SUBSTRATE FIXING THERMOPAD FixU T, THICKNESS 5 mm art.No 05.001.5 WASHER THERMAL INSULATION LAYER BRACKET FixU T, FIXED SUPPORT art.No 02.ft.160 T PROFILE 58x65x2.7 mm art.No 01.2.586527.6 5,9(7 [ PP art.No 04.4.4812.1 HPL PANEL FUNDERMAX UNDERCUT ANCHOR fischer FZP-N HANGER, ADJUSTABLE, FIXED POINT art.No 06.002.1 HANGER, ADJUSTABLE, FLEXIBLE POINT art.No 06.002.2 HORIZONTAL PROFILE art.No 06.2.xxxx CLADDING PANELS DRAWING RAINSCREEN SYSTEM EDITION _ THE SPECIFICATION OF THE PROFILES, ACCESSORIES AND THEIR POSITIONING, HAS TO BE AGREED UPON STATIC ANALYSIS. _ THE STATIC ANALYSIS MUST BE APPLIED FOR EACH PROJECT AND HAS TO RESPECT THE INDIVIDUALITY OF THE PROJECT, SPECIFIC CONDITIONS AND LOCAL REGULATIONS. IT PROVIDES SAFETY CHECK, VERIFICATION OF THE COMPONENTS AND OPTIMIZATION. _ ALL TECHNICAL REQUIREMENTS GIVEN BY THE SUPPLIER OF THE CLADDING PANELS HAVE TO BE SATISFIED. NOTES QV6 CONCEALED FASTENING SYSTEM USING UNDERCUT FIXINGS FUNDERMAX MAX EXTERIOR 01.1 HORIZONTAL SECTION JANUARY 2015

QV6 CONCEALED FASTENING SYSTEM USING UNDERCUT FIXINGSq-vent.eu/wp-content/uploads/2015/04/QV6-FUNDERMAX-UNDERCU… · cladding panels drawing rainscreen system edition _ the specification

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Page 1: QV6 CONCEALED FASTENING SYSTEM USING UNDERCUT FIXINGSq-vent.eu/wp-content/uploads/2015/04/QV6-FUNDERMAX-UNDERCU… · cladding panels drawing rainscreen system edition _ the specification

SUBSTRATE

FIXING

THERMOPAD FixU T, THICKNESS 5 mmart.No 05.001.5

WASHER

THERMAL INSULATION LAYER

BRACKET FixU T, FIXED SUPPORTart.No 02.ft.160

T PROFILE 58x65x2.7 mmart.No 01.2.586527.6

RIVET Ø4.8x12 mmart.No 04.4.4812.1

HPL PANEL FUNDERMAX

UNDERCUT ANCHOR fischer FZP-N

HANGER, ADJUSTABLE, FIXED POINTart.No 06.002.1

HANGER, ADJUSTABLE, FLEXIBLE POINTart.No 06.002.2

HORIZONTAL PROFILEart.No 06.2.xxxx

CLADDING PANELS

DRAWING

RAINSCREEN SYSTEM

EDITION

_ THE SPECIFICATION OF THE PROFILES, ACCESSORIES AND THEIR

POSITIONING, HAS TO BE AGREED UPON STATIC ANALYSIS.

_ THE STATIC ANALYSIS MUST BE APPLIED FOR EACH PROJECT

AND HAS TO RESPECT THE INDIVIDUALITY OF THE PROJECT,

SPECIFIC CONDITIONS AND LOCAL REGULATIONS. IT PROVIDES

SAFETY CHECK, VERIFICATION OF THE COMPONENTS AND

OPTIMIZATION.

_ ALL TECHNICAL REQUIREMENTS GIVEN BY THE SUPPLIER OF THE

CLADDING PANELS HAVE TO BE SATISFIED.

