor

IgnitionTransformer

BurnerMotor

120 V

Page 20: READY Limit Controls and Thermostat Chapter · The current from the control to the thermo-stat heater circuit should be measured with an amperage meter and the anticipator set to

12-20 Limit Controls and Thermostats

Figure 12-27:Double-pole, singlethrow (DPST) relay

extensively on forcedhot water systems toprovide for multiplezones. In order for aswitching relay to usea low voltage switch(thermostat) tocontrol the linevoltage loads (thecirculator), it mustcontain a step downtransformer (from120 to 24 volts), arelay or relays andthe necessary line andlow voltage connec-tions.

Most of today’s switching relays aredouble-pole, double-throw (DPDT), butrelays can be found in several configura-tions. This is the oldest type and cancontrol only one load without exceedingthe contact current capacity of the relay.

Figure 12-27 shows a double-pole,single-throw (DPST) relay that allows fortwo devices to be switched at the sametime. A good application for this type ofrelay is where the switching relay turns on

the circulator andprimary control.

Figure 12-28shows a DPDTswitching relay foruse with a lowvoltage, low (operat-ing) limit control. Atypical use for thiscontrol is to controlan additional zonewith a combinationcontrol package thatwill provide for highlimit, low limit andcirculator operation.

Figure 12-28:DPDT switching relay

Figure 12-29: Panel used with circulators

Figure 12-30: Zone valves panel

Multiple zone switching relays can alsobe used to reduce costs and simplify wiringwhen several zones are used. Figure 12-29shows a panel used with circulators andFigure 12-30 shows a zone valves panel.Note that both panels can work with allmakes and wiring configurations ofthermostats, zone valves and circulators.

Hydro air fan controlsFigure 12-31 shows a wiring diagram

for a typical hydro air fan control. A hydroair system uses boiler water pumpedthrough a fan coil for heating. The fan coilis mounted in an air handler along with theair conditioning coil from the compressor.With these units you can use hot water toheat the air flowing through the same ductsused for summer cooling. The controls are

Chapter 12Limit Controls/Thermostats

Page 21: READY Limit Controls and Thermostat Chapter · The current from the control to the thermo-stat heater circuit should be measured with an amperage meter and the anticipator set to

Chapter 12—Limit Controls and Thermostats 12-21

the interface between the thermostat andthe air handler. They have an isolated endswitch to start the boiler and/or circulator.

When the thermostat calls for heat, thefan control energizes the end switch relayand allows the fan to operate at low speedwhen the water temperature is above theaquastat setting. When the thermostat callsfor cooling, the fan control energizes thecondenser and operates on high speed.Many of these relays also allow selectableone, three, four minute delay on fanoperation in the heating mode.Many ofthese relays also allow selectable one, three,and four minute delay on fan operation inthe heating mode.

Combination controlsWhen the controls are separate units and

scattered around the boiler, they arereferred to as non-integral controls. Whenthey are all in one box, high limit, lowlimit and circulator controls are calledintegral controls. They are also available indual capacity high limit and low limit, oras triple function controls acting as highlimit, low limit, and reverse-acting circula-tor limit.

In older heating systems, non-integratedcontrol systems were used much more thanthey are now. Today’s systems are generallyintegrated control systems that providecontrol of both the burner and circulator by

Figure 12-31:Diagram of typicalhydro fan control(Both HAFC 101 andHAFC 201 are capableof 1 and 2 speedapplications)

Chapter 12Limit Controls/Thermostats

HAFC 201 With 1 Speed Air Handler HAFC 101 With 2 Speed Air Handler

Page 22: READY Limit Controls and Thermostat Chapter · The current from the control to the thermo-stat heater circuit should be measured with an amperage meter and the anticipator set to

12-22 Limit Controls and Thermostats

the room thermostat, and are preferredbecause many new boilers have a boilerwater capacity of only a few gallons. Sincespace and accuracy are also factors, thesecombination controls are almost alwaysnow integral packages.

Triple actingaquastat relays

Dual and triple function aquastatcontrollers incorporate all of the variouslimit functions. Only one boiler waterimmersion element is required, simplifyinginstallation. Figure 12-32 is a schematicdiagram of a triple acting controller, theHoneywell L8124A. This controllerincorporates a line voltage circuit, a lowvoltage circuit, and a switching relay, andincludes all three limit controls: low, high,and reverse.

Assume that the low limit is set to openat 170°F, the high limit is set to open at200°F, and the differential is set at 20°F.The system may be analyzed as follows:

When the thermostat calls for heat, itcloses its switch, energizing the low voltagecircuit through the secondary (24 volt) coilof the step-down transformer. The IKsolenoid electromagnet is energized,pulling in the relay clapper, making contactIK1, closing the line voltage circuit to startthe circulator that also closes contact IK2 inthe line voltage circuit to start the oilburnerat the same time.

