Fyrehalt EVOLUTION May 2017; Version 1.0 This product specification supersedes all previously issued documentation 1 | Page www.smokecontrol.com.au PROPRIETARY ITEM: FYREHALT - EVOLUTION AUTOMATIC OVERHEAD PERIMETER TYPE FABRIC FIRE CURTAIN PART 1 - GENERAL 1.01 SUMMARY A. Section Includes: 1. Fire alarm or smoke detector-activated, overhead coiling fabric fire curtain. 2. Self-closing without auxiliary power. 3. For small and medium protected openings. B. Related Requirements: 1. Access Panels. 2. Load Bearing Header Framing 3. Finish: Powder coating of specified components. 4. Detection and Alarm: Provision of fire alarm. 5. Site Electrical: Provision of 240VAC, 10Amp General purpose outlets (GPO’s) 6. Product Electrical: System connection including cable glands, junction boxes, conductors, wiring devices, and backup power. 1.02 REFERENCES A. National Construction Code and Fire Engineers Report: 1. NCC 2014/2015 2. FE Report Y; Version XX, Dated; B. Standards: 1. AS1670 Automatic detection and alarm systems 2. AS1530.4 Methods for fire tests on building materials, components and structures, Part 4 Fire- resistance test of elements of construction. 3. AS1905.2 Fire Shutters. 4. AS3837Method of test for heat and smoke release rates for materials and products using an oxygen consumption calorimeter 5. AS6905.1 Smoke Doors 6. AS1530.7 Methods for fire tests on building materials, components and structures. Part 7 Smoke control assemblies ambient and medium temperature leakage test procedure. 7. UL864 Control Units for Fire Protective Signaling Systems 1.03 SUSTAINABLE DESIGN REQUIREMENTS A. ESD: Comply with sustainable design requirements including, without limitation, submittal and documentation requirements. B. Credit/Point Goals Applicable To This Section: In addition to global project credit/point goals: 1. Materials & Resources - construction waste management 2. Materials & Resources - recycled content 3. Materials & Resources - regional materials 4. Indoor Environmental Quality - construction IAQ management plan

PROPRIETARY ITEM: FYREHALT - EVOLUTION AUTOMATIC OVERHEAD PERIMETER ... - Smoke Control · 2019-02-20 · 2. Smoke leakage: ≤75m3/hour through the fabric when tested in accordance

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

  • Fyrehalt EVOLUTION May 2017; Version 1.0

    This product specification supersedes all previously issued documentation

    1 | P a g e w w w . s m o k e c o n t r o l . c o m . a u

    PROPRIETARY ITEM: FYREHALT - EVOLUTION

    AUTOMATIC OVERHEAD PERIMETER TYPE FABRIC FIRE CURTAIN

    PART 1 - GENERAL

    1.01 SUMMARY

    A. Section Includes: 1. Fire alarm or smoke detector-activated, overhead coiling fabric fire curtain. 2. Self-closing without auxiliary power. 3. For small and medium protected openings.

    B. Related Requirements: 1. Access Panels. 2. Load Bearing Header Framing 3. Finish: Powder coating of specified components. 4. Detection and Alarm: Provision of fire alarm. 5. Site Electrical: Provision of 240VAC, 10Amp General purpose outlets (GPO’s) 6. Product Electrical: System connection including cable glands, junction boxes, conductors,

    wiring devices, and backup power.

    1.02 REFERENCES

    A. National Construction Code and Fire Engineers Report: 1. NCC 2014/2015 2. FE Report Y; Version XX, Dated;

    B. Standards:

    1. AS1670 − Automatic detection and alarm systems 2. AS1530.4 – Methods for fire tests on building materials, components and structures, Part 4 Fire-

    resistance test of elements of construction.

    3. AS1905.2 – Fire Shutters. 4. AS3837– Method of test for heat and smoke release rates for materials and products using an

    oxygen consumption calorimeter

    5. AS6905.1 – Smoke Doors 6. AS1530.7 – Methods for fire tests on building materials, components and structures. Part 7 –

    Smoke control assemblies – ambient and medium temperature leakage test procedure.

    7. UL864 − Control Units for Fire Protective Signaling Systems

    1.03 SUSTAINABLE DESIGN REQUIREMENTS

    A. ESD: Comply with sustainable design requirements including, without limitation, submittal and documentation requirements.

    B. Credit/Point Goals Applicable To This Section: In addition to global project credit/point goals: 1. Materials & Resources - construction waste management 2. Materials & Resources - recycled content 3. Materials & Resources - regional materials 4. Indoor Environmental Quality - construction IAQ management plan

  • Fyrehalt EVOLUTION May 2017; Version 1.0

    This product specification supersedes all previously issued documentation

    2 | P a g e w w w . s m o k e c o n t r o l . c o m . a u

    1.04 SUBMITTALS

    A. Comply with Submittal Procedures: 1. NCC Clause A2.4 Evidence of Suitability – submit full scale fire test report and Formal Opinion

    from a Registered Testing Authority clearly identifying maximum Fire Resistance Level and

    maximum allowable sizes.

    2. Manufacturers Product data 3. Shop drawings:

    a. Curtain location and unique identification number b. Include opening dimensions c. Show and identify related work performed under other sections of the specifications

    including access and electrical requirements

    4. Quality Assurance/Control Submittals: a. Site Inspection and Test Plan. b. Manufacturers ISO 9001 Certificate of Accreditation

    1.05 CLOSEOUT SUBMITTALS

    A. Comply with Project Closeout: 1. Certificate of Compliance with reference to Fire Engineers Report and Evidence of Suitability. 2. Operation and maintenance manual. 3. Manufacturer’s warranty.

    1.06 QUALITY ASSURANCE

    A. Certifications: 1. AS1530.4 full scale fire test on a complete assembly in a fire rated plasterboard bulkhead 2. National Construction Code Clause C1.10 when tested to AS3837 3. AS1530.7 full scale air (smoke) leakage test on a complete assembly 4. Laboratory cycle tested on a 10m x 3m complete assembly

    B. Pre-Installation Meeting: 1. Schedule and convene a pre-installation meeting prior to commencement of field operations

    with representatives of the following in attendance: Owner, Architect, General Contractor, fire

    curtain sub-contractor, mechanical sub-contractor, electrical sub-contractor, and ceiling/fitout

    sub-contractor

    2. Review substrate conditions, requirements of related work, installation instructions, storage and handling procedures, and protection measures.

    3. Document the responsibilities of various parties and deviations from specifications and installation instructions.

    1.07 DELIVERY, STORAGE, AND HANDLING

    A. Comply with project delivery, storage, and handling requirements.

    B. Comply with manufacturer’s instructions.

  • Fyrehalt EVOLUTION May 2017; Version 1.0

    This product specification supersedes all previously issued documentation

    3 | P a g e w w w . s m o k e c o n t r o l . c o m . a u

    1.08 WARRANTY

    A. Provide manufacturer’s standard one year warranty for Defect Liability Period.

    B. Provide manufacturer’s standard 5 year product and installation warranty in conjunction with a Smoke Control’s standard 5 + 5 year maintenance contract

    C. Maintenance and Testing: 1. Perform minimum quarterly maintenance and testing on each fire curtain as required by the

    manufacturer’s warranty, AS1851 - Maintenance, and as required by the Fire Engineers Report.

    2. Provide Commissioning documentation including Project name, project address, location and curtain number, number of cycles tested, observations, comments (eg: curtain out of alignment),

    notes (eg: curtain alignment repaired), Pass/fail.

    3. Re-certification after the defect liability period

    PART 2 - PRODUCTS

    2.01 MANUFACTURED UNITS

    A. Proprietary item; Model Fyrehalt - EVOLUTION automatic fire curtain.

    B. Manufacturer: 1. Smoke Control Systems Pty Ltd 2. Distributed by Smoke Control Systems Pty Ltd, 26 Ferndell St, South Granville, NSW 2142,

    Australia www.smokecontrol.com.au

    C. Label each fire curtain with following information: 1. Manufacturer’s name and contact details. 2. Curtain location and unique identification number 3. Fire Resistance Level 4. Date of installation

    2.02 DESIGN CRITERIA

    A. Country of Manufacture: Australia

    B. Head box; 150 H x 490 W mm

    C. Side guide; 100 mm x 50mm (nominal, refer manufacturer’s drawings).

    D. Fabric type; 660g/m2 stainless steel woven fabric, incorporating a coated glassfibre material to reduce radiant heat transmission.

    E. Motor type; Proprietary Smoke Control 24V tubular motor with torque selection based on curtain size with upper and lower limit settings.

    F. Bottom bar; 300 mm wide (at the base) sheet metal pan type section, requiring a 310mm min. slot in the ceiling lining.

    See manufacturer’s literature for head box and side guide mounting options.

