David Chapman Copper Development Association [email protected] Copper Development Association Rating of Transformers supplying Harmonic-Rich Loads

Rating of Transformers supplying Harmonic Rich Loadsgo.leonardo-energy.org/rs/europeancopper/images/transformers... · Rating of Transformers supplying Harmonic-Rich Loads. ... Rating

Embed Size (px)

Citation preview

Page 1: Rating of Transformers supplying Harmonic Rich Loadsgo.leonardo-energy.org/rs/europeancopper/images/transformers... · Rating of Transformers supplying Harmonic-Rich Loads. ... Rating

David Chapman

Copper Development Association

[email protected]

Copper Development Association

Rating of Transformers supplying Harmonic-Rich Loads

Page 2: Rating of Transformers supplying Harmonic Rich Loadsgo.leonardo-energy.org/rs/europeancopper/images/transformers... · Rating of Transformers supplying Harmonic-Rich Loads. ... Rating

www.leonardo-energy.org

Copper Development Associationwww.cda.org.uk

Losses in Transformers

No-load loss (‘iron loss’)

– energy consumed in eddy current and

hysteresis loss

– present 100% of the time

Load losses

Resistive loss (‘copper loss’)

– dependent on square of load current

– most important during high load periods

Eddy current loss

Page 3: Rating of Transformers supplying Harmonic Rich Loadsgo.leonardo-energy.org/rs/europeancopper/images/transformers... · Rating of Transformers supplying Harmonic-Rich Loads. ... Rating

www.leonardo-energy.org

Copper Development Associationwww.cda.org.uk

Distribution transformer efficiency standardsHD 428 & 538

Source: CENELEC

Load Losses for DistributionTransformers

No-Load Losses for DistributionTransformers

RATEDPOWER

OIL-FILLED (HD428) UP TO24kV2)

DRY TYPE(HD538)

OIL-FILLED (HD428) UP TO24kV2)

DRY TYPE(HD538)

LIST A LIST B LIST C 12kVPRIMARY

3)

LIST A’ LIST B’ LIST C’ 12kVPRIMARY 3)

kVA W W W W W W W W

50 1,100 1,350 875 N/A 190 145 125 N/A

100 1,750 2,150 1,475 2,000 320 260 210 440

160 2,350 3,100 2,000 2,700 460 375 300 610

250 3,250 4,200 2,750 3,500 650 530 425 820

400 4,600 6,000 3,850 4,900 930 750 610 1,150

630 /4% 6,500 8,400 5,400 7,300 1,300 1,030 860 1,500

630 /6% 6,750 8,700 5,600 7,600 1,200 940 800 1,370

1000 10,500 13,000 9,500 10,000 1,700 1,400 1,100 2,000

1600 17,000 20,000 14,000 14,000 2,600 2,200 1,700 2,800

2500 26,500 32,000 22,000 21,000 3,800 3,200 2,500 4,300

Page 4: Rating of Transformers supplying Harmonic Rich Loadsgo.leonardo-energy.org/rs/europeancopper/images/transformers... · Rating of Transformers supplying Harmonic-Rich Loads. ... Rating

www.leonardo-energy.org

Copper Development Associationwww.cda.org.uk

Distribution transformer efficiency standardsHD 428 & 538

Source: CENELEC

Load Losses for DistributionTransformers

No-Load Losses for DistributionTransformers

RATEDPOWER

OIL-FILLED (HD428) UP TO24kV2)

DRY TYPE(HD538)

OIL-FILLED (HD428) UP TO24kV2)

DRY TYPE(HD538)

LIST A LIST B LIST C 12kVPRIMARY

3)

LIST A’ LIST B’ LIST C’ 12kVPRIMARY 3)

kVA W W W W W W W W

50 1,100 1,350 875 N/A 190 145 125 N/A

100 1,750 2,150 1,475 2,000 320 260 210 440

160 2,350 3,100 2,000 2,700 460 375 300 610

250 3,250 4,200 2,750 3,500 650 530 425 820

400 4,600 6,000 3,850 4,900 930 750 610 1,150

630 /4% 6,500 8,400 5,400 7,300 1,300 1,030 860 1,500

630 /6% 6,750 8,700 5,600 7,600 1,200 940 800 1,370

1000 10,500 13,000 9,500 10,000 1,700 1,400 1,100 2,000

1600 17,000 20,000 14,000 14,000 2,600 2,200 1,700 2,800

2500 26,500 32,000 22,000 21,000 3,800 3,200 2,500 4,300

BA’

