Read carefully the instructions published in this manual before the first use of the level meter. Keep the manual at a safe place. The manufacturer reserves the right to implement changes without prior notice. INSTRUCTION MANUAL průmyslová elektronika RADAR LEVEL METERS WITH GUIDED WAVE GRLM – 70 valid for firmware version 2.X

R METE RS GUIDED WAVE GRLM 70 - Dinel€¦ · PG1 1 OK 46 G1" E200 ... E3000 15 4x 6 E200 ... E3000 4x otvor 6 29 28 180 19 312 62 24 24 E1000 ... E40000 E1000 ... E12000 29 24 24

  • Upload
    others

  • View
    0

  • Download
    0

Embed Size (px)

Citation preview

Page 1: R METE RS GUIDED WAVE GRLM 70 - Dinel€¦ · PG1 1 OK 46 G1" E200 ... E3000 15 4x 6 E200 ... E3000 4x otvor 6 29 28 180 19 312 62 24 24 E1000 ... E40000 E1000 ... E12000 29 24 24

Read carefully the instructions published in this manual before the first use of the level meter. Keep the manual at a safe place. The manufacturer reserves the right to implement changes without prior notice.

INSTRUCTION MANUALprůmyslová elektronika

RadaR level meteRs with guided wave gRlm – 70

valid for firmware version 2.X

Page 2: R METE RS GUIDED WAVE GRLM 70 - Dinel€¦ · PG1 1 OK 46 G1" E200 ... E3000 15 4x 6 E200 ... E3000 4x otvor 6 29 28 180 19 312 62 24 24 E1000 ... E40000 E1000 ... E12000 29 24 24
Page 3: R METE RS GUIDED WAVE GRLM 70 - Dinel€¦ · PG1 1 OK 46 G1" E200 ... E3000 15 4x 6 E200 ... E3000 4x otvor 6 29 28 180 19 312 62 24 24 E1000 ... E40000 E1000 ... E12000 29 24 24

Table of conTenTs

1 .  Measuring principle .................................................................................................................3

2 .  Range of applications ..............................................................................................................3

3 .  Features of variants .................................................................................................................4

4 .  Dimensional drawings .............................................................................................................4

5 .  Installation and putting into operation ...................................................................................6

6.    Installation instructions ..........................................................................................................6

7.  Electrical connection ...............................................................................................................12

8 .  Set-up elements .......................................................................................................................13

9.  Status signalization ..................................................................................................................13

10.  Setting .....................................................................................................................................14

10.1 . Basicsettings ...................................................................................................................14

10.2 . Servicesettings ...............................................................................................................17

10.3 . Additionalfunctions ..........................................................................................................19

11.  HART® communication protocol ...........................................................................................21

12.  The installation of the custom measuring electrode, 

  exchange or shortening of the electrode ..............................................................................22

13.  Order code ..............................................................................................................................24

14.  Accessories ............................................................................................................................24

15.  Safety, protection and compatibility ....................................................................................24

16.  Use, manipulation and maintenance ....................................................................................25

17.  Marking of labels ....................................................................................................................25

18.  Menu structure........................................................................................................................27

19 .  Specifications .........................................................................................................................28

Page 4: R METE RS GUIDED WAVE GRLM 70 - Dinel€¦ · PG1 1 OK 46 G1" E200 ... E3000 15 4x 6 E200 ... E3000 4x otvor 6 29 28 180 19 312 62 24 24 E1000 ... E40000 E1000 ... E12000 29 24 24

GRLM–70 © Dinel, s.r.o.3

1 .  Measuring principleThe GRLM® radar level meters arecompactmeasurementdevicesincludingantransmitterofmicrowavepulses,centralprocessorunitanddisplaymodule.Theelectronicstransmitsveryshortelectricalpulses(0.5ns),whicharelinkedtoaone-wiretransmissionline(measuringelectrode).Measuringelectrodecanbecreatedofrodorrope.Thepulsepropagatesalongtheelectrodeintheformofelectromagneticwavetowardthelevelsurface,whereitispartlyreflectedandthereflectedcomponent is returned to thereceivingmoduleof theelectronics.Theelectronicsmeasures thetimeofflightofelectromagneticwaveand theinstantdistancetothesurfaceleveliscalculated.Accordingtothelevelheight,thelevelmeteroutputissetandthemeasuredvalueisdisplayedonthedisplay.

2 .  range of applicaTionsRadar levelmeters with guidedwave are suited to continuous levelmesurement of variousliquid,mushandbulk-solidmaterials.Levelmetersareresistantagainstchangesintheatmos-phere(pressure,temperature,dust,steam)andtochangesinmediumparameters(changeindi-electricconstant,conductivity).

All operations described in this instruction manual have to be carried out only by trained personnel or an accredited person. Warranty and post warranty service must be exclusively carried out by the manufacturer.

Improper use, installation or set-up of the level meter can result in crashes in the application (overfilling of the tank or damage of system components).

The manufacturer is not responsible for improper use, losses of work caused by either direct or indirect damage, and for expenses incurred during installation or use of the level meter.

safeTy

Alert, warning, danger

Thissymbolinformsyouaboutparticularlyimportantinstructionsforinstallationandoperationofequipmentordangeroussituationsthatmayoccurduringtheinstalla-tionandoperation.Notobservingtheseinstructionsmaycausedisturbance,dam-ageordestructionofequipmentormaycauseinjury

Information

Thissymbolindicatesparticularlyimportantcharacteristicsofthedevice.

Note

Thissymbolindicateshelpfuladditionalinformation.

Valid for:

IntheborderarethetypesGRLM,forwhichisintendedthechapter.all types

used syMbols

Toensuremaximumsafetyofcontrolprocesses,wehavedefinedthefollowingsafetyinstructionsandinformation.Eachinstructionislabeledwiththeappropriatepictogram.

Page 5: R METE RS GUIDED WAVE GRLM 70 - Dinel€¦ · PG1 1 OK 46 G1" E200 ... E3000 15 4x 6 E200 ... E3000 4x otvor 6 29 28 180 19 312 62 24 24 E1000 ... E40000 E1000 ... E12000 29 24 24

4© Dinel, s.r.o. GRLM–70

3 .  feaTures of varianTs

4 .  diMensional drawings

97

70

27

62

2014

var.

�10:

E20

0 ...

E50

00va

r.�1

2: E

200

... E

3000

E200

... E

3000

E100

0 ...

E20

000

46

15

4x 6

var.

�10:

E30

0 ...

E80

00va

r.�1

1(12

): E3

00 ..

. E20

0024

E100

0 ...

E40

000

4

PG11

OK 46

G1"

15

E200

... E

3000

15

4x 6

15E200

... E

3000

4x otvor 6

29

2818

019

312

62

24

24E1

000

... E

4000

0

E100

0 ...

E12

000

29

24

24

20

24E1

000

... E

4000

0

24E

3434

40

GRLM–70_–00

GRLM  –70_–00 without electrode,theelectrodeismadebycustomer(onlyvariant10or30)andconnectedtotheelectrodejunctionbyM8thread.

GRLM  –70_–10 Uncoated stainless steel rod electrode, forlevelmeasurementliquidsandbulksolidmaterials(water,watersolutions,emulsion,oils,diesel,flour,sand,granulates,etc.).Maximumelectrodelength8m.

GRLM –70_–11 Fully coated stainless steel rod electrode (PFA Teflon®), forlevelmeasurementofaggressiveliquidsandverypureliquids. Maximumelectrodelength2m.

GRLM –70_–12 Fully coated stainless steel rod electrode (FEP Teflon®), forlevelmeasurementofaggressiveliquidsanddrinks. Maximumelectrodelength2m.

GRLM –70_–20 Uncoated stainless steel rod electrode with reference tube, foraccuratelevelmeasurementofliquidsincrampedspaces.Maximumelectrodelength3m.

GRLM –70_–30 Uncoated stainless steel rope electrode and weight, forlevelmeasurementofliquidsandbulksolidmaterials(water,grains,sand,flour,cement,etc.)inhighersilos,vessels,reservoirs.Maximumelectrodelength40m.

GRLM –70_–32 Fully coated stainless steel rope electrode and coated weight, forlevelmeasurementofaggressiveliquidsandverypureliquids.Maximumelectrodelength12m.

GRLM –70_–33 Uncoated stainless steel rope electrode with anchorage, forlevelmeasurementofbulksolidmaterials(grains,flour,cement,etc.)inhighersilos,vessels.Maximumelectrodelength40m.

Page 6: R METE RS GUIDED WAVE GRLM 70 - Dinel€¦ · PG1 1 OK 46 G1" E200 ... E3000 15 4x 6 E200 ... E3000 4x otvor 6 29 28 180 19 312 62 24 24 E1000 ... E40000 E1000 ... E12000 29 24 24

GRLM–70 © Dinel, s.r.o.5

97

70

27

62

20 14

var.�10: E200 ... E5000var.�12: E200 ... E3000

E200 ... E3000

E1000 ... E20000

46

15

4x

6

var.�10: E300 ... E8000var.�11(12): E300 ... E200024

E1000 ... E40000

4

PG11

OK

46

G1"

15

E200 ... E3000

15

4x

6

15

E200 ... E3000

4x o

tvor

6

29

28 180 19

312

62

24

24 E1000 ... E40000

E1000 ... E12000

29

24

24

20

24 E1000 ... E40000

24 E

3434

40

GRLM

–70_–10(11,12)

GRLM

–70_–20

97

70

27

62

20 14

var.�10: E200 ... E5000var.�12: E200 ... E3000

E200 ... E3000

E1000 ... E20000

46

15

4x

6

var.�10: E300 ... E8000var.�11(12): E300 ... E200024

E1000 ... E40000

4

PG11

OK

46

G1"

15

E200 ... E3000

15

4x

6

15

E200 ... E3000

4x o

tvor

6

29

28 180 19

312

62

24

24 E1000 ... E40000

E1000 ... E12000

29

24

24

20

24 E1000 ... E40000

24 E

3434

40

GRLM

–70_–30(33)

97

70

27

62

20 14

var.�10: E200 ... E5000var.�12: E200 ... E3000

E200 ... E3000

E1000 ... E20000

46

15

4x

6

var.�10: E300 ... E8000var.�11(12): E300 ... E200024

E1000 ... E40000

4

PG11

OK

46

G1"

