Upload
others
View
21
Download
0
Embed Size (px)
Citation preview
AIR HANDLERR-410A Refrigerant
2-6 Tons
Submittal Data
English Language/IP Units
SD2518AG1 04/17
SAH
Contractor: P.O.:
Engineer:
Project Name: Unit Tag:
SD2518AG1 04/17 2 Page _____ of _____
AIR HANDLER2-6 Tons
SAH
©2017 The manufacturer works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Purchaser’s approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely the manufacturer’s opinion or commendation of its products.
Model Nomenclature
CompatibilityAir Handler Sizing SelectionThe SAH Air Handlers are designed for R-410A refrigerant and should be matched with split compressor section according
to the table below.
Air Handler Indoor Split Model (Single) Indoor Split Model (Dual Capacity)
Outdoor Split Model (Dual Capacity)
RatedAirfl ow(CFM) Electric Heat (kW)
SAH022***1*R1S1* 022 - 800 5
SAH026***1*R1S1* - 026 026 850 5
SAH030***1*R1S1* 030 - - 1000 5
SAH036***1*R1S1* 036 - - 1200 5, 10
SAH036***1*R1S1* - 038 038 1200 5, 10
SAH042***1*R1S1* 042 - - 1300 10, 15
SAH048***1*R1S1* 048 - - 1500 10, 15
SAH048***1*R1S1* - 049 049 1500 10, 15
SAH060***1*R1S1* 060 - - 1800 10, 15, 20
SAH060***1*R1S1* - 064 064 1800 10, 15, 20
SAH066***1*R1S1* 070 - - 2000 10, 15, 20
SAH066***1*R1S1* - 072 072 2000 10, 15, 20
1/31/2017
SAH 036 A 00 1 A 11-3 4-6 7 8-9 10 11
ModelSAH – Series Air Handler
Unit CapacityRefrigeration (DX)
022 MBTUH026 MBTUH030 MBTUH036 MBTUH042 MBTUH048 MBTUH060 MBTUH066 MBTUH
VintageA = Factory Use Only
Electric Heat 00 – None 05 – 5kW (022 – 030 only) No Breakers 10 – 10kW (036 – 066 only) No Breakers 15 – 15kW (042 – 066 only) with Breakers 20 – 20kW (060 - 066 only) with Breakers
*Factory Use Only
Position1 – Multi-position
Future OptionsS – Standard
Voltage1-208-230/60/1
Air CoilR – Refrigerant
Controls/ MotorA – Standard/ 5 Speed ECMC – Aurora AHB/ Variable Speed ECM1
TXV1 – Factory Installed
Rev.: 2/27/2017
S i Ai H dl
R12
114S
15 16*
13
Note: To field convert the SAH to bottomflow air discharge. The SAHBCK kit must be ordered separately.Note: Air flow on the 060 and 066 units in the horizontal configurations should be limited to 1900 cfm in cooling mode, or condensate blow off may occur.
1. Only available with Aurora controls in the compressor section.
Contractor: P.O.:
Engineer:
Project Name: Unit Tag:
SD2518AG1 04/17 3 Page _____ of _____
AIR HANDLER2-6 Tons
SAH
©2017 The manufacturer works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Purchaser’s approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely the manufacturer’s opinion or commendation of its products.
Air Handler Features and Benefi ts Air Coil
Designed for R-410A refrigerant. Configured as an 'A' coil,
aluminum tubes and enhanced corrugated lanced aluminum
fins to provide high efficiencies at low face velocities.
Cabinet
Constructed of heavy gauge environmentally-responsible
galvanized steel for maximum corrosion resistance. All
units are painted with a powder coat finish. All interior
surfaces are lined with 1˝ thick, foil lined acoustic type
fiber insulation, applied in a manner that prevents the
introduction of glass fibers into the air stream. Multiple
knockouts in various sizes facilitate power and low voltage
wiring. Multiple access panels for ease of service.
Factory SealedAchieves 2% or less total airflow leakage rate.
Installation EaseCabinets are shipped in one piece but can be separated for
ease of installation in tight spaces.
Auxiliary/ Emergency Electric Heat
Electric heat packages can be factory or field installed.
For field installed electric heat the Auxiliary Heat
Compatibility table below shows the available heater
packages for the air handler.
ConfigurationsCabinets are factory configured for upflow and horizontal
right hand air discharge installation but can be easily
configured for horizontal left hand or bottomflow air
discharge.
Drain Pans
Two composite drain pans included. One for vertical and
one for horizontal applications. The pans come equipped
with primary and secondary drain connections.
Electrical DisconnectFactory installed circuit breaker on 15kW/20kW heaters.
Expansion Device
Factory installed TXV with internal check valve inside
of cabinet.
Refrigerant Connections
Suction and liquid lines have sweat connections extended
outside of cabinet for ease of connection.
Controls
The SAH Air Handler has two control options.
Control option 'A' has a terminal strip board that uses the
24V input from the thermostat to control the 5 speed ECM
motor.
Control option 'C' has the AHB board. The AHB is part of
the Aurora controls platform and communicates via modbus
to the ABC. The AHB board controls the air handlers
variable speed motor, auxiliary heat staging, provides
condensate overflow protection, air coil freeze protection
FP2, auxiliary heat and blower energy monitoring, leaving
air temperature, and is Symphony compatible with Aurora
controls in the compressor section..
Auxiliary Heat Compatibility
Model kW Stages Air Handler Compatibility
022 - 030 036 042 - 048 060 066
19P659-01 5 1 X X
19P659-02 10 2 X X X X
19P659-03 15 2 X X X
19P659-04 20 2 X X
1/10/2017
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2518AG1 04/17 4 Page _____ of _____
AIR HANDLER2-6 Tons
SAH
©2017 The manufacturer works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Purchaser’s approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely the manufacturer’s opinion or commendation of its products.
Dimensional Data - DX Air Handler
TOP VIEW
YZ
AA
CC
EE
DDBB
FF
BOTTOM VIEW
UV
W
X
A
HJ K
LM
O
FRONT VIEW
P
Q
R
S
T
N
B
C DE
RIGHT SIDE VIEWF
GG
HH
R.SIDE VIEW 2 TON
NNPP
TOP VIEW 2 TON
JJ
KK
LLMM
TOP VIEW 3-6 TON BOTTOM VIEW R.SIDE VIEW 2 TON
RIGHT SIDE VIEW 3-6 TONFRONT VIEW
TOP VIEW 2 TON
Top Flow/Horizontal Unit Configuration
SAH Air Handler - Topflow/Horizontal
Topflow/Overall Cabinet
Horizontal D E
ConfigurationA B C 3/4" cond 1/2" cond F H J K L M N O P Q R S T U V W X Y Z AA BB CC DD EE FF GG HH JJ KK LL MM NN PP QQ
Width Depth HeightPower Supply
Low Voltage
Suction Liquid Low
Voltagein. 17.5 21.2 47.0 42.6 45.1 2.5 1.9 4.8 6.4 8.8 10.1 1.1 1.7 2.9 4.5 13.0 14.6 16.2 2.1 13.3 2.1 18.4 1.7 3.1 4.1 1.1 14.0 1.8 14.0 1.8 43.9 5.1 3.0 4.4 1.7 4.2 42.6 45.1 2.5
cm. 44.5 53.8 119.4 108.2 114.6 6.4 4.8 12.2 16.3 22.4 25.7 2.8 4.3 7.4 11.4 33.0 37.1 41.1 5.3 33.8 5.3 46.7 4.3 7.9 10.4 2.8 35.6 4.6 35.6 4.6 111.5 13.0 7.6 11.2 4.2 10.5 108.2 114.6 6.4in. 21.6 21.2 52.0 50.1 47.6 2.6 1.9 4.8 6.4 8.5 9.7 1.1 1.7 2.9 4.5 16.7 18.3 20.1 2.2 17.2 2.2 18.5 1.6 4.2 6.7 1.2 14.0 3.8 14.0 1.9
cm. 54.9 53.8 132.1 127.3 120.9 6.6 4.7 12.1 16.3 21.6 24.6 2.8 4.4 7.3 11.4 42.4 46.5 51.1 5.5 43.8 5.6 46.9 4.1 10.5 16.9 3.0 35.5 9.6 35.5 4.8in. 24.9 21.2 58.0 56.1 53.2 2.6 1.9 4.8 6.4 9.6 10.8 1.1 1.7 2.9 4.5 20.3 21.9 23.5 2.2 20.6 2.2 18.4 1.7 4.2 6.7 1.5 18.0 3.4 18.0 1.8
cm. 63.2 53.8 147.3 142.5 135.1 6.6 4.8 12.2 16.3 24.4 27.4 2.8 4.3 7.4 11.4 51.6 55.6 59.7 5.6 52.3 5.6 46.7 4.3 10.7 17.0 3.8 45.7 8.6 45.7 4.6Condensate is plastic 3/4" FPT Discharge flange is field installed and extends 1" (25.4 mm) from cabinet
024
036
048-060
Refrigerant Connections
Power Supply
" Y" IS 1 3/8 KNOCKOUT HIGH VOLTAGE"Z" IS 1 1/8 KNOCKOUT HIGH VOLTAGE "AA" IS 7/8 KNOCKOUT LOW VOLTAGE
024 CABINET DIMENSIONS ONLY
POWER SUPPLY
022-030
036
042-066
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2518AG1 04/17 5 Page _____ of _____
AIR HANDLER2-6 Tons
SAH
©2017 The manufacturer works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Purchaser’s approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely the manufacturer’s opinion or commendation of its products.
