28
AIR HANDLER R-410A Refrigerant 2-6 Tons Submittal Data English Language/IP Units SD2518AG1 04/17 SAH

R-410A Refrigerant 2-6 Tons Submittal DataAIR HANDLER R-410A Refrigerant 2-6 Tons Submittal Data English Language/IP Units SD2518AG1 04/17 SAH

  • Upload
    others

  • View
    21

  • Download
    0

Embed Size (px)

Citation preview

Page 1: R-410A Refrigerant 2-6 Tons Submittal DataAIR HANDLER R-410A Refrigerant 2-6 Tons Submittal Data English Language/IP Units SD2518AG1 04/17 SAH

AIR HANDLERR-410A Refrigerant

2-6 Tons

Submittal Data

English Language/IP Units

SD2518AG1 04/17

SAH

Page 2: R-410A Refrigerant 2-6 Tons Submittal DataAIR HANDLER R-410A Refrigerant 2-6 Tons Submittal Data English Language/IP Units SD2518AG1 04/17 SAH

Contractor: P.O.:

Engineer:

Project Name: Unit Tag:

SD2518AG1 04/17 2 Page _____ of _____

AIR HANDLER2-6 Tons

SAH

©2017 The manufacturer works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Purchaser’s approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely the manufacturer’s opinion or commendation of its products.

Model Nomenclature

CompatibilityAir Handler Sizing SelectionThe SAH Air Handlers are designed for R-410A refrigerant and should be matched with split compressor section according

to the table below.

Air Handler Indoor Split Model (Single) Indoor Split Model (Dual Capacity)

Outdoor Split Model (Dual Capacity)

RatedAirfl ow(CFM) Electric Heat (kW)

SAH022***1*R1S1* 022 - 800 5

SAH026***1*R1S1* - 026 026 850 5

SAH030***1*R1S1* 030 - - 1000 5

SAH036***1*R1S1* 036 - - 1200 5, 10

SAH036***1*R1S1* - 038 038 1200 5, 10

SAH042***1*R1S1* 042 - - 1300 10, 15

SAH048***1*R1S1* 048 - - 1500 10, 15

SAH048***1*R1S1* - 049 049 1500 10, 15

SAH060***1*R1S1* 060 - - 1800 10, 15, 20

SAH060***1*R1S1* - 064 064 1800 10, 15, 20

SAH066***1*R1S1* 070 - - 2000 10, 15, 20

SAH066***1*R1S1* - 072 072 2000 10, 15, 20

1/31/2017

SAH 036 A 00 1 A 11-3 4-6 7 8-9 10 11

ModelSAH – Series Air Handler

Unit CapacityRefrigeration (DX)

022 MBTUH026 MBTUH030 MBTUH036 MBTUH042 MBTUH048 MBTUH060 MBTUH066 MBTUH

VintageA = Factory Use Only

Electric Heat 00 – None 05 – 5kW (022 – 030 only) No Breakers 10 – 10kW (036 – 066 only) No Breakers 15 – 15kW (042 – 066 only) with Breakers 20 – 20kW (060 - 066 only) with Breakers

*Factory Use Only

Position1 – Multi-position

Future OptionsS – Standard

Voltage1-208-230/60/1

Air CoilR – Refrigerant

Controls/ MotorA – Standard/ 5 Speed ECMC – Aurora AHB/ Variable Speed ECM1

TXV1 – Factory Installed

Rev.: 2/27/2017

S i Ai H dl

R12

114S

15 16*

13

Note: To field convert the SAH to bottomflow air discharge. The SAHBCK kit must be ordered separately.Note: Air flow on the 060 and 066 units in the horizontal configurations should be limited to 1900 cfm in cooling mode, or condensate blow off may occur.

1. Only available with Aurora controls in the compressor section.

Page 3: R-410A Refrigerant 2-6 Tons Submittal DataAIR HANDLER R-410A Refrigerant 2-6 Tons Submittal Data English Language/IP Units SD2518AG1 04/17 SAH

Contractor: P.O.:

Engineer:

Project Name: Unit Tag:

SD2518AG1 04/17 3 Page _____ of _____

AIR HANDLER2-6 Tons

SAH

©2017 The manufacturer works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Purchaser’s approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely the manufacturer’s opinion or commendation of its products.

Air Handler Features and Benefi ts Air Coil

Designed for R-410A refrigerant. Configured as an 'A' coil,

aluminum tubes and enhanced corrugated lanced aluminum

fins to provide high efficiencies at low face velocities.

Cabinet

Constructed of heavy gauge environmentally-responsible

galvanized steel for maximum corrosion resistance. All

units are painted with a powder coat finish. All interior

surfaces are lined with 1˝ thick, foil lined acoustic type

fiber insulation, applied in a manner that prevents the

introduction of glass fibers into the air stream. Multiple

knockouts in various sizes facilitate power and low voltage

wiring. Multiple access panels for ease of service.

Factory SealedAchieves 2% or less total airflow leakage rate.

Installation EaseCabinets are shipped in one piece but can be separated for

ease of installation in tight spaces.

Auxiliary/ Emergency Electric Heat

Electric heat packages can be factory or field installed.

For field installed electric heat the Auxiliary Heat

Compatibility table below shows the available heater

packages for the air handler.

ConfigurationsCabinets are factory configured for upflow and horizontal

right hand air discharge installation but can be easily

configured for horizontal left hand or bottomflow air

discharge.

Drain Pans

Two composite drain pans included. One for vertical and

one for horizontal applications. The pans come equipped

with primary and secondary drain connections.

Electrical DisconnectFactory installed circuit breaker on 15kW/20kW heaters.

Expansion Device

Factory installed TXV with internal check valve inside

of cabinet.

Refrigerant Connections

Suction and liquid lines have sweat connections extended

outside of cabinet for ease of connection.

Controls

The SAH Air Handler has two control options.

Control option 'A' has a terminal strip board that uses the

24V input from the thermostat to control the 5 speed ECM

motor.

Control option 'C' has the AHB board. The AHB is part of

the Aurora controls platform and communicates via modbus

to the ABC. The AHB board controls the air handlers

variable speed motor, auxiliary heat staging, provides

condensate overflow protection, air coil freeze protection

FP2, auxiliary heat and blower energy monitoring, leaving

air temperature, and is Symphony compatible with Aurora

controls in the compressor section..

Auxiliary Heat Compatibility

Model kW Stages Air Handler Compatibility

022 - 030 036 042 - 048 060 066

19P659-01 5 1 X X

19P659-02 10 2 X X X X

19P659-03 15 2 X X X

19P659-04 20 2 X X

1/10/2017

Page 4: R-410A Refrigerant 2-6 Tons Submittal DataAIR HANDLER R-410A Refrigerant 2-6 Tons Submittal Data English Language/IP Units SD2518AG1 04/17 SAH

Contractor: P.O.: Engineer:

Project Name: Unit Tag:

SD2518AG1 04/17 4 Page _____ of _____

AIR HANDLER2-6 Tons

SAH

©2017 The manufacturer works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Purchaser’s approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely the manufacturer’s opinion or commendation of its products.

Dimensional Data - DX Air Handler

TOP VIEW

YZ

AA

CC

EE

DDBB

FF

BOTTOM VIEW

UV

W

X

A

HJ K

LM

O

FRONT VIEW

P

Q

R

S

T

N

B

C DE

RIGHT SIDE VIEWF

GG

HH

R.SIDE VIEW 2 TON

NNPP

QQ

TOP VIEW 2 TON

JJ

KK

LLMM

TOP VIEW 3-6 TON BOTTOM VIEW R.SIDE VIEW 2 TON

RIGHT SIDE VIEW 3-6 TONFRONT VIEW

TOP VIEW 2 TON

Top Flow/Horizontal Unit Configuration

SAH Air Handler - Topflow/Horizontal

Topflow/Overall Cabinet

Horizontal D E

ConfigurationA B C 3/4" cond 1/2" cond F H J K L M N O P Q R S T U V W X Y Z AA BB CC DD EE FF GG HH JJ KK LL MM NN PP QQ

Width Depth HeightPower Supply

Low Voltage

Suction Liquid Low

Voltagein. 17.5 21.2 47.0 42.6 45.1 2.5 1.9 4.8 6.4 8.8 10.1 1.1 1.7 2.9 4.5 13.0 14.6 16.2 2.1 13.3 2.1 18.4 1.7 3.1 4.1 1.1 14.0 1.8 14.0 1.8 43.9 5.1 3.0 4.4 1.7 4.2 42.6 45.1 2.5

cm. 44.5 53.8 119.4 108.2 114.6 6.4 4.8 12.2 16.3 22.4 25.7 2.8 4.3 7.4 11.4 33.0 37.1 41.1 5.3 33.8 5.3 46.7 4.3 7.9 10.4 2.8 35.6 4.6 35.6 4.6 111.5 13.0 7.6 11.2 4.2 10.5 108.2 114.6 6.4in. 21.6 21.2 52.0 50.1 47.6 2.6 1.9 4.8 6.4 8.5 9.7 1.1 1.7 2.9 4.5 16.7 18.3 20.1 2.2 17.2 2.2 18.5 1.6 4.2 6.7 1.2 14.0 3.8 14.0 1.9

cm. 54.9 53.8 132.1 127.3 120.9 6.6 4.7 12.1 16.3 21.6 24.6 2.8 4.4 7.3 11.4 42.4 46.5 51.1 5.5 43.8 5.6 46.9 4.1 10.5 16.9 3.0 35.5 9.6 35.5 4.8in. 24.9 21.2 58.0 56.1 53.2 2.6 1.9 4.8 6.4 9.6 10.8 1.1 1.7 2.9 4.5 20.3 21.9 23.5 2.2 20.6 2.2 18.4 1.7 4.2 6.7 1.5 18.0 3.4 18.0 1.8

cm. 63.2 53.8 147.3 142.5 135.1 6.6 4.8 12.2 16.3 24.4 27.4 2.8 4.3 7.4 11.4 51.6 55.6 59.7 5.6 52.3 5.6 46.7 4.3 10.7 17.0 3.8 45.7 8.6 45.7 4.6Condensate is plastic 3/4" FPT Discharge flange is field installed and extends 1" (25.4 mm) from cabinet

024

036

048-060

Refrigerant Connections

Power Supply

" Y" IS 1 3/8 KNOCKOUT HIGH VOLTAGE"Z" IS 1 1/8 KNOCKOUT HIGH VOLTAGE "AA" IS 7/8 KNOCKOUT LOW VOLTAGE

024 CABINET DIMENSIONS ONLY

POWER SUPPLY

022-030

036

042-066

Page 5: R-410A Refrigerant 2-6 Tons Submittal DataAIR HANDLER R-410A Refrigerant 2-6 Tons Submittal Data English Language/IP Units SD2518AG1 04/17 SAH

Contractor: P.O.: Engineer:

Project Name: Unit Tag:

SD2518AG1 04/17 5 Page _____ of _____

AIR HANDLER2-6 Tons

SAH

©2017 The manufacturer works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Purchaser’s approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely the manufacturer’s opinion or commendation of its products.

