2017 NFPA Conference & Expo 4 June 2017 FM Global 1 RackStored Distilled Spirits Storage Protection Presented by: Jaap de Vries John A. LeBlanc FM Global June 4, 2017 2017 NFPA Conference & Expo FM Global [Public] 2017 NFPA Conference & Expo Rack-Stored Distilled Spirits Storage Protection Jaap de Vries John A. LeBlanc FM Global [Public] 2017 NFPA Conference & Expo Overview Introduction and history Discussion of rack storage testing Standards development discussion

Rack Distilled Spirits Protection - National Fire Protection …/media/0820CC06DCAC453E9D8… ·  · 2018-02-28Large-Scale Design FM Global [Public] 2017 NFPA Conference & Expo Large-Scale

  • Upload
    vodien

  • View
    214

  • Download
    0

Embed Size (px)

Citation preview

2017 NFPA Conference & Expo 4 June 2017

FM Global 1

Rack‐Stored Distilled Spirits Storage Protection

Presented by:

Jaap de Vries

John A. LeBlanc

FM Global

June 4, 2017

2017 NFPA Conference & Expo

FM Global

[Public]

2017 NFPA Conference & Expo

Rack-Stored Distilled Spirits Storage Protection

Jaap de Vries

John A. LeBlanc

FM Global

[Public]

2017 NFPA Conference & Expo

Overview

Introduction and history

Discussion of rack storage testing

Standards development discussion

2017 NFPA Conference & Expo 4 June 2017

FM Global 2

FM Global

[Public]

2017 NFPA Conference & Expo

Path to Defining Protection

2015 NFPA Conference– Palletized storage

• 7 tier high in a 30 ft (9 m) roof– Leakage testing

– Fire development

– Water transport

0

500

1000

1500

2000

2500

3000

3500

4000

4500

5000

5500

6000

0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300

Time (sec)

Ch

em

ica

l He

at

Re

lea

se R

ate

(kW

)

Alcohol Filled

Water Filled

FM Global

[Public]

2017 NFPA Conference & Expo

Palletized Results

Open area fraction is critical

Open area fraction = 6.7% Open area fraction: 13.5 - 17%

FM Global

[Public]

2017 NFPA Conference & Expo

Palletized Array Recommendation

Open Area Fractions = 13.5 – 17%– Palletized storage of distilled spirits ≤ 75% alcohol

– Stored up to seven tiers high in a 30 ft (9 m) roof

– Ceiling only protection• Wet systems

• K14.0 (K200), QR, 155oF (68oC), pendent sprinklers

– Density = 0.60 gpm/ft2 (24 mm/min)

2017 NFPA Conference & Expo 4 June 2017

FM Global 3

FM Global

[Public]

2017 NFPA Conference & Expo

Rack Storage

Unknowns– Open area fraction

– On-side barrel failure modes

– Impact of greater ceiling heights – 40 ft (12 m)

FM Global

[Public]

2017 NFPA Conference & Expo

ObjectivesFind adequate protection for… 9-tier-high Rack-stored distilled spirits 75% or greater alcohol content Oak-wood barrels 40 ft (12 m) ceilingUsing… Wet (1) or dry (2) pipe ceiling only sprinklers, or In-rack sprinklers (3)

FM Global

[Public]

2017 NFPA Conference & Expo

Rack Storage vs Palletized?

Fire loading

Barrel failure (vertical vs horizontal, barrels size)

Open Area Fraction (water transport)

Initial fire growth

Effect of increased ceiling height

2017 NFPA Conference & Expo 4 June 2017

FM Global 4

FM Global

[Public]

2017 NFPA Conference & Expo

Fire Loading

FM Global

[Public]

2017 NFPA Conference & Expo

Fire Loading Comparison

Liquid loading Total fire loading

12 tier (8-8) 7 tier 8 tier Palletized0

1000

2000

3000

4000

Liq

uid

load

ing

, gal

/ft2

Liqu

id lo

adi

ng,

L/m

2

Palletized

7 tier(Palletized)

0

20

40

60

80

12 tier (8-8) 7 tier 8 tier Palletized0

10k

20k

30k

40k

50k

60k

70k

80k

To

tal f

ire

loa

ding

, B

TU

/ft2

T

otal

fir

e lo

adin

g, M

J/m

2

Oak wood + Liquid (75% alcohol)

7 tierpaletized

0

1M

2M

3M

4M

5M

6M

7M

Palletized

FM Global

[Public]

2017 NFPA Conference & Expo

Single Barrel Tests

2017 NFPA Conference & Expo 4 June 2017

FM Global 5

FM Global

[Public]

2017 NFPA Conference & Expo

Single Barrel Tests

54 gal(200 L)

80 gal(300 L)

92 gal(350 L)

132 gal(500 L)