Dimensional Data - DX Air HandlerBottom Flow Unit Configuration
LEFT SIDE VIEW 2 TON UNIT
BB
AACC
DD
F
C
B
ED
F
LEFT SIDE VIEW
A
GH I
JK L
MN
O
P
Q
R
FRONT VIEW
Z
W
X
Y
TOP VIEW
T
S
U
V
BOTTOM VIEW
LEFT SIDE VIEW 2 TON UNIT
LEFT SIDE VIEW 3-6 TON FRONT VIEW
TOP VIEW BOTTOM VIEW
SAH Air Handler - Bottom flow
Overall Cabinet
Bottomflow D E F
Configuration A B C 1/2" cond 3/4" cond G H I J K L M N O P Q R S T U V W X Y Z AA BB CC DD
Width Depth HeightLow
VoltagePower Supply
Power Supply
Suction Liquid
in. 17.5 21.2 47.0 4.4 1.9 2.5 22.8 25.7 27.3 29.5 30.8 1.1 1.7 2.8 4.5 13.0 14.5 16.2 1.1 1.8 14.0 18.0 2.2 2.2 13.7 18.5 5.0 3.1 1.8 4.3cm. 44.5 53.8 119.4 11.2 4.8 6.4 57.9 65.3 69.3 74.9 78.2 2.8 4.3 7.1 11.4 33.0 36.8 41.1 2.8 4.6 35.6 45.7 5.6 5.6 34.8 47.0 12.7 7.9 4.6 11.0in. 21.5 21.2 52.0 4.4 1.9 2.6 22.8 25.7 27.3 29.3 30.6 1.1 1.7 2.8 4.5 16.6 18.2 20.1 1.2 3.8 14.0 14.0 2.2 2.2 17.3 18.5
cm. 54.6 53.8 132.1 11.2 4.8 6.6 57.9 65.3 69.3 74.5 77.7 2.7 4.3 7.2 11.4 42.2 46.3 51.1 3.0 9.7 35.6 35.6 5.6 5.6 43.8 46.9in. 24.9 21.2 58.0 4.4 1.9 2.6 24.0 27.0 28.5 31.3 32.8 1.1 1.7 2.8 4.5 20.2 21.9 23.5 1.2 3.4 18.0 18.0 2.1 2.2 20.5 18.5
cm. 63.2 53.8 147.3 11.2 4.8 6.6 61.0 68.6 72.4 79.5 83.3 2.8 4.3 7.1 11.4 51.3 55.6 59.7 3.0 8.6 45.7 45.7 5.3 5.6 52.1 47.0
Condensate is plastic 3/4" FPT Discharge flange is field installed and extends 1" (25.4 mm) from cabinet
POWER SUPPLY 024 ONLY
Refrigerant Connections
048-060
036
024
036
042-066
022-030
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2518AG1 04/17 6 Page _____ of _____
AIR HANDLER2-6 Tons
SAH
©2017 The manufacturer works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Purchaser’s approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely the manufacturer’s opinion or commendation of its products.
Dimensional DataRefrigerant Coil
A
BC
H
I
J
K
F
D E
L
G
LEFT SIDE BOTTOM
FRONT
1
2
3
Overall DimensionsUncased 321Models A B C Suction Liquid Condensate
D E F G H I J K LWidth Depth Height* Sweat Sweat NPT
SRAA026U*in. 16.1 20.7 17.5 5/8 3/8 3/4 7.7 8.9 0.3 0.8 2.0 3.6 12.3 13.9 0.7
cm. 40.8 52.6 44.5 1.6 1.0 1.9 19.4 22.5 0.8 1.9 5.1 9.1 31.2 35.3 1.8
SRAA036U*in. 19.7 20.7 21.1 3/4 3/8 3/4 7.2 8.6 0.3 1.1 2.1 3.8 15.9 17.5 0.7
cm. 50.0 52.6 53.6 1.9 1.0 1.9 18.2 21.8 0.8 2.7 5.4 9.5 40.4 44.5 1.8
SRAA048U*in. 23.2 20.7 24.9 3/4 3/8 3/4 8.4 9.6 0.2 0.9 2.1 3.8 19.5 21.0 0.7
cm. 58.9 52.6 63.2 1.9 1.0 1.9 21.3 24.4 0.4 2.3 5.3 9.7 49.5 53.3 1.8
SRAA060U*in. 23.2 20.7 29.4 7/8 1/2 3/4 8.5 9.8 0.3 0.9 2.1 3.8 19.5 21.0 0.7
cm. 58.9 52.6 74.6 2.2 1.3 1.9 21.6 24.9 0.8 2.2 5.3 9.7 49.5 53.3 1.8
ConnectionsRefrigerant Connections Condensate Connections
*NOTE: All refrigerant coils feature factory insta lled TXV.
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2518AG1 04/17 7 Page _____ of _____
AIR HANDLER2-6 Tons
SAH
©2017 The manufacturer works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Purchaser’s approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely the manufacturer’s opinion or commendation of its products.
Dimensional Data - DX Cased Coils
NOTE: Cased coils are shipped with a 1" Flange Kit.
S CASED AIR COIL
Overall Cabinet
A B C D E F G H I J K L M N O
Width Depth Height Suction Liquid Suction Liquid
in. 17.8 21.5 26.3 8.8 10.1 1.0 1.6 1.9 4.8 6.4 2.7 4.4 13.0 14.6 16.2cm. 45.2 54.6 66.8 22.4 25.7 2.5 4.1 4.8 12.2 16.3 6.9 11.2 33.0 37.1 41.1in. 21.5 21.5 31.1 8.5 9.8 1.1 1.7 1.7 4.6 6.3 3.0 4.6 16.8 18.4 20.2cm. 54.6 54.6 79.0 21.6 24.8 2.8 4.3 4.3 11.7 16.0 7.6 11.7 42.5 46.7 51.3in. 24.9 21.4 35.3 9.5 10.8 1.1 1.7 1.9 4.8 6.4 3.0 4.7 20.3 22.0 23.5cm. 63.2 54.4 89.6 24.1 27.4 2.8 4.3 4.8 12.1 16.3 7.6 11.9 51.6 55.9 59.7
048-060
026
036
Refrigerant Connections Condensate ConnectionsTopflow & Horizontal
ConfigurationQ R S T U V W
13.9 2.0 2.0 17.6 2.0 2.0 2.035.3 5.1 5.1 44.7 5.1 5.1 5.117.6 2.0 2.0 17.6 2.0 2.0 2.044.8 5.1 5.1 44.7 5.1 5.1 5.121.0 2.0 2.0 17.6 2.0 2.0 2.053.3 5.1 5.1 44.7 5.1 5.1 5.1
Duct Connections
"C"
"H""I" "J"
"D""E"
"K"
"L"
"M"
"N"
"O"
"F"
"G"
SAH CASED AIR COIL
"W"
"V"
"U"
"B"
"A"
Q
R
S
T
TOP VIEW BOTTOM VIEW
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2518AG1 04/17 8 Page _____ of _____
AIR HANDLER2-6 Tons
SAH
©2017 The manufacturer works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Purchaser’s approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely the manufacturer’s opinion or commendation of its products.
Model Airflow (CFM) Dry Coil
SRAA026C1
600 0.08
800 0.14
1000 0.20
SRAA036C1
1000 0.11
1200 0.14
1400 0.18
SRAA048C1
1200 0.12
1400 0.15
1600 0.19
1800 0.25
SRAA060C1
1600 0.21
1800 0.27
2000 0.33
2200 0.38
3/7/2017
SR Cased Coil Air Side Pressure Drop (inches of WC)
Contractor: P.O.:
Engineer:
Project Name: Unit Tag:
SD2518AG1 04/17 9 Page _____ of _____
AIR HANDLER2-6 Tons
SAH
©2017 The manufacturer works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Purchaser’s approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely the manufacturer’s opinion or commendation of its products.
SAH 5 Speed ECM Blower Performance Data Option ABlower Performance 5 Speed ECM Control Option A
ModelMotor Speed
Motor Tap
T’stat Connection
Blower Size
Motor HP
Airflow (cfm) at External Static Pressure (in. wg)
0 0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45 0.50 0.60 0.70 0.80 0.90 1.00
022
High 5 W
9 x 7 1/2
1130 1115 1100 1090 1080 1065 1050 1040 1030 1015 1000 980 950 - - -
Med High 4 Y2* 1040 1025 1010 1000 990 975 960 945 930 915 900 880 850 - - -
Med 3 950 935 920 905 890 875 860 845 830 815 800 760 730 - - -
Med Low 2 Y1 860 845 830 815 800 785 770 755 740 720 700 660 590 - - -
Low 1 G 740 720 700 680 660 645 630 605 580 540 500 460 - - - -
026
High 5 W
9 x 7 1/2
1130 1115 1100 1090 1080 1065 1050 1040 1030 1015 1000 980 950 - - -
Med High 4 Y2* 1040 1025 1010 1000 990 975 960 945 930 915 900 880 850 - - -
Med 3 950 935 920 905 890 875 860 845 830 815 800 760 730 - - -
Med Low 2 Y1 860 845 830 815 800 785 770 755 740 720 700 660 590 - - -
Low 1 G 740 720 700 680 660 645 630 605 580 540 500 460 - - - -
030
High 5 W
9 x 7 1/2
1220 1205 1190 1180 1170 1160 1150 1140 1130 1115 1100 1050 930 - - -
Med High 4 Y2* 1130 1115 1100 1090 1080 1070 1060 1045 1030 1015 1000 980 950 - - -
Med 3 1040 1030 1020 1005 990 975 960 945 930 915 900 890 850 - - -
Med Low 2 Y1 950 935 920 905 890 875 860 845 830 815 800 770 730 - - -
Low 1 G 790 770 750 735 720 700 680 660 640 620 600 530 500 - - -
036
High 5 W
10 x 8 1/2
1450 1435 1420 1405 1390 1375 1360 1345 1330 1315 1300 1270 1250 1210 - -
Med High 4 Y2* 1350 1335 1320 1305 1290 1275 1260 1245 1230 1215 1200 1170 1140 1100 - -
Med 3 Y1 1170 1150 1130 1115 1100 1080 1060 1045 1030 1015 1000 960 920 880 - -
Med Low 2 1000 980 960 940 920 905 890 870 850 825 800 760 710 650 - -
Low 1 G 990 915 840 800 760 730 700 680 660 630 600 520 470 430 - -
042
High 5 W
11 x 10 1
1960 1945 1930 1915 1900 1880 1860 1845 1830 1810 1790 1750 1700 1660 - -
Med High 4 Y2* 1790 1775 1760 1745 1730 1710 1690 1670 1650 1535 1420 1560 1500 1450 - -
Med 3 1700 1685 1670 1650 1630 1615 1600 1575 1550 1525 1500 1450 1400 1350 - -
Med Low 2 Y1 1630 1560 1600 1520 1560 1535 1510 1490 1470 1445 1420 1370 1300 1250 - -
Low 1 G 1490 1445 1400 1375 1350 1325 1300 1270 1240 1210 1180 1120 1000 930 - -
048
High 5 W
11 x 10 1
1960 1945 1930 1915 1900 1880 1860 1845 1830 1810 1790 1750 1700 1660 1600 -
Med High 4 Y2* 1790 1775 1760 1745 1730 1710 1690 1670 1650 1535 1420 1560 1500 1450 1450 -
Med 3 1700 1685 1670 1650 1630 1615 1600 1575 1550 1525 1500 1450 1400 1350 1350
Med Low 2 Y1 1630 1560 1600 1520 1560 1535 1510 1490 1470 1445 1420 1370 1300 1250 1250 -
Low 1 G 1490 1445 1400 1375 1350 1325 1300 1270 1240 1210 1180 1120 1000 930 930 -
060
High 5 W
11 x 10 1
2210 2230 2190 2194 2170 2155 2130 2120 2100 2087 2060 2020 2000 1960 1920 1890
Med High 4 Y2* 2030 2073 2000 2035 1970 1995 1940 1958 1910 1922 1870 1840 1800 1760 1720 1680
Med 3 1850 1931 1820 1889 1790 1850 1760 1812 1730 1774 1680 1640 1600 1560 1510 1450
Med Low 2 Y1 1770 1796 1740 1761 1710 1718 1680 1682 1630 1651 1590 1560 1500 1450 1400 1340
Low 1 G 1570 1661 1540 1616 1510 1573 1460 1533 1420 1495 1370 1320 1250 1200 1100 1020
066
High 5 W
11 x 10 1
2390 2454 2370 2414 2340 2371 2320 2328 2290 2289 2270 2230 2200 2170 2140 2100
Med High 4 Y2* 2210 2248 2180 2205 2160 2166 2140 2129 2100 2094 2070 2040 2000 1960 1940 1890
Med 3 Y1 2030 2115 2010 2072 1980 2030 1950 1996 1900 1965 1880 1840 1800 1760 1720 1680
Med Low 2 1860 1985 1830 1939 1800 1898 1770 1862 1730 1828 1690 1640 1600 1570 1510 1460
Low 1 G 1780 1784 1750 1742 1720 1696 1680 1656 1640 1625 1600 1550 1500 1460 1400 1380Factory speed settings are in BoldAir flow values are with dry coil and standard filterFor wet coil performance first calculate the face velocity of the air coil (Face Velocity [fpm] = Airflow [cfm] / Face Area [sq ft]). Then for velocities of 200 fpm reduce the static capability by 0.03 in. wg, 300 fpm by 0.08 in. wg, 400 fpm by 0.12in. wg., and 500 fpm by 0.16 in. wg. Highest setting is for auxiliary heat (W) and lowest setting is for constant blower (G). The “Y1” and “Y2” settings must be between the “G” and “W” settings.*Single speed compressor section units will need to remove the TAN wire on the 5 speed motor and replace it with the RED wire. Tape end and secure the TAN wire.The SAH Air Handler blower is factory wired for dual speed compressor section operation.
