8
low voltage QF13-SERIES-DAT JUN 2015 Data Sheet Page 1 of 8 DIN Mount 1 pole Dual Mount 3 pole Dual Mount 3 + N DIN Mount 2 pole AC Circuit Breaker Hydraulic-Magnetic technology 100% rating capability, independent of ambient temperature VC 8036 compliant (SANS 556-1) VDE and CCC approved, CE certified UL 1077 recognised (supplementary protector) AS 3111 approved Ratings 0.1 to 25 A (subject to certification) Optional Shunt Trip (no approvals) Available in various currents and time delays Precision tripping characteristics Ultra compact – 13 mm wide module Trip indication with mid-trip position Reset immediately after overload DIN Mount product in grey shells Dual Mount product in black shells Suitable to use for electrical isolation Shell designed for easier installation onto busbar QF(13) - Series Miniature Circuit Breakers Features Applications AC branch circuit protection (IEC / EN 60947-2) Switch Disconnector (IEC / EN 60947-3) Supplementary protection (UL 1077) Telecom / datacom equipment Lighting control UPS equipment Alternative energy equipment Mobile power generation equipment Railway signalling equipment Residential equipment Industrial equipment Handle lock Surface mounting clips Busbar 57 mm Escutcheon blank (Dual Mount only) 57 mm Safety blank (Dual Mount only) Optional Accessories Auxiliary Switch,Trip Alarm & Combo: Features Auxiliary Switch (DIN and Dual Mount) Auxiliary Switch + Trip Alarm (Dual Mount only) Trip Alarm (Dual Mount only) AC and DC voltages UL 489 listed (Auxiliary Switch: 6 A 250 V AC, 0.5 A 80 V DC) IEC 60947-5-1 approved (Auxiliary Switch: 6 A 240 V AC, 0.5 A 110 V DC; Trip Alarm: 6 A 240 V AC, 0.5 A 110 V DC) Factory fitted Attached to right hand side of Circuit Breaker Compact 6.5 mm width

QF(13) - Series Miniature Circuit Breakers · Maximum Current Rating 25 A Interrupting Capacity 6 kA Product Type Supplementary Protector ... Current Rating 63 A Short-time Withstand

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: QF(13) - Series Miniature Circuit Breakers · Maximum Current Rating 25 A Interrupting Capacity 6 kA Product Type Supplementary Protector ... Current Rating 63 A Short-time Withstand

low voltage

QF13-SERIES-DATJUN 2015

Data SheetPage 1 of 8

DIN Mount1 pole

Dual Mount3 pole

Dual Mount3 + N

DIN Mount2 pole

• AC Circuit Breaker• Hydraulic-Magnetic technology• 100% rating capability, independent of ambient temperature• VC 8036 compliant (SANS 556-1) • VDE and CCC approved, CE certified• UL 1077 recognised (supplementary protector)• AS 3111 approved• Ratings 0.1 to 25 A (subject to certification)• Optional Shunt Trip (no approvals)• Available in various currents and time delays• Precision tripping characteristics• Ultra compact – 13 mm wide module• Trip indication with mid-trip position • Reset immediately after overload• DIN Mount product in grey shells• Dual Mount product in black shells• Suitable to use for electrical isolation• Shell designed for easier installation onto busbar

QF(13) - Series Miniature Circuit Breakers

Features Applications• AC branch circuit protection (IEC / EN 60947-2)• Switch Disconnector (IEC / EN 60947-3)• Supplementary protection (UL 1077)• Telecom / datacom equipment• Lighting control• UPS equipment• Alternative energy equipment• Mobile power generation equipment• Railway signalling equipment• Residential equipment• Industrial equipment

• Handle lock• Surface mounting clips• Busbar• 57 mm Escutcheon blank (Dual Mount only)• 57 mm Safety blank (Dual Mount only)

Optional Accessories Auxiliary Switch, Trip Alarm & Combo:Features• Auxiliary Switch (DIN and Dual Mount)• Auxiliary Switch + Trip Alarm (Dual Mount only)• Trip Alarm (Dual Mount only)• AC and DC voltages• UL 489 listed (Auxiliary Switch: 6 A 250 V AC,

0.5 A 80 V DC)• IEC 60947-5-1 approved (Auxiliary Switch: 6 A 240 V AC,

0.5 A 110 V DC; Trip Alarm: 6 A 240 V AC, 0.5 A 110 V DC)• Factory fitted• Attached to right hand side of Circuit Breaker• Compact 6.5 mm width