15

E200 ... E3000

15

4x

6

15

E200 ... E3000

4x o

tvor

6

29

28 180 19

312

62

24

24 E1000 ... E40000

E1000 ... E12000

29

24

24

20

24 E1000 ... E40000

24 E

3434

40

97

70

27

62

20 14

var.�10: E200 ... E5000var.�12: E200 ... E3000

E200 ... E3000

E1000 ... E20000

46

15

4x

6

var.�10: E300 ... E8000var.�11(12): E300 ... E200024

E1000 ... E40000

4

PG11

OK

46

G1"

15

E200 ... E3000

15

4x

6

15

E200 ... E3000

4x o

tvor

6

29

28 180 19

312

62

24

24 E1000 ... E40000

E1000 ... E12000

29

24

24

20

24 E1000 ... E40000

24 E

3434

40

vysokoteplotní provedení

GRLM

–70_T

97

70

27

62

20 14

var.�10: E200 ... E5000var.�12: E200 ... E3000

E200 ... E3000

E1000 ... E20000

46

15

4x

6

var.�10: E300 ... E8000var.�11(12): E300 ... E200024

E1000 ... E40000

4

PG11

OK

46

G1"

15

E200 ... E3000

15

4x

6

15

E200 ... E30004x

otv

or

629

28 180 19

312

62

24

24 E1000 ... E40000

E1000 ... E12000

29

24

24

20

24 E1000 ... E40000

24 E

3434

40GRLM

–70_–32

Ancho

ring eye for 

varia

nt  G

RLM

-70_-33

97

70

2762

20 14

var.�10: E200 ... E5000var.�12: E200 ... E3000

E200 ... E3000

E1000 ... E20000

46

15

4x

6

var.�10: E300 ... E8000var.�11(12): E300 ... E200024

E1000 ... E40000

4

PG11

OK

46

G1"

15

E200 ... E3000

15

4x

6

15

E200 ... E3000

4x o

tvor

6

29

28 180 19

312

62

24

24 E1000 ... E40000

E1000 ... E12000

29

24

24

20

24 E1000 ... E40000

24 E

3434

40

electr

ode

holde

r

electr

ode

4x h

ole

Page 7: R METE RS GUIDED WAVE GRLM 70 - Dinel€¦ · PG1 1 OK 46 G1" E200 ... E3000 15 4x 6 E200 ... E3000 4x otvor 6 29 28 180 19 312 62 24 24 E1000 ... E40000 E1000 ... E12000 29 24 24

6© Dinel, s.r.o. GRLM–70

BASIC INFORMATIONS

• Install the levelmeter into the upper lid of thetankorreservoirusingawelding flange orfas-tering nut.

•   Themin.distancetoinstallthelevelmeterintoalidoraceilingofatankfromthetankwall isgivenintableright.

• Otherwise, the levelmeter installas faraspo-ssiblefromthewalls,tothemiddlebetweenthewallandtheverticalinlet,seeFig.1.a2.

type of wall d(without ref. tube)

d(with ref. tube)

metal ≥ 300 mm any distance

non-metal ≥ 500 mm any distance

Pleasefollownext3steps:

•  insTallaTion

•  elecTrical connecTion

•  seTTing

5 .  insTallaTion and puTTing inTo operaTion

6 .  insTallaTion insTrucTions

E = m + t + k E = m + t + zall types

Fig. 1: Level meter installation with the rod electrode

Fig. 2: Level meter installation with the rope electrode

E – The length of rope electrodet – Measuring rangem – Dead zone on the beginning of electrodek – Dead zone on the end of electrodez – The lengt of weight (110 mm)d – The distance from the tank wall (min. 300 mm)

Page 8: R METE RS GUIDED WAVE GRLM 70 - Dinel€¦ · PG1 1 OK 46 G1" E200 ... E3000 15 4x 6 E200 ... E3000 4x otvor 6 29 28 180 19 312 62 24 24 E1000 ... E40000 E1000 ... E12000 29 24 24

GRLM–70 © Dinel, s.r.o.7

DEAD ZONE

• Inconnectionwith themeasurementprinciple, thesignals reflected in thearea justunder thelevelmetercannotbeevaluated.The zone(Fig.3and4)determinesthemin.distancepossiblebetweenthelevelmeterandthehighestsurfacelevel. Itisnecessarytoinstallthelevelmetersothatthebinlevelcannotinterferewiththedeadzonewhenfilleduptothemaximumordepletetotheminimum.Ifthemeasuredlevelinterfereswiththedeadzone,thelevelmeterwillnotworkproperly.

• Thesizeofthedeadzoneisaffectedbythesetmeasurementsensitivity.Theminimumdistan-cestothemedium(deadzones)arepresentedinthetablesbelow.

Fig. 3: Level meter dead zone with rod electrode

Fig. 4: Level meter dead zone with rope electrode

measurement sensitivity m k

(rod electrode)k

(rope electrode)low, medium, user (1 - 4) 100 mm 0 mm 110 mm

high, user (5) 150 mm 50 mm 110 mm

user (6, 7) 200 mm 50 mm 110 mm

user (8) 250 mm 50 mm 110 mm

INPUT NECK

• Forcorrectmeasurement it is important toavoid in-stallation in thehighneck.Forshortneckarereco-mmendednextconditions:a<b,b>50mm,whereaistheNeckheightandbistheNeckwidth a ≤ b

b ≥ 50 mma – neck heightb – neck width

Fig. 5: Level meter installation in the input neck

If you can not eliminate all interference, which could affect the measurement of level, it is recommended to use the procedure "TEACHING" (see chap. 10.2 Service settings). This procedure sets the level meter to mode, which suppresses false reflections.

all types

all types

except GRLM-70_-20

Page 9: R METE RS GUIDED WAVE GRLM 70 - Dinel€¦ · PG1 1 OK 46 G1" E200 ... E3000 15 4x 6 E200 ... E3000 4x otvor 6 29 28 180 19 312 62 24 24 E1000 ... E40000 E1000 ... E12000 29 24 24

8© Dinel, s.r.o. GRLM–70

• The end of the socket or the welding flangemust not have an extension into the tankinFig.6.

CONCTRETE SILO

• Forinstallationofthelevelmeteronaconcreteroofthediameterboftheholemustbegreaterthanthethicknessaoftheconcrete,seeFig.8.

• Ifthethicknessaoftheconcreteisgreaterthanthediameterbofthehole,installthelevelmeterinarecess,see.Fig.9.

a < b

NON-METAL TANK

• Forlevelmeterinstallationinnon-conductive tanksitisnecessarytouseametalsheet(dia-metralgreaterthan200mm)beneaththepro-cessfittingwhenscrewingitin.Makesurethatthe plate has direct contact with the processfitting.

Fig. 6: Incorrect welding flange mounting to the tank

Fig. 7: Incorrect welding flange mounting to the tank

Fig. 8: Level meter installation on the roof of the concrete silo

Fig. 9: Level meter installation on the roof of the concrete silo

all types

except GRLM-70_-20

all types

except GRLM-70_-20

Fig. 10: Solar radiation shielding cover

all typesLEVEL METER PROTECTION

• Thelevelmetermustnotbeinstalledinplaceswithdirectsolar radiationandmustbeprotectedagainstweathereffects.

• Iftheinstallationinplaceswithdirectsolarradiationisinevitable,itisnecessarytomountashielding cover abovethelevelmeter.

GRLM-70_-30, 32, 33

Page 10: R METE RS GUIDED WAVE GRLM 70 - Dinel€¦ · PG1 1 OK 46 G1" E200 ... E3000 15 4x 6 E200 ... E3000 4x otvor 6 29 28 180 19 312 62 24 24 E1000 ... E40000 E1000 ... E12000 29 24 24

GRLM–70 © Dinel, s.r.o.9

OUTSIDE THE INFLUENCE OF FILLING

• Donotinstallthelevelmeterinorabovethefillingstream.Theinflowingproductcaninfluencethemeasurementofthelevelmeter.

s -Radius of protec tive zone along the electrode level meter

• If still these objects  intervene  into  the protective zoneofthelevelmeter,itisne-cessarytocreateamapoffalsereflectionsbyactivatingthe"TEACHING"mode(p.16).Incaseofinstalledmixers,itisnecessary topositionthemixersnearthelevelmeter(turningthemixerbladetotheproximityoftheelectrode).fortocreateamapfalsere-flections. Items  inside  the  tank must not be  from  the  electrode  distance  of  less than  100  mm, because a interference ofelectromagnetic field is very strong in thiszone and "TEACHING" mode can not beused.

s = 300 mm

n = 100 mm

n - minimal distance of objects from the electrode from level meter

OBSTACLES IN THE TANK

• The level meter generates electromagne-tic guidedwave,which creates an electro-magneticfieldalong theelectrode.Objectsplaced close to the electrode disturb theelectromagneticfieldandthusaffecttheme-asurement.Therefore,itisdeterminedpro-tective  zone along theelectrodeof radius300 mm.The levelmeter is recommendedto install the tank so that the items placedinside the tank (ladders, various partitions,mixers,etc.)doesnotinterveneintothepro-tectivezone,seeFig.12.

Fig. 11: Level meter installation outside the influence of filling

Fig. 12: Level meter installation outside obstacles in the tank

Fig. 13: Incorrect level meter installation close to obstacles

all types

except GRLM-70_-20

all types

Page 11: R METE RS GUIDED WAVE GRLM 70 - Dinel€¦ · PG1 1 OK 46 G1" E200 ... E3000 15 4x 6 E200 ... E3000 4x otvor 6 29 28 180 19 312 62 24 24 E1000 ... E40000 E1000 ... E12000 29 24 24

10© Dinel, s.r.o. GRLM–70

CRAMPED SPACES

• Forthetypeoflevelmeterwith referen-ce  tube electromagnetic guided wavepropagates inside the reference tube.Thiswaveisnotaffectedbytheambientenvironment. So for this type of radaris not intended protective zone aroundthe electrodes and the levelmeter canbeusedformeasurements incramped spaces.

DEEP TANKS AND SILOS

• Forinstallationofthelevelmeterwithropeelectrode into deep tanks and silos thelengthof theelectrodemustbeselectedsothatthe weightwillbebelowthemini-mummeasuredlevel,seeFig.16.