1/10/17
ed for dual speed compressor section operation.
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2518AG1 04/17 10 Page _____ of _____
AIR HANDLER2-6 Tons
SAH
©2017 The manufacturer works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Purchaser’s approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely the manufacturer’s opinion or commendation of its products.
5-Speed ECM Constant Torque MotorsThe 5-Speed ECM is a 'Constant Torque' ECM motor and
delivers air flow similar to a PSC but operates as efficiently
as an ECM Motor. Because it's an ECM Motor, the 5-Speed
ECM can ramp slowly up to down like the ECM motor. There
are 5 possible speed taps available on the 5-Speed ECM
motor with #1 being the lowest airflow and #5 being the
highest airflow. These speed selections are preset at the
time of manufacture and are easily changed in the field if
necessary.
If more than one tap are energized at the same time, built
in logic gives precedence to the highest tap number and
allows air flow to change with G, Y1, Y2 and W signals. Each
of those 5 speeds has a specific 'Torque' value programmed
into the motor for each speed selection. As static pressure
increases, airflow decreases resulting in less torque on the
rotor. The motor responds only to changes in torque and
adjusts its speed accordingly.
The 5-Speed ECM motor is powered by line voltage but the
motor speed is energized by 24 VAC.
5-Speed ECM Benefits:
• High Efficiency
• Soft Start
• 5 speeds with up to 4 speeds on-line
• Built-in logic allows air flow to change with G, Y1, Y2
and W signals
• Super efficient low airflow continuous blower setting.
Setting Blower Speed - 5-Speed ECM5-Speed ECM blower motors have five (5) speeds of which
three (3) are selectable on single speed and four (4) are
selectable on dual capacity.
Caution: Disconnect all power before performing this operation.
L G NC
High VoltageConnections
3/16 in.
1 2 3 4 5G - Blue
Y1 - Red
AUX - Gray
C - Black
L - OrangeG - Green
N - Brown
Low VoltageConnections 1/4 in.
L G NC
1 2 3 4 5 AUX - GrayG - Blue
Y1 - Red Y2 - Tan
C - Black
L - OrangeG - Green
N - Brown
High VoltageConnections
3/16 in.
Low VoltageConnections 1/4 in.
5-Speed ECM Motor Connections - Single Speed Splits
5-Speed ECM Motor Connections - Dual Capacity Splits
SAH 5 Speed ECM Blower Performance Data Option A cont.
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2518AG1 04/17 11 Page _____ of _____
AIR HANDLER2-6 Tons
SAH
©2017 The manufacturer works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Purchaser’s approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely the manufacturer’s opinion or commendation of its products.
Blower Performance Data Option CBlower Performance Variable Speed ECM Control Option C
MODEL MAX ESPAIR FLOW SPEED SETTINGS
1 2 3 4 5 6 7 8 9 10 11 12
022 0.50 400500
G600
L700
800H
9001000Aux
1100 1200
026 0.50 400500
G600
700L
800900
H1000Aux
1100 1200
030 0.50 400500
G600
700L
800900
H1000Aux
1100 1200
036 0.50 550 650700
G800 850 900
950L
10501100
H1200
1300Aux
042 0.75 650 750 800900
G1000 1150
1200L
13001400
H1500 1600
1700Aux
048 0.75 650 750 800900
G1000 1150 1200
1300L
14001500
H1600
1700Aux
060 0.75 9501100
G1200 1350 1500
1650L
17001800
H2000Aux
2100 2200
066 0.75 9501100
G1200 1350 1500
1650L
1700 18002000
H2100Aux
2200
Factory settings are at recommended G-L-H-Aux speed settingsL-H settings MUST be located within boldface CFM range“Aux” is factory setting for auxiliary/emergency heat and must be equal to or above the “H” setting as well as at least the minimum required for the auxiliary heat package“G” may be located anywhere within the airflow tableCFM is controlled within 5% up to the maximum ESPMax ESP includes allowance for wet coil.
1/10/17
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2518AG1 04/17 12 Page _____ of _____
AIR HANDLER2-6 Tons
SAH
©2017 The manufacturer works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Purchaser’s approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely the manufacturer’s opinion or commendation of its products.
Blower Performance Data Option C cont.
SAH Control Option C AHB Board The SAH Air Handler with the 'Advanced' control option
expands on the capability of the Aurora 'Advanced' Control
(ABC and AXB) in the compressor section, by adding the
AHB board in the air handler.
NOTE: The Energy Monitoring and Leaving Air Temperature features at the AHB board are dependent on the AXB board in the compressor section.
It is highly recommended that the installing/servicing
contractor use an Aurora Interface and Diagnosic Tool
(AID) when installing and servicing an Aurora 'Advanced'
control system.
The AHB board includes the following features:
AHB DIP Switch
DIP 1 - ID: This is the AHB ModBus ID and should always
read Off.
DIP 2 & 3 - Future UseDIP 4 & 5 - Accessory Relay2: A second, DIP configurable,
accessory relay is provided that can be cycled with the
compressor 1 or 2 , blower, or the Dehumidifier (DH)
input. This is to complement the Accessory 1 Relay on
the ABC board.
Position DIP 4 DIP 5 Description
1 ON ON Cycles with Fan or ECM (or G)
2 OFF ONCycles with CC1 first stage of compressor
or compressor spd 1-6
3 ON OFFCycles with CC2 second stage of
compressor or compressor spd 7-12
4 OFF OFF Cycles with DH input from ABC board
IntelliZone2 Zoning Compatibility (Optional IntelliZone2 Communicating Zoning)
A dedicated input to connect and communicate with the
IntelliZone2 (IZ2) zoning system is provided on P7 on the
AHB and AXB. This is a dedicated communication port using
a proprietary ModBus protocol. An AXB in the compressor
section or an AHB in the air handler is required. Consult the
Intellizone2 literature for more information.
Communicating Digital ThermostatsThe Aurora controls system also features either mono-chromatic or color touch screen graphic display thermostats for user interface. These displays not only feature easy to use graphical interface but display alerts and faults in plain English. Many of the features discussed here may not be applicable without these thermostats.
Energy Monitoring (AXB Board Required in Compressor Section)(Standard Sensor Kit on ‘Advanced’ models)The Energy Monitoring Kit includes two current transducers (blower and electric heat) so that the complete power usage of the air handler can be measured. The AID Tool provides configuration detail for the type of blower motor, power adjustment and a line voltage calibration procedure to improve the accuracy. The information can be displayed on the AID Tool or selected communicating thermostats. The TPCM32U03A(*)/04A(*) will display instantaneous energy use while the color touchscreen TPCC32U01(*) will in addition display a 13 month history in graph form. Refer to Compressor Section Start Up Energy Monitoring for configuration details.
Freeze Detection (Air Coil) – uses the FP2 input to protect against ice formation on the air coil. The FP2 input will operate exactly like FP1 except that the set point is 30 degrees and is not field adjustable.
Condensate Overflow – fault is recognized when the impedance between this line and 24 VAC common or chassis ground drops below 100K ohms for 30 seconds continuously.
Leaving Air Temperature (AXB Board Required in Compressor Section)A leaving air temperature (LAT) thermistor is located near the blower inlet and can be read via the AID tool or AWL.
Electric Heat StagingThe AHB board provides two stages of auxiliary heat operation. During normal operation, the first stage of electric heat is energized 10 seconds after the W command is received. If the demand continues the second stage is of electric heat will be energized after 5 minutes. In an Emergency heat operation the time delay between stage one and stage two will be 2 minutes.
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2518AG1 04/17 13 Page _____ of _____
AIR HANDLER2-6 Tons
SAH
©2017 The manufacturer works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Purchaser’s approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely the manufacturer’s opinion or commendation of its products.