  • Fyrehalt EVOLUTION May 2017; Version 1.0

    This product specification supersedes all previously issued documentation

    4 | P a g e w w w . s m o k e c o n t r o l . c o m . a u

    G. Accessories; a. Curtain mounted re-wind switch b. Flush ceiling mounted radial obstruction sensors spaced as required c. Strobes and sounders

    H. Finishes; Dulux Duralloy colour range (Standard)

    I. Load requirements at head = 25kg/m of width

    J. Load requirements at sides (only if side guide required) = 20kg/m of height

    K. Mounting orientation 1. Installation Configuration: Housing attached directly to substrate above opening 2. -/120/120 fire rated bulkhead to be constructed by others in accordance with Smoke Control

    drawing number XXXX

    2. Fabricate and install mounting brackets, hardware, and fasteners needed to attach fire curtain

    assembly to building structure.

    L. Signage on curtain (standard stencils) 1. Green running man (dimensions) 2. Arrows (dimensions) 3. Fire Safety Curtain (dimensions) 4. Push Button (dimensions)

    2.03 PERFORMANCE CRITERIA 1. Fire Resistance Level (FRL): -/120/- 2. Smoke leakage: ≤75m3/hour through the fabric when tested in accordance with a permeability

    test

    3. Group Number for fabric: 1 when tested in accordance with AS3837 4. Durability; medium duty – tested to 500 maintenance free cycles

    5. Maximum pressure; 40Pa (for higher application please discuss with Smoke Control engineering staff)

    6. Maximum allowable gap to non-combustible sill 25mm 7. Combustible floor coverings permitted at threshold (conditions apply) 8. Closing time of 100 - 200mm/sec 9. Time delay to required (exhaust/pressurization) fan speed = 60 seconds (min) – 90 seconds

    (max). Time is dependent on drop height of curtain.

    10. Time delay for rewind; ensure fan speed is zero + 20 seconds prior to reset of alarm signal from FIP enabling curtain rewind.

    11. Fail safe close on loss of power and/or signal trip using battery backup. 12. Motor rewind automatically on re-set of power and alarm signal, no service call needed. 13. Battery backup to reduce nuisance deploys required. 14. Commissioning shall be conducted in conjunction with Mechanical services and detection/alarm

    system. Systems shall be balanced to work together without over pressurizing the fire curtain.

    15. Maintenance shall be conducted quarterly by the Manufacturer and/or their nominated representative to the Manufacturers recommendations.

    2.04 COMPONENTS

    A. Curtain Fabric: Fyrehalt fabric glass 2002 - Glass fibre material with stainless steel wire reinforcement, coated on a single side with polyurethane and incorporating a RED cotton strip for

    identification purposes.

  • Fyrehalt EVOLUTION May 2017; Version 1.0

    This product specification supersedes all previously issued documentation

    5 | P a g e w w w . s m o k e c o n t r o l . c o m . a u

    B. Side Guide Assembly: 1.6mm thick Zincalume mild steel incorporating no moving parts.

    C. Housing Type: 2.0mm thick galvanized mild steel head box incorporating motor brackets, and drive system

    D. Drive system: Drive shaft system forming a single continuous drive unit once installed. Powered by 24V motors and 240V motor controllers. All concealed within the head box structure.

    E. Bottom Bar: 1.6mm thick galvanized mild steel pan section

    F. SCS1500 Series Rewind Motor 1. Tubular motor with fail safe gravity deploy operation 2. Upper and lower limit settings 3. 24 VDC.

    G. SCS1500 Series Master and slave control set 1. Battery backup 2. 240 VAC power 3. Normally open 0 Volt alarm signal

    PART 3 - EXECUTION

    3.01 EXAMINATION

    A. Examine substrates upon which work will be installed. 1. Verify related work performed under other sections is complete and in accordance with shop

    drawings.

    2. Verify wall surfaces are acceptable for installation of fire curtain system components 3. Verify setout point locations.

    B. Coordinate with responsible entity to perform corrective work on unsatisfactory substrates.

    C. Coordinate electrical interface and connection with Electrical sub-contractor.

    D. Coordinate fire and alarm interface with fire sub-contractor.

    E. Commencement of work by installer is acceptance of substrate.

    3.02 INSTALLATION

    A. Install fire curtain system components in accordance with fire test approvals and manufacturer’s installation instructions.

    B. For reliability, corners are to be folded to continue the concertina action of the system. Flat fabric that bunches on rewind will ultimately cause operational issues and affect overall reliability of the system.

    Products not incorporating folded corners are not to be used on this project.

    C. While some Registered Testing Authorities provide Formal Opinions in regards to the expected fire resistance level of fire curtains, they do not discuss nor provide a warranty in regards to their

    reliability. Experience shows that some manufacturer designs of fire curtains do not operate reliably

    once installed and attract extraordinarily high maintenance costs. For this reason multiple barrel,

    overlapped fire curtains are deemed not equivalent to this specification on this project and shall not be

    substituted for a single barrel continuous span system.

    D. Once installed it shall be demonstrated that the system shall gravity fail safe close on the receipt of an alarm signal or loss of power without the need of battery backup. On reset of power and the alarm

    signal the system shall automatically rewind to its standby position.

  • Fyrehalt EVOLUTION May 2017; Version 1.0

    This product specification supersedes all previously issued documentation

    6 | P a g e w w w . s m o k e c o n t r o l . c o m . a u

    3.03 FIELD QUALITY CONTROL

    A. Field Test 1: Calibration

    Follow manufacturer’s cycle test procedures prior to application of mechanical services.

    1. Conduct a minimum of 10 consecutive, error free cycle tests 2. Complete Inspection and Test Plan

    B. Field Test 2: Balancing test

    Test operation on general alarm in conjunction with mechanical services

    1. Adjust fan speed and activation timing to ensure pressure does not exceed 25Pa across fire curtain and to minimize gaps at the sill.

    C. Field Test 3: Commissioning Test operation on general alarm (or zone alarm as required by Fire Engineers Report) by activating an

    adjacent smoke detector

    1. Notify Owner’s Representative, local Fire Services and alarm sub-contractor minimum one week in advance of scheduled testing.

    2. Complete Commissioning submittals.

    END OF SECTION

  • SCS PROJECT - SCS-FHE

    FYREHALT EVOLUTION TYPICAL DETAILS

    ATTENTION: TECHNICAL REQUIREMENTS FOR THIS PROJECT

    No DESCRIPTION

    REQUIREMENT

    RESPONSIBILITY

    1 SHOP DRAWINGS APPROVAL OF SHOP DRAWINGS (SIGNITURE AND DATE) IS

    REQUIRED TO BE RETURNED TO SMOKE CONTROL SYSTEM

    BEFORE MANUFACTURE CAN COMMENCE.

    BUILDER, ARCHITECT

    2 DELIVERIES TO SITE IF REQD, FORKLIFT TO BE MADE AVAILABLE. BUILDER

    3 VERTICAL MOVEMENT

    OF PRODUCT

    IF REQD, CRANE SHALL BE AVAILABLE TO SMOKE CONTROL

    SYSTEMS AT AGREED TIME OF DELIVERY. IF THIS IS NOT

    AVAILABLE, THIS MAY INCUR EXTRA CHARGES.

    BUILDER

    4 STORAGE SUFFICIENT CLEAR FLOOR SPACE TO BE MADE AVAILABLE

    IMMEDIATELY ADJACENT TO EACH INSTALLATION

    LOCATION.

    BUILDER

    5 ACCESS TO WORKFACE

    (INSTALLATION)

    ADEQUATE WORKING AREA REQD., MIN 500mm FROM SYSTEM

    TO STRUCTURE IS IDEAL. SUBJECT TO SITE CONDITIONS.

    BUILDER

    6 BALUSTRADES

    (WHERE PRESENT)

    BALLUSTRADES MUST NOT INTERFERE WITH THE OPERATION

    OF CURTAIN IN ANY WAY. MIN. 100mm FROM SYSTEM TO

    BALUSTRADE OFFSET IS IDEAL.

    BUILDER

    7 ACCESS PANELS

    (INSTALATION WITHIN

    CEILING CAVITY)

    450X450 NOM. ACCESS PANELS TO BE PROVIDED. THREE

    EQUALY SPACED PANELS (ONE ON EITHER END AND ONE DEAD

    CENTRE) WILL BE REQUIRED WHERE ACCESS TO HEAD BOX IS

    RESTRICTED.

    BUILDER, CEILING

    CONTRACTOR

    8 POWER REQUIREMENTS 240 VOLT 10 AMP GPO TO BE LOCATED WITHIN 1 METRE OF

    CURTAIN HEAD BOX ON MOTOR SIDE.

    BUILDER, ELECTRICAL

    9 ALARM SIGNAL,

    ACTIVATION

    0 VOLT NORMALLY OPEN CONTACT (CLOSED ON ALARM) TO

    BE PROVIDED WITHIN 1 METRE OF CURTAIN HEAD BOX ON

    MOTOR SIDE.

