T/PI PRT Insertion Temperature Sensor Installation Instructions TG200825 Issue 3, 03-Aug-2015. 1 Installation Instructions T/PI PRT Insertion Temperature Sensor Important: Retain these instructions These instructions shall be used by trained service personnel only. If the equipment is used in a manner not specified by these instructions, the protection provided by the equipment may be impaired. https://partners.trendcontrols.com 1 Dimensions 2 INSTALLATION 1 BOX CONTENTS T/PI Installation Instructions (TG200825) Pockets for use as immersion sensor; Brass (WB150) Stainless Steel (WS150) 6 mm (0.24”) T/PI-L 400 mm (15.75”) T/PI-S 150 mm (5.91”) 85 mm (3.35”) ACC/DF 105 mm (4.13”) 50 mm (1.97”) 6 mm compression fitting 3 x 4 mm diam. holes on a 30 mm (1.18”) pitch diameter Mounting flange for use as duct sensor Universal Fitting Kit for immersion sensor use in existing pockets clip spring brass bush hexagonal socket grub screw 57 mm (2.24”) 135 mm (5.31”) 14 mm (0.53”) 24 mm (0.95”) Ø8 mm (0.31”) 143 mm (5.63”) Ø6.5 mm (0.25”) R½” (BSPT)

PRT Insertion Temperature Sensor

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

T/PI Installation InstructionsInstallation Instructions
Important: Retain these instructions
These instructions shall be used by trained service personnel only. If the equipment is used in a manner not specified by these instructions, the protection provided by the equipment may be impaired. https://partners.trendcontrols.com
1 Dimensions
2 InSTallaTIon
T/PI Installation Instructions (TG200825)
Pockets for use as immersion sensor; Brass (WB150) Stainless Steel (WS150)
6 m
m (0
.2 4”
85 m
m (3
.3 5”
6 mm compression fitting
3 x 4 mm diam. holes on a 30 mm (1.18”) pitch diameter
Mounting flange for use as duct sensor Universal Fitting Kit for immersion sensor use in existing pockets
clip
2 T/PI PRT Insertion Temperature Sensor Installation Instructions TG200825 Issue 3, 03-Aug-2015.
T/PI Installation Instructions
d
+40 °C (104 °F)
+110 °C (230 °F)
+50 °C (122 °F)
-40 °C (-40 °F)
+50 °C (+122 °F)
Ensure no stratification (e.g. downstream of mixing dampers, heating coils, cooling coils) otherwise use averaging sensor.
Duct
Immersion
Cl2
Note: WS150 or WB150 are NOT suitable for use in chlorine rich environments
Immersion
Installation Instructions T/PI
Drill hole for boss Fix threaded boss
½” BSPT threaded boss
tighten screws
(if using Universal Fixing Kit)
Push adaptor onto probe Adjust probe length *Mount in pocket
if pocket has grub screw, discard spring and clip
clip
spring
pocket length
tighten screw over bush
Install Sensor into Pocket
if pocket has clip retaining groove, push clip over pocket
*If used for chilled water ensure pocket is sealed around probe or fi ll pocket with thermally conducting oil to avoid the build up of condensation in bottom of pocket.
use M24 Spanner
apply sealent to boss thread
either: (if using new pocket) or: (if using old pocket with grub screws)
4 T/PI PRT Insertion Temperature Sensor Installation Instructions TG200825 Issue 3, 03-Aug-2015.
T/PI Installation Instructions
Drill hole in duct
Ø 7 mm (0.28”)
Drill 2 pilot holes
integral foam gasket
compression fi tting
Or: (for thinner material) use complete mounting fl ange
Either: (for thicker material) use compression fi tting only
drill and tap 1/8” BSPT
>6 mm
30 mm (1.18”)
drill 3 holes screw on fl ange mounted fl ange
Either: Or:
Installation Instructions T/PI
5 Remove lid
6 Remove Connector
7 Insert Cable
2 InSTallaTIon (continued)
Either: use M20 fl exible conduit Or: use M16 cable gland
IQ controller
polarity independent
Analogue input channel confi gured for current (I)
IQ system TP/I/22/HF/200-600V (Belden 8761) cable recommended. Terminal size 0.5 to 2.5 mm2 (20 to 14 AWG)
Note: if connecting to an IQ22x controller (including /ADL or / OC), do not connect directly to C (+24V), instead connect to AUX+ (+24V).
Caution: This unit contains static sensitive devices. Suitable anti-static precautions should be taken
throughtout the operation to prevent damage to the units. BS EN100015/1 Basic Specifi cation: protection of electrostatic sensitive devices.
6 T/PI PRT Insertion Temperature Sensor Installation Instructions TG200825 Issue 3, 03-Aug-2015.
T/PI Installation Instructions
9 Replace Connector
10 Replace lid
2 InSTallaTIon (continued)
Note: IP67 (NEMA6) rating is only achieved if the sensor is correctly installed with cable or conduit connection fully tightened.
IQ
IQ Confi guration Manual (90-1533) IQ3 Confi guration Manual (TE200768) IQ4 Confi guration Manual (TE201263) IQeco Confi guration Manual (TE201089)
IQ
or
Installation Instructions T/PI
13 Test System
2 InSTallaTIon (continued)
It is recommended to use SET (Software Tool) for the setting of the sensor type module. For all IQ2 series controllers with firmware version 2.1 or greater, or IQ3/4 series controllers, the following SET Unique Sensor References should be used:
PRT I -10+40 (T/PI/40, °C) PRT I +14+104 F (T/PI/40, °F) PRT I -10+110 (T/PI/110, °C) PRT I +14+230 F (T/PI/110, °F) PRT I -40+50 (T/PI/-40, °C) PRT I -40+122 F (T/PI/-40, °F)
Alternatively set scaling mode to 5 (characterise) and enter scaling manually as defined in the appropriate table.
Note: for IQ3/4, the scaling mode and exponent do not need to be set up.
For all other IQ controllers see Sensor Scaling Reference Card (TB100521A).
Unit /40 /110 /-40
E Exponent 3 3 3
Units °C °F °C °F °C °F
U Upper 40 104 110 230 50 122
L Lower -10 14 -10 14 -40 -40
P Points 2 2 2 2 2 2
x Ix Ox Ox Ox Ox Ox Ox
1 4 -10 14 -10 14 -40 -40
2 20 40 104 110 230 50 122
TIQ
8 T/PI PRT Insertion Temperature Sensor Installation Instructions TG200825 Issue 3, 03-Aug-2015.
T/PI Installation Instructions
Please send any comments about this or any other Trend technical publication to [email protected]