2
Thank you for purchasing Coolmay QM3G-FH HMI PLC All-in-One products. This manual mainly explains the product features, specifications and wiring methods. Detailed PLC programming, please refer to <Coolmay QM3G-FH HMI PLC All-in-One Programming Manual>. Detailed HMI part, refer to <Coolmay TK series HMI Programming Manual>. Product Details 1 Series QM3G: QM3G-FH series 2 HMI 43 : 4.3inch 50 : 5inch 70 /70HD/70K : 7inch t 100 : 10inch . . FH FH FH FH FH Naming rules QM3G 43FH Graph 1 Mounting dimension QM3G-100FH QM3G-43FH QM3G-70KFH Electric Design Product structure RUN:PLC operating indicator COM:flash when PLC communicates with HMI QM3G-43FH Graph3 Graph 6 QM3G-70KFH Hardware Interface Mounting dimension Mechanical Design Input ON Input OFF Filter function High-speed counting Digital relay output index Max current Circuit power voltage Circuit insulation On response time Mechanical life without load Electric life with rated load 2A/point, 4A/4 point COM, 5A/8 point COM, 5A/12 point COM Below DC30V/ Below AC220V Relay mechanical insulation Approx. 10ms 10million times 300,000 times Digital transistor (MOS) output index Max current Circuit power voltage Circuit insulation Isolated voltage (power-terminal) On response time High-speed out put frequency MOS tube: 2A/point, 4A/4 point COM, 5A/12 point COM; MT: 05A/point, 0.8A/4 point COM, 1.6A/12 point COM DC24V Optocoupler insulation 1500VAC High-speed output10μsothers0.5ms Analog input indexes Input signal Response time Analog input Precision PT100/PT1000/thermocouple/NTC/0-10V/0-5V/-10~10V/-5~5V/0-20mA/4-20mA/ 1scanning cycle 0-16 channels 12 bit Analog output indexes Output signal Analog output Precision 0-5V/0-10V/-10~10V/-5~5V/0-20mA/4-20mA/customizations 0-8 channels 12 bit External port com port Environment Operating temperature Relative humidity Storage temperature Vibrational frequency 0°C~50°C 5%~95%RH -20°C~70°C 10-57Hzamplitude 0.035mm; 57Hz-150Hz,acceleration4.9m/s² (10 times each on X, Y, Z, total 80 minutes each) Basic parameter Specifications of HMI PLC All-in-One QM3G-43FH/50 -16MR FH QM3G FH FH 44 -70K /100 - MT digital points analog points (optional) COM port(optional) High-speed counting high speed pulse DI DO AD DA HMI single phase AB phase ABZ phase output 24 20 43FH/50FHMT is MOS output. 70FH/70HD/70KFH/100FHMT: Y0-Y3 is MOS transistor output, Y4-Y35 is transistor output; Chart 1basic parameter QM3G-FH HMI PLC All-in-One User Manual Chart 3mounting dimension Model Max digital points Mounting dimension Boundary dimension W*H*D(mm) A(mm) B(mm) QM3G-43FH QM3G FH -70 /HD 12DI DO 12 24DI20DO 120 192 94 138 134*102*34 200*146*36 Four side mounting holes Terminal block of power supply Terminal block of DO Terminal block of DI PWR:power indicator HMI programming port PLC programming RS232/RS485 PLC operating switch RUN/STOP analog output HMI RS232/ RS485/ PLC- CAN LCD Ethernet port optional 12 12 DI DO 143 86 151*96*36 QM3G-50FH 485P/232H - 1P - 1C1 A0 V 2DA 4AD RT M 24 - - - - - - Graph4 QM3G-50FH Chart 2 Product structure Max analog points 4AI2AO 12A8AO 4AI2AO Electric parameter Input voltage DC24V Digital input indexes Isolation mode Input impedance Photocoupling High-speed input 3.3KΩ Common input 4.3Ω Chart 2: electric parameter Continue to above tableWiring specifications of terminals: 22-14AWG wire. The terminals of this serial are all pluggable ones. Definition of communication interface : Refer to Chart 4:Pin definition QM3G- FH FH 70K /100 - M 60 T 30 Y20 COM4 Y17 Y16 Y15 Y14 COM3 Y13 Y12 Y11 Y10 COM2 Y07 Y06 Y05 Y04 COM1 Y03 Y02 Y01 Y00 COM0 X23 X22 X21 X20 X17 X16 X15 X14 X13 X12 X11 X10 COM X07 X06 X05 X04 X03 X02 X01 X00 COM X24 X26 X25 X27 Y21 Y22 Y23 AD1 AD2 AD3 AD4 GND DA0 DA1 X30 X31 X32 X33 X34 X35 GND1 Y35 Y34 Y33 Y32 Y31 Y27 COM5 Y26 Y25 Y24 Y30 AD5 AD6 AD7 AD8 AD9 AD10 AD12 AD13 AD14 AD15 AD0 AD1 AD2 AD3 AD4 AD11 GND GND1 DA0 DA1 DA3 DA7 DA4 DA5 DA6 DA2 AD0 QM3G-70KFH-44M-16AD8DA QM3G-70KFH-60M-5AD2DA 12 8 High-speed input: current>5.8mA/24V Common input: current >9.9mA/24V High-speed input: current<4.5mA/19V Common input: current >4mA/17V Input level Passive NPN, common terminal isolation, S/S connected to 24V+ Output level Low level NPN, COM connects negative Output level Dry contact, COM connects positive or negative Normally 8 channelsY0-Y3 is100KHzY4-Y7 is 10KHz The total high-speed counting and pulse can not exceed 480KHz. Normally single phase 6 channels 60KHz; Refer to " Chart 1 : basic parameter " 13 14 WIFI optional 15 PLC USB programming port 16 1 10 11 9 4 3 2 5 7 8 14 12 15 16 A:485+ B:485 - Chart 9 PLC485 port Chart 8 COM1/COM2 analog input FG:cover protection GND 0V24V negative 24V24V positive QM3G FH - - MR 70 /HD 24 QM3G-43 /50 FH FH-24MT/R Normally 8 channels: Y0-Y3is 100KHzY4-Y7 10KHz is 35.6 163 5 226 194 275 36 102 120 34 151 96 36 86 143 Graph7 QM3G-100FH X23 X22 X21 X20 COM X16 X15 X14 X13 X12 X11 X10 COM X07 X06 X05 X04 X03 X02 X01 X00 COM Y23 Y22 Y21 Y20 Y17 Y16 Y15 Y14 COM3 Y13 Y12 Y11 Y10 COM2 Y07 Y06 Y05 Y04 COM1 Y03 Y02 Y01 Y00 COM0 AD1 AD2 AD3 AD4 GND DA0 DA1 X17 X27 X26 X25 X24 X30 X31 X32 X33 X34 X35 GND1 Y35 Y34 Y33 Y32 Y31 Y27 COM5 Y26 Y25 Y24 Y30 AD5 AD6 AD7 AD8 AD9 AD10 AD12 AD13 