Page 5: Rating of Transformers supplying Harmonic Rich Loadsgo.leonardo-energy.org/rs/europeancopper/images/transformers... · Rating of Transformers supplying Harmonic-Rich Loads. ... Rating

www.leonardo-energy.org

Copper Development Associationwww.cda.org.uk

Distribution transformer efficiency standardsHD 428 & 538

Source: CENELEC

Load Losses for DistributionTransformers

No-Load Losses for DistributionTransformers

RATEDPOWER

OIL-FILLED (HD428) UP TO24kV2)

DRY TYPE(HD538)

OIL-FILLED (HD428) UP TO24kV2)

DRY TYPE(HD538)

LIST A LIST B LIST C 12kVPRIMARY

3)

LIST A’ LIST B’ LIST C’ 12kVPRIMARY 3)

kVA W W W W W W W W

50 1,100 1,350 875 N/A 190 145 125 N/A

100 1,750 2,150 1,475 2,000 320 260 210 440

160 2,350 3,100 2,000 2,700 460 375 300 610

250 3,250 4,200 2,750 3,500 650 530 425 820

400 4,600 6,000 3,850 4,900 930 750 610 1,150

630 /4% 6,500 8,400 5,400 7,300 1,300 1,030 860 1,500

630 /6% 6,750 8,700 5,600 7,600 1,200 940 800 1,370

1000 10,500 13,000 9,500 10,000 1,700 1,400 1,100 2,000

1600 17,000 20,000 14,000 14,000 2,600 2,200 1,700 2,800

2500 26,500 32,000 22,000 21,000 3,800 3,200 2,500 4,300

C-C’

Page 6: Rating of Transformers supplying Harmonic Rich Loadsgo.leonardo-energy.org/rs/europeancopper/images/transformers... · Rating of Transformers supplying Harmonic-Rich Loads. ... Rating

www.leonardo-energy.org

Copper Development Associationwww.cda.org.uk

Full load losses in a 100kVA C-C’ transformer

12%

88%

Winding

Magnetic

Total loss = 1685 W

Page 7: Rating of Transformers supplying Harmonic Rich Loadsgo.leonardo-energy.org/rs/europeancopper/images/transformers... · Rating of Transformers supplying Harmonic-Rich Loads. ... Rating

www.leonardo-energy.org

Copper Development Associationwww.cda.org.uk

Full load losses in a 100kVA C-C’ transformer

79%

9%

12%

Resistance

Magnetic

Eddy current(10%)

Total loss = 1685 W

Page 8: Rating of Transformers supplying Harmonic Rich Loadsgo.leonardo-energy.org/rs/europeancopper/images/transformers... · Rating of Transformers supplying Harmonic-Rich Loads. ... Rating

www.leonardo-energy.org

Copper Development Associationwww.cda.org.uk

Full load losses in a 100kVA C-C’ transformer

84%

4%

12%

Resistance

Magnetic

Eddy Current(5%)

Total loss = 1685 W

Page 9: Rating of Transformers supplying Harmonic Rich Loadsgo.leonardo-energy.org/rs/europeancopper/images/transformers... · Rating of Transformers supplying Harmonic-Rich Loads. ... Rating

www.leonardo-energy.org

Copper Development Associationwww.cda.org.uk

Current waveform for a typical PC

-2.0000

-1.5000

-1.0000

-0.5000

0.0000

0.5000

1.0000

1.5000

2.0000

0 90 180 270 360

Degrees

Curr

ent (

A)

Page 10: Rating of Transformers supplying Harmonic Rich Loadsgo.leonardo-energy.org/rs/europeancopper/images/transformers... · Rating of Transformers supplying Harmonic-Rich Loads. ... Rating

www.leonardo-energy.org

Copper Development Associationwww.cda.org.uk

0.0000

0.1000

0.2000

0.3000

0.4000

0.5000

0.6000

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17

Harmonic

Cur

rent

(A)