Page 2: QF(13) - Series Miniature Circuit Breakers · Maximum Current Rating 25 A Interrupting Capacity 6 kA Product Type Supplementary Protector ... Current Rating 63 A Short-time Withstand

QF13-SERIES-DATJUN 2015

Data SheetPage 2 of 8

low voltage

Technical Data

Product Type Circuit BreakerApprovals IEC / EN 60947-2, VDENumber of Poles 1 2 (1+N) 2 3 4 (3+N)Operating Voltages 240 V AC 415 V ACMinimum Current Rating 0.1 AMaximum Current Rating 25 AInterrupting Capacity 6 kA

Product Type Supplementary ProtectorApprovals UL 1077

Tested with and without series fuseNumber of Poles 1 2Operating Voltages 120 V AC 120 / 240 V ACMinimum Current Rating 0.1 AMaximum Current Rating 25 AInterrupting Capacity 5 kA

QF(13) - Series Miniature Circuit Breakers

Product Type Circuit BreakerApprovals CCCNumber of Poles 1 2 (1+N) 2 3 4 (3+N)Operating Voltages 240 V AC 415 V ACMinimum Current Rating 1 AMaximum Current Rating 25 AInterrupting Capacity 6 kA

Product Type Circuit BreakerApprovals VC 8036 (SANS 556-1)Number of Poles 1 2 (1+N) 2 3 4 (3+N)Operating Voltages 240 V AC 415 V ACMinimum Current Rating 5 AMaximum Current Rating 25 AInterrupting Capacity 5 kA

Product Type Switch DisconnectorApprovals IEC / EN 60947-3Number of Poles 1 2 3 4Operating Voltages 240 V AC 415 V ACCurrent Rating 63 AShort-time Withstand 6 kA

Product Type Circuit BreakerApprovals AS3111Number of Poles 1 2 (1+N) 2 3Operating Voltages 240 V AC 415 V ACMinimum Current Rating 0.1 AMaximum Current Rating 25 AInterrupting Capacity 6 kA

Page 3: QF(13) - Series Miniature Circuit Breakers · Maximum Current Rating 25 A Interrupting Capacity 6 kA Product Type Supplementary Protector ... Current Rating 63 A Short-time Withstand

low voltage

QF13-SERIES-DATJUN 2015

Data SheetPage 3 of 8

Long Code

Group 1: Frame Type

Code Description Comments QF 13 mm wide Miniature Circuit Breaker

Group 2:Switch/Neutral

Code Description Comments - Not applicable Overload poles do not have any further coding

S Switch Green handle

N NeutralGroup 3:Auxiliary

Code Description Comments- Not applicable Use this code if no Auxiliary used

A Auxiliary Switch (1 x Aux in 1 module) 6.5 mm module fitted on right-hand side

T Trip Alarm (1 x Trip Alarm in 1 module) 6.5 mm module fitted on right-hand side (Dual Mount only)

AT Auxiliary Switch + Trip Alarm combo (combined in 1 module) 6.5 mm module fitted on right-hand side (Dual Mount only)Group 4: No of Poles

Code Description Comments1 Single pole

2 Double pole 2 pole or 1+N

3 Triple pole

4 Four pole 4 pole or 3+N onlyGroup 5: Module Width

Code Description Comments (13) 13 mm module width 13 mm per pole

Group 6: Mounting

Code Description Comments D DIN Mount DIN Mount supplied in grey body only - 45 mm Escutcheon

DM Dual Mount Dual Mount supplied in black body only - 57 mm EscutcheonGroup 7: Time Delays

Code Description Instantaneous Trip Point (x In) Comments1 Long time delay, high instantaneous trip 10 – 20 Orange handle

2 Medium time delay 5 – 10 White handleGroup 8: Current Ratings

Code / Description Comments

0.1, 0.2, 0.3, 0.5, 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 12, 15, 16, 20, 25 ARatings available vary depending on certification

* Other ratings are available as special orders. Check availability.Group 9: Code For future use (-)Group 10:Shunt Trip

(not certified, only offered as special order)

Code Description Comments- Not applicable Use this code if no Shunt Trip is used

V0 100 – 480 V AC Fly leads (approximately 60 mm long)

V5 100 – 480 V AC Internally connected

Other voltages are available as special orders. Check availability.Group 11 Code For future use (-)

