Upload
others
View
1
Download
0
Embed Size (px)
Citation preview
2018 SEAOC CONVENTION PROCEEDINGS
1
Quantitative Evaluation of Code Provisions for Vertically Irregular Frame Buildings
Katherine Wade, Haselton Baker Risk Group, LLC
D. Jared DeBock, California State University, Chico Haselton Baker Risk Group, LLC
Dustin Cook, Colorado State University, Boulder Curt Haselton, California State University, Chico
Haselton Baker Risk Group, LLC Michael Valley, Magnusson Klemencic Associates
Thomas Sabol, Englekirk Structural Engineers University of California, Los Angeles
Abstract Vertically irregular buildings are addressed in building codes
by imposing design requirements and limitations on buildings
with the intention of maintaining acceptable seismic
performance. However, relatively few studies have
quantitatively evaluated the treatment of vertical irregularities
in design codes. This study assesses the collapse
performance of a variety of vertically irregular buildings as
well as their treatment in building codes and standards
(primarily ASCE/SEI 7-16) using the FEMA P695
Methodology.
The following vertical irregularities are examined in this
study: Soft Story Irregularity, Mass Irregularity, and Weak
Story Irregularity; also explored are thresholds for strong-
column/weak-beam (SCWB) requirements and the effect of
gravity-induced lateral loads on collapse potential. These
irregularities were analyzed in OpenSees using non-linear
building frame models ranging from 3 to 20 stories located in
both high and low seismicity regions.
Preliminary results suggest that the ASCE/SEI 7-16 seismic
design provisions generally provide adequate collapse
resistance for regular and vertically irregular buildings.
However, caution is recommended when “optimizing” a
building design by reducing member sizes to the point that
code requirements are barely met throughout the structure; this
may dangerously reduce collapse resistance. It is a further
early conclusion of this work that prohibition of the Equivalent
Lateral Force (ELF) method for some vertical irregularities,
such as Mass Irregularity, is unnecessary, because the ELF
design procedure generally results in equivalent or better
collapse resistance than the Modal Response Spectrum
Analysis (MRSA) procedure (even when the MRSA base shear
is scaled up to 100% of the ELF value, as required in
ASCE/SEI 7-16).
Introduction
This study investigates the performance of vertically irregular
frame buildings for two purposes:
1. Assess the adequacy of current ASCE/SEI 7-16
(ASCE, 2016) provisions for vertical irregularities in
terms of collapse performance.
2. Consider whether additional provisions should
extend the treatment of vertical irregularities in
ASCE/SEI 7-16.
The irregularities and configurations that are examined
include:
Mass/Weight Irregularity
Soft/Weak Story Irregularity
Strong-Column/Weak-Beam Provisions
Gravity-Induced Lateral Demand Irregularity
This paper is an extension of a previous publication (DeBock
et al., 2018) which provided information on the methods used
in this study and preliminary results. The methods of the study
are replicated in this paper and extended with the final results
and conclusions on the collapse performance of vertically
irregular buildings.
Method
The methods and modeling details of this study originally
presented in (DeBock, et. al., 2018) are presented in this and
2018 SEAOC CONVENTION PROCEEDINGS
2
the following sections. The performance of archetype
buildings with vertical irregularities is compared to baseline
archetypes that are not irregular, using collapse resistance as
the metric. Collapse resistance is computed using the FEMA
P695 process (FEMA, 2009). The median spectral
acceleration for which side-sway collapse occurs is computed
by performing incremental dynamic analysis (IDA,
Vamvatsikos & Cornell, 2002) with the FEMA P695 far-field
ground motion set. The median collapse intensity is then
divided by the maximum considered earthquake (MCE)
intensity to compute a collapse margin ratio (CMR) and
adjusted collapse margin ratio (ACMR). FEMA P695 uses
ACMR to compute probability of collapse, given MCE; this
study focuses on changes to the ACMR caused by vertical
irregularities. If a vertical irregularity does not significantly
reduce collapse resistance relative to the baseline (regular)
building, then we conclude that the design procedures used to
account for that irregularity are adequate.
Baseline Archetypes
A set of baseline concrete and steel perimeter moment frame
designs are developed, ranging from three to twenty stories.
The archetypes are designed according to ASCE/SEI 7-16 for
seismic design category (SDC) Dmax and Bmax (i.e. the highest
possible demands for SDC D and SDC B) and referenced
design standards for steel (AISC, 2010a & 2010b) and concrete
(ACI, 2015). The Equivalent Lateral Force procedure (ELF)
and Modal Response Spectrum Analysis (MRSA) from
ASCE/SEI 7-16 Chapter 12 are both used for design. All
frames are designed as Risk Category II structures meeting a
2% design drift limit.