Four barrel sizes tested

FM Global

[Public]

2017 NFPA Conference & Expo

Single Barrel Tests Barrel protection is an industry-wide problem

FM Global

[Public]

2017 NFPA Conference & Expo

Barrel Surface Analysis

100% HD Camera 100% IR Camera50/50

2017 NFPA Conference & Expo 4 June 2017

FM Global 6

FM Global

[Public]

2017 NFPA Conference & Expo

Single Barrel Fire Test Results

0 1000 2000 30000

500

1000

1500

2000

2500

US made200 L

Time after ignition, s

Hea

t re

leas

e ra

te, k

W

Horizontal, full exposure Horizontal, half exposure Vertical, full exposure Vertical, half exposure

0 1000 2000 30000

500

1000

1500

2000

2500

Time after ignition, s

Hea

t re

leas

e ra

te, k

W

Horizontal, full exposure Horizontal, half exposure

US made300 L

0 1000 2000 30000

500

1000

1500

2000

2500

Time after ignition, s

He

at

rele

ase

rate

, kW

Horizontal, full exposure Horizontal, half exposure

US made500 L

54 gal (200 L) barrel tests 132 gal (500L) barrel tests80 gal (300 L) barrel tests

Leak rate does not lead to “catastrophic” increase in heat release rate

FM Global

[Public]

2017 NFPA Conference & Expo

Open Area Fraction

FM Global

[Public]

2017 NFPA Conference & Expo

Open Area Fraction

30 ft(9.1 m)

24 ft(7.3 m)

156 in(396 cm)

152 in(386 cm)

2017 NFPA Conference & Expo 4 June 2017

FM Global 7

FM Global

[Public]

2017 NFPA Conference & Expo

Open Area Fraction

0 100 200 300 400 500 600

0.0

0.1

0.2

0.3

0.4

dm/d

t, ga

l/s

Time, s

30 pt avg. smooth of Test 1 (K14, 100 gpm, dry) 30 pt avg. smooth of Test 1 (K14, 100 gpm, wet)

180 s

FM Global

[Public]

2017 NFPA Conference & Expo

Open Area Fraction

Open area fraction range between 16-18%

FM Global

[Public]

2017 NFPA Conference & Expo

Fire Development

2017 NFPA Conference & Expo 4 June 2017

FM Global 8

FM Global

[Public]

2017 NFPA Conference & Expo

Fire Development

FM Global

[Public]

2017 NFPA Conference & Expo

Findings, Palletized Versus Rack-StoredRack Stored (9 tier high) Palletized (7 tier high)

Fire Loading, BTU/ft2 (MJ/m2)

3.4 x 106 (3.8 x 104) 5.8 x 106 (6.6 x 104 )+74%

Fire Loading, gal/ft2 (L/m2 )

79 (1945) 129 (3173) +63%

Open Area Fraction

16%-18% 7%-17% ~Similar

Fire Growth

Comparable

FM Global

[Public]

2017 NFPA Conference & Expo

Ceiling Height

Rack Stored (9 tier high) Palletized (7 tier high)

Ceiling Height, ft (m)

40 (12) 30 (9.1) -25%

Increased ceiling height would impose the greatest uncertainty. Higher ceilings require higher water flows.

2017 NFPA Conference & Expo 4 June 2017

FM Global 9

FM Global

[Public]

2017 NFPA Conference & Expo

Selection of Initial Protection Point Protect barrels under a 40 ft (12 m) ceiling

– Ceiling only, wet pipe protection

– Flow set to 0.85 gpm/ft2 (34 mm/min )

– K14.0 (K200) or greater orifice FM-Approved sprinklers with a 165ºF (74ºC) operating temperature.

This protection option requires a full scale validation test.

FM Global

[Public]

2017 NFPA Conference & Expo

Large-Scale Design

FM Global

[Public]

2017 NFPA Conference & Expo

BackgroundLarge-Scale Test Design

[in.]cm

2017 NFPA Conference & Expo 4 June 2017

FM Global 10

FM Global

[Public]

2017 NFPA Conference & Expo

BackgroundLarge-Scale Test Design[in.]cm

FM Global

[Public]

2017 NFPA Conference & Expo

Large-Scale Test Design

FM Global

[Public]

2017 NFPA Conference & Expo

BackgroundLarge-Scale Test Design

2017 NFPA Conference & Expo 4 June 2017

FM Global 11

FM Global

[Public]

2017 NFPA Conference & Expo

BackgroundLarge-Scale Test Design, Commodity• Wood type: Oak,

• Formula: CH1.7O0.72N0.001

• Density: 35 lb/ft3 (560 kg/m3 )

• Hcomb: 7,300 BTU/lb (17.1 kJ/g )

• Capacity: 59 gal (225 L)

• Length: 37 in. (94 cm)

