Rack‐Stored Distilled Spirits Storage Protection
Presented by:
Jaap de Vries
John A. LeBlanc
FM Global
June 4, 2017
2017 NFPA Conference & Expo
FM Global
[Public]
2017 NFPA Conference & Expo
Rack-Stored Distilled Spirits Storage Protection
Jaap de Vries
John A. LeBlanc
FM Global
[Public]
2017 NFPA Conference & Expo
Overview
Introduction and history
Discussion of rack storage testing
Standards development discussion
2017 NFPA Conference & Expo 4 June 2017
FM Global 2
FM Global
[Public]
2017 NFPA Conference & Expo
Path to Defining Protection
2015 NFPA Conference– Palletized storage
• 7 tier high in a 30 ft (9 m) roof– Leakage testing
– Fire development
– Water transport
0
500
1000
1500
2000
2500
3000
3500
4000
4500
5000
5500
6000
0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300
Time (sec)
Ch
em
ica
l He
at
Re
lea
se R
ate
(kW
)
Alcohol Filled
Water Filled
FM Global
[Public]
2017 NFPA Conference & Expo
Palletized Results
Open area fraction is critical
Open area fraction = 6.7% Open area fraction: 13.5 - 17%
FM Global
[Public]
2017 NFPA Conference & Expo
Palletized Array Recommendation
Open Area Fractions = 13.5 – 17%– Palletized storage of distilled spirits ≤ 75% alcohol
– Stored up to seven tiers high in a 30 ft (9 m) roof
– Ceiling only protection• Wet systems
• K14.0 (K200), QR, 155oF (68oC), pendent sprinklers
– Density = 0.60 gpm/ft2 (24 mm/min)
2017 NFPA Conference & Expo 4 June 2017
FM Global 3
FM Global
[Public]
2017 NFPA Conference & Expo
Rack Storage
Unknowns– Open area fraction
– On-side barrel failure modes
– Impact of greater ceiling heights – 40 ft (12 m)
FM Global
[Public]
2017 NFPA Conference & Expo
ObjectivesFind adequate protection for… 9-tier-high Rack-stored distilled spirits 75% or greater alcohol content Oak-wood barrels 40 ft (12 m) ceilingUsing… Wet (1) or dry (2) pipe ceiling only sprinklers, or In-rack sprinklers (3)
FM Global
[Public]
2017 NFPA Conference & Expo
Rack Storage vs Palletized?
Fire loading
Barrel failure (vertical vs horizontal, barrels size)
Open Area Fraction (water transport)
Initial fire growth
Effect of increased ceiling height
2017 NFPA Conference & Expo 4 June 2017
FM Global 4
FM Global
[Public]
2017 NFPA Conference & Expo
Fire Loading
FM Global
[Public]
2017 NFPA Conference & Expo
Fire Loading Comparison
Liquid loading Total fire loading
12 tier (8-8) 7 tier 8 tier Palletized0
1000
2000
3000
4000
Liq
uid
load
ing
, gal
/ft2
Liqu
id lo
adi
ng,
L/m
2
Palletized
7 tier(Palletized)
0
20
40
60
80
12 tier (8-8) 7 tier 8 tier Palletized0
10k
20k
30k
40k
50k
60k
70k
80k
To
tal f
ire
loa
ding
, B
TU
/ft2
T
otal
fir
e lo
adin
g, M
J/m
2
Oak wood + Liquid (75% alcohol)
7 tierpaletized
0
1M
2M
3M
4M
5M
6M
7M
Palletized
FM Global
[Public]
2017 NFPA Conference & Expo
Single Barrel Tests
2017 NFPA Conference & Expo 4 June 2017
FM Global 5
FM Global
[Public]
2017 NFPA Conference & Expo
Single Barrel Tests
54 gal(200 L)
80 gal(300 L)
92 gal(350 L)
132 gal(500 L)
Four barrel sizes tested
FM Global
[Public]
2017 NFPA Conference & Expo
Single Barrel Tests Barrel protection is an industry-wide problem
FM Global
[Public]
2017 NFPA Conference & Expo
Barrel Surface Analysis
100% HD Camera 100% IR Camera50/50
2017 NFPA Conference & Expo 4 June 2017
FM Global 6
FM Global
[Public]
2017 NFPA Conference & Expo
Single Barrel Fire Test Results
0 1000 2000 30000
500
1000
1500
2000
2500
US made200 L
Time after ignition, s
Hea
t re
