T/PI Installation InstructionsInstallation Instructions
Important: Retain these instructions
These instructions shall be used by trained service personnel only.
If the equipment is used in a manner not specified by these
instructions, the protection provided by the equipment may be
impaired. https://partners.trendcontrols.com
1 Dimensions
2 InSTallaTIon
T/PI Installation Instructions (TG200825)
Pockets for use as immersion sensor; Brass (WB150) Stainless Steel
(WS150)
6 m
m (0
.2 4”
85 m
m (3
.3 5”
6 mm compression fitting
3 x 4 mm diam. holes on a 30 mm (1.18”) pitch diameter
Mounting flange for use as duct sensor Universal Fitting Kit for
immersion sensor use in existing pockets
clip
2 T/PI PRT Insertion Temperature Sensor Installation Instructions
TG200825 Issue 3, 03-Aug-2015.
T/PI Installation Instructions
d
+40 °C (104 °F)
+110 °C (230 °F)
+50 °C (122 °F)
-40 °C (-40 °F)
+50 °C (+122 °F)
Ensure no stratification (e.g. downstream of mixing dampers,
heating coils, cooling coils) otherwise use averaging sensor.
Duct
Immersion
Cl2
Note: WS150 or WB150 are NOT suitable for use in chlorine rich
environments
Immersion
Installation Instructions T/PI
Drill hole for boss Fix threaded boss
½” BSPT threaded boss
tighten screws
(if using Universal Fixing Kit)
Push adaptor onto probe Adjust probe length *Mount in pocket
if pocket has grub screw, discard spring and clip
clip
spring
pocket length
tighten screw over bush
Install Sensor into Pocket
if pocket has clip retaining groove, push clip over pocket
*If used for chilled water ensure pocket is sealed around probe or
fi ll pocket with thermally conducting oil to avoid the build up of
condensation in bottom of pocket.
use M24 Spanner
apply sealent to boss thread
either: (if using new pocket) or: (if using old pocket with grub
screws)
4 T/PI PRT Insertion Temperature Sensor Installation Instructions
TG200825 Issue 3, 03-Aug-2015.
T/PI Installation Instructions
Drill hole in duct
Ø 7 mm (0.28”)
Drill 2 pilot holes
integral foam gasket
compression fi tting
Or: (for thinner material) use complete mounting fl ange
Either: (for thicker material) use compression fi tting only
drill and tap 1/8” BSPT
>6 mm
30 mm (1.18”)
drill 3 holes screw on fl ange mounted fl ange
Either: Or:
Installation Instructions T/PI
5 Remove lid
6 Remove Connector
7 Insert Cable
2 InSTallaTIon (continued)
Either: use M20 fl exible conduit Or: use M16 cable gland
IQ controller
polarity independent
Analogue input channel confi gured for current (I)
IQ system TP/I/22/HF/200-600V (Belden 8761) cable recommended.
Terminal size 0.5 to 2.5 mm2 (20 to 14 AWG)
Note: if connecting to an IQ22x controller (including /ADL or /
OC), do not connect directly to C (+24V), instead connect to AUX+
(+24V).
Caution: This unit contains static sensitive devices. Suitable
anti-static precautions should be taken
throughtout the operation to prevent damage to the units. BS
EN100015/1 Basic Specifi cation: protection of electrostatic
sensitive devices.
6 T/PI PRT Insertion Temperature Sensor Installation Instructions
TG200825 Issue 3, 03-Aug-2015.
T/PI Installation Instructions
9 Replace Connector
10 Replace lid
2 InSTallaTIon (continued)
Note: IP67 (NEMA6) rating is only achieved if the sensor is
correctly installed with cable or conduit connection fully
tightened.
IQ
IQ Confi guration Manual (90-1533) IQ3 Confi guration Manual
(TE200768) IQ4 Confi guration Manual (TE201263) IQeco Confi
guration Manual (TE201089)
IQ
or
Installation Instructions T/PI
13 Test System
2 InSTallaTIon (continued)
It is recommended to use SET (Software Tool) for the setting of the
sensor type module. For all IQ2 series controllers with firmware
version 2.1 or greater, or IQ3/4 series controllers, the following
SET Unique Sensor References should be used:
PRT I -10+40 (T/PI/40, °C) PRT I +14+104 F (T/PI/40, °F) PRT I
-10+110 (T/PI/110, °C) PRT I +14+230 F (T/PI/110, °F) PRT I -40+50
(T/PI/-40, °C) PRT I -40+122 F (T/PI/-40, °F)
Alternatively set scaling mode to 5 (characterise) and enter
scaling manually as defined in the appropriate table.
Note: for IQ3/4, the scaling mode and exponent do not need to be
set up.
For all other IQ controllers see Sensor Scaling Reference Card
(TB100521A).
Unit /40 /110 /-40
E Exponent 3 3 3
Units °C °F °C °F °C °F
U Upper 40 104 110 230 50 122
L Lower -10 14 -10 14 -40 -40
P Points 2 2 2 2 2 2
x Ix Ox Ox Ox Ox Ox Ox
1 4 -10 14 -10 14 -40 -40
2 20 40 104 110 230 50 122
TIQ
8 T/PI PRT Insertion Temperature Sensor Installation Instructions
TG200825 Issue 3, 03-Aug-2015.
T/PI Installation Instructions
Please send any comments about this or any other Trend technical
publication to
[email protected]
© 2015 Honeywell Technologies Sàrl, ECC Division. All rights
reserved. Manufactured for and on behalf of the Environmental and
Combustion Controls Division of Honeywell Technologies Sàrl, Z.A.
La Pièce, 16, 1180 Rolle, Switzerland by its Authorized
Representative, Trend Control Systems Limited.
Trend Control Systems Limited reserves the right to revise this
publication from time to time and make changes to the content
hereof without obligation to notify any person of such revisions or
changes.