F6Test Relay Test Report
Test Result Details 17-feb-15
CASA COMPRESORA/TB COMPRESORA/SEL 351A
CASA COMPRESORA/TB COMPRESORA Location Path
Relay Under Test General Parameters
A-B-C Vn
In 2000.000%
SEL 351A
1000.00%
120 : 1 CTR
Phase Names And Rotation
Max Test Voltage
Max Test Current
Model
A V (Ph-Ph) Hz
5.000 69.00
60.000
2 : 1
CASA COMPRESORA
1111540235
In Vn fn
SEL
SEL 351A
VTR
Nominal Ratings:
Station Name
Manufacturer
Serial Number
Relay Name
Protected Object Parameters
TB COMPRESORA Protected Object Name
Protected Object Parameters
Test Name Test Type Ramp Pickup Etapa 1
Pickup Etapa 1
Pass Evaluation Edwin
Pickup Etapa 1=59Hz
Tested By
Tested Date
Test Definition Description
Test Definition Name
11/01/2015
Ramp Result
Expected Test Objective Actual -tol [Hz] +tol [Hz] Error[Hz] Eval
[Hz] [Hz]
0.000 Pass 0.002 59.000 59.000 Pickup etapa 1 0.002
EDP PROYECTOS S.A.C Page 1 of 35
F6Test Relay Test Report
Test Result Details 17-feb-15
CASA COMPRESORA/TB COMPRESORA/SEL 351A
CASA COMPRESORA/TB COMPRESORA Location Path
Test Name Test Type VF-Char Tiempo de Operación etapa 1
Tiempo de Operación etapa 1
Pass Evaluation Edwin
Pickup =59Hz t=0.15s
Tested By
Tested Date
Test Definition Description
Test Definition Name
11/01/2015
Relay Functions
Function Type f1 Frequency Function Name Display Values in Inherent Operating Time ms 0 Secondary
General Tolerances
ms 150.0 Absolute Minimum Time Absolute Minimum Current Hz 0.000
Fault
Type Element
Type Characteristic Name
Hz
Pickup Setting Time
+% -%
Frequency
Tolerance
+% -%
Time Tolerance
x fn
SEL Definite Time 59.0000 F< Ph-N 0.9833 1.0000 1.0000 10.0000 10.0000 0.1500
EDP PROYECTOS S.A.C Page 2 of 35
Test Result Details 17-feb-15
CASA COMPRESORA/TB COMPRESORA/SEL 351A
t exp t min t max t act Eval Frequency Value [x f Set] [ms] [ms] [ms] [ms] [Hz] [% ]
Error
Under
1.000 Pass 300.0 2.0 197.6 150.0 31.7 58.9863
1.000 Pass 300.0 2.0 192.8 150.0 28.5 58.9827
0.999 Pass 300.0 2.0 193.8 150.0 29.2 58.9651
0.999 Pass 300.0 2.0 191.9 150.0 27.9 58.9597
0.999 Pass 300.0 2.0 191.3 150.0 27.5 58.9536
Under
Test Name Test Type Ramp Derivada
df/dt=-1.00 Hz/s (No Op)
NoOp Evaluation Edwin
Pendiente = -1.00.................Se espera que No Opere
Tested By
Tested Date
Test Definition Description
Test Definition Name
11/01/2015
EDP PROYECTOS S.A.C Page 3 of 35
Test Result Details 17-feb-15
CASA COMPRESORA/TB COMPRESORA/SEL 351A
Ramp Result
Expected Test Objective Actual -tol [Hz] +tol [Hz] Error[Hz] Eval
[Hz] [Hz]
NoOp df/dt=-1.0Hz/s (No Op)
Test Name Test Type Ramp Derivada
df/dt=-1.04 Hz/s (No Op)
NoOp Evaluation Edwin
Pendiente = -1.04.................Se espera que No Opere
Tested By
Tested Date
