R7284U1004 Universal Digital Electronic Oil Primary Training Module. Agenda. R7284U Product Overview Key Features and Benefits Installation and Set Up Normal Operation Lockouts and Resetting Troubleshooting Error History Diagnostics Summary Product Cross Reference and Support Materials. - PowerPoint PPT Presentation

Citation preview

Page 1: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

R7284U1004 Universal Digital Electronic Oil Primary

Training Module

Page 2: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

2HONEYWELL - CONFIDENTIAL

Agenda

• R7284U Product Overview• Key Features and Benefits• Installation and Set Up• Normal Operation• Lockouts and Resetting• Troubleshooting• Error History• Diagnostics• Summary• Product Cross Reference and Support Materials

Page 3: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

3HONEYWELL - CONFIDENTIAL

R7284U Universal Electronic Oil Primary

• What is an Electronic Oil Primary?- It is a line voltage, safety rated,

primary control for residential oil fired burners used in boilers, forced air furnaces and water heaters.Applicable for use with both

hydronic and forced air systems.

- Used with a cad cell flame sensor, operates an oil burner and optional oil valve.

Universal Oil Primary Part Number:

R7284U1004

Page 4: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

4HONEYWELL - CONFIDENTIAL

R7284 Key Feature Summary

1. Diagnostics with actionable information

2. Error logging for “deep dive” troubleshooting when needed

3. Universal and Configurable

4. Real time status

5. Ease of Use

Integrated Display – No External Tool!

i

Page 5: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

5HONEYWELL - CONFIDENTIAL

R7284 Features - Diagnostics

• Diagnostics with actionable information- Igniter spark detection- Cad cell high during run- Cad cell adjustment/cleaning- Flame proven late in trial- Low voltage alarms

• Error history for “deep dive” troubleshooting

Last 10 errors What the error was How many cycles ago it occurred

• Diagnostic information can be hidden from homeowner view

• No external tool required!

Points the technician towards the cause of failure

i

Page 6: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

6HONEYWELL - CONFIDENTIAL

R7284 Features - Diagnostics with actionable information

• For the Oil Dealer- Reduce unnecessary part changing

- Reduce service contract costs

- Reduce customer costs

- Reduce call-backs

• For the technicians- No more head scratching in front of the

homeowner

- Show the homeowner why you’re changing the right part

- If lockout was due to voltage – show the homeowner why you’re not changing anything!

Improve Customer Service and the Bottom Line

i

Page 7: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

7HONEYWELL - CONFIDENTIAL

R7284U Features

• Universal compatibility- This control replaces Beckett, Carlin, White Rodgers

and most prior Honeywell Residential Oil Primary Controls

- Can be used as an interrupted or an intermittent control- One OS# covers the full range of timing offerings- One control covers 15, 30, 45 second lockout

timings

• Field Adjustable valve-on delay, trial for ignition (lockout times), and blower-off delay- Valve-on delay 0 to 30 seconds in 5 second increments

- Trial for ignition selectable 15, 30 or 45 seconds

- Blower-off delay 0 to 8 minutes in 15 second increments

• Pump priming cycle

• Limited recycle

i

Page 8: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

8HONEYWELL - CONFIDENTIAL

Much more than adding a display to the control!

i

R7284 Features – Competitive Comparison

Page 9: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

9HONEYWELL - CONFIDENTIAL

R7284U Display Key Features

• English, Spanish, French language alpha-numeric display- Current system status

- Cad Cell reading

- Diagnostic information

- Field adjustable setup of the control – data can be hidden from homeowner view

RUNNING

200 OHMS

Page 10: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

10HONEYWELL - CONFIDENTIAL

Additional R7284U Features

•Recessed wiring pocket creates more space near the quick connect terminals

•Safe start check – check for flame presence prior to lighting the burner

•Compatible with power venters without integral timers

•Oil-resistant plastic cover for electronics

•EnviraCOMTM communications enabled:- Includes EnviraCOM™ Connection for local networking & diagnostics

-Compatible with the Honeywell EnviraLINK™ remote monitoring application, which enables dealers to monitor their customers systems remotely.