NOTES

QV6CONCEALED FASTENING SYSTEMUSING UNDERCUT FIXINGS

FUNDERMAX MAX EXTERIOR

01.1 HORIZONTAL SECTION

JANUARY 2015

Page 2: QV6 CONCEALED FASTENING SYSTEM USING UNDERCUT FIXINGSq-vent.eu/wp-content/uploads/2015/04/QV6-FUNDERMAX-UNDERCU… · cladding panels drawing rainscreen system edition _ the specification

FIXING

THERMOPAD FixU T, THICKNESS 5 mmart.No 05.001.5

WASHER

THERMAL INSULATION LAYER

BRACKET FixU T, FIXED SUPPORTart.No 02.ft.160

T PROFILE 58x65x2.7 mmart.No 01.2.586527.6

RIVET Ø4.8x12 mmart.No 04.4.4812.1

HPL PANEL FUNDERMAX

HORIZONTAL PROFILEart.No 06.2.xxxx

SFS BLIND FASTENER TU-S

HANGER, ADJUSTABLE, FIXED POINTart.No 06.002.4

HANGER, ADJUSTABLE, FLEXIBLE POINTart.No 06.002.5

SUBSTRATE

CLADDING PANELS

DRAWING

RAINSCREEN SYSTEM

EDITION

_ THE SPECIFICATION OF THE PROFILES, ACCESSORIES AND THEIR

POSITIONING, HAS TO BE AGREED UPON STATIC ANALYSIS.

_ THE STATIC ANALYSIS MUST BE APPLIED FOR EACH PROJECT

AND HAS TO RESPECT THE INDIVIDUALITY OF THE PROJECT,

SPECIFIC CONDITIONS AND LOCAL REGULATIONS. IT PROVIDES

SAFETY CHECK, VERIFICATION OF THE COMPONENTS AND

OPTIMIZATION.

_ ALL TECHNICAL REQUIREMENTS GIVEN BY THE SUPPLIER OF THE

CLADDING PANELS HAVE TO BE SATISFIED.

NOTES

QV6CONCEALED FASTENING SYSTEMUSING UNDERCUT FIXINGS

FUNDERMAX MAX EXTERIOR

01.2 HORIZONTAL SECTION_OPTION 2

JANUARY 2015

Page 3: QV6 CONCEALED FASTENING SYSTEM USING UNDERCUT FIXINGSq-vent.eu/wp-content/uploads/2015/04/QV6-FUNDERMAX-UNDERCU… · cladding panels drawing rainscreen system edition _ the specification

THERMOPAD FixU T, THICKNESS 5 mmart.No 05.001.5

BRACKET FixU T, FIXED SUPPORTart.No 02.ft.160

FIXING

RIVET Ø4.8x12 mmart.No 04.4.4812.1

BRACKET FixU L, FLEXIBLE SUPPORTart.No 02.fl.160

THERMOPAD FixU L, THICKNESS 5 mmart.No 05.001.1

SUBSTRATE

THERMAL INSULATION LAYER

T PROFILE 58x65x2.7 mmart.No 01.2.586527.6

HANGER, FLEXIBLE POINTart.No 06.002.3

HORIZONTAL PROFILEart.No 06.2.xxxx

UNDERCUT ANCHOR fischer FZP-N

HANGER, ADJUSTABLE, FIXED POINTart.No 06.002.4

HPL PANEL FUNDERMAX

CLADDING PANELS

DRAWING

RAINSCREEN SYSTEM

EDITION

_ THE SPECIFICATION OF THE PROFILES, ACCESSORIES AND THEIR

POSITIONING, HAS TO BE AGREED UPON STATIC ANALYSIS.

_ THE STATIC ANALYSIS MUST BE APPLIED FOR EACH PROJECT

AND HAS TO RESPECT THE INDIVIDUALITY OF THE PROJECT,

SPECIFIC CONDITIONS AND LOCAL REGULATIONS. IT PROVIDES

SAFETY CHECK, VERIFICATION OF THE COMPONENTS AND

OPTIMIZATION.

_ ALL TECHNICAL REQUIREMENTS GIVEN BY THE SUPPLIER OF THE

CLADDING PANELS HAVE TO BE SATISFIED.