DescriptionOperating Temperature Range -40 oC to +85 oCMounting Options DIN Rail, Dual mounting (DIN & Mini), surface mountTime Delay Curves 1, 2

Example Code: QF---AT-3(13)-D-2-15A------Group 1 2 3 4 5 6 7 8 9 10 11

Requirement QFFrame

Switch /Neutral

Auxiliary + Trip Alarm

Triple pole13 mm module width

DIN RailMedium

delaycurve 2

Current Rating 15 A

Future use Shunt Trip Future use

Long Code QF - AT 3 (13) D 2 15A - - -

For options not listed, please contact CBI for assistance

Breaker QF Wire Size mm² (IEC) Wire Gauge (UL) Torque (IEC) Torque (UL) Comments

1 Pole & 2 Pole 0.75 - 35 mm² 18 – 2 – AWG 2.5 Nm 20 in-lb Pozidriv #2Combi head

3 Pole & 4 Pole 0.75 - 35 mm² - 2.5 Nm - Pozidriv #2Combi head

QF(13) - Series Miniature Circuit Breakers

Page 4: QF(13) - Series Miniature Circuit Breakers · Maximum Current Rating 25 A Interrupting Capacity 6 kA Product Type Supplementary Protector ... Current Rating 63 A Short-time Withstand

QF13-SERIES-DATJUN 2015

Data SheetPage 4 of 8

low voltage

Time Delay Curves

105

130

150

1500

15

00

200

300

400

500

2000

2500

3000

4000

5000

0.001

0.01

0.1

1

10

100

1000

10000

100000

100

1000

Trip

ping

Tim

e (S

econ

ds)

% Rated Current

OPERATING CHARACTERISTICS

CURVE 1

Minimum

Maximum

QF(13) - Series Miniature Circuit Breakers

Page 5: QF(13) - Series Miniature Circuit Breakers · Maximum Current Rating 25 A Interrupting Capacity 6 kA Product Type Supplementary Protector ... Current Rating 63 A Short-time Withstand

QF13-SERIES-DATJUN 2015

low voltage

Data SheetPage 5 of 8

Time Delay Curves

105

130

150

1500

15

00

200

300

400

500

2000

2500

3000

4000

5000

0.001

0.01

0.1

1

10

100

1000

10000

100000

100

1000

Trip

ping

Tim

e (S

econ

ds)

% Rated Current

OPERATING CHARACTERISTICS

CURVE 2

Minimum

Maximum

QF(13) - Series Miniature Circuit Breakers

* The published time delay curves are generated at 30oC ambient temperature with the Circuit Breaker mounted in the up-right position. The “must hold”, “must trip” and “instantaneous trip” current values are not affected by temperature, although delay time for the other operating current values may have to be adjusted using the temperature compensation curve which is available on request.

Page 6: QF(13) - Series Miniature Circuit Breakers · Maximum Current Rating 25 A Interrupting Capacity 6 kA Product Type Supplementary Protector ... Current Rating 63 A Short-time Withstand

QF13-SERIES-DATJUN 2015

Data SheetPage 6 of 8

low voltage

Internal Impedance vs Current Rating

0 5 10 15 20 25 30 35 40 45 50 55 60 650.1

1

10

100

1,000

10,000Q-Range impedance values

Amp rating

Impe

danc

e (mΩ

)

Minimum

Maximum

QF(13) - Series Miniature Circuit Breakers

Page 7: QF(13) - Series Miniature Circuit Breakers · Maximum Current Rating 25 A Interrupting Capacity 6 kA Product Type Supplementary Protector ... Current Rating 63 A Short-time Withstand

low voltage

QF13-SERIES-DATJUN 2015

Data SheetPage 7 of 8

97.2

[3.8

27]

57.0

[2.2

44]

69.8[2.750]

TEST BUTTON(on Trip Alarm only)

AUXILIARY/ TRIP ALARM (AT)

6.5[0.256]

19.3 ± 0.3[0.760 ± 0.012] 36.5

[1.436]18.0[0.709]

6.0[0.236]

11.7[0.461]

18.0[0.709]

37.7[1.483]

CONNECTING TERMINALS DETAIL (COMMON TO ALL)

0.8[0.0315]

1.42.80

[0.110]

6.8

[0.2

70]

2.3

[0.0

90]

0.5

x 45

°[0

.020

]