AD14 AD15 AD0 AD1 AD2 AD3 AD4 AD11 GND GND1 DA0 DA1 DA3 DA7 DA4 DA5 DA6 DA2 AD0 QM3G-100KH-44M-16AD8DA QM3G-100KH-60M-5AD2DA COM4 normally AB phase 2 channels 60KHz +1 hannel 10KHz; normally ABZ phase 2 channels 60KHz; customizations 4 5 Note:A/B,A1/B1 Please refer to the product silkscreen for special model interface identification. MR is relay outputMRT is mix outputOptional according to customer requirements 134 94 217 154 262 180 QM3G-50FH QM3G-70FH/HD 146 200 36 192 138 10 11 3 2 16 14 7 9 5 1 4 8 13 6 Graph5 QM3G-70FH/HD 12 12 8 8 More specs can be customized if bulk order QM3G FH -100 30DI3 DO 0 262 180 275*194*36 16AI AO 8 QM3G FH -70K 30DI3 DO 0 217 154 226*163*35.6 16AI AO 8 QM3G FH - MR 70 /HD-40 QM3G FH -70 /100FH-24MR 12 12 24 16 12 12 QM3G FH FH 38 -70K /100 - MR 20 18 QM3G FH - - MT 70 /HD 44 24 20 Normally 6 channels single phase 60KHz or AB(Z) channel 2 channels 60KHz+AB phaze 1 channel 10KHz QM3G- 43FH / 50FH come with 1XRS232 on HMI 1 RS485 or 2 Rs485 can be optional on PLC (1 485 port is changed from default 232port) QM3G-43FH/50FH can be added 1XWIFIon PLC (cannot coexist with default 232 on PLC) QM3G FH FH 48 -70K /100 - MR 24 24 QM3G-43FH/50FH All-in-One COM Port Description PIN# PLC-485-2 serial port3 PLC-485-1 serial port 2 PLC-232 serial port3 HMI-232 optional default 8 9 (485+) (485-) (RXD) (TXD) (GND) (GND) (TXD) (RXD) Optional, cannot coexist with default 232 and WIFI (optional) 1 6 2 3 5 4 7 COM1 Db9 port terminal 485 PLC-WIFI Optional, cannot coexist with default 232 and 485-2 (optional) Chart 4: Pin definition DA0 DA1 GND AD0 AD1 AD2 AD3 GND B A Y13 Y12 Y11 Y10 Y07 Y06 Y05 Y04 Y03 Y02 Y01 Y00 COM X13 X12 X11 X10 X07 X06 X05 X04 X03 X02 X01 X00 COM Y13 Y12 Y11 Y10 Y07 Y06 Y05 Y04 Y03 Y02 Y01 Y00 COM DA0 DA1 GND AD0 AD1 AD2 AD3 GND B A X13 X12 X11 X10 X07 X06 X05 X04 X03 X02 X01 X00 COM Y21 Y20 Y17 Y16 Y15 Y14 COM3 Y13 Y12 Y11 Y10 COM2 Y07 Y06 Y05 Y04 COM1 Y03 Y02 Y01 Y00 COM0 X23 X22 X21 X20 X17 X16 X15 X14 X13 X12 X11 X10 COM X07 X06 X05 X04 X03 X02 X01 X00 COM X24 X25 X26 X27 AD07 AD05 AD00 GND GND DA00 DA06 A B Y22 Y23 AD06 AD04 AD03 AD02 AD01 DA01 DA02 DA03 DA04 DA05 DA07 QM3G-70KFH QM3G-43FH QM3G-50FH 6 13 1 4 17 10 3 10 11 12 1 4 2 8 5 9 7 2 8 14 7 5 15 9 16 16 3 QM3G-100FH QM3G-70 /HD FH is RS48517 17 11 14 12 18 PLC/HMI RS485 18 43FH/50 /70 /70HD FH FH 70K /100 Type-B port FH FH is 43 /50 /70 /70HD FH FH FH 70K /100 mini USB port FH FH is 15 19 WiFi switch optional 19 19 19 19 is Type-C port; Is Type-C port; 14 7 and 10inch can be added CAN/Etheret/Wi Fi(Occupies the default port 232) on PLC 7 and 10 inch come with 1X RS232 on HMI and 1X485 is optional Acceleration and deceleration are independent. High-speed counting and pulse can't over 480KHz. default 8 6 The features are as below. 1. PLC compatible with FX3G/FX3U/FX3S PLC. It operate fast. 2. The digital points are 30 inputs and 30 outputs at most. 3. Support several high-speed counting and high-speed pulse. 4. 32K steps program capacity,32K power-off retentive registers,support interrupt,linear and circular interpolation,PID self-adjusting. 5. 6. 7 More models are supported to customize if bulk order. Super functions. Highly integration. The digital output can be transistor,relay or mixed output.Analog can reach up to 16 input and 8 output. It has 2 PLC COM port (Rs232 and USB Port), 1 downloading port on HMI. Acceleration and deceleration are independent. Special encryption.Set password as 12345678 to thoroughly prevent reading data.(PLC only supports 8-bit password encryption) PLC is compatible with programming software GX Developer8.86Q and GX Works2, and HMI is mView software. . The network module can be selected according to customer requirements to realize remote control. The total high-speed counting and pulse can not exceed 480KHz. ④⑤ 4. Module type M: Main module of universal controller 5. Digital output (DO) type R: relayT: trnasistor(MOS tube)RT: both relay and transistor 6. Analog input (AD) 4 channels for 43FH/50FH12 for 70FH/HD 16 for 70KFH/100FH 7. Analog output (DA) 2 channels for 43FH/50FH8 for 70FH/70HD/70KFH/100FH 8. AI type E: Thermocouple E(can be customized as type K T, S or J supports negative temperature) PTPT100 PT1000PT1000 NTC thermistor 10K, 50K, 100K A0: 0-20mA A4: 4-20mA V5: 0-5V V: 0-10V V5_:-5V~5V V_:-10~10V (only 7 and 10 inch support V5_ and V_) 9. AO type A0: 0-20mA A4: 4-20mA V5: 0-5V V: 0-10V V5_:-5V~5V V_:-10~10V(only 7 inch and 10 inch support negative voltage covers 2 channels) 10. C1 singe phase high-speed countingC2 AB phase countingC3 ABZ phase counting; Normally support 6 single phase 60KHz , or 2 AB ( Z ) 60KHz + 1 AB 10KHz 11. P0:10KHz high speed pulse;P:100KHz high speed pulse;Normally 8 channels,Y0-Y3 is 100KHz,Y4-Y7 is 10KHz; That high speed counting plus high speed pulse must be withi 480KHz 12. com port optional refers to Chart 1'basic parameter’ 3. Digital input and output (DI/DO) 16: 8DI 8DO 24: 12DI 12DO 38: 20DI 18DO 44: 24DI 20 DO 60: 30DI 30DO QM3G-70KFH/100FH-58MR With filter function, the filter time can be set among 0-60ms,defaulted as 10ms 30 28 30 2 16 8 2 PLC 13 6 6 13 Automation Expert 6 13 1 4 10 11 3 2 8 5 7 9 17 16 14 3 4 5 6 7 8 9 10 11 12 1 2