Page 11: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

11HONEYWELL - CONFIDENTIAL

Control Layout

EnviraCOM™ Communications

Data Port

EnviraCOM™

Terminals.

T-T Terminals

i Button – Reset, and access diagnostic history

Alpha-Numeric Display – 16 character two line display and Buttons –

Adjust timings and

access error history

information on display

Page 12: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

12HONEYWELL - CONFIDENTIAL

Control Layout

Recessed Spade Terminals – control

mounts more easily on junction box

Spade Terminals – L2 and Cad Cell

Recessed Wiring Pocket – Creates more wiring space in the junction box

Spade Terminals –

Igniter, Motor, Valve,

Limit, and L1

Page 13: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

Set-Up

Page 14: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

14HONEYWELL - CONFIDENTIAL

Hold all three buttons at once for 3 seconds to enter setup menuSelect CONT. with arrow buttons and press the i button to continue

Set-Up of the R7284U

STANDBYINSTALLER SETUP

QUIT [CONT.]

i

Page 15: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

15HONEYWELL - CONFIDENTIAL

Select desired language: English, French or Spanish using the arrow buttons

Select CONT. with arrow buttons and press the i button to continue

Set-Up of the R7284U

LANGUAGE

[ENG] FR ESP

i

Page 16: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

16HONEYWELL - CONFIDENTIAL

VALVE ON DELAY

0:10

VALVE ON DELAY

0:00

VALVE ON DELAY

0:05

VALVE ON DELAY

0:15

Set-Up of the R7284U

Adjust valve on delay with the up and down arrows.Press the i button to continue

i

Page 17: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

17HONEYWELL - CONFIDENTIAL

IGNITION TIME

0:30

Set-Up of the R7284U

• This option allows you to adjust the trial for ignition time or lockout timing by selecting 15, 30 or 45 seconds

Adjust the trial for ignition timing with the up and down arrows.Press the i button to continue

i

Page 18: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

18HONEYWELL - CONFIDENTIAL

IGNITION TIME

LOCKED

Set-Up of the R7284U

• The ignition time is only adjustable during the first 100 cycles. After this time pressing the up or down arrow will display the “LOCKED” message

i

Page 19: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

19HONEYWELL - CONFIDENTIAL

BURNER OFF DELAY

3:45

Set-Up of the R7284U

Adjust burner motor off delay with the up and down arrows.Press the i button to continue

BURNER OFF DELAY

4:00

i

Page 20: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

20HONEYWELL - CONFIDENTIAL

TT CONFIGURED

[NO] YES

Set-Up of the R7284U

• This option allows you to configure the TT terminals with an internal “jumper”

• Setting allows the R7284U1004 to replace controls where line voltage stats are used or the TT call goes to the aquastat.

Select NO or YES with the up and down arrows.Press the i button to continue

i

Page 21: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

21HONEYWELL - CONFIDENTIAL

SPARK IN ON DELAY

[NO] YES

Set-Up of the R7284U

• This option allows you have the igniter spark during the valve on delay timing

Select NO or YES with the up and down arrows.Press the i button to continue

i

Page 22: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

22HONEYWELL - CONFIDENTIAL

SPARK DURING RUN

[NO] YES

Set-Up of the R7284U

• The option allows to setup the control for interrupted or intermittent operation

• By selecting NO, the control will function as an interrupted control, sparking the igniter only during the trial for ignition

• Selecting YES will cause intermittent functionality, sparking the igniter during the entire run cycle

• Interrupted ignition uses less electricity and also reduces the amount of wear and cleaning/replacement needed of an electrodes

Select NO or YES with the up and down arrows.Press the i button to continue

i

Page 23: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

23HONEYWELL - CONFIDENTIAL

• The ALLOWED RESETS menu give the installer the opportunity to select the number lockouts the unit can enter before entering restricted lockout