ECM Speed Info
1▶ 2 ◀ G 3 4 5 6 7 8 9 10 11 12
Option ◀▶ Enter ◙
ECM Speed Info
1 2 G▶ 3 ◀ Lo 4 5 6 7 8 9 10 11 12
Option ◀▶ Enter ◙
ECM Speed Info
1 2 G 3 Lo 4 5▶ 6 ◀ Hi 7 8 9 10 11 12
Option ◀▶ Enter ◙
ECM Speed Info
1 2 G 3 Lo 4 5 6 Hi 7 8 9▶10 ◀ Aux 11 12
Option ◀▶ Enter ◙
ECM Speed Info
Blower Only Speed 3Lo Compressor 6Hi Compressor 9Aux Heat 10
Want To Change?
YesOption ◀▶
NoEnter ◙
Cooling Airflow Setup
--- ECM Only ---The airflow will be
adjusted by the chosenamount in cooling mode.
Adjustment:-15%
Want To Change?
Yes Option ◀▶
No Enter ◙
Cooling Airflow Setup
--- ECM Only ---The airflow will be
adjusted by the chosenamount in cooling mode.
Adjustment:-15%
Change ▼▲ Enter ◙
Setting Blower Speed - Variable Speed ECM The ABC board’s Yellow Config LED will flash the current
ECM blower speed selections for “G”, low, and high
continuously with a short pause in between. The speeds
can also be confirmed with the AID Tool under the Setup/
ECM Setup screen. The Aux will not be flashed but can be
viewed in the AID Tool. The ECM blower motor speeds can
be field adjusted with or without using an AID Tool.
ECM Setup without an AID Tool
The blower speeds for “G”, Low (Y1), High (Y2), and Aux
can be adjusted directly at the Aurora ABC board which
utilizes the push button (SW1) on the ABC board. This
procedure is outlined in the ECM Configuration Mode
portion of the Aurora ‘Base’ Control System section. The
Aux cannot be set manually without an AID Tool.
ECM Setup with an AID Tool
A much easier method utilizes the AID Tool to change
the airflow using the procedure below. First navigate to
the Setup screen and then select ECM Setup. This screen
displays the current ECM settings. It allows the technician
to enter the setup screens to change the ECM settings.
Change the highlighted item using the ◀ and ▶ buttons and
then press the ◙ button to select the item.
Selecting YES will enter ECM
speed setup, while selecting NO
will return to the previous screen.
ECM Speed Setup - These screens allow the technician to
select the “G”, low, high, and auxiliary heat blower speed for
the ECM blower motor. Change the highlighted item using
the ▲ and ▼ buttons. Press the ◙ button to select the speed.
After the auxiliary heat speed setting is selected the AID
Tool will automatically transfer back to the ECM Setup screen.
Cooling Airflow Setup - These screens allow the technician
to select -15%, -10%, -5%, None or +5%. Change the
adjustment percentage using the ▲ and ▼ buttons. Press
the ◙ button to save the change.
Blower Performance Data Option C cont.
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2518AG1 04/17 14 Page _____ of _____
AIR HANDLER2-6 Tons
SAH
©2017 The manufacturer works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Purchaser’s approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely the manufacturer’s opinion or commendation of its products.
SR Coil Physical CharacteristicsAir Handler Model Number (Refrigerant) 026 036 048 060
Evaporator
Coil
Air Coil Total Face Area, ft2 [m2] 3.89 [0.36] 4.86 [0.45] 5.83 [0.54] 6.81 [0.63]
Tube outside diameter - in. [mm] 3/8 [9.52]
Number of rows 3
Fins per inch 12
Suction line connection - in. [mm] sweat 5/8 [15.87] 3/4 [19.05] 7/8 [22.23]
Liquid line connection - in. [mm] sweat 3/8 [9.52] 1/2 [12.7]
Refrigerant R-410a
Nominal cooling capacity - tons [kW] 1.8 [6.44] 2.1 [7.59] 2.5 [8.79] 3 [10.55] 3.5 [12.30] 4 [14.06] 5 [17.58] 5.5 [19.33]
Condensate drain connection - (FPT) in. [mm] 3/4 [19.05]
Filter Standard - 1” [51mm] Field Supplied.16 X 20
[406 X 508]
20 X 20
[508 x 508]
22 X 20
[559 x 508]
3/7/17
Physical DataAir Handler Model Number (Refrigerant) 022 026 030 036 042 048 060 066
Evaporator Coil
Air Coil Total Face Area, ft2 [m2] 3.89 [0.36] 4.86 [0.45] 5.83 [0.54] 6.81 [0.63]
Tube outside diameter - in. [mm] 3/8 [9.52]
Number of rows 3
Fins per inch 12
Suction line connection - in. [mm] sweat 5/8 [15.87] 3/4 [19.05] 7/8 [22.23]
Liquid line connection - in. [mm] sweat 3/8 [9.52] 1/2 [12.7]
Refrigerant R-410a
Nominal cooling capacity - tons [kW] 1.8 [6.44] 2.1 [7.59] 2.5 [8.79] 3 [10.55] 3.5 [12.30] 4 [14.06] 5 [17.58] 5.5 [19.33]
Condensate drain connection - (FPT) in. [mm] 3/4 [19.05]
Blower Wheel Size (Dia x W), in. [mm]9 X 7
[229 x 178] ]10 X 8
[254 x 203]11 x 10
[279 x 254]
Blower motor type/speeds Variable Speed ECM/ 5 Speed ECM
Blower motor output - hp [W] 1/2 [373] 1 [746]
Filter Standard - 1” [51mm] Field Supplied.16 X 20
[406 X 508]20 X 20
[508 x 508]22 X 20
[559 x 508]
Electrical characteristics (60hz) 208/230 - 1ph
Shipping weight - lbs. [kg] 147 [66.7] 168 [76.2] 198 [89.6] 206 [93.4]
Operating weight - lbs. [kg] 139 [63.0] 150 [68.0] 180 [81.6] 188 [85.3]
1/31/2017
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2518AG1 04/17 15 Page _____ of _____
AIR HANDLER2-6 Tons
SAH
©2017 The manufacturer works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Purchaser’s approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely the manufacturer’s opinion or commendation of its products.
Electrical Data
Model
Electric Heat CapacitySupply Circuit
Rated Voltage
Voltage Min/Max
Fan Motor FLA
Heater Ampacity
Total Unit FLA
Minimum Circuit
Ampacity
Maximum Fuse/HACRKW BTUH
240v 240v 208v 240v 208v 240v 208v 240v 208v 240v
0220 0 -
208-230/60/1 197/253
4.0 - - 4.0 4.0 5.0 5.0 10 10
4.8 16,382 single 4.0 17.3 20.0 21.3 24.0 26.6 30.0 30 30
0260 0 - 4.0 - - 4.0 4.0 5.0 5.0 10 10
4.8 16,382 single 4.0 17.3 20.0 21.3 24.0 26.6 30.0 30 30
0300 0 - 4.0 - - 4.0 4.0 5.0 5.0 10 10
4.8 16,382 single 4.0 17.3 20.0 21.3 24.0 26.6 30.0 30 30
036
0 0 - 4.0 - - 4.0 4.0 5.0 5.0 10 10
4.8 16,382 single 4.0 17.3 20.0 21.3 24.0 26.6 30.0 30 30
9.6 32,765 single 4.0 34.7 40.0 38.7 44.0 48.4 55.0 50 60
042
0 0 - 7.0 - - 7.0 7.0 8.8 8.8 15 15
9.6 32,765 single 7.0 34.7 40.0 41.7 47.0 52.1 58.8 60 60
14.4 49,147 single 7.0 52.0 60.0 59.0 67.0 73.8 83.8 80 90
14.4 49,147L1/L2 7.0 34.7 40.0 41.7 47.0 52.1 58.8 60 60
L3/L4 - 17.3 20.0 17.3 20.0 21.6 25.0 25 25
048
0 0 - 7.0 - - 7.0 7.0 8.8 8.8 15 15
9.6 32,765 single 7.0 34.7 40.0 41.7 47.0 52.1 58.8 60 60
14.4 49,147 single 7.0 52.0 60.0 59.0 67.0 73.8 83.8 80 90
14.4 49,147L1/L2 7.0 34.7 40.0 41.7 47.0 52.1 58.8 60 60
L3/L4 - 17.3 20.0 17.3 20.0 21.6 25.0 25 25
060
0 0 - 7.0 - - 7.0 7.0 8.8 8.8 15 15
9.6 32,765 single 7.0 34.7 40.0 41.7 47.0 52.1 58.8 60 60
14.4 49,147 single 7.0 52.0 60.0 59.0 67.0 73.8 83.8 80 90
14.4 49,147L1/L2 7.0 34.7 40.0 41.7 47.0 52.1 58.8 60 60
L3/L4 - 17.3 20.0 17.3 20.0 21.6 25.0 25 25
19.2 65,530 single 7.0 69.3 80.0 76.3 87.0 95.4 108.8 100 110
19.2 65,530L1/L2 7.0 34.7 40.0 41.7 47.0 52.1 58.8 60 60
L3/L4 - 34.7 40.0 34.7 40.0 43.4 50.0 50 50
066
0 0 - 7.0 - - 7.0 7.0 8.8 8.8 15 15
9.6 32,765 single 7.0 34.7 40.0 41.7 47.0 52.1 58.8 60 60
14.4 49,147 single 7.0 52.0 60.0 59.0 67.0 73.8 83.8 80 90
14.4 49,147L1/L2 7.0 34.7 40.0 41.7 47.0 52.1 58.8 60 60
L3/L4 - 17.3 20.0 17.3 20.0 21.6 25.0 25 25
19.2 65,530 single 7.0 69.3 80.0 76.3 87.0 95.4 108.8 100 110
19.2 65,530L1/L2 7.0 34.7 40.0 41.7 47.0 52.1 58.8 60 60
L3/L4 - 34.7 40.0 34.7 40.0 43.4 50.0 50 50
Rev.Rated Voltage of 208/230/60/1HACR circuit breaker in USA only
1/10/17
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2518AG1 04/17 16 Page _____ of _____
AIR HANDLER2-6 Tons
SAH
©2017 The manufacturer works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Purchaser’s approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely the manufacturer’s opinion or commendation of its products.
Electrical Data cont.