NOTES

QV6CONCEALED FASTENING SYSTEMUSING UNDERCUT FIXINGS

FUNDERMAX MAX EXTERIOR

02.1 VERTICAL SECTION

JANUARY 2015

Page 4: QV6 CONCEALED FASTENING SYSTEM USING UNDERCUT FIXINGSq-vent.eu/wp-content/uploads/2015/04/QV6-FUNDERMAX-UNDERCU… · cladding panels drawing rainscreen system edition _ the specification

THERMOPAD FixU T, THICKNESS 5 mmart.No 05.001.5

BRACKET FixU T, FIXED SUPPORTart.No 02.ft.160

FIXING

BRACKET FixU L, FLEXIBLE SUPPORTart.No 02.fl.160

HANGER, ADJUSTABLE, FIXED POINTart.No 06.002.4

SUBSTRATE

THERMAL INSULATION LAYER

HANGER, FLEXIBLE POINTart.No 06.002.6

HORIZONTAL PROFILEart.No 06.2.xxxx

SFS BLIND FASTENER TU-S

T PROFILE 58x65x2.7 mmart.No 01.2.586527.6

HPL PANEL FUNDERMAX

RIVET Ø4.8x12 mmart.No 04.4.4812.1

THERMOPAD FixU L, THICKNESS 5 mmart.No 05.001.1

CLADDING PANELS

DRAWING

RAINSCREEN SYSTEM

EDITION

_ THE SPECIFICATION OF THE PROFILES, ACCESSORIES AND THEIR

POSITIONING, HAS TO BE AGREED UPON STATIC ANALYSIS.

_ THE STATIC ANALYSIS MUST BE APPLIED FOR EACH PROJECT

AND HAS TO RESPECT THE INDIVIDUALITY OF THE PROJECT,

SPECIFIC CONDITIONS AND LOCAL REGULATIONS. IT PROVIDES

SAFETY CHECK, VERIFICATION OF THE COMPONENTS AND

OPTIMIZATION.

_ ALL TECHNICAL REQUIREMENTS GIVEN BY THE SUPPLIER OF THE

CLADDING PANELS HAVE TO BE SATISFIED.

NOTES

QV6CONCEALED FASTENING SYSTEMUSING UNDERCUT FIXINGS

FUNDERMAX MAX EXTERIOR

02.2 VERTICAL SECTION|_OPTION 2

JANUARY 2015

Page 5: QV6 CONCEALED FASTENING SYSTEM USING UNDERCUT FIXINGSq-vent.eu/wp-content/uploads/2015/04/QV6-FUNDERMAX-UNDERCU… · cladding panels drawing rainscreen system edition _ the specification

HANGER, ADJUSTABLE, FIXED POINTart.No 06.002.1

UNDERCUT ANCHOR fischer FZP-N

HORIZONTAL PROFILEart.No 06.2.xxxx

SUBSTRATE

THERMAL INSULATION LAYER

HPL PANEL FUNDERMAX

FIXING

THERMOPAD FixU L, THICKNESS 5 mmart.No 05.001.1

WASHER

BRACKET FixU L, FLEXIBLE SUPPORTart.No 02.fl.160

T PROFILE 58x65x2.7 mmart.No 01.2.586527.6

L PROFILE 66x66x2 mmart.No 01.1.66662.6

HANGER, ADJUSTABLE, FLEXIBLE POINTart.No 06.002.2

RIVET Ø4.8x12 mmart.No 04.4.4812.1

EDITION

CLADDING PANELS

DRAWING

RAINSCREEN SYSTEM

EDITION

_ THE SPECIFICATION OF THE PROFILES, ACCESSORIES AND THEIR

POSITIONING, HAS TO BE AGREED UPON STATIC ANALYSIS.

_ THE STATIC ANALYSIS MUST BE APPLIED FOR EACH PROJECT

AND HAS TO RESPECT THE INDIVIDUALITY OF THE PROJECT,

SPECIFIC CONDITIONS AND LOCAL REGULATIONS. IT PROVIDES

SAFETY CHECK, VERIFICATION OF THE COMPONENTS AND

OPTIMIZATION.

_ ALL TECHNICAL REQUIREMENTS GIVEN BY THE SUPPLIER OF THE

CLADDING PANELS HAVE TO BE SATISFIED.

