102
Type KAVR, KAVS, KVTR Auto-reclose and Check Synchronism Relays Service Manual R8505F

r8505f Kvar Kavs Kvtr

Embed Size (px)

Citation preview

Page 1: r8505f Kvar Kavs Kvtr

Type KAVR, KAVS, KVTR

Auto-reclose and Check Synchronism Relays

Service Manual

R8505F

Page 2: r8505f Kvar Kavs Kvtr
Page 3: r8505f Kvar Kavs Kvtr

HANDLING OF ELECTRONIC EQUIPMENT

A person�s normal movements can easily generate electrostatic potentials of several thousand volts. Discharge of these voltages into semiconductor devices when handling circuits can cause serious damage, which often may not be immediately apparent but the reliability of the circuit will have been reduced.

The electronic circuits of AREVA T&D products are immune to the relevant levels of electrostatic discharge when housed in their cases. Do not expose them to the risk of damage by withdrawing modules unnecessarily.

Each module incorporates the highest practicable protection for its semiconductor devices. However, if it becomes necessary to withdraw a module, the following precautions should be taken to preserve the high reliability and long life for which the equipment has been designed and manufactured.

1. Before removing a module, ensure that you are a same electrostatic potential as the equipment by touching the case.

2. Handle the module by its front-plate, frame, or edges of the printed circuit board. Avoid touching the electronic components, printed circuit track or connectors.

3. Do not pass the module to any person without first ensuring that you are both at the same electrostatic potential. Shaking hands achieves equipotential.

4. Place the module on an antistatic surface, or on a conducting surface which is at the same potential as yourself.

5. Store or transport the module in a conductive bag.

More information on safe working procedures for all electronic equipment can be found in BS5783 and IEC 60147-0F.

If you are making measurements on the internal electronic circuitry of an equipment in service, it is preferable that you are earthed to the case with a conductive wrist strap.

Wrist straps should have a resistance to ground between 500k � 10M ohms. If a wrist strap is not available you should maintain regular contact with the case to prevent the build up of static. Instrumentation which may be used for making measurements should be earthed to the case whenever possible.

AREVA T&D strongly recommends that detailed investigations on the electronic circuitry, or modification work, should be carried out in a Special Handling Area such as described in BS5783 or IEC 60147-0F.