    BUILDER, ELECTRICAL,

    FIRE

    10 PRESSURISATION,

    EXHAUST SYSTEMS

    IMPORTANT: BALANCING TO CONSIDER AFFECTS OF

    CURTAINS 20 PA MAX. PRESSURE DIFFERENTIAL STRONGLY

    RECOMMENDED.

    BULDER,

    MECHANICAL SERVICES

    11 TUNING ALL SCAFFOLDING & OTHER TRADES TO BE CLEAR 2 DAYS

    PRIOR TO TUNING & COMMISSIONING.

    BUILDER

    12 COMMISSIONING

    STAGE 1

    PRACTICAL COMPLETION TESTS: PERMANENT POWER &

    ALARMS CONNECTED FOR DRY RUN PRIOR TO CSC. CURTAINS

    MUST BE ISOLATED DURING INDIVIDUAL COMMISSIONING OF

    OTHER ESSENTIAL SERVICES.

    (PRODUCT LOCKED IN OPEN POSITION AFTER TESTING)

    SMOKE CONTROL

    SYSTEMS & BUILDER

    13 COMMISSIONING

    STAGE 2

    COORDINATED SERVICES COMMISSIONING (CSC) SMOKE CONTROL

    SYSTEMS

    14 COMMISSIONING

    STAGE 3

    WITNESS TESTING, FINAL COMMISSIONING & HANDOVER SMOKE CONTROL

    SYSTEMS

    IRFOR INFORMATION ONLY

    26/07/2016-

    PRODUCT SPECIFICATIONS

    SYSTEM COMPONENT MATERIALS FRL

    COLOUR/FINISH

    FILE: AU

    16046.dw

    g --- PLO

    TTED

    O

    N 16/08/2017 BY IG

    OR REBEN

    KO

    THIS DRAWING IS COPYRIGHT AND THE PROPERTY OF THE AUTHOR, AND

    MUST NOT BE RETAINED, COPIED OR USED WITHOUT THE AUTHORITY OF

    SMOKE CONTROL SYSTEMS PTY. LTD.

    DO NOT SCALE FROM DRAWING, USE PROVIDED DIMENSIONS ONLY.

    ALL DISCREPENCIES MUST BE BROUGHT TO THE ATTENTION OF AUTHOR.

    SMOKE CONTROL SYSTEMS DO NOT TAKE RESPONSIBILITY OF

    MEASUREMENTS PROVIDED BY OTHERS.

    R

    e

    v

    CHK REASON DATE

    CLIENT

    NSW HEADOFFICEPHONE: 1300 665 47126 FERNDELL ST,(ENTER VIA STRAITS AVE)SOUTH GRANVILLE NSW 2142

    VICTORIA OFFICEPHONE: 0417 657 623336 SETTLEMENT RDTHOMASTOWN VIC 3074

    WESTERN AUSTRALIA:AUSTRALIAN FIRE CONTROLPHONE: 08 9399 6957UNIT 2, 71-73 BRANT RDKELMSCOTT WA 6997

    NEW ZEALANDPHONE: 09 300 1980LEVEL 4, 369 QUEEN STAUCKLAND NZ 1010

    WWW.SMOKECONTROL.COM.AU

    1 2 3 45 6

    1 2 3 4 5 6A

    BC

    DE

    F

    DRAWN BY

    START DATE

    DRAWING NUMBER

    ISSUE STATUS:

    TITLE

    PROJECT

    AB

    EF

    >

    SCALE

    @A2

    SUB SET (CATEGORY)

    COPY ONLY

    INFORMATION GIVEN IN SMOKECONTROL.COM.AU AND PUBLICATIONS

    FOR DOWNLOAD ARE GIVEN TO THE BEST OF OUR KNOWLEDGE AND

    IN GOOD FAITH. SMOKE CONTROL IS NOT RESPONSIBLE IF

    RECIPIENTS OF TEST REPORTS, ASSESSMENTS OR LITERATURE

    MISINTERPRET THE CONTENTS AND WRONGLY USE PRODUCTS BASED

    ON THOSE MISINTERPRETATIONS. NO LIABILITY IS ACCEPTED FOR

    ERROR OMISSIONS IN THIS WEB SITE OR OUR DOCUMENTS. IN THE

    INTERESTS OF IMPROVEMENTS AND CONTINUED DEVELOPMENT

    SMOKE CONTROL RESERVES THE RIGHT TO CHANGE SPECIFICATION

    WITHOUT NOTICE.

    DISCLAIMER

    SCS-FHE

    FYREHALT EVOLUTION TEMPLATE

    COVER SHEET

    PRODUCT SPECS

    SCS-FHE-0001

    IGOR REBENKO FOR INFORMATION

    26/07/2016 N/A

    FYREHALT EVOLUTION

    PRODUCT TEMPLATE

    00 - SPECIFICATIONS

    FYREHALT

    EVOLUTION

    FABRIC

    -/120/-

    FABRIC

    STANDARD (GREY)

    SIDE GUIDES GALVANISED STEEL BOTTOM TRAY

    DULUX DURALLOY POWDER COAT RANGE

    OTHER RANGES AVAILABLE BUT MAY INCUR EXTRA COS - PLEASE CONTACT SCS FOR ADVICE

    HEAD BOX & BOTTOM BAR GALVANISED STEEL SHROUDS

    DRAWING INDEX

    SHEET DESCRIPTION REV

    00 - SPECIFICATIONS

    0001 COVER SHEET -

    01 - PLANS

    0101 SQUARE CONFIG. PLAN -

    0102 OTHER CLOSED CONFIGURATIONS -

    0103 TYP. OPEN ENDED CONFIGURATION PLAN -

    02 - ELEVATIONS

    0201 ELEVATION SECTION 1 -

    0202 ELEVATION SECTION 2 -

    03 - DETAILS

    0301 HEAD BOX DETAIL -

    0302 HEAD BOX DETAIL -

    0303 STUD WALL END GUIDE DETAIL -

    0304 FR POST END GUIDE DETAIL -

    0305 SENSOR MOUTING & 224 HEAD BOX DETAIL -

    10 - ELECTRICAL

    1001 TYP. ELECTRICAL COORDINATION -

    1002 TYP. OBSTRUCTION SENSOR SETOUT -

  • D

    FILE: AU

    16046.dw

    g --- PLO

    TTED

    O

    N 16/08/2017 BY IG

    OR REBEN

    KO

    THIS DRAWING IS COPYRIGHT AND THE PROPERTY OF THE AUTHOR, AND

    MUST NOT BE RETAINED, COPIED OR USED WITHOUT THE AUTHORITY OF

    SMOKE CONTROL SYSTEMS PTY. LTD.

    DO NOT SCALE FROM DRAWING, USE PROVIDED DIMENSIONS ONLY.

    ALL DISCREPENCIES MUST BE BROUGHT TO THE ATTENTION OF AUTHOR.

    SMOKE CONTROL SYSTEMS DO NOT TAKE RESPONSIBILITY OF

    MEASUREMENTS PROVIDED BY OTHERS.

    R

    e

    v

    CHK REASON DATE

    CLIENT

    NSW HEADOFFICEPHONE: 1300 665 47126 FERNDELL ST,(ENTER VIA STRAITS AVE)SOUTH GRANVILLE NSW 2142

    VICTORIA OFFICEPHONE: 0417 657 623336 SETTLEMENT RDTHOMASTOWN VIC 3074

    WESTERN AUSTRALIA:AUSTRALIAN FIRE CONTROLPHONE: 08 9399 6957UNIT 2, 71-73 BRANT RDKELMSCOTT WA 6997

    NEW ZEALANDPHONE: 09 300 1980LEVEL 4, 369 QUEEN STAUCKLAND NZ 1010

    WWW.SMOKECONTROL.COM.AU

    1 2 3 45 6

    1 2 3 4 5 6A

    BC

    DE

    F

    DRAWN BY

    START DATE

    DRAWING NUMBER

    ISSUE STATUS:

    TITLE

    PROJECT

    AB

    EF

    >

    SCALE

    @A2

    SUB SET (CATEGORY)

    COPY ONLY

    INFORMATION GIVEN IN SMOKECONTROL.COM.AU AND PUBLICATIONS

    FOR DOWNLOAD ARE GIVEN TO THE BEST OF OUR KNOWLEDGE AND

    IN GOOD FAITH. SMOKE CONTROL IS NOT RESPONSIBLE IF

    RECIPIENTS OF TEST REPORTS, ASSESSMENTS OR LITERATURE

    MISINTERPRET THE CONTENTS AND WRONGLY USE PRODUCTS BASED

    ON THOSE MISINTERPRETATIONS. NO LIABILITY IS ACCEPTED FOR

    ERROR OMISSIONS IN THIS WEB SITE OR OUR DOCUMENTS. IN THE

    INTERESTS OF IMPROVEMENTS AND CONTINUED DEVELOPMENT

    SMOKE CONTROL RESERVES THE RIGHT TO CHANGE SPECIFICATION

    WITHOUT NOTICE.