Dimensional Data - DX Air HandlerBottom Flow Unit Configuration

LEFT SIDE VIEW 2 TON UNIT

BB

AACC

DD

F

C

B

ED

F

LEFT SIDE VIEW

A

GH I

JK L

MN

O

P

Q

R

FRONT VIEW

Z

W

X

Y

TOP VIEW

T

S

U

V

BOTTOM VIEW

LEFT SIDE VIEW 2 TON UNIT

LEFT SIDE VIEW 3-6 TON FRONT VIEW

TOP VIEW BOTTOM VIEW

SAH Air Handler - Bottom flow

Overall Cabinet

Bottomflow D E F

Configuration A B C 1/2" cond 3/4" cond G H I J K L M N O P Q R S T U V W X Y Z AA BB CC DD

Width Depth HeightLow

VoltagePower Supply

Power Supply

Suction Liquid

in. 17.5 21.2 47.0 4.4 1.9 2.5 22.8 25.7 27.3 29.5 30.8 1.1 1.7 2.8 4.5 13.0 14.5 16.2 1.1 1.8 14.0 18.0 2.2 2.2 13.7 18.5 5.0 3.1 1.8 4.3cm. 44.5 53.8 119.4 11.2 4.8 6.4 57.9 65.3 69.3 74.9 78.2 2.8 4.3 7.1 11.4 33.0 36.8 41.1 2.8 4.6 35.6 45.7 5.6 5.6 34.8 47.0 12.7 7.9 4.6 11.0in. 21.5 21.2 52.0 4.4 1.9 2.6 22.8 25.7 27.3 29.3 30.6 1.1 1.7 2.8 4.5 16.6 18.2 20.1 1.2 3.8 14.0 14.0 2.2 2.2 17.3 18.5

cm. 54.6 53.8 132.1 11.2 4.8 6.6 57.9 65.3 69.3 74.5 77.7 2.7 4.3 7.2 11.4 42.2 46.3 51.1 3.0 9.7 35.6 35.6 5.6 5.6 43.8 46.9in. 24.9 21.2 58.0 4.4 1.9 2.6 24.0 27.0 28.5 31.3 32.8 1.1 1.7 2.8 4.5 20.2 21.9 23.5 1.2 3.4 18.0 18.0 2.1 2.2 20.5 18.5

cm. 63.2 53.8 147.3 11.2 4.8 6.6 61.0 68.6 72.4 79.5 83.3 2.8 4.3 7.1 11.4 51.3 55.6 59.7 3.0 8.6 45.7 45.7 5.3 5.6 52.1 47.0

Condensate is plastic 3/4" FPT Discharge flange is field installed and extends 1" (25.4 mm) from cabinet

POWER SUPPLY 024 ONLY

Refrigerant Connections

048-060

036

024

036

042-066

022-030

Page 6: R-410A Refrigerant 2-6 Tons Submittal DataAIR HANDLER R-410A Refrigerant 2-6 Tons Submittal Data English Language/IP Units SD2518AG1 04/17 SAH

Contractor: P.O.: Engineer:

Project Name: Unit Tag:

SD2518AG1 04/17 6 Page _____ of _____

AIR HANDLER2-6 Tons

SAH

©2017 The manufacturer works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Purchaser’s approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely the manufacturer’s opinion or commendation of its products.

Dimensional DataRefrigerant Coil

A

BC

H

I

J

K

F

D E

L

G

LEFT SIDE BOTTOM

FRONT

1

2

3

Overall DimensionsUncased 321Models A B C Suction Liquid Condensate

D E F G H I J K LWidth Depth Height* Sweat Sweat NPT

SRAA026U*in. 16.1 20.7 17.5 5/8 3/8 3/4 7.7 8.9 0.3 0.8 2.0 3.6 12.3 13.9 0.7

cm. 40.8 52.6 44.5 1.6 1.0 1.9 19.4 22.5 0.8 1.9 5.1 9.1 31.2 35.3 1.8

SRAA036U*in. 19.7 20.7 21.1 3/4 3/8 3/4 7.2 8.6 0.3 1.1 2.1 3.8 15.9 17.5 0.7

cm. 50.0 52.6 53.6 1.9 1.0 1.9 18.2 21.8 0.8 2.7 5.4 9.5 40.4 44.5 1.8

SRAA048U*in. 23.2 20.7 24.9 3/4 3/8 3/4 8.4 9.6 0.2 0.9 2.1 3.8 19.5 21.0 0.7

cm. 58.9 52.6 63.2 1.9 1.0 1.9 21.3 24.4 0.4 2.3 5.3 9.7 49.5 53.3 1.8

SRAA060U*in. 23.2 20.7 29.4 7/8 1/2 3/4 8.5 9.8 0.3 0.9 2.1 3.8 19.5 21.0 0.7

cm. 58.9 52.6 74.6 2.2 1.3 1.9 21.6 24.9 0.8 2.2 5.3 9.7 49.5 53.3 1.8

ConnectionsRefrigerant Connections Condensate Connections

*NOTE: All refrigerant coils feature factory insta lled TXV.

Page 7: R-410A Refrigerant 2-6 Tons Submittal DataAIR HANDLER R-410A Refrigerant 2-6 Tons Submittal Data English Language/IP Units SD2518AG1 04/17 SAH

Contractor: P.O.: Engineer:

Project Name: Unit Tag:

SD2518AG1 04/17 7 Page _____ of _____

AIR HANDLER2-6 Tons

SAH

©2017 The manufacturer works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Purchaser’s approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely the manufacturer’s opinion or commendation of its products.

Dimensional Data - DX Cased Coils

NOTE: Cased coils are shipped with a 1" Flange Kit.

S CASED AIR COIL

Overall Cabinet

A B C D E F G H I J K L M N O

Width Depth Height Suction Liquid Suction Liquid

in. 17.8 21.5 26.3 8.8 10.1 1.0 1.6 1.9 4.8 6.4 2.7 4.4 13.0 14.6 16.2cm. 45.2 54.6 66.8 22.4 25.7 2.5 4.1 4.8 12.2 16.3 6.9 11.2 33.0 37.1 41.1in. 21.5 21.5 31.1 8.5 9.8 1.1 1.7 1.7 4.6 6.3 3.0 4.6 16.8 18.4 20.2cm. 54.6 54.6 79.0 21.6 24.8 2.8 4.3 4.3 11.7 16.0 7.6 11.7 42.5 46.7 51.3in. 24.9 21.4 35.3 9.5 10.8 1.1 1.7 1.9 4.8 6.4 3.0 4.7 20.3 22.0 23.5cm. 63.2 54.4 89.6 24.1 27.4 2.8 4.3 4.8 12.1 16.3 7.6 11.9 51.6 55.9 59.7

048-060

026

036

Refrigerant Connections Condensate ConnectionsTopflow & Horizontal

ConfigurationQ R S T U V W

13.9 2.0 2.0 17.6 2.0 2.0 2.035.3 5.1 5.1 44.7 5.1 5.1 5.117.6 2.0 2.0 17.6 2.0 2.0 2.044.8 5.1 5.1 44.7 5.1 5.1 5.121.0 2.0 2.0 17.6 2.0 2.0 2.053.3 5.1 5.1 44.7 5.1 5.1 5.1

Duct Connections

"C"

"H""I" "J"

"D""E"

"K"

"L"

"M"

"N"

"O"

"F"

"G"

SAH CASED AIR COIL

"W"

"V"

"U"

"B"

"A"

Q

R

S

T

TOP VIEW BOTTOM VIEW

Page 8: R-410A Refrigerant 2-6 Tons Submittal DataAIR HANDLER R-410A Refrigerant 2-6 Tons Submittal Data English Language/IP Units SD2518AG1 04/17 SAH

Contractor: P.O.: Engineer:

Project Name: Unit Tag:

SD2518AG1 04/17 8 Page _____ of _____

AIR HANDLER2-6 Tons

SAH

©2017 The manufacturer works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Purchaser’s approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely the manufacturer’s opinion or commendation of its products.

Model Airflow (CFM) Dry Coil

SRAA026C1

600 0.08

800 0.14

1000 0.20

SRAA036C1

1000 0.11

1200 0.14

1400 0.18

SRAA048C1

1200 0.12

1400 0.15

1600 0.19

1800 0.25

SRAA060C1

1600 0.21

1800 0.27

2000 0.33

2200 0.38

3/7/2017

SR Cased Coil Air Side Pressure Drop (inches of WC)

Page 9: R-410A Refrigerant 2-6 Tons Submittal DataAIR HANDLER R-410A Refrigerant 2-6 Tons Submittal Data English Language/IP Units SD2518AG1 04/17 SAH

Contractor: P.O.:

Engineer:

Project Name: Unit Tag:

SD2518AG1 04/17 9 Page _____ of _____

AIR HANDLER2-6 Tons

SAH

©2017 The manufacturer works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Purchaser’s approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely the manufacturer’s opinion or commendation of its products.

SAH 5 Speed ECM Blower Performance Data Option ABlower Performance 5 Speed ECM Control Option A

ModelMotor Speed

Motor Tap

T’stat Connection

Blower Size

Motor HP

Airflow (cfm) at External Static Pressure (in. wg)

0 0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45 0.50 0.60 0.70 0.80 0.90 1.00

022

High 5 W

9 x 7 1/2

1130 1115 1100 1090 1080 1065 1050 1040 1030 1015 1000 980 950 - - -

Med High 4 Y2* 1040 1025 1010 1000 990 975 960 945 930 915 900 880 850 - - -

Med 3 950 935 920 905 890 875 860 845 830 815 800 760 730 - - -

Med Low 2 Y1 860 845 830 815 800 785 770 755 740 720 700 660 590 - - -

Low 1 G 740 720 700 680 660 645 630 605 580 540 500 460 - - - -

026

High 5 W

9 x 7 1/2

1130 1115 1100 1090 1080 1065 1050 1040 1030 1015 1000 980 950 - - -

Med High 4 Y2* 1040 1025 1010 1000 990 975 960 945 930 915 900 880 850 - - -

Med 3 950 935 920 905 890 875 860 845 830 815 800 760 730 - - -

Med Low 2 Y1 860 845 830 815 800 785 770 755 740 720 700 660 590 - - -

Low 1 G 740 720 700 680 660 645 630 605 580 540 500 460 - - - -

030

High 5 W

9 x 7 1/2

1220 1205 1190 1180 1170 1160 1150 1140 1130 1115 1100 1050 930 - - -

Med High 4 Y2* 1130 1115 1100 1090 1080 1070 1060 1045 1030 1015 1000 980 950 - - -

Med 3 1040 1030 1020 1005 990 975 960 945 930 915 900 890 850 - - -

Med Low 2 Y1 950 935 920 905 890 875 860 845 830 815 800 770 730 - - -

Low 1 G 790 770 750 735 720 700 680 660 640 620 600 530 500 - - -

036

High 5 W

10 x 8 1/2

1450 1435 1420 1405 1390 1375 1360 1345 1330 1315 1300 1270 1250 1210 - -

Med High 4 Y2* 1350 1335 1320 1305 1290 1275 1260 1245 1230 1215 1200 1170 1140 1100 - -

Med 3 Y1 1170 1150 1130 1115 1100 1080 1060 1045 1030 1015 1000 960 920 880 - -

Med Low 2 1000 980 960 940 920 905 890 870 850 825 800 760 710 650 - -

Low 1 G 990 915 840 800 760 730 700 680 660 630 600 520 470 430 - -

042

High 5 W

11 x 10 1

1960 1945 1930 1915 1900 1880 1860 1845 1830 1810 1790 1750 1700 1660 - -

Med High 4 Y2* 1790 1775 1760 1745 1730 1710 1690 1670 1650 1535 1420 1560 1500 1450 - -