QM3G FH HMI PLC All-in-One User Manual - Coolmay All-in-One User Manual.p… · Thank you for purchasing Coolmay QM3G-FH HMI PLC All-in-One products. This manual mainly explains the

  • Upload
    others

  • View
    19

  • Download
    0

Embed Size (px)

Citation preview

  • Thank you for purchasing Coolmay QM3G-FH HMI PLC All-in-One products. This manual mainly explains the product

    features, specifications and wiring methods. Detailed PLC programming, please refer to . Detailed HMI part, refer to .

    Product Details

    1 Series QM3G: QM3G-FH series

    2 HMI 43 : 4.3inch 50 : 5inch 70 /70HD/70K : 7inch t 100 : 10inch

    .

    . FH FH FH FH FH

    Naming rules QM3G 43FH

    Graph 1 Mounting dimension

    QM3G-100FHQM3G-43FH QM3G-70KFH

    Electric Design

    Product structure

    RUN:PLC operating indicator

    COM:flash when PLC communicates with HMI

    QM3G-43FHGraph3

    Graph 6 QM3G-70KFH

    Hardware Interface

    Mounting dimension

    Mechanical Design

    Input ON

    Input OFF

    Filter function

    High-speed counting

    Digital relay output index

    Max current

    Circuit power voltage

    Circuit insulation

    On response time

    Mechanical life without load

    Electric life with rated load

    2A/point, 4A/4 point COM, 5A/8 point COM, 5A/12 point COM

    Below DC30V/ Below AC220V

    Relay mechanical insulation

    Approx. 10ms

    10million times

    300,000 times

    Digital transistor (MOS) output index

    Max current

    Circuit power voltage

    Circuit insulation

    Isolated voltage (power-terminal)

    On response time

    High-speed output frequency

    MOS tube: 2A/point, 4A/4 point COM, 5A/12 point COM; MT: 05A/point, 0.8A/4 point COM, 1.6A/12 point COM

    DC24V

    Optocoupler insulation

    1500VAC

    High-speed output:10μs;others:0.5ms

    Analog input indexes

    Input signal

    Response time

    Analog input

    Precision

    PT100/PT1000/thermocouple/NTC/0-10V/0-5V/-10~10V/-5~5V/0-20mA/4-20mA/

    1scanning cycle

    0-16 channels

    12 bit

    Analog output indexes

    Output signal

    Analog output

    Precision

    0-5V/0-10V/-10~10V/-5~5V/0-20mA/4-20mA/customizations

    0-8 channels

    12 bit

    External port

    com port

    Environment

    Operating temperature

    Relative humidity

    Storage temperature

    Vibrational frequency

    0°C~50°C

    5%~95%RH

    -20°C~70°C

    10-57Hz,amplitude 0.035mm; 57Hz-150Hz,acceleration4.9m/s² (10 times each on X, Y, Z, total 80 minutes each)