    DISCLAIMER

    SCS-FHE

    FYREHALT EVOLUTION

    PLAN

    SQUARE CONFIGURATION

    SCS-FHE-0101

    IGOR REBENKO FOR INFORMATION

    26/07/2016 1:25

    FYREHALT EVOLUTION

    PRODUCT TEMPLATE

    01 - PLANS

    1

    PLAN

    FYREHALT EVOLUTION - FIRE CURTAIN

    SCALE 1:25 @ A2

    2 3

    E

    4600 (BU

    LKH

    EAD

    &

    CU

    RTAIN

    H

    EAD

    BO

    X - IN

    TERN

    AL)

    493

    5586 (CU

    RTAIN

    H

    EAD

    BO

    X - EXTERN

    AL)

    493

    FIRE CURTAIN BOTTOM TRAY CLEAR ZONE SHOWN DASHED

    2000

    307

    2600

    307

    693

    507

    5786 (CURTAIN HEAD BOX - EXTERNAL)

    11071107

    493

    4800 (BULKHEAD & CURTAIN HEAD BOX - INTERNAL)

    493

    3071293 307 1293

    5600 (BU

    LKH

    EAD

    EXTERN

    AL)

    7

    7

    5800 (BULKHEAD EXTERNAL)

    77

    1100 1100

    500

    A

    0201

    A

    0201

    B

    0202

    B

    0202

    IRFOR INFORMATION ONLY

    26/07/2016-

  • A

    IR FOR APPROVAL 26/07/2016

    FILE: Fyrehalt Evolution.dwg --- PLO

    TTED ON

    16/08/2017 BY IGOR REBEN

    KOTHIS DRAWING IS COPYRIGHT AND THE PROPERTY OF THE AUTHOR, ANDMUST NOT BE RETAINED, COPIED OR USED WITHOUT THE AUTHORITY OFSMOKE CONTROL SYSTEMS PTY. LTD.DO NOT SCALE FROM DRAWING, USE PROVIDED DIMENSIONS ONLY.ALL DISCREPENCIES MUST BE BROUGHT TO THE ATTENTION OF AUTHOR.SMOKE CONTROL SYSTEMS DO NOT TAKE RESPONSIBILITY OFMEASUREMENTS PROVIDED BY OTHERS.

    Rev CHK REASON DATE

    CLIENT

    NSW HEADOFFICEPHONE: 1300 665 47126 FERNDELL ST,(ENTER VIA STRAITS AVE)SOUTH GRANVILLE NSW 2142

    VICTORIA OFFICEPHONE: 0417 657 623336 SETTLEMENT RDTHOMASTOWN VIC 3074

    WESTERN AUSTRALIA:AUSTRALIAN FIRE CONTROLPHONE: 08 9399 6957UNIT 2, 71-73 BRANT RDKELMSCOTT WA 6997

    NEW ZEALANDPHONE: 09 300 1980LEVEL 4, 369 QUEEN STAUCKLAND NZ 1010

    WWW.SMOKECONTROL.COM.AU

    1 2 3 4 5 61 2 3 4 5 6

    AB

    CD

    EF

    DRAWN BY

    START DATE

    DRAWING NUMBER

    ISSUE STATUS:

    TITLE

    PROJECT

    AB

    EF

    >

    SCALE@A2

    SUB SET (CATEGORY)

    COPY ONLY

    INFORMATION GIVEN IN SMOKECONTROL.COM.AU ANDPUBLICATIONS FOR DOWNLOAD ARE GIVEN TO THE BEST OF OURKNOWLEDGE AND IN GOOD FAITH. SMOKE CONTROL IS NOTRESPONSIBLE IF RECIPIENTS OF TEST REPORTS, ASSESSMENTS ORLITERATURE MISINTERPRET THE CONTENTS AND WRONGLY USEPRODUCTS BASED ON THOSE MISINTERPRETATIONS. NO LIABILITY ISACCEPTED FOR ERROR OMISSIONS IN THIS WEB SITE OR OURDOCUMENTS. IN THE INTERESTS OF IMPROVEMENTS ANDCONTINUED DEVELOPMENT SMOKE CONTROL RESERVES THE RIGHTTO CHANGE SPECIFICATION WITHOUT NOTICE.

    DISCLAIMER

    SCS-FHE

    FYREHALT EVOLUTIONOTHER CLOSEDCONFIGURATIONS

    SCS-FHE-0102

    IGOR REBENKO FOR INFORMATION

    26/07/2016 NTS

    FYREHALT EVOLUTIONPRODUCT TEMPLATE

    01 - PLANS

    REFLECTED CEILING PLANCONFIG 1

    REFLECTED CEILING PLANCONFIG 2

    REFLECTED CEILING PLANCONFIG 3

    REFLECTED CEILING PLANCONFIG 4

  • FILE: AU

    16055-AR.dw

    g --- PLO

    TTED

    O

    N 16/08/2017 BY IG

    OR REBEN

    KO

    THIS DRAWING IS COPYRIGHT AND THE PROPERTY OF THE AUTHOR, AND

    MUST NOT BE RETAINED, COPIED OR USED WITHOUT THE AUTHORITY OF

    SMOKE CONTROL SYSTEMS PTY. LTD.

    DO NOT SCALE FROM DRAWING, USE PROVIDED DIMENSIONS ONLY.

    ALL DISCREPENCIES MUST BE BROUGHT TO THE ATTENTION OF AUTHOR.

    SMOKE CONTROL SYSTEMS DO NOT TAKE RESPONSIBILITY OF

    MEASUREMENTS PROVIDED BY OTHERS.

    R

    e

    v

    CHK REASON DATE

    CLIENT

    NSW HEADOFFICEPHONE: 1300 665 47126 FERNDELL ST,(ENTER VIA STRAITS AVE)SOUTH GRANVILLE NSW 2142

    VICTORIA OFFICEPHONE: 0417 657 623336 SETTLEMENT RDTHOMASTOWN VIC 3074

    WESTERN AUSTRALIA:AUSTRALIAN FIRE CONTROLPHONE: 08 9399 6957UNIT 2, 71-73 BRANT RDKELMSCOTT WA 6997

    NEW ZEALANDPHONE: 09 300 1980LEVEL 4, 369 QUEEN STAUCKLAND NZ 1010

    WWW.SMOKECONTROL.COM.AU

    1 2 3 45 6

    1 2 3 4 5 6A

    BC

    DE

    F

    DRAWN BY

    START DATE

    DRAWING NUMBER

    ISSUE STATUS:

    TITLE

    PROJECT

    AB

    EF

    >

    SCALE

    @A2

    SUB SET (CATEGORY)

    COPY ONLY

    INFORMATION GIVEN IN SMOKECONTROL.COM.AU AND PUBLICATIONS

    FOR DOWNLOAD ARE GIVEN TO THE BEST OF OUR KNOWLEDGE AND

    IN GOOD FAITH. SMOKE CONTROL IS NOT RESPONSIBLE IF

    RECIPIENTS OF TEST REPORTS, ASSESSMENTS OR LITERATURE

    MISINTERPRET THE CONTENTS AND WRONGLY USE PRODUCTS BASED

    ON THOSE MISINTERPRETATIONS. NO LIABILITY IS ACCEPTED FOR

    ERROR OMISSIONS IN THIS WEB SITE OR OUR DOCUMENTS. IN THE

    INTERESTS OF IMPROVEMENTS AND CONTINUED DEVELOPMENT

    SMOKE CONTROL RESERVES THE RIGHT TO CHANGE SPECIFICATION

    WITHOUT NOTICE.

    DISCLAIMER

    SCS-FHE

    FYREHALT EVOLUTION

    TYP. OPEN ENDED

    CONFIGURATION PLAN

    SCS-FHE-AR-0103

    IGOR REBENKO FOR INFORMATION

    26/07/2016 SCALE: 1:25

    FYREHALT EVOLUTION

    PRODUCT TEMPLATE

    01 - PLANS

    1

    PLAN

    TYP. OPEN ENDED CONFIGURATION PLAN

    SCALE 1:25 @ A2

    2476 (SYSTEM

    O

    UTER) TBC

    7678 (SYSTEM OUTER) TBC

    493

    6692 (SYSTEM INNER) TBC

    493

    493

    1983 (SYSTEM

    IN

    NER) TBC

    46

    DROP TRAY SHOWN HATCHED

    297

    115 NOM.

    HEAD BOX ABOVE SHOWN DASHED

    192

    99

    1500 (VO

    ID

    ABO

    VE)

    4420 (VOID ABOVE)

    2172055

    500

    IR FOR INFORMATION ONLY 26/07/2016-

    28

    1

    0302

    1

    0303

  • FILE: AU

    16046.dw

    g --- PLO

    TTED

    O

    N 16/08/2017 BY IG

    OR REBEN

    KO

    THIS DRAWING IS COPYRIGHT AND THE PROPERTY OF THE AUTHOR, AND

    MUST NOT BE RETAINED, COPIED OR USED WITHOUT THE AUTHORITY OF

    SMOKE CONTROL SYSTEMS PTY. LTD.