•  The  distance  the  electrode  from  the tank wallmustbeatleast300mm.Other-wise,thelevelmeterinstallasfaraspossi-blefromthewalls,tothemiddlebetweenthewallandtheverticalinlet,seeFig.16.Itmustbeensuredthattheropeelectrodecouldnottouchthevesselwallcausedbythemotionofthemedium.

• Takecaredoesnotexceedthemaximumtensileloadoftheropeelectrode.Theva-lueofthemax.tensilestrengthisspecifiedinchapter"Technicalspecifications".Highloadscanbreaktherope.Tensileloadde-pendsontheheightandshapeofthetank,thedensityandadhesionof themediumandtherateatwhichthetankisemptied.

E = m + t + z

HUMIDITY

• Itissuitabletorunthecableunderacablebushing(obliquelydowninslack)accord-ing to Fig. 15 to preventpenetration  of humidity.Then therainandcondensingwatercanflowofffreely.

• Thecablebushingandconnectorhavetobesufficiently tightenedtopreventpen-etrationofhumidity.

Fig. 14: Level meter installation with reference tube in cramped spaces

Fig. 15: Prevention to avoid intrusion of humidity through cable gland

Fig. 16: Level meter installation with the rope electrode

GRLM-70_-20

GRLM-70_-30, 32, 33

all types

E – The length of rope electrodet – Measuring rangem – Dead zone on the beginning of electrodez – The lengt of weight (110 mm)d – The distance from the tank wall (min. 300 mm)

Page 12: R METE RS GUIDED WAVE GRLM 70 - Dinel€¦ · PG1 1 OK 46 G1" E200 ... E3000 15 4x 6 E200 ... E3000 4x otvor 6 29 28 180 19 312 62 24 24 E1000 ... E40000 E1000 ... E12000 29 24 24

GRLM–70 © Dinel, s.r.o.11

Rope electrode level meter must untangle and then can be inserted into the tank.

ROPE ELECTRODE WITH ANCHORAGE

• Forinstallationofthelevelmeterwith ropeelectrodewith ancho-rage into deep tanks and silosit is recommended to place theanchorage closer to axis of thesilo than is the position of levelmeter. See Fig. 17. This moun-tingwill lower theThis installati-onwillreducethesideforcesofthemediaontheropeelectrode.

• In case of anchoring we re-commend to preload the ropeelectrode by tension force ofabout100N.

Fig. 17: Recommended Level meter installation with anchorage

GRLM-70_-33

97

70

27

62

2014

var.

�10:

E20

0 ...

E50

00va

r.�1

2: E

200

... E

3000

E200

... E

3000

E100

0 ...

E20

000

46

15

4x 6

var.

�10:

E30

0 ...

E80

00va

r.�1

1(12

): E3

00 ..

. E20

0024

E100

0 ...

E40

000

4

PG11

OK 46

G1"

15

E200

... E

3000

15

4x 6

15E200

... E

3000

4x otvor 6

29

2818

019

312

62

24

24E1

000

... E

4000

0

E100

0 ...

E12

000

29

24

24

20

24E1

000

... E

4000

0

24E

3434

40

VARIANT WITHOUT ELECTRODE

• Type of level meter withoutelectrode issuppliedwithoutanelectrode. It is therefore nece-ssarytoacustomertomounthisownmademeasuringelectrode.The diameter of the electrodemustbebetween8-10mm.Foraconnectionitisnecessarythaton the electrode is made M8thread.Theconnectionprocedu-reisgiveninSec.12page22.

Fig. 18: Level meter witout electrode

GRLM-70_-00

For the type of level GRLM-70_-00 manufactu-rer is not responsible for failures related to the mounted measuring electrode.

d

E

Page 13: R METE RS GUIDED WAVE GRLM 70 - Dinel€¦ · PG1 1 OK 46 G1" E200 ... E3000 15 4x 6 E200 ... E3000 4x otvor 6 29 28 180 19 312 62 24 24 E1000 ... E40000 E1000 ... E12000 29 24 24

12© Dinel, s.r.o. GRLM–70

7 .  elecTrical connecTionThelevelmeterisdesignedtobeconnectedtosupplyunitortocontrollerthroughacablewiththeouterdiameterof6÷8mm(recommendedcross-sectionofcores0.5÷0.75mm2)bymeansofboltedclipsplacedunderdisplaymodule.Connectthepluspole(+U)totheterminal(+),theminuspoleto0Vtotheterminal(-)andtheshieldingtotheterminal( )(onlyforshieldedcables).

Procedure  to  connect  the  cable  to  the level meter:  

1. Unscrewthenutoftheupperlid.

2. Take the upper edge of the displaymoduleandtakeitoutcarefullybymildswingingup.

3. If you cannot grasp the module, youcanuseasmallscrewdriver.Insertitasfaras theseamanduse fromseveralsidestoslightlyliftthemodule.

4. Releasethecablebushingandthreadthestrippedsupplycablein.

5. Connectthecableintotheboltedclipsaccording to the diagram in Fig. 20.Tighten theboltenclipsand thecablebushing.

6. Insertdisplaymoduletothelevelme-ter.

7. Slip the silicone seal on thread oflevelmeterandtightenthenutoftheupperlid.Connectthecabletothese-quentialunit.

Display unit connector

Terminal block

Metal clip

Fig. 20: Internal view of terminal block

Fig. 19: Connection diagram of the level meter

Electrical connection must be done in de-energized state!

With regard to possible occurrence of electrostatic charge on non-conductive parts of the level meter for explosive areas (GRLM–70Xi–_ _–I), level meters must be grounded with ground terminal! It will be done using a screw placed on the head of the level meter under the cable bushing.

The voltage source should be preferably realized as a stabilized power supply unit with safe voltage from 18 to 36 V DC, which can be a part of the evaluation or display device.

In case of strong electromagnetic interferences (EMI), parallel cable ducting with power lines, or when cable length exceeds 30 m we recommended to use shielded cable.

Page 14: R METE RS GUIDED WAVE GRLM 70 - Dinel€¦ · PG1 1 OK 46 G1" E200 ... E3000 15 4x 6 E200 ... E3000 4x otvor 6 29 28 180 19 312 62 24 24 E1000 ... E40000 E1000 ... E12000 29 24 24

GRLM–70 © Dinel, s.r.o.13

button 

• Set-upmodeaccess• Confirmationofselectediteminthemenu• Movethecursorintheline• Savingofset-updata

button 

• Moveinthemenu• Changeofvalues

button 

• Cancellingofcarriedoutchanges• Shiftonelevelup

9 .  sTaTus signalizaTion

1) symbol appears in the lower left corner of the display

8 .  seT-up eleMenTs

displej funkce

„NO ECHO“ Lighting intermittently – the level meter is not able to receive echo for a long time. Incorrect installation of the level meter.

„NO PASSWORD“ It will appear in the item "MENU" – the level meter is protected using a password against unauthorised setting. Enter the correct password.

„LOW POWER“ Low supply voltage level meter

Symbol „T“ 1) Lighting permanently – "TEACHING" mode activation.

Symbol „E“ 1) Lighting intermittently – correct echo receiving (of the reflected signal) from the measured surface level.

Symbol

ESC OK

www.dinel.cz

Ultrasonic Level Meter ULM-70

ESC OK

1745T E mm 1) Lighting permanently – level meter is locked against unauthorized set-

tings by a password. You must enter the correct password to unlock it.

Setthelevelmeterusing3buttonsplacedonthedisplaymodule.AllsettingsareaccessibleintheGRLM-70set-upmodeaccess.

* Slow flashing while the reflected signal (echo) is received from the measured level.

The type of level meter GRLM-70_ _-_-_-I-B is supplied without a display module DM-70. To set the level meter it is required to join the display module. Once set, the display module can be disconnected and the level meter can measure without him.

ESC OK

www.dinel.cz

Ultrasonic Level Meter ULM-70

ESC OK

1745T E mm

ESC OK

www.dinel.cz

Ultrasonic Level Meter ULM-70

ESC OK

1745T E mm

Teachingmode activation Units

Displayof measured values

Set-up elements

Echo receiving

Warning signs

Lock of level meter

Page 15: R METE RS GUIDED WAVE GRLM 70 - Dinel€¦ · PG1 1 OK 46 G1" E200 ... E3000 15 4x 6 E200 ... E3000 4x otvor 6 29 28 180 19 312 62 24 24 E1000 ... E40000 E1000 ... E12000 29 24 24

14© Dinel, s.r.o. GRLM–70

MIN LEVELMAX LEVELUN ITSDAMP INGSENS IT IV ITYTEACH ING

MIN ACTUAL LEVEL0 2 8 7 0 mm

OUTPUT : 0 4 . 0 0 mA

LEVEL : 0 6 0 0 0 mm

DISPLAY: 0 0 0 0 0 %

MAX ACTUAL LEVEL0 2 8 7 0 mm

OUTPUT : 2 0 . 0 0 mA

LEVEL : 0 0 2 5 0 mm

DISPLAY: 0 0 1 0 0 %

START ING

Dinel®

10 .  seTTingSetthelevelmeterusing3buttonsplacedonthedisplaymodule(seeChapterSet-upelements).After5min.ofinactivity,thelevelmeterautomaticallyreturnsbacktothemeasurementmode.Ifthepassword isactive, the levelmeterwill bealso locked.Theval-uesthathavenotbeenconfirmedusingthebutton willnotbesaved!After themeter is locked,youcannotchange thesetting!Whenyouattempttoedit,thewords"NOPASSWORD"willappearonthedisplay.Howtounlockthelevelmeterisgivenonpage21.Afterconnectionofthesupplyvoltagetothelevelmeterthedisplayshowsthelogo"Dinel"andthetext"Starting"(approx.30s).Then,thelevelmetergoestothemeasuringmodeandthedisplayshowsthecurrentmeasuredvalue.

10 .1 .  basic seTTings

MIN LEVEL and MAX LEVEL

Youcanfreelydefinetheminimum / maximum distance fromthefrontsurfaceofthelevelmeter(item"LEVEL"forcurrents4/20mA).The"DISPLAY"isintendedtosetthevalueshowedonthedisplay.Settingtheunitsisdoneinthe"UNITS".