    Basic parameter

    Specifications of

    HMI PLC All-in-One

    QM3G-43FH/50 -16MRFH

    QM3G FH FH 44-70K /100 - MT

    digital points

    analog points

    (optional)COM port(optional) High-speed counting

    high speed pulse

    DI DO AD DA HMIsingle phase

    ABphase

    ABZphase output

    24 20

    43FH/50FH:MT is MOS output. 70FH/70HD/70KFH/100FH:MT: Y0-Y3 is MOS transistor output, Y4-Y35 is transistor output;

    Chart 1:basic parameter

    QM3G-FH HMI PLC All-in-One User Manual

    Chart 3:mounting dimension

    Model Max digitalpoints

    Mounting dimension Boundary dimensionW*H*D(mm)A(mm) B(mm)

    QM3G-43FH

    QM3G FH-70 /HD

    12DI DO12

    24DI20DO

    120

    192

    94

    138

    134*102*34

    200*146*36

    Four side mounting holes

    Terminal block of power supply

    Terminal block of DO

    Terminal block of DI

    PWR:power indicator

    HMI programming port

    PLC programming RS232/RS485

    PLC operating switch RUN/STOP

    analog output

    HMI RS232/RS485/PLC-CAN

    LCD

    Ethernet port optional

    12 12DI DO 143 86 151*96*36

    QM3G-50FH

    485P/232H-1P-1C1A0V2DA4ADRTM24 ------

    Graph4 QM3G-50FH

    Chart 2 Product structure

    Max analogpoints

    4AI2AO

    12A8AO

    4AI2AO

    Electric parameter

    Input voltage DC24V

    Digital input indexes

    Isolation mode

    Input impedance

    Photocoupling

    High-speed input 3.3KΩ Common input 4.3Ω

    Chart 2: electric parameter

    (Continue to above table)

    Wiring specifications of terminals: 22-14AWG wire. The terminals of this serial are all pluggable ones.

    Definition of communication interface : Refer to Chart 4:Pin definition

    QM3G- FH FH70K /100 - M60 T 30

    Y20COM4Y17Y16Y15Y14

    COM3Y13Y12Y11Y10

    COM2Y07Y06Y05Y04

    COM1Y03Y02Y01Y00

    COM0

    X23X22X21X20X17X16X15X14X13X12X11X10COMX07X06X05X04X03X02X01X00COM

    X24

    X26X25

    X27

    Y21Y22Y23

    AD1

    AD2

    AD3

    AD4

    GN

    DDA

    0DA

    1

    X30

    X31

    X32

    X33

    X34

    X35

    GND1

    Y35

    Y34

    Y33

    Y32

    Y31

    Y27

    COM5

    Y26

    Y25

    Y24

    Y30

    AD

    5A

    D6

    AD

    7A

    D8

    AD

    9A

    D10

    AD

    12

    AD

    13

    AD

    14

    AD

    15

    AD

    0A

    D1

    AD

    2A

    D3

    AD

    4

    AD11

    GN

    DGN

    D1D

    A0

    DA

    1

    DA

    3

    DA

    7

    DA

    4D

    A5

    DA

    6

    DA

    2

    AD0

    QM3G-70KFH-44M-16AD8DA

    QM3G-70KFH-60M-5AD2DA12 8

    High-speed input: current>5.8mA/24V Common input: current >9.9mA/24V

    High-speed input: current4mA/17V

    Input level Passive NPN, common terminal isolation, S/S connected to 24V+

    Output level Low level NPN, COM connects negative

    Output level Dry contact, COM connects positive or negative

    Normally 8 channels,Y0-Y3 is100KHz,Y4-Y7 is 10KHz

    The total high-speed counting and pulse can not exceed 480KHz.

    Normallysingle phase6 channels

    60KHz;

    Refer to " Chart 1 : basic parameter "

    13

    14

    WIFI optional15PLC USB programming port16

    1

    10 11 9

    4 3

    25

    7814

    12 15

    16

    A:485+

    B:485 -

    Chart 9 PLC485 port

    Chart 8 COM1/COM2

    analog input

    FG:cover protection GND0V:24V negative24V:24V positive

    QM3G FH- - MR70 /HD 24

    QM3G-43 /50FH FH-24MT/R Normally 8 channels:Y0-Y3is

    100KHz,Y4-Y710KHz

    is

    35.6

    163

    5 226

    194

    275

    36

    102

    120

    34

    151

    96

    36

    86

    143

    Graph7 QM3G-100FH

    X23X22X21X20COM

    X16X15X14X13X12X11X10COMX07X06X05X04X03X02X01X00COM

    Y23Y22Y21Y20

    Y17Y16Y15Y14

    COM3Y13Y12Y11Y10

    COM2Y07Y06Y05Y04

    COM1Y03Y02Y01Y00

    COM0

    AD1

    AD2

    AD3

    AD4

    GN

    DDA0

    DA1

    X17

    X27X26X25X24

    X3

    0X

    31

    X3

    2X

    33

    X34

    X35

    GND1

    Y3

    5Y

    34

    Y3

    3Y

    32

    Y3

    1

    Y2

    7

    COM5

    Y2

    6Y

    25

    Y2

    4

    Y3

    0

    AD

    5A

    D6

    AD

    7A

    D8

    AD

    9A

    D10

    AD

    12

    AD

    13

    AD

    14

    AD

    15

    AD

    0A

    D1

    AD

    2A

    D3

    AD

    4

    AD11

    GN

    DGN

    D1D

    A0

    DA

    1

    DA

    3

    DA

    7

    DA

    4D

    A5

    DA

    6

    DA

    2

    AD0

    QM3G-100KH-44M-16AD8DA

    QM3G-100KH-60M-5AD2DA

    COM4normallyAB phase2 channels

    60KHz+1 hannel10KHz;

    normallyABZ phase2 channels

    60KHz;

    customizations

    4

    5

    【Note:A/B,A1/B1

    Please refer to the product silkscreen for special model interface identification.