Harmonic profile of a typical PC

Page 11: Rating of Transformers supplying Harmonic Rich Loadsgo.leonardo-energy.org/rs/europeancopper/images/transformers... · Rating of Transformers supplying Harmonic-Rich Loads. ... Rating

www.leonardo-energy.org

Copper Development Associationwww.cda.org.uk

Typical harmonic profile - 6 pulse converter

0

5

10

15

20

25

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25

Harmonic number

%

Page 12: Rating of Transformers supplying Harmonic Rich Loadsgo.leonardo-energy.org/rs/europeancopper/images/transformers... · Rating of Transformers supplying Harmonic-Rich Loads. ... Rating

www.leonardo-energy.org

Copper Development Associationwww.cda.org.uk

There are two issues that affect Transformers

supplying harmonic-rich loads:

• Triple-n harmonic currents circulate in delta windings,

increasing resistive losses, operating temperature and

reducing effective load capacity

• Harmonic currents, being of higher frequency, cause

increased magnetic losses in the core and increased

eddy current and skin effect losses in the windings

Effect of harmonics on transformers

Page 13: Rating of Transformers supplying Harmonic Rich Loadsgo.leonardo-energy.org/rs/europeancopper/images/transformers... · Rating of Transformers supplying Harmonic-Rich Loads. ... Rating

www.leonardo-energy.org

Copper Development Associationwww.cda.org.uk

Effect of triple-n harmonics in transformers

Triple-n harmonic currents circulate in delta windings - they do not propagate back onto the supply network

Page 14: Rating of Transformers supplying Harmonic Rich Loadsgo.leonardo-energy.org/rs/europeancopper/images/transformers... · Rating of Transformers supplying Harmonic-Rich Loads. ... Rating

www.leonardo-energy.org

Copper Development Associationwww.cda.org.uk

Harmonic mitigation by transformerDelta-star transformers

Page 15: Rating of Transformers supplying Harmonic Rich Loadsgo.leonardo-energy.org/rs/europeancopper/images/transformers... · Rating of Transformers supplying Harmonic-Rich Loads. ... Rating

www.leonardo-energy.org

Copper Development Associationwww.cda.org.uk

There are two issues that affect Transformers

supplying harmonic-rich loads:

• Triple-n harmonic currents circulate in delta windings,

increasing resistive losses, operating temperature and

reducing effective load capacity

• Harmonic currents, being of higher frequency, cause

increased magnetic losses in the core and increased

eddy current and skin effect losses in the windings

Effect of harmonics on transformers

Page 16: Rating of Transformers supplying Harmonic Rich Loadsgo.leonardo-energy.org/rs/europeancopper/images/transformers... · Rating of Transformers supplying Harmonic-Rich Loads. ... Rating

www.leonardo-energy.org

Copper Development Associationwww.cda.org.uk

Increased Eddy current losses in transformers

2

1

2maxhIPP

hh

hhefeh ∑=

=

=

where: Peh is the total eddy current lossPef is the eddy current loss at fundamental frequencyh is the harmonic orderIh is the per unit RMS current at harmonic h

Increased eddy current loss can be calculated by:

Page 17: Rating of Transformers supplying Harmonic Rich Loadsgo.leonardo-energy.org/rs/europeancopper/images/transformers... · Rating of Transformers supplying Harmonic-Rich Loads. ... Rating

www.leonardo-energy.org

Copper Development Associationwww.cda.org.uk

K-Rating of Transformers

There are two approaches to rating transformers supplying harmonic rich load:-

• Designing for the anticipated duty - e.g.theAmerican system, established by UL and manufacturers, which specifies harmonic capabilityof the transformer - known as K-factor.

• De-rating to survive the anticipated duty - e.g. the European system, developed by IEC, which defines de-rating factor for standard transformers - known as factor K.