Med 3 1700 1685 1670 1650 1630 1615 1600 1575 1550 1525 1500 1450 1400 1350 - -

Med Low 2 Y1 1630 1560 1600 1520 1560 1535 1510 1490 1470 1445 1420 1370 1300 1250 - -

Low 1 G 1490 1445 1400 1375 1350 1325 1300 1270 1240 1210 1180 1120 1000 930 - -

048

High 5 W

11 x 10 1

1960 1945 1930 1915 1900 1880 1860 1845 1830 1810 1790 1750 1700 1660 1600 -

Med High 4 Y2* 1790 1775 1760 1745 1730 1710 1690 1670 1650 1535 1420 1560 1500 1450 1450 -

Med 3 1700 1685 1670 1650 1630 1615 1600 1575 1550 1525 1500 1450 1400 1350 1350

Med Low 2 Y1 1630 1560 1600 1520 1560 1535 1510 1490 1470 1445 1420 1370 1300 1250 1250 -

Low 1 G 1490 1445 1400 1375 1350 1325 1300 1270 1240 1210 1180 1120 1000 930 930 -

060

High 5 W

11 x 10 1

2210 2230 2190 2194 2170 2155 2130 2120 2100 2087 2060 2020 2000 1960 1920 1890

Med High 4 Y2* 2030 2073 2000 2035 1970 1995 1940 1958 1910 1922 1870 1840 1800 1760 1720 1680

Med 3 1850 1931 1820 1889 1790 1850 1760 1812 1730 1774 1680 1640 1600 1560 1510 1450

Med Low 2 Y1 1770 1796 1740 1761 1710 1718 1680 1682 1630 1651 1590 1560 1500 1450 1400 1340

Low 1 G 1570 1661 1540 1616 1510 1573 1460 1533 1420 1495 1370 1320 1250 1200 1100 1020

066

High 5 W

11 x 10 1

2390 2454 2370 2414 2340 2371 2320 2328 2290 2289 2270 2230 2200 2170 2140 2100

Med High 4 Y2* 2210 2248 2180 2205 2160 2166 2140 2129 2100 2094 2070 2040 2000 1960 1940 1890

Med 3 Y1 2030 2115 2010 2072 1980 2030 1950 1996 1900 1965 1880 1840 1800 1760 1720 1680

Med Low 2 1860 1985 1830 1939 1800 1898 1770 1862 1730 1828 1690 1640 1600 1570 1510 1460

Low 1 G 1780 1784 1750 1742 1720 1696 1680 1656 1640 1625 1600 1550 1500 1460 1400 1380Factory speed settings are in BoldAir flow values are with dry coil and standard filterFor wet coil performance first calculate the face velocity of the air coil (Face Velocity [fpm] = Airflow [cfm] / Face Area [sq ft]). Then for velocities of 200 fpm reduce the static capability by 0.03 in. wg, 300 fpm by 0.08 in. wg, 400 fpm by 0.12in. wg., and 500 fpm by 0.16 in. wg. Highest setting is for auxiliary heat (W) and lowest setting is for constant blower (G). The “Y1” and “Y2” settings must be between the “G” and “W” settings.*Single speed compressor section units will need to remove the TAN wire on the 5 speed motor and replace it with the RED wire. Tape end and secure the TAN wire.The SAH Air Handler blower is factory wired for dual speed compressor section operation.

1/10/17

ed for dual speed compressor section operation.

Page 10: R-410A Refrigerant 2-6 Tons Submittal DataAIR HANDLER R-410A Refrigerant 2-6 Tons Submittal Data English Language/IP Units SD2518AG1 04/17 SAH

Contractor: P.O.: Engineer:

Project Name: Unit Tag:

SD2518AG1 04/17 10 Page _____ of _____

AIR HANDLER2-6 Tons

SAH

©2017 The manufacturer works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Purchaser’s approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely the manufacturer’s opinion or commendation of its products.

5-Speed ECM Constant Torque MotorsThe 5-Speed ECM is a 'Constant Torque' ECM motor and

delivers air flow similar to a PSC but operates as efficiently

as an ECM Motor. Because it's an ECM Motor, the 5-Speed

ECM can ramp slowly up to down like the ECM motor. There

are 5 possible speed taps available on the 5-Speed ECM

motor with #1 being the lowest airflow and #5 being the

highest airflow. These speed selections are preset at the

time of manufacture and are easily changed in the field if

necessary.

If more than one tap are energized at the same time, built

in logic gives precedence to the highest tap number and

allows air flow to change with G, Y1, Y2 and W signals. Each

of those 5 speeds has a specific 'Torque' value programmed

into the motor for each speed selection. As static pressure

increases, airflow decreases resulting in less torque on the

rotor. The motor responds only to changes in torque and

adjusts its speed accordingly.

The 5-Speed ECM motor is powered by line voltage but the

motor speed is energized by 24 VAC.

5-Speed ECM Benefits:

• High Efficiency

• Soft Start

• 5 speeds with up to 4 speeds on-line

• Built-in logic allows air flow to change with G, Y1, Y2

and W signals

• Super efficient low airflow continuous blower setting.

Setting Blower Speed - 5-Speed ECM5-Speed ECM blower motors have five (5) speeds of which

three (3) are selectable on single speed and four (4) are

selectable on dual capacity.

Caution: Disconnect all power before performing this operation.

L G NC

High VoltageConnections

3/16 in.

1 2 3 4 5G - Blue

Y1 - Red

AUX - Gray

C - Black

L - OrangeG - Green

N - Brown

Low VoltageConnections 1/4 in.

L G NC

1 2 3 4 5 AUX - GrayG - Blue

Y1 - Red Y2 - Tan

C - Black

L - OrangeG - Green

N - Brown

High VoltageConnections

3/16 in.

Low VoltageConnections 1/4 in.

5-Speed ECM Motor Connections - Single Speed Splits

5-Speed ECM Motor Connections - Dual Capacity Splits

SAH 5 Speed ECM Blower Performance Data Option A cont.

Page 11: R-410A Refrigerant 2-6 Tons Submittal DataAIR HANDLER R-410A Refrigerant 2-6 Tons Submittal Data English Language/IP Units SD2518AG1 04/17 SAH

Contractor: P.O.: Engineer:

Project Name: Unit Tag:

SD2518AG1 04/17 11 Page _____ of _____

AIR HANDLER2-6 Tons

SAH

©2017 The manufacturer works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Purchaser’s approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely the manufacturer’s opinion or commendation of its products.

Blower Performance Data Option CBlower Performance Variable Speed ECM Control Option C

MODEL MAX ESPAIR FLOW SPEED SETTINGS

1 2 3 4 5 6 7 8 9 10 11 12

022 0.50 400500

G600

L700

800H

9001000Aux

1100 1200

026 0.50 400500

G600

700L

800900

H1000Aux

1100 1200

030 0.50 400500

G600

700L

800900

H1000Aux

1100 1200

036 0.50 550 650700

G800 850 900

950L

10501100

H1200

1300Aux

042 0.75 650 750 800900

G1000 1150

1200L

13001400

H1500 1600

1700Aux

048 0.75 650 750 800900

G1000 1150 1200

1300L

14001500

H1600

1700Aux

060 0.75 9501100

G1200 1350 1500

1650L

17001800

H2000Aux

2100 2200

066 0.75 9501100

G1200 1350 1500

1650L

1700 18002000

H2100Aux

2200

Factory settings are at recommended G-L-H-Aux speed settingsL-H settings MUST be located within boldface CFM range“Aux” is factory setting for auxiliary/emergency heat and must be equal to or above the “H” setting as well as at least the minimum required for the auxiliary heat package“G” may be located anywhere within the airflow tableCFM is controlled within 5% up to the maximum ESPMax ESP includes allowance for wet coil.

1/10/17

Page 12: R-410A Refrigerant 2-6 Tons Submittal DataAIR HANDLER R-410A Refrigerant 2-6 Tons Submittal Data English Language/IP Units SD2518AG1 04/17 SAH

Contractor: P.O.: Engineer:

Project Name: Unit Tag:

SD2518AG1 04/17 12 Page _____ of _____

AIR HANDLER2-6 Tons

SAH

©2017 The manufacturer works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Purchaser’s approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely the manufacturer’s opinion or commendation of its products.

Blower Performance Data Option C cont.

SAH Control Option C AHB Board The SAH Air Handler with the 'Advanced' control option

expands on the capability of the Aurora 'Advanced' Control

(ABC and AXB) in the compressor section, by adding the

AHB board in the air handler.

NOTE: The Energy Monitoring and Leaving Air Temperature features at the AHB board are dependent on the AXB board in the compressor section.

It is highly recommended that the installing/servicing

contractor use an Aurora Interface and Diagnosic Tool

(AID) when installing and servicing an Aurora 'Advanced'

control system.

The AHB board includes the following features:

AHB DIP Switch

DIP 1 - ID: This is the AHB ModBus ID and should always

read Off.

DIP 2 & 3 - Future UseDIP 4 & 5 - Accessory Relay2: A second, DIP configurable,

accessory relay is provided that can be cycled with the

compressor 1 or 2 , blower, or the Dehumidifier (DH)

input. This is to complement the Accessory 1 Relay on

the ABC board.

Position DIP 4 DIP 5 Description

1 ON ON Cycles with Fan or ECM (or G)

2 OFF ONCycles with CC1 first stage of compressor

or compressor spd 1-6

3 ON OFFCycles with CC2 second stage of

compressor or compressor spd 7-12

4 OFF OFF Cycles with DH input from ABC board

IntelliZone2 Zoning Compatibility (Optional IntelliZone2 Communicating Zoning)

A dedicated input to connect and communicate with the

IntelliZone2 (IZ2) zoning system is provided on P7 on the

AHB and AXB. This is a dedicated communication port using

a proprietary ModBus protocol. An AXB in the compressor

section or an AHB in the air handler is required. Consult the

Intellizone2 literature for more information.

Communicating Digital ThermostatsThe Aurora controls system also features either mono-chromatic or color touch screen graphic display thermostats for user interface. These displays not only feature easy to use graphical interface but display alerts and faults in plain English. Many of the features discussed here may not be applicable without these thermostats.

Energy Monitoring (AXB Board Required in Compressor Section)(Standard Sensor Kit on ‘Advanced’ models)The Energy Monitoring Kit includes two current transducers (blower and electric heat) so that the complete power usage of the air handler can be measured. The AID Tool provides configuration detail for the type of blower motor, power adjustment and a line voltage calibration procedure to improve the accuracy. The information can be displayed on the AID Tool or selected communicating thermostats. The TPCM32U03A(*)/04A(*) will display instantaneous energy use while the color touchscreen TPCC32U01(*) will in addition display a 13 month history in graph form. Refer to Compressor Section Start Up Energy Monitoring for configuration details.

Freeze Detection (Air Coil) – uses the FP2 input to protect against ice formation on the air coil. The FP2 input will operate exactly like FP1 except that the set point is 30 degrees and is not field adjustable.

Condensate Overflow – fault is recognized when the impedance between this line and 24 VAC common or chassis ground drops below 100K ohms for 30 seconds continuously.

Leaving Air Temperature (AXB Board Required in Compressor Section)A leaving air temperature (LAT) thermistor is located near the blower inlet and can be read via the AID tool or AWL.