• Head diameter: 23 in. (58 cm)

• Bilge diameter 27 in. (68 cm)

FM Global

[Public]

2017 NFPA Conference & Expo

Additional Single Barrel Testing

FM Global

[Public]

2017 NFPA Conference & Expo

Additional Single Barrel Testing

2017 NFPA Conference & Expo 4 June 2017

FM Global 12

FM Global

[Public]

2017 NFPA Conference & Expo

Additional Single Barrel Testing

0 500 1000 1500 20000

50

100

HR

R

Time, s

Empty 9.3% MC Empty 6.2% MC Empty 12% MC

0 500 1000 1500 2000 25000

500

1000

1500

HR

R

Time, s

Empty 9.3% MC Empty 6.2% MC Empty 12% MC Full 9.5% MC Full 11% MC

FM Global

[Public]

2017 NFPA Conference & Expo

Protection design for first test

Test 1• K-factor: 14 gpm/psi1/2 (200 lpm/bar1/2 ) • Orientation: Pendent• RTI 45 ft1/2s1/2 (25 m1/2s1/2), QR• Temperature rating 165◦F (74◦C)• # sprinklers installed: 64• Sprinkler spacing: 10 ft x 10 ft (3.0 m x 3.0 m)• Discharge pressure: 37 psi (2.6 bar) • Per sprinkler discharge: 85 gpm (322 lpm)• Design density: 0.85 gpm/ft2 (34 mm/min )

Large-Scale Test Design, Test 1

FM Global

[Public]

2017 NFPA Conference & Expo

4510 gal (17000 L ) of 75/25% mixture

Tier 5-7Tier 1-4 Tier 8-9

Large-Scale Test Design

2017 NFPA Conference & Expo 4 June 2017

FM Global 13

FM Global

[Public]

2017 NFPA Conference & Expo

• 72 in. x 72 in pan (1.8 m x 1.8 m )

• 100% ethanol

• 20 gal (76 L) spill

• Centered among 4 sprinklers

Large-Scale Test Design

FM Global

[Public]

2017 NFPA Conference & Expo

BackgroundLarge-Scale Result, Test 1

FM Global

[Public]

2017 NFPA Conference & Expo

Protection design for first testTest 2• K-factor: 16.8 gpm/psi1/2 (240 lpm/bar1/2 ) • Orientation: Upright• RTI 214 ft1/2s1/2 (118 m1/2s1/2 ), SR• Temperature rating 286◦F (141◦C )• # sprinklers installed: 64• Sprinkler spacing: 10 ft x 10 ft (3.0 m x 3.0 m)• Discharge pressure: 25 psi (1.7 bar)• Per sprinkler discharge: 85 gpm (322 lpm)• Design density: 0.85 gpm/ft2 (34 mm/min)• Delay 40 seconds

Large-Scale Design, Test 2 (Dry Pipe)

2017 NFPA Conference & Expo 4 June 2017

FM Global 14

FM Global

[Public]

2017 NFPA Conference & Expo

BackgroundLarge-Scale Result, Test 2

FM Global

[Public]

2017 NFPA Conference & Expo

Protection design for first testTest 3, Ceiling• K-factor: 11.2 gpm/psi1/2 (160 lpm/bar1/2 ) • Orientation: Upright• RTI 199 ft1/2s1/2 (110 m1/2s1/2), SR• Temperature rating 286◦F (141◦C)• # sprinklers installed: 64• Sprinkler spacing: 10 ft x 10 ft (3.0 m x 3.0 m)• Discharge pressure: 25 psi (1.7 bar )• Per sprinkler discharge: 30 gpm (114 lpm)• Design density: 0.3 gpm/ft2 (12 mm/min)• Time delay 40 seconds

Large-Scale Design, Test 3 (IRAS)

FM Global

[Public]

2017 NFPA Conference & Expo

Protection design for first testTest 3, IRAS• K-factor: 8.0 gpm/psi1/2 (115 lpm/bar1/2 ) • Orientation: Upright• RTI ~45 ft1/2s1/2 (~25 m1/2s1/2), QR• Temperature rating 155◦F (68◦C)• # sprinklers installed: 13• Sprinkler spacing: 4 ft (1.2 m) on line• Discharge pressure: 32 psi (2.2 bar)• Per sprinkler discharge: 45 gpm (170 lpm)• Time delay 40 seconds

Large-Scale Design, Test 3 (Dry Pipe)

2017 NFPA Conference & Expo 4 June 2017

FM Global 15

FM Global

[Public]

2017 NFPA Conference & Expo

BackgroundLarge-Scale Design Test 3 (IRAS)

FM Global

[Public]

2017 NFPA Conference & Expo

BackgroundLarge-Scale Test Result Test 3

FM Global

[Public]