NOTES

QV6CONCEALED FASTENING SYSTEMUSING UNDERCUT FIXINGS

FUNDERMAX MAX EXTERIOR

03 EXTERNAL CORNER

JANUARY 2015

Page 6: QV6 CONCEALED FASTENING SYSTEM USING UNDERCUT FIXINGSq-vent.eu/wp-content/uploads/2015/04/QV6-FUNDERMAX-UNDERCU… · cladding panels drawing rainscreen system edition _ the specification

FIXING

THERMOPAD FixU T, THICKNESS 5 mmart.No 05.001.5

WASHER

BRACKET FixU T, FIXED SUPPORTart.No 02.ft.160

T PROFILE 58x65x2.7 mmart.No 01.2.586527.6

RIVET Ø4.8x12 mmart.No 04.4.4812.1

HANGER, ADJUSTABLE, FIXED POINTart.No 06.002.1

HPL PANEL FUNDERMAX

THERMAL INSULATION LAYER

SUBSTRATE

HORIZONTAL PROFILEart.No 06.2.xxxx

HANGER, ADJUSTABLE, FLEXIBLE POINTart.No 06.002.2

UNDERCUT ANCHOR fischer FZP-N

CLADDING PANELS

DRAWING

RAINSCREEN SYSTEM

EDITION

_ THE SPECIFICATION OF THE PROFILES, ACCESSORIES AND THEIR

POSITIONING, HAS TO BE AGREED UPON STATIC ANALYSIS.

_ THE STATIC ANALYSIS MUST BE APPLIED FOR EACH PROJECT

AND HAS TO RESPECT THE INDIVIDUALITY OF THE PROJECT,

SPECIFIC CONDITIONS AND LOCAL REGULATIONS. IT PROVIDES

SAFETY CHECK, VERIFICATION OF THE COMPONENTS AND

OPTIMIZATION.

_ ALL TECHNICAL REQUIREMENTS GIVEN BY THE SUPPLIER OF THE

CLADDING PANELS HAVE TO BE SATISFIED.

NOTES

QV6CONCEALED FASTENING SYSTEMUSING UNDERCUT FIXINGS

FUNDERMAX MAX EXTERIOR

04 INTERNAL CORNER

JANUARY 2015

Page 7: QV6 CONCEALED FASTENING SYSTEM USING UNDERCUT FIXINGSq-vent.eu/wp-content/uploads/2015/04/QV6-FUNDERMAX-UNDERCU… · cladding panels drawing rainscreen system edition _ the specification

RIVET Ø4.8x12 mmart.No 04.4.4812.1

FIXING

BRACKET FixU L, FLEXIBLE SUPPORTart.No 02.fl.160

THERMOPAD FixU L, THICKNESS 5 mmart.No 05.001.1

SUBSTRATE

THERMAL INSULATION LAYER

T PROFILE 58x65x2.7 mmart.No 01.2.586527.6

UNDERCUT ANCHOR fischer FZP-N

SELF-DRILLING SCREW

HPL PANEL FUNDERMAX

L PROFILE 60x40x2 mmart.No 01.1.60402.6

L PROFILE 40x20x2 mmart.No 01.1.40202.6

HANGER, FLEXIBLE POINTart.No 06.002.3

HORIZONTAL PROFILEart.No 06.2.xxxx

PERFORATED ALUMINUIM SHEET

CLADDING PANELS

DRAWING

RAINSCREEN SYSTEM

EDITION

_ THE SPECIFICATION OF THE PROFILES, ACCESSORIES AND THEIR

POSITIONING, HAS TO BE AGREED UPON STATIC ANALYSIS.

_ THE STATIC ANALYSIS MUST BE APPLIED FOR EACH PROJECT

AND HAS TO RESPECT THE INDIVIDUALITY OF THE PROJECT,

SPECIFIC CONDITIONS AND LOCAL REGULATIONS. IT PROVIDES

SAFETY CHECK, VERIFICATION OF THE COMPONENTS AND

OPTIMIZATION.

_ ALL TECHNICAL REQUIREMENTS GIVEN BY THE SUPPLIER OF THE

CLADDING PANELS HAVE TO BE SATISFIED.

