RA 1 Group
2007.01
System Appliances Division
Air Conditioning R&D Team
TRAIN MANUALTRAIN MANUAL- Vivace1 Inverter - - Vivace1 Inverter -
RA 1 Group
Inverter Air ConditionerInverter Air Conditioner
Operation Equivalent to LoadOperation Equivalent to Load: Changing the Capacity equivalent to Indoor Load.: Changing the Capacity equivalent to Indoor Load.
Outdoor Temperature
Ther
mal
Ene
rgy
ConvensionalHeat Pump
Variable SpeedHeat Pump
Space Load
Outdoor Temperature
Ther
mal
Ene
rgy
Space Load
High SpeedSystem Capacity
Low SpeedSystem Capacity
Move Balance Point
Space Load
Outdoor Temperature
Ther
mal
Ene
rgy System Capacity
Balance Point
RA 1 Group
AS12BPAN Residential Test For Cooling
0
5
10
15
20
25
30
35
40
0 60 120 180 240 300 360
Time(Min)
Roo
m T
emp.(
℃)
0
500
1000
1500
2000
2500
3000
3500
4000
4500
5000
Pow
er Input
(W)
Room Temp_AS12BPAN Room Temp_AS12HPAPower Input_AS12BPAN Integ Power Input_AS12BPANPower Input_AS12HPA Integ Power Input_AS12HPA
27℃ Setting 23℃ Setting25℃ Setting
InverterAS12BPAN
Non Inverter AS12HPA
Inverter Air ConditionerInverter Air Conditioner
Example )Example )
RA 1 Group
AS12BPAN Residential Test for Heating
0
5
10
15
20
25
30
0 60 120 180 240 300 360
Time(Min)
Room
Tem
p.(
℃)
0
500
1000
1500
2000
2500
3000
3500
4000
4500
5000
Pow
er Input
(W)
Room Temp_AS12BPAN Room Temp_AS12HPAPower Input_AS12BPAN Integ Power Input_AS12BPANPower Input_AS12HPA Integ Power Input_AS12HPA
InverterAS12BPAN
Non Inverter AS12HPA
Inverter Air ConditionerInverter Air Conditioner
Example )Example )
RA 1 Group
Inverter Air ConditionerInverter Air Conditioner
The Type of InverterThe Type of Inverter
Type Motor Wave Control
Method
Power
Control
Efficiency Noise
(sound)
Cost
AC
Inverter
Induction
Motor
Sin
Wave
V/F
ConstantNormal △ ○ High
DC
Inverter
Burshless
DC motor
Permanent Magnet Motor
120deg
RectangleSensorless PWM
Wide ○ △ Higher
Sin
Wave
180deg
Sensorless
Vector
Control
Wider ○ ○ Highest
RA 1 Group
Comparison of Inverter Line-UpComparison of Inverter Line-Up
LG
7K 9K 12K 18K 21K 24K 28K
Panasonic
Premium
Deluxe
Standard
Premium
Deluxe
Standard
Daikin Premium
Deluxe
Standard
SAMSUNG Premium
Deluxe
Standard
RA 1 Group
INDOOR OUTDOOR
Moderato1
Inv.
AQV09VBAN AQV09VBAX
AQV12VBAN AQV12VBAX
9,12kBtu/hr
AQV09VBAX
Outdoor Unit : WW type
4wire(E,L,N,C)
AC communication
AQV09VBAN
AQV12VBAX
4wire(E,L,N,C)
AC communication
AQV12VBAN
For Europe
Indoor Unit : Vivace1 type
Moderato1 InverterModerato1 Inverter
RA 1 Group
The Feature of Product – View of the UnitThe Feature of Product – View of the Unit
RA 1 Group
The Feature of Product – Remote ControlThe Feature of Product – Remote Control
RA 1 Group
The Feature of ProductThe Feature of Product
RA 1 Group
The Feature of Product – Good Morning ModeThe Feature of Product – Good Morning Mode
RA 1 Group
The Feature of Product – Silence ModeThe Feature of Product – Silence Mode
RA 1 Group
Product SpecificationProduct Specification
AQV09VBA AQV12VBA
Indoor Unit Outdoor Unit Indoor Unit Outdoor Unit
Type Wall-mounted Wall-mounted
Performance