    DO NOT SCALE FROM DRAWING, USE PROVIDED DIMENSIONS ONLY.

    ALL DISCREPENCIES MUST BE BROUGHT TO THE ATTENTION OF AUTHOR.

    SMOKE CONTROL SYSTEMS DO NOT TAKE RESPONSIBILITY OF

    MEASUREMENTS PROVIDED BY OTHERS.

    R

    e

    v

    CHK REASON DATE

    CLIENT

    NSW HEADOFFICEPHONE: 1300 665 47126 FERNDELL ST,(ENTER VIA STRAITS AVE)SOUTH GRANVILLE NSW 2142

    VICTORIA OFFICEPHONE: 0417 657 623336 SETTLEMENT RDTHOMASTOWN VIC 3074

    WESTERN AUSTRALIA:AUSTRALIAN FIRE CONTROLPHONE: 08 9399 6957UNIT 2, 71-73 BRANT RDKELMSCOTT WA 6997

    NEW ZEALANDPHONE: 09 300 1980LEVEL 4, 369 QUEEN STAUCKLAND NZ 1010

    WWW.SMOKECONTROL.COM.AU

    1 2 3 45 6

    1 2 3 4 5 6A

    BC

    DE

    F

    DRAWN BY

    START DATE

    DRAWING NUMBER

    ISSUE STATUS:

    TITLE

    PROJECT

    AB

    EF

    >

    SCALE

    @A2

    SUB SET (CATEGORY)

    COPY ONLY

    INFORMATION GIVEN IN SMOKECONTROL.COM.AU AND PUBLICATIONS

    FOR DOWNLOAD ARE GIVEN TO THE BEST OF OUR KNOWLEDGE AND

    IN GOOD FAITH. SMOKE CONTROL IS NOT RESPONSIBLE IF

    RECIPIENTS OF TEST REPORTS, ASSESSMENTS OR LITERATURE

    MISINTERPRET THE CONTENTS AND WRONGLY USE PRODUCTS BASED

    ON THOSE MISINTERPRETATIONS. NO LIABILITY IS ACCEPTED FOR

    ERROR OMISSIONS IN THIS WEB SITE OR OUR DOCUMENTS. IN THE

    INTERESTS OF IMPROVEMENTS AND CONTINUED DEVELOPMENT

    SMOKE CONTROL RESERVES THE RIGHT TO CHANGE SPECIFICATION

    WITHOUT NOTICE.

    DISCLAIMER

    SCS-FHE

    FYREHALT EVOLUTION

    ELEVATION SECTION 1

    SCS-FHE-0201

    IGOR REBENKO FOR INFORMATION

    26/07/2016 ----

    FYREHALT EVOLUTION

    PRODUCT TEMPLATE

    02 - ELEVATIONS

    A

    ELEVATION LOOKING NORTH

    FYREHALT EVOLUTION - FIRE CURTAIN

    SCALE 1:25 @ A2

    LEVEL 8

    FCL

    2700

    LEVEL 7

    U/S BULKHEAD

    2900

    5800 (BULKHEAD EXTERNAL)

    7

    5786 (CURTAIN HEAD BOX - EXTERNAL)

    7

    493

    4800 (BULKHEAD & CURTAIN HEAD BOX - INTERNAL)

    493

    370 N

    OM

    .

    200

    2700 (FLC)

    122

    2778 (CU

    RTAIN

    D

    RO

    P LEN

    GTH

    )

    2900 (SYSTEM

    H

    EIG

    HT)

    11001100

    2 3

    1

    0301

    TYP.

    IRFOR INFORMATION ONLY

    26/07/2016-

  • FILE: AU

    16046.dw

    g --- PLO

    TTED

    O

    N 16/08/2017 BY IG

    OR REBEN

    KO

    THIS DRAWING IS COPYRIGHT AND THE PROPERTY OF THE AUTHOR, AND

    MUST NOT BE RETAINED, COPIED OR USED WITHOUT THE AUTHORITY OF

    SMOKE CONTROL SYSTEMS PTY. LTD.

    DO NOT SCALE FROM DRAWING, USE PROVIDED DIMENSIONS ONLY.

    ALL DISCREPENCIES MUST BE BROUGHT TO THE ATTENTION OF AUTHOR.

    SMOKE CONTROL SYSTEMS DO NOT TAKE RESPONSIBILITY OF

    MEASUREMENTS PROVIDED BY OTHERS.

    R

    e

    v

    CHK REASON DATE

    CLIENT

    NSW HEADOFFICEPHONE: 1300 665 47126 FERNDELL ST,(ENTER VIA STRAITS AVE)SOUTH GRANVILLE NSW 2142

    VICTORIA OFFICEPHONE: 0417 657 623336 SETTLEMENT RDTHOMASTOWN VIC 3074

    WESTERN AUSTRALIA:AUSTRALIAN FIRE CONTROLPHONE: 08 9399 6957UNIT 2, 71-73 BRANT RDKELMSCOTT WA 6997

    NEW ZEALANDPHONE: 09 300 1980LEVEL 4, 369 QUEEN STAUCKLAND NZ 1010

    WWW.SMOKECONTROL.COM.AU

    1 2 3 45 6

    1 2 3 4 5 6A

    BC

    DE

    F

    DRAWN BY

    START DATE

    DRAWING NUMBER

    ISSUE STATUS:

    TITLE

    PROJECT

    AB

    EF

    >

    SCALE

    @A2

    SUB SET (CATEGORY)

    COPY ONLY

    INFORMATION GIVEN IN SMOKECONTROL.COM.AU AND PUBLICATIONS

    FOR DOWNLOAD ARE GIVEN TO THE BEST OF OUR KNOWLEDGE AND

    IN GOOD FAITH. SMOKE CONTROL IS NOT RESPONSIBLE IF

    RECIPIENTS OF TEST REPORTS, ASSESSMENTS OR LITERATURE

    MISINTERPRET THE CONTENTS AND WRONGLY USE PRODUCTS BASED

    ON THOSE MISINTERPRETATIONS. NO LIABILITY IS ACCEPTED FOR

    ERROR OMISSIONS IN THIS WEB SITE OR OUR DOCUMENTS. IN THE

    INTERESTS OF IMPROVEMENTS AND CONTINUED DEVELOPMENT

    SMOKE CONTROL RESERVES THE RIGHT TO CHANGE SPECIFICATION

    WITHOUT NOTICE.

    DISCLAIMER

    SCS-FHE

    FYREHALT EVOLUTION

    ELEVATION SECTION 2

    SCS-FHE-0202

    FOR INFORMATION

    26/07/2016 1:25

    FYREHALT EVOLUTION

    PRODUCT TEMPLATE

    02 - ELEVATIONS

    B

    ELEVATION LOOKING WEST

    FYREHALT EVOLUTION - FIRE CURTAIN

    SCALE 1:25 @ A2

    LEVEL 8

    FCL

    2700

    LEVEL 7

    U/S BULKHEAD

    2900

    5600 (BULKHEAD EXTERNAL)

    7

    5586 (CURTAIN HEAD BOX - EXTERNAL)

    7

    493

    4600 (BULKHEAD & CURTAIN HEAD BOX - INTERNAL)

    493

    370 N

    OM

    .

    200

    2700 (FLC)

    122

    2778 (CU

    RTAIN

    D

    RO

    P LEN

    GTH

    )

    2900 (SYSTEM

    H

    EIG

    HT)

    500

    2600

    E D

    1

    0301

    TYP.

    IRFOR INFORMATION ONLY

    26/07/2016-

  • FILE: AU

    16046.dw

    g --- PLO

    TTED

    O

    N 16/08/2017 BY IG

    OR REBEN

    KO

    THIS DRAWING IS COPYRIGHT AND THE PROPERTY OF THE AUTHOR, AND

    MUST NOT BE RETAINED, COPIED OR USED WITHOUT THE AUTHORITY OF

    SMOKE CONTROL SYSTEMS PTY. LTD.

    DO NOT SCALE FROM DRAWING, USE PROVIDED DIMENSIONS ONLY.

    ALL DISCREPENCIES MUST BE BROUGHT TO THE ATTENTION OF AUTHOR.

    SMOKE CONTROL SYSTEMS DO NOT TAKE RESPONSIBILITY OF

    MEASUREMENTS PROVIDED BY OTHERS.