    MR is relay output;MRT is mix output,Optional according to customer requirements

    134

    94

    217

    154

    262

    180

    QM3G-50FH

    QM3G-70FH/HD

    146

    200

    36

    192

    138

    10 11

    3

    2

    1614 7

    9

    5

    1

    4

    8

    136

    Graph5 QM3G-70FH/HD

    12 12

    8 8

    ※ More specs can be customized if bulk order

    QM3G FH-100 30DI3 DO0 262 180 275*194*3616AI AO8QM3G FH-70K 30DI3 DO0 217 154 226*163*35.616AI AO8

    QM3G FH- MR70 /HD-40

    QM3G FH-70 /100FH-24MR

    12 12

    24 16

    12 12

    QM3G FH FH 38-70K /100 - MR 20 18

    QM3G FH- - MT70 /HD 44 24 20

    Normally 6 channels single phase 60KHz or AB(Z) channel 2 channels 60KHz+AB phaze 1 channel 10KHz

    QM3G-43FH/50FHcome with 1XRS232 on HMI

    1 RS485 or2 Rs485 can beoptional on PLC

    (1 485 port is changed from

    default 232port)

    QM3G-43FH/50FHcan be added

    1XWIFIon PLC(cannot coexist

    with default 232 on PLC)

    QM3G FH FH 48-70K /100 - MR 24 24

    QM3G-43FH/50FH All-in-One COM Port Description

    PIN#PLC-485-2serial port3

    PLC-485-1serial port 2

    PLC-232serial port3 HMI-232

    optional default

    8

    9

    √(485+)

    √(485-)

    √(RXD)

    √(TXD)

    √(GND) √(GND)

    √(TXD)

    √(RXD)

    Optional, cannot coexist with default 232 and WIFI (optional)

    1

    6

    2

    3

    5

    4

    7

    COM1Db9 port

    terminal 485

    PLC-WIFI

    Optional, cannot coexist with default 232 and 485-2 (optional)

    Chart 4: Pin definition

    DA0

    DA1

    GND

    AD0

    AD1

    AD2

    AD3

    GND

    B A

    Y13Y12Y11Y10Y07Y06Y05Y04Y03Y02Y01Y00COM

    X13X12X11X10X07X06X05X04X03X02X01X00COM

    Y13Y12Y11Y10Y07Y06Y05Y04Y03Y02Y01Y00COM

    DA0

    DA1

    GND

    AD0

    AD1

    AD2

    AD3

    GND

    B A

    X13X12X11X10X07X06X05X04X03X02X01X00COM

    Y21Y20Y17Y16Y15Y14

    COM3Y13Y12Y11Y10

    COM2Y07Y06Y05Y04

    COM1Y03Y02Y01Y00

    COM0

    X23X22X21X20X17X16X15X14X13X12X11X10COMX07X06X05X04X03X02X01X00COM

    X24

    X25

    X26

    X27

    AD07

    AD05

    AD00

    GND

    GND

    DA00

    DA06

    A B Y22

    Y23

    AD06

    AD04

    AD03

    AD02

    AD01

    DA01

    DA02

    DA03

    DA04

    DA05

    DA07

    QM3G-70KFHQM3G-43FH QM3G-50FH

    6

    13

    14

    1710 3

    10 11

    12

    1

    4

    2 859

    72

    814

    75

    15

    916

    16

    3

    QM3G-100FHQM3G-70 /HDFH

    is RS485】

    17

    17

    11

    14

    12

    18

    PLC/HMI RS48518

    43FH/50 /70 /70HDFH FH

    70K /100 Type-B portFH FH is

    43 /50 /70 /70HDFH FH FH

    70K /100 mini USB portFH FH is

    15

    19

    WiFi switch optional19

    19

    19

    19

    is Type-C port;

    Is Type-C port;

    14

    7 and 10inch can be added

    CAN/Etheret/WiFi(Occupies the

    default port 232) on PLC

    7 and 10 inchcome with 1X RS232on HMI and

    1X485 is optional

    Acceleration anddeceleration are

    independent.High-speedcounting and pulse can't

    over 480KHz.

    default

    8 6

    The features are as below.

    1. PLC compatible with FX3G/FX3U/FX3S PLC. It operate fast.

    2. The digital points are 30 inputs and 30 outputs at most.

    3. Support several high-speed counting and high-speed pulse.

    4. 32K steps program capacity,32K power-off retentive registers,support interrupt,linear and circular interpolation,PID self-adjusting.

    5.

    6.

    7

    More models are supported to customize if bulk order.

    Super functions.

    Highly integration. The digital output can be transistor,relay or mixed

    output.Analog can reach up to 16 input and 8 output. It has 2 PLC COM port (Rs232 and USB Port), 1 downloading port on HMI.

    Acceleration and deceleration are independent.

    Special encryption.Set password as 12345678 to thoroughly prevent reading data.(PLC only supports 8-bit password encryption)

    PLC is compatible with programming software GX Developer8.86Q and GX Works2, and HMI is mView software.

    . The network module can be selected according to customer requirements to realize remote control.