• 0, 1, 3 or unlimited lockouts can be selected• Lockout requires the i button to be held for 2 seconds to reset• Restricted lockout requires the i button to be held for 10

seconds before reset

ALLOWED RESETS

0 1 [3] NOLIMIT

Set-Up of the R7284U

Adjust number of allowed resets with the up and down arrows.Press the i button to continue

ALLOWED RESETS

0 [1] 3 NOLIMIT

i

Page 24: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

24HONEYWELL - CONFIDENTIAL

Set-Up of the R7284U

• This menu allows the user to configure the appliance configuration for specific EnviraCOM messages

• Boiler, Furnace or Water Heater are the selectable options• This setting is only needed if the unit is part of an EnviraCOM

communicating system

Select the type of appliance for the oil primary application Boiler, Furnace or Water Heater.

Press the i button to continue

APPLIANCE TYPE

[BLR] FURN WH

i

Page 25: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

25HONEYWELL - CONFIDENTIAL

SHOW DIAGNOSTICS

[NO] YES

Set-Up of the R7284U

• The Show Diagnostics menu allows the technician to give access to the diagnostic information during normal operation or keep it hidden

• Selecting YES allows the diagnostic information to be view during normal operation

• Selecting NO does allows the information to be viewed only in the installer mode

Select NO or YES with the up and down arrows.Press the i button to continue

i

Page 26: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

26HONEYWELL - CONFIDENTIAL

INSTALLER SETUP

[QUIT]CONT.

Set-Up of the R7284U

INSTALLER SETUP

QUIT [CONT.]

Select QUIT with arrow buttons and press the i button to continue

i

Page 27: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

27HONEYWELL - CONFIDENTIAL

RE-BASELINE?

[NO] YES

Set-Up of the R7284U

• Once QUIT is selected the user is prompted to RE-BASELINE the control

• Selecting YES restarts the the averaging process for the Cad Cell reading and Ignition Time

• Selecting NO continues to use the averages that have already been established

Select QUIT with arrow buttons and press the i button to continue

STANDBY

i

Page 28: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

28HONEYWELL - CONFIDENTIAL

R7284U Default Setting

• Menu- Language

- Valve On Delay

- Ignition Time (Lockout)

- Burner Motor Off Delay

- TT Configured On

- Spark In On Delay

- Spark During Run

- Allowed Resets

- Appliance Type

- Show Diagnostics

- Re-Baseline

• Factory Default- English

- 0 seconds

- 15 seconds

- 0 seconds

- No

- No

- No

- 3

- Boiler

- Yes

- No

Page 29: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

Normal Operation

Page 30: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

30HONEYWELL - CONFIDENTIAL

R7284U Normal Operation

• In Idle mode the R7284 shows

STANDBY

Page 31: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

31HONEYWELL - CONFIDENTIAL

R7284U Normal Operation

• When there is a call for heat

CALL FOR HEAT

Page 32: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

32HONEYWELL - CONFIDENTIAL

VALVE ON DELAY

0:0

VALVE ON DELAY

0:5

VALVE ON DELAY

0:4

VALVE ON DELAY

0:3

VALVE ON DELAY

0:2

VALVE ON DELAY

0:1

R7284U Normal Operation

• The valve on delay will then begin a countdown• For example a 5 second valve on delay would show

Page 33: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

33HONEYWELL - CONFIDENTIAL

IGNITION TRIAL

0:15

IGNITION TRIAL

0:14

IGNITION TRIAL

0:13

IGNITION TRIAL

0:12

IGNITION TRIAL

0:11

IGNITION TRIAL

0:10

R7284U Normal Operation

• Next the trial for ignition will begin• The display will countdown until the time runs out

or flame is established

Page 34: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

34HONEYWELL - CONFIDENTIAL

IGNITION TRIAL

0:10

PUMP PRIME

1:10

R7284U Normal Operation – Pump Priming

• Pressing “up” during the trial for ignition enables the pump priming mode

• Every press up the up button adds a minute to the trial for ignition timing up to 10 minutes

