protection of HV motor

Embed Size (px)

Citation preview

  • 7/29/2019 protection of HV motor

    1/28

    E/CT 165 first issed, May 1995

    J.Y. Blanc

    He graduated as an engineer fromSUPELEC in 1979. He joined MerlinGerin in 1981 as Medium Voltagedielectric engineer. Still in theMV Division, he was then in turn asproject manager for the developmentof:

    - Fluair range primary substationsand equipment,- SF set built-in protection circuit-breakers.He is currently in charge ofdevelopment of MV primarydistribution and switchgear.

    n 165

    control/monitoring and

    protection ofHV motors

  • 7/29/2019 protection of HV motor

    2/28

    Cahier Technique Merlin Gerin n 165 / p.2

  • 7/29/2019 protection of HV motor

    3/28

    Cahier Technique Merlin Gerin n 165 / p.3

    control/monitoring and protection ofHV motors

    contents

    1. Reminder of the various types of Asynchronous cage motors p. 4

    Asynchronous slipring p. 5rotor motors

    Synchronous motors p. 6

    Sizing tolerances p. 6

    Dielectric withstand and tests p. 7

    2. Classical HV starting processes Direct stator starting on p. 8full voltage

    Stator starting on reduced p. 8voltage

    Startor starting with capacitors p. 9

    Rotor starting p. 10

    Choosing the starting mode p. 11

    3. Control and monitoring equipment Electromechanical solutions p. 13

    Electronic solutions p. 15

    4. Protection of HV motors Main fault types p. 18Protection principles p. 18

    Technological evolution p. 22

    Appendix 1: determining motor Calculation hypotheses p. 23

    Overall approach p. 23

    Appendix 2: coordination of protection devices p. 25

    Appendix 3: bibliography p. 26

    Unit power of rotating machinesfrequently exceeds 100 kW in industryand large tertiary. In such cases and/orif the length of the supply line is

    particularly long (voltage drops,losses), use of high voltage motors isadvantageous.The purpose of this Cahier Techniqueis to analyse and compare thesemotors, their starting systems and thevarious protection devices which maybe used, in order to simplify technicalchoices.

    AC motors

    starting mode

  • 7/29/2019 protection of HV motor

    4/28

    Cahier Technique Merlin Gerin n 165 / p.4

    current

    torque

    0

    1

    2

    2

    4

    25 % 50 % 75 % 100 % (N/Ns)

    1

    25

    4

    6

    3

    2

    1

    Cn

    In

    current

    torque

    0 25 % 50 % 75 % 100 % (N/Ns)

    Id

    1. reminder of the various types of AC motors

    Both high and low voltage AC motors,offer a large variety of electrical,dynamic and technologicalcharacteristics. However, except for asmall number of motors used for highlyspecific applications, they can bedivided into three families, namely:c asynchronous cage motors;c asynchronous slipring rotor motors;c synchronous motors.

    They differ from each other in:c starting current and torque values;

    c speed variation in normal operation;c power factor and efficiency values asa function of load.

    HV motors are supplied with a voltagerarely exceeding 7.2 kV, their powerranges from 100 kW to over 10 MW,with an average of 800 kW.

    asynchronous cage motorsThese HV motors fall into two maincategories according to their rotorcomposition which can be single ordouble cage.

    This enables choice of starting currentand torque characteristics:c single cage rotors have:v a relatively low starting torque (0.6to 1 C

    n),

    v a maximum torque of around 2to 2.2 C

    n,

    v a starting current ranging from 4.5to 5.5 In,(Cn: rated torque, In: rated current);

    c double cage or deep slot rotors have:v a slightly higher starting torque (0.8to 1.2 C

    n),

    v a maximum torque of around 2

    to 2.2 Cn (slightly higher for deep slots),v a starting current ranging from 5to 6.5 In.

    Figures 1 and 2 show the form of thesecurves as a function of speed (N/N

    s).

    Note that:c single cage motors have a minimumtorque (0.5 to 0.6 C

    n), whereas the

    torque curve, varying according to thespeed of the double cage or deep slotmotors, continues to increase up tomaximum torque.c these motors are ideal for intensive useand dangerous environments, due to:

    fig. 2: curves C(N) andI(N) of an asynchronous double cage motor.

    I

    In

    C

    Cn

    fig. 1: curves C (N) andI(N) of an asynchronous single cage motor.

    C

    Cn

    I

    In

  • 7/29/2019 protection of HV motor

    5/28

    Cahier Technique Merlin Gerin n 165 / p.5

    fig. 4: curves C (g) of an asynchronous slipring rotor motor.

    v the simplicity of rotor design in

    short-circuit providing them with an

    excellent mechanical and electrical

    robustness,

    v absence of brushes.

    These two features allow maintenance

    to be reduced to a minimum.

    The torque characteristics of

    asynchronous cage motors are

    especially suitable for machines such

    as centrifugal pumps, compressors,

    converter sets, machine-tools and fans.

    However, all these motors have the

    drawback of a relatively low power

    factor, around 0.8 to 0.9 on full load,

    and even less when they are running

    on low load (see fig. 3).

    If asynchronous motor installed power

    is high, reactive power compensation is

    required. This may either be global, for

    each set of motors or for each motor

    (large units).

    asynchronous slipringrotor motorsThe rotor winding of these motors

    connected to sliprings means the

    resistance of this circuit can be

    modified by introducing external

    resistances.In the motor stability zone,

    corresponding to the positive slope of

    curve C = f (g) (see fig. 4), the slippage"g" is proportional to the rotor

    resistance:

    g = 1

    ARr C

    where g % = Ns N

    Ns100

    where:

    Ns

    : synchronous speed,

    N : operating speed.

    A = 3V2 p

    M

    L1 = constant

    where:

    V: phase to neutral supply voltage,p: number of pole pairs,

    : pulsation of supply currents,M: reciprocal stator-rotor inductance,

    L1: total stator choke,

    (L1

    = M + Ls)

    Rr: rotor resistance = rotor inherent

    resistance + external resistances,

    C: motor torque.

    cos

    0 2/4 3/4 4/4

    0.5

    0.6

    0.7

    0.8

    0.9

    cos

    (P/Pn)

    fig. 3: efficiency curves (P) and power factor curves cos(P) of an asynchronous double

    cage motor.

    CM

    C

    Rr R'r > Rr R''r > R'r

    CnCd

    C'd

    C''d

    1

    0.50

    0.5

    1 2 g

    operation

    on generator

    operation

    on motor

    operation in

    regenerative

    braking

    rotor stability zone

    in short-circuit

  • 7/29/2019 protection of HV motor

    6/28

    Cahier Technique Merlin Gerin n 165 / p.6

    c the power factor which may be set bythe exciting current.Technologically, they are identical toAC generators.

    In order to obtain asynchronous torqueand avoid oscillations, the rotors areequipped with a damping cage. Thiscage means synchronous motors canbe started with a low load torque insimilar fashion to asynchronous singlecage motors (they have practically thesame characteristic torque and currentcurves). To avoid surge voltages in theexciting circuit, this circuit is shuntedduring starting and on tripping by aresistance with a value chosenbetween 5 and 10 times the resistance

    of the exciting circuit.In view of the fact that theasynchronous torque tends to zero onapproaching synchronous speed,coupling to the network when motorstarting is complete cannot take placeat synchronous speed as is the case forAC generators. The result is invariablya transient state varying according tothe speed acquired at the end ofstarting and motor power. To limit thistransient state:c either use a relay to monitor slippageby measuring frequency of the rotor

    current passing through the startingresistance. This relay controls excitingcircuit supply when slippage is at itslowest.This device is practically indispensablewhen the synchronous motor accountsfor a large part of total installed power.c or apply the exciting current in twostages, automatically or manually.