Page 18: Rating of Transformers supplying Harmonic Rich Loadsgo.leonardo-energy.org/rs/europeancopper/images/transformers... · Rating of Transformers supplying Harmonic-Rich Loads. ... Rating

www.leonardo-energy.org

Copper Development Associationwww.cda.org.uk

K-Rating of Transformers - US System

2

1

2maxhIK

hh

hh∑=

=

=

where: h is the harmonic orderIh is the RMS current at h in per unit of total current

First, calculate the K factor of the load according to:

Page 19: Rating of Transformers supplying Harmonic Rich Loadsgo.leonardo-energy.org/rs/europeancopper/images/transformers... · Rating of Transformers supplying Harmonic-Rich Loads. ... Rating

www.leonardo-energy.org

Copper Development Associationwww.cda.org.uk

For this typical PC load, the K factor is 11.6

(For worked examples see LPQI AN 3.5.2 or IEE 1100 1992)

p y

0.0000

0.1000

0.2000

0.3000

0.4000

0.5000

0.6000

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17

Harmonic

Cur

rent

(A)

K-Rating of Transformers - US System

Page 20: Rating of Transformers supplying Harmonic Rich Loadsgo.leonardo-energy.org/rs/europeancopper/images/transformers... · Rating of Transformers supplying Harmonic-Rich Loads. ... Rating

www.leonardo-energy.org

Copper Development Associationwww.cda.org.uk

K-Rating of Transformers - US System

Next, a transformer with a higher K rating is selected from the standard range:

4, 9, 13, 20, 30, 40, 50

Page 21: Rating of Transformers supplying Harmonic Rich Loadsgo.leonardo-energy.org/rs/europeancopper/images/transformers... · Rating of Transformers supplying Harmonic-Rich Loads. ... Rating

www.leonardo-energy.org

Copper Development Associationwww.cda.org.uk

K-Rating of Transformers - European SystemIn Europe, the transformer de-rating factor is calculated according to the formulae in BS 7821 Part 4. The factor K is given by:

5.0

2

2

1

21

11

⎥⎥⎦

⎢⎢⎣

⎟⎟

⎜⎜

⎛⎟⎟⎠

⎞⎜⎜⎝

⎛⎟⎠⎞

⎜⎝⎛

++= ∑

=

+

Nn

n

nq

IIn

II

eeK

e is ratio of eddy current loss (50 Hz) to resistive loss

n is the harmonic order

q is dependent on winding type & frequency, typically 1.5 to 1.7

Page 22: Rating of Transformers supplying Harmonic Rich Loadsgo.leonardo-energy.org/rs/europeancopper/images/transformers... · Rating of Transformers supplying Harmonic-Rich Loads. ... Rating

www.leonardo-energy.org

Copper Development Associationwww.cda.org.uk

K-Rating of Transformers - European System

For the same PC load, the de-rating factor is 78%

p y

0.0000

0.1000

0.2000

0.3000

0.4000

0.5000

0.6000

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17

Harmonic

Cur

rent

(A)

Page 23: Rating of Transformers supplying Harmonic Rich Loadsgo.leonardo-energy.org/rs/europeancopper/images/transformers... · Rating of Transformers supplying Harmonic-Rich Loads. ... Rating

www.leonardo-energy.org

Copper Development Associationwww.cda.org.uk

0

2

4

6

8

10

12

14

16

1 2 5 10 20 41

No of Units (pairs)

K F

acto

r

Harmonic Diversity - K Factor

Page 24: Rating of Transformers supplying Harmonic Rich Loadsgo.leonardo-energy.org/rs/europeancopper/images/transformers... · Rating of Transformers supplying Harmonic-Rich Loads. ... Rating

www.leonardo-energy.org

Copper Development Associationwww.cda.org.uk

K-Rating - Calculation software

Page 25: Rating of Transformers supplying Harmonic Rich Loadsgo.leonardo-energy.org/rs/europeancopper/images/transformers... · Rating of Transformers supplying Harmonic-Rich Loads. ... Rating

www.leonardo-energy.org

Copper Development Associationwww.cda.org.uk

K-Rating - Calculation software

Page 26: Rating of Transformers supplying Harmonic Rich Loadsgo.leonardo-energy.org/rs/europeancopper/images/transformers... · Rating of Transformers supplying Harmonic-Rich Loads. ... Rating