Capacity Cooling kW
(Low / Std / Max)
0.99 / 2.5 / 3.5 0.99 / 3.50 / 4.20
Heating 0.85 / 3.5 / 5.0 0.85 / 4.00 / 5.50
RunningFrequency
Cooling Hz(Low / Std / Max)
20 / 46 / 70 20 / 71 / 93
Heating 20 / 67 / 95 20 / 77 / 102
Dehumidifying ℓ/h 1.4 1.8
Air Volume Cooling ㎥ /min
(H/M/L)
8.6/8.1/7.6 28 8.9/8.3/7.6 28
Heating 9.5/8.9/8.3 27 10.0/9.4/8.8 27
Noise Cooling dB
(H/L)
41/25 51 43/25 53
Heating 41/25 51 43/25 53
Energy Efficiency Ratio
Cooling W/W(Std)
4.10 [A Grade] 3.40 [A Grade]
Heating 4.10 [A Grade] 3.64 [A Grade]
Power ph-V-Hz 1-220/240-50 1-220/240-50
Power
Power Consumption
Cooling W(Low / Std / Max)
240 / 610 / 1030 240 / 1030 / 1450
Heating 210 / 853 / 1450 200 / 1100 / 1600
Operating Current
Cooling A(Low / Std / Max)
1.5 / 3.0 / 5.1 1.5 / 4.8 / 6.8
Heating 1.3 / 4.5 /6.9 1.3 / 5.2 / 7.4
Power Factor Cooling %
(Low / Std / Max)
75 / 90 / 95 75 / 90 / 95
Heating 75 / 90 / 95 75 / 90 / 95
Power Cord
Length m 2 2
Number of Core Wire 3 3
Capacity A 10 10
RA 1 Group
Product SpecificationProduct SpecificationAQV09VBA AQV12VBA
Indoor Unit Outdoor Unit Indoor Unit Outdoor Unit
Type Wall-mounted Wall-mounted
Size
Outer Dimension W x H x D mm 825 X 285 X 189 720 X 548 X 265 825 X 285 X 189 720 X 548 X 265
Weight (Net) kg 9.0 33.5 9.0 33.5
Refrigerant Pipe
Liquid mm x L(m) Φ6.35 x 5 Φ6.35 x 5
Gas mm x L(m) Φ9.52 x 5 Φ9.52 x 5
Max. Length m 15 15
Max. Height m 8 8
Drain Hose D x L(mm) Φ18 x 550 Φ18 x 550
Compressor
Type Rotary, G4C090LUBER Rotary, G4C090LUBER
Motor Type Hermetic Hermetic
Rated Output 853W 853W
Oil Type FREOLα68ES-T FREOLα68ES-T
Heat Exchanger 2 Row 14 Step 2 Row 24 Step 2 Row 14 Step 2 Row 24 Step
Refrigerant Control Unit EEV EEV
Freezer Oil Capacity cc 320 320
Refrigerant to Change (R410A) g 900 900
Cooling Test Condition Indoor Unit : DB27 WB 19℃ ℃ Outdoor Unit : DB35 WB 24℃ ℃
Heating Test Condition Indoor Unit : DB20 WB 15℃ ℃ Outdoor Unit : DB7 WB 6℃ ℃
Operation Condition Range
CoolingIndoor 16 ~ 32℃ ℃ 16 ~ 32℃ ℃
Outdoor 10 ~ 43℃ ℃ 10 ~ 43℃ ℃
HeatingIndoor 27 or less℃ 27 or less℃
Outdoor -10 ~ 24℃ ℃ -10 ~ 24℃ ℃
RA 1 Group
AccessoryAccessory
RA 1 Group
Exploded View and Parts List (INDOOR)Exploded View and Parts List (INDOOR)
RA 1 Group
Exploded View and Parts List (OUTDOOR)Exploded View and Parts List (OUTDOOR)
RA 1 Group
Disassembly & Reassembly (INDOOR)Disassembly & Reassembly (INDOOR)
RA 1 Group
Disassembly & Reassembly (INDOOR)Disassembly & Reassembly (INDOOR)
RA 1 Group
Disassembly & Reassembly (OUTDOOR)Disassembly & Reassembly (OUTDOOR)
RA 1 Group
Disassembly & Reassembly (OUTDOOR)Disassembly & Reassembly (OUTDOOR)
RA 1 Group
Option CodeOption Code
RA 1 Group
Refrigerating Cycle DiagramRefrigerating Cycle Diagram
RA 1 Group
Evaporator Cycle DiagramEvaporator Cycle Diagram
9,12K
RA 1 Group
Condenser Cycle DiagramCondenser Cycle Diagram
RA 1 Group
Wiring DiagramWiring Diagram
RA 1 Group
SYSTEM WIREMAX
LENGTHTERMINAL
AC Serial 4-wire
* Power 3 wire (L,N,E)•Serial 1 wire
(common use of Power-N line ) L N cross-connection makes Communication Error.