Field low voltage point to point wiring:Communicating Thermostat Control Option C
From
Communicating
Thermostat
To Air
Handler
PB3
To Compressor
Section
ABC Board P7
C C C
R R R
- - -
+ + +
Air Handler transformer must be 100VA. 1/10/2017
Field low voltage point to point wiring:Non-Communicating Thermostat Control Option C
From
Thermostat
To ABC in
Compressor
Section
From ABC
P7 in
Compressor
Section
To PB2
in Air
Handler
C C C C
R R R R
G G - -
O O + +
Y1 Y1
Y2 Y2
W2 W
L L
Air Handler transformer must be 100VA. 3/7/2017
Field low voltage point to point wiring:Standard Non-Communicating Control Option A
From
Thermostat
To Air
Handler
To Compressor
Section
C C C
R R R
G G
O O O
Y1 Y1 Y1
Y2 Y2 Y2
W2 W
L L L
Air Handler transformer must be 75VA.
24V Thermostat must be wired to the loose stripped wires connected to the terminal block
in the air handler. DAMAGE TO THERMOSTAT MAY OCCUR IF WIRED INCORRECTLY.
SEE AIR HANDLER SCHEMATIC.
3/9/2017
From Communicating
Thermostat
To ABC P7 in Compressor
Section
C CR R- -+ +
Air Handler transformer must be 75VA.
Field low voltage point to point wiring:Communicating Thermostat Control Option A
From ABC Outputs
To Air Handler
C CR RG G
CC Y1CC2 Y2EH1 W
OL
4/4/2017
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2518AG1 04/17 17 Page _____ of _____
AIR HANDLER2-6 Tons
SAH
©2017 The manufacturer works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Purchaser’s approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely the manufacturer’s opinion or commendation of its products.
Wiring SchematicsSAH Air Handler Control Option A Schematic
Air Handler No Electric Heat
97P901-01
Tan
Transformer
Blk/WhYellow
24V
L2L1
PB
Black
Blue
Red NOTE 1 Orange
Brown
1
2
3
L N G
5 SpeedECM
BlowerMotor
C
4
5
O
C
Y1
G
S
W1
L
X2
X1
R
Y2
TB
12V
Black
Blue
Red
Tan
Grey
12V
12V
12V
Thermostat
R
CY1
O
L1
Y2
G
W
Blue
Grey
Red
White
Black
GL2L1
208-230/60/1
Light emitting diode - Green
208-230V Relay coil
Electric Heat Contactor
Polarized connector
Factory Low voltage wiringFactory Line voltage wiringField low voltage wiringField line voltage wiringOptional blockDC Voltage PCB tracesInternal junctionQuick connect terminal
Thermal Limit Switch
Field wire lug
Ground
HE -
PB -
Heater element
Power block
Legend
N.O., N.C.
G
L1
ER1 to ER4 - Aux heat stage relays
1 2 3P
EHC
EHC
Breaker
TS
Notes:1 – To operate in 208V mode replace the blue transformer wire connected to PB-L2 with red transformer wire.
2 – Low voltage wiring CLASS 2.
NOTE 3
3 – 24V Thermostat must be wired as shown to the loose wires using wire nuts. DO NOT CONNECT THERMOSTAT TO TB.
WIRE 24V THERMOSTAT AS SHOWN CONNECTED TO THE STRIP WIRES ALREADY CONNECTED TO TB. DO NOT CONNECT DIRECTLY TO THE TB TERMINALS. DAMAGE TO THE STAT MAY OCCUR. TB CAN BE USED TO CONNECT TO THE ABC BOARD IN THE COMPRESSOR SECTION
Grn/Yel
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2518AG1 04/17 18 Page _____ of _____
AIR HANDLER2-6 Tons
SAH
©2017 The manufacturer works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Purchaser’s approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely the manufacturer’s opinion or commendation of its products.
Wiring Schematics cont.
SAH Air Handler Control Option A Schematic
Air Handler 5kW Electric Heat
97P901-02
Light emitting diode - Green
208-230V Relay coil
Electric Heat Contactor
Polarized connector
Factory Low voltage wiringFactory Line voltage wiringField low voltage wiringField line voltage wiringOptional blockDC Voltage PCB tracesInternal junctionQuick connect terminal
Thermal Limit Switch
Field wire lug
Ground
HE -
PB -
Heater element
Power block
Legend
N.O., N.C.
G
L1
ER1 to ER4 - Aux heat stage relays
1 2 3P
EHC
EHC
Breaker
TS
HE1 TS1FL1
GL2L1
208-230/60/1
2
3
1RELAY
Yellow
White
Blue
Blue
Yellow
Blue
Tan
Transformer
Blk/WhYellow
24V
L2L1PBBlack
Blue
Red NOTE 1 Orange
Brown
1
2
3
L N G
5 SpeedECM
BlowerMotor
C
4
5
O
C
Y1
G
S
W1
L
X2
X1
R
Y2
TB
12V
Black
Blue
Red
Tan
Grey
12V
12V
12V
Thermostat
R
CY1
O
L1
Y2
G
W
Blue
Grey
Red
White
Black
Blue
White
Notes:1 – To operate in 208V mode replace the blue transformer wire connected to PB-L2 with red transformer wire.
2 – Low voltage wiring CLASS 2.
R1
WIRE 24V THERMOSTAT AS SHOWN CONNECTED TO THE STRIP WIRES ALREADY CONNECTED TO TB. DO NOT CONNECT DIRECTLY TO THE TB TERMINALS. DAMAGE TO THE STAT MAY OCCUR. TB CAN BE USED TO CONNECT TO THE ABC BOARD IN THE COMPRESSOR SECTION
NOTE 3
3 – 24V Thermostat must be wired as shown to the loose wires using wire nuts. DO NOT CONNECT THERMOSTAT TO TB.
Grn/Yel
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2518AG1 04/17 19 Page _____ of _____
AIR HANDLER2-6 Tons
SAH
©2017 The manufacturer works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Purchaser’s approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely the manufacturer’s opinion or commendation of its products.
Wiring Schematics cont.SAH Air Handler Control Option A Schematic
Air Handler 10kW Electric Heat
97P901-03
Light emitting diode - Green
208-230V Relay coil
Electric Heat Contactor
Polarized connector
Factory Low voltage wiringFactory Line voltage wiringField low voltage wiringField line voltage wiringOptional blockDC Voltage PCB tracesInternal junctionQuick connect terminal
Thermal Limit Switch
Field wire lug
Ground
HE -
PB -
Heater element
Power block
Legend
N.O., N.C.
G
L1
ER1 to ER4 - Aux heat stage relays
1 2 3P
EHC
EHC
Breaker
TS
HE1FL1
RELAY
HE2 FL2
GL2L1
208-230/60/12
3
1RELAY
Yellow
WhiteBrown
Blue
Blue
Blue
Yellow
Blue
Yellow
Blue
Blue
Yellow
Orange
Tan
Transformer
Blk/WhYellow
24V
L2L1PBBlack
Blue
Red NOTE 1 Orange
Brown
1
2
3
L N G
5 SpeedECM
BlowerMotor
C
4
5
O
C
Y1
G
S
W1
L
X2
X1
R
Y2
TB
12V
Black
Blue
Red
Tan
Grey
12V
12V
12V
Thermostat
R
CY1
O
L1
Y2
G
W
Blue
Grey
Red
White
Black
Blue
White
Notes:1 – To operate in 208V mode replace the blue transformer wire connected to PB-L2 with red transformer wire.
2 – Low voltage wiring CLASS 2.
R1 R2
TS1
Yellow
Yellow
WIRE 24V THERMOSTAT AS SHOWN CONNECTED TO THE STRIP WIRES ALREADY CONNECTED TO TB. DO NOT CONNECT DIRECTLY TO THE TB TERMINALS. DAMAGE TO THE STAT MAY OCCUR. TB CAN BE USED TO CONNECT TO THE ABC BOARD IN THE COMPRESSOR SECTION
NOTE 3
3 – 24V Thermostat must be wired as shown to the loose wires using wire nuts. DO NOT CONNECT THERMOSTAT TO TB.
Grn/Yel
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2518AG1 04/17 20 Page _____ of _____
AIR HANDLER2-6 Tons
SAH
©2017 The manufacturer works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Purchaser’s approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely the manufacturer’s opinion or commendation of its products.
Wiring Schematics cont.SAH Air Handler Control Option A Schematic
Air Handler 15kW Electric Heat
97P901-04
HE3 FL3
HE1 TS1FL1
5
4
3
1
H
HSEQ1
5
4
3
1
H
HSEQ2
RELAY
HE2 FL2
208-
230/6
0/1
GL2
L1
BRK1
L2L1
BRK2
G
Circu
it 120
8-23
0/60/1
Circu
it 2
Blue
Yellow
Yellow
Blue
Blue
2
3
1 Orange
Blue
White
Brown
YellowBlack
Black
Red
Brown
Blue
Yellow
Blue
Blue Red
Tan
Transformer
Blk/WhYellow
24V
L2L1PBBlack
Blue
Red NOTE 1 Orange
Brown
1
2
3
L N G
5 SpeedECM
BlowerMotor
C
4
5
O
C
Y1
G
S
W1
L
X2
X1
R
Y2
TB
12V
Black
Blue
Red
Tan
Grey
12V
12V
12V
Thermostat
R
CY1
O
L1
Y2
G
W
Blue
Grey
Red
White
Black
White
Blue
Black
Red
NOTE 2
R1
TS2Yellow
Black
WIRE 24V THERMOSTAT AS SHOWN CONNECTED TO THE STRIP WIRES ALREADY CONNECTED TO TB. DO NOT CONNECT DIRECTLY TO THE TB TERMINALS. DAMAGE TO THE STAT MAY OCCUR. TB CAN BE USED TO CONNECT TO THE ABC BOARD IN THE COMPRESSOR SECTION
NOTE 4
Grn/Yel
Notes:1 – To operate in 208V mode replace the blue transformer wire connected to PB-L2 with red transformer wire.
2 – Use manufacturer’s part number 19P592-01 (jumper bar assembly) when single source power is required.
3 – Low voltage wiring CLASS 2.4 – 24V Thermostat must be wired as shown to the loose wires using wire nuts. DO NOT CONNECT THERMOSTAT TO TB.
Light emitting diode - Green
208-230V Relay coil
Electric Heat Contactor
Polarized connector
Factory Low voltage wiringFactory Line voltage wiringField low voltage wiringField line voltage wiringOptional blockDC Voltage PCB tracesInternal junctionQuick connect terminal
Thermal Limit Switch
Field wire lug
Ground
HE -
PB -
Heater element
Power block
Legend
N.O., N.C.
