MultiSafe-MX
Fire and gas detectionFire suppression controlSIL 2/ SIL 3 suitable
Integrated addressable and conventional fire and gas system
MultiSafe-MX control panel is a SIL certified, fully flexibleintegrated fire detection, fire suppression control, gas detection,and intruder alarm system.
General description
The MultiSafe-MX system is intended forthe protection of high hazard, high riskplant and facilities.The MultiSafe-MX is certified, by Europeanlaboratories, to comply with the applicableregulations.The panel is composed of dedicated cards,installed in 1 9 racks which have their ownintelligence, programmed foractive/passive fire protection, gasdetection, intruder alarm and logicfunctions.Moreover, the MultiSafe-MX can interactwith supervisory and SCADA systems viaEthernet, TCP/IP or Modbus.
Applications Fire and Gas detection andmeasurement systems. Automatic fire extinguishing controlsystems. Integrated systems, intruder/burglaralarm, CCTV and logic functions. Fire protection systems in accordancewith the recommendations of NFPA 72.
Features
Benefits
SIL2 / SIL 3 suitable
Can replace a safety PLC system
Front plug-in/out cards
System flexibility
Automatic monitoring of card and CPU fault Operational safetyTwo CPU's, in hot back-up to one other
Automatic software configuration
Device calibration data and event logging
Tracks maintenance and incidents
Hot swap of cards and CPU's
Easy and rapid maintenance
Addressable fire detection
Reduced cabling
Easy PC-configuration
User friendly interface
MultiSafe-MX
www.simtronics.eu
Technical dataControl panel, 1 9" - 3HEExpansion rack, 1 3 cards slots, 1 9" - 3HEFront plug-inHot swap
DIRECT CONTROL AND INTERFACING4-20 mA inputsSpecific cards and modules for 4-20 mAAddressable devices Total 1 30 loops, 1 27 addresses per loopDetection cardsSpecific cardsLogic / VotingSpecific programmable function for I/OcardsI/OsMultiple cards, 1 6 inputs and outputs, andI/O modules on busFire extinguishing controls certified to EN 1 2094-1Dedicated native cards for this function cancontrol up to 64 extinguishing zonesExtinguishing controls (directional valves)Dedicated native cards for this function, withno logic and control limitationRepeatersOn BUSRemote controlFrom PC with IRIDE software and Pro-S81programCommunicationTCP/IP on EthernetMulti-panel architectureEthernet and Modbus, copper or fibre optic,redundantGraphic mapsIRIDE programExternal SCADA interfacingStandard MODBUS RTU, proprietaryprotocol on Ethernet available upon requestPOWER SUPPLYFeeder
Battery charger
ENVIRONMENTALTemperatures- Storage- OperationalHumidity
2.5A, 4A or 20A, can be paralleledCertified to EN 54-4, with fault indication incase of mains supply failure, batterycharger or battery fault, overheatingCan be coupled with feederBattery charge and aging status monitoring,through microcontroller-processedalgorithm; thermal compensation duringbattery charging; testing button; batterycapacity : 1 1 0 Ah.
-40C to +85C5C to +50C5% to 95% RH (non-condensing)
Simtronics AS
SYSTEM CAPACITYMaximum number of racks per panel10Maximum number of cards per rack13Maximum number of configurable zones (*1 ) 300 + 300Maximum number of devices per zone (*2)99 + 99 + 99Maximum number of devices per panel (*3)1 651 0Maximum number of panels connectable to each other 64(*1 ) = 300 safety zones and 300 security zones(*2) = 99 inputs, 99 outputs, 99 logic relations(*3) = based on all racks containing 1 3 addressable cards eachELECTRONIC MODULARITY ON BASE RACKDisplay (LCD)Liquid crystal, back lit, graphictype, 320 x 240 pixelCPUsHot back-up redundant configuration- MSMX-U1 002-1RJ45- MSMX-U1 002-2Fibre opticBasic cards- MSMX-T8004Default inputs/outputs- MSMX-U1 006-1Display + keyboard- MSMX-E2003BackplaneELECTRONIC MODULARITY ON ADDITIONAL RACKSBasic and terminal cards- MSMX-E2001 -1Ribbon cable connector (IDC)- MSMX-E2001 -2Heavy duty connector- MSMX-T8001 /8003Terminal block module (cable plug)- MSMX-T8006/8007Relay- MSMX-E2002Rack controller (and internal bus)ADDITIONAL CARDS ON EXPANSION RACKS (MAXIMUM 8 RACKS)- MSMX-F3002 Eight inputs, conventional detection- MSMX-F4001 One 4-20 mA analogue input- MSMX-F4002 Two 4-20 mA analogue inputs- MSMX-F4003 Eight 4-20 mA analogue inputs- MSMX-F5001 Eight 500 mA monitored outputs- MSMX-F5002 Sixteen open collector outputs- MSMX-F5003 Eight polarity reversal-monitored outputs- MSMX-F5004 Four monitored outputs- MSMX-F6001 Fire extinguishing control, certified to EN1 2094-1- MSMX-F6002 Special logic control- MSMX-F7002 Analogue addressable loop control, ESP protocol- MSMX-F7007 Analogue addressable loop control, SSP protocol- MSMX-F7006 MODBUS RTUAPPROVALSIMQ-certified to EN 54-2 and EN 54-4 (fire detection)IMQ-certified to CEI 79-2 (intruder alarm)CPD-certified to EN 1 2094-1 (fire extinguishing)TUV-certified to IEC61 508 (functional safety) SIL 2 & 3
Kabelgaten 8, kern NringsparkP.O. Box 31 4, kern, NO-051 1 Oslo, NorwayTel. +47 2264 5055Email: [email protected]
Simtronics SAS
792, av de la FleurideBP 1 1 061 , 1 3781 Aubagne Cedex - FranceTel : +33 (0)4 42 1 8 06 00Email: [email protected]
Specifications subject to changes without prior notice. R01 /201 4.
GENERALBase rackExpansionCard installationCard replacement