Page 4: r8505f Kvar Kavs Kvtr
Page 5: r8505f Kvar Kavs Kvtr
Page 6: r8505f Kvar Kavs Kvtr
Page 7: r8505f Kvar Kavs Kvtr
Page 8: r8505f Kvar Kavs Kvtr
Page 9: r8505f Kvar Kavs Kvtr
Page 10: r8505f Kvar Kavs Kvtr
Page 11: r8505f Kvar Kavs Kvtr
Page 12: r8505f Kvar Kavs Kvtr
Page 13: r8505f Kvar Kavs Kvtr
Page 14: r8505f Kvar Kavs Kvtr
Page 15: r8505f Kvar Kavs Kvtr
Page 16: r8505f Kvar Kavs Kvtr
Page 17: r8505f Kvar Kavs Kvtr
Page 18: r8505f Kvar Kavs Kvtr
Page 19: r8505f Kvar Kavs Kvtr
Page 20: r8505f Kvar Kavs Kvtr
Page 21: r8505f Kvar Kavs Kvtr
Page 22: r8505f Kvar Kavs Kvtr
Page 23: r8505f Kvar Kavs Kvtr
Page 24: r8505f Kvar Kavs Kvtr
Page 25: r8505f Kvar Kavs Kvtr
Page 26: r8505f Kvar Kavs Kvtr
Page 27: r8505f Kvar Kavs Kvtr
Page 28: r8505f Kvar Kavs Kvtr
Page 29: r8505f Kvar Kavs Kvtr
Page 30: r8505f Kvar Kavs Kvtr
Page 31: r8505f Kvar Kavs Kvtr
Page 32: r8505f Kvar Kavs Kvtr
Page 33: r8505f Kvar Kavs Kvtr
Page 34: r8505f Kvar Kavs Kvtr
Page 35: r8505f Kvar Kavs Kvtr
Page 36: r8505f Kvar Kavs Kvtr
Page 37: r8505f Kvar Kavs Kvtr
Page 38: r8505f Kvar Kavs Kvtr
Page 39: r8505f Kvar Kavs Kvtr
Page 40: r8505f Kvar Kavs Kvtr
Page 41: r8505f Kvar Kavs Kvtr
Page 42: r8505f Kvar Kavs Kvtr
Page 43: r8505f Kvar Kavs Kvtr
Page 44: r8505f Kvar Kavs Kvtr
Page 45: r8505f Kvar Kavs Kvtr
Page 46: r8505f Kvar Kavs Kvtr
Page 47: r8505f Kvar Kavs Kvtr
Page 48: r8505f Kvar Kavs Kvtr
Page 49: r8505f Kvar Kavs Kvtr
Page 50: r8505f Kvar Kavs Kvtr
Page 51: r8505f Kvar Kavs Kvtr
Page 52: r8505f Kvar Kavs Kvtr
Page 53: r8505f Kvar Kavs Kvtr
Page 54: r8505f Kvar Kavs Kvtr
Page 55: r8505f Kvar Kavs Kvtr
Page 56: r8505f Kvar Kavs Kvtr
Page 57: r8505f Kvar Kavs Kvtr
Page 58: r8505f Kvar Kavs Kvtr
Page 59: r8505f Kvar Kavs Kvtr
Page 60: r8505f Kvar Kavs Kvtr
Page 61: r8505f Kvar Kavs Kvtr
Page 62: r8505f Kvar Kavs Kvtr
Page 63: r8505f Kvar Kavs Kvtr
Page 64: r8505f Kvar Kavs Kvtr
Page 65: r8505f Kvar Kavs Kvtr
Page 66: r8505f Kvar Kavs Kvtr
Page 67: r8505f Kvar Kavs Kvtr
Page 68: r8505f Kvar Kavs Kvtr
Page 69: r8505f Kvar Kavs Kvtr
Page 70: r8505f Kvar Kavs Kvtr
Page 71: r8505f Kvar Kavs Kvtr
Page 72: r8505f Kvar Kavs Kvtr
Page 73: r8505f Kvar Kavs Kvtr
Page 74: r8505f Kvar Kavs Kvtr
Page 75: r8505f Kvar Kavs Kvtr
Page 76: r8505f Kvar Kavs Kvtr
Page 77: r8505f Kvar Kavs Kvtr
Page 78: r8505f Kvar Kavs Kvtr
Page 79: r8505f Kvar Kavs Kvtr
Page 80: r8505f Kvar Kavs Kvtr
Page 81: r8505f Kvar Kavs Kvtr
Page 82: r8505f Kvar Kavs Kvtr
Page 83: r8505f Kvar Kavs Kvtr
Page 84: r8505f Kvar Kavs Kvtr
Page 85: r8505f Kvar Kavs Kvtr
Page 86: r8505f Kvar Kavs Kvtr
Page 87: r8505f Kvar Kavs Kvtr
Page 88: r8505f Kvar Kavs Kvtr
Page 89: r8505f Kvar Kavs Kvtr
Page 90: r8505f Kvar Kavs Kvtr
Page 91: r8505f Kvar Kavs Kvtr
Page 92: r8505f Kvar Kavs Kvtr
Page 93: r8505f Kvar Kavs Kvtr
Page 94: r8505f Kvar Kavs Kvtr
Page 95: r8505f Kvar Kavs Kvtr
Page 96: r8505f Kvar Kavs Kvtr
Page 97: r8505f Kvar Kavs Kvtr
Page 98: r8505f Kvar Kavs Kvtr
Page 99: r8505f Kvar Kavs Kvtr

Page 203

continued overleaf

REPAIR FORM

Please complete this form and return it to AREVA T&D with theequipment to be repaired. This form may also be used in the case of application queries.

AREVA T&D St. Leonards WorksStaffordST17 4LX,England

For: After Sales Service Department

Customer Ref: ________________________ Model No: _________________

Contract Ref: ________________________ Serial No: _________________

Date: ________________________

1. What parameters were in use at the time the fault occurred?

AC volts _____________ Main VT/Test set

DC volts _____________ Battery/Power supply

AC current _____________ Main CT/Test set

Frequency _____________

2. Which type of test was being used? ________________________________________

3. Were all the external components fitted where required? Yes/No(Delete as appropriate.)

4. List the relay settings being used

______________________________________________________________________

______________________________________________________________________

______________________________________________________________________

5. What did you expect to happen?

______________________________________________________________________

______________________________________________________________________

______________________________________________________________________

______________________________________________________________________

Page 100: r8505f Kvar Kavs Kvtr

Page 204

___________________________________ ____________________________________Signature Title

___________________________________ ____________________________________Name (in capitals) Company name

6. What did happen?

______________________________________________________________________

______________________________________________________________________

______________________________________________________________________

______________________________________________________________________

7. When did the fault occur?

Instant Yes/No Intermittent Yes/No

Time delayed Yes/No (Delete as appropriate).

By how long? __________

8. What indications if any did the relay show?

______________________________________________________________________

______________________________________________________________________

______________________________________________________________________

9. Was there any visual damage?

______________________________________________________________________

______________________________________________________________________

______________________________________________________________________

10. Any other remarks which may be useful:

______________________________________________________________________

______________________________________________________________________

______________________________________________________________________

Page 101: r8505f Kvar Kavs Kvtr
Page 102: r8505f Kvar Kavs Kvtr

AREVA T&D's Automation & Information Systems Business www.areva-td.com T&D Worldwide Contact Centre online 24 hours a day: +44 (0) 1785 25 00 70 http://www.areva-td.com/contactcentre/

Pub

licat

ion:

R85

05F