Page 35: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

35HONEYWELL - CONFIDENTIAL

R7284U Normal Operation

• Once flame is proven we will see this message along with the ohms reading

FLAME PROVEN

255 OHMS

Page 36: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

36HONEYWELL - CONFIDENTIAL

R7284U Normal Operation

• The display will then show status as running until the call for heat ends

• The ohms will change based on the strength of the flame

RUNNING

255 OHMS

RUNNING

300 OHMS

RUNNING

311 OHMS

Page 37: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

37HONEYWELL - CONFIDENTIAL

BURNER OFF DELAY

0:05

BURNER OFF DELAY

0:04

BURNER OFF DELAY

0:03

BURNER OFF DELAY

0:02

BURNER OFF DELAY

0:01

BURNER OFF DELAY

0:00

R7284U Normal Operation

• Once the call for heat ends the control will display the burner motor off delay countdown

• The display will countdown until the time runs out

Page 38: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

38HONEYWELL - CONFIDENTIAL

R7284U Normal Operation

• Once completed the display will return to standby

STANDBY

Page 39: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

Lockouts and Resettingthe R7284U

Page 40: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

40HONEYWELL - CONFIDENTIAL

Soft Lockout

• Soft Lockouts are entered for the following reasons- Failed ignition attempt line voltage less than alarm level

- Burner relay failure

SOFT LOCKOUT

Page 41: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

41HONEYWELL - CONFIDENTIAL

Soft Lockout

SOFT LOCKOUT

15:00

• Soft Lockouts automatically exit after the lockout period expires

• The countdown is not displayed until the error clears

• User can exit soft lockout by holding the i button for longer than 2 seconds

SOFT LOCKOUT

14:59

SOFT LOCKOUT

14:58

SOFT LOCKOUT

14:57

Page 42: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

42HONEYWELL - CONFIDENTIAL

Hard Lockout

• Hard Lockouts are entered for the following Reasons- A failed ignition attempt

- Flame sensed during valve on delay

- Flame sensed during the burner off delay

- Welded burner relay

- Exceeding the maximum number of recycles

HARD LOCKOUT

Page 43: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

43HONEYWELL - CONFIDENTIAL

Hard Lockout

• The unit remains in Hard Lockout until:- User presses and holds the i button 2 seconds

- Remote Reset signal is received via EnviraCOM™

HARD LOCKOUT

Page 44: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

44HONEYWELL - CONFIDENTIAL

Restricted Hard Lockout

• Each Hard Lockout instance is counted by the control

• When the specified number is reached the control goes into Restricted Hard Lockout

LOCKOUT

CALL SERVICE

Page 45: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

45HONEYWELL - CONFIDENTIAL

Restricted Hard Lockout

• Restricted Hard Lockout can only be exited by holding the i button for longer than 10 seconds

LOCKOUT

CALL SERVICE

Page 46: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

Troubleshooting

Page 47: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

47HONEYWELL - CONFIDENTIAL

R7284U Troubleshooting

• If Ignition did not occur and the cannot determine why the following will be displayed

NO IGNITION

Page 48: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

48HONEYWELL - CONFIDENTIAL

R7284U Troubleshooting

• If no ignition occurred and the R7284 cannot detect the spark igniter

NO IGNITION

CHECK IGNITER

Page 49: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

49HONEYWELL - CONFIDENTIAL

R7284U Troubleshooting

• If no ignition occurs and the Cad Cell shifts significantly during the trial for ignition but did not reach the establish flame threshold the following is displayed

NO IGNITION

CHECK CAD CELL

Page 50: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

50HONEYWELL - CONFIDENTIAL

R7284U Troubleshooting

• If the voltage drops below the minimum threshold the following is displayed

LOW VOLTAGE

30% LOW

Page 51: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

51HONEYWELL - CONFIDENTIAL

R7284U Troubleshooting

• If Flame is lost more than the allowed number of times

EXCEEDED

MAX RECYCLES

Page 52: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

52HONEYWELL - CONFIDENTIAL

R7284U Troubleshooting

• Flame was sensed during the valve on delay period

FLAME PROVEN

DURING ON DELAY

Page 53: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

53HONEYWELL - CONFIDENTIAL

R7284U Troubleshooting

• Flame was sensed during the burner motor off delay period

FLAME PROVEN

DURING OFF DELAY

Page 54: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

54HONEYWELL - CONFIDENTIAL

R7284U Troubleshooting

• When an internal error is sensed such as an A/D failure, relay failure, etc.