Electric Heat StagingThe AHB board provides two stages of auxiliary heat operation. During normal operation, the first stage of electric heat is energized 10 seconds after the W command is received. If the demand continues the second stage is of electric heat will be energized after 5 minutes. In an Emergency heat operation the time delay between stage one and stage two will be 2 minutes.

Page 13: R-410A Refrigerant 2-6 Tons Submittal DataAIR HANDLER R-410A Refrigerant 2-6 Tons Submittal Data English Language/IP Units SD2518AG1 04/17 SAH

Contractor: P.O.: Engineer:

Project Name: Unit Tag:

SD2518AG1 04/17 13 Page _____ of _____

AIR HANDLER2-6 Tons

SAH

©2017 The manufacturer works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Purchaser’s approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely the manufacturer’s opinion or commendation of its products.

ECM Speed Info

1▶ 2 ◀ G 3 4 5 6 7 8 9 10 11 12

Option ◀▶ Enter ◙

ECM Speed Info

1 2 G▶ 3 ◀ Lo 4 5 6 7 8 9 10 11 12

Option ◀▶ Enter ◙

ECM Speed Info

1 2 G 3 Lo 4 5▶ 6 ◀ Hi 7 8 9 10 11 12

Option ◀▶ Enter ◙

ECM Speed Info

1 2 G 3 Lo 4 5 6 Hi 7 8 9▶10 ◀ Aux 11 12

Option ◀▶ Enter ◙

ECM Speed Info

Blower Only Speed 3Lo Compressor 6Hi Compressor 9Aux Heat 10

Want To Change?

YesOption ◀▶

NoEnter ◙

Cooling Airflow Setup

--- ECM Only ---The airflow will be

adjusted by the chosenamount in cooling mode.

Adjustment:-15%

Want To Change?

Yes Option ◀▶

No Enter ◙

Cooling Airflow Setup

--- ECM Only ---The airflow will be

adjusted by the chosenamount in cooling mode.

Adjustment:-15%

Change ▼▲ Enter ◙

Setting Blower Speed - Variable Speed ECM The ABC board’s Yellow Config LED will flash the current

ECM blower speed selections for “G”, low, and high

continuously with a short pause in between. The speeds

can also be confirmed with the AID Tool under the Setup/

ECM Setup screen. The Aux will not be flashed but can be

viewed in the AID Tool. The ECM blower motor speeds can

be field adjusted with or without using an AID Tool.

ECM Setup without an AID Tool

The blower speeds for “G”, Low (Y1), High (Y2), and Aux

can be adjusted directly at the Aurora ABC board which

utilizes the push button (SW1) on the ABC board. This

procedure is outlined in the ECM Configuration Mode

portion of the Aurora ‘Base’ Control System section. The

Aux cannot be set manually without an AID Tool.

ECM Setup with an AID Tool

A much easier method utilizes the AID Tool to change

the airflow using the procedure below. First navigate to

the Setup screen and then select ECM Setup. This screen

displays the current ECM settings. It allows the technician

to enter the setup screens to change the ECM settings.

Change the highlighted item using the ◀ and ▶ buttons and

then press the ◙ button to select the item.

Selecting YES will enter ECM

speed setup, while selecting NO

will return to the previous screen.

ECM Speed Setup - These screens allow the technician to

select the “G”, low, high, and auxiliary heat blower speed for

the ECM blower motor. Change the highlighted item using

the ▲ and ▼ buttons. Press the ◙ button to select the speed.

After the auxiliary heat speed setting is selected the AID

Tool will automatically transfer back to the ECM Setup screen.

Cooling Airflow Setup - These screens allow the technician

to select -15%, -10%, -5%, None or +5%. Change the

adjustment percentage using the ▲ and ▼ buttons. Press

the ◙ button to save the change.

Blower Performance Data Option C cont.

Page 14: R-410A Refrigerant 2-6 Tons Submittal DataAIR HANDLER R-410A Refrigerant 2-6 Tons Submittal Data English Language/IP Units SD2518AG1 04/17 SAH

Contractor: P.O.: Engineer:

Project Name: Unit Tag:

SD2518AG1 04/17 14 Page _____ of _____

AIR HANDLER2-6 Tons

SAH

©2017 The manufacturer works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Purchaser’s approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely the manufacturer’s opinion or commendation of its products.

SR Coil Physical CharacteristicsAir Handler Model Number (Refrigerant) 026 036 048 060

Evaporator

Coil

Air Coil Total Face Area, ft2 [m2] 3.89 [0.36] 4.86 [0.45] 5.83 [0.54] 6.81 [0.63]

Tube outside diameter - in. [mm] 3/8 [9.52]

Number of rows 3

Fins per inch 12

Suction line connection - in. [mm] sweat 5/8 [15.87] 3/4 [19.05] 7/8 [22.23]

Liquid line connection - in. [mm] sweat 3/8 [9.52] 1/2 [12.7]

Refrigerant R-410a

Nominal cooling capacity - tons [kW] 1.8 [6.44] 2.1 [7.59] 2.5 [8.79] 3 [10.55] 3.5 [12.30] 4 [14.06] 5 [17.58] 5.5 [19.33]

Condensate drain connection - (FPT) in. [mm] 3/4 [19.05]

Filter Standard - 1” [51mm] Field Supplied.16 X 20

[406 X 508]

20 X 20

[508 x 508]

22 X 20

[559 x 508]

3/7/17

Physical DataAir Handler Model Number (Refrigerant) 022 026 030 036 042 048 060 066

Evaporator Coil

Air Coil Total Face Area, ft2 [m2] 3.89 [0.36] 4.86 [0.45] 5.83 [0.54] 6.81 [0.63]

Tube outside diameter - in. [mm] 3/8 [9.52]

Number of rows 3

Fins per inch 12

Suction line connection - in. [mm] sweat 5/8 [15.87] 3/4 [19.05] 7/8 [22.23]

Liquid line connection - in. [mm] sweat 3/8 [9.52] 1/2 [12.7]

Refrigerant R-410a

Nominal cooling capacity - tons [kW] 1.8 [6.44] 2.1 [7.59] 2.5 [8.79] 3 [10.55] 3.5 [12.30] 4 [14.06] 5 [17.58] 5.5 [19.33]

Condensate drain connection - (FPT) in. [mm] 3/4 [19.05]

Blower Wheel Size (Dia x W), in. [mm]9 X 7

[229 x 178] ]10 X 8

[254 x 203]11 x 10

[279 x 254]

Blower motor type/speeds Variable Speed ECM/ 5 Speed ECM

Blower motor output - hp [W] 1/2 [373] 1 [746]

Filter Standard - 1” [51mm] Field Supplied.16 X 20

[406 X 508]20 X 20

[508 x 508]22 X 20

[559 x 508]

Electrical characteristics (60hz) 208/230 - 1ph

Shipping weight - lbs. [kg] 147 [66.7] 168 [76.2] 198 [89.6] 206 [93.4]

Operating weight - lbs. [kg] 139 [63.0] 150 [68.0] 180 [81.6] 188 [85.3]

1/31/2017

Page 15: R-410A Refrigerant 2-6 Tons Submittal DataAIR HANDLER R-410A Refrigerant 2-6 Tons Submittal Data English Language/IP Units SD2518AG1 04/17 SAH

Contractor: P.O.: Engineer:

Project Name: Unit Tag:

SD2518AG1 04/17 15 Page _____ of _____

AIR HANDLER2-6 Tons

SAH

©2017 The manufacturer works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Purchaser’s approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely the manufacturer’s opinion or commendation of its products.

Electrical Data

Model

Electric Heat CapacitySupply Circuit

Rated Voltage

Voltage Min/Max

Fan Motor FLA

Heater Ampacity

Total Unit FLA

Minimum Circuit

Ampacity

Maximum Fuse/HACRKW BTUH

240v 240v 208v 240v 208v 240v 208v 240v 208v 240v

0220 0 -

208-230/60/1 197/253

4.0 - - 4.0 4.0 5.0 5.0 10 10

4.8 16,382 single 4.0 17.3 20.0 21.3 24.0 26.6 30.0 30 30

0260 0 - 4.0 - - 4.0 4.0 5.0 5.0 10 10

4.8 16,382 single 4.0 17.3 20.0 21.3 24.0 26.6 30.0 30 30

0300 0 - 4.0 - - 4.0 4.0 5.0 5.0 10 10

4.8 16,382 single 4.0 17.3 20.0 21.3 24.0 26.6 30.0 30 30

036

0 0 - 4.0 - - 4.0 4.0 5.0 5.0 10 10

4.8 16,382 single 4.0 17.3 20.0 21.3 24.0 26.6 30.0 30 30

9.6 32,765 single 4.0 34.7 40.0 38.7 44.0 48.4 55.0 50 60

042

0 0 - 7.0 - - 7.0 7.0 8.8 8.8 15 15

9.6 32,765 single 7.0 34.7 40.0 41.7 47.0 52.1 58.8 60 60

14.4 49,147 single 7.0 52.0 60.0 59.0 67.0 73.8 83.8 80 90

14.4 49,147L1/L2 7.0 34.7 40.0 41.7 47.0 52.1 58.8 60 60

L3/L4 - 17.3 20.0 17.3 20.0 21.6 25.0 25 25

048

0 0 - 7.0 - - 7.0 7.0 8.8 8.8 15 15

9.6 32,765 single 7.0 34.7 40.0 41.7 47.0 52.1 58.8 60 60

14.4 49,147 single 7.0 52.0 60.0 59.0 67.0 73.8 83.8 80 90

14.4 49,147L1/L2 7.0 34.7 40.0 41.7 47.0 52.1 58.8 60 60

L3/L4 - 17.3 20.0 17.3 20.0 21.6 25.0 25 25

060

0 0 - 7.0 - - 7.0 7.0 8.8 8.8 15 15

9.6 32,765 single 7.0 34.7 40.0 41.7 47.0 52.1 58.8 60 60

14.4 49,147 single 7.0 52.0 60.0 59.0 67.0 73.8 83.8 80 90

14.4 49,147L1/L2 7.0 34.7 40.0 41.7 47.0 52.1 58.8 60 60

L3/L4 - 17.3 20.0 17.3 20.0 21.6 25.0 25 25

19.2 65,530 single 7.0 69.3 80.0 76.3 87.0 95.4 108.8 100 110

19.2 65,530L1/L2 7.0 34.7 40.0 41.7 47.0 52.1 58.8 60 60

L3/L4 - 34.7 40.0 34.7 40.0 43.4 50.0 50 50

066

0 0 - 7.0 - - 7.0 7.0 8.8 8.8 15 15

9.6 32,765 single 7.0 34.7 40.0 41.7 47.0 52.1 58.8 60 60

14.4 49,147 single 7.0 52.0 60.0 59.0 67.0 73.8 83.8 80 90

14.4 49,147L1/L2 7.0 34.7 40.0 41.7 47.0 52.1 58.8 60 60

L3/L4 - 17.3 20.0 17.3 20.0 21.6 25.0 25 25

19.2 65,530 single 7.0 69.3 80.0 76.3 87.0 95.4 108.8 100 110

19.2 65,530L1/L2 7.0 34.7 40.0 41.7 47.0 52.1 58.8 60 60

L3/L4 - 34.7 40.0 34.7 40.0 43.4 50.0 50 50

Rev.Rated Voltage of 208/230/60/1HACR circuit breaker in USA only

1/10/17

Page 16: R-410A Refrigerant 2-6 Tons Submittal DataAIR HANDLER R-410A Refrigerant 2-6 Tons Submittal Data English Language/IP Units SD2518AG1 04/17 SAH

Contractor: P.O.: Engineer:

Project Name: Unit Tag:

SD2518AG1 04/17 16 Page _____ of _____

AIR HANDLER2-6 Tons

SAH

©2017 The manufacturer works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Purchaser’s approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely the manufacturer’s opinion or commendation of its products.