    The total

    high-speed counting and pulse can not exceed 480KHz.

    ① ② ③ ④ ⑤ ⑥ ⑦ ⑧ ⑨ ⑩ ⑪ ⑫

    4. Module type M: Main module of universal controller5. Digital output (DO) type R: relay; T: trnasistor(MOS tube); RT: both relay and transistor6. Analog input (AD) 4 channels for 43FH/50FH,12 for 70FH/HD ,16 for 70KFH/100FH7. Analog output (DA) 2 channels for 43FH/50FH,8 for 70FH/70HD/70KFH/100FH8. AI type E: Thermocouple E(can be customized as type K T, S or J supports negative temperature) PT:PT100 PT1000:PT1000 NTC thermistor 10K, 50K, 100K A0: 0-20mA A4: 4-20mA V5: 0-5V V: 0-10V V5_:-5V~5V V_:-10~10V (only 7 and 10 inch support V5_ and V_) 9. AO type A0: 0-20mA A4: 4-20mA V5: 0-5V V: 0-10V V5_:-5V~5VV_:-10~10V(only 7 inch and 10 inch support negative voltage covers 2 channels)10. C1 singe phase high-speed counting,C2 AB phase counting,C3 ABZ phase counting;Normally support 6 single phase 60KHz , or 2 AB ( Z ) 60KHz + 1 AB 10KHz11. P0:10KHz high speed pulse;P:100KHz high speed pulse;Normally 8 channels,Y0-Y3 is 100KHz,Y4-Y7 is 10KHz;That high speed counting plus high speed pulse must be withi 480KHz12. com port optional refers to Chart 1'basic parameter’

    3. Digital input and output (DI/DO) 16: 8DI 8DO 24: 12DI 12DO 38: 20DI 18DO 44: 24DI 20 DO 60: 30DI 30DO

    QM3G-70KFH/100FH-58MR

    With filter function, the filter time can be set among 0-60ms,defaulted as 10ms

    30 28

    30

    2

    16 8

    2

    PLC

    13 6

    6

    13

    Automation Expert

    6

    13

    14 1011 3

    2 8 5 79

    17

    16

    14

    3456

    7

    8910

    11

    12

    12

  • Devices Distribution and Statement of Power-down Save

    X00 X13 12 points~ X00 X27 24 points~

    Y00~Y23 20 points

    Auxiliary Relay M

    State S [S0-S9] 10point initial state/ [S10 S999] 990point holding/ [S1000 S4095] 3096point general ~ ~

    Timer T

    [T0~T199] 200point 100ms general / [ [T250~T255] 6点 100ms holding

    QM3G-43FH/50FH-24M

    Programming Reference

    max digital points

    digital output Y

    HMI PLC All-in-one's device power-off maintenance is permanently maintained, that is,all the devices in the holding area are not lost after the module is powered off.

    The real-time clock uses a rechargeable battery to ensure that the clock is the current time. All

    power-off hold functions must ensure DC 24V.The voltage after the source is loaded is 23V or more,

    otherwise the power-off function will be abnormal.and the PLC power-on time is longer than 2 minutes,

    [M0~M383] / [M384~M1535] holding 384point general 1152point / [M1536 M7679 6144point g~ ] eneral

    QM3G-70FH/HD-44M QM3G-70KFH/100FH-60M

    programming software PLC:compatible with PLC programming software GX Developer 8.86Q and GX Works2 HMI:mView HMI programming software

    Data Register D

    [V0 V7] [Z0 Z7] 16point indexing~ ~

    [0 127] 128point general/ [D128 D7999] 7872point Holding/ [D8000 D8511] 512point Special ~D ~ ~

    Nested Pointer [N0~N7] 8points Master control

    [P0~P255] 256points/[ ]P0~P1280 1281 points (26232 version or above)

    constantK

    H

    16bit -32,768~32,767 32bit -2,147,483,648~2,147,483,64732bits 0~FFFFFFFFH16 bits 0~FFFFH

    Shenzhen Coolmay Technology Co., Ltd

    Tel:0755-86950416 86960332 26051858 26400661

    QQ: 1687435500

    Website: en.coolmay.com

    Version: 2021/06

    X00 X35 30 points~

    Y00~Y35 30 points only limited to 24V DC, we suggest you to use the power supply which output voltage is 18W or higher than 18W),and wiring correctly, then electrify it.

    2、Before installing the product, please tighten the screw and clamp guide to avoid falling.3、Please do not wiring or plug cable when the power is on, otherwise it may cause electric shock or circuit damagement. Disconnect the power switch immediately when the product smells or sounds abnormal. Do not drop metal shavings and wire tips into the control vent holes during screwing hole and wiring, which may cause product malfunctions and faults.4、Please do not tie the power cord and communication cable together or let them too close, you should keep them for more than 10cm distance. The strong and weak electricity should be separated and properly grounded. If the interference is serious the communication and high frequency signal input and output cables should be the shielded cables to improve anti-jamming performance.

    7、Do not disassemble the product or modify the wiring optionally . Otherwise it may cause fault, malfunction, loss, or fire.

    8、Please make sure to turn off the all power when you install or dismantle the product, otherwise it may cause malfunction or fault.

    —— Before using this product, please read the relevant manual Carefully use the product under the environmental conditions specified in the manual.

    5、The digital input is an externally powered DC24V leakage type (passive NPN) with the input signal isolated from the power supply.

