Quality Control Project File
For the Construction of ASME B31.3 Process Piping in the Province of Alberta
ABSA Registration#: AQP-2842 Expiry Date: Sept 10, 2020
Client / Owner:
Project Name:
Project No.:
Job Description:
LSD:
AFE:
Bandit Pipeline Job number:
Bandit Pipeline
PO BOX 12248, Highway 16 West,
LLOYDMINSTER, AB T9V 3C5
Phone (780) 875-8764 / Fax (780) 875-7684
www.banditpipeline.com
Quality Control Project File
For Pipeline construction as per csa z662-15 in the
Province of Alberta
Client / Owner:
Project Name:
Project No.:
Job Description:
LSD:
AFE:
Bandit Pipeline Job number:
PO BOX 12248,
Highway 16 West, LLOYDMINSTER, AB T9V 3C5
Phone (780) 875-8764 Fax (780) 875-7684
www.banditpipeline.com
Revision 3, April 26, 2017
QC Package Progress Checklist
Cover Sheet (Complete with Client/Owner Name, Project Name, Project Number, Job
Description, Location (LSD), AFE#, Bandit Job Number)
New Job Information Sheet (To be completed prior to start of job)
Pre-Job Review Document (To be completed & signed off prior to start of job)
Project Documents (Contract Documents, Scope of Work)
Construction Travel Sheet (To be started & signed off at the start of job and as the
job progresses)
Completion of Construction Forms (AB-81, AB-83 ABSA) (LIB-1001, LIB-1002
TSASK) To be completed at the end of job, signed off by Field QC & Owners Inspector.
Owners Specifications (P&ID’s, Line Lists, General Arrangement Drawings, etc.)
Construction Drawings (As-Built Drawings complete with Bill of Material, Heat Numbers,
Dimensions, Welder Stamp# & Name, Weld Map, X-ray Map, Customer Name, Location, Line Number,Job Number, Test Pressure, Weld Procedure Number, Code of Construction, etc. )
NDE Reports (X-Ray & Mag Particle Reports, NDE Examiners Certifications & Eye
Examination Records)
Welding Documents (Welder’s Log, Welder Stamp & Name, Welder Certificates)
Pressure Test Records (Pressure Test Examination Procedure/Checklist, Pressure Test
Procedure Record, Pressure Gauge, Chart Recorder & Deadweight Calibration Certificates, TestCharts) All Pressure tests must be signed off by the Owners Inspector and the Bandit Representative.
Material Test Reports (MTR’s) (Material Purchase Orders, Material Receiving Inspection
Report, Material Receiving Record, Packing Slips, MTR’s)
Corrective Action Request (Exhibit 18)
Safety Documents
OWNER’S ACCEPTANCE OF TURNOVER PACKAGE
Signing this form indicates acceptance of completion of the following project and receipt of the Turnover Package file including all documentation for the following
project:
BANDIT PIPELINE JOB#
OWNER: Project Name: LSD: AFE#
Owner Representative: (print) ________________________________
Signature: _______________________________________________◄
Please return this completed form to: Attention Quality Control Manager: Bandit Pipeline PO BOX 12248, Highway 16 West, LLOYDMINSTER, AB T9V 3C5 Phone (780) 875-8764 Fax (780) 875-7684 www.banditpipeline.com Scanned Documents may be sent by e-mail to [email protected] or [email protected]
Quality Control System Project File
Table of Contents
Section 1. Construction Plan
Section 2. Contract Documents Including Permits
Section 3. DBM (Design Basis Memorandum)
Section 4. Design Specs / Construction Drawings
Section 5. Material Documents (MTR’s & Shipping Tallies)
Section 6. Welding Documents
Section 7. NDE (Non-Destructive Examination)
Section 8. Pressure Test Records
Section 9. Crossing Records
Section 10. Project Completion
Section 11. Non-Conformance / Corrective Action Reports
Section 12. Safety
Visit us at www.banditenergy.ca
SECTION 1
CONSTRUCTION PLAN
Revised: April-26-17
New Job Information Form
Date: Client Company Name:
Contact Info: Contact Ph.#:
e-mail: Client Project #: Project Name:
Client PO or AFE#: Billing Address:
Inspector Name: Inspector Ph.#:
Inspector e-mail: Contract:
F/A: Other: (Diameter Inch, etc.)
Location(s):
Area:
Contractor: Supervisor: Field QCI:
Pipeline: Field Fab: Shop Fab:
Scope of Work: (Description of Job Requirements)
Please complete this form and send into the office at the start of job. Job Number (Assigned from Office)
A copy of this completed form is required by the QC Department at the start of the job.
Bandit Pipeline Quality Control Manual
Revision No. 5 November 1 2017 Page 38
CONSTRUCTION TRAVEL SHEET
Date Travel Sheet Initiated: Bandit Pipeline Job No.