leas
e ra
te, k
W
Horizontal, full exposure Horizontal, half exposure Vertical, full exposure Vertical, half exposure
0 1000 2000 30000
500
1000
1500
2000
2500
Time after ignition, s
Hea
t re
leas
e ra
te, k
W
Horizontal, full exposure Horizontal, half exposure
US made300 L
0 1000 2000 30000
500
1000
1500
2000
2500
Time after ignition, s
He
at
rele
ase
rate
, kW
Horizontal, full exposure Horizontal, half exposure
US made500 L
54 gal (200 L) barrel tests 132 gal (500L) barrel tests80 gal (300 L) barrel tests
Leak rate does not lead to “catastrophic” increase in heat release rate
FM Global
[Public]
2017 NFPA Conference & Expo
Open Area Fraction
FM Global
[Public]
2017 NFPA Conference & Expo
Open Area Fraction
30 ft(9.1 m)
24 ft(7.3 m)
156 in(396 cm)
152 in(386 cm)
2017 NFPA Conference & Expo 4 June 2017
FM Global 7
FM Global
[Public]
2017 NFPA Conference & Expo
Open Area Fraction
0 100 200 300 400 500 600
0.0
0.1
0.2
0.3
0.4
dm/d
t, ga
l/s
Time, s
30 pt avg. smooth of Test 1 (K14, 100 gpm, dry) 30 pt avg. smooth of Test 1 (K14, 100 gpm, wet)
180 s
FM Global
[Public]
2017 NFPA Conference & Expo
Open Area Fraction
Open area fraction range between 16-18%
FM Global
[Public]
2017 NFPA Conference & Expo
Fire Development
2017 NFPA Conference & Expo 4 June 2017
FM Global 8
FM Global
[Public]
2017 NFPA Conference & Expo
Fire Development
FM Global
[Public]
2017 NFPA Conference & Expo
Findings, Palletized Versus Rack-StoredRack Stored (9 tier high) Palletized (7 tier high)
Fire Loading, BTU/ft2 (MJ/m2)
3.4 x 106 (3.8 x 104) 5.8 x 106 (6.6 x 104 )+74%
Fire Loading, gal/ft2 (L/m2 )
79 (1945) 129 (3173) +63%
Open Area Fraction
16%-18% 7%-17% ~Similar
Fire Growth
Comparable
FM Global
[Public]
2017 NFPA Conference & Expo
Ceiling Height
Rack Stored (9 tier high) Palletized (7 tier high)
Ceiling Height, ft (m)
40 (12) 30 (9.1) -25%
Increased ceiling height would impose the greatest uncertainty. Higher ceilings require higher water flows.
2017 NFPA Conference & Expo 4 June 2017
FM Global 9
FM Global
[Public]
2017 NFPA Conference & Expo
Selection of Initial Protection Point Protect barrels under a 40 ft (12 m) ceiling
– Ceiling only, wet pipe protection
– Flow set to 0.85 gpm/ft2 (34 mm/min )
– K14.0 (K200) or greater orifice FM-Approved sprinklers with a 165ºF (74ºC) operating temperature.
This protection option requires a full scale validation test.
FM Global
[Public]
2017 NFPA Conference & Expo
Large-Scale Design
FM Global
[Public]
2017 NFPA Conference & Expo
BackgroundLarge-Scale Test Design
[in.]cm
2017 NFPA Conference & Expo 4 June 2017
FM Global 10
FM Global
[Public]
2017 NFPA Conference & Expo
BackgroundLarge-Scale Test Design[in.]cm
FM Global
[Public]
2017 NFPA Conference & Expo
Large-Scale Test Design
FM Global
[Public]
2017 NFPA Conference & Expo
BackgroundLarge-Scale Test Design
2017 NFPA Conference & Expo 4 June 2017
FM Global 11
FM Global
[Public]
2017 NFPA Conference & Expo
BackgroundLarge-Scale Test Design, Commodity• Wood type: Oak,
• Formula: CH1.7O0.72N0.001
• Density: 35 lb/ft3 (560 kg/m3 )
• Hcomb: 7,300 BTU/lb (17.1 kJ/g )
• Capacity: 59 gal (225 L)
• Length: 37 in. (94 cm)
• Head diameter: 23 in. (58 cm)
• Bilge diameter 27 in. (68 cm)
FM Global
[Public]
2017 NFPA Conference & Expo
Additional Single Barrel Testing
FM Global
[Public]
2017 NFPA Conference & Expo
Additional Single Barrel Testing
2017 NFPA Conference & Expo 4 June 2017
FM Global 12