Structural Modeling of the Archetype Buildings
General Modeling Considerations
Nonlinear models of the moment frame archetype buildings
are constructed in OpenSEES (PEER, 2016) using the lumped
plasticity method. The lumped plasticity models consist of
linear elastic beam and column elements, joined by nonlinear
elements where plastic deformations are expected to
concentrate, as depicted in Figure 1. Nonlinear behavior is
simulated with plastic hinges at the ends of beams and columns
and with nonlinear joint panel zone elements.
Gravity loads are applied to the frames and also to a leaning
column. Per FEMA P695, the load combination representing
expected gravity loads, 1.05D + 0.25L, is used to compute the
vertical load effects. Gravity loads directly carried by the
frames are distributed on the beams. The remaining gravity
load, which is carried by the building’s gravity system, is
applied to the leaning P-Delta column. Building mass tributary
to the walls is lumped at the wall nodes. For analysis, an
expected mass of 1.05 times the dead weight is considered.
Steel Moment Frame Modeling
Nonlinear beam and column hinges are modeled with the
Modified Ibarra-Medina-Krawinkler deterioration model with
bilinear hysteretic response (Ibarra & Krawinkler, 2005) in
OpenSEES. Initial backbone properties are calculated with the
equations recommended by (NIST, 2017) and cyclic
deterioration parameters are computed from (Lignos &
Krawinkler, 2010). For calculating the nonlinear properties of
the beams and columns, the actual yield strength of the steel is
assumed to be 10% higher than the nominal yield strength (per
NIST, 2017). Although composite action is not considered for
the design of the frame beams, it is considered in the nonlinear
analysis, because steel moment frames are commonly
connected to a diaphragm. The controlling mechanism for
composite action of the slabs is yielding of the shear studs,
which are assumed be ¾” diameter, 75 ksi steel, placed at 12
inches on center. Panel zones are modeled with the Joint2D
element in OpenSEES with nonlinear behavior idealized as
trilinear without cyclic deterioration, based on Chapter 8 of
(NIST, 2017) and (Gupta & Krawinkler, 1999).
Concrete Moment Frame Modeling
Nonlinear beam and column hinges are idealized with trilinear
backbones having peak-oriented hysteretic response and cyclic
deterioration (Ibarra, Medina, & Krawlinker, 2005). The
backbone and hysteretic properties of the nonlinear beam-
column hinges are computed from empirical relationships
developed by (Haselton, et. al., 2008) based on the design
properties of the beams and columns (i.e. concrete strength,
element dimensions, axial load ratio, and reinforcement
detailing). RC OMF joints are calibrated according to
(Altoontash, 2004) & (Lowes, Mitra, Altoontash, 2004) and
are modeled with the Ibarra material model (Ibarra, Medina, &
Krawlinker, 2005) with pinched cyclic response. Joint
strength and rotation capacity depend on joint size,
confinement, concrete strength, and axial load ratio. RC
special moment frame (SMF) joints are not expected to fail, so
they are modeled with elastic elements.
Results
The performance of archetype buildings is gauged by dividing
their ACMR by the ACMR of the baseline to get collapse
resistance relative to the baseline (regular) building—relative
collapse resistance less than 1.0 corresponds to a reduction in
collapse resistance. In some cases, the performance of
buildings designed with the MRSA method are contrasted with
2018 SEAOC CONVENTION PROCEEDINGS
3
Figure 1. Schematic of a lumped plasticity nonlinear frame model (FEMA, 2018).
ELF designed buildings. Baseline and irregular archetypes
designed by the ELF procedure achieve equivalent or higher
collapse resistance than the MRSA designed buildings (even
with ELF and MRSA scaled to the same base shear). This
observation indicates that some limitations on ELF,
particularly the prohibition of ELF for mass irregular
buildings, may be unnecessary.
Weight (Mass) Irregularity
Irregularity
According to ASCE/SEI 7-16 Table 12.3-2, “Weight (mass)
irregularity is defined to exist where the effective mass of any
story is more than 150% of the effective mass of an adjacent
story. A roof that is lighter than the floor below need not be
considered.” Where a mass irregularity exists, ELF design is
prohibited for SDC D and above.