NOTES

QV6CONCEALED FASTENING SYSTEMUSING UNDERCUT FIXINGS

FUNDERMAX MAX EXTERIOR

05 VERTICAL SECTION_FACADE BASE

JANUARY 2015

Page 8: QV6 CONCEALED FASTENING SYSTEM USING UNDERCUT FIXINGSq-vent.eu/wp-content/uploads/2015/04/QV6-FUNDERMAX-UNDERCU… · cladding panels drawing rainscreen system edition _ the specification

ALUMINIUM SHEET

PERFORATED ALUMINIUM SHEET

L PROFILE 40x40x2 mmart.No 01.1.40402.6

HANGER, ADJUSTABLE, FLEXIBLE POINTart.No 06.002.2

HPL PANEL FUNDERMAX

FIXING

RIVET Ø4.8x12 mmart.No 04.4.4812.1

BRACKET FixU T, FIXED SUPPORTart.No 02.ft.160

THERMOPAD FixU T, THICKNESS 5 mmart.No 05.001.5

T PROFILE 58x65x2.7 mmart.No 01.2.586527.6

THERMAL INSULATION LAYER

UNDERCUT ANCHOR fischer FZP-N

HORIZONTAL PROFILEart.No 06.2.xxxx

SUBSTRATE

CLADDING PANELS

DRAWING

RAINSCREEN SYSTEM

EDITION

_ THE SPECIFICATION OF THE PROFILES, ACCESSORIES AND THEIR

POSITIONING, HAS TO BE AGREED UPON STATIC ANALYSIS.

_ THE STATIC ANALYSIS MUST BE APPLIED FOR EACH PROJECT

AND HAS TO RESPECT THE INDIVIDUALITY OF THE PROJECT,

SPECIFIC CONDITIONS AND LOCAL REGULATIONS. IT PROVIDES

SAFETY CHECK, VERIFICATION OF THE COMPONENTS AND

OPTIMIZATION.

_ ALL TECHNICAL REQUIREMENTS GIVEN BY THE SUPPLIER OF THE

CLADDING PANELS HAVE TO BE SATISFIED.

NOTES

QV6CONCEALED FASTENING SYSTEMUSING UNDERCUT FIXINGS

FUNDERMAX MAX EXTERIOR

06 VERTICAL SECTION_ROOFBORDER COVER

JANUARY 2015

Page 9: QV6 CONCEALED FASTENING SYSTEM USING UNDERCUT FIXINGSq-vent.eu/wp-content/uploads/2015/04/QV6-FUNDERMAX-UNDERCU… · cladding panels drawing rainscreen system edition _ the specification

THERMOPAD FixU L, THICKNESS 5 mmart.No 05.001.1

WASHER

BRACKET FixU L, FLEXIBLE SUPPORTart.No 02.fl.160

T PROFILE 58x65x2.7 mmart.No 01.2.586527.6

RIVET Ø4.8x12 mmart.No 04.4.4812.1

HORIZONTAL PROFILEart.No 06.2.xxxx

HANGER, ADJUSTABLE, FLEXIBLE POINTart.No 06.002.2

UNDERCUT ANCHOR fischer FZP-N

HPL PANEL FUNDERMAX

SikaTack-PANEL ADHESIVEart.No 07.001.1

SikaTack-PANEL FIXING TAPEart.No 07.001.3

FIXING

L PROFILE 60x40x2 mmart.No 01.1.60402.6

CLADDING PANELS

DRAWING

RAINSCREEN SYSTEM

EDITION

_ THE SPECIFICATION OF THE PROFILES, ACCESSORIES AND THEIR

POSITIONING, HAS TO BE AGREED UPON STATIC ANALYSIS.

_ THE STATIC ANALYSIS MUST BE APPLIED FOR EACH PROJECT

AND HAS TO RESPECT THE INDIVIDUALITY OF THE PROJECT,

SPECIFIC CONDITIONS AND LOCAL REGULATIONS. IT PROVIDES

SAFETY CHECK, VERIFICATION OF THE COMPONENTS AND

OPTIMIZATION.

_ ALL TECHNICAL REQUIREMENTS GIVEN BY THE SUPPLIER OF THE

CLADDING PANELS HAVE TO BE SATISFIED.