Owner: Owner Project No.
Drawing No. Rev.No. Date Superseded:
Drawing No. Rev.No. Date Superseded: The "Construction Travel Sheet" must be presented to the Owner's Inspector prior to
the start of construction Initial and Date
HOLD points are indicated with an asterisk. *
No. Function Bandit
Pipeline QCI
Owner's Inspector Date
1
Drawings received for construction, Drawings stamped with "Issued for Construction" stamp.
2 Owner's Inspector notified of assignment of inspection hold points.
3 Owner’s Inspector and QCI formulate plan of construction.
4
Registered Weld Procedures, Q.C. Manual, Procedures, and forms available at site and Job File started.
5
Welders qualified for Procedures and have valid Performance Qualifications Cards. Welder's Log Completed. WPS reviewed with welders.
6
Materials checked against P.O., drawings and specifications. Identification confirmed. Color coding applied.
7
Sample of each Welder's work examined, including root spacing, alignment, cleaning, joint preparation, preheat and electrode control.
8 Piping Lot Size Designation Determined for NDE purposes.
9
Completed Visual Examination of all welds. Welder's I.D. stamped and recorded on drawings.
10
Non-destructive Examination: Reports and radiographs reviewed, signed by Level II or III and accepted by Q.C. Radiographs ID Detailed on reports.
11 Heat treatment verified and recorded on drawings.
12 Each system checked against specifications and drawings before pressure test.
13 All deficiencies recorded and signed off by QCI and Owner's Inspector before test.
14 Pressure Test witnessed. Gauge calibration verified; Gauge # recorded.
15 Each system checked after test. Deficiencies recorded and corrected.
16
Construction Data Reports (Technical Safety Authority of Saskatchewan) LIB-1002 prepared and signed by QCI and Owner's Inspector.
17
Completed Construction Declaration Form LIB-1001) and submitted to Technical Safety Authority of Saskatchewan (if applicable).
18 As-built drawings accepted by Owner (Owner's Inspector).
19 Verify that the Inspector / Company representative has been notified of pressure vessel tie-in.
Signature of QCM Date job completed:
EXHIBIT 4
Bandit Pipeline Quality Control Manual
Revision No. 3 April 26 , 2017
EXHIBIT 3
Contract Review Form Owner: Owner Project No.
Scope of Work: Job No.:
Under The Alberta Safety Codes Act and Regulations, the Owner must have an Authorized Quality System for the scope of work if the Owner assumes responsibility for Quality System functions such as material receiving inspection, material traceability, Welder/Welding Operator supervision and Welders/Welding Operators records, control of NDE on site, witnessing pressure tests, and preparing Quality System records. If the Owner does not have an Authorized Quality System for any of these functions, the Quality Control Manager shall make the Owner aware that all requirements of this Quality System must be met. The Owner should also be made aware that they are responsible for registering the design with ABSA when the volume of any new piping system to be installed exceeds 0.5 cubic metres.
Owner’s Representative:
Date Contracted:
Bandit Pipeline QCM:
Date Accepted:
RESPONSIBLE FOR OWNER CONTRACTOR
Drawings and Specifications
Design Registration
Document Control
Material Procurement
Material Identification and Traceability
Welding
Designated Lot sizes established Lot size:
Non Destructive Examination
Heat Treatment
Measuring and Test Equipment
Pressure Tests
Record Retention
Visit us at www.banditenergy.ca
SECTION 2
CONTRACT DOCUMENTS
INCLUDING PERMITS
Visit us at www.banditenergy.ca
SECTION 3
DBM (DESIGN BASIS MEMORANDUM)
Visit us at www.banditenergy.ca
SECTION 4
DESIGN SPECS
CONSTRUCTION DRAWINGS
LINE LIST
Owner: Project : Job#: Drawing No.
Rev. No.
Line No.
Code
Fluid (Air/Steam, etc)
Design Pressure
kPa
Design Temperature
Degrees C (Max. & Min.)
Test Pressure
kPa
Pipe Mat’l
Spec. & Grade
Corrosion Allowance
mm
Pipe NPS &
Schedule
Flange Material &
Rating
NDE
Visit us at www.banditenergy.ca
SECTION 5
MATERIAL DOCUMENTS
(MTR’s & SHIPPING TALLIES)
MATERIAL ORDER & RECEIVE LIST
JOB#: MATERIAL ORDERED FROM: AFE#: CONTACT NAME: LOCATION: INSPECTOR: DATE: SUPERVISOR:
QTY. DESCRIPTION HEAT# MTR’s
Bandit Pipeline Quality Control Manual
Revision No. 3 April 26, 2017
PURCHASE ORDER FORM
TO: Purchase Order number is to be
recorded below.
P.O.# _____________________________
ADDRESS: JOB NO.