Test Definition Description
Test Definition Name
11/01/2015
EDP PROYECTOS S.A.C Page 4 of 35
Test Result Details 17-feb-15
CASA COMPRESORA/TB COMPRESORA/SEL 351A
Ramp Result
Expected Test Objective Actual -tol [Hz] +tol [Hz] Error[Hz] Eval
[Hz] [Hz]
NoOp df/dt=-1.04Hz/s (No Op)
Test Name Test Type Ramp Derivada
dfdt=-1.05 Hzs (Op)
Op Evaluation Edwin
Pendiente = -1.05.................Se espera que Opere
Tested By
Tested Date
Test Definition Description
Test Definition Name
11/01/2015
EDP PROYECTOS S.A.C Page 5 of 35
Test Result Details 17-feb-15
CASA COMPRESORA/TB COMPRESORA/SEL 351A
Ramp Result
Expected Test Objective Actual -tol [Hz] +tol [Hz] Error[Hz] Eval
[Hz] [Hz]
-0.080 Op 59.598 59.678 df/dt=-1.05Hz/s (Op)
Test Name Test Type Ramp Derivada
df/dt=-1.1 Hz/s (Op)
Op Evaluation Edwin
Pendiente = -1.10.................Se espera que Opere
Tested By
Tested Date
Test Definition Description
Test Definition Name
11/01/2015
EDP PROYECTOS S.A.C Page 6 of 35
Test Result Details 17-feb-15
CASA COMPRESORA/TB COMPRESORA/SEL 351A
Ramp Result
Expected Test Objective Actual -tol [Hz] +tol [Hz] Error[Hz] Eval
[Hz] [Hz]
-0.093 Op 59.579 59.672 df/dt=-1.1Hz/s (Op)
Test Name Test Type Ramp Derivada
dfdt=-1.2 Hzs (Op)
Op Evaluation Edwin
Pendiente = -1.2.................Se espera que Opere
Tested By
Tested Date
Test Definition Description
Test Definition Name
11/01/2015
EDP PROYECTOS S.A.C Page 7 of 35
Test Result Details 17-feb-15
CASA COMPRESORA/TB COMPRESORA/SEL 351A
Ramp Result
Expected Test Objective Actual -tol [Hz] +tol [Hz] Error[Hz] Eval
[Hz] [Hz]
-0.078 Op 59.582 59.660 df/dt=-1.2Hz/s (Op)
EDP PROYECTOS S.A.C Page 8 of 35
F6Test Relay Test Report
Test Result Details 17-feb-15
CASA COMPRESORA/TB COMPRESORA/SEL 351A
CASA COMPRESORA/TB COMPRESORA Location Path
Test Name Test Type Ramp Pickup Etapa 2
Pickup Etapa 2
Pass Evaluation Edwin
Pickup Etapa 2=58.9Hz
Tested By
Tested Date
Test Definition Description
Test Definition Name
11/01/2015
Ramp Result
Expected Test Objective Actual -tol [Hz] +tol [Hz] Error[Hz] Eval
[Hz] [Hz]
0.001 Pass 0.002 58.901 58.900 Pickup etapa 2 0.002
EDP PROYECTOS S.A.C Page 9 of 35
F6Test Relay Test Report
Test Result Details 17-feb-15
CASA COMPRESORA/TB COMPRESORA/SEL 351A
CASA COMPRESORA/TB COMPRESORA Location Path
Test Name Test Type VF-Char Tiempo de Operación etapa 2
Tiempo de Operación etapa 2
Pass Evaluation Edwin
Pickup =58.9Hz t=0.15s
Tested By
Tested Date
Test Definition Description
Test Definition Name
11/01/2015
Relay Functions
Function Type f2 Frequency Function Name Display Values in Inherent Operating Time ms 0 Secondary
General Tolerances
ms 150.0 Absolute Minimum Time Absolute Minimum Current Hz 0.000
Fault