2017 NFPA Conference & Expo

BackgroundTest SummaryTest # Test 1 Test 2 Test 3

First/Last Ceiling Sprinkler Operation (min:s)

1:03/3:20 1:49/2:30 2:16/3:19

Total Ceiling Sprinklers Opened 4 15 3 (IRAS)

Peak Gas Temperature, oF (oC)and Time

497 (258)@ 1:03

1783 (973)@2:06

750 (399)@ 3:17

Maximum Steel TC Measurement and Time, oF (oC)

178 (81)@ 7:45

477 (248)@ 2:43

197 (92)@ 3:17

Test Termination Time Ignition (min:s)

30:00 10:00 12:00

2017 NFPA Conference & Expo 4 June 2017

FM Global 16

FM Global

[Public]

2017 NFPA Conference & Expo

Defining New Protection Standards

Palletized storage arrangements– 7 tiers high

– 30 ft (9 m) roof

– On-end barrels

– < 75% alcohol

FM Global

[Public]

2017 NFPA Conference & Expo

Defining New Protection Standards

Palletized storage arrangements– Creating open area fraction

• 13.5 - 17%

• Mandatory flue spaces– 6 in (150 mm) between all pallet rows

– Aisle spill fire protection• Dual sprinkler design

– 0.2 gpm/ft2 (8 mm/min) over aisle + draft curtain

• Band drums on pallet– One ceiling system

FM Global

[Public]

2017 NFPA Conference & Expo

Defining New Protection Standards

Palletized storage arrangements– Ceiling design

• K14.0 (K200), QR, 165oF (74oC), pendent sprinklers

• Density = 0.60 gpm/ft2 (24 mm/min)

– Wet and dry sprinkler system designs• Wet systems

– K14 (K200) / QR / 165oF (74oC)

• Dry systems– K16.8 (K240) / SR / 286oF (140oC)

– ????

2017 NFPA Conference & Expo 4 June 2017

FM Global 17

FM Global

[Public]

2017 NFPA Conference & Expo

Defining New Protection Standards

Rack storage array– 9 tiers high / 30 ft (9 m )

– 40 ft (12 m) roof

– On-side oak barrels

– < 75% alcohol

FM Global

[Public]

2017 NFPA Conference & Expo

Defining New Protection Standards

Standard metal frame rack– Metal walkways

– Open area fraction• 16-18%

FM Global

[Public]

2017 NFPA Conference & Expo

Defining New Protection Standards

Standard metal frame rack– Ceiling only protection

• Wet system– K14.0 (K200), QR, 165oF (74oC), pendent sprinklers

– 37 psi (2.5 bar) / 0.85 gpm/ft2 (34 mm/min)

• Dry system– 40 second water delivery

– K16.8 (K240), SR, 286oF (140oC), upright

– 25 psi (1.7 bar) / 0.85 gpm/ft2 (34 mm/min)

2017 NFPA Conference & Expo 4 June 2017

FM Global 18

FM Global

[Public]

2017 NFPA Conference & Expo

Defining New Protection Standards

Standard metal frame rack• Ceiling + in-rack protection

– Ceiling

» Dry system (40 second delay)

» K11.2 (K160), SR, 286oF (140oC)

» 25 psi (1.7 bar) / 0.3 gpm/ft2 (12 mm/min)

– In-rack

» 1 level above 8th tier / 30 ft (9 m)

» Dry system (40 second delay)

» K8.0 (K115), QR, 155oF (68oC)

» 32 psi (2.2 bar) / 45 gpm (95 L/min)

FM Global

[Public]

2017 NFPA Conference & Expo

Defining New Protection Standards

Standard metal frame rack• Ceiling + in-rack protection

– Extension to higher roof/storage heights

– Use a layer of in-rack sprinklers at a lower level

FM Global

[Public]

2017 NFPA Conference & Expo

Defining New Protection Standards

Rack storage array• Rick type

– Wooden frame, multiple floors

– Wooden walkways

» Loading aisle

» Sample aisles

2017 NFPA Conference & Expo 4 June 2017

FM Global 19

FM Global

[Public]

2017 NFPA Conference & Expo

Defining New Protection Standards

Rick storage array– Ceiling + in-rack protection

• Wooden walkways– IRAS below all

– Horizontal fire spread

• Metal grate walkways????– Use metal rack in-rack design

– Sprinklers below loading aisles

FM Global

[Public]

2017 NFPA Conference & Expo

Questions?

2017 NFPA Conference & Expo

CEUs: To receive CEUs for this session, scan yourbadge at the back of the room before leaving

Evaluation: Complete a session evaluation on the mobile app. (Search app store for ‘NFPA 2017 C&E.’)

Handouts: Handouts will be available via the mobile app and at nfpa.org/conference

Recordings: Audio recordings of all sessions will be available free of charge via NFPA Xchange.