www.leonardo-energy.org

Copper Development Associationwww.cda.org.uk

K-Rating - Calculation software

Page 27: Rating of Transformers supplying Harmonic Rich Loadsgo.leonardo-energy.org/rs/europeancopper/images/transformers... · Rating of Transformers supplying Harmonic-Rich Loads. ... Rating

www.leonardo-energy.org

Copper Development Associationwww.cda.org.uk

K-Rating - Calculation software

Page 28: Rating of Transformers supplying Harmonic Rich Loadsgo.leonardo-energy.org/rs/europeancopper/images/transformers... · Rating of Transformers supplying Harmonic-Rich Loads. ... Rating

www.leonardo-energy.org

Copper Development Associationwww.cda.org.uk

Full load losses in a 100kVA C-C’ transformer

41%53%

6%

Resistance

Magnetic

Eddy Current

Total loss = 3245 W

Page 29: Rating of Transformers supplying Harmonic Rich Loadsgo.leonardo-energy.org/rs/europeancopper/images/transformers... · Rating of Transformers supplying Harmonic-Rich Loads. ... Rating

www.leonardo-energy.org

Copper Development Associationwww.cda.org.uk

80% load losses in a 100kVA C-C’ transformer

39%51%

10%

Resistance

Magnetic

Eddy Current

Total loss = 2156 W

Page 30: Rating of Transformers supplying Harmonic Rich Loadsgo.leonardo-energy.org/rs/europeancopper/images/transformers... · Rating of Transformers supplying Harmonic-Rich Loads. ... Rating

www.leonardo-energy.org

Copper Development Associationwww.cda.org.uk

C11528.190PP

ttempWorkingf

k °=×=×=

⎟⎠⎞

⎜⎝⎛ ∂−

×=− 10t

2TtimeLife

( )

years72402TtimeLife 5.210

PPP

tf

fk

=×=×=− −⎟⎟⎟⎟⎟

⎜⎜⎜⎜⎜

⎛ −×

Effect of additional losses on life-time80 % load

Page 31: Rating of Transformers supplying Harmonic Rich Loadsgo.leonardo-energy.org/rs/europeancopper/images/transformers... · Rating of Transformers supplying Harmonic-Rich Loads. ... Rating

www.leonardo-energy.org

Copper Development Associationwww.cda.org.uk

70% load losses in a 100kVA C-C’ transformer

38%50%

12%

Resistance

Magnetic

Eddy Current

Total loss = 1699 W

Page 32: Rating of Transformers supplying Harmonic Rich Loadsgo.leonardo-energy.org/rs/europeancopper/images/transformers... · Rating of Transformers supplying Harmonic-Rich Loads. ... Rating

www.leonardo-energy.org

Copper Development Associationwww.cda.org.uk

C75.900083.190PP

ttempWorkingf

k °=×=×=

⎟⎠⎞

⎜⎝⎛ ∂−

×=− 10t

2TtimeLife

( )

years382402TtimeLife 075.010

PPP

tf

fk

=×=×=− −⎟⎟⎟⎟⎟

⎜⎜⎜⎜⎜

⎛ −×

Effect of additional losses on life-time70 % load

Page 33: Rating of Transformers supplying Harmonic Rich Loadsgo.leonardo-energy.org/rs/europeancopper/images/transformers... · Rating of Transformers supplying Harmonic-Rich Loads. ... Rating

www.leonardo-energy.org

Copper Development Associationwww.cda.org.uk

The real world

Selection and management

small change in loading - large effect on lifetime.

derate then add the ‘headroom’

management practices must maintain derating

for the life of the transformer when

– adding new loads

– making changes to any harmonic filters within the

installation

Page 34: Rating of Transformers supplying Harmonic Rich Loadsgo.leonardo-energy.org/rs/europeancopper/images/transformers... · Rating of Transformers supplying Harmonic-Rich Loads. ... Rating

David Chapman

Copper Development Association

[email protected]

Copper Development Association

www.cda.org.uk