SHIP TO: DATE:
ADDRESS: ORDERED BY:(print)
PLEASE NOTIFY US IF UNABLE TO SHIP COMPLETE ORDER BY DATE SPECIFIED!
Item # Quan Spec
# Gr Sch Size Dimension Description
1
2
3
4
5
6
7
8
9
10 APPROVED BY: (signature)
NOTE:
Mill Certificates (MTR's) (indication that fittings are registered with Technical Safety Authority of Saskatchewan); Canadian Registration Nos. (CRN's), if applicable; pipe heat
numbers and specifications MUST accompany fittings, pipe, and applicable products (valves,
gaskets, etc.)
NO ORDER WILL BE ACCEPTED IF THIS CERTIFICATION IS NOT DELIVERED WITH THE PRODUCT!
EXHIBIT 5
Bandit Pipeline Quality Control Manual
Revision No. 3 April 26, 2017
PURCHASE ORDER RECORD SHEET
DATE P.O. No. ITEMS PURCHASED VENDOR ORDERED BY APPROV'D BY
Note: Mill Test Certificates and Saskatchewan CRNs must be received with all piping materials and valves.
EXHIBIT 6
Bandit Pipeline Quality Control Manual
Revision No. 3 April 26, 2017
Material Receiving Inspection Report
Bandit Pipeline Job File No.:
Material Receiving Report No.:
Owner:
Owner Project / AFE No.:
Purchase Order No.:
Date Shipment Received:
Packing Slip No.:
Material Purchased By: Client Engineer Bandit Pipeline
Vendor / Supplier: MTR's Received with Shipment Yes No Delivering Carrier Freight Bill No.
CRN Documents for Fittings Received with Shipment Yes No
Corrective Action Report Required Yes No Corrective Action Report No.:
Loss/Damage Report Required Yes No Loss/Damage Report No.:
Description of Shipment (Materials) (e.g. Pipe & Fittings)
Comments
Inspected By: Date
Accepted By: Date
EXHIBIT 11
Visit us at www.banditenergy.ca
SECTION 6
WELDING DOCUMENTS
WELDER QUALS
OTHER JOINING RECORDS
(FLEXPIPE; POLY; ETC.)
2018 WELDERS LOG
Revision No. 3 April 26th, 2017
EXHIBIT 8
NAME SYMBOL ASSIGNED ABSA File No.
TSASK WELDER’S
LICENCE No. PROCESS
WELDING PROCEDURE QUALIFIED
TO
MATERIAL "P"
GROUP
FILLER METAL
"F" GROUP
POSITION QUALIFIC.
MAX. DEPOSITED
WELD METAL
MIN. PIPE DIA
PQ CARD
EXPIRY DATE
AB Art Davidson 5 W-06980 Card No. 0493 SMAW / SMAW
BPL-2 BPCSG-1 P1-P11 F3 F4 ALL 6.34-15.79 25 mm Aug 14
2017
SK Art Davidson 5 022960 SMAW / SMAW
BPL-2 BPCSG-1
P1 – 15F P34, P4x F3 F4 ALL 6.35-15.79 25 mm Aug 14
2017
AB Mark Stutt Y W-17320 Card No.3601 SMAW / SMAW BPL-2 P-1 F3 F4 All 0.250”-0.622” 1” July 08
2018
SK Mark Strutt Y 026206 SMAW / SMAW
BPL-2 BPCSG-1
P1 – 15F P34, P4x F3 F4 All 6.35-15.79 25 mm July 08
2018
AB Landon Brosnikoff W-26963 Card No. 3471 SMAW / SMAW BPL-2 P-1 F3 F4 `12- .250”-MAX 1” May 01
2017
SK Landon Brosnikoff 023911 SMAW / SMAW
BPL-2 BPCSG-1
P1 – 15F P34, P4x F3 F4 All(6G) 6.35-MAX 25 mm May 01
2017
Ab Paul Dumanowski P W-14144 Card No. 3513 SMAW / SMAW BPL-2
P1
F3 F4 All .250”-MAX 1” O.D Aug 21
2017
SK Paul Dumanowski P 023005 SMAW / SMAW
BPCSG-1 BPL-2
P1 – 15F P34, P4x F3 F4 All 6.35-MAX 25mm Aug 21
2017
AB Scott Cowan W-24295 Card No.3615 SMAW / SMAW BPL-2 P1 F3 F4 All .250”-.622” 1” O.D Sept 09
2018
SK Scott Cowan 025632 SMAW / SMAW BPL-2 P1 – 15F
P34,P4x F3 F4 All(6G) 6.35-15.79 25mm Sept 09 2018
2018 WELDERS LOG
Revision No. 3 April 26th, 2017
EXHIBIT 8
NAME SYMBOL ASSIGNED
ABSA File No.
TSASK
WELDER’S LICENCE No.
PROCESS WELDING
PROCEDURE QUALIFIED
TO
MATERIAL "P"
GROUP
FILLER METAL
"F" GROUP
POSITION QUALIFIC.