    R

    e

    v

    CHK REASON DATE

    CLIENT

    NSW HEADOFFICEPHONE: 1300 665 47126 FERNDELL ST,(ENTER VIA STRAITS AVE)SOUTH GRANVILLE NSW 2142

    VICTORIA OFFICEPHONE: 0417 657 623336 SETTLEMENT RDTHOMASTOWN VIC 3074

    WESTERN AUSTRALIA:AUSTRALIAN FIRE CONTROLPHONE: 08 9399 6957UNIT 2, 71-73 BRANT RDKELMSCOTT WA 6997

    NEW ZEALANDPHONE: 09 300 1980LEVEL 4, 369 QUEEN STAUCKLAND NZ 1010

    WWW.SMOKECONTROL.COM.AU

    1 2 3 45 6

    1 2 3 4 5 6A

    BC

    DE

    F

    DRAWN BY

    START DATE

    DRAWING NUMBER

    ISSUE STATUS:

    TITLE

    PROJECT

    AB

    EF

    >

    SCALE

    @A2

    SUB SET (CATEGORY)

    COPY ONLY

    INFORMATION GIVEN IN SMOKECONTROL.COM.AU AND PUBLICATIONS

    FOR DOWNLOAD ARE GIVEN TO THE BEST OF OUR KNOWLEDGE AND

    IN GOOD FAITH. SMOKE CONTROL IS NOT RESPONSIBLE IF

    RECIPIENTS OF TEST REPORTS, ASSESSMENTS OR LITERATURE

    MISINTERPRET THE CONTENTS AND WRONGLY USE PRODUCTS BASED

    ON THOSE MISINTERPRETATIONS. NO LIABILITY IS ACCEPTED FOR

    ERROR OMISSIONS IN THIS WEB SITE OR OUR DOCUMENTS. IN THE

    INTERESTS OF IMPROVEMENTS AND CONTINUED DEVELOPMENT

    SMOKE CONTROL RESERVES THE RIGHT TO CHANGE SPECIFICATION

    WITHOUT NOTICE.

    DISCLAIMER

    SCS-FHE

    FYREHALT EVOLUTION

    HEAD BOX DETAIL

    UNDER 3000 DROP

    SCS-FHE-0301

    IGOR REBENKO FOR INFORMATION

    26/07/2016 1:2

    FYREHALT EVOLUTION

    PRODUCT TEMPLATE

    03 - DETAILS

    1

    ELEVATION

    FYREHALT EVOLUTION HEADBOX: UNDER 3000 DROP

    SCALE 1:2 @ A2

    FCL

    U/S BULKHEAD

    BU

    LKH

    EAD

    - VARIABLE

    122

    VARIABLE

    10

    314 MIN. (REQD. CEILING GAP)

    10

    10

    294 (CURTAIN BOTTOM TRAY)

    500 (BULKHEAD)

    493 (CURTAIN HEAD BOX)

    7

    751501437557

    FRL -/120/120 BULKHEAD SUPPLIED & INSTALLED BY OTHERS

    3/ 16mm FYRECHECK OR EQUIVILENT

    4/ HEAVY GAUGE SCREWS @ 1500 MAX. CRS. (VARIABLE)

    STRONGLY RECOMMENDED 25mm MDF INTERNAL

    LINING FOR FIXING FIBERSHIELD FIRE CURTAIN

    2/ M10 BOOKER RODS COUNTER BORED INTO 25mm MDF

    M10 DROP-IN ANCHORS TYP. 35mm EMBED.

    IRFOR INFORMATION ONLY

    26/07/2016-

    NOTE:

    BULKHEAD SUPPLIED, INSTALLED

    AND CERTIFIED TO FRL -/120/120

    AND BE ABLE TO SUPPORT 35KG

    PER LINEAR METRE BY OTHERS.

    CURTAIN DROP

    3000 MAX.

    DROPS OVER 3000

    WILL REQUIRE 225mm

    TALL HEADBOX

  • FILE: AU

    16046.dw

    g --- PLO

    TTED

    O

    N 16/08/2017 BY IG

    OR REBEN

    KO

    THIS DRAWING IS COPYRIGHT AND THE PROPERTY OF THE AUTHOR, AND

    MUST NOT BE RETAINED, COPIED OR USED WITHOUT THE AUTHORITY OF

    SMOKE CONTROL SYSTEMS PTY. LTD.

    DO NOT SCALE FROM DRAWING, USE PROVIDED DIMENSIONS ONLY.

    ALL DISCREPENCIES MUST BE BROUGHT TO THE ATTENTION OF AUTHOR.

    SMOKE CONTROL SYSTEMS DO NOT TAKE RESPONSIBILITY OF

    MEASUREMENTS PROVIDED BY OTHERS.

    R

    e

    v

    CHK REASON DATE

    CLIENT

    NSW HEADOFFICEPHONE: 1300 665 47126 FERNDELL ST,(ENTER VIA STRAITS AVE)SOUTH GRANVILLE NSW 2142

    VICTORIA OFFICEPHONE: 0417 657 623336 SETTLEMENT RDTHOMASTOWN VIC 3074

    WESTERN AUSTRALIA:AUSTRALIAN FIRE CONTROLPHONE: 08 9399 6957UNIT 2, 71-73 BRANT RDKELMSCOTT WA 6997

    NEW ZEALANDPHONE: 09 300 1980LEVEL 4, 369 QUEEN STAUCKLAND NZ 1010

    WWW.SMOKECONTROL.COM.AU

    1 2 3 45 6

    1 2 3 4 5 6A

    BC

    DE

    F

    DRAWN BY

    START DATE

    DRAWING NUMBER

    ISSUE STATUS:

    TITLE

    PROJECT

    AB

    EF

    >

    SCALE

    @A2

    SUB SET (CATEGORY)

    COPY ONLY

    INFORMATION GIVEN IN SMOKECONTROL.COM.AU AND PUBLICATIONS

    FOR DOWNLOAD ARE GIVEN TO THE BEST OF OUR KNOWLEDGE AND

    IN GOOD FAITH. SMOKE CONTROL IS NOT RESPONSIBLE IF

    RECIPIENTS OF TEST REPORTS, ASSESSMENTS OR LITERATURE

    MISINTERPRET THE CONTENTS AND WRONGLY USE PRODUCTS BASED

    ON THOSE MISINTERPRETATIONS. NO LIABILITY IS ACCEPTED FOR

    ERROR OMISSIONS IN THIS WEB SITE OR OUR DOCUMENTS. IN THE

    INTERESTS OF IMPROVEMENTS AND CONTINUED DEVELOPMENT

    SMOKE CONTROL RESERVES THE RIGHT TO CHANGE SPECIFICATION

    WITHOUT NOTICE.

    DISCLAIMER

    SCS-FHE

    FYREHALT EVOLUTION

    HEAD BOX DETAIL

    OVER 300 DROP

    SCS-FHE-0302

    IGOR REBENKO FOR INFORMATION

    26/07/2016 AS SHOWN

    FYREHALT EVOLUTION

    PRODUCT TEMPLATE

    03 - DETAILS

    1

    ELEVATION

    FYREHALT EVOLUTION HEADBOX: OVER 3000 DROP

    SCALE 1:2 @ A2

    IRFOR INFORMATION ONLY

    26/07/2016-

    493 (CURTAIN HEAD BOX)

    751501437550

    FCL

    U/S SLAB

    224

    VARIABLE

    10

    10

    314 MIN. (REQD. CEILING GAP)

    10

    10

    294 (CURTAIN BOTTOM TRAY)

    CURTAIN DROP

    OVER 3000

    UNDER 3000 WILL

    REQUIRE 125mm TALL

    HEADBOX

  • LINE OF CURTAIN BOTTOM TRAY

    CURTAIN HEAD ABOVESHOWN DASHED

    SIDE GUIDE

    WALL NIB SPAN FROM FFLTO BOTTOM OF HEADBOX

    3842

    16 280

    297

    FIRE WALL IS NOMINAL.BY BUILDER

    11

    200

    NO

    M. W

    ALL

    5646

    102

    25

    FILE: Fyrehalt Evolution.dwg --- PLO

    TTED ON

    16/08/2017 BY IGOR REBEN

    KOTHIS DRAWING IS COPYRIGHT AND THE PROPERTY OF THE AUTHOR, ANDMUST NOT BE RETAINED, COPIED OR USED WITHOUT THE AUTHORITY OFSMOKE CONTROL SYSTEMS PTY. LTD.DO NOT SCALE FROM DRAWING, USE PROVIDED DIMENSIONS ONLY.ALL DISCREPENCIES MUST BE BROUGHT TO THE ATTENTION OF AUTHOR.SMOKE CONTROL SYSTEMS DO NOT TAKE RESPONSIBILITY OFMEASUREMENTS PROVIDED BY OTHERS.