Electrical Data cont.

Field low voltage point to point wiring:Communicating Thermostat Control Option C

From

Communicating

Thermostat

To Air

Handler

PB3

To Compressor

Section

ABC Board P7

C C C

R R R

- - -

+ + +

Air Handler transformer must be 100VA. 1/10/2017

Field low voltage point to point wiring:Non-Communicating Thermostat Control Option C

From

Thermostat

To ABC in

Compressor

Section

From ABC

P7 in

Compressor

Section

To PB2

in Air

Handler

C C C C

R R R R

G G - -

O O + +

Y1 Y1

Y2 Y2

W2 W

L L

Air Handler transformer must be 100VA. 3/7/2017

Field low voltage point to point wiring:Standard Non-Communicating Control Option A

From

Thermostat

To Air

Handler

To Compressor

Section

C C C

R R R

G G

O O O

Y1 Y1 Y1

Y2 Y2 Y2

W2 W

L L L

Air Handler transformer must be 75VA.

24V Thermostat must be wired to the loose stripped wires connected to the terminal block

in the air handler. DAMAGE TO THERMOSTAT MAY OCCUR IF WIRED INCORRECTLY.

SEE AIR HANDLER SCHEMATIC.

3/9/2017

From Communicating

Thermostat

To ABC P7 in Compressor

Section

C CR R- -+ +

Air Handler transformer must be 75VA.

Field low voltage point to point wiring:Communicating Thermostat Control Option A

From ABC Outputs

To Air Handler

C CR RG G

CC Y1CC2 Y2EH1 W

OL

4/4/2017

Page 17: R-410A Refrigerant 2-6 Tons Submittal DataAIR HANDLER R-410A Refrigerant 2-6 Tons Submittal Data English Language/IP Units SD2518AG1 04/17 SAH

Contractor: P.O.: Engineer:

Project Name: Unit Tag:

SD2518AG1 04/17 17 Page _____ of _____

AIR HANDLER2-6 Tons

SAH

©2017 The manufacturer works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Purchaser’s approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely the manufacturer’s opinion or commendation of its products.

Wiring SchematicsSAH Air Handler Control Option A Schematic

Air Handler No Electric Heat

97P901-01

Tan

Transformer

Blk/WhYellow

24V

L2L1

PB

Black

Blue

Red NOTE 1 Orange

Brown

1

2

3

L N G

5 SpeedECM

BlowerMotor

C

4

5

O

C

Y1

G

S

W1

L

X2

X1

R

Y2

TB

12V

Black

Blue

Red

Tan

Grey

12V

12V

12V

Thermostat

R

CY1

O

L1

Y2

G

W

Blue

Grey

Red

White

Black

GL2L1

208-230/60/1

Light emitting diode - Green

208-230V Relay coil

Electric Heat Contactor

Polarized connector

Factory Low voltage wiringFactory Line voltage wiringField low voltage wiringField line voltage wiringOptional blockDC Voltage PCB tracesInternal junctionQuick connect terminal

Thermal Limit Switch

Field wire lug

Ground

HE -

PB -

Heater element

Power block

Legend

N.O., N.C.

G

L1

ER1 to ER4 - Aux heat stage relays

1 2 3P

EHC

EHC

Breaker

TS

Notes:1 – To operate in 208V mode replace the blue transformer wire connected to PB-L2 with red transformer wire.

2 – Low voltage wiring CLASS 2.

NOTE 3

3 – 24V Thermostat must be wired as shown to the loose wires using wire nuts. DO NOT CONNECT THERMOSTAT TO TB.

WIRE 24V THERMOSTAT AS SHOWN CONNECTED TO THE STRIP WIRES ALREADY CONNECTED TO TB. DO NOT CONNECT DIRECTLY TO THE TB TERMINALS. DAMAGE TO THE STAT MAY OCCUR. TB CAN BE USED TO CONNECT TO THE ABC BOARD IN THE COMPRESSOR SECTION

Grn/Yel

Page 18: R-410A Refrigerant 2-6 Tons Submittal DataAIR HANDLER R-410A Refrigerant 2-6 Tons Submittal Data English Language/IP Units SD2518AG1 04/17 SAH

Contractor: P.O.: Engineer:

Project Name: Unit Tag:

SD2518AG1 04/17 18 Page _____ of _____

AIR HANDLER2-6 Tons

SAH

©2017 The manufacturer works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Purchaser’s approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely the manufacturer’s opinion or commendation of its products.

Wiring Schematics cont.

SAH Air Handler Control Option A Schematic

Air Handler 5kW Electric Heat

97P901-02

Light emitting diode - Green

208-230V Relay coil

Electric Heat Contactor

Polarized connector

Factory Low voltage wiringFactory Line voltage wiringField low voltage wiringField line voltage wiringOptional blockDC Voltage PCB tracesInternal junctionQuick connect terminal

Thermal Limit Switch

Field wire lug

Ground

HE -

PB -

Heater element

Power block

Legend

N.O., N.C.

G

L1

ER1 to ER4 - Aux heat stage relays

1 2 3P

EHC

EHC

Breaker

TS

HE1 TS1FL1

GL2L1

208-230/60/1

2

3

1RELAY

Yellow

White

Blue

Blue

Yellow

Blue

Tan

Transformer

Blk/WhYellow

24V

L2L1PBBlack

Blue

Red NOTE 1 Orange

Brown

1

2

3

L N G

5 SpeedECM

BlowerMotor

C

4

5

O

C

Y1

G

S

W1

L

X2

X1

R

Y2

TB

12V

Black

Blue

Red

Tan

Grey

12V

12V

12V

Thermostat

R

CY1

O

L1

Y2

G

W

Blue

Grey

Red

White

Black

Blue

White

Notes:1 – To operate in 208V mode replace the blue transformer wire connected to PB-L2 with red transformer wire.

2 – Low voltage wiring CLASS 2.

R1

WIRE 24V THERMOSTAT AS SHOWN CONNECTED TO THE STRIP WIRES ALREADY CONNECTED TO TB. DO NOT CONNECT DIRECTLY TO THE TB TERMINALS. DAMAGE TO THE STAT MAY OCCUR. TB CAN BE USED TO CONNECT TO THE ABC BOARD IN THE COMPRESSOR SECTION

NOTE 3

3 – 24V Thermostat must be wired as shown to the loose wires using wire nuts. DO NOT CONNECT THERMOSTAT TO TB.

Grn/Yel

Page 19: R-410A Refrigerant 2-6 Tons Submittal DataAIR HANDLER R-410A Refrigerant 2-6 Tons Submittal Data English Language/IP Units SD2518AG1 04/17 SAH

Contractor: P.O.: Engineer:

Project Name: Unit Tag:

SD2518AG1 04/17 19 Page _____ of _____

AIR HANDLER2-6 Tons

SAH

©2017 The manufacturer works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Purchaser’s approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely the manufacturer’s opinion or commendation of its products.

Wiring Schematics cont.SAH Air Handler Control Option A Schematic

Air Handler 10kW Electric Heat

97P901-03

Light emitting diode - Green

208-230V Relay coil

Electric Heat Contactor

Polarized connector

Factory Low voltage wiringFactory Line voltage wiringField low voltage wiringField line voltage wiringOptional blockDC Voltage PCB tracesInternal junctionQuick connect terminal

Thermal Limit Switch

Field wire lug

Ground

HE -

PB -

Heater element

Power block

Legend

N.O., N.C.

G

L1

ER1 to ER4 - Aux heat stage relays

1 2 3P

EHC

EHC

Breaker

TS

HE1FL1

RELAY

HE2 FL2

GL2L1

208-230/60/12

3

1RELAY

Yellow

WhiteBrown

Blue

Blue

Blue

Yellow

Blue

Yellow

Blue

Blue

Yellow

Orange

Tan

Transformer

Blk/WhYellow

24V

L2L1PBBlack

Blue

Red NOTE 1 Orange

Brown

1

2

3

L N G

5 SpeedECM

BlowerMotor

C

4

5

O

C

Y1

G

S

W1

L

X2

X1

R

Y2

TB

12V

Black

Blue

Red

Tan

Grey

12V

12V

12V

Thermostat

R

CY1

O

L1

Y2

G

W

Blue

Grey

Red

White

Black

Blue

White

Notes:1 – To operate in 208V mode replace the blue transformer wire connected to PB-L2 with red transformer wire.

2 – Low voltage wiring CLASS 2.

R1 R2

TS1

Yellow

Yellow

WIRE 24V THERMOSTAT AS SHOWN CONNECTED TO THE STRIP WIRES ALREADY CONNECTED TO TB. DO NOT CONNECT DIRECTLY TO THE TB TERMINALS. DAMAGE TO THE STAT MAY OCCUR. TB CAN BE USED TO CONNECT TO THE ABC BOARD IN THE COMPRESSOR SECTION

NOTE 3

3 – 24V Thermostat must be wired as shown to the loose wires using wire nuts. DO NOT CONNECT THERMOSTAT TO TB.

Grn/Yel

Page 20: R-410A Refrigerant 2-6 Tons Submittal DataAIR HANDLER R-410A Refrigerant 2-6 Tons Submittal Data English Language/IP Units SD2518AG1 04/17 SAH

Contractor: P.O.: Engineer:

Project Name: Unit Tag:

SD2518AG1 04/17 20 Page _____ of _____

AIR HANDLER2-6 Tons

SAH

©2017 The manufacturer works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Purchaser’s approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely the manufacturer’s opinion or commendation of its products.

Wiring Schematics cont.SAH Air Handler Control Option A Schematic

Air Handler 15kW Electric Heat

97P901-04

HE3 FL3

HE1 TS1FL1

5

4

3

1

H

HSEQ1

5

4

3

1

H

HSEQ2

RELAY

HE2 FL2

208-

230/6

0/1

GL2

L1

BRK1

L2L1

BRK2

G

Circu

it 120

8-23

0/60/1

Circu

it 2

Blue

Yellow

Yellow

Blue

Blue

2

3

1 Orange

Blue

White

Brown

YellowBlack

Black

Red

Brown

Blue

Yellow

Blue

Blue Red

Tan

Transformer

Blk/WhYellow

24V

L2L1PBBlack

Blue

Red NOTE 1 Orange

Brown

1

2

3

L N G

5 SpeedECM

BlowerMotor

C

4

5

O

C

Y1

G

S

W1

L

X2

X1

R

Y2

TB

12V

Black

Blue

Red

Tan

Grey

12V

12V

12V

Thermostat

R

CY1

O

L1

Y2

G

W

Blue

Grey

Red

White

Black

White

Blue

Black

Red

NOTE 2

R1

TS2Yellow

Black

WIRE 24V THERMOSTAT AS SHOWN CONNECTED TO THE STRIP WIRES ALREADY CONNECTED TO TB. DO NOT CONNECT DIRECTLY TO THE TB TERMINALS. DAMAGE TO THE STAT MAY OCCUR. TB CAN BE USED TO CONNECT TO THE ABC BOARD IN THE COMPRESSOR SECTION

NOTE 4

Grn/Yel

Notes:1 – To operate in 208V mode replace the blue transformer wire connected to PB-L2 with red transformer wire.