MAX. DEPOSITED
WELD METAL
MIN. PIPE DIA
PQ CARD
EXPIRY DATE
AB
SK Leon McKnight 0242279 SMAW /
SMAW BPL-2 P1-15F P34, P4x F3 F4 All(6G) 6mm-16mm 25mm Mar 16
2018
2018 WELDERS LOG
Revision No. 3 April 26th, 2017
EXHIBIT 8
NAME SYMBOL ASSIGNED
ABSA File No.
TSASK
WELDER’S LICENCE No.
PROCESS WELDING
PROCEDURE QUALIFIED
TO
MATERIAL "P"
GROUP
FILLER METAL
"F" GROUP
POSITION QUALIFIC.
MAX. DEPOSITED
WELD METAL
MIN. PIPE DIA
PQ CARD
EXPIRY DATE
BANDIT PIPELINE12248 Lloydminster,ABPH. (780) 875-8764 CLIENT CLIENT REPRESENTATIVE
PROJECT: PROJECT #:
LOCATION: AREA NAME:
LSD SEC TWP RGE W____M DATE
This procedure for end-to-end joints for pipe with the same diameter and wall thickness1
2
3
4
5
6
7
8
9
10
Owner's Representative (Print Name): ___________________________
Owner's Representative:____________________________________________◄
Date of Contract:
Fusion equipment may not be explosion proof; therefore take all necessary precautions if fusing in a combustable atmosphere.
Clean pipe ends to remove all dirt and contaminants.
Keep heating tool surfaces clean throughout process using clean, dry, non-synthetic cloths or paper
Heat the heating tool / iron to manufacturers specified minimum and maximum temperature, ensuring two points of the heating tool / iron is not greater than 20° F on equipment for pipe smaller than 18" in pipe larger than 18".
When fusing, shield joining equipment from inclement weather and winds to help ensure temperature
Place pipe ends in fusion machine and face down to stops.
Check hi/low alignment: adjust; re-face.
Heat pipe ends to manufacturers recommended heater face surface temperature; use contact for a uniformly sized bead around entire pipe on both ends. Use the following table for guidelines.
Pipe Size Bead Width
1 1/4" to 3" About 1/16"
3" to 6" 1/16" to 1/8"
6" to 8" 1/8" to 3/16"
8" and larger 3/16" to 1/4"
Fuse pipe using enough pressure to roll melt swell bead over to pipe surface. Hold this pressure for specifications) or about 30 seconds per inch of pipe diameter (eg: 4" pipe cool for 120 seconds [2
Cool for an additional 3 to 10 minutes. The fusion may then be removed from the machine. Allow an manufacturer's specifications) cooling time prior to any type of rough handling or testing. You must (the larger the pipe, the longer the cooling time).
Inspect the fusion. Double bead width = 2 to 2 1/2 times bead height; uniform bead size and shape
BANDIT PIPELINE12248 Lloydminster,ABPH. (780) 875-8764 CLIENT CLIENT REPRESENTATIVE
PROJECT: PROJECT #:
LOCATION: AREA NAME:
LSD SEC TWP RGE W____M DATE
Pipe Manufacturer Type of Pipe
Pipe Manufacturer'r Recommeded Fusion Parameters Provided ? Copy Attached ?
SDR Pipe Designation Code:
Fusion Equipment (Type & Manufacturer Fusion Technician
Ambient Temperature Wind Speed Precipitation
Joint # Heater Plate Temp
Drag Pressure
Hydraulic Pressre
Fusion Pressure
Heater Plate Hold Time
Clamped Cooling
Time
Visual Bead Accept / Reject
Soak Time Remarks
Yes / No Yes / No
Fusion Joint Tested Pass / Fail
FIELD OPERATIONS
Form #: Revision #: Revision Date: PAGE:
14-0010 10 Dec. 7, 2016 1 of 3
Daily Field Report – North America
Upon Completion email back to the Oil & Gas Company as well as Shawcor Canada - [email protected]
US - [email protected]
Customer Information Customer Name Date (m/ft) Installed Job Location FP Sales Order # Site Weather LSD Customer Rep. Pictures Taken YES NO Produced Fluid Contractor Sketch Provided YES NO Application (Flow Line, Transfer, SWD, etc.) Crimp Kit # Fitting Protection & Checklist Reminder Comments Denso Tape Fittings Accept Decline Any kinks have been repaired correctly YES NO Polyken Tape Fittings Accept Decline All ends of pipe night capped YES NO Installed Anode Kit Accept Decline Equip. Operates @ 9000 PSI YES NO Educated on Pigging Tags YES NO Equip. Operates @ 8500 PSI YES NO Tracer Wire Used YES NO Surface Lines are padded and secured YES NO Fitting Information
# Fitting Type & Serial #
GPS/LSD (Format or Unit
Used) Wetness Checked
Fittings Inspected
(no damage, vent hole, correct size)
Pipe Insertion Distance (inches)
Crimp Locations (inches)
Pipe End
Denso Pasted
Clamp min. of 4”
from sleeve
end
Run #, (m) Mark
Pipe Desc.