0.055][

Circuit diagram when the Circuit Breaker is in

the “OFF” position

Trip Alarm Switch

15

16

18

Auxiliary Switch

11

12

14

Q-A

UX

RoHS

AUXI

LIAR

Y SW

ITCH

TRIP

ALA

RM S

WIT

CH

EN/IE

C 60

947-

5-1

110

VDC

: 0,5

A24

0 VA

C : 6

A

15

18

16

11

12

14

Uim

p =

2.5

kVIc

w

= 0

.1kA

UTIL

. CAT

. AC1

2/DC

12PO

LLUT

ION

DEG

REE

3

110

VDC

: 0,5

A24

0 VA

C : 6

AS

A00

5438

DE

V

141211

151816

NC

NO

C

C

NC

NO

Auxiliary available (6.5 mm module width) to match the unit to which it is attached.

Available types as listed in Group 3:

• Type T - Trip Alarm as shown in outline drawings (fitted on a Dual Mount product)

• Type AT - Auxiliary Switch + Trip Alarm (as shown)• Type A - Auxiliary Switch

QF(13) - Series Miniature Circuit Breakers

Typical outline of Auxiliary Switch / Trip Alarm

Typical outline for an Auxiliary module attached to a Dual mount single pole Circuit BreakerAll dimensions in mm [ inch ]Tolerance ± 0.4 unless otherwise specified

Page 8: QF(13) - Series Miniature Circuit Breakers · Maximum Current Rating 25 A Interrupting Capacity 6 kA Product Type Supplementary Protector ... Current Rating 63 A Short-time Withstand

A member of the Group

AUSTRALIACBI-electric: Australia90 Fairbank Road Clayton SouthMelbourne Victoria 3169 AustraliaTel: +61 3 9590 3500Fax: +61 3 9551 1051Email: [email protected]: www.cbi-electric.com.au

SOUTH AFRICACBI-electric: low voltageTripswitch Drive ElandsfonteinGauteng South AfricaTel: +27 11 928 2000Fax: + 27 11 392 2354Email: [email protected]: www.cbi-lowvoltage.co.za

USACBI-electric: North America35 E. Uwchlan Ave Suite 328Exton PA 19341 USATel: +1 610 524 9949Fax: +1 610 524 9945E-mail: [email protected]: www.cbibreakers.com

QF13-SERIES-DATJUN 2015

Data SheetPage 8 of 8

low voltage

Please review our Customer Terms and Conditions on www.cbi-lowvoltage.co.zaAll rights reserved. Unless otherwise indicated, all materials on these pages are copyrighted by CBI (Pty) Ltd. No part of these pages, either text or image may be used for any purpose other than personal use. Therefore, reproduction, modification, storage in a retrieval system or retransmission, in any form or by any means, electronic, mechanical or otherwise, for reasons other than personal use, is strictly prohibited without prior written permission. CBI (Pty) Ltd reserves the right to alter any details of this document without notice and while every effort is made to ensure the accuracy of the content, no warranty is given as to accuracy of this document and no responsibility will be accepted for error or misinterpretation and any resulting loss.

12.8[0.504]

(nominal)

74.0[2.913]

(nominal)

63.8[2.512]

44.0[1.732]

18.6[0.732]

19.0[0.746]

44.0[1.732]

60.0[2.362]

5.0[0.197]

12.8 ± 0.2[0.504 ± 0.008]

25.6 ± 0.4[1.008 ± 0.016]

38.4 ± 0.6[1.512 ± 0.024]

51.2 ± 0.8[2.016 ± 0.031]

45.0

[1.7

72]

97.2

[3.8

27]

Outline Dimensions: Dual Mount

Outline Dimensions: DIN Mount

QF(13) - Series Miniature Circuit Breakers

12.8[0.504]

(nominal)

64.8[2.551]

(nominal)

69.8[2.748]

45.0[1.772]

19.6[0.774]

19.6[0.772]

44.7[1.760]

61.0[2.402]

5.0[0.197]

12.8 ± 0.2[0.504 ± 0.008]

25.6 ± 0.4[1.008 ± 0.016]

38.4 ± 0.6[1.512 ± 0.024]

51.2 ± 0.8[2.016 ± 0.031]

57.0

[2.2

44]

97.2

[3.8

27]

All dimensions in mm [ inch ]Tolerance ± 0.4 unless otherwise specified

All dimensions in mm [ inch ]Tolerance ± 0.4 unless otherwise specified