Type Element
Type Characteristic Name
Hz
Pickup Setting Time
+% -%
Frequency
Tolerance
+% -%
Time Tolerance
x fn
SEL Definite Time 58.9000 F< Ph-N 0.9817 1.0000 1.0000 10.0000 10.0000 0.1500
EDP PROYECTOS S.A.C Page 10 of 35
Test Result Details 17-feb-15
CASA COMPRESORA/TB COMPRESORA/SEL 351A
t exp t min t max t act Eval Frequency Value [x f Set] [ms] [ms] [ms] [ms] [Hz] [% ]
Error
Under
1.000 Pass 300.0 2.0 198.7 150.0 32.5 58.9000
1.000 Pass 300.0 2.0 193.6 150.0 29.1 58.8868
1.000 Pass 300.0 2.0 193.9 150.0 29.3 58.8808
1.000 Pass 300.0 2.0 200.6 150.0 33.7 58.8742
0.999 Pass 300.0 2.0 194.9 150.0 29.9 58.8635
Under
Test Name Test Type Ramp Derivada Etapa 2
dfdt=-1.00 Hzs (No Op)
NoOp Evaluation Edwin
Pendiente = -1.00.................Se espera que no Opere
Tested By
Tested Date
Test Definition Description
Test Definition Name
11/01/2015
EDP PROYECTOS S.A.C Page 11 of 35
Test Result Details 17-feb-15
CASA COMPRESORA/TB COMPRESORA/SEL 351A
Ramp Result
Expected Test Objective Actual -tol [Hz] +tol [Hz] Error[Hz] Eval
[Hz] [Hz]
NoOp df/dt=-1.0Hz/s (No Op)
Test Name Test Type Ramp Derivada Etapa 2
dfdt=-1.04 Hzs (No Op)
NoOp Evaluation Edwin
Pendiente = -1.04.................Se espera que no Opere
Tested By
Tested Date
Test Definition Description
Test Definition Name
11/01/2015
EDP PROYECTOS S.A.C Page 12 of 35
Test Result Details 17-feb-15
CASA COMPRESORA/TB COMPRESORA/SEL 351A
Ramp Result
Expected Test Objective Actual -tol [Hz] +tol [Hz] Error[Hz] Eval
[Hz] [Hz]
NoOp df/dt=-1.04Hz/s (No Op)
Test Name Test Type Ramp Derivada Etapa 2
dfdt=-1.05 Hzs (Op)
Op Evaluation Edwin
Pendiente = -1.05.................Se espera que Opere
Tested By
Tested Date
Test Definition Description
Test Definition Name
11/01/2015
EDP PROYECTOS S.A.C Page 13 of 35
Test Result Details 17-feb-15
CASA COMPRESORA/TB COMPRESORA/SEL 351A
Ramp Result
Expected Test Objective Actual -tol [Hz] +tol [Hz] Error[Hz] Eval
[Hz] [Hz]
-0.080 Op 59.598 59.678 df/dt=-1.05Hz/s (Op)
Test Name Test Type Ramp Derivada Etapa 2
dfdt=-1.1 Hzs (Op)
Op Evaluation Edwin
Pendiente = -1.1.................Se espera que Opere
Tested By
Tested Date
Test Definition Description
Test Definition Name
11/01/2015
EDP PROYECTOS S.A.C Page 14 of 35
Test Result Details 17-feb-15
CASA COMPRESORA/TB COMPRESORA/SEL 351A
Ramp Result
Expected Test Objective Actual -tol [Hz] +tol [Hz] Error[Hz] Eval
[Hz] [Hz]
-0.075 Op 59.597 59.672 df/dt=-1.1Hz/s (Op)
Test Name Test Type Ramp Derivada Etapa 2
dfdt=-1.2 Hzs (Op)
Op Evaluation Edwin
Pendiente = -1.2.................Se espera que Opere
Tested By
Tested Date
Test Definition Description
Test Definition Name
11/01/2015
EDP PROYECTOS S.A.C Page 15 of 35