Run #, (m) Mark
Pipe Desc.
Name of Installation Tech Signature Training # Expiry Date
Name of Installation Tech Signature Training # Expiry Date
Name of Installation Tech Signature Training # Expiry Date
Name of Installation Tech Signature Training # Expiry Date
Name of Installation Tech Signature Training # Expiry Date GPS GPS Coordinates are not exact, they are usually between 3-15m/10-49ftand fi
Comments:
FIELD OPERATIONS
Form #: Revision #: Revision Date: PAGE:
14-0010 10 Dec. 7, 2016 2 of 3
Daily Field Report – North America
Upon Completion email back to the Oil & Gas Company as well as Shawcor Canada - [email protected]
US - [email protected]
# Fitting Type & Serial # GPS/LSD Wetness
Checked
Fittings Inspected
(no damage, vent hole, correct size)
Pipe Insertion Distance (inches)
Crimp Locations (inches)
Pipe End
Denso Pasted
Clamp min. of 4”
from sleeve
end
Run #, (m) Mark
Pipe Desc.
Run #, (m) Mark
Pipe Desc.
Name of Installation Tech Signature Training # Expiry Date
Name of Installation Tech Signature Training # Expiry Date
Name of Installation Tech Signature Training # Expiry Date
Name of Installation Tech Signature Training # Expiry Date
Name of Installation Tech Signature Training # Expiry Date
Name of Installation Tech Signature Training # Expiry Date
Name of Installation Tech Signature Training # Expiry Date
Name of Installation Tech Signature Training # Expiry Date GPS GPS Coordinates are not exact, they are usually between 3-15m/10-49ftand
Comments:
FIELD OPERATIONS
Form #: Revision #: Revision Date: PAGE:
14-0010 10 Dec. 7, 2016 3 of 3
Daily Field Report – North America
Upon Completion email back to the Oil & Gas Company as well as Shawcor Canada - [email protected]
US - [email protected]
Field Pictures and Sketch (Tank battery, main pumping station, equipment, adjacent or crossing lines, roads, etc.)
Visit us at www.banditenergy.ca
SECTION 7
NDE
(NON-DESTRUCTIVE EXAMINATION)
Bandit Pipeline Quality Control Manual
Revision No. 3 April 26, 2017
NONDESTRUCTIVE EXAMINER’S LOG
NAME OF COMPANY COMPLY WITH
REQUIREMENTS OF (CGSB or ASNT-TC-1A)
APPOINTED TO PERFORM RT (RADIOGRAPHIC) UT (ULTRASONIC)
PT (LIQUID PENETRANT) MT (MAGNETIC
PARTICLE)
LEVEL III EXAMINER CERT # EXPIRY LEVEL II
EXAMINER CERT # EXPIRY
EXHIBIT 23
X-RAY LOG / REQUEST JOB #: PURCHASE ORDER #: AFE #: LOCATION: DESCRIPTION: REQUESTED BY: NDE CONTRACTOR:
DATE X-RAY # LINE # / SPOOL # SIZE / SCH. WELDER I.D. CODE PROCEDURE
Visit us at www.banditenergy.ca
SECTION 8
PRESSURE TEST RECORDS
Pressure Test Dead Weight Pressure Monitoring Log
Date: From: To: M.O.P: Min. Test Pressure: Max. Test Pressure:
Test Medium: Duration: Contractor: Material: Grade: Spec:
O.D: Wall Thickness: Coating: Length: Volume: Inspector:
License #: Approval #: Line #:
Monitor and Record Pressure (verify test charts against dead weight frequently)
Time: Pressure: Initials: Time: Pressure: Initials:
Bandit Pipeline Quality Control Manual
Revision No. 3 April 26, 2017
PRESSURE TEST EXAMINATION PROCEDURE / CHECKLIST
PRESSURE TEST EXAMINATION GUIDE Q.C. INSPECTOR
OWNER’S INSPECTOR
DATE
1 Test area posted and all unnecessary personnel removed from test area
2 All involved personnel properly trained, qualified, aware of hazards involved
3 All punch list items corrected
4 Pressure test specifications confirmed as per “Approved for Construction” drawings
5 All items subject to damage removed or isolated (control valves, safety valves, instruments, expansion joints, etc)
6 Equipment with internals (i.e. filters) isolated or removed
7 Vents and drains correctly installed
8 Open and Closed positions of all valves verified
9 Shipping bars in place (bellows)
10 Piping bolted to pilings: Hanger stops in place
11 Source of test medium verified: appropriate for temperature