ACTUAL LEVEL: Actual distance to levelOUTPUT: current 4 mA / 20 mALEVEL: Definition of the min / max levelDISPLAY: The value showed on the display

BAS IC SETT INGSSERV ICED IAGNOST ICCLONE SETT INGSPASSWORDLANGUAGEINFO

MIN LEVELMAX LEVELUN ITSDAMP INGSENS IT IV ITYTEACH ING

UN ITS

LEVEL : mm

DISPLAY: %

SAVED

Ifinthebottomofthedisplayappears(whenenteringthevalues)theinscription"OUTOFLIMITS",thevaluespecifiedfortheitem"LEVEL"isoutsidethemeasuringrangeofthelevelmeter.Iftheinscription"SPANTOOSMALL"isshown,itmustbespecifiedalargerspanbetweenMinandMaxvalues.Formoreinformation,seechapter"Specifications".Thedecimalpointpositionoftheitem'LEVEL'isfirmlyset(accordingtotheselectedunits),intheitem"DISPLAY"itisfreelyadjustable.

After the first start of the levelmeter it is necessary to performthebasicconfiguration(settingofthemeasuringrange,choiceofunits,possiblydamping,sensitivityandteaching).Thesettingsareaccessible in the basicmenu by pressing the "BASICSET-TINGS".

Page 16: R METE RS GUIDED WAVE GRLM 70 - Dinel€¦ · PG1 1 OK 46 G1" E200 ... E3000 15 4x 6 E200 ... E3000 4x otvor 6 29 28 180 19 312 62 24 24 E1000 ... E40000 E1000 ... E12000 29 24 24

GRLM–70 © Dinel, s.r.o.15

UNITS

LEVEL : mm

DISPLAY: %

DAMP ING

05

UNITS

Levelmetercanprocessandconvertalargenumberofdifferentphysical values.Thesettingisdoneintheitem"UNITS".

MIN LEVELMAX LEVELUN ITSDAMP INGSENS IT IV ITYTEACH ING

LEVEL: Unit selection (mm, cm, m, in, ft)DISPLAY: The unit showed on the display (%, mm, cm, m, in, ft, l, hl, m3, gal, bbl, mA)

DAMPING

Settingthe response timeofthemeasurements.Thefunctionisusefulforsuppressinglevelfluc-tuations,wavesandrapidchangesofthelevel.Thereactiontimewilldependontheexponentialfunction.Dampingwithadefineddelayinsecondsrepresentsthetimewhenexponentialreaches2/3ofitsmaximumvalue.

The damping time can be set in the interval from 0 to 99 s.

1. Toentertothemenupress thesamebuttontoselect"BASICSETTINGS".Then,usingand select"UNITS".

2. Nowthemenuitem"UNITS"isshown. Bypressingthe and buttonmakethesettingsofindividualitems.

3. Bypressing buttonsave thedata.Bynextpressesof thebutton leave themenu.Thelevelmeterreturnstomeasurementmode.

MIN LEVELMAX LEVELUN ITSDAMP INGSENS IT IV ITYTEACH ING

1. Toentertothemenupress thesamebuttontoselect"BASICSETTINGS".Then,usingand select"DAMPING".

2. Nowthemenuitem"DAMPING"isshown. Bypressingthe and buttonmakethesettingsofindividualitems.

3. Bypressing buttonsave thedata.Bynextpressesof thebutton leave themenu.Thelevelmeterreturnstomeasurementmode.

1. Toentertothemenupress thesamebuttontoselect"BASICSETTINGS". Then,usingand select "MINLEVEL"or"MAXLEVEL".

2. Nowitisshowntheitem"MINLEVEL"("MAXLEVEL").Bypressing and settheoutputcur-rent"OUTPUT",thedistanceforthedefinedcurrent"LEVEL"thevalueonthedisplay "DISPLAY".

3. Bypressing buttonsave thedata.Bynextpressesof thebutton leave themenu.Thelevelmeterreturnstomeasurementmode.

Page 17: R METE RS GUIDED WAVE GRLM 70 - Dinel€¦ · PG1 1 OK 46 G1" E200 ... E3000 15 4x 6 E200 ... E3000 4x otvor 6 29 28 180 19 312 62 24 24 E1000 ... E40000 E1000 ... E12000 29 24 24

16© Dinel, s.r.o. GRLM–70

MIN LEVELMAX LEVELUN ITSDAMP INGSENS IT IV ITYTEACH ING

You can set the sensitivity in four degrees:LOW (1) – MEDIUM (3) – HIGH (5) – USER (1 - 8).

SENS IT IV ITY

SENSITIVITY

Thesettingisdoneusingtwoparameters.Atfirtsthesettingisdefinedinfourstepsofthelevelmetersensitivity.Threestepsarebasicsensitivityandfourthstepcontainsuseroptions.

STEP 1 - „LOW“ – Low sensitivity in case of surrounding interferences affecting the measurement. STEP 3 - „MEDIUM“ – Medium sensitivity (suitable for most applications).STEP 5 - „HIGH“ – Enhanced sensitivity for measured mediums partly absorbing the guided wave (foams)STEP 1 - 8 - „USER“ – user freely adjustable sensitivity in eight steps

Thenissetthethetypeofmaterial.Withthisfunction,youcanchoosefromtwotypesofmaterials.Ifthemeasuredmaterialliquid(water,aqueoussolutions,emulsions,oil,diesel,etc.)selectLIQUID.Ifthemediumissolid(grain,sand,flour,cement,granulates,etc.)selectSOLID.Selectingthetypeofmediatakesintoaccountthedifferentreflectivepropertiesofthemedium.

1. Pressingthebuttonxxxisforenterthemenu,pressthesamebuttontoselecttheitem"BASICSETTINGS".Thenbypressingthebuttonsxxxandxxxisselectedtheitem"SENSITIVITY".

2. Usingthebuttonsxxxandxxxsetthepropersensitivity..

3. Afterswitchingthesensitivitytostep"USER",theusercanmovethroughdifferent(eight)levelsofsensitivitybypressingxxx.Pressxxxtoconfirmtheselection..

4. Nextusingthexxxandxxxbuttonsissetthetypeofmaterial.

5. Aftercompletionofsettingpressingofthexxxbuttonsavesthesetting.Continuebypressingxxxtoexitamenuandthelevelmeterreturnstothemeasuringmode.

You can set the material from two types:

LIQUID – SOLID.

SENS IT IV ITY : LOW

1 2 3 4 5 6 ! 7 ! 8 !

MATER IAL : L IQU ID

Table of recommended sensitivity according to rel. permittivity of the medium is given on page 32

Sensitivity steps 6-8 are highly sensitive, so use them only in exceptional cases for media with a low dielectric constant, or after consultation with the manufacturer.

SENS IT IV ITY

SENS IT IV ITY : USER

1 2 3 4 5 6 ! 7 ! 8 !

MATER IAL : L IQU ID

TEACHING

Themodeservesforsuppressing false reflectionsresultingfromreflectionoftheguidedwavefromroughnessesonwallsofthetank,variouspartitions,mixers,otherobstacles,orifdistanceelectrodefromthewalloftankislowerthan300mm.Thesensorstartingthismodedetectsfalsereflectionsandsavetheminthememory.Thenthesefalsereflectionswillnotaffectthesubse-quentmeasurement(theyaremasked).

Before starting the mode it is necessary to empty the tank completely.TEACH ING

TANK MUST ME EMPTY

START

MIN LEVELMAX LEVELUN ITSDAMP INGSENS IT IV ITYTEACH ING

TEACH ING

TANK MUST ME EMPTY

ARE YOU SURE?

Page 18: R METE RS GUIDED WAVE GRLM 70 - Dinel€¦ · PG1 1 OK 46 G1" E200 ... E3000 15 4x 6 E200 ... E3000 4x otvor 6 29 28 180 19 312 62 24 24 E1000 ... E40000 E1000 ... E12000 29 24 24

GRLM–70 © Dinel, s.r.o.17

Before starting the mode, it is necessa-ry to completely empty the tank!Incaseofinstalledmixers,itisnecessary topositionthemixersnearthe levelmeter(turningthemixerbladetotheproximityoftheelectrode).Note: If there are significant obstacles inthe upper half of the tank,multiple  false reflectionscanoccurespecially inclosedtanks.

ELECTRODE

Settingofthelengthandtypeoftheelectrode.Thefunctionisusedwhenisneededtochangethelength(e.g.shorteningoftheelectrode),orthetypeofelectrodes(e.g.exchangeofrodandropetypeofelectrode).

First,choosethetypeofelectrode.

„ROD“ – for rod-electrodes of type 10„ROPE“ – for rope-electrodes type 30„ANCHORED ROPE“ – for anchored rope electrode type 33

Thensetthelengthoftheelectrode.Eitherselectthe"AUTODETECTION"andthelevelmeterwillmeasurethelengthoftheelectrodeitself,orselectthe"Manual"andthelengthoftheelectrodemustbeenteredmanuallyviathedisplaymodule.

Fig. 21: Turning the mixer blade to the proximity of the electrode before activation "Teaching" mode

10 .2 .  service seTTings

In the supplemented configuration, you can set parameters ofsensitivity, mapping of false reflections, temperature differencecompensation, behaviour in case of fault conditions or HART® communication.Here,youcansetthesensorintotheinitialstateorresetitaswell.Thesettingsareaccessibleinthebasicmenuundertheitem"SERVICE".

Before setting of the length and type of the electrode it is first necessary to empty the tank in which the level meter is placed, since in this tank will be necessary to run the procedure "TEACHING".

1. Toentertothemenupress thesamebuttontoselect"BASICSETTINGS".Then,usingand select"TEACHING".

2. Nowthemenuitem"TEACHING"isshown. Afterpressingthebutton youareaskedifyouaresuretorunthe"TEACHING"procedure.Bypressing buttonthesystemstarts"teaching"(falsereflectionmapping).Duringthemapping,thedisplayshowsflashingsign"RUNNING".

3. Theprocedureiscompletelyfinishedwhenyoucanseetheinscription"DONE".Itisthenpos-sibletoexitthemenubyrepeatedpressingthebutton .

TEACH ING

TANK MUST BE EMPTY

RUNN ING

TEACH ING

TANK MUST BE EMPTY

DONEPRESS TO EX IT ESC

BAS IC SETT INGSSERV ICED IAGNOST ICCLONE SETT INGSPASSWORDLANGUAGEINFO

n = 100 mm

n - minimal distance of objects from the electrode from level meter

Page 19: R METE RS GUIDED WAVE GRLM 70 - Dinel€¦ · PG1 1 OK 46 G1" E200 ... E3000 15 4x 6 E200 ... E3000 4x otvor 6 29 28 180 19 312 62 24 24 E1000 ... E40000 E1000 ... E12000 29 24 24

18© Dinel, s.r.o. GRLM–70

When the setting of the type and length of the electrodes is carried out outside the tank it is required to insert a metallic plate (with diameter greater than 200 mm) in the place of process connection (thread) before this setting - see Fig. 7. The metal plate must be in good electrical contact with the thread.