15m
N L C
From Indoor
- 27 -
CabinetEarthscrew
Communication System Communication System
RA 1 Group
9/12K BTU (AC)
Figure
2 PCBs
Terminal
Error
Display
MAIN
Board
- 28 -
Inverter ControllerInverter Controller
RA 1 Group
Inverter Controller (Block Diagram-INDOOR)Inverter Controller (Block Diagram-INDOOR)
RA 1 Group
Inverter Controller PCB (INDOOR)Inverter Controller PCB (INDOOR)
RA 1 Group
Inverter Controller (Block Diagram-OUTDOOR)Inverter Controller (Block Diagram-OUTDOOR)
RA 1 Group
Inverter Controller PCB (OUTDOOR)Inverter Controller PCB (OUTDOOR)
RA 1 Group
Filter CAPACITOR
RECTIFIERSRFI FILTER &SURGE SUPPLESSION
Reactor & PFC
SMPS
IPM
INVERTER & PFCCONTROLLER
SensorlessRotor PositionDetector
CompressorBLDC Motor
Cycle Controller
TemperatureSensor
FanMotorEEV
Communication
Driver
PowerPulg
INDOORUnit
Block Diagram of Outdoor Unit Inverter Controller
INVERTER partCONVERTER part230Vac
50Hz
310Vdc0-310V
6600rpm max
- 33 -
Inverter ElectronicsInverter Electronics
RA 1 Group
Intelligent Temperature Control Intelligent Temperature Control
Rapid Temperature Response
High Stability
High Reliability
Robust Fuzzy Control
RA 1 Group
1st HoldFrequency
Frequency
Time
Start ControlStart Control
2nd HoldFrequency
1st Holding Time = 1minute
Start FrequencyCase 1
Start FrequencyCase 2
Start FrequencyCase 3
Fuzzy Control
Fuzzy Control
Fuzzy Control
2nd Holding Time= 1minute
Fuzzy Control Interval= 1 minute
Compressor Rotation FrequencyCompressor Rotation Frequency
RA 1 Group
Protection Control – Protection Control – Overload ProtectionOverload Protection
T_Trip
T_Down
T_Hold
T_Up Release
Indoor unitHeat Exchanger
Temperature
Compressor Frequency Down Region
Prevent to RaiseCompressor Frequency
RA 1 Group
T_trip
T_down
T_hold
T_UpRelease
Discharge Temperature T[℃]
시간[s]
Prevent to raise Hz
Hz Down
C o mp T r i p
10min
stay
Hz Down
Protection Control Protection Control – – Discharge Temperature Over Heat ProtectionDischarge Temperature Over Heat Protection
RA 1 Group
Heating ModeCooling Mode
Current [A]
Hz Down (1Hz/2sec)
Hz Hold
50 30 Outdoor
Temperature[℃]
I_down_cool_30
I_down_cool_50
I_trip
I_down
2.0A
0.4A Hz Down (1Hz/2sec)
Hz Hold
10 50
Id′
I_Down_Heat_10
I_Down_Heat_50
I_trip
Current[A]
Outdoor Temperature
[℃]
Protection Control Protection Control – Over Current Protection– Over Current Protection
RA 1 Group
Protection Control – Protection Control – Freezing Evaporator ProtectionFreezing Evaporator Protection
RA 1 Group
Indoor Unit Display For Error DetectingIndoor Unit Display For Error Detecting
RA 1 Group
Outdoor LED Error DisplayOutdoor LED Error Display
RA 1 Group
Outdoor LED Error DisplayOutdoor LED Error Display
RA 1 Group
TroubleshootingTroubleshooting
RA 1 Group
RA 1 Group
RA 1 Group
RA 1 Group
RA 1 Group
RA 1 Group
RA 1 Group
RA 1 Group
RA 1 Group
Wiring Diagram (INDOOR)Wiring Diagram (INDOOR)
RA 1 Group
Wiring Diagram (OUTDOOR)Wiring Diagram (OUTDOOR)
RA 1 Group - 54 -
1. Temperature sensor off from the holder
Correct temperature detection can control the air conditioner
2. To loosen screws makes controller trouble
,especially Heat-Sink part
Check Point In ServiceCheck Point In Service
RA 1 Group - 55 -
3. Always putting silicon grease
on the surface between Power semiconductor and heat-sink
Also putting insulation mica on non insulated power semiconductor.
4. Confirm POWER OFF and LED OFF
before Connecting / Dis-Connecting BLDC FAN socket.
Connecting / Dis-connecting of BLDC FAN SOCKET can make
Damage to both PCB assy and BLDC FAN MOTOR (9K/12K model).
This cause troubles like fire, reset trouble, etc.
5. Make sure to connect power wire tightly
to the terminal block screw and OUTLET (power plug).
RA 1 Group
6. Make sure not to take of the seals stuck on Case Control
for making air flow through controller cool the heat-sink.
AIR FLOW
Into heatsink
7. KEEP CLEAR around air inlet of indoor unit.
Blocking air flow cause HIGH-LOAD CONDITION and error occurs
because of protecting inverter controller especially in heating
mode.