    The exciting sources can be either

    separate:

    c motor set, exciter;

    c thyristor rectifier;

    or placed at the end of the motor shaft:c reversed generator;

    c rotating "diode rectifier and armature"reversed AC generator.

    The techniques most frequently used

    are the thyristor rectifier and the"rotating diodes".

    The latter does away with brushes,

    removes the exciting cubicle and, in

    addition, is often fitted with asynchronisation and recoupling

    mechanism should synchronism fail.

    These motors can supply reactiveenergy by increasing the excitingcurrent. This characteristic, whichenables compensation of network

    reactive loads, is one of the mainreasons these motors are chosen.

    The curves in figure 5 show statorcurrent variation as a function ofexciting current for a given constantload (Mordey curves). Use of this typeof motor for small powers is fairly rare.On the other hand, it is frequently usedabove 2,000 kW for its excellentefficiency and control of its powerfactor. In the case of highly regularmovements, synchronous motors are anecessity. However, the machines

    being driven must have a relatively lowload torque during starting, and sizingof the dampening cage limits startingrate.

    sizing tolerancesThe electromechanical characteristicsof motors are defined by standard

    IEC 34-1. In the case of certain rated

    characteristic values, the standard

    defines the tolerances to be compliedwith by the manufacturer. It is useful tobe familiar with these tolerances since,

    for certain characteristics, they directlyaffect the choice of motor and

    equipment power and the setting of theprotection devices.

    The table in figure 6 gives the

    tolerances of the main characteristic

    values.

    By decreasing external resistance onstarting, the characteristic C (g) istranslated and the starting torqueadapted to the torque of the machine

    being driven. Note that maximumtorque value does not depend on rotorresistance.

    Moreover, for small slippages, rotorcurrent is inversely proportional to rotorresistance. Its amplitude is given by:

    I2 = Bg

    Rr

    where

    B = VM

    L1.

    Stator current follows the same law,except for the winding ratio and themagnetising current.

    Consequently, the choice of initial rotorresistance solves virtually all theproblems concerning high startingtorque and inrush current on thenetwork and ensures these tworequirements are satisfied. The variouspossibilities for using asynchronousslipring rotor motors make themsuitable for driving machines with highstarting torque such as crushers,mixers, conveyors, etc.

    Moreover, machines requiring highregenerative braking also use this typeof motor.

    Just as for asynchronous cage motors,the power factor in normal operation isrelatively low: this characteristic and thepresence of sliprings and rotorresistances mean these motors areincreasingly replaced by double cage ordeep slot motors.

    Figure 4 represents the characteristicC (g) curves, according to rotorresistance value and the stabilityzones. These curves show the

    advantage of introducing a highresistance in the rotor circuit as ameans of obtaining efficientregenerative braking.

    synchronous motorsThe main differences withasynchronous motors are:c their constant speed (synchronousspeed);c the rotor circuit supplied with DC;

    fig. 5 synchronous motor: Mordey curves.

    0 (i) excitation

    (I) stator

    stabilit

    ylim

    it full load1/2 load

    1/4 load

    cos AR cos AVcos = 1

  • 7/29/2019 protection of HV motor

    7/28

    Cahier Technique Merlin Gerin n 165 / p.7

    dielectric withstand andtestsMotors, just like all electrical network

    components, are subjected to a varietyof surge voltages. They are particularlysensitive to steep front surge voltagesor high frequency since they are"jammed" by the first turns of the statorwindings.

    Switching surge voltages

    These are the result of transientphenomena occurring during changesin status in the supply network.The following phenomena, specific toinductive circuits and thus to motors,must be taken into consideration:c current pinch-off on current breaking;

    c multiple re-ignitions on breaking andprearcing on current making if thebreaking device is capable of breakingthe high frequency currentscorresponding to these phenomena.

    Steep front surge voltages

    These are the result of direct or indirectlightning strokes. They spread onto thenetwork, creating a dielectric stresswhich, even when limited by the use ofsurge arresters, can be considerable.Surge voltage is studied in detail in"Cahier Technique" n 151"Overvoltages and insulation

    coordination in MV and HV" andspecial motor sensitivity in"Cahier Technique" n 143 "Behaviourof the SF6 MV circuit-breakers Fluarcfor switching motor starting currents".To check the motors capacity towithstand to these various surgevoltages, the motors undergostandardized tests performed asdefined by IEC 34-1 standard.

    The test voltage is applied between thewinding being tested and the body ofthe machine to which the magneticcircuits and all the other stator and rotor

    windings are connected.

    Two types of tests are stipulated in the

    standards: standard frequency tests

    and impulse withstand tests.

    Standard frequency testWithstand to switching surge voltages

    is checked in compliance with standard

    IEC 71, by the standard frequency

    withstand test. Testing commences

    with a voltage of less than U/2 which is

    gradually increased up to 2 U + 1,000V,

    at which level it is applied for one

    minute.

    For the stator, U is the specified supplyvoltage. For the rotor, U is the voltage

    which appears, with the rotor circuit

    open, when the specified statorsupply voltage is applied with the

    rotor locked in rotation. If the motor

    is reversible (change of rotation

    direction of motor already started), the

    test voltage applied to the rotor will be4 U + 1,000 V.

    Impulse withstand test

    This test consists in applying animpulse voltage representative of

    lightning:

    c buildup time: 1.2 s;

    c dropdown time at Upeak/2: 50 s;

    c test voltage:

    Upeak

    = 4 U + 5,000 V.

    The windings are subjected to a

    number of positive and negative waves.

    Impulse withstand tests are not

    currently mandatory in standards, as

    they can lead to early ageing of

    armature and winding insulation.

    More generally, the dielectric testsmust not be repeated; if a second testis performed, it will be carried out at

    80 % of the voltages indicated above.

    value tolerance

    asynchronous motors

    current with locked rotor + 20 % of current

    and short-circuited (no lower limit)

    torque with locked rotor - 15 % to + 25 % of torque guaranteed

    minimum torque during starting - 15 % of torque guaranteed for cage motors Cdu at

    a third of rated torque andi

    at half of torque withlocked rotor, at full voltage

    maximum torque - 10 % of torque guaranteed provided that once thistolerance is applied, the torque remains u 1.6 timesrated torque

    synchronous motors

    current with locked rotor + 20 % of value guaranteed

    torque with locked rotor - 15 % to + 25 % of value guaranteed

    pull-out torque - 10 % of value guaranteed provided that once thistolerance is applied, the torque remains u 1.35 timesrated torque (1.5 for synchronous motors with salientpoles)

    fig. 6: tolerances on the main characteristic values as in standard IEC 34-1.

  • 7/29/2019 protection of HV motor

    8/28

    Cahier Technique Merlin Gerin n 165 / p.8

    0 0.2 0.4 0.6 0.8 1

    0.2

    0.4

    0.6

    0.8

    1

    2. classical HV starting processes

    The main HV motor starting processesare as follows:c direct stator starting on full voltage;c stator starting on reduced voltage bystar-delta connection, by reactance orby autotransformer;c stator starting by capacitors;c rotor starting.

    direct stator starting on fullvoltageThis starting mode is used forasynchronous motors with cage rotorand for synchronous motors.

    Current peak on starting is around 4to 7 In, according to motorcharacteristics, and can last for roughly1 to 10 seconds depending on themoment of total inertia (motor +machine), motor torque and loadtorque.