Test Result Details 17-feb-15
CASA COMPRESORA/TB COMPRESORA/SEL 351A
Ramp Result
Expected Test Objective Actual -tol [Hz] +tol [Hz] Error[Hz] Eval
[Hz] [Hz]
-0.078 Op 59.582 59.660 df/dt=-1.2Hz/s (Op)
EDP PROYECTOS S.A.C Page 16 of 35
F6Test Relay Test Report
Test Result Details 17-feb-15
CASA COMPRESORA/TB COMPRESORA/SEL 351A
CASA COMPRESORA/TB COMPRESORA Location Path
Test Name Test Type Ramp Pickup Etapa 3
Pickup Etapa 3
Pass Evaluation Edwin
Pickup Etapa 3=58.8Hz
Tested By
Tested Date
Test Definition Description
Test Definition Name
11/01/2015
Ramp Result
Expected Test Objective Actual -tol [Hz] +tol [Hz] Error[Hz] Eval
[Hz] [Hz]
0.001 Pass 0.002 58.801 58.800 Pickup etapa 3 0.002
EDP PROYECTOS S.A.C Page 17 of 35
F6Test Relay Test Report
Test Result Details 17-feb-15
CASA COMPRESORA/TB COMPRESORA/SEL 351A
CASA COMPRESORA/TB COMPRESORA Location Path
Test Name Test Type VF-Char Tiempo de Operación etapa 3
Tiempo de Operación etapa 3
Pass Evaluation Edwin
Pickup =58.8Hz t=0.15s
Tested By
Tested Date
Test Definition Description
Test Definition Name
11/01/2015
Relay Functions
Function Type f3 Frequency Function Name Display Values in Inherent Operating Time ms 0 Secondary
General Tolerances
ms 150.0 Absolute Minimum Time Absolute Minimum Current Hz 0.000
Fault
Type Element
Type Characteristic Name
Hz
Pickup Setting Time
+% -%
Frequency
Tolerance
+% -%
Time Tolerance
x fn
SEL Definite Time 58.8000 F< Ph-N 0.9800 1.0000 1.0000 10.0000 10.0000 0.1500
EDP PROYECTOS S.A.C Page 18 of 35
Test Result Details 17-feb-15
CASA COMPRESORA/TB COMPRESORA/SEL 351A
t exp t min t max t act Eval Frequency Value [x f Set] [ms] [ms] [ms] [ms] [Hz] [% ]
Error
Under
1.000 Pass 300.0 2.0 193.5 150.0 29.0 58.7916
1.000 Pass 300.0 2.0 210.9 150.0 40.6 58.7772
0.999 Pass 300.0 2.0 209.5 150.0 39.7 58.7580
0.999 Pass 300.0 2.0 210.7 150.0 40.5 58.7399
0.999 Pass 300.0 2.0 212.5 150.0 41.7 58.7291
Under
Test Name Test Type Ramp Derivada Etapa 3
dfdt=-1.00 Hzs (No Op)
NoOp Evaluation Edwin
Pendiente = -1.00.................Se espera que no Opere
Tested By
Tested Date
Test Definition Description
Test Definition Name
11/01/2015
EDP PROYECTOS S.A.C Page 19 of 35
Test Result Details 17-feb-15
CASA COMPRESORA/TB COMPRESORA/SEL 351A
Ramp Result
Expected Test Objective Actual -tol [Hz] +tol [Hz] Error[Hz] Eval
[Hz] [Hz]
NoOp df/dt=-1.0Hz/s (No Op)
Test Name Test Type Ramp Derivada Etapa 3
dfdt=-1.04 Hzs (No Op)
NoOp Evaluation Edwin
Pendiente = -1.04.................Se espera que no Opere
Tested By
Tested Date
Test Definition Description
Test Definition Name
11/01/2015
EDP PROYECTOS S.A.C Page 20 of 35
Test Result Details 17-feb-15
CASA COMPRESORA/TB COMPRESORA/SEL 351A