2 – Use manufacturer’s part number 19P592-01 (jumper bar assembly) when single source power is required.

3 – Low voltage wiring CLASS 2.4 – 24V Thermostat must be wired as shown to the loose wires using wire nuts. DO NOT CONNECT THERMOSTAT TO TB.

Light emitting diode - Green

208-230V Relay coil

Electric Heat Contactor

Polarized connector

Factory Low voltage wiringFactory Line voltage wiringField low voltage wiringField line voltage wiringOptional blockDC Voltage PCB tracesInternal junctionQuick connect terminal

Thermal Limit Switch

Field wire lug

Ground

HE -

PB -

Heater element

Power block

Legend

N.O., N.C.

G

L1

ER1 to ER4 - Aux heat stage relays

1 2 3P

EHC

EHC

Breaker

TS

If two separate circuits are used to supply power to theauxiliary heat kit, the Installer will need to verify that each leg ofthe auxiliary heat circuit breakers are wired from the powersupply correctly in order for the electric heat kit to operateproperly. This can be done by measuring the supply sidevoltage of the auxiliary heat circuit breakers. Put a voltmeter onthe L2 side of Circuit Breaker One and on the L2 side of CircuitBreaker Two. The voltmeter should read approximately 0 volts.If the meter reads high voltage, the auxiliary heat breakersneed to be rewired so that breakers in the auxiliary heat kitmatch the wiring of the Disconnect Panel breakers. Meaning,L1 and L2 from one breaker in the disconnect panel mustconnect to L1 and L2 at one of the auxiliary heat circuitbreakers and L1 and L2 from the other breaker in thedisconnect panel must connect to L1 and L2 of the otherauxiliary heat circuit breaker, making sure that the L1 and L2from each disconnect breaker matches the L1 and L2 at eachof the auxiliary heat breakers.

Dual Power Supply Connections

Page 21: R-410A Refrigerant 2-6 Tons Submittal DataAIR HANDLER R-410A Refrigerant 2-6 Tons Submittal Data English Language/IP Units SD2518AG1 04/17 SAH

Contractor: P.O.: Engineer:

Project Name: Unit Tag:

SD2518AG1 04/17 21 Page _____ of _____

AIR HANDLER2-6 Tons

SAH

©2017 The manufacturer works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Purchaser’s approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely the manufacturer’s opinion or commendation of its products.

Wiring Schematics cont.SAH Air Handler Control Option A Schematic

Air Handler 20kW Electric Heat

97P901-05

Factory Low voltage wiring

Legend

HE4FL4HE3 FL3

HE1FL1

5

4

3

1

H

HSEQ1

5

4

3

1

H

HSEQ2

RELAY RELAY

HE2 FL2

208-

230/6

0/1

GL2

L1

BRK1

L2L1

BRK2

G

Circu

it 120

8-23

0/60/1

Circu

it 2

Blue Blue

BlueBlue

Yellow

Black

Yellow

Black

Blue

Blue

2

3

1 Orange

Blue

White

White

Brown

Brown

Blue

BlackBlack

RedRed

RedBlack

Black

Red

Tan

Transformer

Blk/WhYellow

24V

L2L1PBBlack

Blue

Red NOTE 1 Orange

Brown

1

2

3

L N G

5 SpeedECM

BlowerMotor

C

4

5

O

C

Y1

G

S

W1

L

X2

X1

R

Y2

TB

12V

Black

Blue

Red

Tan

Grey

12V

12V

12V

Thermostat

R

CY1

O

L1

Y2

G

W

Blue

Grey

Red

White

Black

White

Blue

Black

Red

NOTE 2

R1R2

TS1Yellow

Black

TS2Yellow

Black

WIRE 24V THERMOSTAT AS SHOWN CONNECTED TO THE STRIP WIRES ALREADY CONNECTED TO TB. DO NOT CONNECT DIRECTLY TO THE TB TERMINALS. DAMAGE TO THE STAT MAY OCCUR. TB CAN BE USED TO CONNECT TO THE ABC BOARD IN THE COMPRESSOR SECTION

NOTE 4

Grn/Yel

Notes:1 – To operate in 208V mode replace the blue transformer wire connected to PB-L2 with red transformer wire.

2 – Use manufacturer’s part number 19P592-01 (jumper bar assembly) when single source power is required.

3 – Low voltage wiring CLASS 2.4 – 24V Thermostat must be wired as shown to the loose wires using wire nuts. DO NOT CONNECT THERMOSTAT TO TB.

Light emitting diode - Green

208-230V Relay coil

Electric Heat Contactor

Polarized connector

Factory Low voltage wiringFactory Line voltage wiringField low voltage wiringField line voltage wiringOptional blockDC Voltage PCB tracesInternal junctionQuick connect terminal

Thermal Limit Switch

Field wire lug

Ground

HE -

PB -

Heater element

Power block

Legend

N.O., N.C.

G

L1

ER1 to ER4 - Aux heat stage relays

1 2 3P

EHC

EHC

Breaker

TS

If two separate circuits are used to supply power to theauxiliary heat kit, the Installer will need to verify that each leg ofthe auxiliary heat circuit breakers are wired from the powersupply correctly in order for the electric heat kit to operateproperly. This can be done by measuring the supply sidevoltage of the auxiliary heat circuit breakers. Put a voltmeter onthe L2 side of Circuit Breaker One and on the L2 side of CircuitBreaker Two. The voltmeter should read approximately 0 volts.If the meter reads high voltage, the auxiliary heat breakersneed to be rewired so that breakers in the auxiliary heat kitmatch the wiring of the Disconnect Panel breakers. Meaning,L1 and L2 from one breaker in the disconnect panel mustconnect to L1 and L2 at one of the auxiliary heat circuitbreakers and L1 and L2 from the other breaker in thedisconnect panel must connect to L1 and L2 of the otherauxiliary heat circuit breaker, making sure that the L1 and L2from each disconnect breaker matches the L1 and L2 at eachof the auxiliary heat breakers.

Dual Power Supply Connections

Page 22: R-410A Refrigerant 2-6 Tons Submittal DataAIR HANDLER R-410A Refrigerant 2-6 Tons Submittal Data English Language/IP Units SD2518AG1 04/17 SAH

Contractor: P.O.: Engineer:

Project Name: Unit Tag:

SD2518AG1 04/17 22 Page _____ of _____

AIR HANDLER2-6 Tons

SAH

©2017 The manufacturer works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Purchaser’s approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely the manufacturer’s opinion or commendation of its products.

Wiring Schematics cont.SAH Air Handler Control Option C Schematic 97P903-01

SUC

PHW HW

SCT

P8

MOTO

R P6

RS48

5 P7

ZONE P9

ABC

STEP

PER

ANA

ACC2

DHDI

V

C R L1 L1 L2 L2P1

2P1

0P5

P11

CR(-)(+) CR(-)(+) CR(-)(+)

P4P2

K1K2

K3

C

1C

2C

3CO

NDVS

DAT

AVS

PUM

PP3

V+CRTXRX +5

P14

10P1

CT2

43

CT2

43

CT1

21

CT1

21

StatusG

DISC

H

P16

P17

P18

P15

AHB™

SW1

Modbus Add. IDFuture Use

12345

ONOFF

Future UseAcc 2 – Dip 4Acc 2 – Dip 5

CCO

+5C

S+5

CPW

MC

C4

XC

CS

+5C

+58

CC

C7

69

Grn

23

45

1

ECM Blower Motor

234 1

Green/YellowBlue

Transformer

24V

YellowBlack/White

Black Blue

Red

Brown

Brown

Black

Black

Brown

Brown

T Gray

Gray

Communicating Thermostat

Green

White

BlackBlack

RedWhite

Green

PB2

PB3

Blower Motor Current Transducer

Leaving Air Temperature LAT

Condensate Overflow

Orange

Brown

RS485 NET

C R - + ABC P7

ABC Control Board in Split Unit

Unit Power 208-230/60/1

GL1 L2

T Black

BlackFP2 Sensor

PB1

L1

L2

Red

Note:1

White

Black

Black

Orange

Not UsedWhite

Orange

Accessory 2 Output

Analog Output 0-10VDC

Communicating Thermostat will connect to the COMM STAT (C R + -) power block PB3 in the air handler. A 4-conductor, 20AWG wire will need to connect from the TO ABC (C R + -) power block (PB2) in the Air Handler to the ABC P7(See detail ‘A’ on schematic) connection on the ABC board in the compressor section.

Detail ‘A’

TO COMM STAT C R + -TO ABC

C R + -

NOTE:3

CT

Not Used

Blower Pe

Factory settingsL-H settings MU"Aux" is factory "G" may be locaCFM is controlleMax ESP includ

066 0

MODEL MAX

022 0

026 0

030

060 0

0

036 0

042 0

048 0

Grn/Yel

Light emitting diode - Green

Fused Limit

Polarized connector

Factory Low voltage wiringFactory Line voltage wiringField low voltage wiringField line voltage wiringOptional blockDC Voltage PCB tracesInternal junctionQuick connect terminal

Thermal Limit Switch

Field wire lug

Ground

HE -

PB -

SW1 -

Heater element

Power block

DIP package 4 position

Legend

N.O., N.C.

G

L1

1 2 3P

Breaker

TS

FL

Notes:1 – To operate in 208V mode replace the blue transformer

wire connected to PB1-L2 with red transformer wire.

2 – Low voltage wiring CLASS 2.3 – DIP switch 1 on SW1 must be set in the OFF position.

Ther

mosta

t

RC

Y1

O

DH

Y2

G

W

LO

Non-Communicating Thermostat

LORCOGY1Y2

DHW

P1 ABC Board

Non-Communicating Thermostat will connect to the P1 connection on the ABC board in the compressor section. A 4-conductor, 20AWG wire will need to connect from the ABC P7 (See detail ‘A’ on schematic) connection to the TO ABC (C R + -) power block (PB2) in the Air Handler.

Air Handler No Electric Heat

Page 23: R-410A Refrigerant 2-6 Tons Submittal DataAIR HANDLER R-410A Refrigerant 2-6 Tons Submittal Data English Language/IP Units SD2518AG1 04/17 SAH

Contractor: P.O.: Engineer:

Project Name: Unit Tag:

SD2518AG1 04/17 23 Page _____ of _____

AIR HANDLER2-6 Tons

SAH

©2017 The manufacturer works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Purchaser’s approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely the manufacturer’s opinion or commendation of its products.