    If this starting mode is used, thenetwork must be able to withstand theabove current overload without

    disturbing the other loads, and themachine being driven must be able towithstand the mechanical impact due tothe motor torque. The simplicity of bothequipment and motor and the resultingsavings mean that this mode is verypopular and even recommendedprovided that voltage drop on thenetwork on start up is acceptable. Thedecisive factor lies in the motor power/short-circuit power ratio.

    stator starting on reducedvoltage

    Star-delta startingThis starting mode is used to reduce:c current in a ratio of e;c starting torque by a third.

    It is used in LV and for low powers, butrarely in HV due to the high currentpeaks when moving to delta. In thiscase it is replaced by reactancestarting.

    Voltage reduced by resistanceCommonly used in LV, it is rarely usedin HV due to the Joules to be dissipatedand resistance insulation problems.

    Voltage reduced by reactance

    This starting mode (refer to powerdiagram, figure n 8) is the one whichreduces current inrush on the networkin the simplest manner. Since motorstarting torque is low, the machinesbeing driven must have a relatively lowload torque during start up:compressors, centrifugal pumps,converter sets, etc.In point of fact, asynchronous motortorque varies according to square of the

    supply voltage , whereas the absorbedcurrent remains proportional to thisvoltage.

    C'd = Cd UdUn

    2

    where :C'

    d: starting torque with reduced

    voltage,C

    d: starting torque with full voltage,

    Ud: starting voltage,

    Un: rated operating voltage.

    I

    'd = Id

    Ud

    Un

    where:I'd: starting current with reducedvoltage,Id: starting current with full voltage.These relationships can also beexpressed using the ratedcharacteristics as follows:

    I'dIn

    = Id

    In

    UdUn

    .

    The curves in figure 7 give the ratiovariations as a function of

    the ratio UdUn

    .

    Voltage at the motor terminalsincreases gradually during starting. Theresulting start up is smooth.c operation and schematic diagram:v first stage:operation on reduced voltage byclosing the line contactor C

    L,

    v second stage:normal operation by closing the short-circuit contactor C

    C;

    c determining a starting reactance(see fig. 9)

    Starting voltage is determined by the

    maximum current inrush l'd authorised

    on the network:

    Ud = Un I'dId

    .

    The phase-to-phase voltage drop in the

    reactance has the following value:

    Un

    Ud

    = j 3 L I'd

    .

    The diagram in figure 9 shows that this

    relationship can be expressed in anarithmetic form for asynchronousmotors, since the power factor at theinitial moment start up moment is

    initiated is virtually the same as the

    power factor of the starting inductance.

    Therefore:

    L = Un Ud3 I'd

    .

    Knowledge of start up time and

    operation rate is required to determinereactive power.

    Voltage reduced by autotransformer

    This starting mode sometimes makes it

    possible to reconcile reduction of

    current inrush on the network and

    motor torque value. In point of fact, it

    has the advantage of reducing current

    inrush according to the square of the

    winding ratio:

    fig. 7: graphs showing start-up on reduced

    voltage (by reactance or star-delta).

    UdUn

    I'dId

    andC'dCd

    C'd

    Cd

    I'dId

  • 7/29/2019 protection of HV motor

    9/28

    Cahier Technique Merlin Gerin n 165 / p.9

    I'd

    d

    Un

    Ud

    rating of the neutral point contactor tobe reduced;c there is an alternative version of thisconfiguration in which the neutral point

    contactor is removed. This version isnot recommended since the move fromreduced to full voltage necessites themotor-network link be cut. In view of therelatively short switching time, and theresidual voltage at the motor terminals,a current inrush exceeding startingcurrent can ocur on transfer to normaloperation. This is unacceptable for boththe network and the motor and can leadto the tripping of the protection devices.

    stator starting withcapacitorsThis process enables motor full voltage

    starting characteristics to bemaintained. It is mainly used forkeeping the starting torque ofsynchronous motors constant duringstart up, for example in cement worksand crushing plants.

    Capacitors, as well as motor, supplypart of the reactive energy during thestarting phase: the motor power factoris small at this stage. Power inrush on

    I'dIn

    = Id

    In

    UdUn

    2

    C'dCn

    = CdCn

    UdUn

    2

    where:

    I'd: starting current on network side with

    reduced voltage.

    These relationships are used to

    determine the value of reduced voltage

    authorised on the network, as a function

    of the ratio'dn

    or of the ratioC'dCn

    authorised by the machine being driven.

    The curve in figure 10 gives the

    variation ofUdUn

    as a function

    of'dn

    orC'dCn

    .

    c operation and schematic diagram

    (see fig. 11)C

    L: line contactor,

    CC: short-circuit contactor,

    CPN

    : HV neutral point formationcontactor,

    AT: autotransformer

    v first stageoperation on reduced voltage by

    closing CPN

    which causes CL

    to close,

    v second stageoperation in inductance by opening CPN,

    v third stage

    operation on full voltage by closing CC.

    Remarks:

    c in theory the second stage is short(around one second) since in mostcases it is a slowing-down time;Use of an autotransformer with air gapsconsiderably reduces this fault, butrequires knowledge of the value of thecurrent absorbed by the motor at theend of the first stage;

    c the move to full voltage invariablyresults in a transient state whoseduration varies according to the speedacquired at the end of the first stageand the value of the current absorbed;

    c the current flowing through theneutral point on start up is equal to thedifference between the motor currentand the line current, excluding themagnetising current of theautotransformer. This enables the

    fig. 9: vectorial diagram to determine L.fig. 11: power diagram: starting by

    autotransformer.

    fig. 10: graphs showing start up byautotransformer on reduced voltage.

    0 0.2 0.4 0.6 0.8 1

    0.2

    0.4

    0.6

    0.8

    1

    I'dId

    andC'dCd

    Ud

    Un

    fig. 8: power diagram: starting by reactance.

    J L I'd

    3

    M

    neutral point

    AT

    3L

    CL CC CPN

    3L

    CC

    CL

    M

    3L

    L

    j

  • 7/29/2019 protection of HV motor

    10/28

    Cahier Technique Merlin Gerin n 165 / p.10

    the network is reduced accordingly(see fig. 12).

    This technique is tricky to implementand calls for a study of the motor and

    capacitors to avoid resonance andsurge voltage (due to motor self-excitation), as well as mechanicaloscillations on the transmissionsystem.

    Moreover, control equipment must bechosen especially for capacitorswitching.

    rotor startingThis starting mode solves virtually allthe problems which may occur onstarting, namely:c reduction of current inrush on thenetwork with increase in motor torque;c adaptation of motor torque to loadtorque;c long, progressive starting (e.g. forloads with high inertia).

    This mode can only be used forasynchronous slipring rotor motors andfor synchronous induction motors (its

    use is increasingly rare in industry).It is particularly used for load starts.

    Example of a rotor start in n time

    This start up is illustrated in figures 13and 14. Motor torque varies betweentwo values at each notch. The lowervalue is taken as being equal to therated torque. At each notch, rotorresistance changes value and thetorque-speed characteristic evolves. Inthe last stage, rotor resistance is simplyequal to the rotor internal resistance.c first stagestator supply and starting on full rotorresistance by closing C

    L;

    c second stageshort-circuiting of the first section of therotor resistance by closing C

    1;

    c third stageshort-circuiting of the second section ofthe rotor resistance by closing C

    2;

    c Nth stageshort-circuiting of the n-1 section of therotor resistance by closing C

    n-1.

    The number of stages, or notches, n isalways greater by 1 than the number ofsections or contactors.

    This number n is determinedapproximately by the formula:

    n = log gn

    logCnCp

    or byCnCp

    = gnn

    where:C

    p= peak torque,

    gn

    = rated slippage.

    According to each case, n can bededuced from Cp, and vice-versa.

    Complete determination of rotor startingequipment calls for knowledge ofoperation (hourly rate and startingtime). Lack of standards for HV motorsmeans this equipment is determined ineach individual case by specialists.