Mass irregularities are examined in both steel and RC SMF
frames between 3 and 20 stories by placing excess mass at
different locations in the building. Only SMF buildings are
tested because limitations on mass irregularities are only
applicable in SDC D and above, and OMF buildings are
unusual in these regions. Buildings designed using MRSA and
ELF are tested. The mass ratios tested relative to the next
adjacent story are between 1.5 and 3.0. Each variant tested
trigger strength and drift checks and, if necessary, are re-
designed.
Results
At first look, it appears that steel buildings are more negatively
affected by mass irregularity than concrete buildings (see
Figure 2 and Figure 3), but this observation is an artifact of the
archetype designs, and is not expected it to be true in general.
The negative trend seen in Figure 3 is caused by the baseline
steel variants having much higher design overstrength than
some of the irregular variants; the static overstrength of mass
irregular steel models decreases by as much as 30% relative to
the baseline; for comparison the mass-irregular concrete
models maintain static overstrengths values within 2% of the
baseline. In the case of the three-story MRSA designed steel
frame variants with mass irregularity at the second story, the
member sizes in the steel buildings did not change when the
mass irregularity are introduced, even though the design base
shear increased substantially (as much as a 60% increase for
mass ratio = 3.0 for the three-story building). Therefore, the
decline in collapse resistance in the steel buildings is attributed
to a reduction in “overdesign;” when the overdesign of each
member remains nearly the same, as in the RC SMF archetypes
shown in Figure 2, no significant declines in collapse
resistance are observed.
Lea
nin
g (
P-Δ
)
colu
mn
Elastic beam/
column
Nonlinear
plastic hinge Nonlinear joint
element
2018 SEAOC CONVENTION PROCEEDINGS
4
In some of the RC frame buildings, the performance of the re-
designed mass irregular buildings even improves relative to the
baseline design. In all cases (including where the collapse
performance diminishes with increasing mass ratio), the ELF
designed buildings perform better than the MRSA designed
buildings. This is an interesting finding because mass
irregularity triggers a MRSA design in ASCE/SEI 7-16.
Figure 2. RC SMF V2 mass irregularity (FEMA, 2018).
Figure 3. Steel SMF V2 mass irregularity (FEMA, 2018).
The performance of the ELF and MRSA designed buildings
can be further investigated by examining the design demands
produced by each method. The story shears and overturning
moments using ELF are generally larger than those using
MRSA. Figure 4 and Figure 5 exemplify this finding,
presenting the design forces for an RC frame building with a
mass irregularity at the 3rd story. The MRSA design picks up
the increased force demand at the mass irregular third story,
however overall, the ELF designed building will be equally
strong at the irregular story and stronger than the MRSA
building in the floors above.
Figure 4. Comparison of ELF and MRSA design forces in
a mass irregular building (FEMA, 2018).
Figure 5. Comparison of ELF and MRSA story shear
forces in a mass irregular building (FEMA, 2018).
Conclusion and Recommendations
Based upon the superior collapse performance of ELF
designed buildings relative to MRSA designed buildings, it is
recommended that the prohibition on ELF design for mass
irregular buildings be removed from ASCE/SEI 7-16. It is
interesting to note that mass irregularities are examined in
this study by adjusting the mass ratio at a single story at a
time. A future study examining the effect of increased mass
over multiple stories on collapse may be valuable.
Soft and Weak Story Irregularities
Irregularity
According to ASCE/SEI 7-16 Table 12.3-2, a soft story
irregularity exists where there is “a story in which the lateral
stiffness is less than 70% of that in the story above or less
than 80% of the average stiffness of the three stories above.”
If the story stiffness is less than 60% of the story above or
2018 SEAOC CONVENTION PROCEEDINGS
5
less than 70% of the average of the three stories above, then it
has an extreme soft story irregularity.
Weak story irregularity exists where, “the story lateral
strength is less than 80% of that in the story above. The story
lateral strength is the total lateral strength of all seismic-
resisting elements sharing the story shear for the direction
under consideration.” An extreme weak story irregularity
occurs when the strength of a story is less than 65% of the
strength of the story above.
Where soft story irregularities exist, the ELF method is
prohibited (similar to the mass irregularity) for SDC D and
above. Weak story irregularities and extreme soft story
irregularities are prohibited in SDC E and F. Extreme weak
story irregularities are prohibited for SDC D and above, and
limited to 2 stories or 30 feet in SDC B and C.
Soft/weak story irregularities and extreme irregularities are
examined in RC SMF and OMF buildings between 4 and 20
stories tall. All of these buildings are designed using the ELF
procedure.