NOTES

QV6CONCEALED FASTENING SYSTEMUSING UNDERCUT FIXINGS

FUNDERMAX MAX EXTERIOR

07.1 HORIZONTAL SECTION_WINDOW REVEAL

JANUARY 2015

Page 10: QV6 CONCEALED FASTENING SYSTEM USING UNDERCUT FIXINGSq-vent.eu/wp-content/uploads/2015/04/QV6-FUNDERMAX-UNDERCU… · cladding panels drawing rainscreen system edition _ the specification

SELF-DRILLING SCREW

ALUMINIUM SHEET

THERMOPAD FixU L, THICKNESS 5 mmart.No 05.001.1

WASHER

BRACKET FixU L, FLEXIBLE SUPPORTart.No 02.fl.160

T PROFILE 58x65x2.7 mmart.No 01.2.586527.6

HANGER, ADJUSTABLE, FLEXIBLE POINTart.No 06.002.2

UNDERCUT ANCHOR fischer FZP-N

HPL PANEL FUNDERMAX

FIXING

RIVET Ø4.8x12 mmart.No 04.4.4812.1

HORIZONTAL PROFILEart.No 06.2.xxxx

CLADDING PANELS

DRAWING

RAINSCREEN SYSTEM

EDITION

_ THE SPECIFICATION OF THE PROFILES, ACCESSORIES AND THEIR

POSITIONING, HAS TO BE AGREED UPON STATIC ANALYSIS.

_ THE STATIC ANALYSIS MUST BE APPLIED FOR EACH PROJECT

AND HAS TO RESPECT THE INDIVIDUALITY OF THE PROJECT,

SPECIFIC CONDITIONS AND LOCAL REGULATIONS. IT PROVIDES

SAFETY CHECK, VERIFICATION OF THE COMPONENTS AND

OPTIMIZATION.

_ ALL TECHNICAL REQUIREMENTS GIVEN BY THE SUPPLIER OF THE

CLADDING PANELS HAVE TO BE SATISFIED.

NOTES

QV6CONCEALED FASTENING SYSTEMUSING UNDERCUT FIXINGS

FUNDERMAX MAX EXTERIOR

07.2 HORIZONTAL SECTION_WINDOW REVEAL

JANUARY 2015

Page 11: QV6 CONCEALED FASTENING SYSTEM USING UNDERCUT FIXINGSq-vent.eu/wp-content/uploads/2015/04/QV6-FUNDERMAX-UNDERCU… · cladding panels drawing rainscreen system edition _ the specification

8.1SUBSTRATE

THERMAL INSULATION LAYER

RIVET Ø4.8x12 mmart.No 04.4.4812.1

FIXING

BRACKET FixU L, FLEXIBLE SUPPORTart.No 02.fl.160

THERMOPAD FixU L, THICKNESS 5 mmart.No 05.001.1

T PROFILE 58x65x2.7 mmart.No 01.2.586527.6

HPL PANEL FUNDERMAX

HANGER, FLEXIBLE POINTart.No 06.002.3

UNDERCUT ANCHOR fischer FZP-N

HORIZONTAL PROFILEart.No 06.2.xxxx

ALUMINIUM SHEET

SELF-DRILLING SCREW

CLADDING PANELS

DRAWING

RAINSCREEN SYSTEM

EDITION

_ THE SPECIFICATION OF THE PROFILES, ACCESSORIES AND THEIR

POSITIONING, HAS TO BE AGREED UPON STATIC ANALYSIS.

_ THE STATIC ANALYSIS MUST BE APPLIED FOR EACH PROJECT

AND HAS TO RESPECT THE INDIVIDUALITY OF THE PROJECT,

SPECIFIC CONDITIONS AND LOCAL REGULATIONS. IT PROVIDES

SAFETY CHECK, VERIFICATION OF THE COMPONENTS AND

OPTIMIZATION.

_ ALL TECHNICAL REQUIREMENTS GIVEN BY THE SUPPLIER OF THE

CLADDING PANELS HAVE TO BE SATISFIED.