• The control will need to be replaced

INTERNAL ERROR

Page 55: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

55HONEYWELL - CONFIDENTIAL

R7284U Troubleshooting

• If the Enviracom bus is shorted or there is a bad circuit

ENVIRACOM ERROR

Page 56: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

56HONEYWELL - CONFIDENTIAL

R7284U Troubleshooting

• If flame is proven late in 2 consecutive trials the following message is displayed

FLAME PROVEN

LATE IN TRIAL

Page 57: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

57HONEYWELL - CONFIDENTIAL

R7284U Troubleshooting

• When the cad cell resistance is high during the last run cycle.

CAD CELL

HIGH DURING RUN

Page 58: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

58HONEYWELL - CONFIDENTIAL

R7284U Troubleshooting

• If flame has been present in idle mode for longer than 1 hour

FLAME PROVEN

OUT OF SEQUENCE

Page 59: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

Error History

Page 60: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

60HONEYWELL - CONFIDENTIAL

Error History

• Control saves the last 10 errors• Accessing error history:

STANDBY

and Buttons –

Access error history

during normal operation

i Button – Press during error history to return to normal operation

Page 61: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

61HONEYWELL - CONFIDENTIAL

Error History Menu

Press UP or DOWN to view the error history

STANDBYERROR 1NO IGNITIONLAST CYCLE

Press UP to go to the next errorr

i

The control will automatically cycle through 3 screens

Advance to next slide

Page 62: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

62HONEYWELL - CONFIDENTIAL

5

CYCLES AGO

ERROR 2NO IGNITION

CHECK CAD CELL

Error History Menu

Press UP to go to the next error

i

Advance to next slide

The control will automatically cycle through 3 screens

Page 63: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

63HONEYWELL - CONFIDENTIAL

ERROR HISTORY

END

Error History Menu

Press i to return to the normal operating status

STANDBY

i

Page 64: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

Diagnostics

Page 65: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

65HONEYWELL - CONFIDENTIAL

Diagnostic Information

• View current status• Access baseline information• Cycle count information• Info can be hidden from Homeowner

STANDBY

i Button – Press during normal operation to access information

Page 66: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

66HONEYWELL - CONFIDENTIAL

STANDBY

Diagnostic Information

Press the i button at any time to access the system information

i

Page 67: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

67HONEYWELL - CONFIDENTIAL

TT OPEN

LIMIT OPEN

System Status

• The first menu shows the current status of the TT and Limit Inputs

Pressing the i button will advance to the current Cad Cell reading

i

Page 68: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

68HONEYWELL - CONFIDENTIAL

CAD CELL

75265 OHMS

VIEW HISTORY

[NO] YES

System Status

Pressing the i button again will advance to the view history option if it was enabled in the installer setup

i

VIEW HISTORY

NO [YES]

• Selecting YES allows the Technician to view the current reading, average of last 10 and the baseline reading for the Cad Cell and Trial for Ignition timingPress i to continue

Page 69: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

69HONEYWELL - CONFIDENTIAL

CAD CELL

System History

• The Cad Cell screen will automatically scroll through 4 screens• The baseline readings are calculated base on the average of

the first 500 cyclesPressing the i during any of the screens will advance to the ignition timing