Soft and weak story irregularities are investigated using RC
SMF and OMF frames for target strength ratios between 0.6
and 0.8, and stiffness ratios between 0.6 and 0.9 relative to the
story above. Soft and weak story irregularities are achieved by
increasing the story height. Weak story irregularities are also
achieved with an alternative approach—increasing the strength
of the story above.
Results
The first method (increased story height) of creating the
irregularity does not produce clear trends in the RC SMF or
OMF collapse performance. As seen in Figure 6 and Figure 7,
the collapse performance does not tend to drop below
approximately 85% of the baseline model performance. In
part, this is because increasing the story height does not always
result in a decrease in story strength, particularly for OMF
variants whose columns are governed by lateral force demands
rather than strong-column-weak-beam ratio requirements.
Similar observations are made when collapse resistance is
plotted against relative stiffness, rather than relative strength.
The second method for achieving a weak story—increasing the
strength of the story directly above the “weak” story—tends to
result in collapse resistance somewhat higher for extreme weak
story ratios than for moderate weak story ratios (see Figure 8
and Figure 9). Haselton, et. al., 2010, showed that a weak story
irregularity caused by strengthening upper stories, similar to
this study, does not reduce collapse performance of RC
moment frames. The reason is a “weak” story irregularity in
code-conforming buildings really means the adjacent story is
strong—so collapse resistance is not compromised.
Figure 6. Soft/Weak story irregular RC SMF (FEMA,
2018).
Figure 7. Soft/Weak story irregular RC OMF (FEMA,
2018).
Figure 8. Weak story irregular RC SMF (FEMA, 2018).
2018 SEAOC CONVENTION PROCEEDINGS
6
Figure 9. Weak story irregular RC OMF (FEMA, 2018).
Conclusions and Recommendations
Based upon the acceptable collapse performance of the
soft/weak story archetypes (i.e. their collapse resistance does
not drop substantially below that of the baseline), it is
concluded that weak and soft story irregularities in code
conforming buildings are acceptable. This conclusion is
largely due to the fact that code conforming soft stories must
still meet drift requirements and “weak story” really means
“strong adjacent story.” These results suggest that the
prohibition of extreme weak story irregularities in SDC D and
the height limitation on extreme weak story irregularities in
SDC B and C may be overly conservative. More study would
be required to comment on the prohibition of weak and
extreme soft story irregularities in SDC E and F.
Strong-Column/Weak-Beam (SCWB)
Congifuration
Though strong-column/weak-beam (SCWB) is not a building
irregularity, it is a component of building configuration that
affects the collapse performance of the building. SCWB ratio
is currently addressed in material standards (ACI, 2015 &
AISC, 2010) and not ASCE/SEI 7-16.
The effect of SCWB ratios is examined in both steel and RC
SMF and OMF buildings (RC frames presented in this paper).
SCWB ratios between 0.5 and 2.0, and 0.4 and 1.0 for the SMF
and OMF buildings respectively are examined. “Realistic”
designs are created by setting a minimum SCWB ratio and
allowing the ratio to exceed the minimum where other design
factors control. “Exact” designs are created by exactly
matching the target SCWB ratio at each joint in the building
by allowing other design requirements to be violated.
Results
Overall, the collapse performance improves with increasing
SCWB ratio (see Figures 10-11). This is due to the damage
spreading out over the height of the building as the SCWB ratio
increases. It is also observed that the variants with SCWB
ratios below the material standard baseline (1.2 for RC frames)
tend to perform less favorably.
It is interesting to note that the way in which the SCWB ratio
is achieved affects the collapse performance of the building.
In some cases where the beam sizes are increased to reduce the
SCWB ratio, the collapse performance actually improves.
A further study (not examined in detail in this paper) is
designed to determine whether the enhanced performance of
increased SCWB ratio requirements might be achieved
economically by placing the highest SCWB ratio requirements
at the base of the building and allowing the requirements to
step down along the height of the building. It is determined
that this method of varying the SCWB target along the height
of the building has the potential to maintain or even increase
collapse performance in a cost-effective manner as long as the
minimum SCWB target at the top of the building does not drop
below the current material standard requirements.
Figure 10. SCWB RC SMF (FEMA, 2018).
Figure 11. SCWB RC OMF (FEMA, 2018).