    RemarkA linear start is sometimes required.This calls for power electronics

    enabling monitoring of rotor energy: forexample using a Gratz bridge and achopper to make a continually variableresistance (see fig. 15).

    fig. 13: power diagram: rotor starting.

    fig. 12: vectorial diagram for starting by

    capacitor.

    fig. 14: symmetrical rotor starting diagram.

    power suppliedby the network

    active power

    power suppliedby capacitors

    apparentmotor poweron starting

    inductivereactivepower

    M

    neutral point

    3L

    CL

    3L

    C1

    C2

    Cn - 1

    4th 3rd 2nd stage 1st stage

    0 1 g

    Cn

    Cp

    CM

    C

    gn g4 g3 g2 g1

  • 7/29/2019 protection of HV motor

    11/28

    Cahier Technique Merlin Gerin n 165 / p.11

    C

    C

    3

    3

    C

    C

    3

    C

    3 n

    3 n

    3 n

    n

    n

    characteristics examples

    constant torque piston compressor

    parabolic torque pump:

    valve opened

    - - - - valve closed

    high breakaway crusher

    torque

    Starting conditionsIn view of the required startingcharacteristics, it is necessary to checkthat starting can take place in correctly

    as far as motor torque, current inrushand starting time are concerned, for thestarting techniques underconsideration:

    c motor torque is always greater thanload torque (see fig. 17);c current inrush on the network and thecorresponding voltage drop are

    acceptable to the network;c starting time is compatible with theequipment used.

    Approximative calculation of startingtimeOperation of the motor-driven machineassembly is governed by the followingmechanical equation:

    Cm Cr = Jddt

    where:C

    m: motor torque with Un voltage,

    Cr: load torque,

    J: inertia of rotating frames (motor andmachine driven),

    ddt

    : angular acceleration.

    Angular velocity varies from 0 to nthroughout starting time t. Moreover, amean accelerating torque C

    a, equal to

    the mean difference between Cm

    andC

    rcan be defined:

    This results in Ca

    = (Cm

    - Cr) mean

    = J(n 0)

    thence:

    t = J nCa

    .

    Bearing in mind that real motor torquevaries according to the square of itssupply voltage:

    C'mCm

    = UrealUn

    2

    with real voltage.

    Cm

    = motor torque with real tension.Reducing this voltage will thus reduce

    Ca, hence increasing starting time.

    fig. 16: rreminder of load torque curves of machines to be driven (loads). fig. 17: case of non-starting (C'm < Cr).

    choosing the starting modeChoice of starting mode is conditioned

    by ensuring that the motor torque and

    the load torque of the load are properlymatched.

    Knowledge of the load torque is

    required (see fig. 16).

    torque

    1.8

    0.9

    0speed

    Cm

    C'm

    C'r

    C

    Cn

    NI

    I0

    R1

    I

    N0

    R2

    H

    L

    --

    + +N

    M

    3L

    tachometer dynamo

    fig. 15: setting speed by rotor chopper.

  • 7/29/2019 protection of HV motor

    12/28

    Cahier Technique Merlin Gerin n 165 / p.12

    Starting mode selection table

    The table in figure 18 summarises the

    advantages and disadvantages of the

    main starting modes for the various

    applications.

    For a given torque, the current

    absorbed on the network is establishedin the following increasing order:

    c rotor starting;

    c starting by autotransformer;

    c starting by stator impedance;c direct starting.

    Choice of starting mode calls for good

    communication between the electricalenergy supplier and the manufacturerof the motor and machine being driven.

    The vital characteristics for making thischoice are:c supply network power and maximumauthorised current inrush;

    c motor torque and current at fullvoltage as a function of rotation speed;c load torque of the machine driven(see fig. 16);

    c moment of inertia of the rotatingframes.

    If the supply network power/motor powerratio is less than 5, particular care mustbe paid to choice of starting mode andchoice of coordination of the protectiondevices (see appendices 1 and 2).

    fig. 18: starting mode selection table for the most common applications.

    application application starting mode controlled by advantagesneeds characteristics disadvantages

    permanent or machines requiring direct 1 or 1 simplicity,quasi-permanent high start torque less investment.

    process i 1/jour on starting:frequent starts > 1/day motors with low current direct chigh torque;

    inrush or low power 1 chigh current inrush,;chigh mechanical stresses.

    pumps, fans, machines starting stator 2 reduction of current inrushcompressors, with low torque by reactance on startingfrequent starts (possible adjustment).

    optimisation of when starting current stator by 3 optimisation of torquestarting characteristics must be reduced, but autotransformer (reduced) and of current inrush

    the necessary starting on startingtorque maintained (possible adjustment).

    optimisation of the most difficult starts rotor generally small current inrush andhigh torque 3 high starting torque.starting characteristics

  • 7/29/2019 protection of HV motor

    13/28

    Cahier Technique Merlin Gerin n 165 / p.13

    3. control and monitoring equipment

    The function of this equipment is

    threefold:

    c energising and stopping (control);

    c disconnecting the motor should a

    fault occur (protection);

    c monitoring the motor (monitoring).

    When we talk about monitoring, thisimplies the equipment is capable (or

    not) of:

    c initializing the start (starting sequenceautomation);

    cacting on motor speed;c supplying information on motor

    electrical status and contributing to

    protection.

    The monitoring function chiefly relies on

    power electronics and low currents

    (digital technology); it is currently being

    fully developed. Protection of

    HV motors will be dealt with in the next

    chapter.

    electromechanical

    solutionsThe choice between the various

    devices (switch, circuit-breaker or

    contactor) depends on:

    c operation rate;

    c electrical endurance;

    c motor power.

    The main breaking device

    characteristics are summarised in the

    table in figure 19.

    Fuse-switches

    By their very design, the breaking

    capacity, mechanical and electrical

    endurance of switches is low. Thislimits their use to small powers

    (In

    = approx. 50 A - 5,500 V) andto rates of two to three operations a

    day.

    Moreover, the low breaking capacity ofthese devices makes choice ofprotection devices tricky.

    Circuit-breakersCircuit-breakers are generally used forhigh motor powers of more than 300 A,with a small operation rate, and foroperating voltages of more than 6.6 kV.

    Their use can naturally be extended tolower powers, operable by switch orcontactor.

    Fuse-contactorsc operation rateTheir simple control mechanismcombined with the robustness and

    simplicity of their contacts meancontactors have a high operation rate.This rate cannot be withstood by circuit-breakers, even special ones, and evenless so by switches.

    Some installations use contactors withmechanical latching to do away withpermanent consumption of the closingelectromagnet. This may reduceendurance as a result of the greatercomplexity of the kinematic chain.

    c network short-circuit powerThis factor does not really affectcontactors thanks to the presence of

    fuses placed immediately after theisolating switch or next to thedisconnecting contacts on the busbarside. These fuses with their highbreaking capacity, limit the short-circuitcurrent.

    This special feature means that,if network power is increased, themotor feeder cubicles can bemaintained. The busbar supports arestrengthened if required.

    FusesFuse rating is determined according to:c rated current In;c the I

    d/I

    nratio (I

    d= starting current);

    c starting time determined using thechart in figure 20 page 14.

    Finally, it should be pointed out thatfuses protect the motor againstovercurrents roughly five times greaterthan motor rated current and that theymust be combined with additionalprotection devices (thermal relays, etc.

    see "protection device" chapter).Current transformersThe increasing use of digital protectiondevices means unconventional currentsensors can be used (e.g. Rogowskitoroids). These sensors have theadvantage of being linear and thusdelivering an accurate signalthroughout the useful current range.