G
L1
ER1 to ER4 - Aux heat stage relays
1 2 3P
EHC
EHC
Breaker
TS
If two separate circuits are used to supply power to theauxiliary heat kit, the Installer will need to verify that each leg ofthe auxiliary heat circuit breakers are wired from the powersupply correctly in order for the electric heat kit to operateproperly. This can be done by measuring the supply sidevoltage of the auxiliary heat circuit breakers. Put a voltmeter onthe L2 side of Circuit Breaker One and on the L2 side of CircuitBreaker Two. The voltmeter should read approximately 0 volts.If the meter reads high voltage, the auxiliary heat breakersneed to be rewired so that breakers in the auxiliary heat kitmatch the wiring of the Disconnect Panel breakers. Meaning,L1 and L2 from one breaker in the disconnect panel mustconnect to L1 and L2 at one of the auxiliary heat circuitbreakers and L1 and L2 from the other breaker in thedisconnect panel must connect to L1 and L2 of the otherauxiliary heat circuit breaker, making sure that the L1 and L2from each disconnect breaker matches the L1 and L2 at eachof the auxiliary heat breakers.
Dual Power Supply Connections
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2518AG1 04/17 21 Page _____ of _____
AIR HANDLER2-6 Tons
SAH
©2017 The manufacturer works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Purchaser’s approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely the manufacturer’s opinion or commendation of its products.
Wiring Schematics cont.SAH Air Handler Control Option A Schematic
Air Handler 20kW Electric Heat
97P901-05
Factory Low voltage wiring
Legend
HE4FL4HE3 FL3
HE1FL1
5
4
3
1
H
HSEQ1
5
4
3
1
H
HSEQ2
RELAY RELAY
HE2 FL2
208-
230/6
0/1
GL2
L1
BRK1
L2L1
BRK2
G
Circu
it 120
8-23
0/60/1
Circu
it 2
Blue Blue
BlueBlue
Yellow
Black
Yellow
Black
Blue
Blue
2
3
1 Orange
Blue
White
White
Brown
Brown
Blue
BlackBlack
RedRed
RedBlack
Black
Red
Tan
Transformer
Blk/WhYellow
24V
L2L1PBBlack
Blue
Red NOTE 1 Orange
Brown
1
2
3
L N G
5 SpeedECM
BlowerMotor
C
4
5
O
C
Y1
G
S
W1
L
X2
X1
R
Y2
TB
12V
Black
Blue
Red
Tan
Grey
12V
12V
12V
Thermostat
R
CY1
O
L1
Y2
G
W
Blue
Grey
Red
White
Black
White
Blue
Black
Red
NOTE 2
R1R2
TS1Yellow
Black
TS2Yellow
Black
WIRE 24V THERMOSTAT AS SHOWN CONNECTED TO THE STRIP WIRES ALREADY CONNECTED TO TB. DO NOT CONNECT DIRECTLY TO THE TB TERMINALS. DAMAGE TO THE STAT MAY OCCUR. TB CAN BE USED TO CONNECT TO THE ABC BOARD IN THE COMPRESSOR SECTION
NOTE 4
Grn/Yel
Notes:1 – To operate in 208V mode replace the blue transformer wire connected to PB-L2 with red transformer wire.
2 – Use manufacturer’s part number 19P592-01 (jumper bar assembly) when single source power is required.
3 – Low voltage wiring CLASS 2.4 – 24V Thermostat must be wired as shown to the loose wires using wire nuts. DO NOT CONNECT THERMOSTAT TO TB.
Light emitting diode - Green
208-230V Relay coil
Electric Heat Contactor
Polarized connector
Factory Low voltage wiringFactory Line voltage wiringField low voltage wiringField line voltage wiringOptional blockDC Voltage PCB tracesInternal junctionQuick connect terminal
Thermal Limit Switch
Field wire lug
Ground
HE -
PB -
Heater element
Power block
Legend
N.O., N.C.
G
L1
ER1 to ER4 - Aux heat stage relays
1 2 3P
EHC
EHC
Breaker
TS
If two separate circuits are used to supply power to theauxiliary heat kit, the Installer will need to verify that each leg ofthe auxiliary heat circuit breakers are wired from the powersupply correctly in order for the electric heat kit to operateproperly. This can be done by measuring the supply sidevoltage of the auxiliary heat circuit breakers. Put a voltmeter onthe L2 side of Circuit Breaker One and on the L2 side of CircuitBreaker Two. The voltmeter should read approximately 0 volts.If the meter reads high voltage, the auxiliary heat breakersneed to be rewired so that breakers in the auxiliary heat kitmatch the wiring of the Disconnect Panel breakers. Meaning,L1 and L2 from one breaker in the disconnect panel mustconnect to L1 and L2 at one of the auxiliary heat circuitbreakers and L1 and L2 from the other breaker in thedisconnect panel must connect to L1 and L2 of the otherauxiliary heat circuit breaker, making sure that the L1 and L2from each disconnect breaker matches the L1 and L2 at eachof the auxiliary heat breakers.
Dual Power Supply Connections
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2518AG1 04/17 22 Page _____ of _____
AIR HANDLER2-6 Tons
SAH
©2017 The manufacturer works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Purchaser’s approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely the manufacturer’s opinion or commendation of its products.
Wiring Schematics cont.SAH Air Handler Control Option C Schematic 97P903-01
SUC
PHW HW
SCT
P8
MOTO
R P6
RS48
5 P7
ZONE P9
ABC
STEP
PER
ANA
ACC2
DHDI
V
C R L1 L1 L2 L2P1
2P1
0P5
P11
CR(-)(+) CR(-)(+) CR(-)(+)
P4P2
K1K2
K3
C
1C
2C
3CO
NDVS
DAT
AVS
PUM
PP3
V+CRTXRX +5
P14
10P1
CT2
43
CT2
43
CT1
21
CT1
21
StatusG
DISC
H
P16
P17
P18
P15
AHB™
SW1
Modbus Add. IDFuture Use
12345
ONOFF
Future UseAcc 2 – Dip 4Acc 2 – Dip 5
CCO
+5C
S+5
CPW
MC
C4
XC
CS
+5C
+58
CC
C7
69
Grn
23
45
1
ECM Blower Motor
234 1
Green/YellowBlue
Transformer
24V
YellowBlack/White
Black Blue
Red
Brown
Brown
Black
Black
Brown
Brown
T Gray
Gray
Communicating Thermostat
Green
White
BlackBlack
RedWhite
Green
PB2
PB3
Blower Motor Current Transducer
Leaving Air Temperature LAT
Condensate Overflow
Orange
Brown
RS485 NET
C R - + ABC P7
ABC Control Board in Split Unit
Unit Power 208-230/60/1
GL1 L2
T Black
BlackFP2 Sensor
PB1
L1
L2
Red
Note:1
White
Black
Black
Orange
Not UsedWhite
Orange
Accessory 2 Output
Analog Output 0-10VDC
Communicating Thermostat will connect to the COMM STAT (C R + -) power block PB3 in the air handler. A 4-conductor, 20AWG wire will need to connect from the TO ABC (C R + -) power block (PB2) in the Air Handler to the ABC P7(See detail ‘A’ on schematic) connection on the ABC board in the compressor section.
Detail ‘A’
TO COMM STAT C R + -TO ABC
C R + -
NOTE:3
CT
Not Used
Blower Pe
Factory settingsL-H settings MU"Aux" is factory "G" may be locaCFM is controlleMax ESP includ
066 0
MODEL MAX
022 0
026 0
030
060 0
0
036 0
042 0
048 0
Grn/Yel
Light emitting diode - Green
Fused Limit
Polarized connector
Factory Low voltage wiringFactory Line voltage wiringField low voltage wiringField line voltage wiringOptional blockDC Voltage PCB tracesInternal junctionQuick connect terminal
Thermal Limit Switch
Field wire lug
Ground
HE -
PB -
SW1 -
Heater element
Power block
DIP package 4 position
Legend
N.O., N.C.
G
L1
1 2 3P
Breaker
TS
FL
Notes:1 – To operate in 208V mode replace the blue transformer
wire connected to PB1-L2 with red transformer wire.
2 – Low voltage wiring CLASS 2.3 – DIP switch 1 on SW1 must be set in the OFF position.
Ther
mosta
t
RC
Y1
O
DH
Y2
G
W
LO
Non-Communicating Thermostat
LORCOGY1Y2
DHW
P1 ABC Board
Non-Communicating Thermostat will connect to the P1 connection on the ABC board in the compressor section. A 4-conductor, 20AWG wire will need to connect from the ABC P7 (See detail ‘A’ on schematic) connection to the TO ABC (C R + -) power block (PB2) in the Air Handler.
Air Handler No Electric Heat
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2518AG1 04/17 23 Page _____ of _____
AIR HANDLER2-6 Tons
SAH
©2017 The manufacturer works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Purchaser’s approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely the manufacturer’s opinion or commendation of its products.
Wiring Schematics cont.SAH Air Handler Control Option C Schematic 97P903-02
Air Handler 5kW Electric Heat
SUC
PHW HW
SCT
P8
MOTO
R P6
RS48
5 P7
ZONE P9
ABC
STEP
PER
ANA
ACC2
DHDI
V
C R L1 L1 L2 L2P1
2P1
0P5
P11
CR(-)(+) CR(-)(+) CR(-)(+)
P4P2
K1K2
K3
C
1C
2C
3CO
NDVS
DAT
AVS
PUM
PP3
V+CRTXRX +5
P14
10P1
CT2
43
CT2
43
CT1
21
CT1
21
StatusG
DISC
H
P16
P17
P18
P15
AHB™
SW1
Modbus Add. IDFuture Use
12345
ONOFF
Future UseAcc 2 – Dip 4Acc 2 – Dip 5
CCO
+5C
S+5
CPW
MC
C4
XC
CS
+5C
+58
CC
C7
69
Grn
23
45
1
ECM Blower Motor
234 1
Green/YellowBlue
Transformer
24V
YellowBlack/White
BlackBlue
Red
White
Blue
Brown
Brown
Black
Black
Brown
Brown
T Gray
Gray
White
Green
BlackBlack
RedGreen
White
PB2
Auxiliary Heat Current Transducer
Blower Motor Current Transducer
Leaving Air Temperature LAT
Condensate Overflow
Orange
Brown
HE1 TS1FL1
GL2L1
208-230/60/1
2
3
1RELAY
Yellow
White
Blue
Blue
Yellow
Blue
FP2 Sensor T Black
Black
PB1L1 L2
Red
Blue
BrownWires Not Used
Note:1
PB4
R1
PB3 TO COMM STAT C R + -TO ABC
C R + -
NOTE:3
RS485 NET
C R - + ABC P7
ABC Control Board in Split Unit
Detail ‘A’
Communicating Thermostat
Communicating Thermostat will connect to the COMM STAT (C R + -) power block PB3 in the air handler. A 4-conductor, 20AWG wire will need to connect from the TO ABC (C R + -) power block (PB2) in the Air Handler to the ABC P7(See detail ‘A’ on schematic) connection on the ABC board in the compressor section.