The procedure for replacing or shortening the electrode is given in chapter 12 on page 22.

The function of Autodetection can only be used for electrodes longer than 500 mm.

ELECTRODE FA I LURE MODEHARTFACTORY DEFAULTRESET

ELECTRODE

TANK MUST BE EMPTY

T Y P E : R O D

LENGTH: MANUAL  05000 mm

You can choose type of electrode from three options: ROD – ROPE – ANCHORING ROPE

You can enter the length of electrode by two ways: MANUAL – AUTO DETECTION.

HART

HART® mode(pointtopoint,multidrop)andmultidropmodeaddress setting.Upto15unitscanbeconnectedtoonetwo-wiredcableinthemultidropmode..

In case of the address "00", the point to point mode is enabled. The range from "01" to "15" is reserved for addresses in the multidrop mode.

After you press the button "RUNNING" will be displayed for about 3 sec. After the initial values are set, "DONE" will be appear on the display.

FACTORY DEFAULT

Toreset the initial values ofthelevelmetersetbythemanufacturer,pressthebutton (seetheFactorydefaulttable,p.32.

ELECTRODE FA I LURE MODEHARTFACTORY DEFAULTRESET

HART

00

FACTORY DEFAULT

ARE YOU SURE?

RUNN ING

ELECTRODE FA I LURE MODEHARTFACTORY DEFAULTRESET

POLL ING ADDRESS

FACTORY DEFAULT

NO ECHO: Current in case of echo lossThe values can be set in five steps: 3,75 mA – 4 mA – 20 mA – – 22 mA – LAST (last measured data).

FAILURE MODE

Itdefines the output currentofthelevelmeterincaseofecholoss("NOECHO").

ELECTRODE FA I LURE MODEHARTFACTORY DEFAULTRESET

FA ILURE MODE

NO ECHO: 4 .00 mA

FACTORY DEFAULT

DONEPRESS ESC TO EX IT

Page 20: R METE RS GUIDED WAVE GRLM 70 - Dinel€¦ · PG1 1 OK 46 G1" E200 ... E3000 15 4x 6 E200 ... E3000 4x otvor 6 29 28 180 19 312 62 24 24 E1000 ... E40000 E1000 ... E12000 29 24 24

GRLM–70 © Dinel, s.r.o.19

BAS IC SETT INGSSERV ICED IAGNOST ICCLONE SETT INGSPASSWORDLANGUAGEINFO

10 .4 .  addiTional funcTions

Additionalfunctionsincludemodestodisplaytemperatureinthetankortofindouttheactualflowingcurrentintheloop.Besides,tolockmodificationsusingapassword,languageversionandinforma-tionaboutthelevelmeterversion.Allofthefunctionsareaccessiblefromthemainmenu.

DIAGNOSTIC

Itcontainsinformationsaboutactualvalueofdistancetolevelfromlevelmeter"DISTANCETOLEVEL"andaboutcurrentflowingthroughtheloop"CURRENT".Itcanbeusedforexampletochecktheset-tingsoftheconnectedevaluationdeviceordiagnoseanyproblemwiththemeasurementlevel.

D ISTANCE TO LEVEL

01220 mm

DISTANCE TO LEVELCURRENT

BAS IC SETT INGSSERV ICED IAGNOST ICCLONE SETT INGSPASSWORDLANGUAGEINFO

CLONE SETT INGS

NOW CLON ING

CLONE SETT INGS

SENSOR D ISPLAYMODULE

D ISPLAYMODULE

SENSOR

→→

1. Press toenterthemenuandselecttheitem"CLONESETTINGS".Copyingofthesettingsfromthebodyofthelevelmetertodisplaymoduleisdonebyselecting"SENSOR→ DISPLAYMODULE".TotransferthesettingsfromthedisplaymoduletoanotherlevelmeterselecttheitemDISPLAYMODULE→ SENSOR.

CLONE SETT INGS

SENSOR D ISPLAYMODULE

D ISPLAYMODULE

SENSOR

→→

ARE YOU SURE?

CLONE SETTINGS

Thismodeisintendedforcopyingofthelevelmeter(GRLM–70body) configuration  into  the  display  module (DM–70) andback.Thedisplaymodule can thenbe removed from the levelmeterbodyandputintoanotherlevelmeterandmaketherethesettingstransfer(cloning).The"CLONESETTINGS"modetransfersalldata,excludingset-tingofthe"Teaching"andHART®.

CUURENT

17 .30 mA

D ISTANCE TO LEVELCURRENT

RESET

Complete restartofthelevelmeter.Thesameeffecthasalsoashort-timeinterruptionofthesupplyvoltage.Toenabletheresetting,pressthebutton .

ELECTRODE FA I LURE MODEHARTFACTORY DEFAULTRESET

RESET

ARE YOU SURE?

During the restart process, "RUNNING" will be displayed. Then the level meter will be automatically turned off and on.

Page 21: R METE RS GUIDED WAVE GRLM 70 - Dinel€¦ · PG1 1 OK 46 G1" E200 ... E3000 15 4x 6 E200 ... E3000 4x otvor 6 29 28 180 19 312 62 24 24 E1000 ... E40000 E1000 ... E12000 29 24 24

20© Dinel, s.r.o. GRLM–70

Incompatible type of level meter and length of electrode. Transfer of the settings can be realized only with the same type of level meter and with same length of electrode.

1. Usethebuttons and inthemenu"PASSWORD"toselectthemode"ENTER"forenteringthepasswordorthemode"CHANGE"forchangingthepassword(whenactivated,thewordsaredisplayedinversely).Pressthebutton onceagaintoconfirmtheselection.Youcanchangethepasswordonlywhenthelevelmeterisunlocked.Otherwise,thewords"NOPASSWORD"willbedisplayed.

2. Nowyoucaneditthepassword.Theactualediteditemisdisplayedinversely.Pressthebuttontomovetothenextposition(clockwisedirection),button servestochangethevalues(0...9).

3. Aftertheoperationiscompleted,confirmtheediteddatabypressingthebutton .

Display of status information to confirm data:"YES" – correctly edited password"NO" – incorrectly edited password"OK" – the password saved (only in case of "CHANGE")The password is automatically hidden after it is edited or changed ("00000" will appear). To deactivate the password, edit the nu-merical combination "00000" in the mode "CHANGE".

PASSWORD

ENTER

0 0 0 0 0

PASSWORD

CHANGE

0 0 0 0 0

BAS IC SETT INGSSERV ICED IAGNOST ICCLONE SETT INGSPASSWORDLANGUAGEINFO

The data set is not stored into the display module (DM–70). The transfer can not be done. It is necessary to repeat the procedure of the copying the settings in the mode "CLONE SETTINGS".

The level meter with activated password will be automatically locked after 5 minutes of inactivity or after 5 min. from switching to measuring mode. Locking of level meter is indicated in the lower left corner of the screen by the symbol

ESC OK

www.dinel.cz

Ultrasonic Level Meter ULM-70

ESC OK

1745T E mm .

If the password is lost, contact the manufacturer.

PASSWORD

Youcanlockthelevelmeterdataagainstunauthorized editing.Afteractivatingthepasswordthedatamayberead,butcannotbeedited.Ifyoutrytoeditthesettings(withouttruepassword)thedisplayshows"NOPASSWORD".Thepasswordcanbeany5-digitnumericcombination.Thecombinationofnumbers00000isre-servedfordisablingthepassword.

1.

2. Theselectedmodestartsbypressingbutton Duringtransmissionthedisplayshows"NOWCLONING".

3. Aftercompletingtheprocessinthemiddleofthescreendisplays"DONE".Itisthenpossibletoleavethemenuandthemodebypressingthebutton .

CLONE SETT INGS

WARN ING–CLON ING IS NOT POSS IBLE

WRONG SENSOR TYPE

PRESS ESC TO EX IT

CLONE SETT INGS

WARN ING–CLON ING IS NOT POSS IBLE

NO SETT INGS SAVED

PRESS ESC TO EX IT

Page 22: R METE RS GUIDED WAVE GRLM 70 - Dinel€¦ · PG1 1 OK 46 G1" E200 ... E3000 15 4x 6 E200 ... E3000 4x otvor 6 29 28 180 19 312 62 24 24 E1000 ... E40000 E1000 ... E12000 29 24 24

GRLM–70 © Dinel, s.r.o.21

11 .  HarT® coMMunicaTion proTokolUniversalcommunication interfacefordatacommunicationofperipheraldeviceswiththe levelmeter.Datatransmissionrunsthroughthesamelineasthe4÷20mAcurrentloopwithoutimpactonanalogcommunication.

SENSOR

GRLM-70N -10 - I HART

ELECTRODE : 1000 mm

SN: 140015 SW: 2 .1

D ISPLAY MODULE

DM-70

SN: 140085

SW: 4 .1

SENSORD ISPLAY MODULE

SENSORD ISPLAY MODULE

BAS IC SETT INGSSERV ICED IAGNOST ICCLONE SETT INGSPASSWORDLANGUAGEINFO

INFO

Informationaboutthetype,serialnumberandproductiondateofthelevelmeter(type,serialnumber–SNandfirmwareversion–SW).

LANGUAGE

Settingthelanguageofdisplaymenu.

BAS IC SETT INGSSERV ICED IAGNOST ICCLONE SETT INGSPASSWORDLANGUAGEINFO

JAZYK

ENGL ISH

You can set three kinds of language:ČESKY – ENGLISH – по русски

HART®

modem

USB / RS232HART®

communicator

GRLM–70

PC

≈ 250 R Power supply unit

HART Specifications

TheversionoftheHARTProtocolisrevision5. UniversalCommands:0,1,2,3,6,11,12,13,14,15,16,17,18,19andCommonsPracticeCommands:34,35,40,42,44,49.

Obr. 22: Typical hardware configuration with HART

Page 23: R METE RS GUIDED WAVE GRLM 70 - Dinel€¦ · PG1 1 OK 46 G1" E200 ... E3000 15 4x 6 E200 ... E3000 4x otvor 6 29 28 180 19 312 62 24 24 E1000 ... E40000 E1000 ... E12000 29 24 24

22© Dinel, s.r.o. GRLM–70

12 .  THe insTallaTion of THe cusToM Measuring elecTrode, excHange or sHorTening of THe elecTrode

1. CreateyourownelectrodeasshownonFig.24.Thelengthoftheelectrodemustbeabout7mmshorterthanthedimension"E"infigure23.Thematerialoftheelectrodeisrecommendedtobeusedstainlesssteeltype1.4571(AISI316Ti)orsimilardependingontheapplication.

2. Onthethreadofpreparedelectrode,applythreadglueforsecuringthreadedfasteners(gluequantityisspecifiedbythemanufactu-rer).Theadhesivemustmeettherequirementsdependonthespecificapplication,forexample:withstandinghightemperatures,corrosivechemicals,resp.contactwithfood.

3. Screwtheelectrodeusingsuitablepliersoraspanner(onthesideoftheelectrode)andaflatspanner10mm(onthesideoftheelectrodeholder)firmlyintotheelectrodeholder.

4. Letthegluedjunctiontoharden,asrecommendedbythegluemanufacturer,thenthelevelmeterisreadyforinstallation.

5. Afteran installation intoanempty tank,setanew levelmeterelectrodetypeandthelength-seeChap.10.2.ELECTRODE

6. Ifnecessary,enteranewrangeoflevelmeasurement-seeChap.10.1.MIN/MAXLEVEL.

24E

8 h1

1

M8

1510

rýhování

50

Theprocedureofreplacementofthemeasuringelectrode-appliesonlytoversions10,30,33

1. Heatthejunctionplace(threadedconnection)oftheelectrodeandtheelectrodeholder(seeFigures25and26)usingaheatgunatabout120-150°C(or220-250°Cforhightempera-tureversion).

2. Unscrewtheelectrodeusingsuitablepliers(forrodelectrodes)orflatspanner7mm(incaseofropeelectrode)andaflatspanner10mm(onthesideoftheelectrodeholder)awayfromtheelectrodeholder.

3. Applytheglueforsecuringofthreadedfasteners(gluequantityspecifiedbythemanufacturer)tothethreadofthenewelectrode(madeacc.Fig.24.).Theusedgluemustmeettherequi-rementsdependonthespecificapplication, forexample:withstandinghightemperatures,corrosivechemicals,resp.contactwithfood.24

E

8 h1

1

M8

1510

rýhování

50

Fig. 23: Drawing of the level meter with size "E"

Fig. 24: The drawing of the measuring electrode marked with the threaded connection and grooving

electrode holder

electrode

The installation of the custom measuring electrode, - applies to type 00

striations

dimension

Page 24: R METE RS GUIDED WAVE GRLM 70 - Dinel€¦ · PG1 1 OK 46 G1" E200 ... E3000 15 4x 6 E200 ... E3000 4x otvor 6 29 28 180 19 312 62 24 24 E1000 ... E40000 E1000 ... E12000 29 24 24

GRLM–70 © Dinel, s.r.o.23

Fig. 27: Scheme of the weight for the rope electrode

1. If necessary, remove the rodor ropeelectrode from theelectrodeholder-seepoints1and2of"Theprocedureofreplacementofthemeasuringelectrode"

2. Rodelectrodesareadvisedtobeshortenedbyusingasuitablehacksawanddeburrtheendoftheelectrode.Fortheropeelectrodeisneededtoloosenthreefixingscrewsontheweightandpullouttheropeend,seeFigure27.Makesurethattheropelengthaftertrimmingiscorrect-thecableisembeddedinweighttoapprox.60mm.Shorteningtheropeisbestdonebymeansofsidecuttingpliers.Takecaretoavoidfrayingoftheropeend.

3. Inserttheendoftheropeintotheweightagainandsecurebytighteningofthethreescrews.

4. Ifyouunmountedtheelectrodefromtheelectrodeholder,re-assemblethem-seeparagraphs3to7of"Theprocedureofreplacementofthemeasuringelectrode"

Places to be heated, see "The procedure of replacement of

the measuring electrode"

Fig. 25: The threaded connection of the electrode holder with the rod electrode

Fig. 26: The threaded connection of the electrode holder with the rope electrode

1. 2. 3. 4. Screwtheelectrodeusingsuitablepliersoraspanner(onthesideoftheelectrode)andaflat

spanner10mm(onthesideoftheelectrodeholder)firmlyintotheelectrodeholder..5. Letthegluedjunctiontoharden,asrecommendedbythegluemanufacturer,thenthelevel

meterisreadyforinstallation.6. Afteraninstallationintoanemptytank,setanewlevelmeterelectrodetypeandthelength

-seeChap.10.2.ELECTRODE7. Ifnecessary,enteranewrangeoflevelmeasurement-seeChap.10.1.MIN/MAXLEVEL.

Shortening of the measuring electrode - applies only to versions 10, 30, 33

Page 25: R METE RS GUIDED WAVE GRLM 70 - Dinel€¦ · PG1 1 OK 46 G1" E200 ... E3000 15 4x 6 E200 ... E3000 4x otvor 6 29 28 180 19 312 62 24 24 E1000 ... E40000 E1000 ... E12000 29 24 24

24© Dinel, s.r.o. GRLM–70

13 .  order code

14 .  accessories

15 .  safeTy, proTecTion, coMpaTibiliTy and explosion proof

Performance:

Electrodeperformance:00 – without electrode10 – Uncoated St. steel rod electrode11 – Fully coated St. steel rod electrode (PFA)12 – Fully coated St. steel rod electrode (FEP)20 – Uncoated St. steel rod electrode with reference

tube30 – Uncoated St. steel rope electrode and weight32 – Fully coated rope electrode and weight

(FEP + PTFE)33 – Uncoated St. stel rope electrode with anchorage

N –Normal - usable in non-explosive areas only Xi –Explosion proof - suitable for explosive areasNT, XiT –High temperature performance

GRLM – 70 –

Outputtype: I – current

– –

Processconnection:G – thread G1"

E Length electrode in mm–B – without module DM-70, metal lid

Standard – included in the price of the level meter

• 1xofseal(asbestosfree),• otherseals(PTFE,Al,etc.)

volitelné – za příplatek

• FixingsteinlesssteelnutsG1“

• SteelorSteinlesssteelwelding

flangeON-G1",NN-G1"

ThelevelmeterGRLM–70isequippedwithprotectionagainstreversepolarityandoutputcurrentoverload.ProtectionagainstdangerouscontactissecuredbylowsafetyvoltagethatcomplieswithEN332000-4-41.ElectromagneticcompatibilityaccordingtoEN55022/B,EN61326/Z1andEN61000-4-2to6.

The explosion proof of GRLM-70Xi (XiT) is ensured by compliance with the followingstandards: EN 60079-0: 2007; EN 60079-11: 2007 and BS EN 60079-26: 2007. ExplosionproofofGRLM-70Xi(XiT)isprovenbyFTZÚ-AO210Ostrava-Radvanice:certificateNo:FTZÚ13ATEX0212X

Special conditions for safe use of variant GRLM-70XiLevelmetersGRLM-70Xi(XiT)aredesignedforconnectiontointrinsicallysafecircuitswithgalvanicisolation.Ifyouusethedevicewithoutgalvanicisolation(Zenerbarriers)itisnecessarytooffsetapotentialbetweenthesensorandthegroundingpointofthebarriers.

Page 26: R METE RS GUIDED WAVE GRLM 70 - Dinel€¦ · PG1 1 OK 46 G1" E200 ... E3000 15 4x 6 E200 ... E3000 4x otvor 6 29 28 180 19 312 62 24 24 E1000 ... E40000 E1000 ... E12000 29 24 24

GRLM–70 © Dinel, s.r.o.25

LevelmeterslabeldataGRLM–70N(T)

Symbolofproducer:logoDinel®

Internetaddress:www.dinel.czCountryoforigin:MadeinCzechRepublicLevelmetertype:GRLM–70N_–__–G–IE______Serialnumber:Ser.No.:______–(fromtheleft:productionyear,serialproductionnumber)Supplyvoltage:Ui= 18...36V=Outputcurrentrange:I =4...20mAAmbienttemperaturerange:ta=-30...+70°CProtectionclass:IP67Compliancemark: Electro-waste take-back system mark:

16 .  use, ManipulaTion and MainTenance

Maximumoutputparametersofintrinsicallysafeunitsmustcorrespondwithlimitinputparametersofthelevelmeter.Intheevaluationofintrinsicsafetyofthecircuitmustbetakenintoaccounttheparametersoftheconnectedcable(especiallyitsinductanceandcapacitance).

TheelectrodepartoftheGRLM-70Xi(XiT)canbeplacedinzone0,thebodywithelectronicscanbeplacedinzone1.Inzone20canbeplacedwholelevelmeter.

17 .  Marking of labels

The levelmeterdoesnot requireanypersonnel for itsoperation.Follow-updisplayingdevice isusedtoinformthetechnologicalentityoperatingpersonnelonthemeasuredsubstancelevelheightduringtheoperation.

Maintenanceofthisequipmentconsistsinverificationofintegrityofthelevelmeterandofthesup-plycable.Dependingonthecharacterofthesubstancemeasured,werecommendtoverifyatleastonceperyeartheclarityoftheultrasoundtransduceremittingfieldandtocleanit,respectively.Incaseanyvisibledefectsarediscovered, themanufactureror resellerof thisequipmentmustbecontactedimmediately.

It is forbidden to perform any modifications or interventions into the GRLM–70 level meter without manufacturer's approval. Potential repairs must be carried out by the manufacturer or by a manufacturer authorized service organization only.

Installation, commissioning, operation and maintenance of the GRLM–70 level meter has to be carried out in accordance with this instruction manual; the provisions of regulations in force regarding the installation of electrical equipment have to be adhered to.

The level meter must be installed to prevent tensile overload of the rope electrode.

Page 27: R METE RS GUIDED WAVE GRLM 70 - Dinel€¦ · PG1 1 OK 46 G1" E200 ... E3000 15 4x 6 E200 ... E3000 4x otvor 6 29 28 180 19 312 62 24 24 E1000 ... E40000 E1000 ... E12000 29 24 24

26© Dinel, s.r.o. GRLM–70

LevelmeterslabeldataGRLM–70Xi:

Symbolofproducer:logoDinel®

Internetaddress:www.dinel.czCountryoforigin:MadeinCzechRepublicLevelmetertype:GRLM–70Xi–__–G–IE______Serialnumber:Ser.No.:______–(fromtheleft:productionyear,serialproductionnumber)Supplyvoltage:Ui= 18...36V=Outputcurrentrange:I =4...20mALimitoperatingparameters:Ui= 30V=,Ii=132mA;Pi=0,99W;Ci=370nF;Li=0,9mHAmbienttemperaturerange:ta=-30...+70°CLabelofnon-explosivedevice:Performance:II1/2GExiaIIBT5Ga/GbNumberofcertificateofintrinsicallysafety:FTZÚ13ATEX0212XProtectionclass:IP67Compliancemark: ,No.ofauthorizedpersonexaminingcontrolofsystemquality:1026Electro-wastetake-backsystemmark:

LevelmeterslabeldataGRLM–70XiT:

Real label size is 70x20mm.

Symbolofproducer:logoDinel®

Internetaddress:www.dinel.czCountryoforigin:MadeinCzechRepublicLevelmetertype:GRLM–70XiT–__–G–IE______Serialnumber:Ser.No.:______–(fromtheleft:productionyear,serialproductionnumber)Supplyvoltage:Ui= 18...36V=Outputcurrentrange:I =4...20mALimitoperatingparameters:Ui= 30V=,Ii=132mA;Pi=0,99W;Ci=370nF;Li=0,9mHAmbienttemperaturerange:ta=-30...+70°CLabelofnon-explosivedevice:Performance:II1/2GExiaIIBT5Ga/GbNumberofcertificateofintrinsicallysafety:FTZÚ13ATEX0212XProtectionclass:IP67Compliancemark: ,No.ofauthorizedpersonexaminingcontrolofsystemquality:1026Electro-wastetake-backsystemmark:

Page 28: R METE RS GUIDED WAVE GRLM 70 - Dinel€¦ · PG1 1 OK 46 G1" E200 ... E3000 15 4x 6 E200 ... E3000 4x otvor 6 29 28 180 19 312 62 24 24 E1000 ... E40000 E1000 ... E12000 29 24 24

GRLM–70 © Dinel, s.r.o.27

18 . 

Men

u s

Tru

cTu

reM

INM

AX

05

00

SE

NS

OR

GR

LM

-70

N-1

0-I

HA

RT

EL

EC

TR

OD

E:

10

00

mm

SN

: 1

40

01

5

SW

: 2

.1

DIS

PL

AY

MO

DU

LE

DM

-70

SN

: 1

40

08

5

SW

: 4

.1

SE

NS

OR

DIS

PL

AY

MO

DU

LE

BA

SIC

SE

TT

ING

SS

ER

VIC

ED

IAG

NO

ST

ICC

LO

NE

SE

TT

ING

SP

AS

SW

OR

DL

AN

GU

AG

EIN

FO

BA

SIC

SE

TT

ING

SS

ER

VIC

ED

IAG

NO

ST

ICC

LO

NE

SE

TT

ING

SP

AS

SW

OR

DL

AN

GU

AG

EIN

FO

BA

SIC

SE

TT

ING

SS

ER

VIC

ED

IAG

NO

ST

ICC

LO

NE

SE

TT

ING

SP

AS

SW

OR

DL

AN

GU

AG

EIN

FO

BA

SIC

SE

TT

ING

SS

ER

VIC

ED

IAG

NO

ST

ICC

LO

NE

SE

TT

ING

SP

AS

SW

OR

DL

AN

GU

AG

EIN

FO

BA

SIC

SE

TT

ING

SS

ER

VIC

ED

IAG

NO

ST

ICC

LO

NE

SE

TT

ING

SP

AS

SW

OR

DL

AN

GU

AG

EIN

FO

BA

SIC

SE

TT

ING

SS

ER

VIC

ED

IAG

NO

ST

ICC

LO

NE

SE

TT

ING

SP

AS

SW

OR

DL

AN

GU

AG

EIN

FO

BA

SIC

SE

TT

ING

SS

ER

VIC

ED

IAG

NO

ST

ICC

LO

NE

SE

TT

ING

SP

AS

SW

OR

DL

AN

GU

AG

EIN

FO

MIN

LE

VE

LM

AX

LE

VE

LU

NIT

SD

AM

PIN

GS

EN

SIT

IVIT

YT

EA

CH

ING

AC

TU

AL

02

87

0m

m

OU

TP

UT

:0

4.0

0m

A

LE

VE

L:

06

00

0m

m

DIS

PL

AY

:0

00

00

%

AC

TU

AL

02

87

0m

m

OU

TP

UT

:2

0.0

0m

A

LE

VE

L:

00

25

0m

m

DIS

PL

AY

:0

01

00

%

UN

ITS

LE

VE

L:

mm

DIS

PL

AY

:%

DA

MP

ING

EL

EC

TR

OD

E F

AIL

UR

E M

OD

EH

AR

TF

AC

TO

RY

DE

FA

UL

TR

ES

ET

TE

AC

HIN

G

TA

NK

MU

ST

BE

EM

PT

Y

ST

AR

T

EL

EC

TR

OD

E

TA

NK

MU

ST

BE

EM

PT

Y

TY

PE

: R

OD

LE

NG

TH

: M

AN

UA

L 

05

00

0 m

m

FA

ILU

RE

MO

DE

NO

EC

HO

: 4

.00

mA

HA

RT

RE

SE

T AR

E Y

OU

SU

RE

?

FA

CT

OR

Y D

EF

AU

LT

AR

E Y

OU

SU

RE

?

DIS

TA

NC

E T

O L

EV

EL

01

22

0 m

m

DIS

TA

NC

E T

O L

EV

EL

CU

RR

EN

TC

UR

RE

NT 1

7.3

0 m

A

CL

ON

E S

ET

TIN

G

SE

NS

OR

DIS

PL

AY

MO

DU

LE

DIS

PL

AY

MO

DU

LE

SE

NS

OR

→ →

PA

SS

WO

RD

EN

TE

R

00

00

0

LA

NG

UA

GE

EN

GL

ISH

PO

LL

ING

AD

DR

ES

S

SE

NS

ITIV

ITY

SE

NS

ITIV

ITY

: M

ED

IUM

1 2

3

4 5

6!

7!

8!

MA

TE

RIA

L:

LIQ

UID

Page 29: R METE RS GUIDED WAVE GRLM 70 - Dinel€¦ · PG1 1 OK 46 G1" E200 ... E3000 15 4x 6 E200 ... E3000 4x otvor 6 29 28 180 19 312 62 24 24 E1000 ... E40000 E1000 ... E12000 29 24 24

28© Dinel, s.r.o. GRLM–70

19 .  specificaTions

TecHnical specificaTions– level MeTer

Supplyvoltage GRLM–70N–__GRLM–70Xi–__

18...36VDC18...30VDC

Output 4...20mA,HART®

Basicerror1)(forreferencereflector) -GRLM-70_-20inarea0,1–0,2m/0,2–2,0m/2,0 –40m-othertypesinarea0,1–0,2m/0,2–2,0m/2,0 –40m

± 5mm/±3mm/±2mm± 10mm/±4mm/±2mm

Resolution 1mm

Maximallengthofmeasuringelectrode GRLM–70_–10GRLM–70_–11(12)GRLM–70_–20GRLM–70_–30(33)GRLM–70_–32

8m2m3m40m12m

Deadzone2)-formeasur.sensitivity-low,medium,user(1-4)-high,user(5)-user(6,7)-user(8)

100/0mm3)150/50mm3)200/50mm3)250/50mm3)

ElectricalparametersforvariantsXi(XiT) –max.internalvalues Ui=30VDC;Ii=132mA;Pi=0,99W;Ci=370nF;Li=0,9mH

Measurementsensitivity(8degrees) low(1)-medium(3)-high(5)-user(1-8)

Failureindication (echoloss,internal failure)Adjustableinmodes: 3,75mA,4mA,20mA,

22mA,LAST4)

Damping 1..99s

Warmuptime cca60s

Internalresistance/Electricstrength(Electrode-Housing) 10kΩ

Couplingcapacity/Electricstrength(Housing-Supplyleads) 5nF/500VAC

MaximalcurrentoutputloadresistanceforU=24VDC U=22VDC U=20VDC

Rmax=270Ω5)Rmax=180ΩRmax=90Ω

Maximumtensilestrengthoftheropeelectrode 1400kg

Protectionclass IP67

Processconnection screwingwiththreadG1"

Recommendedcable PVC2x0,75mm2

Weight(withoutelectrode) cca0,5kg (1kgvariantNT,XiT)

1) Error is larger at the beginning and end of the rod or rope electrode. More detailed informations can be found in Fig. 28 and 29.2) Dead zone = Blind zone = Blocking distance3) The length of dead zone at the beginnig / at the end of the electrode. (The length of dead zone is 110 mm at the end of rope electrode.)4) Level meter displays last measured value.5) Including 250R resistor in case of HART connection.

Page 30: R METE RS GUIDED WAVE GRLM 70 - Dinel€¦ · PG1 1 OK 46 G1" E200 ... E3000 15 4x 6 E200 ... E3000 4x otvor 6 29 28 180 19 312 62 24 24 E1000 ... E40000 E1000 ... E12000 29 24 24

GRLM–70 © Dinel, s.r.o.29

0

2 mm

-2 mm

3 mm5 mm

-3 mm-5 mm

0,2 m0,1 m

2 m0,2 m

0

2 mm

-2 mm

4 mm6 mm

10 mm

-4 mm-6 mm

-10 mm

0,2 m 0,11 m

E (pro GRLM-70_-30(33))

0,2 m0,1 m

2 m

0,01 m

E (pro GRLM-70_-10(11,12))

E (pro GRLM-70_-20)

6 mm

-6 mm

0

2 mm

-2 mm

3 mm5 mm

-3 mm-5 mm

0,2 m0,1 m

2 m0,2 m

0

2 mm

-2 mm

4 mm6 mm

10 mm

-4 mm-6 mm

-10 mm

0,2 m 0,11 m

E (pro GRLM-70_-30(33))

0,2 m0,1 m

2 m

0,01 m

E (pro GRLM-70_-10(11,12))

E (pro GRLM-70_-20)

6 mm

-6 mm

- hatched place shows dead zone1)

- hatched place shows dead zone1)

1) hatched space applies for set measurement sensitivities: low (1), moderate (3) or user (1-4). When the sensitivity set to high (5), or custom (5-8), the dead zone at the beginning and at the end of the electrode extends, see "Table of sensitivity of the measurement" on page 28.

Fig. 28: The graph of the measurement errors along the rod electrode with reference tube

Fig. 29: The graph of the measurement errors along the rod and wire electrode

for

forfor

0

2 mm

-2 mm

3 mm5 mm

-3 mm-5 mm

0,2 m0,1 m

2 m0,2 m

0

2 mm

-2 mm

4 mm6 mm

10 mm

-4 mm-6 mm

-10 mm

0,2 m 0,11 m

E (pro GRLM-70_-30(33))

0,2 m0,1 m

2 m

0,01 m

E (pro GRLM-70_-10(11,12))

E (pro GRLM-70_-20)

6 mm

-6 mm

0

2 mm

-2 mm

3 mm5 mm

-3 mm-5 mm

0,2 m0,1 m

2 m0,2 m

0

2 mm

-2 mm

4 mm6 mm

10 mm

-4 mm-6 mm

-10 mm

0,2 m 0,11 m

E (pro GRLM-70_-30(33))

0,2 m0,1 m

2 m

0,01 m

E (pro GRLM-70_-10(11,12))

E (pro GRLM-70_-20)

6 mm

-6 mm

Page 31: R METE RS GUIDED WAVE GRLM 70 - Dinel€¦ · PG1 1 OK 46 G1" E200 ... E3000 15 4x 6 E200 ... E3000 4x otvor 6 29 28 180 19 312 62 24 24 E1000 ... E40000 E1000 ... E12000 29 24 24

30© Dinel, s.r.o. GRLM–70

used MaTerials

Sensor part Variants Standard materialLid Alltypes aluminiumwithpowdercoating

Glass Alltypes polycarbonate

Body Alltypes aluminiumwithpowdercoating

Housingwiththread Alltypes St.SteelW.Nr.1.4571(AISI316Ti)

ElectrodeGRLM-70_-10(11,20)GRLM-70_-12GRLM-70_-30(32,33)

St.SteelW.Nr.1.4571(AISI316Ti)St.SteelW.Nr.1.4301(AISI304)St.SteelW.Nr.1.4404(AISI316L)

ElectrodecoatingGRLM-70_-11GRLM-70_-12GRLM-70_-32

PFAFEPFEP

Referencetube GRLM-70_-20 St.SteelW.Nr.1.4301(AISI304)

Weight GRLM-70_-30 St.SteelW.Nr.1.4301(AISI304)

Weightcoating GRLM-70_-32 PTFE

Anchorage GRLM-70_-33 St.SteelW.Nr.1.4301(AISI304)

Displaymodule Alltypes plasticmaterialPOM

TecHnical specificaTions – display Modul

Typeofdisplay matrixOLED

Resolution 128x64pixels

Heightofdigits/Numberofdisplaydigitsofmeasuredvalues 9mm/5digits

Colourofdisplay yellow

Typeofbuttons membrane

Ambienttemperaturerange -30...+70°C

Weight 46g

device classificaTion (according to EN 60079-10-1 and EN 60079-10-2)GRLM–70N Performancefornon-explosiveareas

GRLM–70NT Hightemperatureperformancefornon-Exareas(max.200°C)

GRLM–70Xi(XiT)Performanceforexplosiveareas(gasesorvapour II1/2GExiaIIBT6Ga/GbwithISSU1)

electrodepartzone0,housingzone1andwholelevelmeterzone201) Intrinsically safe supply unit (for example: Dinel IRU–420).

Page 32: R METE RS GUIDED WAVE GRLM 70 - Dinel€¦ · PG1 1 OK 46 G1" E200 ... E3000 15 4x 6 E200 ... E3000 4x otvor 6 29 28 180 19 312 62 24 24 E1000 ... E40000 E1000 ... E12000 29 24 24

GRLM–70 © Dinel, s.r.o.31

97

70

27

62

2014

var.

�10:

E20

0 ...

E50

00va

r.�1

2: E

200

... E

3000

E200

... E

3000

E100

0 ...

E20

000

46

15

4x 6

var.

�10:

E30

0 ...

E80

00va

r.�1

1(12

): E3

00 ..

. E20

0024

E100

0 ...

E40

000

4

PG11

OK 46

G1"

15

E200

... E

3000

15

4x 6

15E200

... E

3000

4x otvor 6

29

2818

019

312

62

24

24E1

000

... E

4000

0

E100

0 ...

E12

000

29

24

24

20

24E1

000

... E

4000

0

24E

3434

40

TeMperaTure and pressure durabiliTy (performance N, Xi)

Variants / Performance temperature tm temperature tp temperature ta

Max. operation pressure for temp. tp

to 30°C to 85°CGRLM–70_–10(20) -40°C ... +300°C -40°C ... +85°C -30°C ... +70°C 15 MPa 10 MPaGRlM –70_–11(12) -40°C ... +200°C -40°C ... +85°C -30°C ... +70°C 4 MPa 1,5 MPaGRLM–70_–30(33) -40°C ... +200°C -40°C ... +85°C -30°C ... +70°C 15 MPa 10 MPaGRLM–70_–32 -40°C ... +130°C -40°C ... +85°C -30°C ... +70°C 1 MPa 0,5 MPa

tp – Temperature in process connection place

tm – Medium operating temperature

ta – Ambient temperature range(on housing)

TeMperaTure durabiliTy (performance NT, XiT)

Variants / Performance temperature tm temperature tp temperature ta

GRLM–70_T–10(20) -40°C ... +300°C -40°C ... +200°C -30°C ... +70°CGRlM –70_T–11(12) -40°C ... +200°C -40°C ... +200°C -30°C ... +70°CGRLM–70_T–30(33) -40°C ... +200°C -40°C ... +130°C -30°C ... +70°CGRLM–70_T–32 -40°C ... +130°C -40°C ... +130°C -30°C ... +70°C

Note: For correct function of the level meter must not be exceeded any of the temperature range (tp, tm or ta).

MaxiMal TeMperaTures for perforMance xi(xiT) caTegory 1/2gtemp. class temperature tp temperature tm temperature ta

T5 -40°C ... +90°C -40°C ... +98°C -30°C ... +70°CT4 -40°C ... +125°C -40°C ... +133°C -30°C ... +70°CT3 -40°C ... +190°C -40°C ... +198°C -30°C ... +70°CT2 -40°C ... +200°C -40°C ... +298°C -30°C ... +70°CT1 -40°C ... +200°C -40°C ... +300°C -30°C ... +70°C

Themaximumallowabletemperatureofthemedium,processconnectionandambienttemperaturedependsinGRLM-70Xi(XiT)atthedesiredtemperatureclass(seetab.MaximumtemperaturesfortheperformanceXi(XiT)category1/2Gandtab.).Thetemperaturevaluecannotbeexceeded,be-causethehotsurfaceofthedevicecouldcauseignitionofanexplosiveorflammableatmosphere.Atthesametimecannotexceedthemaximumtemperatureforthedifferentvariantsoftheelectro-des(Tableoftemperaturedurability).

Page 33: R METE RS GUIDED WAVE GRLM 70 - Dinel€¦ · PG1 1 OK 46 G1" E200 ... E3000 15 4x 6 E200 ... E3000 4x otvor 6 29 28 180 19 312 62 24 24 E1000 ... E40000 E1000 ... E12000 29 24 24

32© Dinel, s.r.o. GRLM–70

facTory defaulT

GRLM–70_-_ _

MINLEVEL(Distancetomin.level) accordingtothelengthoftherod(rope)electrode

MAXLEVEL(Distancetomax.level) 100mm

UNITS mm;%;°C

DAMPING 2

SENSITIVITY MEDIUM

MEDIUM LIQUID

FAILUREMODE–NOECHO 4,00mA

POOLINGADDRESS(HART®) 00

PASSWORD Nopassword

1) Dead zone = Blind zone = Blocking distance

pressure durabiliTy (performance NT, XiT)

Variants / PerformanceMax. operation pressure for temp. tp

to 30°C to 85°C to 130°C to 160°C to 200°CGRLM–70_T–10(20) 15 MPa 10 MPa 3 MPa 2 MPa 1 MPaGRlM –70_T–11(12) 4 MPa 1,5 MPa 2 MPa 1,5 MPa 0,3 MPaGRLM–70_T–30(33) 15 MPa 10 MPa 3 MPa - -GRLM–70_T–32 1 MPa 0,5 MPa 0,1 MPa - -

recoMMended sensiTiviTy depending on THe dielecTric consTanT of THe MediuM

Degrees SensitivityDielectric constant of the medium

for length of electrode to 20 m for length of electrode over 20 m

8! USER (extreme) 1,8 .. 1,9 2 .. 3

7! USER (extreme) 1,9 .. 2 4 .. 6

6! USER (extreme) 2 .. 3 6 .. 8

5 HIGH 3 .. 4 8 .. 10

4 USER 4 .. 6 10 .. 13

3 MEDIUM 6 .. 8 13 .. 16

2 USER 8 .. 10 16 .. 20

1 LOW 10 and more 20 and more

Page 34: R METE RS GUIDED WAVE GRLM 70 - Dinel€¦ · PG1 1 OK 46 G1" E200 ... E3000 15 4x 6 E200 ... E3000 4x otvor 6 29 28 180 19 312 62 24 24 E1000 ... E40000 E1000 ... E12000 29 24 24

GRLM–70 © Dinel, s.r.o.33

Page 35: R METE RS GUIDED WAVE GRLM 70 - Dinel€¦ · PG1 1 OK 46 G1" E200 ... E3000 15 4x 6 E200 ... E3000 4x otvor 6 29 28 180 19 312 62 24 24 E1000 ... E40000 E1000 ... E12000 29 24 24

34© Dinel, s.r.o. GRLM–70

Page 36: R METE RS GUIDED WAVE GRLM 70 - Dinel€¦ · PG1 1 OK 46 G1" E200 ... E3000 15 4x 6 E200 ... E3000 4x otvor 6 29 28 180 19 312 62 24 24 E1000 ... E40000 E1000 ... E12000 29 24 24