    They present no saturation or thermalproblems, as is sometimes the casewith classical Current Transformers(see "Cahier Technique" n 112 "Thebreaking process with a Fluarc SF6

    puffer-type circuit-breaker").

    Special features due to use of fusesor circuit-breakers

    c operation in single-phase due to fusemelt, with the striker not working.

    Today striker reliability is such that therisk is slight. Their dependability maybe increased still further by use of anadditional protection device(undervoltage or unbalance relay).

    fig. 19: breaking device application field.

    device mean rate endurance acceptable motor

    nb operations powerfuse-switch low: 2-3/day 2,000 low i 50 A

    circuit-breaker low: 10/day 10,000 highu 7.2 kVA> 300 A

    fuse-contactor high > 10/h > 100,000 average i 300 A

  • 7/29/2019 protection of HV motor

    14/28

    Cahier Technique Merlin Gerin n 165 / p.14

    fig. 20: fuse determination chart.

    0.01

    0.02

    0.03

    0.04

    0.05

    0.1

    0.5

    1

    5

    10

    50

    100

    t seconds

    100A 125A 160A 200A 250A

    rating of 7.2 kV fuses

    example:

    motor In = 100 A

    Id = 6 . Intd = 5 s

    fuse rating = 200 A

    motor

    Amp In

    10

    20

    30

    40

    50

    60708090

    100

    150

    200

    I

    Id=4

    In Id=

    5In

    Id=6

    In Id=7

    In

  • 7/29/2019 protection of HV motor

    15/28

    Cahier Technique Merlin Gerin n 165 / p.15

    c discrimination with upstreamequipment.This can be hard to achieve when both:v the fuses used have a high rating

    (200 A or 250 A),v and the feeder protected by thesefuses accounts for a large fraction ofthe power supplied by the main circuit-breaker (see fig. 21 and 22).

    However, the high breaking capacity ofthe Rollarc contactors combined withthese fuses allows the use of slightlytime delayed overcurrent relays, thusensuring discrimination. Discriminationis easier to achieve if the motor feederis protected by circuit-breaker butsince, for high short-circuit currents thecurrent is not limited, there is an

    increase in thermal stresses.c surge voltagesSome types of device, in particularvacuum breaking devices, generatesurge voltages on motor energising andstopping (due to their capacity to breakhigh frequency currents, resulting forexample from the current pinch-offphenomenon - see "Cahier Technique"n 143).In order to prevent these surgevoltages progressively damaging motorinsulation, manufacturers place ZnOtype surge voltage limiters in the

    equipment if required.It can be concluded that today'selectromagnetic solutions are reliable,robust, economic and entirely suitablefor most applications.

    electronic solutionsThese provide users with additionalpossibilities and advantages such as:c variable speed;c possibility of speed regulation;c high operation rate;c energy savings.

    The electronic solution is rarely usedjust for starting.

    Before dealing with standard cases ofelectronic devices, it should be pointedout that their use calls for a certainnumber of constructive precautions atmotor level:

    fig. 21: protection diagram showing a high current motor feeder.

    fig. 22: discrimination diagram for a high current motor feeder.

    c safety margin in temperature rise dueto harmonics: a 15 % margin on currentis generally sufficient;c forced ventilation is recommended(motors can run at low speed);

    c reinforced insulation between turnsdue to the high voltage gradientsgenerated by thyristor switching (whichmay reach the magnitude of impulsewithstand test ones).

    t

    I

    contactor

    breaking

    time

    contactor

    overcurrent

    relay

    contactor

    breaking

    capacity

    circuit-breaking

    melting curve

    remain circuit-breaker

    overcurrent relay

    discrimination

    loss

    M

    overcurrent

    relay

    circuit-breaking

    contactor

    main

    circuit breaker

    overcurrent

    relay

  • 7/29/2019 protection of HV motor

    16/28

    Cahier Technique Merlin Gerin n 165 / p.16

    The devices described below are theones most frequently used in mediumvoltage. Only the general principles arepresented.

    The table in figure 23 gives an idea ofthe adequations between the type ofspeed controller, the type of motor andthe type of load driven.

    Autonomous rectifiers/inverters

    With their capacity to deliver variablevoltage and frequency, they guaranteecomplete control of motor speed andtorque.

    A reminder for asynchronous motors:c torque is proportional to U2 if f and Nare constant;c torque is inversely proportional to f fora given voltage and speed.

    There are three types of autonomousrectifiers/inverters.

    c voltage rectifier/inverterv the thyristor rectifier sets voltage,v the thyristor inverter suppliesAC current at variable frequency.

    This configuration is also used byUninterruptible Power Supplies (UPS)used in LV to supply computers. Theonly difference is that frequency andvoltage are fixed.

    c rectifier/inverter with Pulse WidthModulation (PWM)

    v the diode rectifier supplies theinverter,v the inverter generates voltage pulsesenabling reproduction of a sine wave

    with variable period and amplitude (seefig. 24).c current rectifier/inverter (switch)v the thyristor rectifier combined with asmoothing choke acts like aDC generator,v the inverter switches current in turn in

    the motor windings using capacitors.Motor frequency and thus speeddepend on switching speed.A few elements of comparisonbetween these three types ofrectifiers/inverters:c voltage inverterv suitable for high reactance motors,v often requires a filter between inverterand motor,

    v enables regenerative braking if therectifier is reversible.c the PWM inverterv allows a wide range of speeds,v maximum speed limited by themaximum switching frequency

    authorised by the inverter thyristors.Use of power transistors (IGBT) makesit possible to work at far higherfrequencies but at lower powers,v reversible operation possible (tworotation directions).c the current switchv suitable for low reactance motors,v enables operation in the fourquadrants.

    motor loads speed variations power overall speed controllerefficiency type

    asynchronous pumps, fans, 0 % to over 100 % a few 10 kW 0.85 to 0.90 autonomousor synchronous compressors, extruders to a few 100 kW rectifier/inverter

    asynchronous same 60 % to 100 %* a few 100 kW 0.90 to 0.95 subsynchronousslipring to a few MW cascade

    synchronous same 0 % 100 kW to a 0.90 to 0.95 selfcontrolledcentrifugal machines to several times 100 % few 10 MW rectifier/inverterTGV bogies(high speed)

    asynchronous crushers, rolling 0 % to 33 % 100 kW 0.85 to 0.90 cyclo converteror synchronous mills, cement kilns to a few 10 MW

    (low speed)

    *: 100 % corresponds to relative speed at 50 Hz

    fig. 23: application areas of electronic speed controllers for AC motors.

    fig. 24: generation of variable voltages and frequency with PWM speed controllers.

    U

    U

    0

    0

    t

    t

  • 7/29/2019 protection of HV motor

    17/28

    Cahier Technique Merlin Gerin n 165 / p.17

    Subsynchronous cascadeAsynchronous slipring rotor motors arenormally supplied by the network.Speed is adjusted using the rotor

    current by means of a rectifier/inverterset. The rectifier draws off energy from

    the rotor circuit, thus increasing

    slippage. The energy drawn off

    depends on the conduction setting of

    the thyristors of the inverter which

    reinjects energy into the network (see

    fig. 25). The subsynchronous cascade

    enables continuous speed variation

    with a maximum slippage of

    around 40 %.Converter set power is low compared

    with motor power, and the energy

    regenerated results in outstandingoverall efficiency.

    Note that the converter is put into

    operation after starting by rotor

    resistance.

    This assembly can operate at speeds

    higher than synchronous speed

    (supersynchronous) in the case of

    driving loads.

    Selfcontrolled rectifier/inverter

    The motor stator phases (in this case

    synchronous) are supplied in turn just

    as for the current switching

    autonomous rectifier/inverter.

    Switching from one stator phase to thenext is selfcontrolled by motor speed bymeans of a "notched disk" sensor.