CT
Auxiliary Heat Current Transducer
Blo
FactoL-H s"Aux"G" mCFMMax
06
MO
02
02
03
06
03
04
04
Grn/Yel
Light emitting diode - Green
Fused Limit
Polarized connector
Factory Low voltage wiringFactory Line voltage wiringField low voltage wiringField line voltage wiringOptional blockDC Voltage PCB tracesInternal junctionQuick connect terminal
Thermal Limit Switch
Field wire lug
Ground
HE -
PB -
SW1 -
Heater element
Power block
DIP package 4 position
Legend
N.O., N.C.
G
L1
1 2 3P
Breaker
TS
FLNotes:
1 – To operate in 208V mode replace the blue transformer wire connected to PB1-L2 with red transformer wire.
2 – Low voltage wiring CLASS 2.3 – DIP switch 1 on SW1 must be set in the OFF position.
Ther
mosta
t
RC
Y1
O
DH
Y2
G
W
LO
Non-Communicating Thermostat
LORCOGY1Y2
DHW
P1 ABC Board
Non-Communicating Thermostat will connect to the P1 connection on the ABC board in the compressor section. A 4-conductor, 20AWG wire will need to connect from the ABC P7 (See detail ‘A’ on schematic) connection to the TO ABC (C R + -) power block (PB2) in the Air Handler.
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2518AG1 04/17 24 Page _____ of _____
AIR HANDLER2-6 Tons
SAH
©2017 The manufacturer works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Purchaser’s approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely the manufacturer’s opinion or commendation of its products.
Wiring Schematics cont.SAH Air Handler Control Option C Schematic 97P903-03
Communicating Thermostat
Communicating Thermostat will connect to the COMM STAT (C R + -) power block PB3 in the air handler. A 4-conductor, 20AWG wire will need to connect from the TO ABC (C R + -) power block (PB2) in the Air Handler to the ABC P7(See detail ‘A’ on schematic) connection on the ABC board in the compressor section.
SUC
PHW HW
SCT
P8
MOTO
R P6
RS48
5 P7
ZONE P9
ABC
STEP
PER
ANA
ACC2
DHDI
V
C R L1 L1 L2 L2P1
2P1
0P5
P11
CR(-)(+) CR(-)(+) CR(-)(+)
P4P2
K1K2
K3
C
1C
2C
3CO
NDVS
DAT
AVS
PUM
PP3
V+CRTXRX +5
P14
10P1
CT2
43
CT2
43
CT1
21
CT1
21
StatusG
DISC
H
P16
P17
P18
P15
AHB™
SW1
Modbus Add. IDFuture Use
12345
ONOFF
Future UseAcc 2 – Dip 4Acc 2 – Dip 5
CCO
+5C
S+5
CPW
MC
C4
XC
CS
+5C
+58
CC
C7
69
Grn
23
45
1
ECM Blower Motor
234 1
Green/YellowBlue
Transformer
24V
YellowBlack/WhiteBlack Blue
Red
White
BrownBlue
Blue
Brown
Brown
Black
Black
Brown
Brown
T Gray
Gray
White
Green
BlackBlack
RedGreen
White
PB2
PB3
Auxiliary Heat Current Transducer
Blower Motor Current Transducer
Leaving Air Temperature LAT
Condensate Overflow
Orange
Brown
HE1FL1
RELAY
HE2 FL2
GL2L1
208-230/60/1
2
3
1RELAY
Yellow
WhiteBrown
Blue
Blue
Blue
Yellow
Blue
Yellow
Blue
Blue
Yellow
T Black
BlackFP2 Sensor
PB1L1 L2
Red
Note:1
PB4
TS1
Yellow
Yellow
R1 R2
NOTE:3
TO COMM STAT C R + -
TO ABC C R + -
RS485 NET
C R - + ABC P7
ABC Control Board in Split Unit
Detail ‘A’
CT
Auxiliary Heat Current Transducer
Blower P
Factory settinL-H settings M"Aux" is facto"G" may be loCFM is controMax ESP inc
066
MODEL M
022
026
030
060
036
042
048
Grn/Yel
Ther
mosta
t
RC
Y1
O
DH
Y2
G
W
LO
Non-Communicating Thermostat
LORCOGY1Y2
DHW
P1 ABC Board
Non-Communicating Thermostat will connect to the P1 connection on the ABC board in the compressor section. A 4-conductor, 20AWG wire will need to connect from the ABC P7 (See detail ‘A’ on schematic) connection to the TO ABC (C R + -) power block (PB2) in the Air Handler.
Notes:1 – To operate in 208V mode replace the blue transformer
wire connected to PB1-L2 with red transformer wire.
2 – Low voltage wiring CLASS 2.
3 – DIP switch 1 on SW1 must be set in the OFF position.
Light emitting diode - Green
Fused Limit
Polarized connector
Factory Low voltage wiringFactory Line voltage wiringField low voltage wiringField line voltage wiringOptional blockDC Voltage PCB tracesInternal junctionQuick connect terminal
Thermal Limit Switch
Field wire lug
Ground
HE -
PB -
SW1 -
Heater element
Power block
DIP package 4 position
Legend
N.O., N.C.
G
L1
1 2 3P
Breaker
TS
FL
Air Handler 10kW Electric Heat
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2518AG1 04/17 25 Page _____ of _____
AIR HANDLER2-6 Tons
SAH
©2017 The manufacturer works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Purchaser’s approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely the manufacturer’s opinion or commendation of its products.
Wiring Schematics cont.
SAH Air Handler Control Option C Schematic 97P903-04
Air H
Yellow
Blue
Yellow
T Black
BlackFP2 Sensor
Red
Note:1
L2
Note:2
L1
PB4
TS2
Black
Yellow
SUC
PHW HW
SCT
P8
MOTO
R P6
RS48
5 P7
ZONE P9
ABC
STEP
PER
ANA
ACC2
DHDI
V
C R L1 L1 L2 L2P1
2P1
0P5
P11
CR(-)(+) CR(-)(+) CR(-)(+)
P4P2
K1K2
K3
C
1C
2C
3CO
NDVS
DAT
AVS
PUM
PP3
V+CRTXRX +5
P14
10P1
CT2
43
CT2
43
CT1
21
CT1
21
StatusG
DISC
H
P16
P17
P18
P15
AHB™
SW1
Modbus Add. IDFuture Use
12345
ONOFF
Future UseAcc 2 – Dip 4Acc 2 – Dip 5
CCO
+5C
S+5
CPW
MC
C4
XC
CS
+5C
+58
CC
C7
69
Grn
23
45
1
ECM Blower Motor
234 1
Green/YellowBlue
PB1
Transformer
24V
Red
Black
YellowBlack/White
Black Blue
Red
White
BrownBlue
Blue
Brown
Brown
Black
Black
Brown
Brown
T Gray
Gray
White
Green
BlackBlack
RedGreen
White
PB2
PB3
Auxiliary Heat Current Transducer
Blower Motor Current Transducer
Leaving Air Temperature LAT
Condensate Overflow
Orange
Brown
HE3 FL3
HE1 TS1FL1
5
4
3
1
H
HSEQ1
5
4
3
1
H
HSEQ2
RELAY
HE2 FL2
208-
230/6
0/1
GL2
L1
BRK1
L2L1
BRK2
G
Circu
it 120
8-23
0/60/1
Circu
it 2
Blue
Blue
Yellow
Blue
Blue
2
3
1
Blue
White
BrownBrown
YellowBlack
BlueRed
Black
Red
R1
NOTE:4
TO COMM STAT C R + -TO ABC
C R + -
RS485 NET
C R - + ABC P7
ABC Control Board in Split Unit
Detail ‘A’
Communicating Thermostat
Communicating Thermostat will connect to the COMM STAT (C R + -) power block PB3 in the air handler. A 4-conductor, 20AWG wire will need to connect from the TO ABC (C R + -) power block (PB2) in the Air Handler to the ABC P7(See detail ‘A’ on schematic) connection on the ABC board in the compressor section.
CT
Auxiliary Heat Current Transducer
Blowe
Factory sL-H settin"Aux" is f"G" may bCFM is coMax ESP
066
MODEL
022
026
030
060
036
042
048
Grn/Yel
Light emitting diode - Green
Fused Limit
Polarized connector
Factory Low voltage wiringFactory Line voltage wiringField low voltage wiringField line voltage wiringOptional blockDC Voltage PCB tracesInternal junctionQuick connect terminal
Thermal Limit Switch
Field wire lug
Ground
HE -
PB -
SW1 -
Heater element
Power block
DIP package 4 position
Legend
N.O., N.C.
G
L1
1 2 3P
Breaker
TS
FL
Notes:1 – To operate in 208V mode replace the blue transformer
wire connected to PB1-L2 with red transformer wire.
2 – Use manufacturer’s part number 19P592-01 (jumper bar assembly) when single source power is required.3 – Low voltage wiring CLASS 2.4 – DIP switch 1 on SW1 must be set in the OFF position.
Ther
mosta
t
RC
Y1
O
DH
Y2
G
W
LO
Non-Communicating Thermostat
LORCOGY1Y2
DHW
P1 ABC Board
Non-Communicating Thermostat will connect to the P1 connection on the ABC board in the compressor section. A 4-conductor, 20AWG wire will need to connect from the ABC P7 (See detail ‘A’ on schematic) connection to the TO ABC (C R + -) power block (PB2) in the Air Handler.