12 Properly calibrated gauges and recorders
PRESSURE TEST COMPLETION Q.C. INSPECTOR
OWNER’S INSPECTOR
DATE
1 Examination for leaks during test
2 Specified test pressure reached and maintained for specified time
3 All temporary blinds (blanks) removed
4 Temporary gaskets exchanged for correct gaskets
5 Shipping bars removed from bellows
6 Spring hanger stops removed: cold setting checked
7 Safety valves: “UV” or “V” symbol and correct set pressure and capacity installed
8 Safety valve vents correct size; adequately supported; drain holes and or weather hoods installed
9 Screens for pumps and compressors installed (initial start-up and permanent screens)
EXHIBIT 26
Bandit Pipeline Quality Control Manual
Revision No. 5 November 1 2017 Page 46
PRESSURE TEST PROCEDURE RECORD
Client
Job #
Date:
Pipeline Designation Number(s):
Item Description for Testing:
Code (ASME B31.3 / CSA Z662 / Other):
Type of Pressure Testing: Hydro ☐ Pneumatic ☐ Other ☐ Type: Test Medium Used: Temperature for Medium: Design Pressure:
Operating Pressure Test Pressure
Design Temperature Operating Temperature Test Temperature Duration of Pressurizing:
As Required for Visual Inspection
Or Actual
Start (time) Pressure Hold Release (time) Start (time) Pressure Hold Release (time) Examination Procedure: (Check One) Visual ☐ Other ☐
Pressure Gauge I.D. # Range
Last Calibration Date:
Pressure Gauge I.D. # Range
Last Calibration Date:
Dead Weight I.D. # Range
Last Calibration Date:
*Dead Weight Reading* (RECORD READINGS)
THIS CERTIFIES THAT THE ABOVE STATEMENTS ARE CORRECT AND THE EQUIPMENT DESCRIBED WAS FREE OF LEAKS
Date Time Pressure Results of Pressure Test (circle one) Accept Reject
Test Witnessed and Accepted By:
Bandit Pipeline Print Name:
Signature:
Date:
Test Witnessed and Accepted By:
Owner's Inspector Print Name:
Signature:
Date:
Recorded By:
EXHIBIT 27
Visit us at www.banditenergy.ca
SECTION 9
CROSSING RECORDS
BANDIT PIPELINE12248 Lloydminster,ABPH. (780)875-8764
Exhibit BP:IM-29NAME OF EXISTING FACILITY OWNER CROSSING AGREEMENT NUMBER.
PROJECT: PROJECT #:LOCATION: AREA NAME:
LSD SEC TWP RGE W____MTYPE OF FACILITY: (Check One )
PIPELINE NROADRAIL ROADWATER COURSEDATA CABLEPOWER CABLEOTHER: ( Specify )
DAMAGE REPAIR SATISFACTORY:
REGULATORY AGENCIES NOTIFIED OF DAMAGE:
INDICATE APPROXIMATE LOCATION ON PLAN "A"
R.R. DEPTH EXISTING DEPTH NEW ROAD
RIVER BED DEPTH NEW PL DEPTH EXISTING
M DEPTH
LINE
LINE SIZE CASED WT GRADE UNCASED
PIPELINE - ROW ROAD, RR X-ING, RIVER CROSSING R/W
INDICATE:B&C 1) DEPTH TO EXISTING LINE ( ON ELEVATION )2) DEPTH OF NEW LINE ABOVE OR BELOW EXISTING LINE. ( ON ELEVATION )3) CATHODIC PROTECTION INSTALLED: YES NO IF YES, WHAT TYPE?
IF POSSIBLE PROVIDE PHOTOGRAPH AND ATTACH TO THIS REPORTOWNER OF FOREIN OR EXISTING FACILITY: SIZE AND CONDITION OF EXISTING FACILITY:
( NEW ) OIL, GAS, WATER, ETC. CONTRACTOR DOING WORK:
PREPAIRED BY: ( PRINT ) DATE COMPLETED: APPROVAL: ( SIGN )OWNER:FOREIGN:
TYPE OF DAMAGE:
EXISTING
EXISTING
BANDIT PIPELINE12248 Lloydminster,ABPH. (780)875-8764NAME OF EXISTING FACILITY OWNER CROSSING AGREEMENT NUMBER.
PROJECT: PROJECT #:LOCATION: AREA NAME:
LSD SEC TWP RGE W____MTYPE OF FACILITY: (Check One )
PIPELINE NROADRAIL ROADWATER COURSEDATA CABLEPOWER CABLEOTHER: ( Specify )
DAMAGE REPAIR SATISFACTORY:
REGULATORY AGENCIES NOTIFIED OF DAMAGE:
INDICATE APPROXIMATE LOCATION ON PLAN "A"
R.R. DEPTH EXISTING DEPTH NEW ROAD
RIVER BED DEPTH NEW PL DEPTH EXISTING
M DEPTH
LINE
LINE SIZE CASED WT GRADE UNCASED
PIPELINE - ROW ROAD, RR X-ING, RIVER CROSSING R/W
INDICATE:B&C 1) DEPTH TO EXISTING LINE ( ON ELEVATION )2) DEPTH OF NEW LINE ABOVE OR BELOW EXISTING LINE. ( ON ELEVATION )3) CATHODIC PROTECTION INSTALLED: YES NO IF YES, WHAT TYPE?