Ramp Result
Expected Test Objective Actual -tol [Hz] +tol [Hz] Error[Hz] Eval
[Hz] [Hz]
NoOp df/dt=-1.04Hz/s (No Op)
Test Name Test Type Ramp Derivada Etapa 3
dfdt=-1.05 Hzs (Op)
Op Evaluation Edwin
Pendiente = -1.05.................Se espera que Opere
Tested By
Tested Date
Test Definition Description
Test Definition Name
11/01/2015
EDP PROYECTOS S.A.C Page 21 of 35
Test Result Details 17-feb-15
CASA COMPRESORA/TB COMPRESORA/SEL 351A
Ramp Result
Expected Test Objective Actual -tol [Hz] +tol [Hz] Error[Hz] Eval
[Hz] [Hz]
-0.080 Op 59.598 59.678 df/dt=-1.05Hz/s (Op)
Test Name Test Type Ramp Derivada Etapa 3
dfdt=-1.1 Hzs (Op)
Op Evaluation Edwin
Pendiente = -1.1.................Se espera que Opere
Tested By
Tested Date
Test Definition Description
Test Definition Name
11/01/2015
EDP PROYECTOS S.A.C Page 22 of 35
Test Result Details 17-feb-15
CASA COMPRESORA/TB COMPRESORA/SEL 351A
Ramp Result
Expected Test Objective Actual -tol [Hz] +tol [Hz] Error[Hz] Eval
[Hz] [Hz]
-0.075 Op 59.597 59.672 df/dt=-1.1Hz/s (Op)
Test Name Test Type Ramp Derivada Etapa 3
dfdt=-1.2 Hzs (Op)
Op Evaluation Edwin
Pendiente = -1.2.................Se espera que Opere
Tested By
Tested Date
Test Definition Description
Test Definition Name
11/01/2015
EDP PROYECTOS S.A.C Page 23 of 35
Test Result Details 17-feb-15
CASA COMPRESORA/TB COMPRESORA/SEL 351A
Ramp Result
Expected Test Objective Actual -tol [Hz] +tol [Hz] Error[Hz] Eval
[Hz] [Hz]
-0.078 Op 59.582 59.660 df/dt=-1.2Hz/s (Op)
EDP PROYECTOS S.A.C Page 24 of 35
F6Test Relay Test Report
Test Result Details 17-feb-15
SE CHIPMO/CELDA SSAA/SEL 351A
SE CHIPMO/CELDA SSAA Location Path
Test Name Test Type Ramp Pickup Etapa 4
Pickup Etapa 4
Pass Evaluation Edwin
Pickup Etapa 4=58.7Hz
Tested By
Tested Date
Test Definition Description
Test Definition Name
11/01/2015
Ramp Result
Expected Test Objective Actual -tol [Hz] +tol [Hz] Error[Hz] Eval
[Hz] [Hz]
0.001 Pass 0.002 58.701 58.700 Pickup etapa 4 0.002
EDP PROYECTOS S.A.C Page 25 of 35
F6Test Relay Test Report
Test Result Details 17-feb-15
SE CHIPMO/CELDA SSAA/SEL 351A
SE CHIPMO/CELDA SSAA Location Path
Test Name Test Type VF-Char Tiempo de Operación etapa 4
Tiempo de Operación etapa 4
Pass Evaluation Edwin
Pickup =58.7Hz t=0.15s
Tested By
Tested Date
Test Definition Description
Test Definition Name
11/01/2015
Relay Functions
Function Type f4 Frequency Function Name Display values in Inherent Op Time ms 0 Secondary
General Tolerances
ms 150.0 Absolute Minimum Time Absolute Minimum Hz 0.000
Fault
Type Element
Type Characteristic Name
Hz
Pickup Setting Time
+% -%
Frequency
Tolerance
+% -%
Time Tolerance
x fn
SEL Definite Time 58.6980 F< Ph-N 0.9783 1.0000 1.0000 10.0000 10.0000 0.1500