Wiring Schematics cont.SAH Air Handler Control Option C Schematic 97P903-02

Air Handler 5kW Electric Heat

SUC

PHW HW

SCT

P8

MOTO

R P6

RS48

5 P7

ZONE P9

ABC

STEP

PER

ANA

ACC2

DHDI

V

C R L1 L1 L2 L2P1

2P1

0P5

P11

CR(-)(+) CR(-)(+) CR(-)(+)

P4P2

K1K2

K3

C

1C

2C

3CO

NDVS

DAT

AVS

PUM

PP3

V+CRTXRX +5

P14

10P1

CT2

43

CT2

43

CT1

21

CT1

21

StatusG

DISC

H

P16

P17

P18

P15

AHB™

SW1

Modbus Add. IDFuture Use

12345

ONOFF

Future UseAcc 2 – Dip 4Acc 2 – Dip 5

CCO

+5C

S+5

CPW

MC

C4

XC

CS

+5C

+58

CC

C7

69

Grn

23

45

1

ECM Blower Motor

234 1

Green/YellowBlue

Transformer

24V

YellowBlack/White

BlackBlue

Red

White

Blue

Brown

Brown

Black

Black

Brown

Brown

T Gray

Gray

White

Green

BlackBlack

RedGreen

White

PB2

Auxiliary Heat Current Transducer

Blower Motor Current Transducer

Leaving Air Temperature LAT

Condensate Overflow

Orange

Brown

HE1 TS1FL1

GL2L1

208-230/60/1

2

3

1RELAY

Yellow

White

Blue

Blue

Yellow

Blue

FP2 Sensor T Black

Black

PB1L1 L2

Red

Blue

BrownWires Not Used

Note:1

PB4

R1

PB3 TO COMM STAT C R + -TO ABC

C R + -

NOTE:3

RS485 NET

C R - + ABC P7

ABC Control Board in Split Unit

Detail ‘A’

Communicating Thermostat

Communicating Thermostat will connect to the COMM STAT (C R + -) power block PB3 in the air handler. A 4-conductor, 20AWG wire will need to connect from the TO ABC (C R + -) power block (PB2) in the Air Handler to the ABC P7(See detail ‘A’ on schematic) connection on the ABC board in the compressor section.

CT

Auxiliary Heat Current Transducer

Blo

FactoL-H s"Aux"G" mCFMMax

06

MO

02

02

03

06

03

04

04

Grn/Yel

Light emitting diode - Green

Fused Limit

Polarized connector

Factory Low voltage wiringFactory Line voltage wiringField low voltage wiringField line voltage wiringOptional blockDC Voltage PCB tracesInternal junctionQuick connect terminal

Thermal Limit Switch

Field wire lug

Ground

HE -

PB -

SW1 -

Heater element

Power block

DIP package 4 position

Legend

N.O., N.C.

G

L1

1 2 3P

Breaker

TS

FLNotes:

1 – To operate in 208V mode replace the blue transformer wire connected to PB1-L2 with red transformer wire.

2 – Low voltage wiring CLASS 2.3 – DIP switch 1 on SW1 must be set in the OFF position.

Ther

mosta

t

RC

Y1

O

DH

Y2

G

W

LO

Non-Communicating Thermostat

LORCOGY1Y2

DHW

P1 ABC Board

Non-Communicating Thermostat will connect to the P1 connection on the ABC board in the compressor section. A 4-conductor, 20AWG wire will need to connect from the ABC P7 (See detail ‘A’ on schematic) connection to the TO ABC (C R + -) power block (PB2) in the Air Handler.

Page 24: R-410A Refrigerant 2-6 Tons Submittal DataAIR HANDLER R-410A Refrigerant 2-6 Tons Submittal Data English Language/IP Units SD2518AG1 04/17 SAH

Contractor: P.O.: Engineer:

Project Name: Unit Tag:

SD2518AG1 04/17 24 Page _____ of _____

AIR HANDLER2-6 Tons

SAH

©2017 The manufacturer works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Purchaser’s approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely the manufacturer’s opinion or commendation of its products.

Wiring Schematics cont.SAH Air Handler Control Option C Schematic 97P903-03

Communicating Thermostat

Communicating Thermostat will connect to the COMM STAT (C R + -) power block PB3 in the air handler. A 4-conductor, 20AWG wire will need to connect from the TO ABC (C R + -) power block (PB2) in the Air Handler to the ABC P7(See detail ‘A’ on schematic) connection on the ABC board in the compressor section.

SUC

PHW HW

SCT

P8

MOTO

R P6

RS48

5 P7

ZONE P9

ABC

STEP

PER

ANA

ACC2

DHDI

V

C R L1 L1 L2 L2P1

2P1

0P5

P11

CR(-)(+) CR(-)(+) CR(-)(+)

P4P2

K1K2

K3

C

1C

2C

3CO

NDVS

DAT

AVS

PUM

PP3

V+CRTXRX +5

P14

10P1

CT2

43

CT2

43

CT1

21

CT1

21

StatusG

DISC

H

P16

P17

P18

P15

AHB™

SW1

Modbus Add. IDFuture Use

12345

ONOFF

Future UseAcc 2 – Dip 4Acc 2 – Dip 5

CCO

+5C

S+5

CPW

MC

C4

XC

CS

+5C

+58

CC

C7

69

Grn

23

45

1

ECM Blower Motor

234 1

Green/YellowBlue

Transformer

24V

YellowBlack/WhiteBlack Blue

Red

White

BrownBlue

Blue

Brown

Brown

Black

Black

Brown

Brown

T Gray

Gray

White

Green

BlackBlack

RedGreen

White

PB2

PB3

Auxiliary Heat Current Transducer

Blower Motor Current Transducer

Leaving Air Temperature LAT

Condensate Overflow

Orange

Brown

HE1FL1

RELAY

HE2 FL2

GL2L1

208-230/60/1

2

3

1RELAY

Yellow

WhiteBrown

Blue

Blue

Blue

Yellow

Blue

Yellow

Blue

Blue

Yellow

T Black

BlackFP2 Sensor

PB1L1 L2

Red

Note:1

PB4

TS1

Yellow

Yellow

R1 R2

NOTE:3

TO COMM STAT C R + -

TO ABC C R + -

RS485 NET

C R - + ABC P7

ABC Control Board in Split Unit

Detail ‘A’

CT

Auxiliary Heat Current Transducer

Blower P

Factory settinL-H settings M"Aux" is facto"G" may be loCFM is controMax ESP inc

066

MODEL M

022

026

030

060

036

042

048

Grn/Yel

Ther

mosta

t

RC

Y1

O

DH

Y2

G

W

LO

Non-Communicating Thermostat

LORCOGY1Y2

DHW

P1 ABC Board

Non-Communicating Thermostat will connect to the P1 connection on the ABC board in the compressor section. A 4-conductor, 20AWG wire will need to connect from the ABC P7 (See detail ‘A’ on schematic) connection to the TO ABC (C R + -) power block (PB2) in the Air Handler.

Notes:1 – To operate in 208V mode replace the blue transformer

wire connected to PB1-L2 with red transformer wire.

2 – Low voltage wiring CLASS 2.

3 – DIP switch 1 on SW1 must be set in the OFF position.

Light emitting diode - Green

Fused Limit

Polarized connector

Factory Low voltage wiringFactory Line voltage wiringField low voltage wiringField line voltage wiringOptional blockDC Voltage PCB tracesInternal junctionQuick connect terminal

Thermal Limit Switch

Field wire lug

Ground

HE -

PB -

SW1 -

Heater element

Power block

DIP package 4 position

Legend

N.O., N.C.

G

L1

1 2 3P

Breaker

TS

FL

Air Handler 10kW Electric Heat

Page 25: R-410A Refrigerant 2-6 Tons Submittal DataAIR HANDLER R-410A Refrigerant 2-6 Tons Submittal Data English Language/IP Units SD2518AG1 04/17 SAH

Contractor: P.O.: Engineer:

Project Name: Unit Tag:

SD2518AG1 04/17 25 Page _____ of _____

AIR HANDLER2-6 Tons

SAH

©2017 The manufacturer works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Purchaser’s approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely the manufacturer’s opinion or commendation of its products.

Wiring Schematics cont.

SAH Air Handler Control Option C Schematic 97P903-04

Air H

Yellow

Blue

Yellow

T Black

BlackFP2 Sensor

Red

Note:1

L2

Note:2

L1

PB4

TS2

Black

Yellow

SUC

PHW HW

SCT

P8

MOTO

R P6

RS48

5 P7

ZONE P9

ABC

STEP

PER

ANA

ACC2

DHDI

V

C R L1 L1 L2 L2P1

2P1

0P5

P11

CR(-)(+) CR(-)(+) CR(-)(+)

P4P2

K1K2

K3

C

1C

2C

3CO

NDVS

DAT

AVS

PUM

PP3

V+CRTXRX +5

P14

10P1

CT2

43

CT2

43

CT1

21

CT1

21

StatusG

DISC

H

P16

P17

P18

P15

AHB™

SW1

Modbus Add. IDFuture Use

12345

ONOFF

Future UseAcc 2 – Dip 4Acc 2 – Dip 5

CCO

+5C

S+5

CPW

MC

C4

XC

CS

+5C

+58

CC

C7

69

Grn

23

45

1

ECM Blower Motor

234 1

Green/YellowBlue

PB1

Transformer

24V

Red

Black

YellowBlack/White

Black Blue

Red

White

BrownBlue

Blue

Brown

Brown

Black

Black

Brown

Brown

T Gray

Gray

White

Green

BlackBlack

RedGreen

White

PB2

PB3

Auxiliary Heat Current Transducer

Blower Motor Current Transducer

Leaving Air Temperature LAT

Condensate Overflow

Orange

Brown

HE3 FL3

HE1 TS1FL1

5

4

3

1

H

HSEQ1

5

4

3

1

H

HSEQ2

RELAY

HE2 FL2

208-

230/6

0/1

GL2

L1

BRK1

L2L1

BRK2

G

Circu

it 120

8-23

0/60/1

Circu

it 2

Blue

Blue

Yellow

Blue

Blue

2

3

1

Blue

White

BrownBrown

YellowBlack

BlueRed

Black

Red

R1

NOTE:4

TO COMM STAT C R + -TO ABC

C R + -

RS485 NET

C R - + ABC P7

ABC Control Board in Split Unit

Detail ‘A’

Communicating Thermostat

Communicating Thermostat will connect to the COMM STAT (C R + -) power block PB3 in the air handler. A 4-conductor, 20AWG wire will need to connect from the TO ABC (C R + -) power block (PB2) in the Air Handler to the ABC P7(See detail ‘A’ on schematic) connection on the ABC board in the compressor section.

CT

Auxiliary Heat Current Transducer

Blowe

Factory sL-H settin"Aux" is f"G" may bCFM is coMax ESP

066

MODEL

022

026

030

060

036

042

048

Grn/Yel

Light emitting diode - Green

Fused Limit

Polarized connector

Factory Low voltage wiringFactory Line voltage wiringField low voltage wiringField line voltage wiringOptional blockDC Voltage PCB tracesInternal junctionQuick connect terminal

Thermal Limit Switch

Field wire lug

Ground

HE -

PB -

SW1 -

Heater element

Power block

DIP package 4 position

Legend

N.O., N.C.

G

L1

1 2 3P

Breaker

TS

FL

Notes:1 – To operate in 208V mode replace the blue transformer

wire connected to PB1-L2 with red transformer wire.

2 – Use manufacturer’s part number 19P592-01 (jumper bar assembly) when single source power is required.3 – Low voltage wiring CLASS 2.4 – DIP switch 1 on SW1 must be set in the OFF position.

Ther

mosta

t

RC

Y1

O

DH

Y2

G

W

LO

Non-Communicating Thermostat

LORCOGY1Y2

DHW

P1 ABC Board

Non-Communicating Thermostat will connect to the P1 connection on the ABC board in the compressor section. A 4-conductor, 20AWG wire will need to connect from the ABC P7 (See detail ‘A’ on schematic) connection to the TO ABC (C R + -) power block (PB2) in the Air Handler.