    There is thus a correspondence

    between the excitation flux and the

    armature flux, as for DC machines, and

    the pull-out risk is zero.

    Since switching presents problems both

    on starting and at low speed, the con-

    verter control system must be modified.

    This solution is ideal for synchronous

    motors.

    Cyclo converter

    Each motor phase is "supplied" by athree-phase double bridge.The first bridge is used to draw off

    current throughout the positive cycle oneach of the network phases accordingto the required frequency.

    The second bridge is used for reversecurrent during negative alternation toone of the phases.

    The cyclo converter produces a three-

    phase pseudo mains requiring filteringand with a frequency varying between0 % and a third of network frequency.

    fig. 25: subsynchronous cascade power diagram.

    M

    P

    Pr

    3L

    3L

    3L

  • 7/29/2019 protection of HV motor

    18/28

    Cahier Technique Merlin Gerin n 165 / p.18

    "Motor protection" groups all theprotection devices used to preventserious damage due to abnormaloperating conditions at supply, motor orprocess level.

    The protection devices to be installedare chosen according to the followingcriteria:c operating conditions;c importance of the operationperformed by the motor;c the degree of dependability required;

    c the relative cost of the protectiondevice with respect to the motor;c the likelihood of the faults consideredoccurring.

    As well as:c the type of load driven;c disturbances which could occur onthe network;c the type of motor protected.

    The faults listed below may thereforerequire use of a protection device.

    main fault types

    Asynchronous motors

    c overloads;c short-circuits;c phase breaking, reversal andunbalance;c insulation fault between turns;c stator frame;c under and overvoltage;c incomplete starting.

    Synchronous motors

    All the above faults, plus:c loss of synchronism;c loss of excitation;

    c rotor frame;c prolonged operation in asynchronousmode on starting;c overloads and short-circuits in theexciting winding;c reverse power (operation onAC generator).

    Other faults linked to the process orload

    c over frequent starts;c locked rotor;c underpower or undercurrent.

    The detection/protection processes forthe main fault types are studied in theparagraph below.

    protection principles

    Overloads

    Overloads can be detected by reverse

    time overcurrent relays, thermal imagerelays or heat sensors.

    The relays process the information

    "current absorbed by the motor" whichis generally detected by current

    transformers.

    The heat sensors are inserted in the

    live parts of the motor.

    c reverse time overcurrent relaysTheir use requires:

    v either an operating curve I(t) allowing

    starting, or a device blocking the relay

    during starting,v an operating threshold I0 close to therated current In of the motor

    I0 1.10 In .

    These relays do not memorise theoverloads.

    c thermal image relays

    These relays are certainly the mostsuitable since they ensure the greatest

    possible advantage is derived frommotor overload possibilities without

    damage.

    The operating curve I(t) of the relay

    must enable the starting current to flowwithout tripping and be approved by the

    motor manufacturer.

    c heat sensors

    These are resistors, the ohmic value ofwhich varies with temperature.

    In theory these devices are not used bythemselves, but rather back up therelays using the current absorbed as ameasuring means.

    Overloads due to temperature rise of abearing are, in theory, insufficient fordetection by the overload relays.

    Bearings must therefore be protectedby thermostats or heat sensors.

    Short-circuits

    Short-circuits on circuit-breakerequipment are detected byinstantaneous operation overcurrentrelays, set above the starting current.

    On fuse-contactors, short-circuits arecleared by the fuses.

    However, an useful solution is to addslightly time delayed overcurrent relaysto the fuses. This means that thecontactor can be used right up to itsbreaking capacity.

    Phase breaking, reversal andunbalance

    These faults are detected by a filterwhich highlights the negative phasesequence components.

    It is vital to monitor phase breaking andunbalance since these faults give riseto:c increased current, in the stator,;c additional temperature rise by Jouleeffect, due to the fact that all out-of-balance states result in the appearanceof reverse currents flowing through the

    rotor at twice supply frequency in therotor.

    Phase reversal is detected either bycurrents or voltages:c by currents: this reversal is detectedafter contactor closing: the drivenmachine receives the fault;c by voltages: this means contactorclosing can be prohibited, if necessary,if phase order is not the normal networkone.

    Insulation fault in winding

    Stator windings may have faultsbetween turns on the same phase or

    between windings of different phases.As a result of its electrical position, thefault may not be detected quicklyenough by the overload protectiondevice, thus causing serious damage.These faults are normally detected bycurrent comparison.

    c longitudinal earth leakage protectionProvides protection against faultsbetween windings of different phases.For this, the ends of the motor windingsmust be accessible on the neutral side.

    4. protection of HV motors

  • 7/29/2019 protection of HV motor

    19/28

    Cahier Technique Merlin Gerin n 165 / p.19

    Faults are shown up by comparing theinput and output currents of the samephase (see fig. 26).If there are no faults, these currents are

    identical and the protection relay is nottripped. It trips when the differencebetween these currents reaches avalue set by the relay setting.

    c transverse earth leakage protectionProvides protection against faultsbetween turns of the same phase.It applies to machines with dividedphases, i.e. with two windings perphase.The operating principle is the same asabove, that is the currents of eachwinding are compared (see fig. 27).

    Stator frame

    This protection device is vital to complywith the statement of the 14.11.1988 onworkers' protection. It is chosenaccording to the earthing system of thenetwork supplying the motor.

    c motor protection supplied by networkwith earthed or impedance-earthedneutral.The fault is detected by measuring thezero sequence current formed betweenthe faulty phase and the network frame.Low threshold overcurrent relays areused for measuring.The zero sequence current is deliveredby three parallel-connected currenttransformers or, better still, by a toroid(see fig. 28).Use of a toroid prevents theappearance of a false zero sequencecomponent due to unequal saturation ofcurrent transformers on motor starting,and allows a relatively low operatingthreshold.

    These relays must operate for a faultcurrent value such that frame potentialcompared with earth is never raised tomore than 24 V in conductiveenvironments, with frames

    interconnected, or 50 V in otherinstallation cases.

    Knowledge of earth connection valueand of the frame interconnectionconfiguration is therefore necessary todetermine this setting point.If the frames are not interconnected,the value of the operating threshold isgiven by:

    IF i 24 or 50 V

    RTM.

    fig. 28: diagram showing a stator frame zero sequence protection with toroid sensor or CT +

    earthed or impedance-earthed neutral.

    NM

    protection

    relay

    fig. 26: diagram showing a longitudinal earth leakage protection.

    M N

    protection

    relay

    zero

    sequence

    current relay

    toroid

    CT

    zero

    sequence

    current relay

    eventually toroid

    fig. 27: diagram showing a transverse earth leakage protection.

  • 7/29/2019 protection of HV motor

    20/28

    Cahier Technique Merlin Gerin n 165 / p.20

    RTM

    is the value of the earth resistance

    of the frame in question.

    Note that the lower the threshold, the

    earlier the detection, and the smaller

    the risk of damage to the magnetic

    circuits.

    c unearthed neutral

    The fault is detected by continuous

    measurement of global network

    insulation compared to earth by means

    of DC injection devices such as

    continuous insulation monitors (see

    diagram 1 in figure 29) or by zero

    sequence overvoltage relays where this

    overvoltage is delivered by three

    voltage transformers with the

    secondary winding in open delta (see

    diagram 2 in figure 29).

    Under and overvoltage

    (see fig. 30)

    c undervoltage

    This relatively common protection

    prevents the motor from working on

    overload and waiting for tripping by the

    overload protection device. Moreover, if

    the contactor coil is supplied by an

    auxiliary LV source not from the

    network, the latch undervoltage

    protection device is vital to prevent

    untimely startup on restoration of

    power.