    When you use it, you need to connect COM to the 24V positive pole of the external power supply

    QM3G-FH series HMI PLC All-in-One User Manual

    Diagram10 Input wiring

    Diagram 11 Relay output equivalent circuit Diagram 12 Transistor output equivalent circuit

    Diagram 13 Inductive load absorption circuit schematic

    Diagram 14 Pulse output wiring diagram

    Note:The internal circuit in all diagrams is for reference only※The PLC input (X) is an externally powered DC24V sinker (passive NPN) and the input signal

    is isolated from the power supply. Connect COM to positive 24V of external power supply while using.

    1K

    3.9K

    COM(S/S)

    X0 0V

    X1

    1K

    3.9K

    COM0

    Y003

    Y000load

    load

    COM1

    Y007

    Y004

    DC24Vfuse

    load

    load

    AC0~220Vfuse~

    load

    load

    load

    load

    sink output type

    DC24Vfuse

    DC24Vfuse

    COM0

    Y003

    Y000

    COM1

    Y007

    Y004

    COM0Y1

    COM2Y10

    COM1Y4

    R=200Ω C=0.22uF,250VAC

    RC

    ~

    COM1Y5

    ~

    PLC relay output

    Inductive load

    DC24V power supply

    freewheeling diode1N404

    PLC transistor output

    inductive load

    freewheeling diode1N404

    DC24V power supply

    PLC relay output

    inductive load

    AC220V power supply

    inductive load

    PLC relay output

    AC220V power supply

    Varistor10D471k(undercurrent)

    +

    -

    +

    -

    +

    -

    +

    -

    +

    -

    +

    -

    +

    -

    +

    -

    R

    COM1

    Y4

    Y5

    Y6

    Y7direction

    pulse(Pul)

    direction

    pulse(Pul)

    COM0

    Y0

    Y1

    Y2

    Y3

    PLCequivalent

    circuit

    direction

    pulse(Pul)

    direction

    pulse(Pul)

    DC24V(5V drive requires 2k )Ω resistor

    GND

    AD0

    AD1

    AD15

    +104p

    GND

    DA0

    DA1

    DA7

    AI

    (analog input common)

    ( 1)analog input104p

    + (analog input 2)

    If the analog input is unstable please add 104p porcelain as appropriate chip capacitor or external magnetic loop filter increase the ability to interfere

    104p

    + (analog input 16)

    -

    ( )analog output common

    + (analog output 8)

    + (analog output 2)

    + (analog output 1)

    FROM instruction can read directly: FROM K0 K0 D400 K16, reads 16 channel analog input.

    Note:Detailed settings, please refer to "Coolmay QM3G-FH series All-in-One Programming Manual"

    Serial No. register address

    D8050

    D8051

    D8052

    D8053

    D8054

    D8055

    D8056

    D8057

    setting range

    0-4000

    0-4000

    0-4000

    0-4000

    0-4000

    0-4000

    0-4000

    0-4000

    output type

    when D8058.0~D8058.7=0

    type is 0~20mA;

    when D8058.0~D8058.7=1

    type is 4~20mA。

    The temperature type is one after the decimal point is reserved,like 182℃=18.2

    Note: more details please refer to

    ※ The number of filtering cycles = (R23600 ~ R23615) * PLC scan time, the default is 100, the data can not be lessthan or equal to 0. If RS23600 = 1, a PLC scan cycle is sampled once, and the first analog input is changed once.

    The larger the value of R23600~R23615 is set, the more stable the result is.

    D8073 is the smoothing filter coefficient of all analog inputs. Setting range: 0~999

    Sampling of analog inputs

    The equivalent circuit of the PLC output part of the transistor output type is shown in Diagram 12.

    the output terminal are several groups, each group is electrically isolated,

    For the inductive load connected to the AC circuit, the external circuit should consider the RC transient voltage

    absorption circuit; corresponding to the inductive load of the DC loop, consider adding a freewheeling diode, as

    Diagram 13.

    Stepping or servo motor wiring as shown in Diagram 14, 3G series PLC default Y0-Y7 is pulse point, direction can be customized

    Note: 5V drive must be connected to resistor on DC24V

    As know from the

    figure, and different groups of output can be

    connected to different power circuits; the transistor output stage can only be used for DC24V load circuits. Output wiring is

    NPN, COM common cathode.

    shown in

    2KΩ

    PLC anti- interference processing1、Strong and weak currents should be separated and wired, and not common ground;when there is strong electric interference,magnetic rings should be added on the power supply side;and properly and effectively grounded according to the type of the chassis.2、when the analog quantity is disturbed, 104 ceramic capacitors can be added for filtering,and a correctand effective grounding can be performed.

    register read directly: D[8030]~D[8045]is the input value corresponding to the analog quantity [AD0~AD15]. The constant scan timewhen the analog input has

    thermocouple type You can only do up to 15 channels, of which AD4 (D8034) is the ambient temperature of the thermocouple.

    You can do 16 channels without the thermocouple type.]

    scan time is changed to D8059, which is started by M8039 (this function is available on version 26232)

    QM3G-70FH/HD All-in-One com port

    PIN#

    PLC-485-2serial port3

    PLC-485-1serial port 2

    PLC-232serial port3

    HMI-232(default)、cannot coexsit

    with 485 on HMI

    optional

    8

    9

    √(RXD)

    √(TXD)

    √(GND) √(GND)

    √(TXD)

    √(RXD)

    QM3G-70KFH/100FH All-in-One com port

    PIN#PLC-485-1

    serial port2

    DB 9 port default optional

    8

    9

    √(485+)

    PLC optional with

    default 232 and

    HMI optional 485

    Cannot coexist

    PLC-485-2serial port 3

    PLC-232serial port 3

    PLC-WIFI

    optional

    PLC-CAN

    optional

    COM2(DB9 port near the power supply) COM1 (DB9 port far away f rom the power supply)