FM Global
[Public]
2017 NFPA Conference & Expo
Additional Single Barrel Testing
0 500 1000 1500 20000
50
100
HR
R
Time, s
Empty 9.3% MC Empty 6.2% MC Empty 12% MC
0 500 1000 1500 2000 25000
500
1000
1500
HR
R
Time, s
Empty 9.3% MC Empty 6.2% MC Empty 12% MC Full 9.5% MC Full 11% MC
FM Global
[Public]
2017 NFPA Conference & Expo
Protection design for first test
Test 1• K-factor: 14 gpm/psi1/2 (200 lpm/bar1/2 ) • Orientation: Pendent• RTI 45 ft1/2s1/2 (25 m1/2s1/2), QR• Temperature rating 165◦F (74◦C)• # sprinklers installed: 64• Sprinkler spacing: 10 ft x 10 ft (3.0 m x 3.0 m)• Discharge pressure: 37 psi (2.6 bar) • Per sprinkler discharge: 85 gpm (322 lpm)• Design density: 0.85 gpm/ft2 (34 mm/min )
Large-Scale Test Design, Test 1
FM Global
[Public]
2017 NFPA Conference & Expo
4510 gal (17000 L ) of 75/25% mixture
Tier 5-7Tier 1-4 Tier 8-9
Large-Scale Test Design
2017 NFPA Conference & Expo 4 June 2017
FM Global 13
FM Global
[Public]
2017 NFPA Conference & Expo
• 72 in. x 72 in pan (1.8 m x 1.8 m )
• 100% ethanol
• 20 gal (76 L) spill
• Centered among 4 sprinklers
Large-Scale Test Design
FM Global
[Public]
2017 NFPA Conference & Expo
BackgroundLarge-Scale Result, Test 1
FM Global
[Public]
2017 NFPA Conference & Expo
Protection design for first testTest 2• K-factor: 16.8 gpm/psi1/2 (240 lpm/bar1/2 ) • Orientation: Upright• RTI 214 ft1/2s1/2 (118 m1/2s1/2 ), SR• Temperature rating 286◦F (141◦C )• # sprinklers installed: 64• Sprinkler spacing: 10 ft x 10 ft (3.0 m x 3.0 m)• Discharge pressure: 25 psi (1.7 bar)• Per sprinkler discharge: 85 gpm (322 lpm)• Design density: 0.85 gpm/ft2 (34 mm/min)• Delay 40 seconds
Large-Scale Design, Test 2 (Dry Pipe)
2017 NFPA Conference & Expo 4 June 2017
FM Global 14
FM Global
[Public]
2017 NFPA Conference & Expo
BackgroundLarge-Scale Result, Test 2
FM Global
[Public]
2017 NFPA Conference & Expo
Protection design for first testTest 3, Ceiling• K-factor: 11.2 gpm/psi1/2 (160 lpm/bar1/2 ) • Orientation: Upright• RTI 199 ft1/2s1/2 (110 m1/2s1/2), SR• Temperature rating 286◦F (141◦C)• # sprinklers installed: 64• Sprinkler spacing: 10 ft x 10 ft (3.0 m x 3.0 m)• Discharge pressure: 25 psi (1.7 bar )• Per sprinkler discharge: 30 gpm (114 lpm)• Design density: 0.3 gpm/ft2 (12 mm/min)• Time delay 40 seconds
Large-Scale Design, Test 3 (IRAS)
FM Global
[Public]
2017 NFPA Conference & Expo
Protection design for first testTest 3, IRAS• K-factor: 8.0 gpm/psi1/2 (115 lpm/bar1/2 ) • Orientation: Upright• RTI ~45 ft1/2s1/2 (~25 m1/2s1/2), QR• Temperature rating 155◦F (68◦C)• # sprinklers installed: 13• Sprinkler spacing: 4 ft (1.2 m) on line• Discharge pressure: 32 psi (2.2 bar)• Per sprinkler discharge: 45 gpm (170 lpm)• Time delay 40 seconds
Large-Scale Design, Test 3 (Dry Pipe)
2017 NFPA Conference & Expo 4 June 2017
FM Global 15
FM Global
[Public]
2017 NFPA Conference & Expo
BackgroundLarge-Scale Design Test 3 (IRAS)
FM Global
[Public]
2017 NFPA Conference & Expo
BackgroundLarge-Scale Test Result Test 3
FM Global
[Public]
2017 NFPA Conference & Expo
BackgroundTest SummaryTest # Test 1 Test 2 Test 3
First/Last Ceiling Sprinkler Operation (min:s)
1:03/3:20 1:49/2:30 2:16/3:19
Total Ceiling Sprinklers Opened 4 15 3 (IRAS)
Peak Gas Temperature, oF (oC)and Time
497 (258)@ 1:03
1783 (973)@2:06
750 (399)@ 3:17
Maximum Steel TC Measurement and Time, oF (oC)
178 (81)@ 7:45
477 (248)@ 2:43
197 (92)@ 3:17
Test Termination Time Ignition (min:s)