    The "voltage" information is provided by

    a voltage transformer and processed by

    a time-delayable threshold device.

    c overvoltage

    This protection is necessary if there is a

    risk of strong fluctuations occurring on

    the supply network. It means it is no

    longer necessary to wait for the

    overload relays to trip, since

    overvoltage results in motor overcurrent

    and increased motor torque which

    could be detrimental for the machine

    being driven.

    The fault is detected by time delayed

    overvoltage measuring relays.

    Incomplete or overlong starting

    This protection is justified for starting in

    several stages.

    It is provided by a time delay relay put

    into operation at the beginning of

    starting and removed at the end. The

    value monitored may be speed or

    current.

    Prolonged use of the starting system,calculated to run for a set time, is thusavoided.

    Loss of synchronismThis protection is vital for synchronousmotors.

    In point of fact, the dampening cageof a synchronous motor is relativelyfragile. If the motor jams, inducedcurrents will flow through this cage andcould destroy it if the motor is notdisconnected.Jamming may occur following amechanical overload, undervoltage, aloss of or drop in excitation.

    This fault is detected by underimpedance or power factor relayssupplied by voltage transformersand current transformers (see fig. 31).

    fig. 29: insulation fault monitoring diagram with continuous insulation monitor or zero sequence

    voltage relay - unearthed neutral

    fig. 30: diagram showing under and

    overvoltage protection. In most cases, two

    VTs supply the relay phase-to-phase

    voltages.

    voltage

    relay

    M

    zero sequence

    voltage relay

    DC injection

    insulation

    monitorsurge

    voltage

    limiterC

    R = load resistance

    R R R

    diagram 1

    diagram 2

  • 7/29/2019 protection of HV motor

    21/28

    Cahier Technique Merlin Gerin n 165 / p.21

    directional power

    relay

    M

    under

    impedance

    or cos relay

    M

    Loss of excitationThis loss due, for example, to a break inrotor winding, causes the motor to jam.It can be detected by:

    c the "loss of synchronism" protectiondescribed above;c or an exciting undercurrent orundervoltage relay.

    Rotor frame of a synchronous motor

    This protection is determined accordingto the supply configuration and theDC production mode.

    If the entire DC exciting circuit isunearthed, an insulation fault will notaffect motor operation.However, should a second fault occur,it may give rise to an overload or short-

    circuit with all its consequences. Therelays used to detect this type of faultare generally devices injecting lowfrequency 10 Hz or 20 Hz AC current(see fig. 32).

    The 50 Hz frequency is also used,which requires that no 50 Hzcomponents must be present in theexciting circuit.

    Prolonged operation in theasynchronous mode on starting

    Overlong starting on synchronousmotors causes excessive temperaturerise of the damping cage.

    Either the "incomplete starting"protection described above is used or athermal device adapted to the rotorthermal time constant, placed in series

    with the inductance during starting (seefig. 32 element b).

    Overload and short-circuit in theexciting windingThese protection devices preventdamage due to temperature rise of theexciting winding and its power supply.The fault is detected by an excitingovercurrent relay. Moreover an excitingundervoltage relay is normally used,tripping on voltage drop, caused forexample by a short-circuit.

    On starting, it is used as an excitingvoltage presence relay and authorisesclosing of the exciting contactor atthe end of starting in the

    asynchronous mode (see fig. 32element g).

    Reverse power

    This protection particularly applies tosynchronous motors.

    When the supply circuit-breaker trips, itprevents energy from being sent backto the loads connected on the samebusbar. It also prevents a fault on thisbusbar from being supplied by themotor.

    The protection device has to detect areversal in current or power direction.

    Its function is therefore performed by adirectional power relay (see fig. 33).

    Frequent starts

    Too many starts over a given period oftime may cause motor damage if themotor is not designed for such anoperation.

    This protection is provided by a relayperforming metering and time delayfunctions, which automatically limits:c either the number of starts over agiven period of time;c or the time interval between start upsover a given period of time.

    fig. 31: protection against loss of

    synchronism.

    fig. 32: rotor protection devices on startup

    and in operation.

    a. exciting windingb. thermal protection: prolonged operation inasynchronous modec. starting resistanced. exciting contactore. rotor frame protectionf. overcurrent protectiong. undervoltage protectionh. to tripping of motor feeder contactors. continuous source

    fig. 33: protection against reverse power.

    ab

    c

    d

    e

    f

    g

    h

    s

    Z

    U

  • 7/29/2019 protection of HV motor

    22/28

    Cahier Technique Merlin Gerin n 165 / p.22

    Locked rotor

    Jamming of a motor for mechanicalreasons causes an overcurrent roughlyequivalent to starting current. The

    resulting temperature rise isconsiderably greater since rotor lossesare maintained at their highest valuethroughout jamming and ventilation isno longer present if connected to rotorrotation. As a result, when there is arisk of jamming, the "locked rotor"protection is necessary since overloadrelays sometimes have an excessivelylong response time.

    This fault is detected by an overcurrentrelay set at a value less than thestarting current. This value is validated

    after a time delay initiated when themotor is energised. This time delay isset at a value greater than or equal to

    normal starting time.

    Undercurrent or underpower

    Pumps may be damaged when

    unpriming occurs. Unpriming could also

    result in a drop in the active power

    absorbed by the motor. Protection

    against this fault is provided by an

    undercurrent relay.

    technological evolutionThe term "relay" is often used in the

    above description of the various

    protection devices. This is a thetraditionally used term (relay = a type ofprotection device) which goes back tothe time when motor protection

    required the use of separate "relays"each with a single protection function.

    In the seventies, manufacturers broughtout RACKS able to house a number ofdifferent protection devices in order tomeet needs more closely.

    In the eighties digital technologyincreased adaptation possibilities stillfurther. Thus a single programmabledevice performs the various protectionand control/monitoring functionsrequired in each specific case.

  • 7/29/2019 protection of HV motor

    23/28

    Cahier Technique Merlin Gerin n 165 / p.23

    overall approachThe approach chosen by the designeris to look for the best technico-economic choice. For this, first try andvalidate the easiest and mosteconomical solution. Then, if this doesnot work, follow the order shown in thetable in figure 34.

    Direct starting

    Motor apparent power at the beginningof starting:

    Sm = Pn

    cos Id

    In

    Sm = 1,500

    0.845 = 8,925kVA

    where, with power factor on starting:cos

    d= 0.15, i.e. :

    d= 81.

    This power is vectorially added to thepower delivered by the transformer onthe other feeders (see fig. 35).

    The total value of the apparent powerrequired by the transformer isgraphically deduced from the following:

    S 9,580 kVA.The maximum inrush authorised is6,000 kVA: direct starting is thus notpossible.

    Starting by reactance

    Introduction of a reactance reduces theapparent power absorbed by the motor.The available starting power isgraphically determined (see fig. 35).

    When the motor starts, the presence ofthe reactance means that the powerfactor approaches zero. Thus

    d 90.

    appendix 1: determining motor starting mode

    The purpose of the example below isnot to fully deal with a problem butrather to illustrate, through an example,an approach wich helps to choose theappropriate starting mode for a givenapplication.

    calculation hypothesesAsynchronous motor with:c rated power P

    n= 1,500 kW;

    c rated voltage Un

    = 5,500 V;

    c efficiency x power factor: x cos = 0.84;c starting torque/rated torque ratio onfull voltage:

    CdCn

    = 0.8

    c starting current/rated current ratio onfull voltage:

    Id

    In

    = 5 ;

    c breakaway torque of the drivenmachine: 0.2 C

    n;

    c main supply transformer power:Pt = 3 MVA;c maximum apparent power inrushauthorised by the transformer network:S

    t= 6 MVA.