EDP PROYECTOS S.A.C Page 26 of 35
Test Result Details 17-feb-15
SE CHIPMO/CELDA SSAA/SEL 351A
t exp t min t max t act Eval Frequency Value [x f Set] [ms] [ms] [ms] [ms] [Hz] [% ]
Error
Under
1.000 Pass 300.0 2.0 206.3 150.0 37.5 58.6893
1.000 Pass 300.0 2.0 198.5 150.0 32.3 58.6817
0.999 Pass 300.0 2.0 208.3 150.0 38.9 58.6653
0.999 Pass 300.0 2.0 209.6 150.0 39.7 58.6543
0.999 Pass 300.0 2.0 212.1 150.0 41.4 58.6362
Under
EDP PROYECTOS S.A.C Page 27 of 35
F6Test Relay Test Report
Test Result Details 17-feb-15
SE MANTO- PLANTA/CELDA SEP 04/SEL 351A
SE MANTO- PLANTA/CELDA SEP 04 Location Path
Test Name Test Type Ramp Pickup Etapa 5
Pickup Etapa 5
Pass Evaluation Edwin
Pickup Etapa 5=58.6Hz
Tested By
Tested Date
Test Definition Description
Test Definition Name
11/01/2015
Ramp Result
Expected Test Objective Actual -tol [Hz] +tol [Hz] Error[Hz] Eval
[Hz] [Hz]
0.001 Pass 0.002 58.601 58.600 Pickup etapa 5 0.002
Test Name Test Type VF-Char Tiempo de Operación etapa 5
Tiempo de Operación etapa 5
Pass Evaluation Edwin
Pickup =58.6Hz t=0.15s
Tested By
Tested Date
Test Definition Description
Test Definition Name
11/01/2015
Relay Functions
Function Type f5 Frequency Function Name Display values in Inherent Op Time ms 0 Secondary
General Tolerances
ms 150.0 Absolute Minimum Time Absolute Minimum Hz 0.000
EDP PROYECTOS S.A.C Page 28 of 35
Test Result Details 17-feb-15
SE MANTO- PLANTA/CELDA SEP 04/SEL 351A
Fault
Type Element
Type Characteristic Name
Hz
Pickup Setting Time
+% -%
Frequency
Tolerance
+% -%
Time Tolerance
x fn
SEL Definite Time 58.6020 F< Ph-N 0.9767 1.0000 1.0000 10.0000 10.0000 0.1500
t exp t min t max t act Eval Frequency Value [x f Set] [s] [s] [s] [s] [Hz] [% ]
Error
Under
0.998 Pass 0.3000 0.0020 0.2144 0.1500 42.9333 58.4800
0.997 Pass 0.3000 0.0020 0.2088 0.1500 39.2000 58.4300
0.995 Pass 0.3000 0.0020 0.2046 0.1500 36.4000 58.3100
0.993 Pass 0.3000 0.0020 0.2054 0.1500 36.9333 58.1900
0.990 Pass 0.3000 0.0020 0.2039 0.1500 35.9333 58.0200
Under
EDP PROYECTOS S.A.C Page 29 of 35
F6Test Relay Test Report
Test Result Details 17-feb-15
SE MANTO- PLANTA/CELDA SEP 04/SEL 351A
SE MANTO- PLANTA/CELDA SEP 04 Location Path
Test Name Test Type Ramp Pickup Etapa 6
Pickup Etapa 6
Pass Evaluation Edwin
Pickup Etapa 6=57.5Hz
Tested By
Tested Date
Test Definition Description
Test Definition Name
11/01/2015
Ramp Result
Expected Test Objective Actual -tol [Hz] +tol [Hz] Error[Hz] Eval
[Hz] [Hz]
0.001 Pass 0.002 57.501 57.500 Pickup etapa 6 0.002
EDP PROYECTOS S.A.C Page 30 of 35
F6Test Relay Test Report
Test Result Details 17-feb-15
SE MANTO- PLANTA/CELDA SEP 04/SEL 351A
SE MANTO- PLANTA/CELDA SEP 04 Location Path