    Rev CHK REASON DATE

    CLIENT

    NSW HEADOFFICEPHONE: 1300 665 47126 FERNDELL ST,(ENTER VIA STRAITS AVE)SOUTH GRANVILLE NSW 2142

    VICTORIA OFFICEPHONE: 0417 657 623336 SETTLEMENT RDTHOMASTOWN VIC 3074

    WESTERN AUSTRALIA:AUSTRALIAN FIRE CONTROLPHONE: 08 9399 6957UNIT 2, 71-73 BRANT RDKELMSCOTT WA 6997

    NEW ZEALANDPHONE: 09 300 1980LEVEL 4, 369 QUEEN STAUCKLAND NZ 1010

    WWW.SMOKECONTROL.COM.AU

    1 2 3 4 5 61 2 3 4 5 6

    AB

    CD

    EF

    DRAWN BY

    START DATE

    DRAWING NUMBER

    ISSUE STATUS:

    TITLE

    PROJECT

    AB

    EF

    >

    SCALE@A2

    SUB SET (CATEGORY)

    COPY ONLY

    INFORMATION GIVEN IN SMOKECONTROL.COM.AU ANDPUBLICATIONS FOR DOWNLOAD ARE GIVEN TO THE BEST OF OURKNOWLEDGE AND IN GOOD FAITH. SMOKE CONTROL IS NOTRESPONSIBLE IF RECIPIENTS OF TEST REPORTS, ASSESSMENTS ORLITERATURE MISINTERPRET THE CONTENTS AND WRONGLY USEPRODUCTS BASED ON THOSE MISINTERPRETATIONS. NO LIABILITY ISACCEPTED FOR ERROR OMISSIONS IN THIS WEB SITE OR OURDOCUMENTS. IN THE INTERESTS OF IMPROVEMENTS ANDCONTINUED DEVELOPMENT SMOKE CONTROL RESERVES THE RIGHTTO CHANGE SPECIFICATION WITHOUT NOTICE.

    DISCLAIMER

    SCS-FHE

    FYREHALT EVOLUTIONSTUD WALLEND GUIDE DETAIL

    SCS-FHE-0303

    IGOR REBENKO FOR INFORMATION

    26/07/2016 1:5

    FYREHALT EVOLUTIONPRODUCT TEMPLATE

    03 - DETAILS

    1

    PLANEND GUIDE DETAIL

    SCALE 1:2 @ A2

    IR FOR INFORMATION ONLY 26/07/2016-

  • FILE: AU

    16055-AR.dw

    g --- PLO

    TTED

    O

    N 16/08/2017 BY IG

    OR REBEN

    KO

    THIS DRAWING IS COPYRIGHT AND THE PROPERTY OF THE AUTHOR, AND

    MUST NOT BE RETAINED, COPIED OR USED WITHOUT THE AUTHORITY OF

    SMOKE CONTROL SYSTEMS PTY. LTD.

    DO NOT SCALE FROM DRAWING, USE PROVIDED DIMENSIONS ONLY.

    ALL DISCREPENCIES MUST BE BROUGHT TO THE ATTENTION OF AUTHOR.

    SMOKE CONTROL SYSTEMS DO NOT TAKE RESPONSIBILITY OF

    MEASUREMENTS PROVIDED BY OTHERS.

    R

    e

    v

    CHK REASON DATE

    CLIENT

    NSW HEADOFFICEPHONE: 1300 665 47126 FERNDELL ST,(ENTER VIA STRAITS AVE)SOUTH GRANVILLE NSW 2142

    VICTORIA OFFICEPHONE: 0417 657 623336 SETTLEMENT RDTHOMASTOWN VIC 3074

    WESTERN AUSTRALIA:AUSTRALIAN FIRE CONTROLPHONE: 08 9399 6957UNIT 2, 71-73 BRANT RDKELMSCOTT WA 6997

    NEW ZEALANDPHONE: 09 300 1980LEVEL 4, 369 QUEEN STAUCKLAND NZ 1010

    WWW.SMOKECONTROL.COM.AU

    1 2 3 45 6

    1 2 3 4 5 6A

    BC

    DE

    F

    DRAWN BY

    START DATE

    DRAWING NUMBER

    ISSUE STATUS:

    TITLE

    PROJECT

    AB

    EF

    >

    SCALE

    @A2

    SUB SET (CATEGORY)

    FOR APPROVALPLEASE PROVIDE NAME, COMPANY, DATE, & SIGNATURE FOR YOUR FORMAL

    APPROVAL OF THESE SHOP DRAWINGS. THIS IS REQD. FOR SCS TO COMMENCE

    MANUFACTURE OF PARTS.

    SCS-FHE

    FYREHALT EVOLUTION

    FR POST END GUIDE DETAIL

    SCS-FHE-0304

    IGOR REBENKO FOR INFORMATION

    26/07/2016 SCALE: 1:2

    FYREHALT EVOLUTION

    PRODUCT TEMPLATE

    03 - DETAILS

    1

    PLAN

    POST CONNECTION DETAIL

    SCALE 1:2 @ A2

    TYPICAL FOR BOTH POSTS

    94 FR PO

    ST

    99

    3

    NOMINAL CLADDING BY OTHERS

    5

    94 FR POST

    103

    6039

    60x99x2844 LG MAXILITE FR BOARD

    94

    46

    57

    FRL 120/120/120 POST

    10g x 50LG SUPER TEK SCREWS @ 500 CRS.

    PACKING FOR CLADDING BY OTHERS

    FYREHALT EVOLUTION

    SIDE GUIDE

    2

    ELEVATION SECTION

    FR POST INSTALL

    SCALE 1:2 @ A2

    3220

    20

    70x70x5 70LG ANGLE

    150x150x5 ANGLE 70 LG

    2/ M12 x 50LG DYNABOLT

    M12 x 50LG DYNABOLT

    14 PILOT HOLE THROUGH ANGLE

    M12 DRILLED & TAPPED POST

    M12 x 50LG BOLT & WASHER FIXING

    FYRFLEX SEAL TO SLAB

    2

    -

    NUT WELDED TO ANGLE

    M12 x50LG BOLT & WASHER

    150

    75

    35

    75 35

    15094

    20

    70

    35

    2 2

    2

    2

    2

    200

    IR FOR INFORMATION ONLY 26/07/2016-

  • 224

    493

    28138

    >300

    0

    OBSTRUCTION SENSOR - OPTIONAL EXTRA

    BALUSTRADE BY OTHERS MUST NOT INTERFERE WITH CURTAIN IN ANY WAY

    FILE: Fyrehalt Evolution.dwg --- PLO

    TTED ON

    16/08/2017 BY IGOR REBEN

    KOTHIS DRAWING IS COPYRIGHT AND THE PROPERTY OF THE AUTHOR, ANDMUST NOT BE RETAINED, COPIED OR USED WITHOUT THE AUTHORITY OFSMOKE CONTROL SYSTEMS PTY. LTD.DO NOT SCALE FROM DRAWING, USE PROVIDED DIMENSIONS ONLY.ALL DISCREPENCIES MUST BE BROUGHT TO THE ATTENTION OF AUTHOR.SMOKE CONTROL SYSTEMS DO NOT TAKE RESPONSIBILITY OFMEASUREMENTS PROVIDED BY OTHERS.

    Rev CHK REASON DATE

    CLIENT

    NSW HEADOFFICEPHONE: 1300 665 47126 FERNDELL ST,(ENTER VIA STRAITS AVE)SOUTH GRANVILLE NSW 2142

    VICTORIA OFFICEPHONE: 0417 657 623336 SETTLEMENT RDTHOMASTOWN VIC 3074

    WESTERN AUSTRALIA:AUSTRALIAN FIRE CONTROLPHONE: 08 9399 6957UNIT 2, 71-73 BRANT RDKELMSCOTT WA 6997

    NEW ZEALANDPHONE: 09 300 1980LEVEL 4, 369 QUEEN STAUCKLAND NZ 1010

    WWW.SMOKECONTROL.COM.AU

    1 2 3 4 5 61 2 3 4 5 6

    AB

    CD

    EF

    DRAWN BY

    START DATE

    DRAWING NUMBER

    ISSUE STATUS:

    TITLE

    PROJECT

    AB

    EF

    >

    SCALE@A2

    SUB SET (CATEGORY)

    COPY ONLY

    INFORMATION GIVEN IN SMOKECONTROL.COM.AU ANDPUBLICATIONS FOR DOWNLOAD ARE GIVEN TO THE BEST OF OURKNOWLEDGE AND IN GOOD FAITH. SMOKE CONTROL IS NOTRESPONSIBLE IF RECIPIENTS OF TEST REPORTS, ASSESSMENTS ORLITERATURE MISINTERPRET THE CONTENTS AND WRONGLY USEPRODUCTS BASED ON THOSE MISINTERPRETATIONS. NO LIABILITY ISACCEPTED FOR ERROR OMISSIONS IN THIS WEB SITE OR OURDOCUMENTS. IN THE INTERESTS OF IMPROVEMENTS ANDCONTINUED DEVELOPMENT SMOKE CONTROL RESERVES THE RIGHTTO CHANGE SPECIFICATION WITHOUT NOTICE.