    HMI-485 HMI-232

    default

    Ethernet port

    √(485+)

    √(485-)

    √(485-)

    √(RXD)

    √(TXD)

    √(GND)

    √(H)

    √(L)

    Optional

    PLC

    Network

    port not

    Occupy

    Ser ia l

    port

    s ignal

    optional

    √(RXD)

    √(TXD)

    √(GND)

    √(485+)

    √(485-)

    2

    3

    5

    4

    7

    1

    6

    2

    3

    5

    4

    7

    COM1

    Db9 port

    24V

    Diagram 11 shows the equivalent circuit diagram of the relay output module. The output terminals are severalgroups. Each group is electrically isolated. Different groups of output contacts are connected to different powercircuits

    1、In case of damaging the product, please confirm power supply range first (the regular power supply

    Extended file register R [R0~R22999] 23000points support power outage/[R23000~R23999] 1000points internal use

    pointer JUMP、CALL branch

    Interruption [ ] points input interruption/I0□□~I5□□ I6□□~I8□□ I010~I0606 [ ]3points timer interruption/[ ]6points counter interruption

    [T246~T249] 4point 1ms grand total holding / [T256~T319] 64 points 1ms general [T200~T245] 46point 10ms General ※The 10ms timer will be affected by the scan period.

    If the scan period is 12ms, the timer becomes 12ms and executes once.

    [M8000~M8511] 512point special

    Data Register V,Z

    Ports short circuit

    24V, and the X terminal is connected to the power supply 0V, that is, the input

    has a signal

    Two-wire system (magnetic control switch): The positive pole of the magnetic switch is

    connected to PLC X terminal, and the negative pole is connected to 0V.

    Three-wire system (photoelectric sensor or encoder):The PLC switch is

    connected to a three-wire photoelectric sensor or encoder, the power supply

    of the sensor or encoder is connected to the positive electrode of the power

    supply, and the signal line is connected to the X terminal. The encoder and

    photoelectric sensor are required to be NPN type (PNP needs special customization).

    :The COM (S/S) of the PLC input terminal is connected to

    (Continue to above table)

    Note: The analog input range and the corresponding value of the register can be found in

    TO instruction direct output:TO K0 K0 D500 K8,output 8 channels analog

    Equivalent Circuit

    Email: [email protected]

    Counter C

    high-speed counter

    [C0 C15] 16point General~ [C200 C219] 20point General~

    16bit up counter 32bit up and down counter

    [C235 45 single phase single counting] ~C2 [C246~C250single phase dual counting

    ~]

    [C251 C255 dual phase dual counting] [C16 C199] 184point holding~ [C220 C234] 15point holding ~

    AO

    digital input X

    6、The COM of the binary input/output (transistor) is common to the cathode.

    terminal A B

    terminal A1 B1

    PLC-WIFI

    √(H)

    HMI-485

    PLC-CAN

    √(L)

    HMIP L C

    o p t i o n a l

    PLC optionalWith default 232,Optional 485-2 cannot

    coexist

    Diagram 15 PLC analog wiring

    Analog input register(AD means analog input precision is 12 bit);supports FROM instructions or register direct assignment operation

    catalog

    Product Information 1Basic Parameters.............................. 1Mechanical Design............................. 2Electric Design .................................. 3Equivalent Circuit............................. 4

    .................................

    ...Programming Reference...................... 5Tips....................................................6

    Analog output register(DA means analog input, precision is 12 bit); support TO instructions or register direct assignment operation

    PLC digital outputs wiring:

    Transistor: Output is NPN, COM is connected to the negative pole, and Y is connected to

    the positive pole of the power supply w ith a load .

    Relay: D ry contact output, COM can be connected to the positive or negative.

    analog input is AD0~AD15,analog output is DA0~DA7.The negativeterminals are respectively connected to the GND of the analog input/output terminals.7 inch and 10 inch optional.One of the negative voltage outputs occupies two DAs, that is, up to 4 negative voltage outputs can be selected ( the wiring can be connected to DAx and GND,such as DA0 and GND, DA2 and GND, etc. The actual output terminal is subject to the product factory test report)

    negative voltage output can be

    PLC analog wiringTwo-wire system:the positive pole of the power supply is connected to the positive pole of the transmitter; the negative pole

    of the transmitter is connected to the AD side; the negative pole of power supply is connected to GND,which normally it is wring

    way of 4-20mA/0-20mA transmitter

    Three-wire system:the positive pole of the power supply is connected to the positive pole of the transmitter; the negative pole of the power supply and the negative pole of the signal output are the same terminal and transmitter signal output is connected to the AD terminal;Four-wire system:the positive and negative poles of the power supply are respectively connected to the positive and negative poles of the power supply of the transmitter,and the positive and negative poles of the transmitter signal output are respectively connected to the AD and GND terminals;The analog line of the temperature is connected to the AD terminal and the GND terminal respectively. if I is a three-wire Pt100, it needs to be connected in two lines. The GND common terminal of the analog input and output can be shared.

    Register direct assignment operation :D[8050]~D[8057] corresponding to the analog output value of [DA0~DA7], which optional two-way DA is used when the negative output is selected, the set value range is as follows

    Detailed refers to

    PLC digital inputs wiring:

    PLC

    de fau l tO p t i o n a l a n d d e f a u l t

    2 3 2 , O p t i o n a l 4 8 5 c a n n o t c o e x i s t

    Opt i ona l and de fau l t 232 , Op t i ona l W IF I

    canno t coex i s t

    (Dir)

    (Dir)

    (Dir)

    (Dir)

    Tips

    X00 X13 12 points~

    页 1页 2