Air Handler 15kW Electric Heat
If two separate circuits are used to supply power to the auxiliary heat kit, the Installer will need to verify that each leg of the auxiliary heat circuit breakers are wired from the power supply correctly in order for the electric heat kit to operate properly. This can be done by measuring the supply side voltage of the auxiliary heat circuit breakers. Put a voltmeter on the L2 side of Circuit Breaker One and on the L2 side of Circuit Breaker Two. The voltmeter should read approximately 0 volts. If the meter reads high voltage, the auxiliary heat breakers need to be rewired so that breakers in the auxiliary heat kit match the wiring of the Disconnect Panel breakers. Meaning, L1 and L2 from one breaker in the disconnect panel must connect to L1 and L2 at one of the auxiliary heat circuit breakers and L1 and L2 from the other breaker in the disconnect panel must connect to L1 and L2 of the other auxiliary heat circuit breaker, making sure that the L1 and L2 from each disconnect breaker matches the L1 and L2 at each of the auxiliary heat breakers.
Dual Power Supply Connections
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2518AG1 04/17 26 Page _____ of _____
AIR HANDLER2-6 Tons
SAH
©2017 The manufacturer works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Purchaser’s approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely the manufacturer’s opinion or commendation of its products.
Wiring Schematics cont.SAH Air Handler Control Option C Schematic 97P903-05
RS485 NET
C R - + ABC P7
ABC Control Board in Split Unit
Detail ‘A’
Air Han
SUC
PHW HW
SCT
P8
MOTO
R P6
RS48
5 P7
ZONE P9
ABC
STEP
PER
ANA
ACC2
DHDI
V
C R L1 L1 L2 L2P1
2P1
0P5
P11
CR(-)(+) CR(-)(+) CR(-)(+)
P4P2
K1K2
K3
C
1C
2C
3CO
NDVS
DAT
AVS
PUM
PP3
V+CRTXRX +5
P14
10P1
CT2
43
CT2
43
CT1
21
CT1
21
StatusG
DISC
H
P16
P17
P18
P15
AHB™
SW1
Modbus Add. IDFuture Use
12345
ONOFF
Future UseAcc 2 – Dip 4Acc 2 – Dip 5
CCO
+5C
S+5
CPW
MC
C4
XC
CS
+5C
+58
CC
C7
69
Grn
23
45
1
ECM Blower Motor
234 1
Green/YellowBlue
PB1
Transformer
24V
HE4FL4HE3 FL3
HE1FL1
5
4
3
1
H
HSEQ1
5
4
3
1
H
HSEQ2
RELAY RELAY
HE2 FL2
208-
230/6
0/1
GL2
L1
BRK1
L2L1
BRK2
G
Circu
it 120
8-23
0/60/1
Circu
it 2
Blue Blue
BlueBlue
Yellow
Black
Yellow
Black
Blue
Blue
2
3
1
Blue
White
White
Brown
Brown
Blue
BlackBlack
RedRed
RedBlack
Black
Red
Red
Black
YellowBlack/White
Black Blue
Red
White
BrownBlue
Blue
Brown
Brown
Black
Black
Brown
Brown
T Gray
Gray
White
Green
BlackBlack
RedGreen
White
PB2
PB3
Auxiliary Heat Current Transducer
Blower Motor Current Transducer
Leaving Air Temperature LAT
Condensate Overflow
Orange
Brown T Black
BlackFP2 Sensor
Red
Note:1
Note:2
L1
L2
PB4
TS1
Black
YellowTS1
Yellow
Black
R1R2
NOTE:4
TO COMM STAT C R + -
TO ABC C R + -
Communicating Thermostat
Communicating Thermostat will connect to the COMM STAT (C R + -) power block PB3 in the air handler. A 4-conductor, 20AWG wire will need to connect from the TO ABC (C R + -) power block (PB2) in the Air Handler to the ABC P7(See detail ‘A’ on schematic) connection on the ABC board in the compressor section.
CT
Auxiliary Heat Current Transducer
Blower P
Factory settinL-H settings M"Aux" is facto"G" may be loCFM is controMax ESP inc
066
MODEL M
022
026
030
060
036
042
048Grn/Yel
Ther
mosta
t
RC
Y1
O
DH
Y2
G
W
LO
Non-Communicating Thermostat
LORCOGY1Y2
DHW
P1 ABC Board
Non-Communicating Thermostat will connect to the P1 connection on the ABC board in the compressor section. A 4-conductor, 20AWG wire will need to connect from the ABC P7 (See detail ‘A’ on schematic) connection to the TO ABC (C R + -) power block (PB2) in the Air Handler.
Light emitting diode - Green
Fused Limit
Polarized connector
Factory Low voltage wiringFactory Line voltage wiringField low voltage wiringField line voltage wiringOptional blockDC Voltage PCB tracesInternal junctionQuick connect terminal
Thermal Limit Switch
Field wire lug
Ground
HE -
PB -
SW1 -
Heater element
Power block
DIP package 4 position
Legend
N.O., N.C.
G
L1
1 2 3P
Breaker
TS
FL
Notes:1 – To operate in 208V mode replace the blue transformer
wire connected to PB1-L2 with red transformer wire.
2 – Use manufacturer’s part number 19P592-01 (jumper bar assembly) when single source power is required.3 – Low voltage wiring CLASS 2.4 – DIP switch 1 on SW1 must be set in the OFF position.
Air Handler 20kW Electric Heat
If two separate circuits are used to supply power to the auxiliary heat kit, the Installer will need to verify that each leg of the auxiliary heat circuit breakers are wired from the power supply correctly in order for the electric heat kit to operate properly. This can be done by measuring the supply side voltage of the auxiliary heat circuit breakers. Put a voltmeter on the L2 side of Circuit Breaker One and on the L2 side of Circuit Breaker Two. The voltmeter should read approximately 0 volts. If the meter reads high voltage, the auxiliary heat breakers need to be rewired so that breakers in the auxiliary heat kit match the wiring of the Disconnect Panel breakers. Meaning, L1 and L2 from one breaker in the disconnect panel must connect to L1 and L2 at one of the auxiliary heat circuit breakers and L1 and L2 from the other breaker in the disconnect panel must connect to L1 and L2 of the other auxiliary heat circuit breaker, making sure that the L1 and L2 from each disconnect breaker matches the L1 and L2 at each of the auxiliary heat breakers.
Dual Power Supply Connections
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2518AG1 04/17 27 Page _____ of _____
AIR HANDLER2-6 Tons
SAH
©2017 The manufacturer works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Purchaser’s approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely the manufacturer’s opinion or commendation of its products.
Engineering Guide Specifi cationsGeneral
The air handler shall provide vertical upflow, downflow, or
horizontal configurations in one package. Units shall be
listed by a nationally recognized safety-testing laboratory
or agency, such as Underwriter’s Laboratory (UL) or
Environmental Testing Laboratories (Intertek-ETL). The
air handler units shall be designed and AHRI performance
listed to operate with the geothermal split condensing units
as provided by the manufacturer. Each unit shall be pallet
mounted and shipped using dense cardboard corners/top
and stretch wrap for easy shipping damage inspection.
Casing and Cabinet The cabinet shall be fabricated from heavy-gauge
galvanized steel and polyester powder coat paint to
withstand 1000 hours of salt spray testing. The interior
shall be insulated with 1 in. thick, multi-density, cleanable
aluminum foil coated glass fiber with edges sealed or
tucked under flanges to prevent the introduction of glass
fibers into the discharge air. One large blower compartment
access panel shall be provided and shall be removable
with supply and return ductwork in place. The internal
components layout shall provide for major service with
the unit in-place for restricted access installations. The
blower assembly access shall be slide-out serviceable via a
‘works-in-a-drawer’ design. The cabinet shall be convertible
to horizontal or downflow applications by reconfiguring
the cabinet using only a nut driver. The unit shall be ‘zero
clearance’ approved on any of its external surfaces.
Refrigeration Circuit All units shall provide a fin tube air-to-refrigerant heat
exchanger of the “A” coil design. The finned tube coil shall
be sized for low-face velocity and constructed of lanced
aluminum fins bonded to aluminum tubes in a staggered
pattern. The coil shall include a composite drain pan.
The thermal expansion valve shall be factory installed and
provide proper superheat over the entire liquid temperature
range with minimal “hunting.” The valve shall operate in the
cooling mode through the use of an internal check valve.
Blower Motor and AssemblyThe blower shall be an oversized direct drive centrifugal
type with a dynamically balanced wheel. The housing
and wheel shall be designed for quiet low outlet velocity
operation and of galvanized or galvalume steel construction.
Tight blower housing geometry shall not be permitted. The
blower housing shall be removable from the unit without
disconnecting the supply air ductwork for servicing of the
blower motor through a ‘works-in-a-drawer’ design. The
high efficiency blower motor shall be either a 5 speed ECM
or a variable speed ECM type. The blower motor shall be
isolated from the housing by rubber grommets. The motor
shall be permanently lubricated ball bearings and have
thermal overload protection.
Electrical A control section shall be located within the air handler
compartment and shall contain either a 75VA or 100VA
transformer, 24 volt activated. Transformers shall be
protected by internal circuit breakers. Units shall be
name-plated for use with time delay fuses or HACR circuit
breakers. Unit controls shall be either communicating
or 24 volt type. An Aurora AHB (control option C), a
microprocessor-based controller interfaces with the ABC
located in the compressor section to control unit operation,
shall be optional. The AHB control shall provide operational
sequencing, blower speed control, air coil freeze detection,
condensate overflow sensing, auxiliary heat staging, field
selectable options, and accessory output.
An integral circuit breaker shall be provided on all units
employing 15 kW or 20 kW electric heat. The control
shall maintain the blower operation 30 seconds after the
compressor or electric heat inputs have terminated.
A terminal block with screw terminals will be provided
for field control wiring. All units shall have knockouts for
entrance of low and line voltage wiring. The blower motor
and control box shall be harness plug wired for easy
removal.
An optional Aurora Interface Diagnostic (AID) Tool shall
communicate with the Aurora control allowing quick and
easy access to setup, monitoring, and troubleshooting of
any Aurora control. The device shall include the features of
fault description and history, manual operation capability,
sensor readings, timings, and other diagnostic tools.
Piping Refrigerant connections shall be made using sweat
copper joints. The condensate connections shall be a 3/4 in.
NPT.
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2518AG1 04/17 28 Page _____ of _____
AIR HANDLER2-6 Tons
SAH
©2017 The manufacturer works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Purchaser’s approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely the manufacturer’s opinion or commendation of its products.
Revision Guide
Pages: Description: Date: By:
All Document Creation 01 Mar. 2017 JM