Air Handler 15kW Electric Heat

If two separate circuits are used to supply power to the auxiliary heat kit, the Installer will need to verify that each leg of the auxiliary heat circuit breakers are wired from the power supply correctly in order for the electric heat kit to operate properly. This can be done by measuring the supply side voltage of the auxiliary heat circuit breakers. Put a voltmeter on the L2 side of Circuit Breaker One and on the L2 side of Circuit Breaker Two. The voltmeter should read approximately 0 volts. If the meter reads high voltage, the auxiliary heat breakers need to be rewired so that breakers in the auxiliary heat kit match the wiring of the Disconnect Panel breakers. Meaning, L1 and L2 from one breaker in the disconnect panel must connect to L1 and L2 at one of the auxiliary heat circuit breakers and L1 and L2 from the other breaker in the disconnect panel must connect to L1 and L2 of the other auxiliary heat circuit breaker, making sure that the L1 and L2 from each disconnect breaker matches the L1 and L2 at each of the auxiliary heat breakers.

Dual Power Supply Connections

Page 26: R-410A Refrigerant 2-6 Tons Submittal DataAIR HANDLER R-410A Refrigerant 2-6 Tons Submittal Data English Language/IP Units SD2518AG1 04/17 SAH

Contractor: P.O.: Engineer:

Project Name: Unit Tag:

SD2518AG1 04/17 26 Page _____ of _____

AIR HANDLER2-6 Tons

SAH

©2017 The manufacturer works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Purchaser’s approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely the manufacturer’s opinion or commendation of its products.

Wiring Schematics cont.SAH Air Handler Control Option C Schematic 97P903-05

RS485 NET

C R - + ABC P7

ABC Control Board in Split Unit

Detail ‘A’

Air Han

SUC

PHW HW

SCT

P8

MOTO

R P6

RS48

5 P7

ZONE P9

ABC

STEP

PER

ANA

ACC2

DHDI

V

C R L1 L1 L2 L2P1

2P1

0P5

P11

CR(-)(+) CR(-)(+) CR(-)(+)

P4P2

K1K2

K3

C

1C

2C

3CO

NDVS

DAT

AVS

PUM

PP3

V+CRTXRX +5

P14

10P1

CT2

43

CT2

43

CT1

21

CT1

21

StatusG

DISC

H

P16

P17

P18

P15

AHB™

SW1

Modbus Add. IDFuture Use

12345

ONOFF

Future UseAcc 2 – Dip 4Acc 2 – Dip 5

CCO

+5C

S+5

CPW

MC

C4

XC

CS

+5C

+58

CC

C7

69

Grn

23

45

1

ECM Blower Motor

234 1

Green/YellowBlue

PB1

Transformer

24V

HE4FL4HE3 FL3

HE1FL1

5

4

3

1

H

HSEQ1

5

4

3

1

H

HSEQ2

RELAY RELAY

HE2 FL2

208-

230/6

0/1

GL2

L1

BRK1

L2L1

BRK2

G

Circu

it 120

8-23

0/60/1

Circu

it 2

Blue Blue

BlueBlue

Yellow

Black

Yellow

Black

Blue

Blue

2

3

1

Blue

White

White

Brown

Brown

Blue

BlackBlack

RedRed

RedBlack

Black

Red

Red

Black

YellowBlack/White

Black Blue

Red

White

BrownBlue

Blue

Brown

Brown

Black

Black

Brown

Brown

T Gray

Gray

White

Green

BlackBlack

RedGreen

White

PB2

PB3

Auxiliary Heat Current Transducer

Blower Motor Current Transducer

Leaving Air Temperature LAT

Condensate Overflow

Orange

Brown T Black

BlackFP2 Sensor

Red

Note:1

Note:2

L1

L2

PB4

TS1

Black

YellowTS1

Yellow

Black

R1R2

NOTE:4

TO COMM STAT C R + -

TO ABC C R + -

Communicating Thermostat

Communicating Thermostat will connect to the COMM STAT (C R + -) power block PB3 in the air handler. A 4-conductor, 20AWG wire will need to connect from the TO ABC (C R + -) power block (PB2) in the Air Handler to the ABC P7(See detail ‘A’ on schematic) connection on the ABC board in the compressor section.

CT

Auxiliary Heat Current Transducer

Blower P

Factory settinL-H settings M"Aux" is facto"G" may be loCFM is controMax ESP inc

066

MODEL M

022

026

030

060

036

042

048Grn/Yel

Ther

mosta

t

RC

Y1

O

DH

Y2

G

W

LO

Non-Communicating Thermostat

LORCOGY1Y2

DHW

P1 ABC Board

Non-Communicating Thermostat will connect to the P1 connection on the ABC board in the compressor section. A 4-conductor, 20AWG wire will need to connect from the ABC P7 (See detail ‘A’ on schematic) connection to the TO ABC (C R + -) power block (PB2) in the Air Handler.

Light emitting diode - Green

Fused Limit

Polarized connector

Factory Low voltage wiringFactory Line voltage wiringField low voltage wiringField line voltage wiringOptional blockDC Voltage PCB tracesInternal junctionQuick connect terminal

Thermal Limit Switch

Field wire lug

Ground

HE -

PB -

SW1 -

Heater element

Power block

DIP package 4 position

Legend

N.O., N.C.

G

L1

1 2 3P

Breaker

TS

FL

Notes:1 – To operate in 208V mode replace the blue transformer

wire connected to PB1-L2 with red transformer wire.

2 – Use manufacturer’s part number 19P592-01 (jumper bar assembly) when single source power is required.3 – Low voltage wiring CLASS 2.4 – DIP switch 1 on SW1 must be set in the OFF position.

Air Handler 20kW Electric Heat

If two separate circuits are used to supply power to the auxiliary heat kit, the Installer will need to verify that each leg of the auxiliary heat circuit breakers are wired from the power supply correctly in order for the electric heat kit to operate properly. This can be done by measuring the supply side voltage of the auxiliary heat circuit breakers. Put a voltmeter on the L2 side of Circuit Breaker One and on the L2 side of Circuit Breaker Two. The voltmeter should read approximately 0 volts. If the meter reads high voltage, the auxiliary heat breakers need to be rewired so that breakers in the auxiliary heat kit match the wiring of the Disconnect Panel breakers. Meaning, L1 and L2 from one breaker in the disconnect panel must connect to L1 and L2 at one of the auxiliary heat circuit breakers and L1 and L2 from the other breaker in the disconnect panel must connect to L1 and L2 of the other auxiliary heat circuit breaker, making sure that the L1 and L2 from each disconnect breaker matches the L1 and L2 at each of the auxiliary heat breakers.

Dual Power Supply Connections

Page 27: R-410A Refrigerant 2-6 Tons Submittal DataAIR HANDLER R-410A Refrigerant 2-6 Tons Submittal Data English Language/IP Units SD2518AG1 04/17 SAH

Contractor: P.O.: Engineer:

Project Name: Unit Tag:

SD2518AG1 04/17 27 Page _____ of _____

AIR HANDLER2-6 Tons

SAH

©2017 The manufacturer works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Purchaser’s approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely the manufacturer’s opinion or commendation of its products.

Engineering Guide Specifi cationsGeneral

The air handler shall provide vertical upflow, downflow, or

horizontal configurations in one package. Units shall be

listed by a nationally recognized safety-testing laboratory

or agency, such as Underwriter’s Laboratory (UL) or

Environmental Testing Laboratories (Intertek-ETL). The

air handler units shall be designed and AHRI performance

listed to operate with the geothermal split condensing units

as provided by the manufacturer. Each unit shall be pallet

mounted and shipped using dense cardboard corners/top

and stretch wrap for easy shipping damage inspection.

Casing and Cabinet The cabinet shall be fabricated from heavy-gauge

galvanized steel and polyester powder coat paint to

withstand 1000 hours of salt spray testing. The interior

shall be insulated with 1 in. thick, multi-density, cleanable

aluminum foil coated glass fiber with edges sealed or

tucked under flanges to prevent the introduction of glass

fibers into the discharge air. One large blower compartment

access panel shall be provided and shall be removable

with supply and return ductwork in place. The internal

components layout shall provide for major service with

the unit in-place for restricted access installations. The

blower assembly access shall be slide-out serviceable via a

‘works-in-a-drawer’ design. The cabinet shall be convertible

to horizontal or downflow applications by reconfiguring

the cabinet using only a nut driver. The unit shall be ‘zero

clearance’ approved on any of its external surfaces.

Refrigeration Circuit All units shall provide a fin tube air-to-refrigerant heat

exchanger of the “A” coil design. The finned tube coil shall

be sized for low-face velocity and constructed of lanced

aluminum fins bonded to aluminum tubes in a staggered

pattern. The coil shall include a composite drain pan.

The thermal expansion valve shall be factory installed and

provide proper superheat over the entire liquid temperature

range with minimal “hunting.” The valve shall operate in the

cooling mode through the use of an internal check valve.

Blower Motor and AssemblyThe blower shall be an oversized direct drive centrifugal

type with a dynamically balanced wheel. The housing

and wheel shall be designed for quiet low outlet velocity

operation and of galvanized or galvalume steel construction.

Tight blower housing geometry shall not be permitted. The

blower housing shall be removable from the unit without

disconnecting the supply air ductwork for servicing of the

blower motor through a ‘works-in-a-drawer’ design. The

high efficiency blower motor shall be either a 5 speed ECM

or a variable speed ECM type. The blower motor shall be

isolated from the housing by rubber grommets. The motor

shall be permanently lubricated ball bearings and have

thermal overload protection.

Electrical A control section shall be located within the air handler

compartment and shall contain either a 75VA or 100VA

transformer, 24 volt activated. Transformers shall be

protected by internal circuit breakers. Units shall be

name-plated for use with time delay fuses or HACR circuit

breakers. Unit controls shall be either communicating

or 24 volt type. An Aurora AHB (control option C), a

microprocessor-based controller interfaces with the ABC

located in the compressor section to control unit operation,

shall be optional. The AHB control shall provide operational

sequencing, blower speed control, air coil freeze detection,

condensate overflow sensing, auxiliary heat staging, field

selectable options, and accessory output.

An integral circuit breaker shall be provided on all units

employing 15 kW or 20 kW electric heat. The control

shall maintain the blower operation 30 seconds after the

compressor or electric heat inputs have terminated.

A terminal block with screw terminals will be provided

for field control wiring. All units shall have knockouts for

entrance of low and line voltage wiring. The blower motor

and control box shall be harness plug wired for easy

removal.

An optional Aurora Interface Diagnostic (AID) Tool shall

communicate with the Aurora control allowing quick and

easy access to setup, monitoring, and troubleshooting of

any Aurora control. The device shall include the features of

fault description and history, manual operation capability,

sensor readings, timings, and other diagnostic tools.

Piping Refrigerant connections shall be made using sweat

copper joints. The condensate connections shall be a 3/4 in.

NPT.

Page 28: R-410A Refrigerant 2-6 Tons Submittal DataAIR HANDLER R-410A Refrigerant 2-6 Tons Submittal Data English Language/IP Units SD2518AG1 04/17 SAH

Contractor: P.O.: Engineer:

Project Name: Unit Tag:

SD2518AG1 04/17 28 Page _____ of _____

AIR HANDLER2-6 Tons

SAH

©2017 The manufacturer works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice. Purchaser’s approval of this data set signifies that the equipment is acceptable under the provisions of the job specification. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely the manufacturer’s opinion or commendation of its products.

Revision Guide

Pages: Description: Date: By:

All Document Creation 01 Mar. 2017 JM