2018 SEAOC CONVENTION PROCEEDINGS
7
Conclusion
There is no need to consider SCWB in ASCE/SEI 7-16 at this
time. Increasing the SCWB ratio beyond the material
standards generally increases collapse performance. There are
also preliminary results that suggest that stepping the target
SCWB ratio along the height of the building may be an
economic way to benefit from increasing the SCWB
requirements, however more study is required to make a
specific recommendation for how prescriptive requirements
could be structured to achieve this enhanced performance.
Gravity-Induced Lateral Demand (GILD)
Irregularity
Gravity-induced lateral demand (GILD) is not currently
recognized in ASCE/SEI 7-16 as a vertical irregularity.
However, recent studies (Dupuis, et. al., 2014 and Shorka, et.
al., 2014) have recommended that the National Building Code
of Canada recognize and restrict GILD irregular buildings due
to ratcheting behavior, increased inelastic drifts, and decreased
collapse capacity.
GILD is examined in this study predominately in 20 story steel
SMF and OMF buildings. The irregularity is achieved by
sloping all of the columns at a single story. The GILD
irregularity is quantified as the GILD ratio, which is defined as
the gravity-induced lateral demand normalized by the story
shear capacity. The tested GILD ratio values range from 0 to
0.5.
Results
When the building is designed for GILD, the collapse capacity
generally remains within 15% of the baseline, even increasing
with GILD ratio in some cases. Though collapse performance
is the main metric for performance used in this study, the drift
demands are also tracked for the GILD irregular buildings and
it is found that these demands amplified in the GILD irregular
buildings relative to regular buildings. This finding is in
keeping with an earlier study (Shorka, et. al., 2014), which
found that applying GILD over the entire height of the building
may have a negative effect on collapse performance, although
GILD at a single story tends to result in smaller amplification
in displacement demands.
Naturally, the archetype set of buildings tested in this study is
limited. These buildings are subjected to only the horizontal
components of far-field crustal ground motions and P-Delta
effects are simulated using the “Pdelta” transformation in
OpenSees. A few small tests are used to examine the effects
of (1) vertical ground motions on ratcheting behavior and
collapse performance, and (2) the effect of the linear
transformation method. The addition of vertical ground
motions are found to reduce the predicted ACMR by ~6%, a
relatively minimal effect. The “exact” transformation
(corotational) also has a minimal effect on the collapse
performance, reducing ACMR by ~3%.
The GILD demands are considered in the design of the
archetype buildings. To determine how GILD could affect
buildings designed without consideration for the additional
lateral demands, additional archetypes are created that do not
account for GILD in the proportioning of their members.
Figure 14 shows that the collapse performance can diminish
significantly when GILD is not considered in the design,
showing reductions in ACMR as great as ~50%.
Figure 12. GILD Steel SMF (FEMA, 2018).
Figure 13. GILD Steel OMF (FEMA, 2018).
Conclusion
Based upon this study, there is not a clear need for GILD
irregularities to be addressed in ASCE/SEI 7-16. However, it
is very important that designers do not neglect GILD in the
proportioning of the lateral system. Further study is
recommended to examine how GILD applied over the height
of the building, and other factors such as subduction ground
motions, or other methods for achieving GILD (as have been
tested in other studies) may affect collapse performance.
2018 SEAOC CONVENTION PROCEEDINGS
8
Figure 14. GILD Steel SMF (not designed for GILD),
(FEMA, 2018).
Conclusions and Recommendations
In general, this study has found that the ASCE/SEI 7-16
treatment of vertical irregularities results in satisfactory
collapse performance in code-conforming buildings. None of
the code-conforming irregular buildings examined in this
study presented unacceptable collapse performance.
In the case of Mass Irregularities, it is recommended that
Equivalent Later Force (ELF) method design be allowed.
This recommendation is based upon the favorable collapse
performance of ELF designed mass irregular buildings
relative to Modal Response Spectrum Analysis (MRSA)
buildings, even when the MRSA base shear is scaled to 100%
of the ELF base shear.
Weak and soft stories do not appear to cause a problem; due
predominately to the fact that code conforming weak and soft
stories must still meet drift and strength requirements. Weak
stories in code-conforming buildings may really be thought of
as strong upper story irregularities. These results suggest that
the prohibition of extreme weak story irregularities in SDC D
and the height limitation on extreme weak story irregularities
in SDC B and C may be overly conservative. More study
would be required to comment on the prohibition of weak and
extreme soft story irregularities in SDC E and F.
Increased strong-column/weak-beam (SCWB) ratio above
material standard requirements does generally improve
collapse performance. There is also preliminary evidence
that stepping the SCWB target down along the height of the
building may enhance collapse performance in an economic
manner.