IF POSSIBLE PROVIDE PHOTOGRAPH AND ATTACH TO THIS REPORT
OWNER OF FOREIN OR EXISTING FACILITY: SIZE AND CONDITION OF EXISTING FACILITY:
( NEW ) OIL, GAS, WATER, ETC. CONTRACTOR DOING WORK:
PREPAIRED BY: ( PRINT ) DATE COMPLETED: APPROVAL: ( SIGN )OWNER:FOREIGN:
TYPE OF DAMAGE:
EXISTING
EXISTING
Visit us at www.banditenergy.ca
SECTION 10
PROJECT COMPLETION DOCUMENTS
Form# BA-2017-02
COMPLETION OF PIPELINE CONSTRUCTION
_____________DECLARATION & CERTIFICATE OF INSPECTION _______ NOTE: This declaration shall be completed and signed by the person(s) responsible, in whole or in part, for the construction, installation, testing and inspection of the pipeline system described below. All piping on this project has been constructed inspected and tested in accordance with CSA Z662 Oil and Gas Pipeline Systems Code and is not under ABSA or TSASK jurisdiction.
1 Owner of Pipeline:
2 Engineer or Contractor:
(Name and Address)
3 Type of Pipeline:
4 Location of Pipeline: (Sec, TWP, Rge)
5 Description of Pipeline System(s)
6 Bandit Pipeline Job Number: 7 Owner’s AFE#
STATEMENT OF COMPLIANCE I, the undersigned, employed by Bandit Pipeline, declare that the described pipeline system complies in all respects with the regulations for construction, installation, testing and inspection and that all applicable test data reports have been delivered to the owner.
(Signature) (Print Name) (Title) (Date)
Bandit Pipeline Box 12248, Lloydminster, AB T9V 3C5 (Company) (Address) (City, Postal Code)
CERTIFICATE OF INSPECTION I, the undersigned, employed by _ ___ have verified that all required
examination and testing has been completed, and have inspected the piping system described above to the extent necessary to be satisfied that it conforms to all applicable examination requirements of the Code of Construction and of the engineering design, and state that, to the best of my knowledge and belief, the contractor has constructed this pipeline system in accordance with CSA Z662 (Latest
Edition). By signing this certificate, neither the inspector nor his or her employer makes any warranty, expressed or implied, concerning the piping described in this report. Furthermore, neither the
inspector nor his or her employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this pipeline inspection.
Date: Owner’s Inspector Name (please print) Owner’s Inspector Signature:
AB-81 2005-03
COMPLETION OF CONSTRUCTION
DECLARATION
NOTE: This declaration shall be completed and signed by the person
responsible, in whole or in part, for the construction, installation, testing and inspection of the pressure piping system and forwarded to the Administrator/Chief Inspector.
(1) Owner of Plant: .
(Name and Address) (2) Engineer or Contractor: (Name and Address) (3) Type of Plant: (4) Location of Plant:
(Sec, TWP, Rge) (5) Description of Pressure Piping System(s): . STATEMENT OF COMPLIANCE
I, the undersigned, declare that the described pressure piping system, approved under design registration number , complies in all respects with the regulations for construction, installation, testing and inspection and that all applicable pressure piping test data reports have been delivered to the owner.
(Signature) (Print Name) (Title) (Date)
Bandit Pipeline Box 12248, Lloydminster, AB T9V 3C5 (Company) (Address) (City, Postal Code)
The information you provide is necessary only for the administration of the programs as required by the Alberta Safety Codes Act and Regulations in the Boiler Discipline.
AB-83 2011-09
Constructed by: Bandit Pipeline Owner’s Job # Page 1 of 2
PRESSURE PIPING CONSTRUCTION AND TEST DATA REPORT
In accordance with the provisions of the PESR Section 31(1)
Shop Construction ; Field Construction ; Final Data Report ; Partial Data Report (from one ABSA- authorized Contractor to another
ABSA- authorized Contractor).
Complete both sides of this Form 1. Constructed By: Bandit Pipeline Owner’s Job No:
(Name of ABSA authorized primary contractor or subcontractor) Box 12248, Lloydminster AB T9V 3C5
(Address) Certificate of Authorization Permit No. AQP-2842 Expiry Date: Sept 10, 2020 2. Constructed For:
(Name of primary contractor if different from above)
(Address)
Certificate of Authorization Permit No. AQP- Expiry Date: (Required when the primary contractor undertakes some/all of the quality functions, e.g., NDE, PWHT, Tie-in, fabrication, hydro test, final assembly etc.)
