Upload
freddyrivera
View
213
Download
1
Embed Size (px)
DESCRIPTION
Proteccion de Barras
Citation preview
n Merlin Gerin n Modicon n Square D n Telemecanique
2-3 ELECTRICAL NETWORK SELECTION GUIDE
a) Power circuit1. MV/LV sensors and accessories
2. Protections2.1 Definitions2.2 Short-circuit currents2.3 Grounding systems2.4 Selectivity2.5 Protection relays2.6 The MV fuse2.7 MV line protection2.8 MV transformer protection2.9 MV motor protection2.10 MV generator protection2.11 MV capacitor bank protection2.12 MV bus tie protection
Which Sepam should be used for the MV bus section protection? The answer is given in the following pages.
2.13 Reserved for later use2.14 Further information on specific protections
3. Measuring apparatus
4. Metering apparatus
5. Recording apparatus
GUIDE
Follow the guide and the arrow to identify
the place of this documentwithin the detailed table of
contents of part 2-3 a)
date
10/94
C23a)212
revised
12/95
MV bus section protection
SELECTION TABLE elect in the table below the corresponding protection schematicsheet, according to the grounding system, the type of network, and relays.S
MV bus section protection
page 2
date
10/94
C23a)212
revised
12/95
see page 3 see page 3
see page 3
see page 3 see page 3
see page 3
type oftransformer
control by
configuration
UNGROUNDED NEUTRAL
remote transmission
Sepam1000
RESISTANCE GROUNDING upstream
of MV incomers
ZERO SEQUENCE GENERATOR
grounding on busbars
Sepam2000
Sepam1000
Sepam2000
Sepam1000
Sepam2000
without MG (JBus)remote transmissionwithout MG (JBus)
remote transmissionwithout MG (JBus)
withdrawablecircuit breaker (2)fixed circuit breaker (1)withdrawablecircuit breaker (2)fixed circuit breaker (1)withdrawablecircuit breaker (2)fixed circuit breaker (1)
MV
BUS
SECT
ION
/ BS01 / BS11 / BS04
BS07 BS02 BS12 BS10 BS08 BS05
/ / / /
/ /
/ / /
/ BS03 / BS09 / BS06
/
+
important:the solutions proposed in this document are for general use.They are a direct application of the MV protection guide ref.: CG0021X(binder C, chapter 1, topic 3).These elements are to be used as a basic solution for tenders. They couldbe also adapted to specific requirements of customer specifications.Sepam 2000 can be use without remote transmission.
+
Remarks:MV motor feeder with Sepam 1000: undervoltage protection (27) load shedding is notinstalled as standard on each MV motor feeder; it does not exist at present for the Sepam 1000motor (refer to MV motor protection guide, chapter C-2-3 a)2.9 and documentation Sepamrange ref. AC0401/1E page 13 of the 07/94). In this case, the protection (27) is installed inthe bus section; a Sepam 1000 busbar per half busbar BB1 and BB2. The informationload shedding by undervoltage (27) is sent by LV circuits to each MV motor feeder equippedwith a Sepam 1000.MV motor feeder with Sepam 2000: undervoltage protection (27) load shedding is installedas standard on each MV motor feeder (refer to MV motor protection guide, chapter C-2-3 a)2.9).intercubicle locking and source transfer: intercubicle locking between the incomers andbus section is of type 2 on 3, with no possibility of incomer parallel connection. If you wish forautomatic source and/or busbar earth leakage transfer (87B), refer to MT partenaire, binderC, chapter C-2-3 a)2.14 entitled additional information on specific protection devices.
note (1): compartmented switchgear and controlgear with non-metallic partitions (SM6). Metal-enclosed switchgear and controlgear in which components are arranged in separatecompartments as for metal-clad switchgear and controlgear, but with one or more non-metallicpartitions (IEC 298). note (2): metal-clad switchgear and controlgear. Metal-enclosed switchgear and controlgear in which components are arranged in separatecompartments with metal partitions intended to be earthed (IEC 298).
page 3
date
10/94
C23a)212
revised
12/95
MV bus section protection
SELECTION TABLE: MV bus sectionwith cubicle type SM6
elect in the table below the corresponding protection schematicsheet, according to the grounding system, the type of network, and relays.
step 1: selection of the protection schematic sheetstep 2: corresponding accessories proposed
S
step 1
ste
p 1
ste
p 2
MV
BUS
SECT
ION
DM1
(3)
type oftransformer
controlby
configuration
RI
with
relea
se (1
)
with
relea
se (2
)
manual moto.
JBus without remote transmission
Sepa
m 2
000
Sepa
m 1
000
Sepa
m 1
00RT
LV comptstype of control
2 sig
nallin
g lam
ps
2 pu
sh b
utto
ns
1 lo
cal-r
emot
e sw
itch
accessories
addi
tiona
l inc
losu
re o
n to
p cu
bicle
low
volta
ge c
ompa
rtmen
t 100
mm
RESISTANCE GROUNDING
upstreamof MV incomers
JBus without remote transmissionSe
pam
200
0
Sepa
m 1
000
Sepa
m 1
00RT
UNGROUNDED NEUTRAL
B B B O O O
B B B O O O
OB B B O O O
B B B O O O
auxiliary contacts
8 8
BS13 BS16
BS14 BS17
BS15 BS18
BS19 BS20BS19 BS20
O = Optional extraB = Basic proposal
note (1): shunt trip opening release. note (2): opening and closing release.note (3): bus section can be made with the following SM6 cubicles:
CM + DM1-D + GBC-Aor CM + DM1-D with TT (optional) or CM + DM2*-D with TT (optional)
*Important: the single-wire representation of a DM2 cubicle is different from the one proposedin these pages (refer to the SM6 range documentation, reference AC0356/1E).
Sepam 1000or 2000
Sepam 100RT
isolatingsupervisionrelay
transformerzero sequencegeneratorMV/LV voltagetransformer with two secondary windings
earth
testing boxMV current transformer
MV voltagetransformer
resistor
MV fuse
MV circuit breaker
ring current transformer
Sepam100RT
Sepam
P1
grounding platefor THR
voltage testlamp
MV load switch
MV contactor
earth switch
MV motor
MV generator
MV capacitor
THR
SYMBOLS USED
ANSI CODE LEXICON 27 : undervoltage32 : directional power37 : undercurrent38/49 : temperature measure46 : reverse phase / phase balance current47 : phase sequence49 : thermal image50 : instantaneous overcurrent50G : instantaneous zero sequence overcurrent on ring CT50N : instantaneous zero sequence overcurrent on CT51 : time delay overcurrent51G : time delay zero sequence overcurrent on ring CT51N : time delay zero sequence overcurrent on CT51LR : rotor jamming and too long start-up51V : overcurrent with voltage restraint59 : overvoltage59N : zero sequence overvoltage66 : number of start-ups67 : directional current67N : directional zero sequence81 : maximum or minimum frequency87B : busbars differential87G : generator differential87L : line differential87M : motor differential87REF : restricted earth fault differential87T : transformer differential74/94 : transformer monitoring
MV bus section protection
page 4
date
10/94
C23a)212
revised
12/95