Finally, this study of gravity-induced lateral demand (GILD)
does not indicate that GILD should be incorporated into
ASCE/SEI 7-16 as an irregularity at this time. Though GILD
that is not designed for can have very significant negative
effects on collapse performance. Further study is
recommended to determine the effect of GILD on different
building configurations, sites, and ground motion types.
Acknowledgments
The study is part of a project managed by the Applied
Technology Council (ATC) under FEMA contract HSFE60-
12-D-0242 task order HSFE60-16-J-0223, entitled “ATC-123:
Improving Seismic Design of Buildings with Configuration
Irregularities.” Any opinions contained in this article represent
those of the authors and do not necessarily represent the
opinions of ATC or FEMA. The authors gratefully
acknowledge the ATC-123 working group members, technical
committee, and project review panel for their valuable
feedback and contributions.
References
ACI, 2015, Building Code Requirements for Structural
Concrete (ACI 318-14) and Commentary (ACI
318R-14). American Concrete Institute, ACI
Committee 318.
AISC, 2010a, Specification for Structural Steel Buildings
(ANSI/AISC 341-10). American Institute of Steel
Construction, Chicago, IL.
AISC, 2010b, Specification for Structural Steel Buildings
(ANSI/AISC 360-10). American Institute of Steel
Construction, Chicago, IL.
Altoontash A, 2004, Simulation and damage models for
performance assessment of reinforced concrete
beam-column joints, Doctoral Dissertation, Stanford
University, 2004.
ASCE, 2016, Minimum Design Loads for Buildings and
Other Structures, ASCE Standard ASCE/SEI 7-16,
American Society of Civil Engineers, Reston, VA.
FEMA, 2009, FEMA P695: Quantification of Building
Seismic Performance Factors. Prepared by ATC for
FEMA.
FEMA, 2000, FEMA 355D: State of the Art Report on
Connection Performance. Prepared by SEAOC,
ATC, and CUREE for the SAC Joint Venture
Partnership.
FEMA, 2018, FEMA P-2012. Assessing Seismic Performance
of Buildings with Configuration Irregularities.
Prepared by ATC for FEMA.
DeBock D., Wade K., Cook D., Haselton CB., Valley M., &
Sabol T., 2018, “Quantitative Assessment of Code
2018 SEAOC CONVENTION PROCEEDINGS
9
Provisions for Vertical Building Irregularities in
Frame Buildings”. Eleventh U.S. National
Conference on Earthquake Engineering, Los
Angeles, California, June 2018.
Gupta A & Krawinkler H, 1999, Seismic demands for the
performance evaluation of steel moment resisting
frame structures. Doctoral dissertation, Stanford
University.
Haselton CB, Liel AB, Lange ST, Deierlein GG, 2008, Beam-
column element model calibrated for predicting
flexural response leading to global collapse of RC
frame buildings, Pacific Earthquake Engineering
Research Center, PEER.
Haselton CB, Liel AB, Deierlein GG, Dean BS, & Chou JH,
2010, “Seismic collapse safety of reinforced
concrete buildings. I: Assessment of ductile
moment frames.” J. Struct. Eng., 137(4), 481-491.
Ibarra L F, Medina RA & Krawinkler H., 2005, "Hysteretic
Models that Incorporate Strength and Stiffness
Deterioration." Earthquake Engineering and
Structural Dynamics, 34(12): 1489- 1511.
Lignos DG, & Krawinkler H, 2010, “Deterioration modeling
of steel components in support of collapse prediction
of steel moment frames under earthquake loading.”
J. Struct. Eng., 137(11), 1291-1302.
Lowes LN, Mitra N, Altoontash A, 2004, A Beam-Column
Joint Model for Simulating the Earthquake Response
of Reinforced Concrete Frames, PEER 2003/10,
Pacific Earthquake Engineering Research Center,
University of California, Berkeley, California, 2004.
NIST, 2017, Recommended Modeling Parameters and
Acceptance Criteria for Nonlinear Analysis in
Support of Seismic Evaluation, Retrofit, and Design.
NIST GCR 17-917-45, prepared by the Applied
Technology Council for the National Institute of
Technology and Standards, Gaithersburg, Maryland.
PEER, 2016, OpenSEES (Open System for Earthquake
Engineering Simulation). opensees.berkeley.edu.
Vamvatsikos D & Cornell CA, 2002, “Incremental dynamic
analysis.” Earthquake Engineering & Structural
Dynamics, 31(3), 491-514.