8/4/2019 Purging Volume
http://slidepdf.com/reader/full/purging-volume 1/5
DOMESTIC SERVICE LINES (3/4”)
EXPERIMENTAL MEASUREMENT OF GAS LOST (WITH METER)
Gas lost during purging of one short S/L (Uncorrected) = 11.92 CFT for 30 seconds
Gas lost during purging of
service lines as measured with meter
in the presence of Audit personal(Site: Askari X, block B, Near Alama Iqbal Air Port)
Correction factor (for pressure 28 psig) = (28+14.65) / 14.65
= 2.91
Gas lost during purging of one short S/L (Corrected) = 11.92 * 2.91 = 34.7 CFT
THEORATICAL MEASUREMENT OF GAS LOST:
Gas lost during purging = P * D2
Pressure „P‟ = 28 psig
Hole of dia „D‟ = 0.3125 inches
Gas lost during purging = 28 * (0.3125)2
= 2.73 MCFH
Gas lost during purging = 22.78 CFT for 30 secondsof one ¾ “ service line
8/4/2019 Purging Volume
http://slidepdf.com/reader/full/purging-volume 2/5
COMMERCIAL SERVICE LINES (1”)
EXPERIMENTAL MEASUREMENT OF GAS LOST (WITH METER)
Gas lost during purging of one S/L = 65 CFT for 30 second (Uncorrected)
Gas lost during purging of
service lines as measured with meter
in the presence of Audit personal
(Site: Jamia Ghazalia, Patiala Ground, Hall Road Lhr.)
Correction factor (for pressure 35 psig) = (35+14.65) / 14.65
= 3.39
= 65 * 3.39
Gas lost during purging of one S/L = 220.35 CFT (Corrected)
THEORATICAL MEASUREMENT OF GAS LOST:
Gas lost during purging = P * D2
Pressure „P‟ = 35 psig
Hole of dia „D‟ = 0.75 inches
Gas lost during purging = 35 * (0.75)2
= 19.68 MCFH
Gas lost during purging = 164 CFT for 30 seconds
of single 1 “ service line
8/4/2019 Purging Volume
http://slidepdf.com/reader/full/purging-volume 3/5
INDUSTRIAL SERVICE LINES (2“)
EXPERIMENTAL MEASUREMENT OF GAS LOST (WITH METER)
Gas lost during purging of one 2” dia S/L = 6.93 m3 for 60 second (Uncorrected)
Gas lost during purging of
2 “ service lines as measured with meter
in the presence of Audit personal
(Site: FAS TUBE, SUNDER INDUSTRIAL STATE)
= 244.49 CFT
Correction factor (for pressure 60 psig) = (60+14.65) / 14.65
= 5.09
= 244.49*5.09
Gas lost during purging of one S/L = 1242.42 CFT (Corrected)
THEORATICAL MEASUREMENT OF GAS LOST:
Gas lost during purging = P * D2
Pressure „P‟ = 60 psig
Hole of dia „D‟ = 1.5 inches
Gas lost during purging = 60 * (1.5)2
= 135 MCFH
Gas lost during purging = 2250 CFT for 60 seconds
of single 1 “ service line
8/4/2019 Purging Volume
http://slidepdf.com/reader/full/purging-volume 4/5
Type of
Connection
Total Number of
Service Lines Laid
During the Period
Jan. 2009-Aug.2009
Gas lost per
Connection
During
Purging
Gas Consumed in
Packing of
Pipeline Per
Connection
Gas lost
Per
Connection
Total Gas Lost During
the Period
Jan. 2009 Aug.2009
A B C B+C A*(B+C)
Nos. CF CF CF MCF
Domestic 36532 34.7 0.234 34.93 1276.06
Commercial 1140 220.35 0.416 220.766 251.673
Industrial 111 1242.42 3.66 1246.08 138.31
8/4/2019 Purging Volume
http://slidepdf.com/reader/full/purging-volume 5/5
1” Ø MS PIPELINE:
EXPERIMENTAL MEASUREMENT OF GAS LOST (WITH METER)
Gas lost during purging of 457 meter 1” pipeline = 160 CFT for 3minutes
As measured by I-7M meter in the presence
of Audit personal.
(Site: Askari X, block B, Near Alama Iqbal Air Port)
Gas lost per meter length of 1” pipeline = 0.35 CFT
Diameter
of
pipeline
Total Length of
Pipeline Commissioned
During the Period
Jan.2009-Aug.2009
Gas lost Per Unit
length of
Pipeline
During Purging
Gas lost Per
Unit length of
Pipeline
During Packing
Gas lost Per
Unit Length
of Pipeline
Total Gas
Lost
1ӯ448165.9
0.35 0.0351
51.62292+1
56.85806
208.48
2ӯ 224572 25.24 0.111 25.35 5693.12
4ӯ 135746.05 89.26