i

LAST CYCLE

480 OHMS

LAST 10 CYCLES

410 OHMS

BASELINE

380 OHMS

Page 70: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

70HONEYWELL - CONFIDENTIAL

IGNITION TIMELAST CYCLE

12 SECONDS

LAST 10 CYCLES

11 SECONDS

BASELINE

8 SECONDS

System History

• The Ignition Time screen will automatically scroll through 4 screens

Pressing the i during any of the screens will advance to the cycle counts

i

Page 71: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

71HONEYWELL - CONFIDENTIAL

68686

BURNER CYCLES

8688 CYCLES

SINCE BASELINE

5 RECYCLES

SINCE BASELINE

4 LOCKOUTS

SINCE BASELINE

System History

• The Cycle Count screen will automatically scroll through 4 screens

Pressing the i during any of the screens will advance to the view history screen

i

Page 72: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

Summary

Page 73: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

73HONEYWELL - CONFIDENTIAL

R7284 Key Feature Summary

1. Diagnostics with actionable information

2. Error logging for “deep dive” troubleshooting when needed

3. Universal and configurable

4. Real time status

5. Easy of use

Integrated Display – No External Tool!

i

Page 74: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

74HONEYWELL - CONFIDENTIAL

R7284 Features - Diagnostics

• Diagnostics with actionable information- Igniter spark detection- Cad cell high during run- Cad cell adjustment/cleaning- Flame proven late in trial- Low voltage alarms

• Error history for “deep dive” troubleshooting

Last 10 errors What the error was How many cycles ago it occurred

• Diagnostic information can be hidden from homeowner view

• No external tool required!

Points the technician towards the cause of failure

i

Page 75: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

75HONEYWELL - CONFIDENTIAL

R7284 Features - Diagnostics with actionable information

• For the Oil Dealer- Reduce unnecessary part changing

- Reduce service contract costs

- Reduce customer costs

- Reduce call-backs

• For the technicians- No more head scratching in front of the

homeowner

- Show the homeowner why you’re changing the right part

- If lockout was due to voltage – show the homeowner why you’re not changing anything!

Points the technician towards the cause of failure

i

Page 76: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

Product Cross Reference and Support Materials

Page 77: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

77HONEYWELL - CONFIDENTIAL

Product Cross Reference

• Where do I find Honeywell universal electronic oil primary cross reference information?- www.customer.honeywell.com

- Honeywell Application Selection and Cross Reference Guide – Form 63-9575

- Honeywell Laminated Truck Visor – Form 63-9581O

- Technicians Quick Reference Guide Form 69-2500

- Honeywell Residential Technical Support: 1-800-468-1502

63-9575

63-9581O

69-2500

Page 78: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

78HONEYWELL - CONFIDENTIAL

Oil Primary Cross Reference Table

This chart can be found in the Residential Combustion Application Guide: Form #63-9575

Page 79: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

79HONEYWELL - CONFIDENTIAL

www.customer.honeywell.com

• See Cross Reference Search box in right column.

Page 80: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

R7284U Universal Digital Electronic Oil Primary

Knowledge Test

Page 81: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

81HONEYWELL - CONFIDENTIAL

R7284U Oil Primary Knowledge Test

• Now that you completed this training module, take the short quiz to test your knowledge.

Page 82: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

82HONEYWELL - CONFIDENTIAL

Test

1. The R7284U can be used in both hydronic and forced air systems? T or F

2. The Honeywell R7284U can replace most prior Honeywell oil primary controls, as well as Carlin and White Rodgers controls? T or F

3. The display on the R7284U provides real-time status and cad cell readings in ohms? T of F

4. The R7284U has adjustable lockout times of 15, 30 or 45 seconds? T or F

5. The pump priming cycle requires that the installer be present at the oil primary to purge the line? T or F

Page 83: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

83HONEYWELL - CONFIDENTIAL

Test

6. Limited reset prevents the homeowner from continually pressing the reset button instead of calling for service? T or F

7. The display can identify system lockout and potential cause of failure? T or F

8. The valve on and blower off delay times are factory set and cannot be set by the installer during installation? T or F

9. The limited recycle features can help prevent clogging the heat exchanger or flooding? T or F

10.A separate external tool is required to retrieve information from the R7284U1004 oil primary? T or F

Page 84: R7284U1004 Universal Digital Electronic Oil Primary  Training Module

84HONEYWELL - CONFIDENTIAL

Answer Key

1. T2. T3. T4. T5. F – techs can add time to the trial for ignition6. T7. T8. F – timings are field configurable by the tech9. T10.F – no tool is required, info provided on display