The circulator limit switch in thecirculator hot line must be closed to allowthe circulator to operate. It will be closed ifthe boiler water temperature is above180°F. If this switch is open, only theburner will operate, which will cause theboiler water temperature to increase to180°F and then the circulator limit switch

will close and the circulator will start. Thereason for this is that the low limit has abuilt in differential of ten degrees. Thedifferential is added to the set point, lessthe differential. So, you subtract 10 degreesfrom the 170°F set point to get 160°F andthen add 20°F to this number. In thesummer, the burner will operate between160°F and 180°F working off of the 20°differential.

The high limit switch is located in theburner hot line and it must be closed toallow the burner to operate. It will alwaysremain closed unless the boiler watertemperature is higher than 200°F. Thisswitch will again close the circuit when thewater temperature drops below 190°Fbased on its 10° fixed differential.

When the thermostat is satisfied, thecirculator will stop and the burner may alsostop, or it may continue to operate for ashort period if boiler water temperature isbelow 160°F.

This is the control operation during anormal heating cycle, from thermostat onto thermostat off. Now when a hot waterboiler also provides domestic hot water, thelow (operating) limit functions, to causethe burner to run and heat the boiler wateryear round to provide adequate domestichot water through the tankless or the tanktype coil installed in the boiler.

The low limit switch closes to run theburner when the boiler water temperaturedrops below 160°F. It is desirable to openthe circulator switch at the same time sothat the circulator cannot operate untilproper water temperature is again restored.The control manufacturer has incorporateda Single Pole Double Throw (SPDT)switch installed in the hot line to both thecirculator and the burner for this purpose.

Chapter 12Limit Controls/Thermostats

Page 23: READY Limit Controls and Thermostat Chapter · The current from the control to the thermo-stat heater circuit should be measured with an amperage meter and the anticipator set to

Chapter 12—Limit Controls and Thermostats 12-23

Figure 12-32:Schematic diagramfor a triple actingcontroller, HoneywellL8124A

Chapter 12Limit Controls/Thermostats

Note that the hot line, starting at terminal 1, goes directly to a point midway betweenthe low limit switch and the circulator limit switch. This point is the hot side of a SPDTswitch that is actuated by the heat sensing element immersed in the boiler water.

Shows how the external connections will oftenappear in the instruction sheet with the control.

Page 24: READY Limit Controls and Thermostat Chapter · The current from the control to the thermo-stat heater circuit should be measured with an amperage meter and the anticipator set to

12-24 Limit Controls and Thermostats

Caution

Be careful when wiring hot water heating systemswith multiple zones not to hook one set of pow-ered terminals to another. The thermostat circuit(usually TT) is powered by the transformer in thatcontrol. Never hook wires from TT of one controlto the TT of another control or switching relay.This will apply 48 VAC to the circuit and burn outthe controls.

If the water temperature is below 160°F,the double-throw switch will close the hotline to the burner by moving its contact upto terminal B, allowing power to pass to B1and the primary control. The thermostatterminals, T and T of the primary, are nowclosed so the burner starts and will continueto operate until the water temperaturereaches 180°F. Then the double-throwswitch will transfer its contact from B to Wand the burner stops. The boiler watertemperature has now been restored toeffectively provide domestic hot water.When the thermostat again calls for heat,the circulator can operate. The burner canbe energized in two ways: first by an actionof the thermostat and second by action ofthe SPDT switch even when the thermostatis not calling for heat.

Figure 12-32 (previous page) also showsterminals ZC and ZR. These terminals areused when circulated zones are added to thesystem. When a call for heat energizes thezone relay, the use of these two terminalsenables the control to act as though themain zone circulator was called. Thecontrol will start the burner and drop outthe circulator if the boiler water tempera-ture drops below the low limit/differentialset point. This ensures consistent tanklesscoil performance.

Since there may be differences incontrol models as well as control manufac-turers, you are urged to study the operationof the various makes of controllers coveredin the data and instruction sheets suppliedby the manufacturer of the control.

Testing limit controlsHigh limit controls

1. With the burner operating and theroom thermostat calling for heat, move thelimit indicator to the low end of its scale.

2. Allow the burner to operate so thateither the temperature or the pressure of thefurnace or boiler rises to the limit setting.The burner should shut down. If it doesnot, then the limit control is either improp-erly installed or defective.

3. If it does shut down, then set theindicator at the desired temperature orpressure.

Circulator controls1. Set the thermostat to call for heat.2. In the event the boiler water tem-

perature is above the circulator switch(reverse acting aquastat) setting, thecirculator relay should close its contactsand the circulator should operate.

3. Next, turn the thermostat downbelow room temperature. This shouldcause the circulator relay to open itscontacts and stop the circulator.4.If the boiler water temperature isbelow the circulator switch when thethermostat is turned up and calls forheat, the circulator should notoperate until the burner has heatedthe boiler water to the setting of thecirculator control. In the event thecirculator does not operate as out-lined above, then the circulatorcontrol is either improperly installedor faulty.

Chapter 12Limit Controls/Thermostats