    DISCLAIMER

    SCS-FHE

    FYREHALT EVOLUTIONSENSOR MOUTING& 224 HEAD BOX DETAIL

    SCS-FHE-0305

    IGOR REBENKO FOR INFORMATION

    26/07/2016 1:10

    FYREHALT EVOLUTIONPRODUCT TEMPLATE

    03 - DETAILS

    1

    ELEVATIONLARGE HEAD BOX FOR DROPS OVER 3m

    SCALE 1:10 @ A2

    IR FOR INFORMATION ONLY 26/07/2016-

  • FILE: AU

    16046.dw

    g --- PLO

    TTED

    O

    N 16/08/2017 BY IG

    OR REBEN

    KO

    THIS DRAWING IS COPYRIGHT AND THE PROPERTY OF THE AUTHOR, AND

    MUST NOT BE RETAINED, COPIED OR USED WITHOUT THE AUTHORITY OF

    SMOKE CONTROL SYSTEMS PTY. LTD.

    DO NOT SCALE FROM DRAWING, USE PROVIDED DIMENSIONS ONLY.

    ALL DISCREPENCIES MUST BE BROUGHT TO THE ATTENTION OF AUTHOR.

    SMOKE CONTROL SYSTEMS DO NOT TAKE RESPONSIBILITY OF

    MEASUREMENTS PROVIDED BY OTHERS.

    R

    e

    v

    CHK REASON DATE

    CLIENT

    NSW HEADOFFICEPHONE: 1300 665 47126 FERNDELL ST,(ENTER VIA STRAITS AVE)SOUTH GRANVILLE NSW 2142

    VICTORIA OFFICEPHONE: 0417 657 623336 SETTLEMENT RDTHOMASTOWN VIC 3074

    WESTERN AUSTRALIA:AUSTRALIAN FIRE CONTROLPHONE: 08 9399 6957UNIT 2, 71-73 BRANT RDKELMSCOTT WA 6997

    NEW ZEALANDPHONE: 09 300 1980LEVEL 4, 369 QUEEN STAUCKLAND NZ 1010

    WWW.SMOKECONTROL.COM.AU

    1 2 3 45 6

    1 2 3 4 5 6A

    BC

    DE

    F

    DRAWN BY

    START DATE

    DRAWING NUMBER

    ISSUE STATUS:

    TITLE

    PROJECT

    AB

    EF

    >

    SCALE

    @A2

    SUB SET (CATEGORY)

    COPY ONLY

    INFORMATION GIVEN IN SMOKECONTROL.COM.AU AND PUBLICATIONS

    FOR DOWNLOAD ARE GIVEN TO THE BEST OF OUR KNOWLEDGE AND

    IN GOOD FAITH. SMOKE CONTROL IS NOT RESPONSIBLE IF

    RECIPIENTS OF TEST REPORTS, ASSESSMENTS OR LITERATURE

    MISINTERPRET THE CONTENTS AND WRONGLY USE PRODUCTS BASED

    ON THOSE MISINTERPRETATIONS. NO LIABILITY IS ACCEPTED FOR

    ERROR OMISSIONS IN THIS WEB SITE OR OUR DOCUMENTS. IN THE

    INTERESTS OF IMPROVEMENTS AND CONTINUED DEVELOPMENT

    SMOKE CONTROL RESERVES THE RIGHT TO CHANGE SPECIFICATION

    WITHOUT NOTICE.

    DISCLAIMER

    SCS-FHE

    FYREHALT EVOLUTION

    TYP. ELECTRICAL COORDINATION

    SCS-FHE-1001

    IGOR REBENKO FOR INFORMATION

    26/07/2016 1:25

    FYREHALT EVOLUTION

    PRODUCT TEMPLATE

    10 - ELECTRICAL

    1

    PLAN

    FYREHALT EVOLUTION - POWER & FIP REQUIREMENTS

    SCALE 1:25 @ A2

    GPO

    GPO

    GPO

    GPO

    FIP

    MASTER CONTROLLER

    SLAVE CONTROLLER

    SLAVE CONTROLLER

    SLAVE CONTROLLER

    STROBE LOCATIONS TBA

    2

    5

    0

    460

    4

    6

    0

    MASTER CONTROLLER

    CAN BE LOCATED WITHIN 15m OF ONE OF THE FIRE

    CURTAIN MOTORS LOCATED AT CENTRE OF EACH LEG.

    REQUIREMENTS TO BE PROVIDED BY OTHERS:

    1. 240V 10A GPO;

    2. NORMALLY OPEN DRY CONTACT TO FIP.

    3. NORMALLY MOUNTED IS SERVICE CUPBOARD.

    WHERE M.C. IS MOUNTED IN CEILING VOID, AN

    ACCESS PANEL MUST BE PROVIDED WITH CLEAR

    ACCESS TO CONTROL PANEL

    150

    7

    0

    7

    8

    0

    SLAVE CONTROLLER

    CAN BE LOCATED WITHIN 1m OF ALL REMAINING LEGS.

    REQUIREMENTS TO BE PROVIDED BY OTHERS:

    1. 240V 10A GPO.

    2. ACCESS PANEL MUST BE PROVIDED WITH CLEAR

    ACCESS TO CONTROL PANEL

    IRFOR INFORMATION ONLY

    26/07/2016-

  • FILE: AU

    16046.dw

    g --- PLO

    TTED

    O

    N 16/08/2017 BY IG

    OR REBEN

    KO

    THIS DRAWING IS COPYRIGHT AND THE PROPERTY OF THE AUTHOR, AND

    MUST NOT BE RETAINED, COPIED OR USED WITHOUT THE AUTHORITY OF

    SMOKE CONTROL SYSTEMS PTY. LTD.

    DO NOT SCALE FROM DRAWING, USE PROVIDED DIMENSIONS ONLY.

    ALL DISCREPENCIES MUST BE BROUGHT TO THE ATTENTION OF AUTHOR.

    SMOKE CONTROL SYSTEMS DO NOT TAKE RESPONSIBILITY OF

    MEASUREMENTS PROVIDED BY OTHERS.

    R

    e

    v

    CHK REASON DATE

    CLIENT

    NSW HEADOFFICEPHONE: 1300 665 47126 FERNDELL ST,(ENTER VIA STRAITS AVE)SOUTH GRANVILLE NSW 2142

    VICTORIA OFFICEPHONE: 0417 657 623336 SETTLEMENT RDTHOMASTOWN VIC 3074

    WESTERN AUSTRALIA:AUSTRALIAN FIRE CONTROLPHONE: 08 9399 6957UNIT 2, 71-73 BRANT RDKELMSCOTT WA 6997

    NEW ZEALANDPHONE: 09 300 1980LEVEL 4, 369 QUEEN STAUCKLAND NZ 1010

    WWW.SMOKECONTROL.COM.AU

    1 2 3 45 6

    1 2 3 4 5 6A

    BC

    DE

    F

    DRAWN BY

    START DATE

    DRAWING NUMBER

    ISSUE STATUS:

    TITLE

    PROJECT

    AB

    EF

    >

    SCALE

    @A2

    SUB SET (CATEGORY)

    COPY ONLY

    INFORMATION GIVEN IN SMOKECONTROL.COM.AU AND PUBLICATIONS

    FOR DOWNLOAD ARE GIVEN TO THE BEST OF OUR KNOWLEDGE AND

    IN GOOD FAITH. SMOKE CONTROL IS NOT RESPONSIBLE IF

    RECIPIENTS OF TEST REPORTS, ASSESSMENTS OR LITERATURE

    MISINTERPRET THE CONTENTS AND WRONGLY USE PRODUCTS BASED

    ON THOSE MISINTERPRETATIONS. NO LIABILITY IS ACCEPTED FOR

    ERROR OMISSIONS IN THIS WEB SITE OR OUR DOCUMENTS. IN THE

    INTERESTS OF IMPROVEMENTS AND CONTINUED DEVELOPMENT

    SMOKE CONTROL RESERVES THE RIGHT TO CHANGE SPECIFICATION

    WITHOUT NOTICE.

    DISCLAIMER

    SCS-FHE

    FYREHALT EVOLUTION

    TYP. OBSTRUCTION SENSOR SETOUT

    SCS-FHE-1002

    IGOR REBENKO FOR INFORMATION

    26/07/2016 1:25

    FYREHALT EVOLUTION

    PRODUCT TEMPLATE

    10 - ELECTRICAL

    1

    PLAN

    FYREHALT EVOLUTION - OBSTRUCTION SENSOR SETOUT

    SCALE 1:25 @ A2

    D

    2 3

    E

    1242

    1802

    1798

    99

    1977501 3045 1977

    1977501 3045 1977 501

    D

    E

    1802

    1798

    99

    IRFOR INFORMATION ONLY

    26/07/2016-

    1857

    1242

    1857

    501

    Smoke Control - Fyrehalt EVOLUTION -fire curtain-MasterSpec-aSmoke-Control-Fyrehalt-EVOLUTION-fire-curtain-drawing-only