3. Owner: (Name and address)
(Location of installation)
Certificate of Authorization Permit No. AQP- Expiry Date: (Required when the owner undertakes some/all of the quality functions, e.g., NDE, PWHT, Tie-in, fabrication, hydro test, final assembly etc.)
4. Piping Design Alberta Registration No.: PP- (Required if aggregate piping volume is over 0.5m3) 5. Design Responsibility: Owner ; Contractor 6. WP No.: WP- ; Company: Bandit Pipeline Owner’s WP No. (If used): WP-
(Alberta Registration No.) (Alberta Registration No.) WPS No(s). used: ; Owner’s WPS No(s). (If used):
7. Code: ASME B31.1 Non Boiler External Piping ; ASME B31.1 Boiler External Piping ; B31.5 ; B31.9 ; CSA Z662 Steam Pipelines ; ASME B31.3 - Service Category: Normal , D , M , High Pressure ; Severe Cyclic Condition High Purity
Drawing No. Rev. No. Line No.
Fluid (Air/Stm.
Etc.)
Des. Press. kPa
Des. Temp.0C (Max. &
Min.)
Pressure Test kPa
Test Medium
Pipe Mat'l Spec. & Grade
C.A. mm
Pipe NPS &
Schedule
Flange Material &
Rating
PWHT/ Preheat
Temp. 0C NDE
AB-83 2011-09
Constructed by: Bandit Pipeline Owner’s Job # Page 2 of 2
Partial Data Reports certified by sub-contractors are listed below and attached to this Data Report
No. Line No. Spool No. Dwg. No. (with Rev. No.)
Sub-contractor (Name)
AQP No. (if from Alberta)
Expiry (if from Alberta)
Remarks: For partial data report provide information about the code work that was not completed by the subcontractor (e.g., hydrostatic test, PWHT etc.). For final data report provide information about the code work that was not completed by subcontractors and subsequently completed by the primary contractor (e.g., hydrostatic test of entire assembly, PWHT etc.)
Endorse certificate ‘A’ or ‘B’ A. CERTIFICATE OF COMPLIANCE
Signed by the subcontractor when supplying this certificate as a
Partial Data Report
We certify that the statements in this Data Report are correct and that materials, construction and workmanship of the piping fabrication conform to the registered quality system and the applicable Piping code(s). Date: Contractor
Print Authorized Representative’s Name Signature
This certificate is not valid unless it forms part of a Final Data Report signed by Primary Contractor
B. CERTIFICATE OF COMPLIANCE Signed by the primary contractor when supplying this certificate as a
Final Data Report
We certify that the statements in this Data Report are correct and that piping job no. described in this Data Report was constructed in accordance with the Province of Alberta Safety Codes Act and Regulations, and applicable ASME Piping Code(s). Date: Bandit Pipeline Contractor
Print Authorized Representative’s Name Signature
CERTIFICATE OF INSPECTION I, the undersigned, employed by have verified that all required examination and testing has been completed, and inspected the piping described in this construction data report to the extent necessary to be satisfied that it conforms to all applicable examination requirements of the Code and of the engineering design, and state that, to the best of my knowledge and belief, the contractor has constructed this piping in accordance with the Alberta Safety Codes Act and Regulations. By signing this certificate neither the inspector nor his or her employer makes any warranty, expressed or implied, concerning the piping described in this construction data report. Furthermore, neither the inspector nor his or her employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. Date: Date:
Owner’s Inspector Name (please print) ABSA Safety Codes Officer (please print) (BOILER EXTERNAL PIPING ONLY)
Owner’s Inspector Signature: ABSA Safety Codes Officer’s Signature
Current version of this Form may be obtained from www.absa.ca
Visit us at www.banditenergy.ca
SECTION 11
NON-CONFORMANCE
& CORRECTIVE ACTION REPORTS
Bandit Pipeline Quality Control Manual
Revision No. 5 November 1 2017 Page 50
CORRECTIVE ACTION REQUEST
Certificate of Authorization Permit # AQP-2842 Corrective Action Request Report (CAR) #_______
Date: Location: Non-conformance Identified (describe): Non-conformance identified by whom: Corrective Action Taken Immediate Action: Completion Date: Signature: Action to Prevent Recurrence: Completion Date: Signature: Verification of Corrective Action: Verification by: Results (circle one): Acceptable Not Acceptable Date: CAR Closed Date: Signature:
EXHIBIT 14
Visit us at www.banditenergy.ca
SECTION 12
SAFETY
JOB#
Quality Control System Project File
JOB#
Client / Owner: Bandit Pipeline
Project Name:
Project No.:
Job Description:
LSD:
AFE: