Cement Manufacturing Services Electrical & Process Control Technology
Holcim Group Support Ltd Im Schachen 5113 Holderbank
Phone +41 58 858 62 71 Fax: +41 58 858 62 75
The copyright for this document and all appendices are reserved by Holcim Group Support Ltd
HMI Screen Design Guideline
Holcim Group Support Ltd Cement Manufacturing Services
12.4 mbar
12.4 mbar 12.4 mbar
12.4 mbar
12.4 mbar
12.4 mbar
12.4 mbar 12.4 mbar
12.4 mbar
12.4 mbar
12.4 mbar
12.4 mbar
12.4 mbar
HMI Screen Design Guideline Reference No.: CMS-ECT 08/1442/E Revision No.: V 1.1
2/30
HMI Screen Design Guideline
Report Number: CMS-ECT 08/1442/E Date: August 19, 2008 Revision No.: V 1.1
Holcim Group Support Ltd Cement Manufacturing Services
Prepared by: Rudolf Stingelin Reviewed by: Thomas Kindlimann Approved by: Michael Bruckhaus Holcim Group Support Ltd Cement Manufacturing Services Im Schachen CH-5113 Holderbank Phone +41 58 858 62 71 Fax +41 58 858 62 75
HMI Screen Design Guideline Reference No.: CMS-ECT 08/1442/E Revision No.: V 1.1
3/30
Summary This document describes Holcim's recommendations How to design the Human Machine Interface (HMI) screens for Process Control Systems (PCS) used to control the cement production. The objective is to get an as much similar and consistent screen architecture, screen design and operation ergonomic for the HMI in the Holcim Group The main document specifies the ideal solution. The annexes show how to apply this specification with the standard PCS Modifications Version Date Modification Autor V 1.0 19.08.2008 First Release together with Annex 1 R. Stingelin V 1.1 10.09.2008 Modif: Definitions how to display the override of digital values R. Stingelin
HMI Screen Design Guideline Reference No.: CMS-ECT 08/1442/E Revision No.: V 1.1
4/30
Table of Contents
1. General remarks .............................................................................................................................. 6
1.1 Acronyms & Terms .................................................................................................................... 6
2. General basic Definitions (PCS independent) .............................................................................. 7
2.1 Screen hierarchy........................................................................................................................ 7
2.2 Plan screen level ....................................................................................................................... 8
2.3 Department screen level........................................................................................................... 8
2.4 Group screen level and detail screen level ............................................................................. 11
2.5 Department common screen pool ........................................................................................... 11
2.6 Plant common screen pool ...................................................................................................... 11
2.7 Screen architecture.................................................................................................................. 12 2.7.1 Process screen design ........................................................................................................ 13 2.7.2 Trend screen design............................................................................................................ 14 2.7.3 Service screen design ......................................................................................................... 15 2.7.4 Message screen design....................................................................................................... 15
2.8 Screen navigation.................................................................................................................... 16 2.8.1 Plant wide navigation........................................................................................................... 16 2.8.2 Department wide navigation ................................................................................................ 17 2.8.3 Screen family wide navigation ............................................................................................. 18 2.8.4 Additional navigation by navigation arrows ......................................................................... 19
2.9 Example for a screen concept ................................................................................................. 20
3. Displaying Alarms and Events ..................................................................................................... 21
3.1 Message line content............................................................................................................... 21
3.2 Alarm screen display ............................................................................................................... 22
3.3 Event screen display ............................................................................................................... 22
4. Rules, hints and tips for HMI screen designing ......................................................................... 23
HMI Screen Design Guideline Reference No.: CMS-ECT 08/1442/E Revision No.: V 1.1
5/30
4.1 Rules for graphics and mimics ................................................................................................ 23 4.1.1 Equipment drawing and TAG naming.................................................................................. 23 4.1.2 Display of process status and operation status (Colors) ..................................................... 25 4.1.3 Display of bar graphs........................................................................................................... 26 4.1.4 Display of selection and status information's....................................................................... 27 4.1.5 Best practice for graphics and mimics................................................................................. 28
4.1.5.1 Don’t use...................................................................................................................... 28 4.1.5.2 Use............................................................................................................................... 30
Annex 1: Specific Definitions for the Siemens PCS 7 CEMAT Annex 2: Specific Definitions for Rockwell Automation Faktorytalk View Annex 3. Specific Definitions for the ABB IndustrialIT 800xA Annexes will be attached as required depends on the applied PCS
HMI Screen Design Guideline Reference No.: CMS-ECT 08/1442/E Revision No.: V 1.1
6 / 30
1. GENERAL REMARKS
This document describes the following main items of a HMI: - The screen hierarchy - The main screen architecture - The screen navigation concept - The rules how to draw graphic screens In this document main part the ideal concept will be defined independent from the applied HMI system. The annex 1-3 will then show how these definition can be optimal applied to the Holcims standardized HMI systems from Siemens (CEMAT), Rockwell (FactoryTalk View) and ABB (ABB IndustrialIT 800xA). The document does not describe the screen content and the basic use of colors, because this is already done in the Standard Design Criteria.
1.1 Acronyms & Terms
PCS Process Control System HMI Human Machine Interface PLC Programmable Logic Control PAG Platform Architecture Guide Department Production line inside a cost centre defined by HAC 123 Group Process group as defined by HAC 123 Control group Process part with its own start and stop procedure
A Control group can match a Group (HAC123) or it can be a part of a group
Screen Is a displayed content (picture) on an HMI monitor /operator
console Screen area Area
Part of a screen with it specific purpose
CEMAT Siemens PCS for Cement applications FactoryTalk View Platform for HMI design of Rockwell Automation ABB IndustrialIT 800xA Industrial IT system for PCS and HMI of ABB
HMI Screen Design Guideline Reference No.: CMS-ECT 08/1442/E Revision No.: V 1.1
7 / 30
2. GENERAL BASIC DEFINITIONS (PCS INDEPENDENT)
2.1 Screen hierarchy
All screens are embedded in a defined hierarchical level or in a common pool as shown in the next drawing. Find following the description of these levels and pools. This picture shows a typical screen hierarchy with some examples as content. It does not represent a complete screen set
Optional for multiple production lines and departmental overviews
Group screen
Mill feed
531
Group Detail screen
Hydraulic
561-2
Group Detailscreen
Main Drive
561-3
Plant screen level
Groupscreen
Mill circuit
561-1
Dept. screen level
Group screen level
Detail screen level
Dept. Trendscreen
Trend 1
Dept. Trend screen
Trend n
Dept. Service screen
Recipes
Dept. Servicescreen
Silos
Dept.. Messagescreen
Alarms
Dept common screen pool
Dept. Overview screen
Expedition
Dept. Overview screen
Kiln 1
Departmental hierarchy
Other departments
Plant Trend screen1
Trend 1
Plant Trend screen
Trend 2
Plant Message screen
Alarms
Plant common screen pool
Other departments
Dept. Overview screen
Cem mill 1
501-2
Dept. Overview screen
Cem mills 1-n
500-1
Dept. Overview screen
Cem mill 2
502-1
Dept. Overview screen
Cem mill 1
501-1
Plant Overview-
screen
Groupscreen
Cem transport
591
Screen family
Plant Services screen
PCS Sys 1
Plant Service screen
PCS Sys 2
Screen family Screen family
Dept.. Messagescreen
Events
Plant Messagescreen
Events
HMI Screen Design Guideline Reference No.: CMS-ECT 08/1442/E Revision No.: V 1.1
8 / 30
2.2 Plan screen level Plant
Overview- screen
Plant screen level
The plant screen level has only one screen. This screen should display in minimum the navigation to the departmental processes. It has to open after a HMI system start. This screen can display additional a general overview about the running processes of the plant.
2.3 Department screen level
Dept. screen levelDept. Overview
screen
Cem mill 1 501-1
Dept. Overview screen
Cem mill 1
501-2
Dept. Overview screen
Cem mills 1-n
500-1
Other departments Other departments
Optional General overview
Cem mill 1-n (Without hierarchical
structure)
Process overview Cem mill 1
Exeptional Process overview Cem mill 1 spitted
Departmental hierarchy
The ideal solution is to have only one screen to display the process of one production line of this department (e.g. a cement mill process). If one screen is not sufficient to display the process, it can be split as exception in a second or third screen. For multiple production lines additional departmental hierarchies should be defined. Additional a general departmental overview over all production lines can be defined.
HMI Screen Design Guideline Reference No.: CMS-ECT 08/1442/E Revision No.: V 1.1
9 / 30
Typical example of an departmental overview screen for 3 cement mills.
Expedition
Cem mill 2
2008.02:29 14:15:36 521-BC1.R1 Rope switch Beltconveyor Building 4 / 24 m
Auxiliaries
Cem mill 1Raw meal Kiln 1
Kiln 2
Coal mill
Crusher Trend
Acknowledge
Alarms
Overview LVD
Events
HMI Screen Design Guideline Reference No.: CMS-ECT 08/1442/E Revision No.: V 1.1
10 / 30
Normally the following departments should be displayed:
Dept. (HAC 1)
Description
Main departments 2 Raw material preparation (Crusher) 3 Raw meal preparation (Raw mill) 4 Clinker production (Kiln) 5 Cement grinding (Cem mill) 6 Packing and shipping (Expedition) Pre process departments
K Additives handling L Traditional fuel handling V Alternative fuel handling X Correctives handling Auxiliarie departments
M Water supply E Electrical power (Singel line diagram) D General plant services (Compressed air etc.)
Other departments (see HAC manual) should be added as needed. To display common process parts of two departments (e.g. the gas flow between kiln and raw mill or additive handling to multiple cement mills), a common screen should be created and applied to the department screen level.
Dept. screen levelDept. Overview
screen
Gas flow
Dept. Overview screen
Kiln
Dept. Overview screen
Raw mill
Other departments Other departments
Kiln departmentRaw meal department
HMI Screen Design Guideline Reference No.: CMS-ECT 08/1442/E Revision No.: V 1.1
11 / 30
2.4 Group screen level and detail screen level
Groupscreen
Mill feed
531
Groupscreen
Cem transport
591
Group Detail screen
Hydraulic
561-2
Group Detailscreen
Main Drive
561-3
Groupscreen
Mill circuit
561-1
Group screen level
Detail screen level
The group screen has normally one screen for every main process control group. Control groups for detailed display of auxiliary systems or subsystems will normally defined in screens on the detail screen level. If one control group is too big for one screen it has to be spitted to an additional screen.
2.5 Department common screen pool
Dept. Trend screen
Trend 1
Dept. Trend screen
Trend n
Dept. Servicescreen
Recipes
Dept. Servicescreen
Silos
Dept. Messagescreen
Alarms
Dept common screen pool
Screen family
Dept. Messagescreen
Events
These screens contain common content valid inside a department and therefore usable only inside department hierarchy. The screen should be handled in so called families and will have it special navigation rules Families should be built always for multiples screens of the similar content. e.g. Family of trend screens
2.6 Plant common screen pool
Plant Trend screen1
Trend 1
PLant Trend screen
Trend 2
Plant Messagescreen
Alarms
Plan common screen pool
Plant Servicesscreen
PCS Sys 1
Plant Servicesscreen
PCS Sys 2
Screen family Screen family
Plant Message screen
Events
The usage and rules of these screens are similar to those in the department common screen pool. The screens are related to the plant screen level
HMI Screen Design Guideline Reference No.: CMS-ECT 08/1442/E Revision No.: V 1.1
12 / 30
2.7 Screen architecture
The HMI should be built by several basic screen layout witch have to be applied for the complete system. Such basic screens are: - Process screen (Process graphics) - Trend screen (Set of trend curves) - Message screen (Alarm and Events) - Service screen (Recipes, PCS system info, etc Every type of screens has its own screen architecture. But this architecture should be similar to all screens of same type. Every type of screen should be partitioned in several standardized areas as following: Process areas: - Graphic area -.Trend area - Message area Navigation and operation areas - Plant wide navigation area - Department wide navigation area - Common HMI system navigation area - Family wide navigation area Navigation- and operation areas should be placed on top, on bottom or at the side of the screen.
HMI Screen Design Guideline Reference No.: CMS-ECT 08/1442/E Revision No.: V 1.1
13 / 30
2.7.1 Process screen design
Typical architecture for a process screen
ExpeditionCem mill 1
2008.02:29 14:15:36 521-BC1.R1 Rope switch Beltconveyor Building 4 / 24 m
Auxiliaries
Cem mill 2
Cem mill 3
Raw meal Kiln 1
Kiln 2
Coal mill
Crusher
561-3
561-2
531 591
Trend Recipe Silos
Trend
Acknowledge
Alarms
Process area (Graphics)
Overview LVD
Plant wide navigation area
Plant wide navigation area
Department wide navigation area
Last alarm message
Alarms
Events Events 561-1
The plant wide navigation area serves to navigate between department hierarchies. The department wide navigation area serves to navigate inside its department hierarchy including its common screen pool. Process screens will be aplyed for: - Plant overviews - Department overviews - Group views - Detail views The plant overview screen has to contain as minimum the plant wide navigation area to jump into the needed departmental hierarchy structure. The process area should display a plant wide process overview.
HMI Screen Design Guideline Reference No.: CMS-ECT 08/1442/E Revision No.: V 1.1
14 / 30
2.7.2 Trend screen design
Typical architecture for a trend screen
2008.02:29 14:15:36 521-BC1.R1 Rope switch Beltconveyor Building 4 / 24 m
Trend Set 1
Acknowledge
Trend area
Family wide navigation area
Exit button to leave the screen family Name of department
Trend Set 3 Trend Set 4 Cem mill 1 ExitTrend Set 5 Trend Set 6 Trend Set 7 Trend Set 8
Trend Set 2
One ore more trend screens of a department or of a plant build together a screen family. With the exit button this family can be left. The trend area should contain a set of trend curves for values which relate together in the process. The select button has to be named with the functionality of the trend set.
HMI Screen Design Guideline Reference No.: CMS-ECT 08/1442/E Revision No.: V 1.1
15 / 30
2.7.3 Service screen design
The architecture for service- and system information screens is similar to the above described trend screen. It will also be one screen or a screen family. Instead of trend area it has a process(Graphic) area. Service screens will be applied to display additions handlings on the department level or plant level: e.g. - Recipe treatement - Product to silo assignement - PCS system and status information display etc:
2.7.4 Message screen design
Typical architecture for a message screen
Acknowledge
Alarm display area or
Event display area
Operation area to treate the message screen (Find, filter, etc)
Exit button to leave the screen Name of department
(if required)
Cem mill 1 Exit
Alarm screens should by assigned with an initial filtering to its own department.
HMI Screen Design Guideline Reference No.: CMS-ECT 08/1442/E Revision No.: V 1.1
16 / 30
2.8 Screen navigation
2.8.1 Plant wide navigation
The plant wide navigation will be done with buttons assigned to plant wide navigation area as defined above. With it, it is possible to navigate from the plant screen level, department screen level, group screen level and detail screen level to its own and to an other department or between two departments.
Expedition Cem mill 1
2008.02:29 14:15:36 521-BC1.R1 Rope switch Beltconveyor Building 4 / 24 m
Auxiliaries
Cem mill 2
Cem mill 3
Raw meal Kiln 1
Kiln 2
Coal mill
Crusher
561-3
561-2
531 591
Trend Recipe Silos
Trend561-1
Acknowledge
Alarms
Process area (Graphics)
Overview LVD
Plant wide navigation area
Plant wide navigation- and operation
area
Department wide navigation- and operation
area
Last alarm message
Alarms
Plant wide navigation
Groupscreen
Mill feed
531
Group Detail screen
Hydraulic
561-2
Group Detailscreen
Main Drive
561-3
Plant screen leve
Groupscreen
Mill circuit
561-1
Dept. screen leve
Group screen lev
Detail screen lev
Dept. Overview screen
Expedition
Dept. Overview screen
Kiln 1
Departmental hierarchy
Other departmentsOther departments
Dept. Overview screen
Cem mill 1
501-2
Dept. Overview screen
Cem mills 1-n
500-1
Dept. Overview screen
Cem mill 2
502-1
Dept. Overview screen
Cem mill 1
501-1
Plant Overview-
screen
Groupscreen
Cem transport
591
Operation sequence (buttons) Navigation possibilities
HMI Screen Design Guideline Reference No.: CMS-ECT 08/1442/E Revision No.: V 1.1
17 / 30
2.8.2 Department wide navigation
The department wide navigation will be done with buttons assigned to department wide navigation area as defined above. With it, it is possible to navigate inside a departmental hierarchy between the department screen level, group screen level and detail screen level.
ExpeditionCem mill 1
2 008.02:29 14:15:36 521-BC1.R1 Rope switch Beltconveyor Building 4 / 24 m
Auxiliaries
Cem mill 2
Cem mill 3
Raw meal Kiln 1
Kiln 2
Coal mill
Crusher
561-3
561-2
531 591
Trend Recipe Silos
Trend 561-1
Acknowledge
Alarms
Process area (Graphics)
Overview LVD
Plant wide navigation area
Plant wide navigation- and operation
area
Department wide navigation- and operation
area
Last alarm message
Alarms
Groupscreen
Mill feed
531
Group Detailscreen
Hydraulic
561-2
Group Detailscreen
Main Drive
561-3
Plant screen level
Group screen
Mill circuit
561-1
Dept. screen level
Group screen level
Detail screen level
Departmental hierarchy
Other departmentsOther departments
Dept. Overview screen
Cem mill 1
501-2
Dept. Overview screen
Cem mill 1
501-1
Plant Overview-
screen
Groupscreen
Cem transport
591
Department wide navigation
Operation sequence (buttons) Navigation possibilities
HMI Screen Design Guideline Reference No.: CMS-ECT 08/1442/E Revision No.: V 1.1
18 / 30
2.8.3 Screen family wide navigation
The selection of the first screen of a screen family or a single screen from the pool can be done from the department screen level, the group screen level or from the detail screen level, if the related select button is assigned. Inside a screen family other screens of it can be selected. The screen family has to be left by using the EXIT button. With it the display will return to the screen from which you have started to the screen family
Groupscreen
Mill feed
531
Group Detailscreen
Hydraulic
561-2
Group Detailscreen
Main Drive
561-3
Plant screen level
Group screen
Mill circuit
561-1
Dept. screen level
Group screen level
Detail screen level
Dept. Trendscreen
Trend 1
Dept. Trendscreen
Trend n
Dept. Service screen
Recipes
Dept. Servicescreen
Silos
Dept common screen pool
Departmental hierarchy
Other departmentsOther departments
Dept. Overview screen
Cem mill 1
501-2
Dept. Overview screen
Cem mill 1
501-1
Plant Overview-
screen
Groupscreen
Cem transport
591
Screen family
Dept. Trendscreen
Trend n
Single screenss
ExpeditionCem mill 1
2008.02:29 14:15:36 521-BC1.R1 Rope switch Beltconveyor Building 4 / 24 m
Auxiliaries
Cem mill 2
Cem mill 3
Raw meal Kiln 1
Kiln 2
Coal mill
Crusher
561-3
561-2
531 591
Trend Recipe Silos
Trend 561-1
Acknowledge
Alarms
Process area (Graphics)
Overview LVD
Plant wide navigation area
Plant wide navigation- and operation
area
Department wide navigatio n- and operation
area
Last alarm message
Alarms
Enter into a screen family
(e.g. Trend screen family)
2008.02:29 14:15:36 521-BC1.R1 Rope switch Beltconveyor Building 4 / 24 m
Trend Set 1
Acknowledge
Trend area
Family wide navigation area
Exit button to leave the screen family Name of department
Trend Set 2 Trend Set 3 Trend Set 4Cem mill 1
Exit Trend Set 5 Trend Set 6 Trend Set 7 Trend Set 8
Family wide navigation
Family EXIT Operation sequence (buttons) Navigation possibilities
HMI Screen Design Guideline Reference No.: CMS-ECT 08/1442/E Revision No.: V 1.1
19 / 30
2.8.4 Additional navigation by navigation arrows
Additional navigation possibilities can be assigned by using arrow buttons indicating the navigation direction. These buttons should e.g. used for: - Horizontal jumping to the next screen following the process flow on different pictures. - Vertical jumping upward to the screen in higher level to which the screen jumping from is related.
Groupscreen
Mill feed
531
Group Detailscreen
Hydraulic
561-2
Group Detailscreen
Main Drive
561-3
Plant screen level
Groupscreen
Mill circuit
561-1
Dept. screen level
Group screen level
Detail screen level
Departmental hierarchy
Other departmentsOther departments
Dept. Overview screen
Cem mill 1
501-2
Dept. Overview screen
Cem mill 1
501-1
Plant Overview-
screen
Groupscreen
Cem transport
591
ExpeditionCem mill 1
2008.02:29 14:15:36 521-BC1.R1 Rope switch Beltconveyor Building 4 / 24 m
Auxiliaries
Cem mill 2
Cem mill 3
Raw meal Kiln 1
Kiln 2
Coal mill
Crusher
561-3
561-2
531 591
Trend Recipe Silos
Trend 561-1
Acknowledge
Alarms
Process area (Graphics)
Overview LVD
Alarms
Navigation by arrows
Operation sequence (buttons) Navigation possibilities
HMI Screen Design Guideline Reference No.: CMS-ECT 08/1442/E Revision No.: V 1.1
20 / 30
2.9 Example for a screen concept
The following picture shows a ideal example for a picture hierarchy with some of the navigation possibilities.
HMI Screen Design Guideline Reference No.: CMS-ECT 08/1442/E Revision No.: V 1.1
21 / 30
3. DISPLAYING ALARMS AND EVENTS
3.1 Message line content
As described in the Standard Design Criteria the following information has to be treated as a minimum in an alarm screen and a message screen.
(Message in separate columns) Date Time Type Tag
(HAC) Value Status Message (where) Message (who) Message (what)
07.11.2008 17:57:02 W 532-1X1.TA:H 85 Mill drive CM building / +0m Temp high
08.11.2008 17:57:02 W 532-1X1.TA:H 85 Mill drive CM building / +0m Temp high
(Message in one column)
Date Time Type Tag (HAC)
Value Status Message (where, who, what)
07.11.2008 17:57:02 W 532-1X1.TA:H 85 Mill drive @ CM building / +0m Temp high
08.11.2008 17:57:02 W 532-1X1.TA:H 85 Mill drive @ CM building / +0m Temp high
Type and status of the message have to be defined by codes according the definitions in the Standard Design Criteria. Additionally colors can be used to distinguish between type and / or status. But it is strongly recommended to apply colors restrictive to get an easy screen view. Example for message type code:
Message type Code examples
Failure F, Failure, !
Warning W, Warning, #
Status S, Status,.$
Diagnostic D, Diagnostic @
Example for message status codes
Message status Code example
Come not acknowledged C
Come acknowledged CA
Gone not acknowledged GA
Gone G
HMI Screen Design Guideline Reference No.: CMS-ECT 08/1442/E Revision No.: V 1.1
22 / 30
3.2 Alarm screen display
The alarm screen displays the existing Failures and Warnings. For an error free process this screen should be empty.
Acknowledge
Exit
Date Time Type Tag (HAC) Value Status Message (where, who, what 08.11.2008 17:57:02 F 522-BC1.R1:F CA Belt conveyor @ CM building / +24m Rope switch 08.11.2008 17:57:02 W 532-BE1.LM:H CA Bucket elevator @ CM building / -2m Level high 07.11.2008 13:34:52 F 532-BC2.R1:F 0 CA Belt conveyor @ CM building / +15m Rope switch 08.11.2008 17:57:02 W 532-1X1.TA:H 85 CA Mill drive @ CM building / +0m Temp max 08.11.2008 17:57:02 W 532-1X1.TB:H 88 CA Mill drive @ CM building / +0m Temp max 08.11.2008 17:57:02 W 532-1X1.TC:H 90 CA Mill drive @ CM building / +0m Temp max 07.11.2008 13:38:52 W 532-BC1.D1:F 0 C Belt conveyor @ CM building / +20m Drift switch 07.11.2008 13:34:52 F 532-BC2.R1:F 0 C Belt conveyor @ CM building / +15m Rope switch
Failure not acknowledged
Warning not acknowledged
Failure or Warning acknowledged
Cem mill 1
Alarms
3.3 Event screen display
The Event screen displays the history of all events happened such as Failures, Warnings, Status and Diagnostic-Events.
Acknowledge
Exit
Date Time Type Tag (HAC) Value Message (where, who, what 08.11.2008 17:57:02 S 532-001.01 Group 532 START 08.11.2008 17:57:02 F 522-BE1.R1:F Belt conveyor @ CM building / +24m Rope switch 08.11.2008 17:57:02 W 532-BE1.LM:H Bucket elevator @ CM building / -2m Level high 08.11.2008 17:57:02 D 532-BE1.S1 Bucket elevator @ CM building / -not standing 07.11.2008 13:34:52 F 532-BC2.R1:F 0 Belt conveyor @ CM building / +15m Rope switch 08.11.2008 17:57:02 W 532-1X1.TA:H 85 Mill drive @ CM building / +0m Temp max 08.11.2008 17:57:02 W 532-1X1.TB:H 88 Mill drive @ CM building / +0m Temp max 08.11.2008 17:57:02 W 532-1X1.TC:H 90 Mill drive @ CM building / +0m Temp max 07.11.2008 13:38:52 W 532-BC1.D1:F 0 Belt conveyor @ CM building / +20m Drift switch 07.11.2008 13:34:52 F 532-BC2.R1:F 0 Belt conveyor @ CM building / +15m Rope switch
History of all events
Cem mill 1
Events
HMI Screen Design Guideline Reference No.: CMS-ECT 08/1442/E Revision No.: V 1.1
23 / 30
4. RULES, HINTS AND TIPS FOR HMI SCREEN DESIGNING
The praxis shows that every person who designs HMI graphic screens has his own understanding and creativity to draw a process for screen display. To reduce such creativity and to get group wide a more consistent philosophy the following chapter will give a guide line to create process graphic screens for the cement production. This will be done giving good and bad examples.
4.1 Rules for graphics and mimics
4.1.1 Equipment drawing and TAG naming
For designing HMI screens the colors as defined in the Holcim Standard Design Criteria have to be applied Standing process
Rules: For TAG's To every equipment has to be assigned a
field indicating its TAG name applying the HAC. If the equipment is electrically driven (motor, valve, heating etc), then clicking on this TAG should open the popup window which controls the drive of this equipment.
The TAG name can be full HAC or reduced HAC depends on the following conditions.
BC1
SG1
531-RF1
LD1 VE1
M BE1.M1
BE1.M2
Rules: Non animated equipment remains transparent or shadowed gray
Normally no motor will be drawn with the exception of multiple drives for the same machine or for big motors (see below) Standing equipment has light gray color
Condition Use of HAC TAG name The screen includes only one process group
HAC 456 BC1
The screen includes several process groups
HAC 123-456 531-RF1
An equipment (machine) has more than one drive (e.g. Bucket elevator)
HAC 456.78 or HAC 123-456.78
BE1.M1 BE1.M2 or 531-BC1.M1531-BC1.M2
M
HMI Screen Design Guideline Reference No.: CMS-ECT 08/1442/E Revision No.: V 1.1
24 / 30
Running process
BC1
SG1
RF1
LD1 VE1
Rules: Normally no motor will be drawn Running equipment has green color
M
M
BE1.M1
BE1.M2
Big drives
Rules: For big drives (including eventually also auxiliary drives) or drives with additional equipment the motor should be drawn as mimic 1X1.M1 HU1
1X1.M3 1X1.M2
1X1:H1
HMI Screen Design Guideline Reference No.: CMS-ECT 08/1442/E Revision No.: V 1.1
25 / 30
4.1.2 Display of process status and operation status (Colors)
Rules: Process driven status information has to be indicated by color changes and visibility changes of the assigned object. Operator driven status information has to be displayed by additional mimic objects.
Display of TAG names
Rules: The back color of the equipment names has to be applied as follows: Process status
Error status
Alarm status
Back color
Standing No error No alarm -SG1 Standing error No alarm -RF1 Running No error No alarm -LD1 Running error Warninge -BC1 Running error Failure -VE1
Additionally a color filed has to be assigned to
the tag for displaying the following additional status Operation status Field color Single start mode blue Local operation mode white Automatic operation mode no visible Override (simulation) orange
BC1
SG1
RF1
LD1 VE1
Display of analog values
Rules: The display of analog values has to be an active field. Clicking on the display field has to open the popup window to treat the analog value: The back color of the value display field has to be applied as follows:
Process status (Value) Alarm
status Back color
Value in limit No alarm 87 % Value out of warning limit Warning 87 % Value out of failure limit Failure 87 % Value simulated No alarm 87 % Value simulated Warning 87 % Value simulated Failure 87 % Value under flow (<4mA) Failure 87 %
If the analog value is in override modus (simulation)
by the PCS, then it has to marked with the additional orange square mimic.
LD1 87 %
LD1 87 %
LD1 87 %
LD1 87 %
HMI Screen Design Guideline Reference No.: CMS-ECT 08/1442/E Revision No.: V 1.1
26 / 30
Display of digital values
Rules: Digital sensors (speed switches, drift switches, level switches etc. ) will be displayed only in case of an error as following
Process status
Sensor status
Alarm status
Back color
Standing No error No alarm Standing error x X1 Running No error No alarm Running error Warning R1 Running error Failure D1
If the digital value or an object is in override status (simulation) by the PCS, then the additional orange square mimic field has to be displayed and the digital object has to be visible in light gray.
In case when only the OK status of the digital signal can be set, the digital object itself can by displayed with an orange background.
D1
SG1 LD1
R1
X1
S1 RF1
R1
BC1
D1
4.1.3 Display of bar graphs
Rules: Analog values as bar graph have to be displayed as brown bar mimic. This bar graph color will not change. The analog value display has to change the color according the description above.
35 m
HMI Screen Design Guideline Reference No.: CMS-ECT 08/1442/E Revision No.: V 1.1
27 / 30
4.1.4 Display of selection and status information's
Single selection (e.g. On/Off)
Rules: Single selections (e.g. On/Off) have to be defined with push buttons as following: Button status Button
color Selection status
Selection is disabled (no action possible) Heating's OFF
Selection is enabled) (selection is possible) Heating's OFF
Selection is activated (Selected) Heating's ON
Heating's OFF
Heating's OFF
Heating's ON
Multiple selection (e.g. Silos))
Rules: Multiple selections (e.g. silos) have to be defined with push buttons as following: Selection status Button
color Selection is activated (Selected) -3S3
Selection is enabled) (selection is possible) -3S2
Selection is disabled (no action possible) -3S1
Prod
uct 2
Prod
uct 3
Prod
uct 1
-3S1 -3S2 -3S3
Status informations (e.g. actually production)
Rules: Information's and Status about the process should be written in white on blue back color.
(e.g. actually produced product)
Fortico
HMI Screen Design Guideline Reference No.: CMS-ECT 08/1442/E Revision No.: V 1.1
28 / 30
4.1.5 Best practice for graphics and mimics
4.1.5.1 Don’t use
No moving objects
Rules: Do not draw continuous moving mimics
No 3 dimensional objects
Rules: Try not to draw 3 dimensional; you … … lose time, … lose place The object looks to complex
Apply only shadowing to get the 3 dimensional feeling
HMI Screen Design Guideline Reference No.: CMS-ECT 08/1442/E Revision No.: V 1.1
29 / 30
No complex object designs
Rules: Do not draw complex objects Keep the simple and understandable
Doing this, the objects can often designed smaller to save space
Do not use the color "running" for non driven equipment
Rules: Try to not apply normally green color for non driven objects (e. g silos)
Typical exception is an air slide
HMI Screen Design Guideline Reference No.: CMS-ECT 08/1442/E Revision No.: V 1.1
30 / 30
4.1.5.2 Use
Use Static position movements
Rules: Apply static mimics to show different position of moving objects