Test Name Test Type VF-Char Tiempo de Operación etapa 6
Tiempo de Operación etapa 6
Pass Evaluation Edwin
Pickup =57.5Hz t=0.15s
Tested By
Tested Date
Test Definition Description
Test Definition Name
11/01/2015
Relay Functions
Function Type f6 Frequency Function Name Display values in Inherent Op Time ms 0 Secondary
General Tolerances
ms 150.0 Absolute Minimum Time Absolute Minimum Hz 0.000
Fault
Type Element
Type Characteristic Name
Hz
Pickup Setting Time
+% -%
Frequency
Tolerance
+% -%
Time Tolerance
x fn
SEL Definite Time 57.5000 F< Ph-N 0.9583 1.0000 1.0000 10.0000 10.0000 0.1500
EDP PROYECTOS S.A.C Page 31 of 35
Test Result Details 17-feb-15
SE MANTO- PLANTA/CELDA SEP 04/SEL 351A
t exp t min t max t act Eval Frequency Value [x f Set] [s] [s] [s] [s] [Hz] [% ]
Error
Under
0.999 Pass 0.3000 0.0020 0.2080 0.1500 38.6667 57.4400
0.997 Pass 0.3000 0.0020 0.2119 0.1500 41.2667 57.3300
0.995 Pass 0.3000 0.0020 0.2015 0.1500 34.3333 57.2100
0.993 Pass 0.3000 0.0020 0.2093 0.1500 39.5333 57.1000
0.991 Pass 0.3000 0.0020 0.2099 0.1500 39.9333 56.9800
Under
EDP PROYECTOS S.A.C Page 32 of 35
F6Test Relay Test Report
Test Result Details 17-feb-15
SE MANTO- PLANTA/CELDA SEP 04/SEL 351A
SE MANTO- PLANTA/CELDA SEP 04 Location Path
Test Name Test Type Ramp Pickup Etapa 7
Pickup Etapa 7
Pass Evaluation Edwin
Pickup Etapa 7=59.1Hz
Tested By
Tested Date
Test Definition Description
Test Definition Name
11/01/2015
Ramp Result
Expected Test Objective Actual -tol [Hz] +tol [Hz] Error[Hz] Eval
[Hz] [Hz]
0.001 Pass 0.002 59.101 59.100 Pickup etapa 7 0.002
EDP PROYECTOS S.A.C Page 33 of 35
F6Test Relay Test Report
Test Result Details 17-feb-15
SE MANTO- PLANTA/CELDA SEP 04/SEL 351A
SE MANTO- PLANTA/CELDA SEP 04 Location Path
Test Name Test Type VF-Char Tiempo de Operación etapa 7
Tiempo de Operación etapa 7
Pass Evaluation Edwin
Pickup =59Hz t=30s
Tested By
Tested Date
Test Definition Description
Test Definition Name
11/01/2015
Relay Functions
Function Type f7 Frequency Function Name Display values in Inherent Op Time ms 0 Secondary
General Tolerances
ms 150.0 Absolute Minimum Time Absolute Minimum Hz 0.000
Fault
Type Element
Type Characteristic Name
Hz
Pickup Setting Time
+% -%
Frequency
Tolerance
+% -%
Time Tolerance
x fn
SEL Definite Time 59.1000 F< Ph-N 0.9850 1.0000 1.0000 10.0000 10.0000 30.0000
EDP PROYECTOS S.A.C Page 34 of 35
Test Result Details 17-feb-15
SE MANTO- PLANTA/CELDA SEP 04/SEL 351A
t exp t min t max t act Eval Frequency Value [x f Set] [s] [s] [s] [s] [Hz] [% ]
Error
Under
0.999 Pass 33.0000 27.0000 30.4965 30.0000 1.6550 59.0400
0.997 Pass 33.0000 27.0000 30.5771 30.0000 1.9237 58.9200
0.995 Pass 33.0000 27.0000 30.6191 30.0000 2.0637 58.8000
Under