NOTES

QV6CONCEALED FASTENING SYSTEMUSING UNDERCUT FIXINGS

FUNDERMAX MAX EXTERIOR

08.1 VERTICAL SECTION_WINDOW LINTEL

JANUARY 2015

Page 12: QV6 CONCEALED FASTENING SYSTEM USING UNDERCUT FIXINGSq-vent.eu/wp-content/uploads/2015/04/QV6-FUNDERMAX-UNDERCU… · cladding panels drawing rainscreen system edition _ the specification

8.2RIVET Ø4.8x12 mmart.No 04.4.4812.1

FIXING

BRACKET FixU L, FLEXIBLE SUPPORTart.No 02.fl.160

THERMOPAD FixU L, THICKNESS 5 mmart.No 05.001.1

L PROFILE 60x40x2 mmart.No 01.1.60402.6

ALUMINIUM SHEET

HPL PANEL FUNDERMAX

HANGER, FLEXIBLE POINTart.No 06.002.3

UNDERCUT ANCHOR fischer FZP-N

HORIZONTAL PROFILEart.No 06.2.xxxx

T PROFILE 58x65x2.7 mmart.No 01.2.586527.6

CLADDING PANELS

DRAWING

RAINSCREEN SYSTEM

EDITION

_ THE SPECIFICATION OF THE PROFILES, ACCESSORIES AND THEIR

POSITIONING, HAS TO BE AGREED UPON STATIC ANALYSIS.

_ THE STATIC ANALYSIS MUST BE APPLIED FOR EACH PROJECT

AND HAS TO RESPECT THE INDIVIDUALITY OF THE PROJECT,

SPECIFIC CONDITIONS AND LOCAL REGULATIONS. IT PROVIDES

SAFETY CHECK, VERIFICATION OF THE COMPONENTS AND

OPTIMIZATION.

_ ALL TECHNICAL REQUIREMENTS GIVEN BY THE SUPPLIER OF THE

CLADDING PANELS HAVE TO BE SATISFIED.

NOTES

QV6CONCEALED FASTENING SYSTEMUSING UNDERCUT FIXINGS

FUNDERMAX MAX EXTERIOR

08.2 VERTICAL SECTION_WINDOW LINTEL

JANUARY 2015

Page 13: QV6 CONCEALED FASTENING SYSTEM USING UNDERCUT FIXINGSq-vent.eu/wp-content/uploads/2015/04/QV6-FUNDERMAX-UNDERCU… · cladding panels drawing rainscreen system edition _ the specification

HANGER, ADJUSTABLE, FIXED POINTart.No 06.002.1

SELF-DRILLING SCREW

ALUMINIUM SHEET

L PROFILE 40x40x2 mmart.No 01.1.40402.6

HPL PANEL FUNDERMAX

FIXING

BRACKET FixU T, FIXED SUPPORTart.No 02.ft.160

THERMOPAD FixU T, THICKNESS 5 mmart.No 05.001.5

RIVET Ø4.8x12 mmart.No 04.4.4812.1

T PROFILE 58x65x2.7 mmart.No 01.2.586527.6

THERMAL INSULATION LAYER

SUBSTRATE

UNDERCUT ANCHOR fischer FZP-N

HORIZONTAL PROFILEart.No 06.2.xxxx

CLADDING PANELS

DRAWING

RAINSCREEN SYSTEM

EDITION

_ THE SPECIFICATION OF THE PROFILES, ACCESSORIES AND THEIR

POSITIONING, HAS TO BE AGREED UPON STATIC ANALYSIS.

_ THE STATIC ANALYSIS MUST BE APPLIED FOR EACH PROJECT

AND HAS TO RESPECT THE INDIVIDUALITY OF THE PROJECT,

SPECIFIC CONDITIONS AND LOCAL REGULATIONS. IT PROVIDES

SAFETY CHECK, VERIFICATION OF THE COMPONENTS AND

OPTIMIZATION.

_ ALL TECHNICAL REQUIREMENTS GIVEN BY THE SUPPLIER OF THE

CLADDING PANELS HAVE TO BE SATISFIED.

NOTES

QV6CONCEALED FASTENING SYSTEMUSING UNDERCUT FIXINGS

FUNDERMAX MAX EXTERIOR

09 VERTICAL SECTION_WINDOW SILL

JANUARY 2015