30:00 10:00 12:00
2017 NFPA Conference & Expo 4 June 2017
FM Global 16
FM Global
[Public]
2017 NFPA Conference & Expo
Defining New Protection Standards
Palletized storage arrangements– 7 tiers high
– 30 ft (9 m) roof
– On-end barrels
– < 75% alcohol
FM Global
[Public]
2017 NFPA Conference & Expo
Defining New Protection Standards
Palletized storage arrangements– Creating open area fraction
• 13.5 - 17%
• Mandatory flue spaces– 6 in (150 mm) between all pallet rows
– Aisle spill fire protection• Dual sprinkler design
– 0.2 gpm/ft2 (8 mm/min) over aisle + draft curtain
• Band drums on pallet– One ceiling system
FM Global
[Public]
2017 NFPA Conference & Expo
Defining New Protection Standards
Palletized storage arrangements– Ceiling design
• K14.0 (K200), QR, 165oF (74oC), pendent sprinklers
• Density = 0.60 gpm/ft2 (24 mm/min)
– Wet and dry sprinkler system designs• Wet systems
– K14 (K200) / QR / 165oF (74oC)
• Dry systems– K16.8 (K240) / SR / 286oF (140oC)
– ????
2017 NFPA Conference & Expo 4 June 2017
FM Global 17
FM Global
[Public]
2017 NFPA Conference & Expo
Defining New Protection Standards
Rack storage array– 9 tiers high / 30 ft (9 m )
– 40 ft (12 m) roof
– On-side oak barrels
– < 75% alcohol
FM Global
[Public]
2017 NFPA Conference & Expo
Defining New Protection Standards
Standard metal frame rack– Metal walkways
– Open area fraction• 16-18%
FM Global
[Public]
2017 NFPA Conference & Expo
Defining New Protection Standards
Standard metal frame rack– Ceiling only protection
• Wet system– K14.0 (K200), QR, 165oF (74oC), pendent sprinklers
– 37 psi (2.5 bar) / 0.85 gpm/ft2 (34 mm/min)
• Dry system– 40 second water delivery
– K16.8 (K240), SR, 286oF (140oC), upright
– 25 psi (1.7 bar) / 0.85 gpm/ft2 (34 mm/min)
2017 NFPA Conference & Expo 4 June 2017
FM Global 18
FM Global
[Public]
2017 NFPA Conference & Expo
Defining New Protection Standards
Standard metal frame rack• Ceiling + in-rack protection
– Ceiling
» Dry system (40 second delay)
» K11.2 (K160), SR, 286oF (140oC)
» 25 psi (1.7 bar) / 0.3 gpm/ft2 (12 mm/min)
– In-rack
» 1 level above 8th tier / 30 ft (9 m)
» Dry system (40 second delay)
» K8.0 (K115), QR, 155oF (68oC)
» 32 psi (2.2 bar) / 45 gpm (95 L/min)
FM Global
[Public]
2017 NFPA Conference & Expo
Defining New Protection Standards
Standard metal frame rack• Ceiling + in-rack protection
– Extension to higher roof/storage heights
– Use a layer of in-rack sprinklers at a lower level
FM Global
[Public]
2017 NFPA Conference & Expo
Defining New Protection Standards
Rack storage array• Rick type
– Wooden frame, multiple floors
– Wooden walkways
» Loading aisle
» Sample aisles
2017 NFPA Conference & Expo 4 June 2017
FM Global 19
FM Global
[Public]
2017 NFPA Conference & Expo
Defining New Protection Standards
Rick storage array– Ceiling + in-rack protection
• Wooden walkways– IRAS below all
– Horizontal fire spread
• Metal grate walkways????– Use metal rack in-rack design
– Sprinklers below loading aisles
FM Global
[Public]
2017 NFPA Conference & Expo
Questions?
2017 NFPA Conference & Expo
CEUs: To receive CEUs for this session, scan yourbadge at the back of the room before leaving
Evaluation: Complete a session evaluation on the mobile app. (Search app store for ‘NFPA 2017 C&E.’)
Handouts: Handouts will be available via the mobile app and at nfpa.org/conference
Recordings: Audio recordings of all sessions will be available free of charge via NFPA Xchange.