    Other data necessary for calculation:c torque-speed C (N) characteristic ofthe motor;c load torque-speed C

    r(N);

    characteristic of the driven machine

    c transformer delivery on feeders otherthan the motor one: 1,200 kVA undercos ' = 0.87.

    OA

    = 1,200 kVA : transformer power

    used on other feeders.

    OB

    = St = 6,000kVA: maximumapparent power authorised. Theapparent power available for starting(motor + reactance) is graphicallydeduced.

    AB

    = Sd = 5,300kVA.Power reduction to be caused by the

    reactance:SdSm

    = 5,3008,925

    0.6 .

    fig. 34: decisive criteria for choosing motor starting mode.

    starting solutions main acceptance criteria

    direct power inrush compatible with network

    reactance c starting torque greater than breakawaytorquec current peak (for full voltageresumption) acceptable by network

    autotransformer the same

    fig. 35: starting power diagram.

    S = 9,580*

    B

    d= 81

    ' = 29.51,200*

    St= 6,000*

    Sd

    = 5,300*

    Sm

    = 8,925*

    A

    active power*: in kVA

  • 7/29/2019 protection of HV motor

    24/28

    Cahier Technique Merlin Gerin n 165 / p.24

    (a)

    (c)

    (d)

    (b)

    (e)

    0 0.1 0.2 0.5 0.8 1

    0.2

    0.8

    5

    1

    1

    Cn

    In

    point of balance

    at reduced

    voltage

    current peak

    on move

    to full voltage

    (N/Ns)

    I'd is the new starting current value.

    Sd = Un I'd 3

    Sm

    = Un

    Id

    3

    thus: I'd = 0.6 Id.

    Moroever:I'd

    Id

    = UdUn

    = 0.6 .

    The value of voltage at the motorterminals is U

    d= 0.6 U

    n. Once the

    electrical problem has been solved, itremains to be seen if this solution isvalid from the mechanical standpoint. Inthe case of direct starting, the startingtorque equals : C

    d = 8 Cn (see fig. 36).

    In the case of starting by reactance, thestarting torque C'

    dequals:

    C'd = 0.8 Cn UdUn

    2

    = 0.288 Cn

    This value is compatible with thebreakaway torque of the machine beingdriven.

    One last point remains to be checked:if the point of mechanical balanceC

    m= C

    ris placed at an excessively low

    speed, a current peak may occur on themove to full voltage. If this peak is toohigh for the network, the starting modewill have to be reconsidered andstarting by autotransformer, for

    example, chosen (see fig. 36).Remark 1Let us assume that the value of thebreakaway torque of the drivenmachine is 0.35 C

    ninstead of 0.2 C

    n.

    Starting by reactance is thenincompatible with the breakawaytorque.The solution of starting byautotransformer must then beenvisaged.

    The apparent power available remainsS

    d= 5,300 kVA. From this value the

    magnetising force of the auto-

    transformer Smg must be deducedwhich, at the initial starting moment, isarithmetically added to motor apparentpower. S

    mgis around 0.2 to 0.4 times

    motor apparent rated power.

    i.e. with the factor 0.4:

    Smg = 0.4Pn

    cos

    Smg = 0.41,500

    0.84 = 720 kVA .

    The power reduction factor is then:

    Sd SmgSm

    = 5,300 7208,925

    = 0.513

    At constant voltage Un, the current

    inrush on the network side is therefore:0.513 Id.

    Determining the reduced startingvoltage U

    d.

    Equality of primary and secondaryautotransformer powers results in thefollowing:

    0.513 Id Un = I"d UdI"

    dis the reduced voltage starting

    current on the motor side

    0.513 Id Un = Id UdUn

    Ud

    hence:UdUn

    2

    = 0.513

    i.e. Ud = 0.718 Un

    New starting torque:

    0.8 Cn UdUn

    2

    = 0.41 Cn .

    This value is sufficient for starting totake place.

    Remark 2

    For a breakaway torque greater than0.41 C

    n, stator starting with this motor

    is no longer possible.

    Either a slipring rotor motor with rotor

    starting must be used, or a motor with aspecial cage possessing a high startingtorque.

    fig. 36: torque and current curves for starting by reactance.

    a: curve C (N) on full voltage

    b: curve C (N) on reduced voltage (0.6 Un)

    c: curve I (N) on full voltage

    d: curve I (N) on reduced voltage (0.6 Un)

    e: curve Cr (N)

    C

    Cn

    I

    In

  • 7/29/2019 protection of HV motor

    25/28

    Cahier Technique Merlin Gerin n 165 / p.25

    appendix 2: coordination of protection devices

    Once the protection devices have beenchosen according to operatingrequirements, they must be coordinatedto obtain the maximum advantage fromtheir possibilities. A balance must besought between untimely tripping anddelay on fault removal. The problem ofprotection device coordination is solvedby studying the curves t (I) of therelays, of the circuit-breaker and of thebreaking capacity of the contactor. Thecharacteristics of the motor shown inthe figure are as follows:

    c Pn

    = 550 kW;c U

    n= 3150 V;

    cIn

    = 130 A;cId = 5 In.

    The contactor is of the Rollarc fuse type.

    Type of protection devices

    c thermal relay with indirect tripping,set at In = 130 A for overloads;c positive phase sequence componentrelay set at 6 I

    n, time delayed at 0.05 s

    for balanced faults;c negative phase sequence componentrelay set at 0.3 or 0.4 In, time delayed

    at 0.6 s.In the case of networks with quasi-permanent unbalances, a two-thresholdrelay is used:c a lower time delayed threshold, setjust above the permanently acceptednegative phase sequence componentratios;c an upper instantaneous threshold forphase break protection.

    Instantaneous tripping by the positivephase sequence component relayenables best use to be made of thecontactors breaking capacity and

    avoids fuse melting. Analysis of thecurves in figure 37 shows that themotor and network are protectedagainst:c unbalances of approximately 0.3 I

    nto 10 I

    n,

    c balanced faults from 6 In to 28 In.

    The fuses only take action beyond 15 Infor unbalanced faults and 25 I

    nfor

    balanced faults.

    The maximum current the contactormay have to break is 28 In = 3,640 A.This value is considerably lower than itsbreaking capacity of 10 kA.

    fig. 37: minutes thermal relay operating zone.

    1 2 5 10 20 50 100

    130 260 650 1,300 2,600 6,500

    0.01

    0.03

    0.05

    0.1

    1

    5

    10

    20

    40

    1

    2

    34

    68

    10

    20

    30

    40

    60

    cold

    hot

    fuse

    phase sequence

    component:

    negative

    positive

    contactor

    breaking

    time

    minutes

    seconds

    Rollarc contactor

    breaking capacity

    thermal relayoperating zone

    3,640 A

    k InIn (A)

  • 7/29/2019 protection of HV motor

    26/28

    Cahier Technique Merlin Gerin n 165 / p.26

    appendix 3: bibliography

    Standards

    c IEC 34-1: Rotating electricalmachines.

    c IEC 71: Insulation coordination.

    Merlin Gerin's Cahier Technique

    c The breaking process with a FluarcSF6 puffer-type circuit-breaker,Cahier Technique n 112 -J. HENNEBERT

    c Behaviour of the SF6 MV circuit-breakers Fluarc for switching motor

    starting currents,Cahier Technique n 143 -J. HENNEBERT and D. GIBBS

    c Overvoltages and insulationcoordination in MV and HV,Cahier Technique n 151 -D. FULCHIRON

  • 7/29/2019 protection of HV motor

    27/28

    Cahier Technique Merlin Gerin n 165 / p.27

  • 7/29/2019 protection of HV motor

    28/28